gas and smoke detection system - lotos.logintrade.net

14
T.T.U. Urbanowicz ul. Mostek 2/8 80-759 Gdańsk Gas and smoke detection system D.Więckiewicz 09.05.2016 A. Stojek Z. Urbanowicz 09.05.2016 D As-built documentation Surname Date Surname Surname Date Status Prepared Checked Approved Remarks Project name Gas and smoke detection system Project no DP01316 TECHNICAL DOCUMENTATION OF LOTOS PETROBALTIC S.A. Archival no Document no Page Of pages Rev. no DP01316 DP01316-E01-1001-1 1 3 1 Contract no: LPB/FH/MG/16153/16 Project no: DP01316 User: LOTOS Petrobaltic Object: LOTOS Petrobaltic System: Gas and smoke detection system Title: Gas detectors instalation consisting of plot plans, circiut diagrams, bill of materials. Technical description of proposed technical solution. The document is the property of T.T.U. Zdzisław Urbanowicz, ul. Mostek 2/8, 80-759 Gdańsk, POLAND and cannot be copied or shared with third parties without written permission of T.T.U. Zdzisław Urbanowicz, ul. Mostek 2/8, 80-759 Gdańsk, POLAND.

Upload: others

Post on 07-Feb-2022

2 views

Category:

Documents


0 download

TRANSCRIPT

T.T.U. Urbanowicz

ul. Mostek 2/8

80-759 Gdańsk

Gas and smoke detection system

D.Więckiewicz 09.05.2016 A. Stojek Z. Urbanowicz 09.05.2016 D As-built documentation

Surname Date Surname Surname Date Status

Prepared Checked Approved Remarks

Project name

Gas and smoke detection system

Project no

DP01316

TECHNICAL DOCUMENTATION OF LOTOS PETROBALTIC S.A.

Archival no Document no Page Of pages Rev. no

DP01316 DP01316-E01-1001-1 1 3 1

Contract no: LPB/FH/MG/16153/16 Project no: DP01316

User: LOTOS Petrobaltic

Object: LOTOS Petrobaltic

System: Gas and smoke detection system

Title:

Gas detectors instalation

consisting of plot plans, circiut diagrams, bill of materials.

Technical description of proposed technical solution.

Th

e d

ocu

me

nt

is th

e p

rop

ert

y o

f T

.T.U

. Z

dzis

ław

Urb

an

ow

icz,

ul. M

oste

k 2

/8,

80

-75

9 G

da

ńsk,

PO

LA

ND

an

d c

an

no

t b

e c

op

ied o

r sha

red

with

th

ird

part

ies w

ith

out

wri

tte

n p

erm

issio

n o

f T

.T.U

. Z

dzis

ław

Urb

an

ow

icz

, u

l. M

oste

k 2

/8,

80

-75

9 G

da

ńsk,

PO

LA

ND

.

T.T.U. Urbanowicz

ul. Mostek 2/8

80-759 Gdańsk

Gas and smoke detection system

TECHNICAL DOCUMENTATION OF LOTOS PETROBALTIC S.A.

Archival no Document no Page Of pages Rev. no

DP01316 DP01316-E01-1001-1 2 3 1

TABLE OF CONTENTS

Title Page / document no

1 Description of the Proposed Technical Solution DP01316-E01-1001-1

2 Bill of Cables DP01316-E01-2001-0

3 Bill of Materials DP04615-E01-2002-0

4 Gas detection. Circiut diagram. DP01316-E01-3001-0

5 Smoke detection. Circiut diagram. DP01316-E01-3002-0

6 Gas and smoke detection area – plot plan DP01316-E01-7001-0

7 Gas and smoke detection– plot plan DP01316-E01-7002-0

8 Dräger. Gas Detection System 1-4

T.T.U. Urbanowicz

ul. Mostek 2/8

80-759 Gdańsk

Gas and smoke detection system

TECHNICAL DOCUMENTATION OF LOTOS PETROBALTIC S.A.

Archival no Document no Page Of pages Rev. no

DP01316 DP01316-E01-1001-1 3 3 1

1. Range of Elaboration

Due to the ABS requirements it is necessary to install gas detectors on the main deck/pipe rack to

ensure safety in Temporary Well Testing System area.

Smoke detection in a boiler container is not related to ABS requirements.

2. Description of the Proposed Technical Solution

Gas detection system.

Gas hazards in Temporary Well Testing area will be monitored by 9 IR gas detectors. Gas detectors

will by calibrated to detect combustible gases (methane). Gas detection controller will by installed in

mobile control container. Gas detection will run the Audible and Visual Signalling Devices. Localization

of gas detectors, controller and Audible and Visual Signalling Devices is shown on DP01316-E01-

7002-0. Gas detectors will be installed above the well testing system devices.

Smoke detection system.

Fire hazards in Boiler Container will be monitored by smoke detectors. Smoke detection controller will

by installed in mobile control container. Smoke detection will run the Audible and Visual Signalling

Devices. Localization of gas detectors, controller and Audible and Visual Signalling Devices is shown

on DP01316-E01-7002-0.

