33' CLEARHIGH BAY
WAREHOUSE (1994 ADDITION)
22' CLEARHIGH BAY
WAREHOUSE
1 STORY COLD DOCK
DOCK AREA WITH OFFICE LEVEL ABOVE
1 STORY OFFICE AREA
ENGINE ROOM W/ ROOFTOP
REFRIGERATION EQUIPMENT
RAIL DOCK
TRUCK PARKING(13 STALLS)
AUTO PARKING(72 STALLS)
TRUCK PARKING(9 STALLS)
TRUCK PARKING(15 STALLS)
02:E03
02:E0402:E04
02:E03
02:E0102:E01
02:E08
02:E0202:E02
02:E01
02:E05
02:E0102:E01
02:E08
02:E0402:E04
02:E05
02:E06
02:E01 02:E02
02:E07
02:E03
02:E01
A. SITE PLAN IS PROVIDED FOR REFERENCE ONLYB. NO REMODEL OR RENOVATION WORK WILL BE
PERFORMED AS PART OF THIS CONTRACT.
GENERAL NOTES - SITE PLAN
DATE:DRAWN BY:CHECKED BY:NEXUS PROJECT #:
Architectural NEXUS, Inc.2505 East Parleys WaySalt Lake City, Utah 84109T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.© Architectural Nexus, Inc. 2014
654321
E
D
C
B
A
3/1
3/2
017
11:5
5:0
7 A
M
ARCHITECTURALSITE PLAN
MDS
455 S
OU
TH
75T
H A
VE
.P
HO
EN
IX, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
16094
3/13/2017
NE
W P
HO
EN
IX A
Z. F
AC
ILIT
Y R
EM
OD
EL
PERMIT SET
AS101
MAD
1" = 40'-0"AS1011 SITE PLAN N
0' 40' 80'20'
KEYNOTE LEGEND02:E01 EXISTING CONCRETE PAVING
02:E02 EXISTING ASPHALT PAVING
02:E03 DESIGNATED FIRE DEPARTMENT ACCESSPATH
02:E04 EXISTING STORM WATER RETENTION FACILITY
02:E05 EXISTING STORAGE TANK
02:E06 EXISTING PUMP HOUSE
02:E07 EXISTING CONTAINER
02:E08 EXISTING DOCK APRON
# Date Revision
A. CONTRACTOR SHALL OBTAIN NECESSARY PERMITS AND INSPECTIONS REQUIRED BY THE GOVERNING
AUTHORITIES.
B. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ADOPTED (OR CURRENT WHERE NONE HAVE
BEEN ADOPTED) BUILDING CODES: 2012 IBC, 2012 IECC, 2012 IRC, 2012 IFC, 2012 IMC, 2012 IPMC, 2012 IPC,
2012 IFGC, 2011 NEC, ALL APPLICABLE LOCAL CODES, ORDINANCES AND AMENDMENTS.
C. ALL WORK SHALL BE DONE IN A NEAT, WORKMANLIKE, FINISHED AND SAFE MANNER UNDER COMPETENT
SUPERVISION.
D. ALL MATERIALS SHALL BE NEW AND OF THE BEST QUALITY, MANUFACTURED IN ACCORDANCE WITH
NEMA, ANSI, U.L. OR OTHER APPLICABLE STANDARDS. THE USE OF MANUFACTURER'S NAMES, MODELS
AND NUMBERS IS INTENDED TO ESTABLISH STYLE, QUALITY, APPEARANCE, USEFULNESS AND BID PRICE.
PROPOSED SUBSTITUTIONS SHALL BE SUBMITTED IN WRITING AND REVIEWED BY THE ENGINEER PRIOR
TO MATERIAL PROCUREMENT.
E. ALL ELECTRICAL EQUIPMENT SHALL BE CAPABLE OF OPERATING SUCCESSFULLY AT FULL-RATED LOAD,
WITHOUT FAILURE, AT AN AMBIENT AIR TEMPERATURE OF 0°F TO 120°F AND AN ELEVATION OF 1,200 FEET
(ABOVE SEA LEVEL). WHERE THESE CRITERIA CANNOT BE MET, ANCILLARY EQUIPMENT AND/OR SPECIAL
DERATING FACTORS AS APPROVED BY THE ENGINEER SHALL BE UTILIZED.
F. PROTECT ALL ELECTRICAL MATERIAL AND EQUIPMENT INSTALLED UNDER THIS CONTRACT AGAINST
DAMAGE BY OTHER TRADES, WEATHER CONDITIONS OR ANY OTHER CAUSES. EQUIPMENT FOUND
DAMAGED OR IN OTHER THAN NEW CONDITION WILL BE REJECTED AS DEFECTIVE.
G. LEAVE THE SITE CLEAN. REMOVE ALL DEBRIS, EMPTY CARTONS, TOOLS, CONDUIT, WIRE SCRAPS AND
ALL MISCELLANEOUS SPARE EQUIPMENT AND MATERIALS USED IN THE WORK DURING CONSTRUCTION.
ALL COMPONENTS SHALL BE FREE OF DUST, GRIT AND FOREIGN MATERIALS BEFORE FINAL
ACCEPTANCE OF WORK.
H. THESE CONSTRUCTION DRAWINGS ARE SUBJECT TO THE INTERPRETATION OF THE DESIGN ENGINEER.
ALL QUESTIONS REGARDING THESE CONSTRUCTION DOCUMENTS SHALL BE BROUGHT TO THE
ENGINEER. ANYONE WHO TAKES UPON THEMSELF THE INTERPRETATION OF THESE CONSTRUCTION
DOCUMENTS OR MAKES REVISIONS TO THE SAME WITHOUT CONFERRING WITH THE DESIGN ENGINEER
SHALL BE RESPONSIBLE FOR THE CONSEQUENCES THEREOF.
I. REFER TO OTHER PLANS FOR EXACT LOCATION OF EQUIPMENT AND ARCHITECTURAL FEATURES.
J. ALL WIRING SHALL BE COPPER UNLESS OTHERWISE NOTED. INSULATION SHALL BE TYPE XHHW OR
THWN. NONMETALIC-SHEATHED CABLE WILL NOT BE PERMITTED.
K. ALL WIRING DEVICES AND ELECTRICAL EQUIPMENT SHALL BE COMMERCIAL GRADE.
L. VERIFY EXACT LOCATION, MOUNTING HEIGHT AND ELECTRICAL REQUIREMENTS OF ALL EQUIPMENT
PROVIDED BY OTHERS PRIOR TO ROUGH-IN. PROVIDE ALL ASSOCIATED EQUIPMENT FOR PROPER
OPERATION AND FINAL CONNECTIONS TO EQUIPMENT PER OWNER.
M. PROVIDE GROUND WIRE IN ALL RACEWAYS SIZED PER NEC ARTICLE 250. INSTALL 250-LB PULL CORD IN
ALL EMPTY CONDUITS INSTALLED AS PART OF THIS PROJECT.
N. ALL UNDERGROUND CONDUIT TO BE SCHEDULE 40 PVC. MINIMUM DEPTH SHALL BE 24", MINIMUM SIZE
3/4". ALL EXPOSED CONDUIT SHALL BE TYPE GRS OR IMC, MINIMUM SIZE 3/4".
O. CONDUIT SHALL BE BURIED A MINIMUM OF 24-INCHES BELOW FINISHED GRADE TO TOP OF CONDUIT(S).
WHERE CONDUIT STUBS UP OUT OF THE EARTH TO ELECTRICAL EQUIPMENT, THE CONDUIT SWEEP AND
CONDUIT LEAVING THE EARTH MUST BE PVC COATED GRS CONDUIT OR RIGID STEEL CONDUIT WRAPPED
WITH 20-MIL RUBBER TAPE HALF-LAPPED TO A THICKNESS OF 40-MILS.
P. ALL CIRCUIT CONDUCTORS, #6 AWG OR SMALLER, SHALL BE "THHN/THWN-2" OR "XHHW" STRANDED
COPPER. ALL OTHER CONDUCTORS SHALL BE "XHHW" STRANDED COPPER. MINIMUM CONDUCTOR SIZE
SHALL BE #12 AWG WITH #12 AWG GROUND FOR POWER CIRCUITS.
GENERAL NOTES
ELECTRICAL ABBREVIATIONS
A, AMP AMP(S), AMPERE(S)
AC ALTERNATING CURRENT MC MANUFACTURER CABLE
AIC AMPS INTERRUPTING CAPACITY MCC MOTOR CONTROL CENTER
AFF ABOVE FINISHED FLOOR MCP MOTOR CIRCUIT PROTECTOR
AFG ABOVE FINISHED GRADE MECH MECHANICAL
AICAMPS INTERRUPTING CAPACITY, SYMM. MFR(S) MANUFACTURER(S)
AL ALUMINUM MH MANHOLE
ARCH
ARCHITECT(URAL)
MIC MICROPHONE
ASYM ASYMMETRICAL MIN MINIMUM
ATS AUTOMATIC TRANSFER SWITCH MISC MISCELLANEOUS
AUTO AUTOMATIC MLO MAIN LUG ONLY
AUX AUXILIARY MOV MOTOR OPERATED VALVE
AWG AMERICAN WIRE GAUGE MPC MINI-POWER CENTER
BC BARE COPPER MPR MOTOR PROTECTION RELAY
BLDG BUILDINGMV, mV MEDIUM VOLTAGE, MILLIVOLT
BOT BOTTOM MVMC MEDIUM VOLTAGE MOTOR CONTROL
CCONDUCTOR, CONDUIT
N.C. NORMALLY CLOSED
CB CIRCUIT BREAKER N.O. NORMALLY OPEN
CKT CIRCUIT N/A NOT APPLICABLE
CLG CEILINGNEUT, N
NEUTRAL
CMU CONCRETE MASONRY UNIT NF NON-FUSED
CNTL CONTROL NG NATURAL GAS
CONC CONCRETE NIC NOT IN CONTRACT
CPT CONTROL POWER TRANSFORMER No. NUMBER
CSI COMMUNICATION SYSTEM INSTALLER NOM NOMINAL
CT CURRENT TRANSFORMER NP NAMEPLATE
Cu COPPER NTS NOT TO SCALE
CV CONTROL VALVE OD OUTSIDE DIAMETER
DB DIRECT BURIAL OH OVERHEAD
DCDIRECT CURRENT, DATA CABLE
OIT OPERATOR INTERFACE TERMINAL
DET DETAIL OL OVERLOAD
DIAG DIAGRAM OWS OPERATOR WORKSTATION
DISC DISCONNECT PBPUSHBUTTON, PULLBOX
DIST DISTRIBUTION PKG'D PACKAGED
DWG DRAWING PMM POWER MONITORING MODULE
(E), (N)
EXISTING / NEW PNL PANEL
EA EACH PP POWER PANEL
EDB ELECTRICAL DUCTBANK PR PAIR
ELECELECTRIC, ELECTRICAL
PRI PRIMARY
ELP EXTRA LONG POND PT POTENTIAL TRANSFORMER
EMH ELECTRICAL MANHOLE PVC POLYVINYL CHLORIDE
ENCLENCLOSURE, ENCLOSED
PWR POWER
EP EXPLOSION PROOF RCPT RECEPTACLE
EPB ELECTRICAL PULLBOX PVC POLYVINYL CHLORIDE
EQUIP EQUIPMENT PW POTABLE WATER
FFUSE, FUSED
PWR POWER
FDR FEEDER RCPT RECEPTACLE
FL FLUORESCENT REF REFERENCE
FLA FULL LOAD AMPS REQ'D REQUIRED
FO FIBER OPTIC REQ'TS REQUIREMENTS
FVNR FULL VOLTAGE NON-REVERSING RMS ROOT MEAN SQUARE
FVR FULL VOLTAGE REVERSING RTU REMOTE TERMINAL UNIT
GDR GROUNDING RESISTOR RVNS REDUCED VOLTAGE NON-REVERSING
GEC GROUNDING ELECTRODE CONDUCTOR RVSS REDUCED VOLTAGE SOFT STARTER
GF GROUND FAULT SA SURGE ARRESTOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER SCR SILICON CONTROLLED RECTIFIER
GFP GROUND FAULT PROTECTION SD SMOKE DETECTOR
GND GROUND SEC SECONDARY
GRS GALVANIZED RIGID STEEL SES SERVICE ENTRANCE SECTION
H, HIHIGH SPEC SPECIFICATION
HMI HUMAN MACHINE INTERFACE SPC SPARE CONDUIT
HP HORSEPOWER SPD SURGE PROTECTION DEVICE
HTR HEATER SSI SECURITY SYSTEM INSTALLER
HTU HEAT TRACE UNIT SSS SOLID-STATE SOFT STARTER
HZ
HERTZ (CYCLES PER SECOND)
ST SHORT TIME
ICOM INTERCOM SWBD SWITCHBOARD
ID INSIDE DIAMETER SWGR SWITCHGEAR
INSTINSTANTANEOUS, INSTRUMENT
SYMM SYMMETRICAL
INTLK INTERLOCK SYS SYSTEM
IPB INSTRUMENT PULLBOX TELCO TELEPHONE COMPANY
JB JUNCTION BOX TEMP TEMPERATURE
KCMIL 1000 CIRCULAR MILS TSP TWISTED SHIELDED PAIR
kV KILOVOLT TST TWISTED SHIELDED TRIAD
kVA KILOVOLT-AMPERE TTB TELEPHONE TERMINAL BOARD
Kvar KILOVOLT-AMPERE REACTIVE TYP TYPICAL
KW KILOWATT UG U/G UNDERGROUND
KWH KILOWATT-HOUR UPS UNINTERRUPTIBLE POWER SUPPLY
LLONG, LENGTH
V VOLT
LAN LOCAL AREA NETWORK VA VOLT-AMPERE
LCP LOCAL CONTROL PANEL VAR VOLT-AMPERE REACTIVE
LCS LOCAL CONTROL STATION VC VACUUM CONTACTOR
LFMC LIQUIDTIGHT FLEXIBLE METAL CONDUT VD VOLTAGE DROP
LT LONG TIME WWATT, WIRE, WIDE
LTG LIGHTING WAN WIDE AREA NETWORK
LV LOW VOLTAGE WP WEATHERPROOF
mA MILLIAMPERE WPWIU WEATHERPROOF WHILE-IN-USE
MAG MAGNETIC XMTR TRANSMITTER
MBJ MAIN BONDING JUMPER Z IMPEDANCE
ELECTRICAL PLAN SYMBOLS
IDENTIFICATION SYMBOLS
XX
#
#
#X
INDICATES KEY NOTE # REFERENCED,
(APPLICABLE ONLY TO SHEET WITH NOTE
IS FOUND)
INDICATES BILL OF MATERIAL #
REFERENCED, (MAY BE APPLICABLE
ACROSS ALL PROJECT SHEETS)
INDICATES BRIEF INSTRUMENT
REFERENCE
INDICATES MISCELLANEOUS REFERENCE
NUMBER OR LETTER (DESCRIBED
FURTHER WITHIN PLANSET WHERE
APPLICABLE)
CXXXX
CONDUIT IDENTIFICATION
(#### = CONDUIT NUMBER,
REFER TO CONDUIT SCHEDULE)
RACEWAYS AND LINETYPES
GROUNDING SYSTEM CONDUCTOR
EXPOSED CONDUIT
UTILITY CONDUIT DUCTBANK
CONDUIT TURNED DOWN
CONDUIT STUBUP
EXISTING CONCEALED CONDUIT
CONDUIT RUN CONCEALED IN
CEILING, FLOOR, OR IN WALLS
GGG
XXXX
XXXX
EXISTING EXPOSED CONDUIT
UNDERGROUND CONDUIT
DUCTBANK
EXISTING UNDERGROUND CONDUIT
DUCTBANK
EXISTING UTILITY CONDUIT
DUCTBANK
OHEOHE
OHEOHE
CHAIN LINK FENCE
EXISTING CHAIN LINK FENCE
UTILITY OVERHEAD ELECTRIC
EXISTING UTILITY OVERHEAD
ELECTRIC
GROUNDING
GROUND SYSTEM CONNECTION
GGG
G
LIGHTNING ROD
GROUND ROD AND WELL
GROUND ROD WITHOUT WELL
RECEPTACLES
SWITCH AND SIMPLEX RECEPTACLE
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE
DUPLEX RECEPTACLE WITH SPLIT WIRE
QUADRAPLEX RECEPTACLE
RECESSED FLOOR DUPLEX RECEPTACLE
RECESSED FLOOR QUADRAPLEX RECEPTACLE
SPECIALTY PURPOSE RECEPTACLE
480V RECEPTACLE
WELDING OR APPLIANCE RECEPTACLE
#
x
S
#
x
#
x
#
x
#
x
#
x
#
x
#
x
#
x
#
x
WHERE,
# = CIRCUIT DESIGNATION
x = DEVICE TYPE DESIGNATION, WHERE
GF = GROUND FAULT CIRCUIT INTERRUPTER
WP = WEATHERPROOF
WPWIU = WP WHILE-IN-USE
SWITCHES
SINGLE POLE SWITCH
SINGLE POLE SWITCH WITH MODIFIER
WHERE,
# = CIRCUIT DESIGNATION
x1 = DESIGNATION OF DEVICE SWITCHED (I.E. a, b, c, etc.)
x2 = SWITCH SUBSCRIPT MODIFIER, WHERE
2 = GROUND FAULT CIRCUIT INTERRUPTER
3 = WEATHERPROOF
4 = WP WHILE-IN-USE
K = KEY OPERATED
M = HORSEPOWER RATED MANUAL STARTER
MC = MOMENTARY CONTACT, THREE POSITION
MO = SWITCH WITH MOTION SENSOR
MS = MANUAL (MOTOR) STARTER OR SWITCH
TC/P = TIME CLOCK / PROGRAMMABLE
R = RHEOSTAT (DIMMER OR SPEED CONTROL)
F = FLUSH MOUNTED
WP = WEATHERPROOF
HOMERUN
MISCELLANEOUS
xx UNDERGROUND BOX
xx = BOX TYPE/DESIGNATION (I.E. EMH, EPB, IPB)
SAFETY SWITCH
xx = DISCONNECT TYPE (I.E. F, NF, CB)
#A = CURRENT RATING OF SWITCH
xx
#A
COMBINATION MOTOR STARTER
LOCAL/PUSHBUTTON CONTROL STATION
IDENTIFICATION SYMBOLS
a
b
c
d
e
f
LOW VOLTAGE CIRCUIT BREAKER
a = BREAKER DESIGNATION
b = AMPS & TRIP SETTING
(AT - AMP TRIP)
(AC - CONTINUOUS RATING)
c = FRAME SIZE (MFR TO
DETERMINE FRAME SIZE UNLESS
INDICATED)
d = BREAKER TYPE
MCP - MOTOR CIRCUIT
PROTECTOR
SS - SOLID-STATE
TM - THERMAL MAGNETIC
e = NUMBER OF POLES
f = WITHSTAND RATING
LOW VOLTAGE DISCONNECT SWITCH
a = DISCONNECT DESIGNATION
b = AMPS RATING
c = NUMBER OF POLES
d = ENCLOSURE RATING (IF
MOUNTED IN SEPARATE ENCL) (I.E.
NEMA 1, 12, 3R, 4X, 7)
e = WITHSTAND RATING
a
b
c
d
f
a
b
FUSE
a = AMPS RATING
b = FUSE TYPE
MOTOR STARTER
a = STARTER SIZE
b = STARTER TYPE (NEMA/IEC)
a
b
OVERLOAD RELAY
a = OVERLOAD TYPE (I.E. OL, EOL)
a
M <UTILITY>
POWER
METER
UTILITY
METER
HP
MOTOR
HP = HORSEPOWER RATING
ONE LINE DIAGRAM
SYMBOLS
DESCRIPTION
120V, 2'x4' FLUORESCENT LUMINAIRE, GRID/LAY-IN MOUNT,
SPECIFICATION GRADE T8 TROFFER, FLAT WHITE STEEL DOOR, #12
ACRYLIC PATTERN, UNIVERSAL VOLTAGE, ELECTRONIC START
BALLAST.
LUMINAIRE SCHEDULE
SYMBOL LAMP(S) FIXTURE MANUFACTURER
METALUX (2GC8-232A-UNV-EB81)
(2) 32W T8
FLUORESCENT
LAMPS
120V, 2'x4' FLUORESCENT LUMINAIRE, GRID/LAY-IN MOUNT,
SPECIFICATION GRADE T8 TROFFER, FLAT WHITE STEEL DOOR, #12
ACRYLIC PATTERN, UNIVERSAL VOLTAGE, ELECTRONIC START
BALLAST. INCLUDE EMERGENCY BATTERY PACK.
METALUX (2GC8-232A-UNV-EB81 + BATTERY PACK)
x1 #
x1 #
x2
A
B
BP
(3) 32W T8
FLUORESCENT
LAMPS
(2) 32W T8
FLUORESCENT
LAMPS
(2) 2W
AC LED
LAMPS
OS OCCUPANCY SENSOR
SP SWITCHPACK / POWER SUPPLY
METALUX (2GC8-332A-UNV-EB81)
COOPER LIGHTING - ALL PRO (APW-GPW232-32W)
SURE-LITES (APX6-R)120V, AC ONLY LED, ALL-PRO EXIT, RED.
EXIT
D
C
(2) 32W T8
FLUORESCENT
LAMPS
METALUX (SSF-232-UNV-EB81-AYC-CHAIN/SET)
120V, 4"x4' FLUORESCENT LUMINAIRE, COMMERCIAL STANDARD
STRIPLITE, PENDANT MOUNT, ELECTRONIC INSTANT START BALLAST.
F
(2) 32W R.S.
FLUORESCENT
LAMPS
DAY BRITE (DWAE232-120-EB10R)
LITHONIA (DMW232AR123-STSL-GEB10RS)
COLUMBIA (LUN4-232-EB8LH120-CPSSL)
120V, 8"x4' VAPORTIGHT (FULLY GASKETED) FLUORESCENT LUMINAIRE,
SURFACE MOUNTED, ONE PIECE, IMPACT RESISTANT ACRYLIC
DIFFUSER WITH SMOOTH SURFACE. UL LISTED FOR WET LOCATIONS.
