Gas Fireplace Framing Guide Models, 21 TRV, 564 SS, 564 SS CF, 564 HO, 864 TRV, 864 TRV CF, 854 ST, 864 HO, 3615 HO, 4415 HO, 4415 HO See-Thru, 6015 HO and 4237 Clean Face Note: For General Reference Only. Aways consult the product Installation Manual for exact installation information. Installation Manuals can be found at www.fireplacex.com 4/24/2017

Upload: others

Post on 31-May-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Gas Fireplace Framing Guide - Cedar Hearth/Mick Gage ... › ... › 08 › Gas_FPFrame_Guide.pdf · Gas Fireplace Framing Guide Models, 21 TRV, 564 SS, 564 SS CF, 564 HO, 864 TRV,

Gas Fireplace Framing Guide

Models, 21 TRV, 564 SS, 564 SS CF, 564 HO, 864 TRV, 864 TRV CF, 854 ST, 864 HO,

3615 HO, 4415 HO, 4415 HO See-Thru, 6015 HO and 4237 Clean Face

Note: For General Reference Only. Aways consult the product Installation Manual for

exact installation information.

Installation Manuals can be found at www.fireplacex.com

4/24/2017

Page 2: Gas Fireplace Framing Guide - Cedar Hearth/Mick Gage ... › ... › 08 › Gas_FPFrame_Guide.pdf · Gas Fireplace Framing Guide Models, 21 TRV, 564 SS, 564 SS CF, 564 HO, 864 TRV,
Page 3: Gas Fireplace Framing Guide - Cedar Hearth/Mick Gage ... › ... › 08 › Gas_FPFrame_Guide.pdf · Gas Fireplace Framing Guide Models, 21 TRV, 564 SS, 564 SS CF, 564 HO, 864 TRV,
Page 4: Gas Fireplace Framing Guide - Cedar Hearth/Mick Gage ... › ... › 08 › Gas_FPFrame_Guide.pdf · Gas Fireplace Framing Guide Models, 21 TRV, 564 SS, 564 SS CF, 564 HO, 864 TRV,

CAUTION: RESTRICTOR ADJUSTMENT REQUIREDThis heater will not operate properly if the vent restrictor is not set for your specific installation. See “Vent configuration” section in the owner’s installation manual.

FIRST FIRE OR START UPYour appliance has been finished with the highest quality paint. Though this paint dries quickly to the touch, it does not cure or become hard until heated up by the appliance during first fire. For this reason the stove will emit light smoke and have a slight odor. Consult your owner’s manual for the complete paint curing instruc-tions. Partially open doors or windows to minimize smoke & odor.

LA PRECAUCIÓN: EL AJUSTE DE RESTRICTOR REQUERIDOEste calentador no funcionará apropiadamente si el restrictor de abertura no está previsto para su instalación específica. See "La configuración de abertura" corte transversal en el manual de instalación del propietario.

EL PRIMERO FUEGO O COMIENZA PARA ARRIBASSu aparato ha estado terminado con la pintura de mejor calidad. Aunque esta pintura se seca rápidamente al tacto, no hace la cura o becomve duro until cali-enta por el aparato durante el primer fuego. Para esta razón la cocina emitirá humo ligero y tendrá un olor leve. Consulte el manual de su propietario para la pintura completa curar las instrucciones. Abra puertas o ventanas parcialmente para minimizar humo & olor.

WARNING:Sheet metal edges can be sharp

ADVERTENCIA:Los bordes de chapa metálica pueden estar afilados

112-10001

Page 5: Gas Fireplace Framing Guide - Cedar Hearth/Mick Gage ... › ... › 08 › Gas_FPFrame_Guide.pdf · Gas Fireplace Framing Guide Models, 21 TRV, 564 SS, 564 SS CF, 564 HO, 864 TRV,
Page 6: Gas Fireplace Framing Guide - Cedar Hearth/Mick Gage ... › ... › 08 › Gas_FPFrame_Guide.pdf · Gas Fireplace Framing Guide Models, 21 TRV, 564 SS, 564 SS CF, 564 HO, 864 TRV,

564 SS GSR2 SCR Top Vent Configuration

8" (203mm) Diameter Vent

Framing

Guide

TRAVIS INDUSTRIES

HOUSE OF FIRE

12521 HARBOUR REACH DRIVE

MUKILTEO, WA 98275-5458

28-1/2"* 724mm

<16-3/4" 426mm�

* Includes the required 1/2" (13mm)

clearance.

