Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
i | P a g e
GAUTENG DEPARTMENT OF INFRUSTRUCTURE
DEVELOPMENT
BUILDING ASSESSMENT REPORT – STRUCTURAL
FOR
75 FOX STREET
AUGUST 2014
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
ii | P a g e
Table of Contents
1. INTRODUCTION …………………………………………………………………………………… 3
1.1 Design Criteria and Specifications……………………………………………………………….. 3
1.2 Scope of the Services Scheme Report…………………………………………………………. 3
2. STRUCTURAL ASSESSMENT………………………………………………………………………… 3
2.1 Building configuration and interfaces with adjacent buildings…………………… 3
2.2 Façade……………………………………………………………………………………………………….. 3
2.3 Roof Waterproofing and Roof Structures………………………………………………….. 4
2.4 General Structural Floor Slab Assessment…………………………………………………. 5
2.5 Structural Column and Concrete Wall Assessment……………………………………. 5
2.6 Foundations………………………………………………………………………………………………. 5
2.7 Basement and Basement Retaining Walls………………………………………………….. 5
2.8 Building Internal Brickwork……………………………………………………………………….. 6
2.9 Building Internal Finishes and Services……………………………………………………… 6
2.10 Staircases………………………………………………………………………………………………… 6
2.11 Structural Floor Loading Allowances Allowed For Future Use…………………. 6
3. PHOTOGRAPHIC EVIDENCE AND COMMENTS…………………………………………. 7
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
3
1. INTRODUCTION
The project brief, as issued by Gauteng Funding Agency (GFA), was to conduct an initial
assessment of the building condition, services, structural integrity of 75 Fox Street, and to
provide recommendations regarding the repairs and renovations of the buildings.
75 Fox Street is an occupied and functional building. The building has a structurally sound building
frame and suffers only from minor detailing errors, water entry problems and internal and external
service leaks. The building itself is in excellent condition, but requires the local details repaired to
ensure that it stays in a good condition for years to come.
The major maintenance items include the replacement of skylights and possible internal staircase
corrections.
The condition of the structural components is described below.
Design Criteria and Specifications
This project will be implemented in compliance with all the requirements of the National
Building Regulations and the new SANS10400, including any town planning prescripts of the
local authority.
Scope of the Services Scheme Report
This report deals with the proposed structural services to be implemented and preliminary
design for the feasibility for the repairs and renovations of the existing buildings.
2. STRUCTURAL ASSESSMENT
2.1 Building configuration and interfaces with adjacent buildings 75 Fox Street building comprises 14 floors, 3 basements below ground, ground floor slab, 9
Floors and a roof slab system with local level differences.
The building has a partial concrete roofs at level 14 and portions of the 13th floor is external (roof
area).
The building has a number of feature balconies and gardens on the northern and southern
facades at various slab levels.
75 Fox Street has no links to adjacent buildings.
2.2 Facade
The existing façade comprises a marble cladding on a structural steel sub-frame fixed onto the
concrete structural frame. The marble cladding is in excellent condition; however the renewal of
the polyurethane joint sealer between the panels is required. In two local positions (above the
southern parking entrance) the cladding panels will need to be re-adjusted. On the northern
façade a missing cladding tile needs to be replaced.
Aluminium windows are included in the façade and are in excellent condition. The window
rubbers between the glazing and the frame have perished in certain locations on the north and
eastern facades and need to be replaced.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
4
The facade parapets are covered with steel panel sheet flashing. These panel junctions need to
be resealed. The steel sheets have been blown off in a number of locations and require
replacement and joint resealing.
The vertical walls above roof level are in need of maintenance (painting) to avoid future damage
of facades and occupancy below roof level.
It is suggested that the external pavements around the building are lifted, levelled and re-laid as
the trees and other damage has caused the walking surface to become uneven and is a tripping
hazard in certain areas.
A window cleaning system exists for cleaning the exterior windows. The rail system is in good
condition; however the mechanical components must be checked by the mechanical engineers.
2.3 Roof Waterproofing and Roof Structures
The flat concrete roof system consists of a stepped roof arrangement over 3 floor levels.
The roof system has occupied floor areas, entertainment area, plant and general roof areas.
There is no plant visible on the roof as it is housed in dedicated covered areas.