G
(2) 32W T8
FLUORESCENT
LAMPS
120V, 8"x4' FLUORESCENT LUMINAIRE, SURFACE MOUNT, GENERAL
PURPOSE WRAP.
120V, 2'x4' FLUORESCENT LUMINAIRE, GRID/LAY-IN MOUNT,
SPECIFICATION GRADE T8 TROFFER, FLAT WHITE STEEL DOOR, #12
ACRYLIC PATTERN, UNIVERSAL VOLTAGE, ELECTRONIC START
BALLAST.
120V, 4.5"x2' T8 FLUORESCENT LUMINAIRE, WHITE ACRYLIC.
H
LITHONIA (2RE-120)
(2) 17W
FLUORESCENT
LAMPS
(4) 32W T8
FLUORESCENT
LAMPS
COOPER LIGHTING - ALL PRO (APW-GPW432-32W)
E
120V, 12"x4' FLUORESCENT LUMINAIRE, SURFACE MOUNT, GENERAL
PURPOSE WRAP.
E1
(6) T8
FLUORESCENT
LAMPS
(2) T8
FLUORESCENT
LAMPS
EXISTING 2'x4' FLUORESCENT LUMINAIRE, PENDANT OR SURFACE
MOUNT.
EXISTING 8"X4' VAPORTIGHT FLUORESCENT LUMINAIRE, PENDANT OR
SURFACE MOUNT.
E2
(6) T5
FLUORESCENT
LAMPS
EXISTING 2'x4' FLUORESCENT LUMINAIRE, PENDANT OR SURFACE
MOUNT.
E3
J
(2) LAMPS
INCANDESCENT
COOPER LIGHTING - ALL PRO (AP2SQ)120/277V, EMERGENCY LUMINAIRE WITH 1½ HOUR BATTERY,
THERMOPLASTIC HOUSING.
(4) T8
FLUORESCENT
LAMPS
EXISTING 8"X8' VAPORTIGHT FLUORESCENT LUMINAIRE, PENDANT OR
SURFACE MOUNT.
E4
480V, 3PH LOAD CALCULATIONS
LOAD DESCRIPTION KVA H.P. AMPS
FIRE PUMP -- 250 302.0
SWITCHBOARD (SWBA)
703.0
480V PANEL LPA2 84.2 -- 101.2
480V PANEL LPA 49.7 -- 59.8
480V PANEL LPE ** EXISTING - NO CHANGES ** 18.0 -- 21.7
480V PANEL LPF 228.9 -- 275.4
MOTOR CONTROL CENTER (MCCA) ** EXISTING - NO CHANGES **
245.0
FREEZER FAN D2-A -- 2 3.4
FREEZER FAN D2-A -- 2 3.4
FREEZER FAN D2-B -- 2 3.4
FREEZER FAN D2-B -- 2 3.4
FREEZER FAN D3-A -- 2 3.4
FREEZER FAN D3-A -- 2 3.4
FREEZER FAN D3-B -- 2 3.4
FREEZER FAN D3-B -- 2 3.4
FREEZER FAN D4-A -- 2 3.4
FREEZER FAN D4-A -- 2 3.4
FREEZER FAN D4-B -- 2 3.4
FREEZER FAN D4-B -- 2 3.4
FREEZER FAN D5-A -- 2 3.4
FREEZER FAN D5-A -- 2 3.4
FREEZER FAN D5-B -- 2 3.4
FREEZER FAN D5-B -- 2 3.4
FREEZER FAN D6-A -- 2 3.4
FREEZER FAN D6-A -- 2 3.4
FREEZER FAN D6-B -- 2 3.4
FREEZER FAN D6-B -- 2 3.4
FREEZER FAN D1-C -- 2 3.4
FREEZER FAN D1-B -- 1 1.8
FREEZER FAN D1-A -- 1 1.8
UNDER FLR VENT FAN -- 2 3.4
EF-2 VENT FAN -- 1 1.8
MAINTENANCE ROOM EXHAUST FAN -- 0.5 1.0
GLYCOL PUMP 1 -- 1.5 2.6
GLYCOL PUMP 2 (BACKUP)
-- 1.5 0.0
PURGE PUMP -- 3 4.8
AMMONIA PUMP 1 -- 3 4.8
WATER JACKET PUMP 1 -- 3 4.8
WATER JACKET PUMP 2 (BACKUP)
-- 3 0.0
AMMONIA PUMP -- 5 7.6
AMMONIA PUMP (BACKUP)
-- 5 0.0
CONDENSOR PUMP -- 5 7.6
CONDENSOR PUMP -- 5 7.6
DOCK HOLDING COND FAN (AC-1)
-- 1 1.8
DOCK HOLDING COND FAN (AC-2)
-- 1 1.8
DOCK HOLDING COND FAN (AC-3)
-- 1 1.8
DOCK HOLDING COND FAN (AC-4)
-- 1 1.8
DOCK HOLDING COND FAN (AC-5)
-- 1 1.8
DOCK HOLDING COND FAN (AC-6)
-- 1 1.8
BLAST FREEZER (B-1) (7.5 HP) <REMOVED>
-- 0 0.0
BLAST FREEZER (B-1) (7.5 HP) <REMOVED>
-- 0 0.0
BLAST FREEZER (B-2) (7.5 HP) <REMOVED>
-- 0 0.0
BLAST FREEZER (B-2) (7.5 HP) <REMOVED>
-- 0 0.0
ROOF CONDENSOR FAN -- 10 14.0
ROOF CONDENSOR FAN -- 10 14.0
AMMONIA PUMP -- 3 4.8
ROOF CONDENSOR HEATER <REMOVED> 18 -- 0.0
ROOF CONDENSOR HEATER <REMOVED> 18 -- 0.0
BLAST FREEZER #3 (2 X 7.5 HP) <REMOVED>
-- 0 0.0
BLAST FREEZER #4 (2 X 7.5 HP) <REMOVED>
-- 0 0.0
FREEZER EVAPORATOR #1 -- 7.5 11.0
FREEZER EVAPORATOR #2 -- 7.5 11.0
FREEZER EVAPORATOR #3 -- 7.5 11.0
FREEZER EVAPORATOR #4 -- 7.5 11.0
FREEZER EVAPORATOR #5 -- 7.5 11.0
DOCK EVAPORATOR #1 -- 3 4.8
DOCK EVAPORATOR #2 -- 3 4.8
DOCK EVAPORATOR #3 -- 3 4.8
FREEZER EVAPORATOR #6 -- 7.5 11.0
SWITCHBOARD (SWBB)
578.6
480V PANEL LPC 62.3 -- 74.9
480V PANEL LPD 53.7 -- 64.6
480V PANEL HVP3 197.9 -- 238.0
SWITCHBOARD (TE)
201.0
480V PANEL HVP1 31.8 -- 38.2
480V PANEL HVP2 38.9 -- 46.8
480V PANEL LPB 73.9 -- 88.9
208V PANEL RPD TRANSFORMER 21.0 -- 25.3
208V PANEL LVP4 TRANSFORMER 1.5 -- 1.8
MOTOR CONTROL CENTER (MCCB) ** EXISTING - NO CHANGES **
0.0
CP-3B (STANDBY)
-- 100 0.0
CP-4B (STANDBY)
-- 100 0.0
CP-3 (STANDBY)
-- 150 0.0
CP-4 (STANDBY)
-- 150 0.0
MOTOR CONTROL CENTER (MCCC) ** EXISTING - NO CHANGES **
608.0
CP-1B (DUTY)
-- 100 124.0
CP-2B (DUTY)
-- 100 124.0
CP-1 (DUTY)
-- 150 180.0
CP-2 (DUTY)
-- 150 180.0
MOTOR CONTROL CENTER (MCCD) ** EXISTING - NO CHANGES **
0.0
CP-5 (STANDBY)
-- 407 0.0
SURGE PROTECTION DEVICE 0 -- 0.0
SUBTOTAL = 2436.6
+25% OF CONTINUOUS LIGHTING LOADS = 45.2
+25% OF LARGEST MOTOR (407HP) =
75.5
MINIMUM SERVICE SIZE = 2557.3
EXISTING SERVICE SIZE = 3000A
DATE:
DRAWN BY:
CHECKED BY:
CEE PROJECT #:
Original drawings remain the property
of the Engineer and as such the
Engineer retains total ownership and
control. The design represented by
these drawings is sold to the client for
a one time use, unless otherwise
agreed upon in writing by the Engineer.
© Controlled Energy Engineers LLC 2017
654321
E
D
C
B
A
CONTROLLED ENERGY
ENGINEERS, LLC
2451 W BIRCHWOOD AVE, #104
MESA, AZ 85202
PHONE: 480.621.5933
Know what's below.before you dig.Call
1-800-782-5348
THIS DRAWING IS A COMPILATION BASED ON INFORMATION FROM, BUT NOT
LIMITED TO, DRAWINGS FROM PREVIOUS PROJECTS:
THIS DRAWING MUST BE FIELD VERIFIED BEFORE USE
DRAWING NOT TO SCALE UNLESS SCALE BAR IS PRESENT
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
# Date Revision
2/2/2017 3:58:55 P
M
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
PERMIT SET
# Date Revision
17002
ZEW
CEE
MAR 13, 2017
,
S
WILSTERMAN
E
n
r
e
ig
e
R
s
t
D
g
O
a
A
e
i
S
t
Z
I
R
e
A
n
N
d
.
U
ZANE E.
P
d
e
I
r
T
R
E
C
s
s
o
f
e
li
n
F
I
o
T
AC
a
E
l
A
.
.
)
e
.
ir
cal
c
t
E
(
O
i
N
g
e
r
e
n
39548
EXPIRES 09-30-2018
3-13-17
1 4-27-17 2ND CITY
SUBMITTAL
2 6-1-17 3RD CITY
SUBMITTAL
3 7-12-17 RAIL DOCK
BATTERY
CHARGING
4 11-15-17 3000A SES
ELECTRICAL
COVER
SHEET
E100
4
1
1
3
3
4
4
B4
B
5
5
7
7
6
6
8
8
9
9
10
10
11
11 12 13 14 15 16 17 18 19 20 21 22
23
23
23.2
23.2
24
24
25
25
26
26
26.6 27
27
29
29
30
30
31
31
32
3222.8 23.6" 26.2 26.9 28 30.6 31.4
B1
B7
B8
B9
C
D1
E
F
G
H
I
J
K1
L1
F-01
C2 C1
C3C3
RB
RC RD
RE
C1
C1
C1
C2 C2
C2 C2
C2 C2
C1 C2 C2
C1 C2 C2
C1 C2 C2
C1 C2 C2
C1 C2 C2
C1 C2 C2
C1
C1
P5
P5
P5
P5
P5
P5
P3P3
P3P3
P3P3
P3P3
P3P3
P3P3
P3P3
P3P3
P3P3
P3P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P5
P5
P5
P5
P5
P5
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P5
P5
P5
P5
P5
P5
P5
P5
P5
P5
P5
P5
P5
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
FA FB FC FD FE FF
C3 C3C3
C2C2 C2 C2
C2 C2
C2 C2
C1
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C2 C2 C2 C3
C4
C1
C2 C2 C2 C3
C4
C1
C2 C2 C2 C3
C4
C1
C2 C2 C2 C3
C4
C1
C4
C2 C2 C2 C3
C4
C1
C2 C2 C2 C3
C4
C1
C2 C2 C2 C3
C4
C1
C2 C2 C2 C3
C4
C1
C2 C2 C2 C3
C4
C1
C2 C2 C2 C3
C4
C1
C2 C2 C2 C3
C4
C1
C4
C4
C2 C2 C2 C3C1
C4
C4
C2 C2 C2 C3C1 C4
C2 C2 C2 C3C1 C4
C2 C2 C2 C3C1 C4
C2 C2 C2 C3C1 C4
C2 C2 C2 C3C1 C4
C2 C2 C2 C3C1 C4
C2 C2 C2 C3C1 C4
C2 C2 C2 C3C1 C4
C2 C2 C2 C3C1 C4
C4
C4
RARF
C2 C1
C2 C1
C2 C1
C2 C1
C2 C1
C2 C1
C2 C1
C2 C1
C2 C1
C2
C3
C1
C2 C1 C1
C2 C1 C1
C2 C1 C1
C2 C1 C1
C2 C1 C1
C2 C1 C1
C2 C1 C1
C2 C1 C1
C2 C1 C1
C2 C1 C1
C2 C1 C1
DR
C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3
DQDPDNDMDLDKDJDHDGDFDDDCDBDA DEC4C1C1C2C2
C2C2C2
C2C2C2C2C1C1C2C2C2C2C2C2C2C2C2
P4
C4C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2C2C2C2C2C2C2
C4C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2C2C2C2C2C2C2
C4C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2C2C2C2C2C2C2
C4C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2C2C2C2C2C2C2
C4C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2C2C2C2C2C2C2
C4C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2C2C2C2C2C2C2
C4C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2C2C2C2C2C2C2
C4C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2C2C2C2C2C2C2
C4C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2C2C2C2C2C2C2
C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2
C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2
C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2
C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2
C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2
C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2
C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2
C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2
C1C1C2C2
C1C1C2C2
C1C1C2C2
C1C1C2C2
C1C1C2C2
C2
C2
C2
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C1C1
C1C1
C1C1
C1C1
C1C1
C1C1
C1C1
C1C1
C1C1
C1C1
C2C2C2C2C2C2
C2C2C2C2C2C2
C1C1
C2C2C2C2C2C2
C1C1
C2C2C2C2C2C2
C1C1
C2C2C2C2C2C2
C1C1
C2C2C2C2C2C2
C1C1
C2C2C2C2C2C2
C1C1
C2C2C2C2C2C2
C1C1
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C3 C3 C3 C3 C3C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
P5
P5
PIR
C1C1
PIR
PIRPIR
PIRPIR
PIRPIR
PIRPIR
PIRPIR
PIRPIR
PIRPIR
PIRPIR
PIRPIR
PIRPIR
PIRPIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
C3C3
C3C3
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
C2
C2
C2
C2
C2
C2
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C2
P3
P4
P4
C1
E1
LPC
29
E1
LPC
27
E1
LPC
29
E1
LPC
27
E1
LPC
29
E1
LPC
27
E1
LPB
1
EXIT
E1
LPB
1
E1
LPB
1
E1
LPB
1
E1
LPB
1
E1
LPB
2
E1
LPB
1
E1
LPB
2
E1
LPB
2
E1
LPB
2
E1
LPB
2
E1
LPB
2
E1
LPB
2
E1
LPB
2
E1
LPB
2
E1
HVP1
4
E1
HVP1
4
E1
HVP1
4
E1
HVP1
4
E1
HVP1
4
E1
HVP1
4
E1
HVP1
4
E1
HVP1
4
E1
HVP1
4
E1
LPC
4
E1
LPC
4
E1
LPC
5
E1
LPC
5
E1
LPC
4
E1
LPC
4
E1
LPC
4
E1
LPC
4
E1
LPC
5
E1
LPC
4
E1
LPC
4
E1
EM
8
NL
E1
LPC
5
E1
LPC
5
E1
LPC
4
E1
LPC
4
E1
LPC
4
E1
LPC
5
E1
LPC
5
E1
LPC
4
E1
LPC
4
E1
LPC
5
E1
LPC
7
E1
LPC
7
E1
LPC
5
E1
LPC
7
E1
LPC
7
E1
LPC
5
E1
LPC
5
E1
LPC
7
E1
LPC
7
E1
LPC
7
E1
LPC
7
E1
EM
8
NL
E1
LPC
5
E1
LPC
7
E1
LPC
7
E1
EM
8
NL
E1
LPC
7
E1
LPC
5
E1
LPC
7
E1
LPC
7
E1
LPC
9
E1
LPC
25
E1
LPC
25
E1
LPC
9
E1
LPC
25
E1
LPC
25
E1
LPC
25
E1
LPC
25
E1
LPC
9
E1
LPC
25
E1
LPC
25
E1
LPC
25
E1
EM
4
NL
E1
LPC
9
E1
LPC
9
E1
LPC
25
E1
LPC
25
E1
LPC
25
E1
LPC
25
E1
LPC
9
E1
LPC
9
E1
LPC
25
E1
LPC
25
E1
LPC
9
E1
HVP2
8
E1
HVP2
8
E1
HVP2
8
E1
HVP2
8
E1
HVP2
8
E1
HVP2
8
E1
LPC
6
E1
LPC
6
E1
LPC
6
E1
LPC
6
E1
LPC
6
E1
LPC
6
E1
LPC
6
E1
LPC
6
E1
LPC
6
E1
EM
4
NL
E1
EM
4
NL
E1
EM
2
NL
E1
EM
2
NL
E1
EM
2
NL
E1
EM
6
NL
E1
EM
6
NL
E1
EM
6
NL
E1
EM
4
NL
E1
EM
4
NL
E1
EM
2
NL
E1
EM
2
NL
E1
EM
2
NL
E1
EM
6
NL
E1
EM
6
NL
E1
EM
6
NL
E1
LPD
17
E1
LPD
19
E1
LPD
17
E1
LPD
19
E1
LPD
17
E1
LPD
19
E1
LPD
17
E1
LPD
19
E1
LPD
17
E1
LPD
19
E1
LPD
17
E1
LPD
19
E1
LPD
17
E1
LPD
19
E1
LPD
17
E1
LPD
19
E1
LPD
17
E1
LPD
19
E1
LPD
6
E1
LPD
2
E1
LPD
2
E1
LPD
6
E1
LPD
2
E1
LPD
2
E1
LPD
2
E1
LPD
2
E1
LPD
6
E1
LPD
6
E1
LPD
2
E1
LPD
2
E1
LPD
2
E1
LPD
2
E1
LPD
6
E1
LPD
6
E1
LPD
2
E1
LPD
2
E1
LPD
4
E1
LPD
4
E1
LPD
4
E1
LPD
4
E1
LPD
4
E1
LPD
4
E1
LPD
4
E1
LPD
4
E1
LPD
4
E1
LPD
4
E1
LPD
4
E1
LPD
4
E1
EM
6
NL
E1
EM
6
NL
E1
EM
6
NL
E1
EM
2
NL
E1
EM
2
NL
E1
EM
2
NL
E1
EM
4
NL
E1
EM
4
NL
E1
EM
4
NL
E1
EM
4
NL
E1
EM
4
NL
E1
EM
4
NL
E1
LPD
11
E1
LPD
11
E1
LPD
11
E1
LPD
11
E1
LPD
11
E1
LPD
11
E1
LPD
1
E1
LPD
1
E1
LPD
1
E1
LPD
1
E1
LPD
1
E1
LPD
1
E1
LPD
5
E1
LPD
5
E1
LPC
16
E1
LPC
14
E1
LPC
16
E1
LPC
14
E2
LPC
12
E2
LPC
10
E2
LPC
10
E2
LPC
12
E2
LPC
10
E2
LPC
12
E2
LPC
12
E2
LP
C
10
E2
LPC
14
E2
LPC
16
E2
LPC
14
E2
LPC
14
E2
LPC
16
E2
LPC
16
E2
LPC
14
E2
LPC
14
E2
LPC
16
E1
LPC
16
E1
LPC
14
E1
LPC
16
E1
LPC
14
E1
LPC
16
E1
LPC
16
E1
LPC
10
E1
LPC
12
E1
LPC
12
E1
LPC
10
E1
LPC
10
E1
LPC
12
E1
LPD
6
E1
LPD
6
E1
EM
4
NL
E1
HVP1
4
E1
EM
8
NL
E1
EM
8
NL
E1
EM
8
NL
E1
LPB
2
E1
LPB
2
E1
HVP1
4
E1
HVP1
4
E1
EM
4
NL
FU
SE
PN
LE
M
E3
FU
SE
PN
LE
M
E3
FU
SE
PN
LE
M
E3
FU
SE
PN
LE
M
E3
FU
SE
PN
LE
M
E3
FU
SE
PN
LE
M
E3
FU
SE
PN
LE
M
E3
FU
SE
PN
LE
M
E3
FU
SE
PN
LE
M
E3
FU
SE
PN
LE
M
E3
FU
SE
PN
LE
M
E3
FU
SE
PN
LE
M
E3
FU
SE
PN
LE
M
E3
FU
SE
PN
LE
M
E3
FU
SE
PN
LE
M
E3
FU
SE
PN
LE
M
E3
FU
SE
PN
LE
M
E3
FU
SE
PN
LE
M
E3
FUSE
PNL EM
E3
FUSE
PNL EM
E3
FU
SE
PN
LE
M
E3
EX
IT
EX
IT
EXIT EXIT
EXIT
EXIT
EXIT EXIT EXIT EXIT
EX
IT
EX
IT
EX
IT
EXIT
EXIT
EX
IT
EXIT EXIT
EXIT
EM-2
EXIT
EX
IT
EXIT
EXIT
EXIT
E4 E4 E4 E4 E3 E3 E3
J
EXIT
EX
IT
EX
IT
EXIT
DATE:
DRAWN BY:
CHECKED BY:
CEE PROJECT #:
Original drawings remain the property
of the Engineer and as such the
Engineer retains total ownership and
control. The design represented by
these drawings is sold to the client for
a one time use, unless otherwise
agreed upon in writing by the Engineer.
© Controlled Energy Engineers LLC 2017
654321
E
D
C
B
A
CONTROLLED ENERGY
ENGINEERS, LLC
2451 W BIRCHWOOD AVE, #104
MESA, AZ 85202
PHONE: 480.621.5933
Know what's below.before you dig.Call
1-800-782-5348
THIS DRAWING IS A COMPILATION BASED ON INFORMATION FROM, BUT NOT
LIMITED TO, DRAWINGS FROM PREVIOUS PROJECTS:
THIS DRAWING MUST BE FIELD VERIFIED BEFORE USE
DRAWING NOT TO SCALE UNLESS SCALE BAR IS PRESENT
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
# Date Revision
2/2/2017 3:58:55 P
M
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
PERMIT SET
# Date Revision
17002
ZEW
CEE
MAR 13, 2017
,
S
WILSTERMAN
E
n
r
e
ig
e
R
s
t
D
g
O
a
A
e
i
S
t
Z
I
R
e
A
n
N
d
.