Minimum Framing Dimensions - Rear Vent Configuration

HINT: place the fireplace so the center

line is at least 5" (127mm) from both

vertical framing members at the rear (this

allows the vent to pass through the

framing without modfications)

Minimum 38" (965mm)

Fireplace Enclosure Height

Route the

electrical line to

a position to the

left rear of the

fireplace.

/.�

33-1/2"

851mm

36-1/2"

Included Firestop (required)

Part# 250-00747

Vent Clearances for B" (203mm) dia. Vent:

1" (25mm) to the sides, 1" (25mm) below,

and 4" (102mm) above the vent to

combustibles

.-·ki··Center of Rear Vent

'J / 24-1/4"

616mm

845mm

Weight: 155 Lbs. (70.4kg)

Minimum Framing Dimensions - Top Vent Configuration

Route the electrical line to

a position to the left rear

of the fireplace.

33-1/2'

,.<'"�

851mm

36-1/2"

927mm

Minimum enclosure height= 38' [=

,,,,� 438mm

y�

927mm The on/off switch/thermostat wire (if

used) should be routed to a location

near the right front of the fireplace.

WARNING: A cut-out for the gas line

may be required on the framing. See

the dimensions under "Gas Line

Connection" for details.

Corner Installations - Rear Vent Configuration A typical 45° installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply).

7"(178mm) Approximate

(varies due to vent installation) __

6" (152mm) Section for 2x6

(51mm X 152mm) Walls

4" (102mm) Section for 2x4

(51mm X 102mm) Walls

45-3/4"

Minimum 1" (25mm) Clearance

564 SS Firestop

Corner Installations - Top Vent Configuration A typical 45" installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply)

45-3/4"

Minimum 1/2" (13mm) Clearance

The on/off switch/thermostat wire (if

used) should be routed to a location

near the right front of the fireplace.

Page 7: Gas Fireplace Framing Guide - Cedar Hearth/Mick Gage ... › ... › 08 › Gas_FPFrame_Guide.pdf · Gas Fireplace Framing Guide Models, 21 TRV, 564 SS, 564 SS CF, 564 HO, 864 TRV,
Page 8: Gas Fireplace Framing Guide - Cedar Hearth/Mick Gage ... › ... › 08 › Gas_FPFrame_Guide.pdf · Gas Fireplace Framing Guide Models, 21 TRV, 564 SS, 564 SS CF, 564 HO, 864 TRV,

564 DF GSR2 SCR Top Vent Configuration

8" (203mm) Diameter Vent

Framing

Guide

TRAVIS INDUSTRIES

HOUSE OF FIRE

12521 HARBOUR REACH DRIVE

MUKILTEO, WA 98275-5458

28-1/2"*

724mm

<16-3/4"

426mm

* Includes the required 1/2" (13mm)

clearance.

Minimum Framing Dimensions - Rear Vent Configuration

HINT: place the fireplace so the center

line is at least 5" (127mm) from both

vertical framing members at the rear (this

allows the vent to pass through the

framing without modfications)

Minimum 38" (965mm)

Fireplace Enclosure Height

Route the

electrical line to

a position to the

left rear of the

fireplace.

/.�

33-1/2"

851mm

36-1/2"

Included Firestop (required)

Part# 250-00747

Vent Clearances for B" (203mm) dia. Vent:

1" (25mm) to the sides, 1" (25mm) below,

and 4" (102mm) above the vent to

combustibles

.-·ki··Center of Rear Vent

'J / 24-1/4"

616mm

= �

845mm

Weight: 155 Lbs. (70.4kg)

Minimum Framing Dimensions - Top Vent Configuration

Route the electrical line to

a position to the left rear

of the fireplace.

33-1/2'

....<'"�851mm

36-1/2"

927mm

Minimum enclosure height= 38 [ /'

17-1/4"

y�

927mm The on/off switch/thermostat wire (if

used) should be routed to a location

near the right front of the fireplace.

WARNING: A cut-out for the gas line

may be required on the framing. See

the dimensions under "Gas Line

Connection" for details.

Corner Installations - Rear Vent Configuration A typical 45° installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply).

7"(178mm) Approximate

(varies due to vent installation) __

6" (152mm) Section for 2x6

(51 mm X 152mm) Walls

4" (102mm) Section for 2x4

(51mm X 102mm) Walls

45-3/4"

Minimum 1" (25mm) Clearance

564 SS Firestop

Corner Installations - Top Vent Configuration A typical 45• installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply)

45-3/4"

Minimum 1/2" (13mm) Clearance

The on/off switch/thermostat wire (if

used) should be routed to a location

near the right front of the fireplace.