The roof is generally covered in a varied size stone aggregate layer, underlain by a damp proof
membrane covering the roof waterproofing. The roof appears to be waterproofed with a
combination of acrylic roof sealant and torch on waterproofing in respective areas.
The majority of areas have recently been recoated in acrylic sealant and is in excellent condition.
There have been reports of water leaks under the new waterproofing in local areas, hence local
repairs of the waterproofing should be allowed for. Allow 10% of the roof area for such repairs.
Under the waterproofing is a screed to fall to fulbore outlets and associate downpipes. The
screed and downpipes are in good working order.
The following concerns need to be addressed with regard to the roof coverings:
1. The stone aggregate layer was not washed when installed and hence there is a layer of
fine material above the waterproofing which has the potential for clodding rainwater
goods and keeping the waterproof surface damp.
2. The stone layer stone size is too small and is being washed into the downpipes and
possibly damaging the downpipes internally in the process and leaking to blockages
down the line.
3. The presence of a damp proof membrane above the waterproofing in certain areas traps
water on the waterproofed surface and hence increases the risk of leaking.
4. Loose laid external pavers require edge restraint to prevent edge breakage.
5. Tiled external areas and skirtings need to be locally repaired and resealed to eliminate
water penetration into the structure.
6. External entrance door to the western fire escape should be covered with a
weatherproof awning.
7. Central skylight to be refurbished/replaced.
8. Central skylight louvres orientation to be corrected to direct storm water outside the
building.
9. Sloping skylight adjacent to the central skylight must be resealed.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
5
10. Entertainment area soft roof requires a gutter system on its lower end to avoid rain
water falling onto the incorrectly orientated louvres of the central skylight.
11. Roof façade walls which are plastered and painted are to be repainted
12. Façade render to be corrected and repaired locally where identified.
13. Safety hooks on the roof need to be replaced with more recent technology fasteners to
comply with latest safety standards.
There is a roof cleaning system with complete structural steel track system. The track system will
require repainting, and the lifting system will require mechanical and electrical check.
All structural steel elements on the roof require de-rusting and repainting.
2.4 General Structural Floor Slab Assessment
In general the existing concrete slab structures are in excellent condition.
The coffer slab construction of the floors from ground up and the flat slab construction of the
basements are all in excellent conditions.
No remedial works are required on the main floor slabs except for the following local issues:
1. Movement joint treatments to be addressed. In the parking slab situation the edges of
the movement joints are chipping and degrading as there is no edge protection. The use
of a steel plate secured on the one side of the movement joint is recommended, or a
suitable architectural joint treatment that can accommodate 20mm structural
movement. In the office ceiling situation, the plaster render must be treated with a
cover strip consistently secured on one side of the joint to cover the joint in the render
to architects details.
2. Replacing of the main southern entrance ramp (ground floor) mentis grating and the
cleaning out of the drainage channel.
3. Replacing of a local portion of screed, centrally on the south façade of basement 1 is
required.
2.5 Structural Column and Concrete Wall Assessment
The building is supported by concrete columns and concrete core walls which are in excellent
condition.
2.6 Foundations The building shows no signs of settlement and hence foundations and bearing strata below are
in good condition.
2.7 Basement and Basement Retaining Walls
The building has three sub-terrainian basements. The basements are in excellent condition
except for the following local defects:
1. Water leak from surface ponding through the basement 1 slab to basement 2 below on
the central southern façade. The replacement of the screed on basement 1 will solve the
problem.
2. Local patches of horizontal water entry through the basement walls. The solution is to
solve the leaking water pipe in Commissioner Street on the adjacent property, as well as
applying local negative waterproofing in local areas. Allow 50m2 of negative
waterproofing.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
6
The basement as two sump pumps which have recently been replaced and are in excellent
condition.
2.8 Building Internal Brickwork
The building’s internal brick walls are in excellent condition. There are a number of internal walls
with superficial cracking, but these can be filled with polyfiller (or similar) and repainted as
required.
In the basement archive, there is a portion of plaster that is peeling off the walls due to a water
leak. Details are in the photo evidence.
2.9 Building Internal Finishes and Services
The building internal finishes and services are in good condition.
Refer to architects report in this regard.
2.10 Staircases
The building has three concrete internal circulation staircases and two structural steel fire
escape stairs, one internal and one external.
The internal concrete stairs are structurally sound and the handrail and surface finish are in
excellent condition.
