gamesa electric pv 2x series pv stations€¦ · concrete solution 1 x pv inverter 2 x pv inverter...

6
Gamesa Electric PV 2X series PV Stations Plug & play MV solution for large-scale 1500 V power plants 2020 | Datasheet

Upload: others

Post on 21-Sep-2020

11 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Gamesa Electric PV 2X series PV Stations€¦ · Concrete Solution 1 x PV Inverter 2 x PV Inverter Container Standard Container Plus Configurations. PVS 2350 PVS 2475 PVS 2600 PVS

Gamesa Electric PV 2X series PV Stations Plug & play MV solution for large-scale 1500 V power plants

2020 | Datasheet

Page 2: Gamesa Electric PV 2X series PV Stations€¦ · Concrete Solution 1 x PV Inverter 2 x PV Inverter Container Standard Container Plus Configurations. PVS 2350 PVS 2475 PVS 2600 PVS

Gamesa Electric PV 2X series – PV Stations Plug & Play MV Solutions

MV Transformer up to 38 kV hermetically sealed

MV Switchgear

Open compartment with metallic grilles for natural ventilation

Closed compartment with natural venilation with filters

Double physical protection (metallic container and inverter enclosure) against dust and sand

Liquid cooling allows to reduce air flow exchange necessities, avoiding dust and sand entrance in critical components

Any O&M task can be performed within the building (metallic container), avoiding climatic conditions exposure

Performance at harsh environmental conditions

Up to 5.2 MW solution based on 2 field-proven Gamesa Electric PV 2X series inverters

More yield in challenging sites: operating up to 50ºC and 2000 m without derating

Best support available from our service organizationReliability

Fully assembled and tested MV solution

Quick installation on field, reducing installation time and costs

Easy to support and mantainPlug & play

Wide range of configurations with outputs from 2250 kVA to 5200 kVA

Bidirectional inverter that allows PV Station to be configured as part of a Battery Energy Storage System (BESS)

Customization at PV station subsystems, such as MV transformer, auxiliaries’ system and DC input configuration, according to customer necessities

Flexibility

Page 3: Gamesa Electric PV 2X series PV Stations€¦ · Concrete Solution 1 x PV Inverter 2 x PV Inverter Container Standard Container Plus Configurations. PVS 2350 PVS 2475 PVS 2600 PVS

Gamesa Electric PV 2X series inverters with liquid/air active cooling

Closed compartment with natural ventilation with metallic grilles with filter for the air inlet

Concrete Solution

1 x PV Inverter 2 x PV Inverter

Container Standard

Container Plus

Configurations

Page 4: Gamesa Electric PV 2X series PV Stations€¦ · Concrete Solution 1 x PV Inverter 2 x PV Inverter Container Standard Container Plus Configurations. PVS 2350 PVS 2475 PVS 2600 PVS

PVS 2350 PVS 2475 PVS 2600 PVS 2250 PVS 2400 PVS 2500

Dc Input

Ratio DC/AC 127% (up to 177% upon request) 129% (up to 179% upon request)

Max. DC Current @25ºC [77ºF] 2 x 1468 A 2 x 1460 A

Max. DC Current @40ºC [104ºF] 2 x 1440 A 2 x 1440 A

Max. DC Current @50ºC [122ºF] 2 x 1412 A 2 x 1400 A

DC Voltage Range 820 - 1500 V 860 - 1500 V 900 - 1500 V 820 - 1500 V 860 - 1500 V 900 - 1500 V

DC Voltage Range MPPT 820 - 1300 V 860 - 1300 V 900 - 1300 V 820 - 1300 V 860 - 1300 V 900 - 1300 V

Nr of DC Ports max 16 fuse +/-max 18 fuse +(up to max 24 fuse +/- monitored upon request)

MPPT 1

Ac Output

Nominal AC Power @25ºC [77ºF] 2363 kVA 2480 kVA 2600 kVA 2270 kVA 2386 kVA 2500 kVA