Page 9: Gas Fireplace Framing Guide - Cedar Hearth/Mick Gage ... › ... › 08 › Gas_FPFrame_Guide.pdf · Gas Fireplace Framing Guide Models, 21 TRV, 564 SS, 564 SS CF, 564 HO, 864 TRV,
Page 10: Gas Fireplace Framing Guide - Cedar Hearth/Mick Gage ... › ... › 08 › Gas_FPFrame_Guide.pdf · Gas Fireplace Framing Guide Models, 21 TRV, 564 SS, 564 SS CF, 564 HO, 864 TRV,

864TRVGSR2

Framing Guide

TRAVIS INDUSTRIES

HOUSE OF FIRE

12521 HARBOUR REACH DRIVE

MUKILTEO, WA 98275-5458 20-5/8'"

Top Vent Configuration 8" (203mm) 0 Vent

Minimum Framing Dimensions - Top Vent Configuration

Route the electrical line to a position to the left rear of the fireplace.

38-1/2"

978mm

41-1/4"

1048mm

Minimum enclosure height= 38-1/2" (978mm)

_.,/-20-3/4"

-� The on/off switch/thermostat wire (if used) should be routed to a location near the right front of the fireplace.

Corner Installations - Top Vent Configuration

A typical 45° installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply).

50-1/2"

15-1/2" 394mm

Minimum 112' (13mm) Clearance

---@

Optional "Extra Room

38-1/4

972mm

Weight: 205 Lbs. (93 Kg)

Rear Vent Configuration 8" (203mm) 0 Vent

30·314" 781mm

Minimum Framing Dimensions - Rear Vent Configuration

HINT: place the fireplace so the center

line is at least 5" (127mm) from both vertical framing members at the rear (this

allows the vent to pass through the framing without modfications)

Route the electrical line to

a position to the left rear of the

fireplace.

38-1/2"

��978mm

41-1/4" 1048mm

Minimum enclosure height= 38-1/2" (978mm)

Included Firestop (required)

Part # 93006094

25-3/4"

Vent Clearances 8" (203mm) dia. Vent:

1" (25mm) to the sides, 1" (25mm) below, and 3" (76mm) above the vent to

combustibles . -··Ir _Center of Rear Vent

::r

38"

965mm

30-3/4"

781mm

-.. �ff ,e;;;

� The on/off switchtthermostat wire (if used) should be routed to a location

near the right front of the fireplace.

Corner Installations - Rear Vent Configuration

A typical 45° installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply).

NOTE

7·112'(91mm) Approximate

{varies due to vent installation)

Most installations use:

6'(152mm)Sectiontor

2X 6Walls(51mm X 152mm)

4"(102mm)Sectionlor

2x4 Walls (21mm X 102mm)

(Travis 1198900166)

50-1/2"

TravisFirestop

Minimum 1" {25mm) Clearance (sku 93006094)

Page 11: Gas Fireplace Framing Guide - Cedar Hearth/Mick Gage ... › ... › 08 › Gas_FPFrame_Guide.pdf · Gas Fireplace Framing Guide Models, 21 TRV, 564 SS, 564 SS CF, 564 HO, 864 TRV,

864 TRV CF GSR2

Framing Guide

\�-TRAVIS INDUSTRIES

HOUSE OF FIRE

12521 HARBOUR REACH DRIVE

MUKILTEO, WA 98275-5458

Minimum Framing Dimensions

44.75"

1137mm

42.75"

1086mm

7.25"

28-3/4"

22"

• Includes the required1/2" (13mm) clearance.

/' 22-112" (559mm) Flush

22" (572mm) lile over install

Optional Extra Room Power � Heat Duct Connection

/ / I /r 7.75"

44.75" 1137mm

39.25" 997mm

25.675"

The bottom of the face is 0.125" (4mm) above the baseplate.

Corner Installations - Top Vent Configuration

205 Lbs. (93 Kg)

Rear Vent Configuration 8" (203mm) 0 Vent

30.75" 781mm

A typical 45° installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply).

52-1/4" Min

15-1/2" 394mm

Minimum 1/2" (13mm) Clearance

Corner Installations - Rear Vent Configuration

A typical 45° installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply).