The internal structural steel fire escape staircase is in excellent condition; however the stair
geometry as built is does not meet current building regulations. The stair length is thread is too
short and the stair inclination appears excessive. It is recommended that this stair is
reconfigured for easier and safer use.
The external steel fire escape is in good condition, but will require local de rusting and a
complete repaint.
For the staircase compliance with new SANS regulations refer to the fire engineer report.
2.11 Structural Floor Loading Allowances Allowed For Future Use
Office and reception areas: 350kg/m2 (Office occupancy + light weight partitions)
Parking: 200kg/m2 (Car parking (no trucks))
Roof Slabs 350kg/m2. All new mechanical plant is best accommodated in existing plant rooms.
Plant Rooms (All floors): 500kg/m2 .
Note no masonry brickwork partitions are allowed internally and externally, unless verified by
structural engineer. In general walls which are required to be masonry (that is bathrooms and
kitchens) already exist.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
7
3. PHOTOGRAPHIC EVIDENCE AND COMMENTS
Figure 1: Northern façade of 75 Fox Street are in excellent condition. The jointing on the
building will need to be resealed and the window rubbers renewed locally where
required.
Figure 2: Southern façade of 75 Fox Street is in excellent condition. The jointing on the
building will need to be resealed and window rubbers renewed locally where
required.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
8
Figure 3: Eastern façade of 75 Fox Street is in excellent condition. The jointing on the building
will need to be resealed and window rubbers renewed locally where required.
Figure 4: Typical roof slab constructed from coffer slabs, with a screed to fall, waterproofing,
damp proof membrane and varied size stone chip layer as a finish.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
9
Figure 5: Roof stone chip layer is maximum 30mm thick and was not washed when installed.
The result is a layer of fines on the waterproofing which will retain moisture and
contribute to clogging of rainwater drainage paths and roof leaks.
Figure 6: External roof tiling tile grout has been placed on a Damp proof membrane. This is a
structurally acceptable detail; however the tiles should be secured on the edges of
the tiled areas to avoid the paving surface breaking out at the edges.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
10
Figure 7: A Damp proof membrane is placed over the waterproofing under tiling and stone
chips this plastic sheet will retain moisture between the sheet and the
waterproofing causing leaks. The use of a nonwoven geotextile is preferred as the
fabric is porous and can dry out, and offers better protection to the waterproofing
from human traffic above. In addition the stone chip size is too small and can easily
be washed into the rainwater downpipes causing damage to the pipes.
Figure 8: South eastern corner of the building showing well maintained roof. A maintenance
schedule and local patching may be required. It is noted that the roof waterproofing
is a mixture of torch on waterproofing and an acrylic based waterproofing product.
It is suggested that one system is standardised and used throughout for future
maintenance.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
11
Figure 9: Mechanical plant air exhausts are present on the roof. It is noted that the mentis
grids have locally sagged and it is recommended that he existing panel is simply
reversed. There is moss growth on certain panels, best removed with a high
pressure washer.
Figure 10: Façade and window washing rails are present on the building and are in good
working order. Now remedial works are required on this system, although the
cleaning mechanism was not inspected on site, this may require maintenance and a
check by the mechanical engineer that it complies with new safety regulations. It is
recommended that the rails are repainted.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
12
Figure 11: The acrylic based waterproofing present is in excellent condition, however local
patching may be required as numerous leaks need may have been reported within
the building. The building movement joints should also be checked for water
tightness and correct detailing.
Figure 12: Perimeter parapet wall flashings are installed in sections. The junctions require
resealing with a flexible product to architects specifications.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
13
Figure 13: A number of parapet flashings have been blown off and will require re-securing and
re-sealing (of the junctions) with a flexible product to architects specifications.
Figure 14: Safety hooks around the building will need to be replaced with newer technology to
comply with new health and safety regulations and best practice.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
14
Figure 15: The building southern façade and roof at roof level looking east. The building has a
central skylight system that requires major refurbishment and resealing due to
reported leaks. There are local smaller sloped skylights that are in good condition,
but should be resealed to ensure that future leaks are prevented.
Figure 16: View of the South western corner of the roof system looking west. All facades are in
good condition; however the junction between the cladding panels will require
resealing. The central roof skylight will require major refurbishment due to constant
leaks.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
15
Figure 17: Roof over the entertainment area directs roof water directly onto the central
skylight and into the vertical glass louvres under the skylight eaves. A gutter and
downpipes is recommended on this roof edge.
