gas and smoke detection system - lotos.logintrade.net
TRANSCRIPT
T.T.U. Urbanowicz
ul. Mostek 2/8
80-759 Gdańsk
Gas and smoke detection system
D.Więckiewicz 09.05.2016 A. Stojek Z. Urbanowicz 09.05.2016 D As-built documentation
Surname Date Surname Surname Date Status
Prepared Checked Approved Remarks
Project name
Gas and smoke detection system
Project no
DP01316
TECHNICAL DOCUMENTATION OF LOTOS PETROBALTIC S.A.
Archival no Document no Page Of pages Rev. no
DP01316 DP01316-E01-1001-1 1 3 1
Contract no: LPB/FH/MG/16153/16 Project no: DP01316
User: LOTOS Petrobaltic
Object: LOTOS Petrobaltic
System: Gas and smoke detection system
Title:
Gas detectors instalation
consisting of plot plans, circiut diagrams, bill of materials.
Technical description of proposed technical solution.
Th
e d
ocu
me
nt
is th
e p
rop
ert
y o
f T
.T.U
. Z
dzis
ław
Urb
an
ow
icz,
ul. M
oste
k 2
/8,
80
-75
9 G
da
ńsk,
PO
LA
ND
an
d c
an
no
t b
e c
op
ied o
r sha
red
with
th
ird
part
ies w
ith
out
wri
tte
n p
erm
issio
n o
f T
.T.U
. Z
dzis
ław
Urb
an
ow
icz
, u
l. M
oste
k 2
/8,
80
-75
9 G
da
ńsk,
PO
LA
ND
.
T.T.U. Urbanowicz
ul. Mostek 2/8
80-759 Gdańsk
Gas and smoke detection system
TECHNICAL DOCUMENTATION OF LOTOS PETROBALTIC S.A.
Archival no Document no Page Of pages Rev. no
DP01316 DP01316-E01-1001-1 2 3 1
TABLE OF CONTENTS
Title Page / document no
1 Description of the Proposed Technical Solution DP01316-E01-1001-1
2 Bill of Cables DP01316-E01-2001-0
3 Bill of Materials DP04615-E01-2002-0
4 Gas detection. Circiut diagram. DP01316-E01-3001-0
5 Smoke detection. Circiut diagram. DP01316-E01-3002-0
6 Gas and smoke detection area – plot plan DP01316-E01-7001-0
7 Gas and smoke detection– plot plan DP01316-E01-7002-0
8 Dräger. Gas Detection System 1-4
T.T.U. Urbanowicz
ul. Mostek 2/8
80-759 Gdańsk
Gas and smoke detection system
TECHNICAL DOCUMENTATION OF LOTOS PETROBALTIC S.A.
Archival no Document no Page Of pages Rev. no
DP01316 DP01316-E01-1001-1 3 3 1
1. Range of Elaboration
Due to the ABS requirements it is necessary to install gas detectors on the main deck/pipe rack to
ensure safety in Temporary Well Testing System area.
Smoke detection in a boiler container is not related to ABS requirements.
2. Description of the Proposed Technical Solution
Gas detection system.
Gas hazards in Temporary Well Testing area will be monitored by 9 IR gas detectors. Gas detectors
will by calibrated to detect combustible gases (methane). Gas detection controller will by installed in
mobile control container. Gas detection will run the Audible and Visual Signalling Devices. Localization
of gas detectors, controller and Audible and Visual Signalling Devices is shown on DP01316-E01-
7002-0. Gas detectors will be installed above the well testing system devices.
Smoke detection system.
Fire hazards in Boiler Container will be monitored by smoke detectors. Smoke detection controller will
by installed in mobile control container. Smoke detection will run the Audible and Visual Signalling
Devices. Localization of gas detectors, controller and Audible and Visual Signalling Devices is shown
on DP01316-E01-7002-0.