NOTE:

7-1/2"(191mm) Approximate

(varies due to vent installation)

Most installations use:

6" (152mm) Section for

4" (102mm) Section for

2x4 Walls (51mm X 102mm)

(Travis# 98900166)

Travis Firestop Minimum 1" {25mm) Clearance (sku 93006094)

52-1/4" Min

Page 12: Gas Fireplace Framing Guide - Cedar Hearth/Mick Gage ... › ... › 08 › Gas_FPFrame_Guide.pdf · Gas Fireplace Framing Guide Models, 21 TRV, 564 SS, 564 SS CF, 564 HO, 864 TRV,
Page 13: Gas Fireplace Framing Guide - Cedar Hearth/Mick Gage ... › ... › 08 › Gas_FPFrame_Guide.pdf · Gas Fireplace Framing Guide Models, 21 TRV, 564 SS, 564 SS CF, 564 HO, 864 TRV,
Page 14: Gas Fireplace Framing Guide - Cedar Hearth/Mick Gage ... › ... › 08 › Gas_FPFrame_Guide.pdf · Gas Fireplace Framing Guide Models, 21 TRV, 564 SS, 564 SS CF, 564 HO, 864 TRV,
Page 15: Gas Fireplace Framing Guide - Cedar Hearth/Mick Gage ... › ... › 08 › Gas_FPFrame_Guide.pdf · Gas Fireplace Framing Guide Models, 21 TRV, 564 SS, 564 SS CF, 564 HO, 864 TRV,
Page 16: Gas Fireplace Framing Guide - Cedar Hearth/Mick Gage ... › ... › 08 › Gas_FPFrame_Guide.pdf · Gas Fireplace Framing Guide Models, 21 TRV, 564 SS, 564 SS CF, 564 HO, 864 TRV,
Page 17: Gas Fireplace Framing Guide - Cedar Hearth/Mick Gage ... › ... › 08 › Gas_FPFrame_Guide.pdf · Gas Fireplace Framing Guide Models, 21 TRV, 564 SS, 564 SS CF, 564 HO, 864 TRV,

6015 HO

Framing Guide

\�-TRAVIS INDUSTRIES

HOUSE OF FIRE

12521 HARBOUR REACH DRIVE

MUKILTEO, WA 98275-5458

7-5/8"

-1-�I

350 lbs_

156 Kg_

34-3/4"

883mm

Minimum Framing Dimensions - LP with Minimum Vent (24" Rise)

® 72"

1829mm

72" 1829mm

64-3/4"

1645mm 17" 432mm Flush Install

@ m /" ,_,,,-- 16-1/2" 420mm Extended The fireplace enclosure must be a minimum ----<" (Tile Over) Install

72" (1829mm) tall (do not build into the fireplace enclosure)

Clearances

• Includes the requisite clearance to framing (1 /8"

4mm to rear, 5/8" 16mm to the sides)

1/2"

12mm

(a) Clearance to Side of Fireplace 5/8" (16mm). Do not place insulation in this space.

LP Min. Vent Installations 72" 1829mm

All Other Installations: 66" 1677mm

NOTE: Drywall or other combustible may contact the side of the fireplace in front of the framing. The material must not protrude in front of the fireplace and may be a maximum W' (13mm) thick.

(b) Clearance to Back of Fireplace 1/8" (4mm). Do not place insulation in this space.

(c) When installed, walls in front of the fireplace must be a minimum 3" (77mm) to the side of the fireplace.

Raised Fireplaces

• The fireplace (and hearth, if desired) may be placed on a platform designed to support the fireplace and vent.

• The base of the fireplace must be a minimum 66H

below the room ceiling.

The firebox opening is approximately 10.375" (264mm) above the base of the fireplace. For a typical raised fireplace of 36" (915mm), place the fireplace on a platform 25.625" (651mm) tall.

LP MIN VENT APPLICATIONS: Framing opening for LP min vent applications is 72" (1829mm). MAKE SURE TO ACCOMMODATE THE REQUIRED FRAMING OPENING.

Corner Installations

Typically 29"

737mm

Minimum 5/8" (16mm) Clearance

----- ---------- ------- ------- --------- -- ---�-

69" Min. 1753mm

Page 18: Gas Fireplace Framing Guide - Cedar Hearth/Mick Gage ... › ... › 08 › Gas_FPFrame_Guide.pdf · Gas Fireplace Framing Guide Models, 21 TRV, 564 SS, 564 SS CF, 564 HO, 864 TRV,