ge water cooling pump wl5000se_ea

Upload: gabox

Post on 09-Mar-2016

68 views

Category:

Documents


4 download

DESCRIPTION

Water Cooling pump for GE X-blade Machine

TRANSCRIPT

  • GESensing & Inspection Technologies X-ray

    Water Cooling Pump

    WL 5000 SE

    Operating Instructions

  • Operating Instructions WL 5000 SE

    Copyright by GE Sensing & Inspection Technologies GmbH Bogenstrasse 41 22926 Ahrensburg

    201/23/2009

    1. Edition, ID No.: 2540570/EB.0109

    1st Edition

    Documentation ID No. 2540570/EB.0109

    Published by GE Sensing & Inspection Technologies GmbH

    Reference: hi, jo, dr Date: 01/23/2009 File: WL5000SE_e.indd

    Printed in Germany 2009

    GE Sensing & Inspection Technologies GmbH reserves the right to technical modifications without prior notice. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise, without the prior written consent of GE Sensing & Inspection Technologies GmbH.

  • Operating Instructions WL 5000 SE

    Copyright by GE Sensing & Inspection Technologies GmbH Bogenstrasse 41 22926 Ahrensburg

    301/23/20091. Edition, ID No.: 2540570/EB.0109

    Table of Contents

    1 Safety Measures ..................................................................................................................................................... 4

    2 Description .............................................................................................................................................................. 5

    3 Putting into Operation .......................................................................................................................................... 6

    4 Maintenance ........................................................................................................................................................... 7

    4.1 Heat Exchanger .......................................................................................................................................................................7

    4.2 Pump .............................................................................................................................................................................................8

    5 Placing out of Operation ....................................................................................................................................... 8

    6 Flow Chart ............................................................................................................................................................... 9

    7 Technical Data ...................................................................................................................................................... 10

    8 Spare Parts ............................................................................................................................................................ 11

    9 Circuit Diagram .................................................................................................................................................... 12

  • Operating Instructions WL 5000 SE

    Copyright by GE Sensing & Inspection Technologies GmbH Bogenstrasse 41 22926 Ahrensburg

    401/23/2009

    1. Edition, ID No.: 2540570/EB.0109

    1 Safety Measures

    Carefully read the Operating Instructions prior to commissioning.

    The mains connection is 230 V 50/60 Hz.

    The coolant is either water or a water-glycol mix according to the Description.

    Use only completely intact cooling hoses.

    Operate the equipment only if the tank is filled to the proper level and the ball valve on the pumps suction side is open. Otherwise the pump might suffer damage.

    The water level must always be above the cooling fins. Otherwise the cooling output is impaired.

    Clean the pump filter according to the Maintenance Instructions. Otherwise the pump may suffer damage.

    Make sure the cooling hoses are pressure-proof and resistant to the coolant used.

    Do not commission the equipment with hoses that are damaged or show leaks.

    Perform maintenance routines only if the water cooling pump is isolated from the power supply, i.e. first switch off the pump and then disconnect the electric connecting cables, e.g. by unplugging the connectors.

    Never open the water cooling pump during operation.

  • Operating Instructions WL 5000 SE

    Copyright by GE Sensing & Inspection Technologies GmbH Bogenstrasse 41 22926 Ahrensburg

    501/23/20091. Edition, ID No.: 2540570/EB.0109

    2 Description

    The WL 5000 SE water cooling pump serves the cooling of X-ray tubes in a closed water circuit.

    The coolant can be either water or a water-glycol mixture.

    Only GlycoShell must be used:

    Article no. 9434660 = 1 liter Do not mix GlycoShell with other coolant additives since this will cause coolant flocculation and total failure of the circulation pump (if necessary empty the water cooling circuit and refill it with a new mixture of GlycoShell and water). Therefore, watch the cooling water color:

    Correct are: Clear or dark blue-green Incorrect are all deviating colors: Red, brown, black e.g.

    Down to a temperature of 25C we recommend a ratio of

    two parts GlycoShell and three parts water.

    (Filling quantity about 5.0 l + 0.075 l/m hose = 6.5 l for a 20 m hose length [10 m inlet + 10 m outlet])

    The water circulates between the cooling unit and the X-ray tube. The water is recooled via an air-cooled heat exchanger. A bypass valve limits the maximum pressure of the pump.

    The maximum cooling output depends on the difference between the ambient temperature and the water outlet temperature.The power amounts to 5000 W with the temperature difference of 13,2 K between water outlet and ambient temperature.

    The cooling hoses with a 9 mm inside diameter are connected to the water cooling pump via hose sleeves.