U
ZANE E.
P
d
e
I
r
T
R
E
C
s
s
o
f
e
li
n
F
I
o
T
AC
a
E
l
A
.
.
)
e
.
ir
cal
c
t
E
(
O
i
N
g
e
r
e
n
39548
EXPIRES 09-30-2018
3-13-17
1 4-27-17 2ND CITY
SUBMITTAL
2 6-1-17 3RD CITY
SUBMITTAL
ELECTRICAL
BUILDING
PLAN
E110
N
0 2 1
SCALE 1/16" = 1'
1
GENERAL NOTES KEY NOTES
1
2
3
EXISTING TRANSFER SWITCH AND 480V PANEL "EM"
1
EXISTING 480V PANEL "LPF", 208V PANEL "RPE" AND TRANSFORMER
EXISTING STANDBY GENERATOR
3
2
A. CONTRACTOR SHALL SUBMIT AS-BUILT DRAWINGS TO ENGINEER AND OWNER.
B. REFER TO SHEET E100 FOR ADDITIONAL GENERAL NOTES.
C. REFER TO SHEET E100 FOR LUMINAIRE SCHEDULE.
D. REFER TO SHEETS E120 AND E121 FOR LEVEL 01 POWER AND LIGHTING PLANS.
E. REFER TO SHEETS E122, E123 AND E124 FOR RAIL DOCK, ACCESS CORRIDORS, AND
WAREHOUSE EXISTING LIGHTING PLAN AND MODIFICATIONS.
F. REFER TO SHEETS E130, E131, E132 AND E133 FOR LEVEL 02 POWER AND LIGHTING
PLANS.
G. REFER TO SHEETS E140 AND E141 FOR SINGLE LINE DIAGRAM.
H. REFER TO SHEETS E150 AND E151 FOR PANEL SCHEDULES.
LEVEL 01 EXISTING
ELECTRICAL EQUIPMENT
INDICATED ON THIS SHEET
2
REFER TO SHEET E122 FOR
RAIL DOCK, CORRIDOR AND
WAREHOUSE EXISTING
LIGHTING AND MODIFICATIONS
2
REFER TO SHEET E123 FOR
CORRIDOR AND WAREHOUSE
EXISTING LIGHTING AND
MODIFICATIONS
2
REFER TO SHEET E124 FOR
CORRIDOR AND WAREHOUSE
EXISTING LIGHTING AND
MODIFICATIONS
2
REFER TO SHEETS E120
AND E121 FOR LEVEL 01
OFFICE REMODEL LIGHTING
AND POWER PLANS
REFER TO SHEETS E130, E131,
E132, AND E133 FOR LEVEL 02
OFFICE REMODEL LIGHTING
AND POWER MODIFICATIONS
2
FR
ON
T
FR
ON
T
DATE:
DRAWN BY:
CHECKED BY:
CEE PROJECT #:
Original drawings remain the property
of the Engineer and as such the
Engineer retains total ownership and
control. The design represented by
these drawings is sold to the client for
a one time use, unless otherwise
agreed upon in writing by the Engineer.
© Controlled Energy Engineers LLC 2017
654321
E
D
C
B
A
CONTROLLED ENERGY
ENGINEERS, LLC
2451 W BIRCHWOOD AVE, #104
MESA, AZ 85202
PHONE: 480.621.5933
Know what's below.before you dig.Call
1-800-782-5348
THIS DRAWING IS A COMPILATION BASED ON INFORMATION FROM, BUT NOT
LIMITED TO, DRAWINGS FROM PREVIOUS PROJECTS:
THIS DRAWING MUST BE FIELD VERIFIED BEFORE USE
DRAWING NOT TO SCALE UNLESS SCALE BAR IS PRESENT
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
# Date Revision
2/2/2017 3:58:55 P
M
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
PERMIT SET
# Date Revision
17002
ZEW
CEE
MAR 13, 2017
,
S
WILSTERMAN
E
n
r
e
ig
e
R
s
t
D
g
O
a
A
e
i
S
t
Z
I
R
e
A
n
N
d
.
U
ZANE E.
P
d
e
I
r
T
R
E
C
s
s
o
f
e
li
n
F
I
o
T
AC
a
E
l
A
.
.
)
e
.
ir
cal
c
t
E
(
O
i
N
g
e
r
e
n
39548
EXPIRES 09-30-2018
3-13-17
1 4-27-17 2ND CITY
SUBMITTAL
2 6-1-17 3RD CITY
SUBMITTAL
3 7-12-17 RAIL DOCK
BATTERY
CHARGING
4 11-15-17 3000A SES
LEVEL 01
POWER
PLAN
E120
N
0 2 1
SCALE 1/4" = 1'
1
KEY NOTES
GENERAL NOTES
A. CONTRACTOR SHALL SUBMIT AS-BUILT DRAWINGS TO ENGINEER AND OWNER.
B. REFER TO SHEET E100 FOR ADDITIONAL GENERAL NOTES.
C. REFER TO SHEET E100 FOR LUMINAIRE SCHEDULE.
D. REFER TO SHEETS E120 AND E121 FOR OFFICE REMODEL LEVEL 01 POWER AND
LIGHTING PLANS.
E. REFER TO SHEETS E130, E131, E132 AND E133 FOR LEVEL 02 POWER AND LIGHTING
PLANS.
F. REFER TO SHEETS E140 AND E141 FOR SINGLE LINE DIAGRAM.
G. REFER TO SHEETS E150 AND E151 FOR PANEL SCHEDULES.
H. REFER TO SHEET E110 FOR PANEL LOCATIONS THAT MAY BE REFERRED TO ON THIS
SHEET BUT NOT INDICATED.
I. FURNISH AND INSTALL CONDUITS, FITTINGS, PULL BOXES, ETC. AS REQUIRED FOR
LIGHTING AND RECEPTACLE BRANCH CIRCUIT NUMBERS INDICATED. USE #12 AWG
CONDUCTORS WITH #12 AWG GROUND FOR 20A AND 15A CIRCUITS. USE #10 AWG
CONDUCTORS WITH #10 AWG GROUND FOR 30A CIRCUITS. DO NOT EXCEED SIX
CURRENT CARRYING CONDUCTORS PER CONDUIT.
J. CONDUITS SHALL BE CONCEALED WHERE POSSIBLE.
K. LIGHT SWITCHES SHALL BE FLUSH MOUNTED AT 42" ABOVE FINISHED FLOOR.
L. RECEPTACLES SHALL BE MOUNTED FLUSH MOUNTED AT 18" ABOVE FINISHED FLOOR.
1
2
3
4
5
6
7
8
EXISTING SERVICE ENTRANCE SECTION (NO MODIFICATION; FOR REFERENCE ONLY)
9
EXISTING UTILITY TRANSFORMER (NO MODIFICATION; FOR REFERENCE ONLY)
10
EXISTING SWBD "SWBA1" (NO MODIFICATION; FOR REFERENCE ONLY)
11
EXISTING SWBD "SWBA2" (NO MODIFICATION; FOR REFERENCE ONLY)
12
EXISTING SWBD "SWBB" (NO MODIFICATION; FOR REFERENCE ONLY)
13
14
EXISTING SWBD "TE" (NO MODIFICATION; FOR REFERENCE ONLY)
15
EXISTING MCCA (NO MODIFICATION; FOR REFERENCE ONLY)
16
EXISTING MCCB (NO MODIFICATION; FOR REFERENCE ONLY)
17
EXISTING MCCC (NO MODIFICATION; FOR REFERENCE ONLY)
18
EXISTING MCCD AND J-BOX (NO MODIFICATION; FOR REFERENCE ONLY)
19
EXISTING 480V PANEL LPA2 (REFER TO PANEL SCHEDULE FOR CHANGES)
20
EXISTING 208V PANEL RPA2 (REFER TO PANEL SCHEDULE FOR CHANGES)
EXISTING 208V PANEL RPA (REFER TO PANEL SCHEDULE FOR CHANGES)
EXISTING 208V PANEL RPAA (REFER TO PANEL SCHEDULE FOR CHANGES)
FC-1 (IU-1). INSTALL 240VAC, 30A FUSED DISCONNECT SWITCH. DISCONNECT SWITCH
ENCLOSURE SHALL HAVE TYPE 1 RATING. INSTALL FUSES SIZED PER HVAC MFR
RECOMMENDATIONS. INSTALL 2-#10, #10 GND, 3/4"C. CIRCUITED TO PANEL
RPA-16,18.
ROOF MOUNTED CU-1 (OU-1). INSTALL 240VAC, 60A FUSED DISCONNECT SWITCH.
DISCONNECT SWITCH ENCLOSURE SHALL HAVE TYPE 3R RATING. INSTALL FUSES
SIZED PER HVAC MFR RECOMMENDATIONS. INSTALL 2-#8, #10 GND, 3/4"C. CIRCUITED
TO PANEL RPA2-35,37.
FC-2 (IU-2). INSTALL 240VAC, 30A FUSED DISCONNECT SWITCH. DISCONNECT SWITCH
ENCLOSURE SHALL HAVE TYPE 1 RATING. INSTALL FUSES SIZED PER HVAC MFR
RECOMMENDATIONS. INSTALL 2-#10, #10 GND, 3/4"C. CIRCUITED TO PANEL
RPA2-26,28.
ROOF MOUNTED CU-2 (OU-2). INSTALL 240VAC, 60A FUSED DISCONNECT SWITCH.
DISCONNECT SWITCH ENCLOSURE SHALL HAVE TYPE 3R RATING. INSTALL FUSES
SIZED PER HVAC MFR RECOMMENDATIONS. INSTALL 2-#8, #10 GND, 3/4"C. CIRCUITED
TO PANEL RPA2-39,41.
ROOF MOUNTED EF-1. INSTALL 7-DAY PROGRAMMABLE WALL SWITCH IN SINGLE OR
DOUBLE GANG BOX.
HR
OFFICE
TRANSPORT
BREAK
ROOM
MENWOMEN
ROUTING &
BILLING
INVENTORY
HALL
WILL CALL &
RECIEVING
DRIVER
WAITING
DRIVERS
WAREHOUSE
ELEV.
STAIR 2
HALL
HALL
MAINTENANCE
SHOP
LOCKERS
STORAGE
ENGINE
ROOM
LOBBY /
RECEPTION
TOILET
J-BOX (E)
RP
A2-1
RP
A2-3
RP
A2-5
RP
A2-7
RPA2-9
RPA2-38
RPA2-9
RP
A2-9
RPA2-9
RPA-1
RPA2-11
RP
A2-11
RP
A2-11
RP
A2-38
RP
A2-38
RPA-7
RP
A-1
1
2
34 5 6
10
9 8 7
11 12 13 14
15
F
30A
F
30A
F
60A
F
60A
1917
1816
#
TC/P
#
TC/P
20 21
RPA2-16
RPA2-38RPA2-11
RPAA-14
RPAA-14
RPA2-9
RPA-7
RPA2-36
RPA2-34
RP
AA
-18
RP
AA
-18
RPAA-18
RP
AA
-18
RP
AA
-18
RPAA-18
HALL
RPAA-18
RP
A-7
RP
A-7
RP
AA
-18
RP
A-9
RP
A-9
RPA-7
RPA2-9
RP
A-1
RPA2-11
RPA2-11
RPA2-38
RPA2-38
RPA-1
RP
A2-9
RP
A2-9
RP
A2-9
RP
A2-9
RPAA-18
21
RPA2-16
21ROOF MOUNTED EF-2. INSTALL 7-DAY PROGRAMMABLE WALL SWITCH IN SINGLE OR
DOUBLE GANG BOX.
RPA2-19
GFCI
RP
A-15
F
RP
A-17
GF
CI
ELEVATOR SUMP
PUMP (SP-1)
GFCI
RPA-29
RECIRC PUMP
(RP-1) (RPA-30)
WATER HEATER
(WH-1) (RPA2-2,4)
22600V, 60A ELEVATOR MOTOR DISCONNECT SWITCH (LPA2-6,8,10). INSTALL 3-#4, #10
GND, 1¼"C. SIZE FUSES PER MFR REQ'TS.
22
23INSTALL FLUSH MOUNT J-BOX COVER AND CONDUIT IN WALL EXTENDING ABOVE
CEILING GRID FOR TV LOCATION.
J
23
J23
J23
23
J
LEVEL 01 OFFICE
AREA REMODEL
INDICATED
ON THIS SHEET
24MOUNTED ON ROOF NEXT TO AIR CONDITIONING UNIT.
GFCI
RPA2-24
24
1
SHADED AREA(S) REPRESENT
AREA(S) BEING REMODELED
ON THIS SHEET
EXISTING BUILDING
FOOTPRINT
F
25
25INSTALL 250V, 30A, 2P FUSED DISCONNECT SWITCH IN MECHANICAL SPACE FOR
ELEVATOR CAR LIGHTS (RPA-3). INSTALL 15A FUSES.
4
REFER TO SHEET
E150, 480 PANEL
LPA2, CKT 6,8,10 FOR
ADDITIONAL INFO
FOR ELEVATOR PUMP
4
4BEING DEMOLISHED
BEING DEMOLISHED
INSTALL NEW
TRANSFORMER PAD PER
SRP REQUIREMENTS
EXISTING PRIMARY CONDUIT
VAULT FOR SECONDARY
CONDUITS PER SRP REQ'TS
EXISTING 480V PANEL LPA TO BE REPLACED WITH NEW (REFER TO PANEL SCHEDULE
AND SINGLE LINE DIAGRAM)
4
26COORDINATE WITH SRP FOR DISCONTINUANCE OF POWER AND REMOVAL OF SRP
PRIMARY CONDUCTORS AND TRANSFORMER.
27CUT EXISTING 4" PRIMARY CONDUIT AND EXTEND TO NEW TRANSFORMER.
26
27
EXISTING PLATFORM
AND CONCRETE PAD
286" CONCRETE PAD
29SHEARED WELDED STEEL WIRE REMESH. SUPPORT IN PLACE WITH DOBIE BLOCKS.
28
29
5'
3'
G
GG
GG
GG
GG
GG
GG
GG
G
G G
G G
30INSTALL 10'X3/4" Cu-CLAD GROUND ROD AND 8"-DIA WELL WITH COVER.
30
30
G
31INSTALL #4/0 BARE Cu GROUNDING ELECTRODE CONDUCTOR (GEC) AT 30" MINIMUM
DEPTH. EXOTHERMICALLY WELD (OR NON-REVERSIBLE CRIMP) TO GROUND RODS.
31
32BOND #4/0 BARE Cu CONDUCTOR TO GROUND RING VIA EXOTHERMICALLY WELD (OR
NON-REVERSIBLE CRIMP) AND EXTEND TO SWGR GROUND BUS (SWGR-SES /
SWGR-MDP). INSTALL CONDUCTOR AT 30" MINIMUM DEPTH.
33BOND #4/0 BARE Cu CONDUCTOR TO GROUND RING VIA EXOTHERMICALLY WELD (OR
NON-REVERSIBLE CRIMP) AND EXTEND TO EXISTING GROUNDING SYSTEM. INSTALL
CONDUCTOR AT 30" MINIMUM DEPTH.
31
31
32
32
33
KEY NOTES
34 SWGR-SES (NEW)
35 SWGR-MDP (NEW)
34
35
36 INSTALL SECONDARY CONDUITS PER SRP REQ'TS (19-4"C PER TABLE 1,
PAGE 6-1)
36
37 INSTALL CONDUIT AND CONDUCTORS BETWEEN SWGR-SES AND
SWGR-MDP PER SINGLE LINE DIAGRAM.
38 INSTALL CONDUIT AND CONDUCTORS BETWEEN SWGR-SES AND
EXISTING FIRE PUMP CONTROLLER PER SINGLE LINE DIAGRAM
(APPROX 300-LF TO SOUTH).
38
37
EXISTING FIRE PUMP BUILDING
4
DATE:
DRAWN BY:
CHECKED BY:
CEE PROJECT #:
Original drawings remain the property
of the Engineer and as such the
Engineer retains total ownership and
control. The design represented by
these drawings is sold to the client for
a one time use, unless otherwise
agreed upon in writing by the Engineer.
© Controlled Energy Engineers LLC 2017
654321
E
D
C
B
A
CONTROLLED ENERGY
ENGINEERS, LLC
2451 W BIRCHWOOD AVE, #104
MESA, AZ 85202
PHONE: 480.621.5933
Know what's below.before you dig.Call
1-800-782-5348
THIS DRAWING IS A COMPILATION BASED ON INFORMATION FROM, BUT NOT
LIMITED TO, DRAWINGS FROM PREVIOUS PROJECTS:
THIS DRAWING MUST BE FIELD VERIFIED BEFORE USE
DRAWING NOT TO SCALE UNLESS SCALE BAR IS PRESENT
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
# Date Revision
2/2/2017 3:58:55 P
M
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
PERMIT SET
# Date Revision
17002
ZEW
CEE
MAR 13, 2017
,
S
WILSTERMAN
E
n
r
e
ig
e
R
s
t
D
g
O
a
A
e
i
S
t
Z
I
R
e
A
n
N
d
.
U
ZANE E.
P
d
e
I
r
T
R
E
C
s
s
o
f
e
li
n
F
I
o
T
AC
a
E
l
A
.
.
)
e
.
ir
cal
c
t
E
(
O
i
N
g
e
r
e
n
39548
EXPIRES 09-30-2018
3-13-17
1 4-27-17 2ND CITY
SUBMITTAL
2 6-1-17 3RD CITY
SUBMITTAL
LEVEL 01
LIGHTING
PLAN
E121
N
0 1 2
SCALE 1/4" = 1'
2
KEY NOTES
GENERAL NOTES
A. CONTRACTOR SHALL SUBMIT AS-BUILT DRAWINGS TO ENGINEER AND OWNER.
B. REFER TO SHEET E100 FOR ADDITIONAL GENERAL NOTES.
C. REFER TO SHEET E100 FOR LUMINAIRE SCHEDULE.
D. REFER TO SHEETS E120 AND E121 FOR LEVEL 01 OFFICE REMODEL POWER AND
LIGHTING PLANS.
E. REFER TO SHEETS E122, E123 AND E124 FOR LEVEL 01 DOCK AND WAREHOUSE LIGHTING
PLANS.
F. REFER TO SHEETS E130, E131, E132 AND E133 FOR LEVEL 02 POWER AND LIGHTING
PLANS.
G. REFER TO SHEETS E140 AND E141 FOR SINGLE LINE DIAGRAM.
H. REFER TO SHEETS E150 AND E151 FOR PANEL SCHEDULES.
I. REFER TO SHEET E110 FOR PANEL LOCATIONS THAT MAY BE REFERRED TO ON THIS
SHEET BUT NOT INDICATED.
J. FURNISH AND INSTALL CONDUITS, FITTINGS, PULL BOXES, ETC. AS REQUIRED FOR
LIGHTING AND RECEPTACLE BRANCH CIRCUIT NUMBERS INDICATED. USE #12 AWG
CONDUCTORS WITH #12 AWG GROUND FOR 20A AND 15A CIRCUITS. USE #10 AWG
CONDUCTORS WITH #10 AWG GROUND FOR 30A CIRCUITS. DO NOT EXCEED SIX
CURRENT CARRYING CONDUCTORS PER CONDUIT.
K. CONDUITS SHALL BE CONCEALED WHERE POSSIBLE.
L. LIGHT SWITCHES SHALL BE FLUSH MOUNTED AT 42" ABOVE FINISHED FLOOR.
M. RECEPTACLES SHALL BE MOUNTED FLUSH MOUNTED AT 18" ABOVE FINISHED FLOOR.
1 EXISTING 480V PANEL LPA
2 EXISTING 480V PANEL LPA2
HR
OFFICE
TRANSPORT
BREAK
ROOM
MEN
WOMEN
ROUTING &
BILLING
INVENTORY
HALL
DRIVER
WAITING
WAREHOUSE
ELEV.