Figure 18: Central Skylight louvres are orientated incorrectly and direct rainwater into the
building instead of out of the building. It is recommended that the louvres are
rotated so that the lower edges face towards the outside of the building.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
16
Figure 19: Pipework on the western façade of the skylight hinders the functioning of louvres. It
is suggested that the pipework is moved to allow proper functioning of the louvre
system.
Figure 20: Broken glass louvre panels as well as the incorrect orientation of the louvres are the
cause of a substantial water entry into the building.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
17
Figure 21: Central skylight system over central internal atrium showing defects in the skylight
panels. The skylight requires a major refurbishment.
Figure 22: Central skylight system over central internal atrium showing defects in the skylight
panels. The skylight requires a major refurbishment.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
18
Figure 23: Central skylight system over central internal atrium showing defects in the skylight
panels. The skylight requires a major refurbishment. The skylight panels are seen to
be waving, which is a cause of water leaks.
Figure 24: The central skylight has a structural steel sub frame which is side fixed to the
concrete below. It is noted that a number of the structural steel frames have loose
anchor bolts at their fixity points. The bolts must be tightened and re-secured and
measures put in place to ensure the bolts don’t work loose over time (eg tack
welding the nuts to the base plate one tightened.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
19
Figure 25: Mechanical plant air exhausts are present on the roof. It is noted that the mentis
grids have locally sagged and it is recommended that he existing panel is simply
reversed. There is moss growth on certain panels, best removed with a high
pressure washer.
Figure 26: Access stairs and cat ladders require de-rusting and repainting. Note the incorrectly
oriented louvres on the central skylight directing storm water into the building.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
20
Figure 27: Service vent pipes require waterproof vent caps, re-rusting and repainting.
Figure 28: Roof torch on waterproofing on Northern face (centrally) into fulbore outlets. The
storm water system and waterproofing is in excellent condition, however the stone
chips are too small and are flowing down the downpipes and causing internal
damage.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
21
Figure 29: External steel access stairways will require de-rusting and repainting.
Figure 30: External tiling to northern entertainment terrace on the roof: The vertical tiled
skirting is breaking away from the wall and allowing water entry behind the tile and
causing vertical damp on the inside of the wall.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
22
Figure 31: Roof slab above eastern fire escape stair has been recently waterproofed. This area
appears to be the part of the roof where the rubbish collects. This area must be
maintained or the rubbish will block the rainwater downpipes.
Figure 32: Door to the Eastern fire escape stair requires a local small canopy over the door to
prevent water entry into the building. The door frame also requires repair due to
forced entry into the stairwell.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
23
Figure 33: Typical façade panels: The panels themselves and substructure are in excellent
condition. The grout between the panels is in excellent condition; however the
polyurethane or similar sealant over the grout has degraded and is peeling off. The
existing sealant should be stripped off and new sealant applied.
Figure 34: Typical façade panels: The panels themselves and substructure are in excellent
condition. The grout between the panels is in excellent condition; however the
polyurethane or similar sealant over the grout has degraded and is peeling off. The
existing sealant should be stripped off and new sealant applied.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
24
Figure 34: Typical façade panels: The panels themselves and substructure are in excellent
condition. The grout between the panels is in excellent condition; however the
polyurethane or similar sealant over the grout has degraded and is peeling off. The
existing sealant should be stripped off and new sealant applied.
Figure 35: Curved Northern high level façade tiling is secured to a curved masonry/concrete
beam: These tiles are at risk of coming loose if the surfaces of the support structure
are not re-waterproofed on top and painted on the rear faces.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
25
Figure 36: Curved Northern high level façade tiling is secured to a curved masonry/concrete
beam: These tiles are at risk of coming loose if the surfaces of the support structure
are not re-waterproofed on top and painted on the rear faces.
Figure 37: The underside of the curved northern façade feature beam requires drip details and
repainting.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
26
Figure 38: The only vertical façade panel that has dislodged and fallen from the façade is on the
north face on the eastern side. The panel appears to have slipped out of its securing
brackets for unknown reasons. This panel will need to be replaced.
Figure 39: The only vertical façade panel that has dislodged and fallen from the façade is on the
north face on the eastern side. The panel appears to have slipped out of its securing
brackets for unknown reasons. This panel will need to be replaced.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
27
Figure 40: Above the southern entrance there are 4 misaligned vertical façade panels due to a
vehicular impact on the panelling above the entrance. These local panels to be re-
alignment and re-secured.