    Water inlet and water outlet are marked by symbols:

    Inlet: O

    ; Outlet: O

    .

  • Operating Instructions WL 5000 SE

    Copyright by GE Sensing & Inspection Technologies GmbH Bogenstrasse 41 22926 Ahrensburg

    601/23/2009

    1. Edition, ID No.: 2540570/EB.0109

    3 Putting into Operation

    - Set up the equipment such that air inlet and air outlet are not blocked. If blocked, the cooling output is impaired.

    - Use the cable to establish the electric connection.

    - Connect the water hoses.

    - Open the filler stub. Fill the tank with drinking water, about 5.0 l + 0.075 l/m hose. The water level must be about 3 cm above the cooling fins.

    The water level must always be above he cooling fins. Otherwise the cooling output is impaired.

    - Start the water circuit to vent trapped air.

    - Check the water level. Add some more water if needed.

    - Close the filler stub.

    - The water cooling pump is ready for operation.

    Filler stub

    LuftaustrittAir Outlet

    LufteintrittAir Inlet

    Minimum 0,80 m Minimum 0,80 m

  • Operating Instructions WL 5000 SE

    Copyright by GE Sensing & Inspection Technologies GmbH Bogenstrasse 41 22926 Ahrensburg

    701/23/20091. Edition, ID No.: 2540570/EB.0109

    4 Maintenance

    Regularly check the water level in the tank. Add drinking water if needed.Clean the heat exchanger and the pump filter once a month*).

    *) Factors such as the formation of algae, heavy soiling or an unusually long operating cycle necessitate shorter maintenance intervals.

    4.1 Heat Exchanger

    As a dirty heat exchanger will lower the cooling output, regular checks are the safest method to find out whether the cooling fins need cleaning or not. If they do, proceed in the following way:

    - Isolate the water cooling pump from the power supply. See Safety Measures.

    - Dismount the siding and the cover.

    - Blow clean the cooling fins by applying compressed air. Be careful not to damage the cooler.

    - Remount the siding and the cover.

  • Operating Instructions WL 5000 SE

    Copyright by GE Sensing & Inspection Technologies GmbH Bogenstrasse 41 22926 Ahrensburg

    801/23/2009

    1. Edition, ID No.: 2540570/EB.0109

    4.2 Pump

    If the equipment is operated with a dirty filter, pump and motor may suffer damage.

    Clean the filter in the following way:

    - Isolate the water cooling pump from the power supply. See Safety Measures.

    - Dismount the siding.

    - Close the ball valve on the pump side.

    - Unscrew the filter cover (see Figure) (24 mm key width).

    Some water will escape. Use a suitable container to catch it.

    - Remove the filter. Clean it or replace it by a new filter.

    - Insert the filter. Screw the filter cover on tight.

    - Open the ball valve. If the filter cover is untight, tighten it once more.

    Do not put the equipment into operation when the ball valve is closed. Otherwise the pump may suffer damage.

    - Remount the siding.

    - Establish the electric connection. Let the water cooling pump run for about 10 minutes to vent trapped air and to simultaneously check the filter housing for leaks. In the event of leaks, check the seat of the screw. Renew the seal, if needed.

    - Check the water level in the tank. Add some water, if needed.

    5 Placing out of Operation

    - Isolate the water cooling pump from the power supply. See Safety Measures.

    - Unplug the electric connectors.

    - Dismount the cooling hoses.

    - Unscrew the drain cap. Drain the cooling liquid. Catch it in a suitable container.

    - Screw the drain cap back on again.

  • Operating Instructions WL 5000 SE

    Copyright by GE Sensing & Inspection Technologies GmbH Bogenstrasse 41 22926 Ahrensburg

    901/23/20091. Edition, ID No.: 2540570/EB.0109

    6 Flow Chart

    O

    O

  • Operating Instructions WL 5000 SE

    Copyright by GE Sensing & Inspection Technologies GmbH Bogenstrasse 41 22926 Ahrensburg

    1001/23/2009

    1. Edition, ID No.: 2540570/EB.0109

    7 Technical Data

    Dimensions and WeightsLength 483 mmWidth 406 mmHeight 481 mmWeight Approximately 38.5 kg without waterTank capacity Approximately 5.0 l*)

    *) In case of frost, use a mixture of drinking water and antifreeze (see Chapter 2 Description).