T.T.U. Zdzisław Urbanowicz

80-759 Gdańsk ul. Mostek 2/8

Tel. (058) 682-20-37

PROJECT DOC NO. PAGE PAGES REVISION DATE

DP01316 DP01316-E01-2001-1 1 2 1 09.05.2016

Bill of cables

No. Cabel name From To Cabel Type Lenght

[m] Diameter

[mm] Manufacture Comments

1. WSD1 =Mobile control

container+GSDC-FDS SD1

MarineCom YOZc X-FR 250 V 1 x 2 x 0,75 mm²

50 8,2 TKF

2. WSD2 SD1 SD2 MarineCom YOZc X-FR 250 V

1 x 2 x 0,75 mm² 5 8,2 TKF

3. WSD3 SD2 PB1 MarineCom YOZc X-FR 250 V

1 x 2 x 0,75 mm² 15 8,2 TKF

4. WSD4 PB1 FH1 MarineCom YOZc X-FR 250 V

1 x 2 x 0,75 mm² 15 8,2 TKF

5. WSD5 FH1 =Mobile control

container+GSDC-FDS MarineCom YOZc X-FR 250 V

1 x 2 x 0,75 mm² 45 8,2 TKF

6. WGD1 =Mobile control

container+GSDC-GDS GD1

MarineCom YOZc X-FR 250 V 2 x 2 x 0,75 mm²

75 12,2 TKF

7. WGD2 =Mobile control

container+GSDC-GDS GD2

MarineCom YOZc X-FR 250 V 2 x 2 x 0,75 mm²

70 12,2 TKF

8. WGD3 =Mobile control

container+GSDC-GDS GD3

MarineCom YOZc X-FR 250 V 2 x 2 x 0,75 mm²

55 12,2 TKF

9. WGD4 =Mobile control

container+GSDC-GDS GD4

MarineCom YOZc X-FR 250 V 2 x 2 x 0,75 mm²

55 12,2 TKF

10. WGD5 =Mobile control

container+GSDC-GDS GD5

MarineCom YOZc X-FR 250 V 2 x 2 x 0,75 mm²

50 12,2 TKF

11. WGD6 =Mobile control

container+GSDC-GDS GD6

MarineCom YOZc X-FR 250 V 2 x 2 x 0,75 mm²

45 12,2 TKF

12. WGD7 =Mobile control

container+GSDC-GDS GD7

MarineCom YOZc X-FR 250 V 2 x 2 x 0,75 mm²

65 12,2 TKF

13. WGD8 =Mobile control

container+GSDC-GDS GD8

MarineCom YOZc X-FR 250 V 2 x 2 x 0,75 mm²

45 12,2 TKF

T.T.U. Zdzisław Urbanowicz

80-759 Gdańsk ul. Mostek 2/8

Tel. (058) 682-20-37

PROJECT DOC NO. PAGE PAGES REVISION DATE

DP01316 DP01316-E01-2001-1 2 2 1 09.05.2016

Bill of cables

No. Cabel name From To Cabel Type Lenght

[m] Diameter

[mm] Manufacture Comments

14. WGD9 =Mobile control

container+GSDC-GDS GD9

MarineCom YOZc X-FR 250 V 2 x 2 x 0,75 mm²

45 12,2 TKF

15. WGH1 =Mobile control

container+GSDC-GDS GH1

MarineCom YOZc X-FR 250 V 2 x 2 x 0,75 mm²

75 12,2 TKF

16. WGH2 =Mobile control

container+GSDC-GDS GH2

MarineCom YOZc X-FR 250 V 1 x 2 x 0,75 mm²

15 12,2 TKF

17. WGSDC Mobile control container

power supply =Mobile control

container+GSDC Marineline YOZp G-type X-Fire

3x2,5 mm2 3 12,6 TKF

T.T.U. Zdzisław Urbanowicz

80-759 Gdańsk ul. Mostek 2/8

Tel. (058) 682-20-37

PROJECT DOC NO. PAGE PAGES REVISION DATE

DP01316 DP01316-E01-2002-1 1 1 1 09.05.2016

Gas detection

Lp. Name Description Type Catalog

number Unit Qty. Manufacture Comments

1. GD1÷GD9 IR-Gas detector ATEX: II 2G Ex d (e) IIC T6

PIR 3000 complete

set d-Version 6811180 set 9 Dräger

DNV-GL

(95 391-14 HH)

2. GDS

Controller x 1

Master Card x 1

8-Channel Card 4..20 mA x 2

8-Channel Display Card x 1

REGARD

4205709

4205702

4206079

4205701

4206078

set 1 Dräger DNV-GL

(A-14074)

3. GH1 GRP Flameproof combination signal –

110 dB (A) / 5 Joule YL6S 225075 pcs. 1 Stahl Baseefa14ATEX0126

4. GH2 Audible and Visual Signalling Devices AS/M/SB/9-

60V/R/RL

7051111FUL-

0128X pcs. 1 Fulleon –

Smoke detection

Lp. Name Description Type Catalog

number Unit Qty. Manufacture Comments

1. FDS Controller Syncro ASM 2 Loop 009-485 pcs. 1 Kentec

GL

(09-LD405702-2-

PDA)

2. PB1 Manual Call point, Loop, addressable HCP-WM - pcs. 1 Hochiki DNV-GL

(13 977 - 15 HH)

3. SD1, SD2 Smoke detector

ALN-EN M

YBN-R3M

MBB-1

- set 2 Hochiki DNV-GL

(13 972 - 15 HH)

4. FH1 Audible and Visual Signalling Devices, Loop,

Addressable

CHQ-WSB YBN-R3M

MBB-1

- set 1 Hochiki –

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

AB

CD

EFF

E

D

C

B

A

DrägerSafety Sp. z o.o.

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

AB

CD

EFF

E

D

C

B

A

DrägerSafety Sp. z o.o.

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

AB

CD

EFF

E

D

C

B

A

DrägerSafety Sp. z o.o.

610

600