STAIR 2
HALL
HALL
MAINTENANCE
SHOP
STORAGE
LOBBY /
RECEPTION
TOILET
1
MO
B
LPA-19BP
2
C
LP
A-21
3
3
MO
4
MO
5
MO
A
LPA-23
6
B
LPA-19BP
6
A
LPA-23
6
A
LPA-23
6
A
LPA-23
6
B
LPA-19BP
6
A
LPA-23
8
A
LPA-23
8
A
LPA-23
7
A
LPA-23
7
7
MO
8
MO
A
LP
A-23
12
9
MO
10
MO
12
MO
13
MO
14
MO
ENGINE
ROOM
208V PANEL RPAA
PS
PS
2 1
OS
6
OS
6
OS
2
OS
2
A
LP
A-23
12
WILL CALL &
RECIEVING
DRIVERS
OFFICE
HALL
A
LPA-21
2
11
MO
1
LPA-21
D
1
LPA-21
D
13
LPA-23
D
14
LPA-23
E
14
LPA-23
E
13
LPA-23
D
12
MO
H
16
LPA-7
16
15
LP
A-1
9
EX
IT
LP
A-1
9
EX
IT
LPA-19
EXIT
LPA-19
EXIT
15
LP
A-7
G
LEVEL 01 OFFICE
AREA REMODEL
INDICATED
ON THIS SHEET
SHADED AREA(S) REPRESENT
AREA(S) BEING REMODELED
ON THIS SHEET
EXISTING BUILDING FOOTPRINT
A
LPA-23
2
A
LPA-23
2
A
LP
A-21
11
A
LP
A-21
11
A
LPA-21
2
A
LP
A-23
11
B
LPA-19BP
2
A
LPA-21
2
A
LPA-21
2
C
LPA-21
4
C
LP
A-21
5
A
LPA-21
2
A
LPA-21
2
C
LP
A-21
5
A
LPA-21
2
A
LP
A-23
12
C3
C3
C3
C3
C3
C3
C3
C3
DG
DF
DD
DC
DB
DA
DE
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
P4
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C2
C2
C2
C1
C2
C2
C2
C1
C2
C2
C2
C1
C2
C2
C2
C1
C2
C2
C2
C1
C2
C2
C2
C1
C2
C2
C2
C1
C2
C2
C2
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C1
C2
C2
C2
C2
C2
C2
C1
C1
C2
C2
C2
C2
C2
C2
C1
C1
C2
C2
C2
C2
C2
C2
C1
C1
C2
C2
C2
C2
C2
C2
C1
C1
C2
C2
C2
C2
C2
C2
C1
C1
C2
C2
C2
C2
C2
C2
C1
C1
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C1
C1
C3
C3
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
E1
LP
C
29
E1
LP
C
27
E1
LP
C
29
E1
LP
C
27
E1
LP
C
29
E1
LP
C
27
E1
LP
B
1
HVP3-1,3,5
L16-20R
HV
P3-7,9,11
L16-20R
HV
P3-8,10,12
L16-20R
HV
P3-13,15,17
L16-20R
HV
P3-14,16,18
L16-20R
HV
P3-19,21,23
L16-30R
HV
P3-20,22,24
L16-30R
E1
LP
B
1
E1
LP
B
1
E1
LP
B
1
E1
LP
B
1
E1
LP
B
2
E1
LP
B
1
E1
LP
B
2
E1
LP
B
2
E1
LP
B
2
E1
LP
B
2
E1
LP
B
2
E1
LP
B
2
E1
LP
B
2
E1
LP
B
2
E1
HV
P1
4
E1
HV
P1
4
E1
HV
P1
4
E1
HV
P1
4
E1
HV
P1
4
E1
HV
P1
4
E1
HV
P1
4
E1
HV
P1
4
E1
HV
P1
4
E1
LP
C
4
E1
LP
C
4
E1
LP
C
4
E1
LP
C
4
E1
LP
C
4
E1
LP
C
4
E1
LP
C
4
E1
LP
C
4
E1
EM
8NL
E1
LP
C
4
E1
LP
C
4
E1
LP
C
4
E1
LP
C
4
E1
LP
C
4
E2
LP
C
12
E2
LP
C
10
E2
LP
C
10
E2
LP
C
12
E2
LP
C
10
E2
LP
C
12
E2
LP
C
12
E2
LPC
10
E1
LP
C
12
E1
LP
C
10
E1
LP
C
10
E1
LP
C
12
E1
HV
P1
4
E1
EM
8NL
E1
EM
8NL
E1
EM
8NL
E1
LP
B
2
E1
LP
B
2
E1
HV
P1
4
E1
HV
P1
4
FUSE
PNL EM
E3
FUSE
PNL EM
E3
FUSE
PNL EM
E3
FUSE
PNL EM
E3
EXIT
EXIT
EX
IT
EX
IT
EX
IT
EXIT
EX
IT
EX
IT
HVP3-2,4,6
L16-20R
E4
E4
E4
E4
J
EX
IT
EX
IT
DATE:
DRAWN BY:
CHECKED BY:
CEE PROJECT #:
Original drawings remain the property
of the Engineer and as such the
Engineer retains total ownership and
control. The design represented by
these drawings is sold to the client for
a one time use, unless otherwise
agreed upon in writing by the Engineer.
© Controlled Energy Engineers LLC 2017
654321
E
D
C
B
A
CONTROLLED ENERGY
ENGINEERS, LLC
2451 W BIRCHWOOD AVE, #104
MESA, AZ 85202
PHONE: 480.621.5933
Know what's below.before you dig.Call
1-800-782-5348
THIS DRAWING IS A COMPILATION BASED ON INFORMATION FROM, BUT NOT
LIMITED TO, DRAWINGS FROM PREVIOUS PROJECTS:
THIS DRAWING MUST BE FIELD VERIFIED BEFORE USE
DRAWING NOT TO SCALE UNLESS SCALE BAR IS PRESENT
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
# Date Revision
2/2/2017 3:58:55 P
M
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
PERMIT SET
# Date Revision
17002
ZEW
CEE
MAR 13, 2017
,
S
WILSTERMAN
E
n
r
e
ig
e
R
s
t
D
g
O
a
A
e
i
S
t
Z
I
R
e
A
n
N
d
.
U
ZANE E.
P
d
e
I
r
T
R
E
C
s
s
o
f
e
li
n
F
I
o
T
AC
a
E
l
A
.
.
)
e
.
ir
cal
c
t
E
(
O
i
N
g
e
r
e
n
39548
EXPIRES 09-30-2018
3-13-17
1 4-27-17 2ND CITY
SUBMITTAL
2 6-1-17 3RD CITY
SUBMITTAL
3 7-12-17 RAIL DOCK
BATTERY
CHARGING
WAREHOUSE
LEVEL 01
LIGHTING
PLAN - 1
E122
N
1" 2" 3"
SCALE 1/8" = 1'
0
GENERAL NOTES KEY NOTES
1
2
3
4
1
2
5
6
3
7
8
9
10
11
12
13
14
15
16
17
A. CONTRACTOR SHALL SUBMIT AS-BUILT DRAWINGS TO ENGINEER AND OWNER.
B. REFER TO SHEET E100 FOR ADDITIONAL GENERAL NOTES.
C. REFER TO SHEET E100 FOR LUMINAIRE SCHEDULE.
D. REFER TO SHEETS E120 AND E121 FOR LEVEL 01 POWER AND LIGHTING PLANS.
E. REFER TO SHEETS E130, E131, E132 AND E133 FOR LEVEL 02 POWER AND LIGHTING
PLANS.
F. REFER TO SHEETS E140 AND E141 FOR SINGLE LINE DIAGRAM.
G. REFER TO SHEETS E150 AND E151 FOR PANEL SCHEDULES.
H. REFER TO SHEET E160 FOR CONTROL SCHEMATICS.
LEVEL 01 EXISTING
ELECTRICAL EQUIPMENT
INDICATED ON THIS SHEET
4
REFER TO SHEET E123 FOR CONTINUATION
ACCESS
CORRIDOR
DRY
WAREHOUSE
BATTERY
CHARGING ROOM
(RAIL DOCK)
COLD
DOCK
EXISTING 480V PANEL "LPB", 208V PANEL "RPB1" AND TRANSFORMER
EXISTING 480V PANEL "HVP1", 208V PANEL "LVP1" AND TRANSFORMER
EXISTING 480V DISCONNECT SWITCH, 208V PANEL "LVP3" AND TRANSFORMER
EXISTING 240V PANEL "LVP4" AND TRANSFORMER
INSTALL NEW 480V PANEL HVP3 NEXT TO EXISTING 208V PANEL LVP3. INSTALL FEEDER
CONDUIT AND CONDUCTORS PER SINGLE LINE DIAGRAM. INSTALL JUNCTION BOX(ES)
AS NECESSARY TO FACILITATE CONDUCTOR PULL AND NOT EXCEED 360° ALLOWABLE
BENDS.
INSTALL L16-20R RECEPTACLE IN BOX. EXTEND 3-#12, #12 GND, 3/4"C TO CONTACTOR
CONTROL PANEL.
INSTALL L16-30R RECEPTACLE IN BOX. EXTEND 3-#10, #10 GND, 3/4"C TO CONTACTOR
CONTROL PANEL.
INSTALL NEW EXIT LIGHT. INSTALL 2-#12, #12 GND, 1/2"C TO NEAREST EMERGENCY CKT
FROM 480V PANEL EM.
EXISTING EXIT LIGHT
EXISTING EMERGENCY LIGHT WITH BATTERY PACK
EXISTING EMERGENCY FLOOD LIGHT ON STANDBY POWER; CONNECTED TO FUSE
PANEL.
EXISTING EMERGENCY FLUORESCENT LUMINAIRE ON STANDBY POWER; CONNECTED
TO FUSE PANEL.
EXISTING LUMINAIRE TO REMAIN. WHERE INDICATED BY "NL", NIGHT LIGHT CIRCUIT
WILL REMAIN ENERGIZED AT ALL TIMES (UTILITY POWER AND GENERATOR VIA 480V
PANEL EM WHEN UTILITY POWER IS LOST).
EXISTING LUMINAIRE TO BE RELOCATED TO ALIGN WITH STORAGE RACK ISLES.
WHERE INDICATED BY "NL", NIGHT LIGHT CIRCUIT WILL REMAIN ENERGIZED AT ALL
TIMES (UTILITY POWER AND GENERATOR VIA 480V PANEL EM WHEN UTILITY POWER IS
LOST).
RE-CIRCUIT LUMINAIRE TO OPERATE ON CIRCUIT EM-8.
REPLACE EMERGENCY LUMINAIRE WITH NEW. REFER TO SHEET E100 FOR ADDITIONAL
REQUIREMENTS.
INSTALL 8"X4' LUMINAIRE WITH 1½ HOUR BATTERY PACK ON ALL STAIR LANDINGS.
6666
17
17
5
12
1212121212
9
8
8
6
6
8
8
7
8
8
12
12
12 12
12
12
12
12
12
11
11
12
12
12 14
12
12
12
1212
1212
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12 12 12
8
11
11
12
12
13 13 13 13 13
1313
13 1313
13
1313
13
13
13
13
13
13 13 13 13
1313
9
10
10
16
8
16
18
INSTALL 600VAC, 30A FUSED DISCONNECT SWITCH FOR TRASH COMPACTOR.
DISCONNECT SWITCH ENCLOSURE SHALL HAVE TYPE 1 RATING. INSTALL FUSES SIZED
PER TRASH COMPACTOR MFR RECOMMENDATIONS. INSTALL 3-#12, #12 GND, 3/4"C
(FROM 480V PANEL HPV3, CIRCUIT 25,27,29).
9
7
15
18
19
INSTALL COMBINATION MOTOR STARTER FOR EXHAUST FAN EF-6. MOTOR STARTER
ENCLOSURE SHALL HAVE TYPE 1 RATING. INSTALL 3-#12, #12 GND, 3/4"C (FROM 480V
PANEL HPV3, CIRCUIT 31,33,35). REFER TO MOTOR CONTROL SCHEMATIC ON SHEET
E160.
20 19
20
CONTACTOR CONTROL PANEL. CONTACTOR CONTROL PANEL ENCLOSURE SHALL
HAVE TYPE 1 RATING. INSTALL 24-#12, #12 GND IN 1-1/4" NIPPLE BETWEEN CONTROL
PANEL AND 480V PANEL HVP3. REFER TO CONTACTOR CONTROL SCHEMATIC ON
SHEET E160.
RAIL DOCK
3
AFS
21
21
AIR FLOW SWITCH PER MECHANICAL PLANS. INSTALL 2-#14, #14 GND, 3/4"C BETWEEN
FLOW SWITCH AND EXHAUST FAN STARTER.
3
3
3
3
22
INSTANT WATER HEATER FOR EYEWASH (IWH-1). INSTALL 3-#3/0, #6 GND, 2"C (FROM
480V PANEL HPV3, CIRCUIT 26,28,30).
22
23
EXHAUST FAN EF-6. INSTALL 3-#12, #12 GND, 3/4"C BETWEEN EXHAUST FAN EF-6
STARTER AND EXHAUST FAN EF-6.
3
23
RB
RC
RD
RE
C1
C1
C1
C2
C2
C2
C2
C2
C2
C1
C2
C2
C1
C2
C2
C1
C2
C2
C1
C2
C2
C1
C2
C2
C1
C2
C2
C1
C1
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
C3
C3
C3
DR
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
DQ
DP
DN
DM
DL
DK
DJ
DH
C4
C1
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C1
C4
C1
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C1
C4
C1
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C1
C4
C1
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C1
C4
C1
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C1
C4
C1
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C1
C4
C1
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C1
C4
C1
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C1
C4
C1
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C1
C4
C1
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C1
C1
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C1
C1
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C1
C1
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C1
C1
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C1
C1
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C1
C1
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C1
C1
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C1
C1
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C1
C1
C1
C2
C2
C1
C1
C2
C2
C1
C1
C2
C2
C1
C1
C2
C2
C1
C1
C2
C2
C2
C2
C2
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C3
C3
C3
C3
C3
C3
C3
C3
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
C2
C2
C2
C2
C2
C2
C3
C3
C3
P3
EX
IT
E1
LP
C
5
E1
LP
C
5
E1
LP
C
5
E1
LP
C
5
E1
LP
C
5
E1
LP
C
5
E1
LP
C
5
E1
LP
C
5
E1
LP
C
7
E1
LP
C
7
E1
LP
C
5
E1
LP
C
7
E1
LP
C
7
E1
LP
C
5
E1
LP
C
5
E1
LP
C
7
E1
LP
C
7
E1
LP
C
7
E1
LP
C
7
E1
EM
8NL
E1
LP
C
5
E1
LP
C
7
E1
LP
C
7
E1
EM
8NL
E1
LP
C
7
E1
LP
C
5
E1
LP
C
7
E1
LP
C
7
E1
LP
C
9
E1
LP
C
25
E1
LP
C
25
E1
LP
C
9
E1
LP
C
25
E1
LP
C
25
E1
LP
C
25
E1
LP
C
25
E1
LP
C
9
E1
LP
C
25
E1
LP
C
25
E1
LP
C
25
E1
EM
4NL
E1
LP
C
9
E1
LP
C
9
E1
LP
C
25
E1
LP
C
25
E1
LP
C
25
E1
LP
C
25
E1
LP
C
9
E1
LP
C
9
E1
LP
C
25
E1
LP
C
25
E1
LP
C
9
E1
HV
P2
8
E1
HV
P2
8
E1
HV
P2
8
E1
HV
P2
8
E1
HV
P2
8
E1
HV
P2
8
E1
LP
C
6
E1
LP
C
6
E1
LP
C
6
E1
LP
C
6
E1
LP
C
6
E1
LP
C
6
E1
LP
C
6
E1
LP
C
6
E1
LP
C
6
E1
LP
C
16
E1
LP
C
14
E1
LP
C
16
E1
LP
C
14
E2
LP
C
14
E2
LP
C
16
E2
LP
C
14
E2
LP
C
14
E2
LP
C
16
E2
LP
C
16
E2
LP
C
14
E2
LP
C
14
E2
LP
C
16
E1
LP
C
16
E1
LP
C
14
E1
LP
C
16
E1
LP
C
14
E1
LP
C
16
E1
LP
C
16
E1
LP
C
10
E1
LP
C
12
E1
EM
4NL
E1
EM
4NL
FUSE
PNL EM
E3
FUSE
PNL EM
E3
FUSE
PNL EM
E3
FUSE
PNL EM
E3
FUSE
PNL EM
E3
FUSE
PNL EM
E3
FUSE
PNL EM
E3
FUSE
PNL EM
E3
FUSE
PNL EM
E3
FUSE
PNL EM
E3
FUSE
PNL EM
E3
FUSE
PNL EM
E3
FUSE
PNL EM
E3
FUSE
PNL EM
E3
FU
SE
PN
LE
M
E3
FU
SE
PN
LE
M
E3
FUSE
PNL EM
E3
EX
IT
EX
IT
EX
IT
EXIT
EX
IT
EX
IT
EX
IT
E3
E3
E3
EXIT
EXIT
DATE:
DRAWN BY:
CHECKED BY:
CEE PROJECT #:
Original drawings remain the property
of the Engineer and as such the
Engineer retains total ownership and
control. The design represented by
these drawings is sold to the client for
a one time use, unless otherwise
agreed upon in writing by the Engineer.
© Controlled Energy Engineers LLC 2017
654321
E
D
C
B
A
CONTROLLED ENERGY
ENGINEERS, LLC
2451 W BIRCHWOOD AVE, #104
MESA, AZ 85202
PHONE: 480.621.5933
Know what's below.before you dig.Call
1-800-782-5348
THIS DRAWING IS A COMPILATION BASED ON INFORMATION FROM, BUT NOT
LIMITED TO, DRAWINGS FROM PREVIOUS PROJECTS:
THIS DRAWING MUST BE FIELD VERIFIED BEFORE USE
DRAWING NOT TO SCALE UNLESS SCALE BAR IS PRESENT
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
# Date Revision
2/2/2017 3:58:55 P
M
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
PERMIT SET
# Date Revision
17002
ZEW
CEE
MAR 13, 2017
,
S
WILSTERMAN
E
n
r
e
ig
e
R
s
t
D
g
O
a
A
e
i
S
t
Z
I
R
e
A
n
N
d
.
U
ZANE E.
P
d
e
I
r
T
R
E
C
s
s
o
f
e
li
n
F
I
o
T
AC
a
E
l
A
.
.
)
e
.
ir
cal
c
t
E
(
O
i
N
g
e
r
e
n
39548
EXPIRES 09-30-2018
3-13-17
1 4-27-17 2ND CITY
SUBMITTAL
2 6-1-17 3RD CITY
SUBMITTAL
WAREHOUSE
LEVEL 01
LIGHTING
PLAN - 2
E123
N
1" 2" 3"
SCALE 1/8" = 1'
0
GENERAL NOTES KEY NOTES
1
2
3
4
5
6
7
8
9
10
A. CONTRACTOR SHALL SUBMIT AS-BUILT DRAWINGS TO ENGINEER AND OWNER.
B. REFER TO SHEET E100 FOR ADDITIONAL GENERAL NOTES.
C. REFER TO SHEET E100 FOR LUMINAIRE SCHEDULE.
D. REFER TO SHEETS E120 AND E121 FOR LEVEL 01 POWER AND LIGHTING PLANS.
E. REFER TO SHEETS E130, E131, E132 AND E133 FOR LEVEL 02 POWER AND LIGHTING
PLANS.
F. REFER TO SHEETS E140 AND E141 FOR SINGLE LINE DIAGRAM.
G. REFER TO SHEETS E150 AND E151 FOR PANEL SCHEDULES.
LEVEL 01 EXISTING
ELECTRICAL EQUIPMENT
INDICATED ON THIS SHEET
1
2
REFER TO SHEET E124 FOR CONTINUATION
REFER TO SHEET E122 FOR CONTINUATION
3
DRY
WAREHOUSE
COOLER COOLER
COLD
DOCK
ACCESS
CORRIDOR
EXISTING 480V PANEL "LPC", 480V PANEL LPCA, 208V PANEL "RPB" AND TRANSFORMER
EXISTING 480V PANEL "HVP2", 208V PANEL "LVP2" AND TRANSFORMER
EXISTING IDF #2
INSTALL 8"X4' LUMINAIRE WITH 1½ HOUR BATTERY PACK ON ALL STAIR LANDINGS.
INSTALL NEW EXIT LIGHT. INSTALL 2-#12, #12 GND, 1/2"C TO NEAREST EMERGENCY CKT
FROM 480V PANEL EM.
EXISTING EXIT LIGHT
EXISTING EMERGENCY LIGHT WITH BATTERY PACK
RE-CIRCUIT LUMINAIRE TO OPERATE ON CIRCUIT EM-8.
RELOCATE EXISTING EMERGENCY LIGHT WITH BATTERY PACK.
11
12
13
EXISTING EMERGENCY FLOOD LIGHT ON STANDBY POWER; CONNECTED TO FUSE
PANEL.
EXISTING EMERGENCY FLUORESCENT LUMINAIRE ON STANDBY POWER; CONNECTED
TO FUSE PANEL.
EXISTING LUMINAIRE TO REMAIN. WHERE INDICATED BY "NL", NIGHT LIGHT CIRCUIT
WILL REMAIN ENERGIZED AT ALL TIMES (UTILITY POWER AND GENERATOR VIA 480V
PANEL EM WHEN UTILITY POWER IS LOST).
EXISTING LUMINAIRE TO BE RELOCATED TO ALIGN WITH STORAGE RACK ISLES.
WHERE INDICATED BY "NL", NIGHT LIGHT CIRCUIT WILL REMAIN ENERGIZED AT ALL
TIMES (UTILITY POWER AND GENERATOR VIA 480V PANEL EM WHEN UTILITY POWER IS
LOST).