Figure 41: Soffits of roof slabs show the resultant damage from previous leaks and need to be
skimmed and repainted.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
28
Figure 42: Marmoran type wall render is peeling off the walls on the southern façade of the
roof walls from water ingress. The wall should be suitably patched and re-rendered.
Figure 43: Façade “flower box” gardens are included in the building north and south facades.
These gardens are irrigated and appear to be functioning well. It is suggested that
the vegetation is replaced as certain plants appear to have “grown too big” for their
environment and may have substantial root systems which will affect the
waterproofing systems. Architectural guidance to be given in this regard.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
29
Figure 44: Façade “flower box” gardens are included in the building north and south facades.
These gardens are irrigated and appear to be functioning well. It is suggested that
the vegetation is replaced as certain plants appear to have “grown too big” for there
environment and may have substantial root systems which will affect the
waterproofing systems. Architectural guidance to be given in this regard.
Figure 45: A rusted structural steel element is present above the windows and sliding doors on
the landscaped boxer boxes. This structural steel element will need to be replaced
where required, preferably with a new galvanised element. This appears to be a
local issue on the southern façade only.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
30
Figure 46: In local areas the window rubbers between the glazing and aluminium frame has
deteriorated and will need to be replaced. This is noted as local issues on the north
and west facades of the building.
Figure 47: Resultant damage to soffits of roof slabs where roof waterproofing had previously
failed. The roof waterproofing has been recently maintained above. The areas above
the affected areas to be rechecked for leaks prior to scrapping, skimming and
repainted the slab soffits as required.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
31
Figure 48: Resultant damage to soffits of roof slabs where roof waterproofing had previously
failed. The roof waterproofing has been recently maintained above. The areas above
the affected areas to be rechecked for leaks prior to scrapping, skimming and
repainted the slab soffits as required. It is noted in addition that the finish around
the light fittings is being damaged from the heat of the light fitting in constant
operation.
Figure 49: Resultant damage to ceilings where roof waterproofing had previously failed. The
roof waterproofing as been recently maintained above. The areas of waterproofing
above the affected areas to be rechecked for leaks prior to scrapping, skimming and
repainted the slab soffits as required. It is noted in addition that the finish around
the light fittings is being damaged from the heat of the light fitting in constant
operation.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
32
Figure 50: Lift motor rooms are in excellent condition, however resultant damage from roof
waterproofing leaks is evident on the roof slab soffit. Roof waterproofing to be
checked for leaks and soffit repainted.
Figure 51: Lift motor rooms are in excellent condition, however resultant damage from roof
waterproofing leaks is evident on the roof slab soffit. Roof waterproofing to be
checked for leaks and soffit repainted.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
33
Figure 52: Aerial view of the internal central atrium. The slab systems are coffer slabs with
edge flower beds constructed as up stand beams. The structure is in excellent
condition.
Figure 53: Typical coffer slab construction of the office floor slabs from ground floor upward,
all in excellent well maintained condition.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
34
Figure 54: Typical ramp between basements in excellent condition. The grooved surface is a
good feature for increased tyre grip.
Figure 55: Typical flat soffit of the ramp system in excellent condition.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
35
Figure 56: Rendered slab soffits within the occupied office spaces did not include provision of a
joint in the finish under the slab movement joint. Hence the slab soffit finish has
cracked in these locations. It is recommended that a detail is developed by the
architect to hide these cracks (non-structural), such as a cover strip consistently
secured to the one face of the joint only.
Figure 57: Rendered slab soffits within the occupied office spaces did not include provision of
joint of the slab movement joint above. Hence the slab soffit finish has cracked in
these locations. It is recommended that a detail is developed by the architect to hide
these cracks (non-structural), such as a cover strip consistently secured to the one
face of the joint only.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
36
Figure 58: Concrete Internal staircases within the building are in excellent condition both in
finish and structurally.
Figure 59: Concrete Internal staircases within the building are in excellent condition both in
finish and structurally.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
37
Figure 60: The eastern internal steel fire escape stair is in good condition, however the riser
geometry makes climbing the stairs difficult. The stairs treads are too short. The
minimum tread length should be 275mm. It is recommended that these staircases
are reconfigured to make their use more comfortable and safe.