    Output DataCooling output 5000 W (T 13,2 K)Circulation rate 6,5 l/min at 3,0 barMains voltage 230 V +/- 10%, 50/60 HzPower input 2,6 ANoise level 63 dB (A) at 50 Hz, measured at a 1 m distance 67 dB (A) at 60 Hz, measured at a 1 m distance

    Environmental ConditionsOperating temperature range -10C +40C (with sufficient antifreeze)Storage temperature range -25C +70C (storage without water)Relative air humidity range 20% 90%

    SettingsMaximum pressure 7,0 bar 0,2 bar

    Power diagram WL 5000 SE20.0

    18.0

    16.0

    14.0

    12.0

    10.0

    8.0

    6.0

    4.0

    2.0

    0.0

    K

    Tempe

    rature differen

    ce betwee

    n am

    bien

    t air

    and forw

    ard water te

    mpe

    rature

    0 500 1000 1500 2000 2500 3000 3500 45004000 5000 5500

    WPower

  • Operating Instructions WL 5000 SE

    Copyright by GE Sensing & Inspection Technologies GmbH Bogenstrasse 41 22926 Ahrensburg

    1101/23/20091. Edition, ID No.: 2540570/EB.0109

    8 Spare Parts

    Item ID-Number

    1 pump complete 9456840

    2 drain cap 9456880

    3 Flachdichtung aus Perbunan, 9456890

    4 thermostat 9396850

    5 cap 9456850

    6 motor 9396860

    7 toothed ring for clutch 9396870

    8 fan 9456860

    9 capacitor f. fan 9078100

    10 filter 9396900

    11 turbine flow rate monitor EKS3 9350820

    12 plug-on electronics 9407300

  • Operating Instructions WL 5000 SE

    Copyright by GE Sensing & Inspection Technologies GmbH Bogenstrasse 41 22926 Ahrensburg

    1201/23/2009

    1. Edition, ID No.: 2540570/EB.0109

    9 Circuit Diagram

    -B2

    Str

    mun

    gswchter

    NNL1L1L1L1 1NN 1 2-X1

    GNYE

    -M2

    -M1

    1

    .

    5

    . 4

    .

    PE

    .

    plug

    M16 - Stecker

    -C1

    N

    L1

    wiring

    diagram

    Stromlaufplan

    2 1

    -B1

    BK BK

    -B2

    2

    .-X1

    3

    .

    3

    .

    4

    .

    Klem

    men

    plan

    term

    inal con

    nection table

    BK BK BN

    BUBN

    RDBUBUWH

    BNBK

    BKBK

    -C2

    -C2

    ESK3

    -RR.10

    BN BU

    -C1

    1

    .-X1

    M 1

    BKBN

    BU

    -M2

    M 1

    BK WH-M

    1

    43 32 4BK

    BKBK

    -B1

    2 1

    BK

    -C3

    B1 Tem

    peratur m

    ax. / tempe

    rature m

    ax

    Lege

    nde

    safety circuit

    Sicherhe

    itskreis

    Sich

    erhe

    itskreis

    safe

    ty circuit

    2

    .

    42

    31

    -C3

    GY

    M1 Pum

    pe / pu

    mp

    M2 Lfter / fan

    C3 Fun

    k-En

    tstrkon

    densator / radio interf

    eren

    ceC2

    Fun

    k-En

    tstrkon

    densator / radio interf

    eren

    ceC1

    Kon

    densator / capa

    citor

    B2 Strm

    ungswchter / o

    w sw

    itch

    supp

    ression capa

    citor

    supp

    ression capa

    citor

    switch

  • Operating Instructions WL 5000 SE

    Copyright by GE Sensing & Inspection Technologies GmbH Bogenstrasse 41 22926 Ahrensburg

    1301/23/20091. Edition, ID No.: 2540570/EB.0109

  • Operating Instructions WL 5000 SE

    Bogenstrasse 41 22926 Ahrensburg Germany www.gesensininspection.comTel.: +49 (0)4102/807-0 Fax: +49 (0)4102/807-189

    Im Interesse der Weiterentwicklung unserer Gerte Behalten wir uns das Recht auf nderungen von Daten und Konstruktionen ohne vorherige Mitteilung vor. Looking for technical improvements, we reserve the right to technical modifications without prior notice.

    Printed in Germany

    GESensing & Inspection Technologies

    GE Sensing & Inspection Technologies GmbH

    GE Sensing & Inspection Technologies, please contact:Service Department

    Tel.:+49 (0)4102 807-117Fax:+49 (0)4102 807-277

    1Safety Measures2Description3Putting into Operation4Maintenance4.1Heat Exchanger4.2Pump

    5Placing out of Operation6Flow Chart7Technical Data8Spare Parts9Circuit Diagram