4 4
5
6
6
4 4
5
5
7
7
12
12
12
11
12
12
12
12
11
12
12
11
12
13
12
12
1212
1212
12 12
12
12
12 12
12
1212
12 12 12
121212
12 12 12 12
12 12 12
12 12 12
12 12 12 12 12
121212
1212 12
121212
12 1212
11
11
11
11
11
11
11
11
11
11
11
8
8
13
7
13
13
13
5
7
13 13 13
13
13
55
5
5
12
12
12
1212
12 12
121212
12
1212
12 12
9
129
12
12
12
12
12
12
8
8
10
2
11
11
11
12
12
12
C2
C1
C3
C3
P5
P5
P5
P5
P5
P5
P5
P5
P5
P5
P5
P5
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P5
P5
P5
P5
P5
P5
P5
P5
P5
P5
P5
P5
P5
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
FA
FB
FC
FD
FE
FF
C2
C2
C2
C2
C2
C2
C2
C2
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C2
C2
C2
C3
C4
C1
C2
C2
C2
C3
C4
C1
C2
C2
C2
C3
C4
C1
C2
C2
C2
C3
C4
C1
C4
C2
C2
C2
C3
C4
C1
C2
C2
C2
C3
C4
C1
C2
C2
C2
C3
C4
C1
C2
C2
C2
C3
C4
C1
C2
C2
C2
C3
C4
C1
C2
C2
C2
C3
C4
C1
C2
C2
C2
C3
C4
C1
C4
C4
C2
C2
C2
C3
C1
C4
C4
C2
C2
C2
C3
C1
C4
C2
C2
C2
C3
C1
C4
C2
C2
C2
C3
C1
C4
C2
C2
C2
C3
C1
C4
C2
C2
C2
C3
C1
C4
C2
C2
C2
C3
C1
C4
C2
C2
C2
C3
C1
C4
C2
C2
C2
C3
C1
C4
C2
C2
C2
C3
C1
C4
C4
C4
RA
RF
C2
C1
C2
C1
C2
C1
C2
C1
C2
C1
C2
C1
C2
C1
C2
C1
C2
C1
C2
C3
C1
C2
C1
C1
C2
C1
C1
C2
C1
C1
C2
C1
C1
C2
C1
C1
C2
C1
C1
C2
C1
C1
C2
C1
C1
C2
C1
C1
C2
C1
C1
C2
C1
C1
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
P5
P5
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C2
P4
P4
C1
E1
EM
4NL
E1
EM
4NL
E1
EM
2NL
E1
EM
2NL
E1
EM
2NL
E1
EM
6NL
E1
EM
6NL
E1
EM
6NL
E1
EM
4NL
E1
EM
4NL
E1
EM
2NL
E1
EM
2NL
E1
EM
2NL
E1
EM
6NL
E1
EM
6NL
E1
EM
6NL
E1
LP
D
17
E1
LP
D
19
E1
LP
D
17
E1
LP
D
19
E1
LP
D
17
E1
LP
D
19
E1
LP
D
17
E1
LP
D
19
E1
LP
D
17
E1
LP
D
19
E1
LP
D
17
E1
LP
D
19
E1
LP
D
17
E1
LP
D
19
E1
LP
D
17
E1
LP
D
19
E1
LP
D
17
E1
LP
D
19
E1
LP
D
6
E1
LP
D
2
E1
LP
D
2
E1
LP
D
6
E1
LP
D
2
E1
LP
D
2
E1
LP
D
2
E1
LP
D
2
E1
LP
D
6
E1
LP
D
6
E1
LP
D
2
E1
LP
D
2
E1
LP
D
2
E1
LP
D
2
E1
LP
D
6
E1
LP
D
6
E1
LP
D
2
E1
LP
D
2
E1
LP
D
4
E1
LP
D
4
E1
LP
D
4
E1
LP
D
4
E1
LP
D
4
E1
LP
D
4
E1
LP
D
4
E1
LP
D
4
E1
LP
D
4
E1
LP
D
4
E1
LP
D
4
E1
LP
D
4
E1
EM
6NL
E1
EM
6NL
E1
EM
6NL
E1
EM
2NL
E1
EM
2NL
E1
EM
2NL
E1
EM
4NL
E1
EM
4NL
E1
EM
4NL
E1
EM
4NL
E1
EM
4NL
E1
EM
4NL
E1
LP
D
11
E1
LP
D
11
E1
LP
D
11
E1
LP
D
11
E1
LP
D
11
E1
LP
D
11
E1
LP
D
1
E1
LP
D
1
E1
LP
D
1
E1
LP
D
1
E1
LP
D
1
E1
LP
D
1
E1
LP
D
5
E1
LP
D
5
E1
LP
D
6
E1
LP
D
6
EX
IT
EX
IT
EXIT
EXIT
EX
IT
EX
IT
EM
-2
EX
IT
EXIT
EX
IT
DATE:
DRAWN BY:
CHECKED BY:
CEE PROJECT #:
Original drawings remain the property
of the Engineer and as such the
Engineer retains total ownership and
control. The design represented by
these drawings is sold to the client for
a one time use, unless otherwise
agreed upon in writing by the Engineer.
© Controlled Energy Engineers LLC 2017
654321
E
D
C
B
A
CONTROLLED ENERGY
ENGINEERS, LLC
2451 W BIRCHWOOD AVE, #104
MESA, AZ 85202
PHONE: 480.621.5933
Know what's below.before you dig.Call
1-800-782-5348
THIS DRAWING IS A COMPILATION BASED ON INFORMATION FROM, BUT NOT
LIMITED TO, DRAWINGS FROM PREVIOUS PROJECTS:
THIS DRAWING MUST BE FIELD VERIFIED BEFORE USE
DRAWING NOT TO SCALE UNLESS SCALE BAR IS PRESENT
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
# Date Revision
2/2/2017 3:58:55 P
M
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
PERMIT SET
# Date Revision
17002
ZEW
CEE
MAR 13, 2017
,
S
WILSTERMAN
E
n
r
e
ig
e
R
s
t
D
g
O
a
A
e
i
S
t
Z
I
R
e
A
n
N
d
.
U
ZANE E.
P
d
e
I
r
T
R
E
C
s
s
o
f
e
li
n
F
I
o
T
AC
a
E
l
A
.
.
)
e.
ir
cal
c
t
E
(
O
i
N
g
e
r
e
n
39548
EXPIRES 09-30-2018
3-13-17
1 4-27-17 2ND CITY
SUBMITTAL
2 6-1-17 3RD CITY
SUBMITTAL
3 7-12-17 RAIL DOCK
BATTERY
CHARGING
4 11-15-17 3000A SES
WAREHOUSE
LEVEL 01
LIGHTING
PLAN - 3
E124
N
1" 2" 3"
SCALE 1/8" = 1'
0
GENERAL NOTES KEY NOTES
1
2
3
4
5
6
1
A. CONTRACTOR SHALL SUBMIT AS-BUILT DRAWINGS TO ENGINEER AND OWNER.
B. REFER TO SHEET E100 FOR ADDITIONAL GENERAL NOTES.
C. REFER TO SHEET E100 FOR LUMINAIRE SCHEDULE.
D. REFER TO SHEETS E120 AND E121 FOR LEVEL 01 POWER AND LIGHTING PLANS.
E. REFER TO SHEETS E130, E131, E132 AND E133 FOR LEVEL 02 POWER AND LIGHTING
PLANS.
F. REFER TO SHEETS E140 AND E141 FOR SINGLE LINE DIAGRAM.
G. REFER TO SHEETS E150 AND E151 FOR PANEL SCHEDULES.
LEVEL 01 EXISTING
ELECTRICAL EQUIPMENT
INDICATED ON THIS SHEET
2
REFER TO SHEET E123 FOR CONTINUATION
COLD
DOCK
FREEZER
FREEZER
COOLER
EXISTING 480V PANEL "LPD", 480V PANEL "LPE", 208V PANEL "RPC" AND TRANSFORMER
EXISTING IDF #3
EXISTING EXIT LIGHT
EXISTING LUMINAIRE TO REMAIN. WHERE INDICATED BY "NL", NIGHT LIGHT CIRCUIT
WILL REMAIN ENERGIZED AT ALL TIMES (UTILITY POWER AND GENERATOR VIA 480V
PANEL EM WHEN UTILITY POWER IS LOST).
EXISTING LUMINAIRE TO BE RELOCATED TO ALIGN WITH STORAGE RACK ISLES.
WHERE INDICATED BY "NL", NIGHT LIGHT CIRCUIT WILL REMAIN ENERGIZED AT ALL
TIMES (UTILITY POWER AND GENERATOR VIA 480V PANEL EM WHEN UTILITY POWER IS
LOST).
INSTALL NEW EXIT LIGHT. INSTALL 2-#12, #12 GND, 1/2"C TO NEAREST EMERGENCY CKT
FROM 480V PANEL EM.
3
3
3
3
3
3
4
5
555
5 5 5
5
5
5
5 5 5
555
5
5
5 5
5 5
5
5 5 5
55
5 5 5
5
5 5
5
5 5
5
5
5
5
5
5
55
55
5
6
5
5
5 5 5
5
555
5 5 5
5 5 5 5 5 5 5 5 5
555555555
5 5 5
6
6
66666
6 6
3
3
7
4
7
INSTALL 600VAC, 60A FUSED DISCONNECT SWITCH FOR BALER. DISCONNECT SWITCH
ENCLOSURE SHALL HAVE TYPE 1 RATING. INSTALL FUSES SIZED PER BALER MFR
RECOMMENDATIONS. INSTALL 3-#8, #10 GND, 3/4"C (FROM 480V PANEL LPF, CIRCUIT
31,33,35).
4
DATE:
DRAWN BY:
CHECKED BY:
CEE PROJECT #:
Original drawings remain the property
of the Engineer and as such the
Engineer retains total ownership and
control. The design represented by
these drawings is sold to the client for
a one time use, unless otherwise
agreed upon in writing by the Engineer.
© Controlled Energy Engineers LLC 2017
654321
E
D
C
B
A
CONTROLLED ENERGY
ENGINEERS, LLC
2451 W BIRCHWOOD AVE, #104
MESA, AZ 85202
PHONE: 480.621.5933
Know what's below.before you dig.Call
1-800-782-5348
THIS DRAWING IS A COMPILATION BASED ON INFORMATION FROM, BUT NOT
LIMITED TO, DRAWINGS FROM PREVIOUS PROJECTS:
THIS DRAWING MUST BE FIELD VERIFIED BEFORE USE
DRAWING NOT TO SCALE UNLESS SCALE BAR IS PRESENT
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
# Date Revision
2/2/2017 3:58:55 P
M
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
PERMIT SET
# Date Revision
17002
ZEW
CEE
MAR 13, 2017
,
S
WILSTERMAN
E
n
r
e
ig
e
R
s
t
D
g
O
a
A
e
i
S
t
Z
I
R
e
A
n
N
d
.
U
ZANE E.
P
d
e
I
r
T
R
E
C
s
s
o
f
e
li
n
F
I
o
T
AC
a
E
l
A
.
.
)
e
.
ir
cal
c
t
E
(
O
i
N
g
e
r
e
n
39548
EXPIRES 09-30-2018
3-13-17
1 4-27-17 2ND CITY
SUBMITTAL
2 6-1-17 3RD CITY
SUBMITTAL
LEVEL 02 -
POWER
PLAN
E130
N
0 2 1
SCALE 1/4" = 1'
1
OFFICE
(RYAN)
HALL
COPY CSR
FINANCE
OFFICE
(TOM)
REGIONAL
DSM
UTILITY
ROOM
OFFICE
(ED)
PROCUREMENT
CONFERENCE
LVP1-10
LVP1-4
LV
P1-4
LVP1-22
LV
P1-22
LVP1-14
WOMENS
MENS
OFFICE
(GLENN)
OFFICE
(DAVE)
LVP1-6
FILE
RPD
KEY NOTES
GENERAL NOTES
A. CONTRACTOR SHALL SUBMIT AS-BUILT DRAWINGS TO ENGINEER AND OWNER.
B. REFER TO SHEET E100 FOR ADDITIONAL GENERAL NOTES.
C. REFER TO SHEET E100 FOR LUMINAIRE SCHEDULE.
D. REFER TO SHEETS E120 AND E121 FOR LEVEL 01 POWER AND LIGHTING PLANS.
E. REFER TO SHEETS E130, E131, E132 AND E133 FOR LEVEL 02 POWER AND LIGHTING
PLANS.
F. REFER TO SHEETS E140 AND E141 FOR SINGLE LINE DIAGRAM.
G. REFER TO SHEETS E150 AND E151 FOR PANEL SCHEDULES.
H. REFER TO SHEET E110 FOR PANEL LOCATIONS THAT MAY BE REFERRED TO ON THIS
SHEET BUT NOT INDICATED.
I. FURNISH AND INSTALL CONDUITS, FITTINGS, PULL BOXES, ETC. AS REQUIRED FOR
LIGHTING AND RECEPTACLE BRANCH CIRCUIT NUMBERS INDICATED. USE #12 AWG
CONDUCTORS WITH #12 AWG GROUND FOR 20A AND 15A CIRCUITS. USE #10 AWG
CONDUCTORS WITH #10 AWG GROUND FOR 30A CIRCUITS. DO NOT EXCEED SIX
CURRENT CARRYING CONDUCTORS PER CONDUIT.
J. CONDUITS SHALL BE CONCEALED WHERE POSSIBLE.
K. LIGHT SWITCHES SHALL BE FLUSH MOUNTED AT 42" ABOVE FINISHED FLOOR.
L. RECEPTACLES SHALL BE MOUNTED FLUSH MOUNTED AT 18" ABOVE FINISHED FLOOR.
1NOT USED.
2ROOF MOUNTED HP-4. INSTALL 600VAC, 30A FUSED DISCONNECT SWITCH.
DISCONNECT SWITCH ENCLOSURE SHALL HAVE TYPE 3R RATING. INSTALL FUSES
SIZED PER HVAC MFR RECOMMENDATIONS. INSTALL 3-#10, #10 GND, 1"C. CIRCUITED
TO PANEL LPCA-1,3,5.
3ROOF MOUNTED HP-3. INSTALL 600VAC, 30A FUSED DISCONNECT SWITCH.
DISCONNECT SWITCH ENCLOSURE SHALL HAVE TYPE 3R RATING. INSTALL FUSES
SIZED PER HVAC MFR RECOMMENDATIONS. INSTALL 3-#10, #10 GND, 1"C. CIRCUITED
TO PANEL LPC-38,40,42.
F
30A
2
F
30A
3
F
30A
4
F
30A
5
4ROOF MOUNTED HP-2. INSTALL 600VAC, 30A FUSED DISCONNECT SWITCH.
DISCONNECT SWITCH ENCLOSURE SHALL HAVE TYPE 3R RATING. INSTALL FUSES
SIZED PER HVAC MFR RECOMMENDATIONS. INSTALL 3-#10, #10 GND, 1"C. CIRCUITED
TO PANEL LPB-13,15,17.
5ROOF MOUNTED HP-1. INSTALL 600VAC, 30A FUSED DISCONNECT SWITCH.
DISCONNECT SWITCH ENCLOSURE SHALL HAVE TYPE 3R RATING. INSTALL FUSES
SIZED PER HVAC MFR RECOMMENDATIONS. INSTALL 3-#10, #10 GND, 1"C. CIRCUITED
TO PANEL LPB-7,9,11.
6ROOF MOUNTED EF-3. INSTALL 7-DAY PROGRAMMABLE WALL SWITCH IN SINGLE OR
DOUBLE GANG BOX.
LV
P1-4
LV
P1-10
8
F
60A
COMPUTER / TELCO
#
TC/P
6
LVP1-10
LV
P1-10
LV
P1-10
LVP1-4
LV
P1-4
LV
P1-6
LVP1-4
LVP1-8
LV
P1-22
LV
P1-14
LVP1-14
LV
P1-12
LV
P1-12
LV
P1-12
LV
P1-12
LV
P1-8
LV
P1-8
LV
P1-8
LV
P1-8
RP
D-23
RPD-23
RPD-23
RP
D-23
LVP1-16 LVP1-16
LV
P1-16
LVP2-17 LVP2-17
LV
P2-17
LV
P2-17
LV
P1-12
LV
P1-12
LV
P1-12
LVP2-9
LV
P2-9
LV
P2-9
LV
P2-9
LV
P1-12
LVP2-11 LVP2-11
LV
P2-11
RPD-21
RP
D-27
RP
D-25
LVP1-10 LVP1-10
RPD-17
6
IWH-205
(LPC-21)
IWH-206
(LPC-23)
8WALL MOUNTED DSI-1. INSTALL 240VAC, 60A FUSED DISCONNECT SWITCH.
DISCONNECT SWITCH ENCLOSURE SHALL HAVE TYPE 1 RATING. INSTALL FUSES
SIZED PER HVAC MFR RECOMMENDATIONS. INSTALL 2-#8, #10 GND, 3/4"C. CIRCUITED
TO PANEL RPD-40,42.
F
60A
7
7ROOF MOUNTED DSO-1. INSTALL 240VAC, 60A FUSED DISCONNECT SWITCH.
DISCONNECT SWITCH ENCLOSURE SHALL HAVE TYPE 3R RATING. INSTALL FUSES
SIZED PER HVAC MFR RECOMMENDATIONS. INSTALL 3-#8, #10 GND, 1"C. CIRCUITED
TO PANEL RPD-40,42.
HP-1
HP-2
HP-3
HP-4
9
9MOUNTED ON ROOF NEXT TO AIR CONDITIONING UNIT.
LEVEL 02 OFFICE
AREA REMODEL
INDICATED
ON THIS SHEET
10INSTALL 277V, 20A SNAP SWITCH NEXT TO WATER HEATER TO SERVE AS
DISCONNECTING MEANS.
SHADED AREA REPRESENT
AREA BEING REMODELED
ABOVE
EXISTING BUILDING FOOTPRINT
SHADED AREA REPRESENTS
AREA BEING REMODELED
ABOVE
EXISTING BUILDING FOOTPRINT
10 10
LVP1-6
RE
FE
R T
O LO
WE
R LE
FT
F
OR
C
ON
TIN
UA
TIO
N
RE
FE
R T
O U
PP
ER
R
IG
HT
F
OR
C
ON
TIN
UA
TIO
N
RE
FE
R T
O S
HE
ET
E
131 F
OR
C
ON
TIN
UA
TIO
N
RPD-14
GFCI
2
9
RPD-16
GFCI
2
9
RPD-18
GFCI
2
DATE:
DRAWN BY:
CHECKED BY:
CEE PROJECT #:
Original drawings remain the property
of the Engineer and as such the
Engineer retains total ownership and
control. The design represented by
these drawings is sold to the client for
a one time use, unless otherwise
agreed upon in writing by the Engineer.
© Controlled Energy Engineers LLC 2017
654321
E
D
C
B
A
CONTROLLED ENERGY
ENGINEERS, LLC
2451 W BIRCHWOOD AVE, #104
MESA, AZ 85202
PHONE: 480.621.5933
Know what's below.before you dig.Call
1-800-782-5348
THIS DRAWING IS A COMPILATION BASED ON INFORMATION FROM, BUT NOT
LIMITED TO, DRAWINGS FROM PREVIOUS PROJECTS:
THIS DRAWING MUST BE FIELD VERIFIED BEFORE USE
DRAWING NOT TO SCALE UNLESS SCALE BAR IS PRESENT
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
# Date Revision
2/2/2017 3:58:55 P
M
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
PERMIT SET
# Date Revision
17002
ZEW
CEE
MAR 13, 2017
,
S
WILSTERMAN
E
n
r
e
ig
e
R
s
t
D
g
O
a
A
e
i
S
t
Z
I
R
e
A
n
N
d
.
U
ZANE E.
P
d
e
I
r
T
R
E
C
s
s
o
f
e
li
n
F
I
o
T
AC
a
E
l
A
.
.
)
e.
ir
cal
c
t
E
(
O
i
N
g
e
r
e
n
39548
EXPIRES 09-30-2018
3-13-17
1 4-27-17 2ND CITY
SUBMITTAL
2 6-1-17 3RD CITY
SUBMITTAL
LEVEL 02 -
POWER
PLAN
E131
N
0 2 1
SCALE 1/4" = 1'
1
PROCUREMENT
STORAGE STORAGE
MENS WOMENS JAN.
TRAINING
SALES MTG.
STAIR 3
LVP2-8
GFCI
KEY NOTES
GENERAL NOTES
A. CONTRACTOR SHALL SUBMIT AS-BUILT DRAWINGS TO ENGINEER AND OWNER.
B. REFER TO SHEET E100 FOR ADDITIONAL GENERAL NOTES.
C. REFER TO SHEET E100 FOR LUMINAIRE SCHEDULE.
D. REFER TO SHEETS E120 AND E121 FOR LEVEL 01 POWER AND LIGHTING PLANS.
E. REFER TO SHEETS E130, E131, E132 AND E133 FOR LEVEL 02 POWER AND LIGHTING
PLANS.
F. REFER TO SHEETS E140 AND E141 FOR SINGLE LINE DIAGRAM.
G. REFER TO SHEETS E150 AND E151 FOR PANEL SCHEDULES.
H. REFER TO SHEET E110 FOR PANEL LOCATIONS THAT MAY BE REFERRED TO ON THIS
SHEET BUT NOT INDICATED.
I. FURNISH AND INSTALL CONDUITS, FITTINGS, PULL BOXES, ETC. AS REQUIRED FOR
LIGHTING AND RECEPTACLE BRANCH CIRCUIT NUMBERS INDICATED. USE #12 AWG
CONDUCTORS WITH #12 AWG GROUND FOR 20A AND 15A CIRCUITS. USE #10 AWG
CONDUCTORS WITH #10 AWG GROUND FOR 30A CIRCUITS. DO NOT EXCEED SIX
CURRENT CARRYING CONDUCTORS PER CONDUIT.
J. CONDUITS SHALL BE CONCEALED WHERE POSSIBLE.
K. LIGHT SWITCHES SHALL BE FLUSH MOUNTED AT 42" ABOVE FINISHED FLOOR.
L. RECEPTACLES SHALL BE MOUNTED FLUSH MOUNTED AT 18" ABOVE FINISHED FLOOR.
1ROOF MOUNTED HP-7. INSTALL 600VAC, 30A FUSED DISCONNECT SWITCH.
DISCONNECT SWITCH ENCLOSURE SHALL HAVE TYPE 3R RATING. INSTALL FUSES
SIZED PER HVAC MFR RECOMMENDATIONS. INSTALL 3-#10, #10 GND, 1"C. CIRCUITED
TO PANEL HPV2-24,26,28.
F
30A
F
30A
2ROOF MOUNTED HP-6. INSTALL 600VAC, 30A FUSED DISCONNECT SWITCH.
DISCONNECT SWITCH ENCLOSURE SHALL HAVE TYPE 3R RATING. INSTALL FUSES
SIZED PER HVAC MFR RECOMMENDATIONS. INSTALL 3-#10, #10 GND, 1"C. CIRCUITED
TO PANEL LPC-18,20,22.
2 1
3ROOF MOUNTED HP-5. INSTALL 600VAC, 30A FUSED DISCONNECT SWITCH.
DISCONNECT SWITCH ENCLOSURE SHALL HAVE TYPE 3R RATING. INSTALL FUSES
SIZED PER HVAC MFR RECOMMENDATIONS. INSTALL 3-#10, #10 GND, 1"C. CIRCUITED
TO PANEL LPCA-7,9,11.
F
30A
3
4ROOF MOUNTED EF-4. INSTALL 7-DAY PROGRAMMABLE WALL SWITCH IN SINGLE OR
DOUBLE GANG BOX.