Nominal AC Power @40ºC [104ºF] 2315 kVA 2430 kVA 2550 kVA 2136 kVA 2240 kVA 2350 kVA

Nominal AC Power @50ºC [122ºF] 2273 kVA 2385 kVA 2500 kVA 2045 kVA 2147 kVA 2250 kVA

Nominal AC Voltage Up to 34.5 kV

AC Power Frequency 50 / 60 Hz

Reactive Power Range Any

Protective Devices

DC input Fuse and motorized load switch

AC input Circuit breaker (Motorized as an option)

Overvoltage Protections DC Type 1 + 2 SPD

Components PV Station

Inverter 1 x PV 2350 1 x PV 2475 1 x PV2600 1 x PV 2250 1 x PV 2400 1 x PV 2500

Transformer 2.36 MVA Dyn 2.48 MVA Dyn 2.6 MVA Dyn 2.27 MVA Dyn 2.39 MVA Dyn 2.5 MVA Dyn

Switchgear 0L1V / 1L1V / 2L1V up to 36 kV

Custom auxiliary transformer Optional

Others Auxiliary cabinet

Communications

Control Modbus TCP/IP (Other upon request)

Monitoring Modbus TCP / IP

Other Features

LVRT Yes

HVRT Yes

Working Ambient Temperature* -20°C / +60°C (-4ºF / +140ºF)

Max. Altitude (whitout derating)** 2000 m (6561 ft)

Dimensions container (width x height x depth)

6058 x 2438 x 2896 mm (20 x 8 x 9.5 ft) /

Dimensions concrete building (width x height x depth)

7500 x 2500 x 3240 mm (24.6 x 8.2 x 10.6 ft)

Weight container 12500 kg (27558 lb)

Weight concrete building 30000 kg concrete building + 5000 kg transformer (66139 lb + 11023 lb)

Protection IP53 (inverter and switchgear compartment) – IP54 as optional / IP10 (transformer compartment)***

Cooling Liquid & forced air

Main Standards Optionals

IEC 62109-1 IEC 62109-2 Container Plus(1) AC & DC cables IP67 protection

IEC 61000-6-2 EN 55011:2016 Low temperature kit UPS

IEC 62116 IEC 61683 C5 corrosion painting upgrade

IEEE 519 IEEE 1547

USA: UL 1741-SA UL62109

C22.2 No 107.1-01:2001 AUS: AS 4777.2:2015

INDIA: CEA 6th February, 2019 IEC TS 62910:2015

Page 5: Gamesa Electric PV 2X series PV Stations€¦ · Concrete Solution 1 x PV Inverter 2 x PV Inverter Container Standard Container Plus Configurations. PVS 2350 PVS 2475 PVS 2600 PVS

* With derating from 25ºC / 77ºF** Up to 4000 m (13123 ft) with derating as optional*** Only applicable for container solution(1) Consult Gamesa Electric for details

PVS 4700 PVS 4950 PVS 5200 PVS 4500 PVS 4800 PVS 5000

Dc Input

Ratio DC/AC 127% (up to 177% upon request) 129% (up to 179% upon request)

Max. DC Current @25ºC [77ºF] 4 x 1468 A 4 x 1460 A

Max. DC Current @40ºC [104ºF] 4 x 1440 A 4 x 1440 A

Max. DC Current @50ºC [122ºF] 4 x 1412 A 4 x 1400 A

DC Voltage Range 820 - 1500 V 860 - 1500 V 900 - 1500 V 820 - 1500 V 860 - 1500 V 900 - 1500 V

DC Voltage Range MPPT 820 - 1300 V 860 - 1300 V 900 - 1300 V 820 - 1300 V 860 - 1300 V 900 - 1300 V

Nr of DC Ports max 16 fuse +/-max 18 fuse +(up to max 24 fuse +/- monitored upon request)

MPPT 1

Ac Output

Nominal AC Power @25ºC [77ºF] 4726 kVA 4960 kVA 5200 kVA 4540 kVA 4772 kVA 5000 kVA