Figure 61: The eastern internal steel fire escape stair is in good condition, however the riser
geometry makes climbing the stairs difficult. The stairs treads are too short. The
minimum tread length should be 275mm. It is recommended that these staircases
are reconfigured to make their use more comfortable and safe.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
38
Figure 62: Basement sump pumps in the lowest basement have been recently replaced and are
in good working order. The pipe system which was previously leaking has been
rerouted and is working well.
Figure 63: Various inspection eyes for the subsoil drainage system are present and are in good
condition.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
39
Figure 64: Basement suspended slabs and surface beds are all in excellent condition
Figure 65: Basement suspended slabs and surface beds are all in excellent condition
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
40
Figure 66: Local horizontal water entry is present on the south basement wall. This will need to
be addressed with a waterproofing product applied to the internal face to architect
specifications.
Figure 67: Vertical water leak through the slab system is present in basement 2. This appears to
a leaking from pooling water above (service leak or other) above in basement 1
which has caused this issue. The leaking service (if applicable) above to be repaired
and the resultant damage repaired.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
41
Figure 68: Vertical water leak through the slab system is present in basement 2. This appears to
a leaking service above in basement 1 which has caused this issue. The leaking
service above to be repaired and the parking surface screed repaired to restore the
waterproof surface.
Figure 69: The building has a movement joints in the north south direction. A noticeable lack of
detailing of this joint within the building is noticeable both in the vertical and
horizontal planes. The joint must be covered with vertical cover strips secured on
one side of the joint only in an architecturally selected material.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
42
Figure 70: The building has a movement joints in the north south direction. A noticeable lack of
detailing of this joint within the building is noticeable both in the vertical and
horizontal planes. The horizontal joint in the parkade to be covered by a steel plate
secured on one face of the movement joint to detail.
Figure 71: The building has a movement joints in the north south direction. A noticeable lack of
detailing of this joint within the building is noticeable both in the vertical and
horizontal planes. The mailing room column joint must be covered with vertical cover
strips secured on one side of the joint only in an architecturally selected material.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
43
Figure 72: Southern basement parking entrance ramp in good condition, however the mentis
storm water grid half way up the ramp must be replaced and the channel below it
cleaned out.
Figure 73: Southern basement parking entrance ramp in good condition, however the mentis
storm water grid half way up the ramp must be replaced and the channel below it
cleaned out.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
44
Figure 74: Unrouted service pipe in basement 1 ceiling void to be directed to nearest drainage
point and ceiling replaced in this area.
Figure 75: Document archive reception area has water supply valve chamber which requires
rechecking for leaks, rerusting and repainting of the valve housing and re-plastering
of the adjacent wall.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
45
Figure 76: Main sewer launder pipes within the building run directly through the archive
document store. These pipes often get blocked which results in sewer entry into the
document store. It is suggested that a new service duct which is appropriately
waterproofed is installed to ensure that if the systems leak, the spillage can be
contained. Architectural guidance is required in this regard.
Figure 77: Sewer leaks are present from overflows caused from occasionally blocked pipes on
the floor above are evident. Containment areas for such sewerage issues is required
from architectural guidance.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
46
Figure 78: There are scattered piles of building rubble on the building roof that needs to be
removed.
Figure 79: There are scattered piles of building rubble on the building roof that needs to be
removed.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
47
Figure 80: Pavement at the southern entrance to the building requires patching of the concrete
surface in the sidewalk zone.
Figure 81: On the southern pavement a pipe exists which appear to serve no purpose that is a
tripping hazard. This pipe to be removed and sidewalk reinstated locally.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
48
Figure 82: Service covers on the eastern face of the building need to be removed, cleaned and
refitted and the pavement repaired locally.
Figure 83: The sidewalks are uneven and untidy. It is recommended that the paving on the
pavement is uplifted and relayed.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
49
Figure 84: The eastern face of the building has settled leaving the retaining walls below
pavement level open to the elements.
Figure 85: Service covers are missing and require replacement on the northern sidewalk.
Report for Department of Infrastructure Development Services Preliminary Report: 75 Fox Street August 2014
50
Figure 86: The storm water drain system is blocked on the Northern side of the building. As a
water pipe is leaking further up the street, there is a large volume of water standing
in the street adjacent to the 75 Fox street building.