5ROOF MOUNTED EF-5. INSTALL 120V, 15A, SPST WALL SWITCH IN SINGLE OR DOUBLE
GANG BOX.
TC/P TC/P
4
4 5
5
CO
AT
LOBBY
HALL
LVP2-7
LVP2-7
LVP2-5
LVP2-5
LVP2-7
LV
P2-13
LVP2-13
LV
P2-13
LV
P2-13
LVP2-13
LVP2-13 LVP2-15
LVP2-15
LV
P2-15
LV
P2-10
LV
P2-10
LVP2-10
LVP2-10
LVP2-10
LV
P2-7
LV
P2-5
LV
P2-7
LV
P2-5
LV
P2-7
LV
P2-7
LV
P2-5
LV
P2-7
LV
P2-5
LVP2-5
RPD-17
RPD-15
GFCI
HP-5
HP-7HP-6
6MOUNTED ON ROOF NEXT TO AIR CONDITIONING UNIT.
6
LVP2-5
LEVEL 02 OFFICE
AREA REMODEL
INDICATED
ON THIS SHEET
RPD-17
SHADED AREA REPRESENT
AREA BEING REMODELED
ABOVE
EXISTING BUILDING FOOTPRINT
FUTURE
OFFICE
LVP2-19
LVP2-19
LV
P2-19
LV
P2-19
LV
P2-19
LV
P2-19
LVP2-19
LVP2-19
RE
FE
R T
O S
HE
ET
E
130 F
OR
C
ON
TIN
UA
TIO
N
RPD-15
GFCI
6
2
HP-8
F
60A
7
7ROOF MOUNTED HP-8. INSTALL 240VAC, 30A FUSED DISCONNECT SWITCH.
DISCONNECT SWITCH ENCLOSURE SHALL HAVE TYPE 3R RATING. INSTALL FUSES
SIZED PER HVAC MFR RECOMMENDATIONS. INSTALL 2-#10, #10 GND, 3/4"C.
CIRCUITED TO PANEL RPD-2,4.
6
2
RPD-13
GFCI
6
2
2
2
RP
D-6
GF
CI
2
DATE:
DRAWN BY:
CHECKED BY:
CEE PROJECT #:
Original drawings remain the property
of the Engineer and as such the
Engineer retains total ownership and
control. The design represented by
these drawings is sold to the client for
a one time use, unless otherwise
agreed upon in writing by the Engineer.
© Controlled Energy Engineers LLC 2017
654321
E
D
C
B
A
CONTROLLED ENERGY
ENGINEERS, LLC
2451 W BIRCHWOOD AVE, #104
MESA, AZ 85202
PHONE: 480.621.5933
Know what's below.before you dig.Call
1-800-782-5348
THIS DRAWING IS A COMPILATION BASED ON INFORMATION FROM, BUT NOT
LIMITED TO, DRAWINGS FROM PREVIOUS PROJECTS:
THIS DRAWING MUST BE FIELD VERIFIED BEFORE USE
DRAWING NOT TO SCALE UNLESS SCALE BAR IS PRESENT
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
# Date Revision
2/2/2017 3:58:55 P
M
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
PERMIT SET
# Date Revision
17002
ZEW
CEE
MAR 13, 2017
,
S
WILSTERMAN
E
n
r
e
ig
e
R
s
t
D
g
O
a
A
e
i
S
t
Z
I
R
e
A
n
N
d
.
U
ZANE E.
P
d
e
I
r
T
R
E
C
s
s
o
f
e
li
n
F
I
o
T
AC
a
E
l
A
.
.
)
e
.
ir
cal
c
t
E
(
O
i
N
g
e
r
e
n
39548
EXPIRES 09-30-2018
3-13-17
1 4-27-17 2ND CITY
SUBMITTAL
2 6-1-17 3RD CITY
SUBMITTAL
LEVEL 02 -
LIGHTING
PLAN
E132
N
0 2 1
SCALE 1/4" = 1'
1
OFFICE
(RYAN)
HALL
COPY
CSR
FINANCE
OFFICE
(TOM)
DSM
UTILITY
ROOM
OFFICE
(ED)
PROCUREMENT
GENERAL NOTES
CONFERENCE
REGIONAL
WOMENS
MENS
OFFICE
(GLENN)
OFFICE
(DAVE)
FILE
RPD
A. CONTRACTOR SHALL SUBMIT AS-BUILT DRAWINGS TO ENGINEER AND OWNER.
B. REFER TO SHEET E100 FOR ADDITIONAL GENERAL NOTES.
C. REFER TO SHEET E100 FOR LUMINAIRE SCHEDULE.
D. REFER TO SHEETS E120 AND E121 FOR LEVEL 01 POWER AND LIGHTING PLANS.
E. REFER TO SHEETS E130, E131, E132 AND E133 FOR LEVEL 02 POWER AND LIGHTING
PLANS.
F. REFER TO SHEETS E140 AND E141 FOR SINGLE LINE DIAGRAM.
G. REFER TO SHEETS E150 AND E151 FOR PANEL SCHEDULES.
H. REFER TO SHEET E110 FOR PANEL LOCATIONS THAT MAY BE REFERRED TO ON THIS
SHEET BUT NOT INDICATED.
I. FURNISH AND INSTALL CONDUITS, FITTINGS, PULL BOXES, ETC. AS REQUIRED FOR
LIGHTING AND RECEPTACLE BRANCH CIRCUIT NUMBERS INDICATED. USE #12 AWG
CONDUCTORS WITH #12 AWG GROUND FOR 20A AND 15A CIRCUITS. USE #10 AWG
CONDUCTORS WITH #10 AWG GROUND FOR 30A CIRCUITS. DO NOT EXCEED SIX
CURRENT CARRYING CONDUCTORS PER CONDUIT.
J. CONDUITS SHALL BE CONCEALED WHERE POSSIBLE.
K. LIGHT SWITCHES SHALL BE FLUSH MOUNTED AT 42" ABOVE FINISHED FLOOR.
L. RECEPTACLES SHALL BE MOUNTED FLUSH MOUNTED AT 18" ABOVE FINISHED FLOOR.
C
LPCA-26
37
C
LPCA-26
37
C
LPCA-26
37
C
LPCA-26
37
35
MO
37
MO
C
LP
CA
-26
36
36
MO
33
MO
32
MO
31
MO
A
LPCA-26
33
A
LPCA-26
33
A
LPCA-26
33
A
LPCA-26
33
C
LP
CA
-26
32
C
LPCA-26
31
C
LPCA-26
31
C
LPCA-26
31
C
LPCA-26
31
B
LPC-32BP
38
A
LPCA-26NL
38
A
LPCA-26
39
A
LPCA-26
38
A
LPCA-26
38
A
LPCA-26
38
A
LPCA-26
38
25
MO
24
MO
21
MO
22
MO
A
LPCA-30
23
A
LPCA-30
23
A
LPCA-30
23
B
LPC-32BP
23
A
LPCA-30
28
A
LPCA-30
28
A
LPCA-30
28
A
LPCA-30
28
A
LPCA-30
28
A
LPCA-30
28
C
LP
CA
-30
27
C
LPCA-30
26
A
LPCA-30
23
A
LPCA-30
23
C
LPCA-30
21
C
LPCA-30
21
26
MO
27
MO
A
LPCA-26
38
A
LPCA-26
38
A
LPCA-26
39
23
OS
PS
28
OS
38
OS
PSOS
C
LP
CA
-26
36
C
LP
CA
-26
32
34
MO
COMPUTER / TELCO
C
LPCA-30
21
C
LPCA-30
21
C
LPCA-30
26
C
LP
CA
-30
27
35
LP
C-37
F
35
LP
C-37
F
35
LP
C-37
F
35
LP
C-37
F
C
LPCA-30
22
C
LPCA-30
22
C
LPCA-30
22
C
LPCA-30
22
B
LPC-32BP
28
16
LP
A-7
G
LPC-32
EXIT
LP
C-3
2
EX
IT
34
LPCA-26
E
FROM SHEET E121
LEVEL 02 OFFICE
AREA REMODEL
INDICATED
ON THIS SHEET
SHADED AREA REPRESENT
AREA BEING REMODELED
ABOVE
EXISTING BUILDING FOOTPRINT
SHADED AREA REPRESENT
AREA BEING REMODELED
ABOVE
EXISTING BUILDING FOOTPRINT
A
LP
CA
-30
24
A
LP
CA
-30
25
RE
FE
R T
O LO
WE
R LE
FT
F
OR
C
ON
TIN
UA
TIO
N
RE
FE
R T
O U
PP
ER
R
IG
HT
F
OR
C
ON
TIN
UA
TIO
N
RE
FE
R T
O S
HE
ET
E
133 F
OR
C
ON
TIN
UA
TIO
N
DATE:
DRAWN BY:
CHECKED BY:
CEE PROJECT #:
Original drawings remain the property
of the Engineer and as such the
Engineer retains total ownership and
control. The design represented by
these drawings is sold to the client for
a one time use, unless otherwise
agreed upon in writing by the Engineer.
© Controlled Energy Engineers LLC 2017
654321
E
D
C
B
A
CONTROLLED ENERGY
ENGINEERS, LLC
2451 W BIRCHWOOD AVE, #104
MESA, AZ 85202
PHONE: 480.621.5933
Know what's below.before you dig.Call
1-800-782-5348
THIS DRAWING IS A COMPILATION BASED ON INFORMATION FROM, BUT NOT
LIMITED TO, DRAWINGS FROM PREVIOUS PROJECTS:
THIS DRAWING MUST BE FIELD VERIFIED BEFORE USE
DRAWING NOT TO SCALE UNLESS SCALE BAR IS PRESENT
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
# Date Revision
2/2/2017 3:58:55 P
M
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
PERMIT SET
# Date Revision
17002
ZEW
CEE
MAR 13, 2017
,
S
WILSTERMAN
E
n
r
e
ig
e
R
s
t
D
g
O
a
A
e
i
S
t
Z
I
R
e
A
n
N
d
.
U
ZANE E.
P
d
e
I
r
T
R
E
C
s
s
o
f
e
li
n
F
I
o
T
AC
a
E
l
A
.
.
)
e
.
ir
cal
c
t
E
(
O
i
N
g
e
r
e
n
39548
EXPIRES 09-30-2018
3-13-17
1 4-27-17 2ND CITY
SUBMITTAL
2 6-1-17 3RD CITY
SUBMITTAL
LEVEL 02 -
LIGHTING
PLAN
E133
N
0 2 1
SCALE 1/4" = 1'
1
PROCUREMENT
STORAGE STORAGE
MEN
WOMEN
JAN.
TRAINING
SALES MTG.
STAIR 3
GENERAL NOTES
A. CONTRACTOR SHALL SUBMIT AS-BUILT DRAWINGS TO ENGINEER AND OWNER.
B. REFER TO SHEET E100 FOR ADDITIONAL GENERAL NOTES.
C. REFER TO SHEET E100 FOR LUMINAIRE SCHEDULE.
D. REFER TO SHEETS E120 AND E121 FOR LEVEL 01 POWER AND LIGHTING PLANS.
E. REFER TO SHEETS E130, E131, E132 AND E133 FOR LEVEL 02 POWER AND LIGHTING
PLANS.
F. REFER TO SHEETS E140 AND E141 FOR SINGLE LINE DIAGRAM.
G. REFER TO SHEETS E150 AND E151 FOR PANEL SCHEDULES.
H. REFER TO SHEET E110 FOR PANEL LOCATIONS THAT MAY BE REFERRED TO ON THIS
SHEET BUT NOT INDICATED.
I. FURNISH AND INSTALL CONDUITS, FITTINGS, PULL BOXES, ETC. AS REQUIRED FOR
LIGHTING AND RECEPTACLE BRANCH CIRCUIT NUMBERS INDICATED. USE #12 AWG
CONDUCTORS WITH #12 AWG GROUND FOR 20A AND 15A CIRCUITS. USE #10 AWG
CONDUCTORS WITH #10 AWG GROUND FOR 30A CIRCUITS. DO NOT EXCEED SIX
CURRENT CARRYING CONDUCTORS PER CONDUIT.
J. CONDUITS SHALL BE CONCEALED WHERE POSSIBLE.
K. LIGHT SWITCHES SHALL BE FLUSH MOUNTED AT 42" ABOVE FINISHED FLOOR.
L. RECEPTACLES SHALL BE MOUNTED FLUSH MOUNTED AT 18" ABOVE FINISHED FLOOR.
44
MO
C
LPCA-28
41
C
LPCA-28
41
C
LPCA-28
41
C
LPCA-28
41
A
LPCA-28
47
A
LPCA-28
39
B
LPC-32BP
47
A
LPCA-28
47
A
LP
CA
-28
45
B
LP
C-32
BP
45
A
LPCA-28
47
B
LPC-32BP
47
A
LPCA-28
47
A
LPCA-28
47
A
LPCA-28
47
A
LPCA-28
47
A
LPCA-28
47
A
LPCA-28
47
B
LPC-32BP
47
A
LPCA-28
47
A
LPCA-28
47
A
LPCA-28
47
A
LPCA-28
47
43
MO
17
MO
45
MO
42
MO
46
MO
47
MO
41
MO
PS
47
OS
47
OS
B
LPC-32BP
39
C
LP
CA
-28
42
C
LP
CA
-28
42
A
LP
CA
-28
45
CO
AT
LOBBY
HALL
39
OS
A
LPCA-28
47
A
LP
CA
-28
45
A
LPCA-28
47
41
MO
LP
C-3
2
EX
IT
LP
C-3
2
EX
IT
LPC-32
EXIT
LPC-32
EXIT
LEVEL 02 OFFICE
AREA REMODEL
INDICATED
ON THIS SHEET
1
1
SHADED AREA REPRESENT
AREA BEING REMODELED
ABOVE
EXISTING BUILDING FOOTPRINT
B
LPC-32BP
48
48
OS
A
LPCA-28
48
A
LPCA-28
48
A
LPCA-28
48
A
LPCA-28
48
A
LPCA-28
48
A
LPCA-28
48
A
LPCA-28
48
A
LPCA-28
48
A
LPCA-28
48
A
LPCA-28
48
B
LPC-32BP
48
PS
A
LPCA-26
39
RE
FE
R T
O S
HE
ET
E
132 F
OR
C
ON
TIN
UA
TIO
N
48
OS
A
LP
CA
-28
46
A
LPCA-28
43
A
LPCA-28
44
FUTURE
OFFICE
LP
C-3
2
EX
IT
2
T-3
45KVA
480V
208V
3PH
EXISTING
208V PANEL
"RPD"
(10KA SCCR)
100A
3P
45KVA
480V
208V
3PH
EXISTING
208V PANEL
"LVP3"
(10KA SCCR)
60A
3P
15KVA
480V
208V
3PH
EXISTING
208V PANEL
"LVP1"
(10KA SCCR)
EXISTING
480V PANEL
"HVP1"
(14KA SCCR)
15KVA
480V
208V
3PH
EXISTING
208V PANEL
"RPB1"
(10KA SCCR)
EXISTING
480V PANEL
"LPB"
(14KA SCCR)
XFMR-T2
30KVA
480V
208V
3PH
EXISTING
208V PANEL
"RPB"
(10KA SCCR)
480V PANEL
"LPC"
(35KA SCCR
REQ'D)
EXISTING
480V PANEL
"LPCA"
(14KA SCCR)
EXISTING
SERVICE FROM SRP
N
G
SPD
(E) GROUNDING
SYSTEM
1200A
3P
800A
3P
800A
3P
800A
3P
800A
3P
800A
3P
TO FIRE PUMP
(250HP)
MCCD
(CB-5)
SWBB MCCC SWBA MCCB
EXISTING
480V PANEL
"EM"
(14KA SCCR)
(E
) S
TA
ND
BY
G
EN
ER
AT
OR
FROM SWBD-MDP
(E) SWBD "SWBB"
M
100A
3P
100A
3P
100A
3P
100A
3P
100A
3P
400A-FRS
3-FUSES
400A
3P
M M M M M
MLO
400A
3P
200A
3P
200A
3P
SPACE
(E) SWBD "TE"
EXISTING
480V PANEL
"LPE"
(14KA SCCR)
EXISTING
480V PANEL
"LPD"
(14KA SCCR)
EXISTING
208V PANEL
"RPC"
(10KA SCCR)
RPA2-XFMR
75KVA
480V
208V
3PH
F28
F29
EXISTING
208V PANEL
"RPA2"
(10KA SCCR)
EXISTING
480V PANEL
"LPA2"
(35KA SCCR)
FROM SWBD-MDP
(E) SWBD "SWBA1"
200A
3P
200A
3P
200A
3P
(E) SWBD "SWBA2"
SPACE SPACE
400A
3P
MCCA
400A
3P
FROM SWBD-MDP
(E) MCC "MCCB"
FROM SWBD-MDP
(E) MCC "MCCC" (E) MCC "MCCD"
100
CP-3B
100
CP-4B
150
CP-3
150
CP-4
100
CP-1B
100
CP-2B
150
CP-1
150
CP-2
FROM SWBD-MDP
407
CP-5
(450FLA)
MLO MLOMLO
45KVA
480V
208V
3PH
F24
30KVA
480V
208V
3PH
EXISTING
208V PANEL
"LVP2"
(10KA SCCR)
480V PANEL
"HVP2"
(35KA SCCR
REQ'D)
EXISTING
480V PANEL
"LPF"
(25KA SCCR)
30KVA
480V
208V
3PH
EXISTING
208V PANEL
"RPE"
(10KA SCCR)
SPARE
F27
F4
F5
F7
F8
F26
F3 F6 F9 F19
F22
F2
DISCONNECT
AND REMOVE
SPACE
9KVA
480V
208V
3PH
EXISTING
FUSE PANEL
"EM"
(200KA SCCR)
30A
3P
10A
3P
100A
3P
EXISTING TRANSFER
SWITCH (10KA SCCR MIN)
7
KEY NOTES
8
DISCONNECT EXISTING CONDUCTOR(S).
75KVA
480V
208V
3PH
EXISTING
208V PANEL
"RPA"
(10KA SCCR)
480V PANEL
"LPA"
(35KA SCCR
REQ'D)
EXISTING
208V PANEL
"RPAA"
(10KA SCCR)
F31
F32
F30
EXTEND EXISTING CONDUCTORS TO NEW SERVICE ENTRANCE AND DISTRIBUTION
PANELS.
T-4
30KVA
480V
240V
3PH
EXISTING
240V PANEL
"LVP4"
(10KA SCCR)
60A
3P
50A
SPACE
(E) 480V, 3∅, 4W, 3000A
SERVICE FROM SRP
(SCA = 43,490A)
N
G
F0
3000AT
LSIG
3P
65KA
SERVICE ENTRANCE SWITCHGEAR (SWBD-SES)
480Y/277V, 3∅, 4W, 3000A BUS
65KA SCCR, TYPE 3R ENCLOSURE
SPD
MCCD
(CB-5)
SWBB MCCC SWBA MCCB
F1
MAIN DISTRIBUTION PANEL (SWBD-MDP)
480Y/277V, 3∅, 4W, 3000A BUS
65KA SCCR, TYPE 3R ENCLOSURE
800AT
LSI
3P
65KA
800AT
LSI
3P
65KA
800AT
LSI
3P
65KA
800AT
LSI
3P
65KA
800AT
LSI
3P
65KA
400AT
LSI
3P
65KA
400AT
LSI
3P
65KA
400AT
LSI
3P
65KA
M SRP
POWER
METER
2000AT
LSI
3P
65KA
MLO
REFER TO PANEL
SCHEDULE
M EXISTING SRP
POWER
METER
EXISTING SES
GG
GG
GG
G
GG
EXTEND #4/0 BARE Cu GEC TO
EXISTING BUILDING GROUNDING
ELECTRODE SYSTEM
7 7 7 7 7 7
4
3 3 3 3 3
3REFER TO FAULT CURRENT TABLE FOR EXISTING CONDUCTOR SIZES AND NUMBER OF
PARALLEL FEEDERS.
8 8 8 8 8
4EXOTHERMIC WELD GEC
7
REFER TO SITE PLAN
FOR GROUNDING
REQ'TS
100A
F10
F12 F14 F16
F11 F13 F15 F17
F21 F25
F40F37
F36
F35
F38
F41
F43 F44 F45
F20
F23
F34
F39
(8 SETS) 4-#500KCMIL,
#400KCMIL GND, 4"C
SRP SECONDARY CONDUITS
PER SRP REQ'TS
5REPLACE EXISTING PANELBOARD WITH NEW. REFER TO PANEL SCHEDULE ON SHEET
E150.
5 5
TO FIRE PUMP
CONTROLLER
(250HP)
F46
6
6DISCONNECT AND REMOVE EXISTING SERVICE ENTRANCE EQUIPMENT.
1
2
RELOCATE EXISTING FEEDER TO EXISTING 480V PANEL LPA AS INDICATED. SPLICE
AND EXTEND WITHIN SWITCHGEAR ENCLOSURE AS REQUIRED.
INSTALL 2 PARALLEL SETS OF 3-#3/0, #3 GND, 2½"C
4
4
4
4
4
4
REFER TO PANEL
SCHEDULE FOR
MODIFICATIONS
REFER TO PANEL
SCHEDULE FOR
MODIFICATIONS
REFER TO PANEL
SCHEDULE FOR
MODIFICATIONS
REFER TO PANEL
SCHEDULE FOR
MODIFICATIONS
REFER TO PANEL
SCHEDULE FOR
MODIFICATIONS
REFER TO PANEL
SCHEDULE FOR
MODIFICATIONS
4
4
4
4
TO EXISTING 480V
PANEL "LPA"
(CONNECTED TO
DIFFERENT
SOURCE)
1
NEW
480V PANEL
"HVP3"
(14KA SCCR
MIN)
REFER TO PANEL
SCHEDULE
2
F18
4
REFER TO PANEL
SCHEDULE FOR
MODIFICATIONS
REFER TO PANEL
SCHEDULE FOR
MODIFICATIONS
REFER TO PANEL
SCHEDULE FOR
MODIFICATIONS
REFER TO PANEL
SCHEDULE FOR
MODIFICATIONS
1
NOTES:
1. FAULT CURRENT CALCULATION RELOCATED TO
SHEET E160.