T.T.U. Zdzisław Urbanowicz
80-759 Gdańsk ul. Mostek 2/8
Tel. (058) 682-20-37
PROJECT DOC NO. PAGE PAGES REVISION DATE
DP01316 DP01316-E01-2001-1 1 2 1 09.05.2016
Bill of cables
No. Cabel name From To Cabel Type Lenght
[m] Diameter
[mm] Manufacture Comments
1. WSD1 =Mobile control
container+GSDC-FDS SD1
MarineCom YOZc X-FR 250 V 1 x 2 x 0,75 mm²
50 8,2 TKF
2. WSD2 SD1 SD2 MarineCom YOZc X-FR 250 V
1 x 2 x 0,75 mm² 5 8,2 TKF
3. WSD3 SD2 PB1 MarineCom YOZc X-FR 250 V
1 x 2 x 0,75 mm² 15 8,2 TKF
4. WSD4 PB1 FH1 MarineCom YOZc X-FR 250 V
1 x 2 x 0,75 mm² 15 8,2 TKF
5. WSD5 FH1 =Mobile control
container+GSDC-FDS MarineCom YOZc X-FR 250 V
1 x 2 x 0,75 mm² 45 8,2 TKF
6. WGD1 =Mobile control
container+GSDC-GDS GD1
MarineCom YOZc X-FR 250 V 2 x 2 x 0,75 mm²
75 12,2 TKF
7. WGD2 =Mobile control
container+GSDC-GDS GD2
MarineCom YOZc X-FR 250 V 2 x 2 x 0,75 mm²
70 12,2 TKF
8. WGD3 =Mobile control
container+GSDC-GDS GD3
MarineCom YOZc X-FR 250 V 2 x 2 x 0,75 mm²
55 12,2 TKF
9. WGD4 =Mobile control
container+GSDC-GDS GD4
MarineCom YOZc X-FR 250 V 2 x 2 x 0,75 mm²
55 12,2 TKF
10. WGD5 =Mobile control
container+GSDC-GDS GD5
MarineCom YOZc X-FR 250 V 2 x 2 x 0,75 mm²
50 12,2 TKF
11. WGD6 =Mobile control
container+GSDC-GDS GD6
MarineCom YOZc X-FR 250 V 2 x 2 x 0,75 mm²
45 12,2 TKF
12. WGD7 =Mobile control
container+GSDC-GDS GD7
MarineCom YOZc X-FR 250 V 2 x 2 x 0,75 mm²
65 12,2 TKF
13. WGD8 =Mobile control
container+GSDC-GDS GD8
MarineCom YOZc X-FR 250 V 2 x 2 x 0,75 mm²
45 12,2 TKF
T.T.U. Zdzisław Urbanowicz
80-759 Gdańsk ul. Mostek 2/8
Tel. (058) 682-20-37
PROJECT DOC NO. PAGE PAGES REVISION DATE
DP01316 DP01316-E01-2001-1 2 2 1 09.05.2016
Bill of cables
No. Cabel name From To Cabel Type Lenght
[m] Diameter
[mm] Manufacture Comments
14. WGD9 =Mobile control
container+GSDC-GDS GD9
MarineCom YOZc X-FR 250 V 2 x 2 x 0,75 mm²
45 12,2 TKF
15. WGH1 =Mobile control
container+GSDC-GDS GH1
MarineCom YOZc X-FR 250 V 2 x 2 x 0,75 mm²
75 12,2 TKF
16. WGH2 =Mobile control
container+GSDC-GDS GH2
MarineCom YOZc X-FR 250 V 1 x 2 x 0,75 mm²
15 12,2 TKF
17. WGSDC Mobile control container
power supply =Mobile control
container+GSDC Marineline YOZp G-type X-Fire
3x2,5 mm2 3 12,6 TKF
T.T.U. Zdzisław Urbanowicz
80-759 Gdańsk ul. Mostek 2/8
Tel. (058) 682-20-37
PROJECT DOC NO. PAGE PAGES REVISION DATE
DP01316 DP01316-E01-2002-1 1 1 1 09.05.2016
Gas detection
Lp. Name Description Type Catalog
number Unit Qty. Manufacture Comments
1. GD1÷GD9 IR-Gas detector ATEX: II 2G Ex d (e) IIC T6
PIR 3000 complete
set d-Version 6811180 set 9 Dräger
DNV-GL
(95 391-14 HH)
2. GDS
Controller x 1
Master Card x 1
8-Channel Card 4..20 mA x 2
8-Channel Display Card x 1
REGARD
4205709
4205702
4206079
4205701
4206078
set 1 Dräger DNV-GL
(A-14074)
3. GH1 GRP Flameproof combination signal –
110 dB (A) / 5 Joule YL6S 225075 pcs. 1 Stahl Baseefa14ATEX0126
4. GH2 Audible and Visual Signalling Devices AS/M/SB/9-
60V/R/RL
7051111FUL-
0128X pcs. 1 Fulleon –
Smoke detection
Lp. Name Description Type Catalog
number Unit Qty. Manufacture Comments
1. FDS Controller Syncro ASM 2 Loop 009-485 pcs. 1 Kentec
GL
(09-LD405702-2-
PDA)
2. PB1 Manual Call point, Loop, addressable HCP-WM - pcs. 1 Hochiki DNV-GL
(13 977 - 15 HH)
3. SD1, SD2 Smoke detector
ALN-EN M
YBN-R3M
MBB-1
- set 2 Hochiki DNV-GL
(13 972 - 15 HH)
4. FH1 Audible and Visual Signalling Devices, Loop,
Addressable
CHQ-WSB YBN-R3M
MBB-1
- set 1 Hochiki –