Nominal AC Power @40ºC [104ºF] 4630 kVA 4860 kVA 5100 kVA 4272 kVA 4480 kVA 4700 kVA

Nominal AC Power @50ºC [122ºF] 4726 kVA 4770 kVA 5000 kVA 4090 kVA 4294 kVA 4500 kVA

Nominal AC Voltage Up to 34.5 kV

AC Power Frequency 50 / 60 Hz

Reactive Power Range Any

Protective Devices

DC input Fuse and motorized load switch

AC input Circuit breaker (Motorized as an option)

Overvoltage Protections DC Type 1 + 2 SPD

Components PV Station

Inverter 2 x PV 2350 2 x PV 2475 2 x PV2600 2 x PV 2250 2 x PV 2400 2 x PV 2500

Transformer 4.76 MVA Dynyn 4.96 MVA Dynyn 5.2 MVA Dynyn 4.54 MVA Dynyn 4.77 MVA Dynyn 5 MVA Dynyn

Switchgear 0L1V / 1L1V / 2L1V up to 36 kV

Custom auxiliary transformer Optional

Others Auxiliary cabinet

Communications

Control Modbus TCP/IP (Other upon request)

Monitoring Modbus TCP / IP

Other Features

LVRT Yes

HVRT Yes

Working Ambient Temperature* -20°C / +60°C (-4ºF / +140ºF)

Max. Altitude (whitout derating)** 2000 m (6561 ft)

Dimensions container (width x height x depth)

12192 x 2438 x 2896 mm (40 x 8 x 9.5 ft)

Dimensions concrete building (width x height x depth)

7500 x 2500 x 3240 mm (24.6 x 8.2 x 10.6 ft)

Weight container 21000 kg (46297 lb)

Weight concrete building 32500 kg concrete building + 10000 kg transformer (71650 lb + 22046 lb)

Protection IP53 (inverter and switchgear compartment) – IP54 as optional / IP10 (transformer compartment)***

Cooling Liquid & forced air

Main Standards Optionals

IEC 62109-1 IEC 62109-2 Container Plus(1) AC & DC cables IP67 protection

IEC 61000-6-2 EN 55011:2016 Low temperature kit UPS

IEC 62116 IEC 61683 C5 corrosion painting upgrade

IEEE 519 IEEE 1547

USA: UL 1741-SA UL62109

C22.2 No 107.1-01:2001 AUS: AS 4777.2:2015

INDIA: CEA 6th February, 2019 IEC TS 62910:2015

Page 6: Gamesa Electric PV 2X series PV Stations€¦ · Concrete Solution 1 x PV Inverter 2 x PV Inverter Container Standard Container Plus Configurations. PVS 2350 PVS 2475 PVS 2600 PVS

Shaping new energy

Worldwide presence

AustraliaAustriaBelgiumBrazilCanada

ChileChinaCroatiaDenmarkEgypt

FranceGermanyGreeceHong KongHungary

IndiaIrelandItalyJapanKorea

MexicoMoroccoNetherlandsNorwayPhilippines

PolandSingaporeSouth AfricaSri LankaSweden

ThailandTurkeyUKUSA

Gamesa ElectricCalle del Mar Mediterráneo, 14-16 28830 San Fernando de Henares (Madrid) Tel: +34 91 655 70 34

[email protected] www.gamesaelectric.com

In order to minimize the environmental impact, this document has been printed on paper made from 50% pure cellulose fiber (ECF), 40% selected pre-consumer recycled fiber, and 10% post-consumer deinked recycled fiber inks based exclusively on vegetable oils with a minimum volatile organic compound (VOC) content. Varnish based predominantly on natural and renewable raw materials.

The present document, its content, its annexes and/or amendments has been drawn up by Siemens Gamesa Renewable Energy for information purposes only and could be modified without prior notice. All the content of the Document is protected by intellectual and industrial property rights owned by Siemens Gamesa Renewable Energy The addressee shall not reproduce any of the information, neither totally nor partially.

Printed date: July 2020

+2.6 gwSOLAR ENERGY

+100 gwWIND POWER

+90COUNTRIES