2. FAULT SOURCE POINTS HAVE BEEN REVISED.
3. SCCR FOR EACH PANELBOARD INDICATED ON
THIS SHEET.
REFER TO PANEL
SCHEDULE
5
4
208V PANEL
"UPS1"
(10KA MIN
SCCR REQ'D)
REFER TO PANEL
SCHEDULE ON SHT E160
20KW UPS
94-#1, #6 GND, 2"C
9
9
4
NOTE: ALL EQUIPMENT INDICATED
ON THIS SHEET IS EXISTING.
MODIFICATIONS TO PANELBOARDS
HAVE BEEN INDICATED HEREIN.
9
4
SPARE SPARE SPARE
F47
400A
3P
3R
TO JOCKEY PUMP
CONTROLLER
(3HP)
3-#10, #10 GND, 3/4"C
(2 SETS) 3-#3/0,
#3/0 GND, 2½"C
(2 SETS) 3-#3/0, 3/0 GND, 2½"C
(APPROX 300-LF TO SOUTH)
10DISCONNECT AND REMOVE EXISTING CONDUIT AND CONDUCTOR.
10
REFER TO PANEL
SCHEDULE FOR
MODIFICATIONS
4
DATE:
DRAWN BY:
CHECKED BY:
CEE PROJECT #:
Original drawings remain the property
of the Engineer and as such the
Engineer retains total ownership and
control. The design represented by
these drawings is sold to the client for
a one time use, unless otherwise
agreed upon in writing by the Engineer.
© Controlled Energy Engineers LLC 2017
654321
E
D
C
B
A
CONTROLLED ENERGY
ENGINEERS, LLC
2451 W BIRCHWOOD AVE, #104
MESA, AZ 85202
PHONE: 480.621.5933
Know what's below.before you dig.Call
1-800-782-5348
THIS DRAWING IS A COMPILATION BASED ON INFORMATION FROM, BUT NOT
LIMITED TO, DRAWINGS FROM PREVIOUS PROJECTS:
THIS DRAWING MUST BE FIELD VERIFIED BEFORE USE
DRAWING NOT TO SCALE UNLESS SCALE BAR IS PRESENT
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
# Date Revision
2/2/2017 3:58:55 P
M
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
PERMIT SET
# Date Revision
17002
ZEW
CEE
MAR 13, 2017
,
S
WILSTERMAN
E
n
r
e
ig
e
R
s
t
D
g
O
a
A
e
i
S
t
Z
I
R
e
A
n
N
d
.
U
ZANE E.
P
d
e
I
r
T
R
E
C
s
s
o
f
e
li
n
F
I
o
T
AC
a
E
l
A
.
.
)
e
.
ir
cal
c
t
E
(
O
i
N
g
e
r
e
n
39548
EXPIRES 09-30-2018
3-13-17
1 4-27-17 2ND CITY
SUBMITTAL
2 6-1-17 3RD CITY
SUBMITTAL
3 7-12-17 RAIL DOCK
BATTERY
CHARGING
4 11-15-17 3000A SES
SINGLE
LINE
DIAGRAM
E140
DISCONNECT SWITCH MTD
TO FIRE PUMP BLDG
FROM SWBD "SWBA2"
(E) MCC "MCCA"
MLO
1
EXHAUST FAN
0.5
MAINT RM
EXHAUST FAN
2
C4-2 UNIT #13
2
C4-2
2
C4-1 UNIT #12
SOUTH FAN
2
C4-1 NORTH
FAN
2
C3-6 UNIT #11
2
C3-6
2
C3-5 UNIT #10
2
C3-5
2
C3-4 UNIT #9
2
C3-4
2
C3-3 UNIT #8
2
C3-3
2
C3-2 UNIT #7
2
C3-2
2
C3-1 UNIT #6
2
C3-1.
2
C2-2 UNIT #5
2
C2-2
2
C2-1 UNIT #4
2
C2-1
(E) MCC "MCCA"
(E) MCC "MCCA"
2
C1-2
1
C1-3 UNIT #3
2
UNDER
FLOOR VENT
FAN
1
C1-1 UNIT #1
SPACE SPACE
ASILE
EVAPORATOR
#3
1.5
GLYCOL PUMP
#1
1.5
GLYCOL PUMP
#2
3
AMMONIA
PUMP RIGHT
SIDE 2
(PURGE
PUMP)
3
AMMONIA
PUMP #1
SPARE
3
JACKET
WATER PUMP
#1
3
JACKET
WATER PUMP
#2
5
AMMONIA
PUMP #1
5
AMMONIA
PUMP #2
5
CONDENSER
WATER PUMP
#1
5
CONDENSER
WATER PUMP
#2
7.5
BLAST
FREEZER FAN
#1
7.5
BLAST
FREEZER FAN
#2
7.5
BLAST
FREEZER FAN
#3
7.5
BLAST
FREEZER FAN
#4
10
ROOF
CONDENSER
FAN #1
10
ROOF
CONDENSER
FAN #2
D-1
1
DOCK
EVAPORATOR
#2
1
DOCK
EVAPORATOR
#3
1
DOCK
EVAPORATOR
#4
1
DOCK
EVAPORATOR
#5
1
DOCK
EVAPORATOR
#6
7.5
BLAST 3
7.5
BLAST 3
7.5
BLAST 4
7.5
B-4
7.5
C5-1
7.5
C5-3
7.5
C5-4
7.5
C6-1
7.5
C6-2
3
D-9
3
D-7
3
D-8
7.5
C5-2 FRICK
CONDENSER
FANS
FRICK
CONDENSER
PUMP
2
2
DATE:
DRAWN BY:
CHECKED BY:
CEE PROJECT #:
Original drawings remain the property
of the Engineer and as such the
Engineer retains total ownership and
control. The design represented by
these drawings is sold to the client for
a one time use, unless otherwise
agreed upon in writing by the Engineer.
© Controlled Energy Engineers LLC 2017
654321
E
D
C
B
A
CONTROLLED ENERGY
ENGINEERS, LLC
2451 W BIRCHWOOD AVE, #104
MESA, AZ 85202
PHONE: 480.621.5933
Know what's below.before you dig.Call
1-800-782-5348
THIS DRAWING IS A COMPILATION BASED ON INFORMATION FROM, BUT NOT
LIMITED TO, DRAWINGS FROM PREVIOUS PROJECTS:
THIS DRAWING MUST BE FIELD VERIFIED BEFORE USE
DRAWING NOT TO SCALE UNLESS SCALE BAR IS PRESENT
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
# Date Revision
2/2/2017 3:58:55 P
M
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
PERMIT SET
# Date Revision
17002
ZEW
CEE
MAR 13, 2017
,
S
WILSTERMAN
E
n
r
e
ig
e
R
s
t
D
g
O
a
A
e
i
S
t
Z
I
R
e
A
n
N
d
.
U
ZANE E.
P
d
e
I
r
T
R
E
C
s
s
o
f
e
li
n
F
I
o
T
AC
a
E
l
A
.
.
)
e
.
ir
cal
c
t
E
(
O
i
N
g
e
r
e
n
39548
EXPIRES 09-30-2018
3-13-17
1 4-27-17 2ND CITY
SUBMITTAL
2 6-1-17 3RD CITY
SUBMITTAL
SINGLE
LINE
DIAGRAM
E141
NOTE: ALL EQUIPMENT INDICATED
ON THIS SHEET IS EXISTING.
SHEET IS FOR REFERENCE ONLY.
VOLTS 277/480V PANEL
EM
(EXISTING)
MAIN 150A MCB
PHASE 3PH, 4 WIRELOCATION BLDG EXT NEAR GENSET BUS 225A
A.I.C. FED FROM LPF MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
EF-1 COMPRESSOR ROOM
1
20 3
1 720
20 1 LIGHTS C5
1920 2 1
1 3 720
20 1 LIGHTS C5
3120 4 1
1 5 720
20 1 LIGHTS C6 / DOCK / MAINT
2160 6 1
EF-2 COMPRESSOR ROOM 15 3
7 720
20 1
LIGHTS DRY WAREHOUSE
(RE-PURPOSE BREAKER)1440 8 1
9 720
SPACE
-- 10
11 720
SPACE
-- 12
SPARE 30 1
13 0
SPACE
-- 14
SPACE
15 --
SPACE
-- 16
SPACE
17 --
SPACE
-- 18
SPACE19 --
SPACE
-- 20
SPACE
21 --
SPACE
-- 22
SPACE
23 --
SPACE
-- 24
SPACE
25 --
SPACE
-- 26
SPACE
27 --
SPACE
-- 28
SPACE
29 --
SPACE
-- 30
12960 VA - 3PH TOTAL CONNECTED 4800 4560 3600
10800VA - CONTINUOUS X 0.25 (*)
= 2700 VA
2160 VA - NON-CONTIN X 1.00 = 2160 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)17100
FEEDER TOTAL (VA) (***)
0 TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
21 LARGEST PHASE CURRENT 6/1/2017 9:42
COMMENT:
VOLTS 277/480V PANEL
LPA2
(EXISTING)
MAIN 225A MCB
PHASE 3PH, 4 WIRELOCATION MAINT ROOM BUS 225A
A.I.C. 35KA IC MIN FED FROM SWBD "SWBA1" MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
RPA2 TRANSFORMER 100 3
1 18979
30 1 HEAT TRACE
2400 2
3 18979
30 1 HEAT TRACE
2400 4
5 18979
60 3
ELEVATOR MOTOR (20HP)
7479 6
SPARE 30 3
7 0
7479 8
9 0
7479 10
11 0
20 2 SPARE
0 12
SPARE 30 1
13 0
0 14
SPARE 30 1
15 0
20 2 SPARE
0 16
SPARE 20 1
17 0
0 18
SPARE 20 1
19 0
20 1 SPARE
0 20
SPACE
21 --
SPACE
-- 22
SPACE
23 --
SPACE
-- 24
SPACE25 --
SPACE
-- 26
SPACE
27 --
SPACE
-- 28
SPACE
29 --
SPACE
-- 30
SPACE
31 --
SPACE
-- 32
SPACE
33 --
SPACE
-- 34
SPACE
35 --
SPACE
-- 36
SPACE37 --
SPACE
-- 38
SPACE
39 --
SPACE
-- 40
SPACE
41 --
SPACE
-- 42
84174 VA - 3PH TOTAL CONNECTED 28858 28858 26458
0
VA - CONTINUOUS X 0.25 (*)
= 0 VA
84174 VA - NON-CONTIN X 1.00 = 84174 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)
86574FEEDER TOTAL (VA) (***)
0
TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)104
LARGEST PHASE CURRENT
11/15/2017 7:34
COMMENT:
VOLTS 277/480V PANEL
LPC
(EXISTING)
MAIN 200A MCB
PHASE 3PH, 4 WIRELOCATION MAINT ROOM BUS 225A
A.I.C. 35KA IC MIN FED FROM SWITCHBOARD SWBB MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
SPACE
1 --
20 1 SPARE
0 2
SPACE
3 --
20 1
DRY WH LTS (ROWS DF/DG)3120 4 1
DRY WH LTS (ROWS DH/DJ)
1
20 1
5 3120
20 1
COOLER / DRY WH LTS (ROWS RB-RE)
2160 6 1
DRY WH LTS (ROWS DK/DL)
1
20 1
7 3120
20 1 SPARE
0 8
DRY WH LTS (ROW DM)
1
20 1
9 1920
-- 10
SPARE 20 1
11 0
20 1 DRY DOCK NORTH LTS
2340 12 1
SPARE 20 1
13 0
20 1 DRY DOCK MIDDLE LTS
2985 14 1
DRY DOCK NORTH LIGHTS
1
20 1
15 2340
20 1 DRY DOCK MIDDLE LTS
3060 16 1
SPARE 20 1
17 0
15 3
LEVEL 02 HVAC (HP-5)
2853 18
SPARE 20 1
19 0
2853 20
SPARE 20 1
21 0
2853 22
SPARE 20 1
23 0
20 1 WALL PACK LTS
4232 24 1
DRY WH LTS (ROWS DN/DP)
1
20 1
25 3600
60 3 SPARE
0 26
RAIL DOCK LTS
1
20 1
27 1440
0 28
ACCESS CORRIDOR LTS
1
20 1
29 960
0 30
RPB TRANSFORMER 60 3
31 4370
SPACE
0 32
33 4370
SPACE
0 34
35 4370
0 36
LEVEL 02 LTS - MID & EXIT
1
20 1
37 2880
20 3 SPARE
38
LEVEL 02 LTS - SOUTH & EXIT
1
20 1
39 880
40
LEVEL 02 LTS - NORTH & EXIT
1
20 1
41 2480
42
62306 VA - 3PH TOTAL CONNECTED 19808 19983 22515
40637VA - CONTINUOUS X 0.25 (*)
= 10159 VA
21669 VA - NON-CONTIN X 1.00 = 21669 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)
77705FEEDER TOTAL (VA) (***)
0
TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
94
LARGEST PHASE CURRENT
11/15/2017 7:34
COMMENT:
VOLTS 277/480V PANEL
LPCA
(EXISTING)
MAIN MLO
PHASE 3PH, 4 WIRELOCATION MAINT ROOM BUS 225A
A.I.C. 14KA IC MIN FED FROM LPC MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
LEVEL 02 HVAC (HP-4)
(RE-PURPOSED BREAKER)
15 3
1 3019
15 3
FREEZER DOOR - (FD3)
368 2 1
3 3019
506 4 1
5 3019
506 6 1
LEVEL 02 HVAC (HP-5)
(RE-PURPOSED BREAKER)
15 3
7 2853
15 3
FREEZER DOOR - (FD4)
506 8
9 2853
506 10
11 2853
506 12
SPARE 15 3
13 0
15 3
FREEZER DOOR - (FD5)
506 14
15 0
506 16
17 0
506 18
SPARE 15 3
19 0
15 3
FREEZER DOOR - BACK (SE DOCK)
506 20
21 0
506 22
23 0
506 24
SPACE
(RELOCATE BREAKER TO PNL LPB)
(INSTALL COVER PLATE OVER SPACE)
25 --
15 3
LEVEL 02 LTS - MID
(RE-PURPOSE BREAKER)2560 26 1
27 --
LEVEL 02 LTS - SOUTH
3280 28 1
29 --
LEVEL 02 LTS - NORTH
(RE-PURPOSED BREAKER)
2480 30 1
SPACE
(RELOCATE BREAKER TO PNL LPB)
(INSTALL COVER PLATE OVER SPACE)
31 --
SPACE
(RELOCATE BREAKER TO PNL LPB)
(INSTALL COVER PLATE OVER SPACE)
0 32
33 --
0 34
35 --
0 36
SPACE
37 --
SPACE
-- 38
SPACE
39 --
SPACE
-- 40
SPACE
41 --
SPACE
-- 42
31871 VA - 3PH TOTAL CONNECTED 10318 11176 10376
9700VA - CONTINUOUS X 0.25 (*)
= 2425 VA
22171 VA - NON-CONTIN X 1.00 = 22171 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)
35954FEEDER TOTAL (VA) (***)
0
TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
43
LARGEST PHASE CURRENT
6/1/2017 9:44
COMMENT:
VOLTS 277/480V PANEL
LPD
(EXISTING)
MAIN 225A MCB
PHASE 3PH, 4 WIRELOCATION MAINT ROOM BUS 225A
A.I.C. 14KA IC MIN FED FROM SWBD "SWBB" MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
DOCK LIGHTS
1
20 1
1 1440
20 1
FREEZER LTS (ROWS FB/FC)2880 2 1
SPARE 20 1
3 0
20 1
COOLER LTS (ROWS RF/RA)
2880 4
DOCK LIGHTS
1
20 1
5 480
20 1
FREEZER LTS (ROW FA)1920 6 1
SPARE 20 1
7 0
20 1 SPARE
0 8 1
SPARE 20 1
9 0
20 1 SPARE
0 10 1
DOCK LIGHTS
1
20 1
11 1440
20 1 SPARE
0 12 1
SPARE 20 1
13 0
20 1 SPARE
0 14 1
SPARE 20 1
15 0
20 1 SPARE
0 16 1
FREEZER LTS (ROWS FE/FE)
1
20 1
17 2160
20 1 SPARE
0 18
FREEZER LTS (ROWS FE/FE)
1
20 1
19 2160
20 1 SPARE
0 20
SPARE 20 1
21 0
20 1 SPARE
0 22
SPARE 20 1
23 0
20 1 SPARE
0 24
PANEL "RPC" TRANSFORMER 70 3
25 6520
SPACE
-- 26
27 6520
SPACE
-- 28
29 6520
SPACE
-- 30
CANOPY & RISER RM LTS
1
20 1
31 1000
20 1 EXTERIOR LTS
500 32 1
SPARE 20 1
33 0
20 1 EXTERIOR LTS
500 34 1
SPARE 20 1
35 0
20 1 EXTERIOR LTS
500 36 1
SPARE 20 3
37 0
20 1 SPARE
0 38
39 0
20 1 SPARE
0 40
41 0
20 1 SPARE
0 42
37420 VA - 3PH TOTAL CONNECTED 14500 9900 13020
14980VA - CONTINUOUS X 0.25 (*)
= 3745 VA
22440 VA - NON-CONTIN X 1.00 = 22440 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)47245
FEEDER TOTAL (VA) (***)
0
TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)57
LARGEST PHASE CURRENT
6/1/2017 9:44
COMMENT:
VOLTS 277/480V PANEL
HVP1
(EXISTING)
MAIN MLO
PHASE 3PH, 4 WIRELOCATION
ACCESS CORR (NEAR FD2)
BUS 100A
A.I.C. 14KA IC MIN FED FROM SWBD "TE" MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
SPARE 20 1
1 0
20 1 SPARE
0 2
SPARE
1
20 1
3 0
20 1
DRY WH LTS (ROWS DD/DE)2640 4 1
SPARE
1
20 1
5 0
20 1 SPARE
0 6
LEVEL 02 HVAC (HP-4) 15 3
7 3019
15 3 SPARE
0 8 1
9 3019
0 10 1
11 3019
0 12 1
PANEL LVP1 TRANSFORMER 30 3
13 3420
30 3
LEVEL 02 HVAC (HP-3)
3269 14
15 3420
3269 16
17 3420
3269 18
31764 VA - 3PH TOTAL CONNECTED 9708 12348 9708
2640VA - CONTINUOUS X 0.25 (*)
= 660 VA
29124 VA - NON-CONTIN X 1.00 = 29124 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)
37704FEEDER TOTAL (VA) (***)
0
TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
45
LARGEST PHASE CURRENT
11/15/2017 7:33
COMMENT:
VOLTS 277/480V PANEL
LPE
(EXISTING)
MAIN MLO
PHASE 3PH, 4 WIRELOCATION MAINT ROOM BUS 225A
A.I.C. 14KA IC MIN FED FROM SWBD "SWBA1" MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
FREEZER DOOR C5 NORTH 30 3
1 1000
30 3 AIR COMPRESSOR AT FIRE RISER
3000 2 1
3 1000
3000 4 1
5 1000
3000 6 1
FREEZER DOOR C5 SOUTH 30 3
7 1000
30 3 FREEZER DOOR C6
1000 8
9 1000
1000 10
11 1000
1000 12
SPARE 20 1
13 0
30 3 SPARE
0 14
SPARE 20 1
15 0
0 16
SPARE 20 1
17 0
0 18
SPARE 20 1
19 0
20 3 SPARE
0 20
SPARE 20 1
21 0
0 22
SPARE 20 1
23 0
0 24
SPACE
25 --
20 1 SPARE
0 26
SPACE
27 --
20 1 SPARE
0 28
SPACE
29 --
20 1 SPARE
0 30
SPACE
31 --
20 1 SPARE
0 32
SPACE
33 --
20 1 SPARE
0 34
SPACE35 --
20 1 SPARE
0 36
SPARE 20 1
37 0
20 1 SPARE
0 38
SPARE 20 1
39 0
20 1 SPARE
0 40
SPARE 20 1
41 0
20 1 SPARE
0 42
18000 VA - 3PH TOTAL CONNECTED 6000 6000 6000
9000
VA - CONTINUOUS X 0.25 (*)
= 2250 VA
9000 VA - NON-CONTIN X 1.00 = 9000 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)
20250FEEDER TOTAL (VA) (***)
0
TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
24
LARGEST PHASE CURRENT
6/1/2017 9:44
COMMENT:
VOLTS 277/480V PANEL
HVP2
(NEW)
MAIN 100A MCB
PHASE 3PH, 4 WIRELOCATION
COLD DOCK (NEAR STAIRS)
BUS 100A
A.I.C. 35KA IC MIN FED FROM SWBD "TE" MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
SPACE
1 --
20 1
DRY WH LTS (ROWS DQ/DR)1440 2 1
SPACE
3 --
SPACE
-- 4
SPACE
5 --
SPACE
-- 6
LEVEL 02 LTS - RM 229 20 1
7 960
SPACE
-- 8
LEVEL 02 LTS - RM 228 20 1
9 1440
20 1 SPARE
0 10
SPACE
11 --
20 3
LEVEL 02 HVAC (HP-7)
2853 12
13 --
2853 14
15 --
2853 16
FREEZER DOOR
1
15 3
17 1000
40 3 PANEL LVP2 TRANSFORMER
2880 18
1 19 1000
2880 20
1 21 1000
2880 22
LEVEL 02 HVAC (HP-6) 30 3
23 4958
100 3 SPARE
0 24
25 4958
0 26
27 4958
0 28
SPARE 20 1
29 0
SPACE
0 30
38914 VA - 3PH TOTAL CONNECTED 14091 13131 11691
4440VA - CONTINUOUS X 0.25 (*)
= 1110 VA
34474 VA - NON-CONTIN X 1.00 = 34474 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)
43384
FEEDER TOTAL (VA) (***)
0 TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
52 LARGEST PHASE CURRENT 11/15/2017 7:33
COMMENT:
VOLTS 277/480V PANEL
LPF
(EXISTING)
MAIN MLO
PHASE 3PH, 4 WIRELOCATION CHARGING / BATTERY RM BUS 400A
A.I.C. 25KA IC MIN FED FROM SWBD "SWBA2" MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
PANEL "RPE" TRANSFORMER 50 3
1 2820
40 3 BATTERY CHARGER
9140 2
3 2820
9140 4
5 2820
9140 6
BATTERY CHARGER 40 3
7 9140
40 3 BATTERY CHARGER
9140 8
9 9140
9140 10
11 9140
9140 12
BATTERY CHARGER 40 3
13 9140
40 3 BATTERY CHARGER
9140 14
15 9140
9140 16
17 9140
9140 18
BATTERY CHARGER 40 3
19 9140
40 3 BATTERY CHARGER
9140 20
21 9140
9140 22
23 9140
9140 24
LIGHTS
1
20 1
25 2100
20 1 LIGHTS
400 26 1
SPARE 20 1
27 0
20 1 SPARE
0 28
SPARE 20 1
29 0
20 1 SPARE
0 30
BALER 35 3
31 3880
40 3 PANEL "EM" VIA TRANSFER SWITCH
4800 32
33 3880
4800 34
35 3880
4800 36
BATTERY CHARGER
*** BACKUP CHARGER - CANNOT BE USED AT
SAME TIME AS OTHER 7 CHARGERS ***
60 3
37 0
60 3
BATTERY CHARGER
*** BACKUP CHARGER - CANNOT BE USED AT
SAME TIME AS OTHER 7 CHARGERS ***
0 38
39 0
0 40
41 0
0 42
228939 VA - 3PH TOTAL CONNECTED 77980 75480 75480
2500
VA - CONTINUOUS X 0.25 (*)
= 625 VA
226439 VA - NON-CONTIN X 1.00 = 226439 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)
234564FEEDER TOTAL (VA) (***)
0
TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
282
LARGEST PHASE CURRENT
11/15/2017 7:35
COMMENT:
VOLTS 480V PANEL
HVP3
MAIN 400A MCB
PHASE 3PH, 3 WIRELOCATION RAIL DOCK / BATTERY ROOM BUS 400A
A.I.C. 14KA IC MIN FED FROM SWITCHBOARD SWBB
MOUNTING SURFACE (TYPE 1)
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
BATTERY CHARGER 1 RECEPT 20 3
1 2355
20 3 BATTERY CHARGER 2 RECEPT
1634 2
3 2355
1634 4
5 2355
1634 6
BATTERY CHARGER 3 RECEPT 20 3
7 2355
20 3 BATTERY CHARGER 4 RECEPT
1634 8
9 2355
1634 10
11 2355
1634 12
BATTERY CHARGER 5 RECEPT 20 3
13 2355
20 3 BATTERY CHARGER 6 RECEPT
2548 14
15 2355
2548 16
17 2355
2548 18
BATTERY CHARGER 7 RECEPT 25 3
19 5097
25 3 BATTERY CHARGER 8 RECEPT
4737 20
21 5097
4737 22
23 5097
4737 24
TRASH COMPACTOR
1
20 3
25 4432
200 3
INSTANT WATER HEATER (IWH-1)
38503 26
1 27 4432
38503 28
1 29 4432
38503 30
EXHAUST FAN (1/2 HP) 20 3
31 305
SPACE
-- 32
33 305
SPACE
-- 34
35 305
SPACE
-- 36
SPACE
37 --
SPACE
-- 38
SPACE
39 --
SPACE
-- 40
SPACE
41 --
SPACE
-- 42
197861 VA - 3PH TOTAL CONNECTED 65954 65954 65954
13296VA - CONTINUOUS X 0.25 (*)
= 3324 VA
184565 VA - NON-CONTIN X 1.00 = 184565 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)
201185FEEDER TOTAL (VA) (***)
0
TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
242
LARGEST PHASE CURRENT
7/13/2017 10:21
COMMENT:
VOLTS 277/480V PANEL
LPB
(EXISTING)
MAIN MLO
PHASE 3PH, 4 WIRELOCATION
ACCESS CORR (NEAR FD1)
BUS 200A
A.I.C. 14 KAIC FED FROM SWBB MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
DRY WH LTS (ROW DA)
1
20 1
1 1680
15 3
LEVEL 02 HVAC (HP-2)
2853 2
DRY WH LTS (ROWS DB)
1
20 1
3 1440
2853 4
DRY WH LTS (ROWS DA/DB ENDCAPS)
1
20 1
5 500
2853 6
<POLE NOT USED> 30 3
7 --
60 3 208V PANEL RPB1 TRANSFORMER
8410 8
LEVEL 02 IWH-205
9 5540
5030 10
LEVEL 02 IWH-206
11 5540
7950 12
LEVEL 02 HVAC (HP-1) 15 3
13 2853
60 3 208V PANEL LVP3 TRANSFORMER
6900 14
15 2853
6900 16
17 2853
6900 18
73909 VA - 3PH TOTAL CONNECTED 22696 24616 26596
3620VA - CONTINUOUS X 0.25 (*)
= 905 VA
70289 VA - NON-CONTIN X 1.00 = 70289 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)80694
FEEDER TOTAL (VA) (***)
0 TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
97 LARGEST PHASE CURRENT 11/15/2017 7:34
COMMENT:
VOLTS 277/480V PANEL
LPA
(NEW)
MAIN 200A MCB
PHASE 3PH, 4 WIRELOCATION MAINT ROOM BUS 225A
A.I.C. 35KA IC MIN FED FROM SWBA1 MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
SPACE
1 --
SPACE
-- 2
MACHINE ROOM LTS
1
20 1
3 2660
SPACE
-- 4
MAINTENANCE ROOM LTS
1
20 1
5 1528
SPACE
-- 6
ELEVATOR LIGHTS
1
20 1
7 280
SPACE
-- 8
LEVEL 01 LTS - SOUTH & EXIIT
1
20 1
9 1280
SPACE
-- 10
LEVEL 01 LTS - NORTH & EXIT
1
20 1
11 1680
SPACE
-- 12
MAINTENANCE ROOM LTS 20 1
13 1528
15 3 36V BATTERY CHARGER
3324 14
PARKING LOT LTS VIA TIME SWITCH
1
20 1
15 800
3324 16
N&S STAIR LIGHTING
1 17 640
3324 18
SPARE 20 1
19 0
SPACE
-- 20
SPACE
21 --
SPACE
-- 22
SPACE
23 --
SPACE
-- 24
SPACE
25 --
SPACE
-- 26
SPACE
27 --
SPACE
-- 28
SPACE
29 --
SPACE
-- 30
SPACE31 --
SPACE
-- 32
SPACE
33 --
SPACE
-- 34
SPACE
35 --
SPACE
-- 36
SPACE
37 --
100 3 TRANSFORMER FEED PANEL RPA
9772 38
SPACE
39 --
9772 40
SPACE
41 --
9772 42
49684 VA - 3PH TOTAL CONNECTED 14904 17836 16944
8868VA - CONTINUOUS X 0.25 (*)
= 2217 VA
40816 VA - NON-CONTIN X 1.00 = 40816 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)55725
FEEDER TOTAL (VA) (***)
0 TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
67 LARGEST PHASE CURRENT 11/15/2017 7:37
COMMENT:
DATE:
DRAWN BY:
CHECKED BY:
CEE PROJECT #:
Original drawings remain the property
of the Engineer and as such the
Engineer retains total ownership and
control. The design represented by
these drawings is sold to the client for
a one time use, unless otherwise
agreed upon in writing by the Engineer.
© Controlled Energy Engineers LLC 2017
654321
E
D
C
B
A
CONTROLLED ENERGY
ENGINEERS, LLC
2451 W BIRCHWOOD AVE, #104
MESA, AZ 85202
PHONE: 480.621.5933
Know what's below.before you dig.Call
1-800-782-5348
THIS DRAWING IS A COMPILATION BASED ON INFORMATION FROM, BUT NOT
LIMITED TO, DRAWINGS FROM PREVIOUS PROJECTS:
THIS DRAWING MUST BE FIELD VERIFIED BEFORE USE
DRAWING NOT TO SCALE UNLESS SCALE BAR IS PRESENT
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
# Date Revision
2/2/2017 3:58:55 P
M
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
PERMIT SET
# Date Revision
17002
ZEW
CEE
MAR 13, 2017
,
S
WILSTERMAN
E
n
r
e
ig
e
R
s
t
D
g
O
a
A
e
i
S
t
Z
I
R
e
A
n
N
d
.
U
ZANE E.
P
d
e
I
r
T
R
E
C
s
s
o
f
e
li
n
F
I
o
T
AC
a
E
l
A
.
.
)
e
.
ir
cal
c
t
E
(
O
i
N
g
e
r
e
n
39548
EXPIRES 09-30-2018
3-13-17
1 4-27-17 2ND CITY
SUBMITTAL
2 6-1-17 3RD CITY
SUBMITTAL
3 7-12-17 RAIL DOCK
BATTERY
CHARGING
4 11-15-17 3000A SES
480V
PANEL
SCHEDULES
E150
EXISTING 480V PANEL EM SCHEDULE
480V PANEL LPA SCHEDULE
(REPLACE EXISTING PANELBOARD WITH NEW ONE HAVING HIGHER SCCR)
(REVISED CIRCUITS TO REFLECT AS-BUILT CONDITIONS)
EXISTING 480V PANEL HVP1 SCHEDULE
(REVISED CIRCUITS TO REFLECT AS-BUILT CONDITIONS)
EXISTING 480V PANEL LPB SCHEDULE
(REVISED CIRCUITS TO REFLECT AS-BUILT CONDITIONS)
EXISTING 480V PANEL LPA2 SCHEDULE
(REVISED CIRCUITS TO REFLECT AS-BUILT CONDITIONS)
480V PANEL LPC SCHEDULE
(REPLACE EXISTING PANELBOARD WITH NEW ONE HAVING HIGHER SCCR)
(REVISED CIRCUITS TO REFLECT AS-BUILT CONDITIONS)
EXISTING 480V PANEL LPCA SCHEDULE
(FREEZER LOADS REMOVED; OTHER LOADS RELOCATED) (REMOVED PANELBOARD)
EXISTING 480V PANEL LPF SCHEDULE
(ADDED BALER CIRCUIT)
EXISTING 480V PANEL LPD SCHEDULE
(REVISED CIRCUITS TO REFLECT AS-BUILT CONDITIONS)
EXISTING 480V PANEL LPE SCHEDULE
(REFERENCE ONLY; NO CHANGES)
480V PANEL HVP2 SCHEDULE
(REPLACE EXISTING PANELBOARD WITH NEW ONE HAVING HIGHER SCCR)
(REVISED CIRCUITS TO REFLECT AS-BUILT CONDITIONS)
NEW 480V PANEL HVP3 SCHEDULE
4
4
4
4
4
4 4
44
4
4
4
VOLTS 120/208V PANEL
RPA
(EXISTING)
MAIN 225A MCB
PHASE 3PH, 4 WIRELOCATION MAINTENANCE ROOM BUS 225A
A.I.C. 10KA IC MIN FED FROM LPA VIA TRANSFORMER MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
EXHAUST FANS (EF-1 & 2) 20 1
1 200
20
1 MAINT ROOM RECEPTS - NE
0 2 1
MAINT RM RECEPT
1
20 1
3 180
1
WATER HEATER RECIRC PUMP (RP-1)
528 4 1
FIRE HOUSE RECEPT, LTS, SPRINKLER 20 1
5 250
1 MAINT ROOM RECEPTS - NW
0 6 1
LEVEL 01 - DF 20 1
7 480
20 1 MAINT ROOM RECEPTS - S
360 8 2
LEVEL 01 RECEPTS - DRIVER / WAITING
2
20 1
9 360
20 1 MAINT ROOM RECEPTS
180 10 1
LEVEL 01 RECEPTS - REC / HALL
4
20 1
11 720
20 1 MAINT OFFICE - LIGHT / RECEPT
520 12 2 1
MAINT OFFICE RECEPT
2
20 1
13 360
20 1 AMERICOLD ELEC CASCADE METER
100 14
FACP 20 1
15 500
15 2 HVAC INDOOR UNIT IU-2
492 16
LEVEL 01 RECEPTS - RM 113,118,120
11
20 1
17 1980
492 18
MAINT RM RECEPT
1
20 1
19 180
20 1 MAIN ENTRANCE SECURITY DOOR
500 20
LOW ROOFTOP RECEPTS
3
15 1
21 540
20 1 SPARE
0 22
MAINT RM RECEPT
1
20 1
23 180
20 1 FIRE SYSTEM
500 24
SPARE 20 1
25 0
20 2 SUMP PUMP
500 26
SPARE 20 1
27 0
500 28
MAINT RM RECEPT
1
20 1
29 180
20 1 SPARE
0 30
AMMONIA STORAGE TANK 20 1
31 250
100 3 PANEL RPAA MAIN FEED ENGINE RM
4270 32
SPARE 20 1
33 0
4270 34
AMMONIA EXHAUST FAN 60 1
35 500
4270 36
SPARE 60 1
37 0
60 3 SPARE
0 38
SPARE 30 1
39 0
0 40
MAINT RM RECEPT
1
20 1
41 180
0 42
24522 VA - 3PH TOTAL CONNECTED 7200 7550 9772
520
VA - CONTINUOUS X 0.25 (*)
= 130 VA
6300
VA - GP RECEPTS X (**)
= 6300 VA
17702 VA - NON-CONTIN X 1.00 = 17702 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)
29446
FEEDER TOTAL (VA) (***)
(** 100% OF FIRST 10KW + 50% OF BALANCE)
35 TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
82 LARGEST PHASE CURRENT 11/15/2017 7:59
COMMENT:
VOLTS 120/208V PANEL
RPA2
(EXISTING)
MAIN 200A MCB
PHASE 3PH, 4 WIRELOCATION MAINTENANCE ROOM BUS 200A
A.I.C. 10KA IC MIN FED FROM LPA2 VIA TRANSFORMER MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
LEVEL 01 RECEPT - BREAK RM VENDING
(RE-PURPOSED BREAKER)
1
20 1
1 180
20
1 ELEVATOR PIT LT & RECEPT
420 2 1 1
LEVEL 01 RECEPT - BREAK RM VENDING
(RE-PURPOSED BREAKER)
1
20
3 180
20
250 4
LEVEL 01 RECEPT - BREAK RM REF
1
20
5 180
20 1 ELEVATOR CAB LTG & RECEPT
380 6
LEVEL 01 RECEPT - BREAK RM MICRO
1
20 1
7 180
1080 8
LEVEL 01 RECEPTS - RM 107 COUNTER
2
20
9 360
0 10
LEVEL 01 - DISPOSAL 20
11 1656
30 2 WATER HEATER
1500 12
IDF #2 ROOM 120V 30 1
13 2000
1500 14
IDF #2 ROOM LIGHTS/RECEPT
1 1
20 1
15 260
20 1 SPARE
0 16
DOCK EM LTS 20 1
17 500
100 3 208V PANEL UPS1
6667 18
DOCK RECEPTS
2
20 3
19 360
6667 20
DOCK RECEPTS
2 21 360
6667 22
DOCK RECEPTS
2 23 360
20 1 SPARE
0 24
IDF #3 SOUTH RECEPTS
2
20 1
25 360
30 2 LEVEL 01 HVAC INDOOR UNIT IU-1
720 26
SPARE 20
27 0
720 28
CONT ENGINE RM EX FAN 20 1
29 500
20 2 SPARE
0 30
AMMONIA PUMP HEATER (AP-2) 20 1
31 1000
0 32
AMMONIA PUMP HEATER (AP-1) 20 1
33 1000
20 1 LEVEL 01 RECEPTS - INVENTORY
1080 34 6
LEVEL 01 HVAC OUTDOOR UNIT OU-1 40 2
35 2760
20 1 SPARE
0 36
37 2760
20 1 LEVEL 01 RECEPTS - ROUTING
1080 38 6
LEVEL 01 HVAC OUTDOOR UNIT OU-2 40 2
39 2676
20 1 SPARE
0 40
41 2676
20 1 LEVEL 01 RECEPTS - BRK RM / TRANS / HR
1800 42 10
50838 VA - 3PH TOTAL CONNECTED 18307 13553 18979
680VA - CONTINUOUS X 0.25 (*)
= 170 VA
6840
VA - GP RECEPTS X (**)
= 6840 VA
43318 VA - NON-CONTIN X 1.00 = 43318 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)57106
FEEDER TOTAL (VA) (***)
(** 100% OF FIRST 10KW + 50% OF BALANCE)
38 TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
159 LARGEST PHASE CURRENT 11/15/2017 7:59
COMMENT:
VOLTS 120/208V PANEL
RPAA
(EXISTING)
MAIN MLO
PHASE 3PH, 4 WIRELOCATION MAINTENANCE ROOM BUS 100A
A.I.C. 10KA IC MIN FED FROM RPA MOUNTING SURFACE
LOAD VA LOAD LOAD
DESCRIPTION LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG DESCRIPTION
ENGINE RM RECEPT - NW
1
20 1
1 180
20 1 CHART RECORDERS
100 2
ENGINE RM RECEPTS
2
20 1
3 360
20 1 SPARE
0 4
ENGINE RM RECEPTS
2
20 1
5 360
20 1
ENGINE RM RECEPT (NEAR A/C)180 6 1
BATTERY RM 20 1
7 180
30 2 SPARE
8
ENGINE RM RECEPT - NW
1
20 1
9 180
10
SPACE
11 --
20 1 SPARE
0 12
SPACE
13 --
20 1 SPARE
0 14
SPACE
15 --
20 1 SPARE
0 16
SPARE 20 1
17 0
20 1 SPARE
0 18
SPARE 20 1
19 0
20 1 SPARE
0 20
SPARE 20 1
21 0
20 1 SPARE
0 22
SPARE 20 1
23 0
20 1 SPARE
0 24
SPARE 20 1
25 0
40 2
AIR COMPRESSOR (ADDED 1998)
3720 26
SPARE 20 1
27 0
3720 28
SPACE
29 --
SPACE
-- 30
SPACE
31 --
SPACE
-- 32
TVSS 40 1
33 10
SPACE
-- 34
TVSS 40 1
35 10
SPACE
-- 36
TVSS 40 1
37 10
SPACE
-- 38
SPACE39 --
SPACE
-- 40
SPACE
41 --
SPACE
-- 42
9010 VA - 3PH TOTAL CONNECTED 4190 4270 550
0
VA - CONTINUOUS X 0.25 (*)
= 0 VA
1260
VA - GP RECEPTS X (**)
= 1260 VA
7750 VA - NON-CONTIN X 1.00 = 7750 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)
12810
FEEDER TOTAL (VA) (***)
(** 100% OF FIRST 10KW + 50% OF BALANCE)
7 TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
35.6 LARGEST PHASE CURRENT 11/15/2017 7:59
COMMENT:
VOLTS 120/208V PANEL
RPB
(EXISTING)
MAIN 100A MCB
PHASE 3PH, 4 WIRELOCATION CORRIDOR - FD3 BUS 100A
A.I.C. 10KA IC MIN FED FROM LPC VIA TRANSFORMER MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
RAIL DOCK RECEPTS
1
20 1
1 180
20 1 RF SYSTEM
250 2
RAIL DOCK RECEPTS
1
20 1
3 180
20 1 BI PART DOOR HEATERS
1000 4
RAIL DOCK RECEPTS
1
20 1
5 180
20 1 BI PART DOOR HEATERS
1000 6
SPACE
7 --
20 1 BI PART DOOR HEATERS
1000 8
SPACE9 --
20 1 BI PART DOOR HEATERS
1000 10
SPARE 20 1
11 0
20 1 BI PART DOOR HEATERS
1000 12
DOCK OUTLETS
2
20 1
13 360
20 1 BI PART DOOR HEATERS
1000 14
DOCK OUTLETS
2
20 1
15 360
20 1 BI PART DOOR HEATERS
1000 16
DOCK OUTLETS
2
20 1
17 360
20 1 SPARE
0 18
DOCK OUTLETS
2
20 1
19 360
20 1 RAIL DOCK DOOR RECEPT
180 20 1
SPARE 20 1
21 0
20 1 RAIL DOCK OUTLET
180 22 1
SPARE 20 1
23 0
20 1 SPARE
0 24
RED/GRN DOCK LTS
1
20 1
25 500
20 1 SPARE
0 26
SPARE 20 1
27 0
20 1 SPARE
0 28
DOCK OUTLETS
2
20 1
29 360
20 1 DOCK SCALE RECEPT
180 30 1
DOCK OUTLETS
2
20 1
31 360
20 1 SPARE
0 32
SPARE 20 1
33 0
20 1 FIRE ALARM PANELS
250 34
SPARE 20 1
35 0
20 1 SPARE
0 36
DAIR, MAID COMPUTER OUTLET
1
20 1
37 180
20 1 SPARE
0 38
SPARE 50 2
39 0
20 1 SPARE
0 40
41 0
20 1 SPARE
0 42
11420 VA - 3PH TOTAL CONNECTED 4370 3970 3080
500VA - CONTINUOUS X 0.25 (*)
= 125 VA
3420
VA - GP RECEPTS X (**)
= 3420 VA
7500 VA - NON-CONTIN X 1.00 = 7500 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)13235
FEEDER TOTAL (VA) (***)
(** 100% OF FIRST 10KW + 50% OF BALANCE)19 TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
36.780236 LARGEST PHASE CURRENT 6/1/2017 9:38
COMMENT:
VOLTS 120/208V PANEL
RPC
(EXISTING)
MAIN 150A MCB
PHASE 3PH, 4 WIRELOCATION COLD DOCK AREA - SOUTH BUS 225A
A.I.C. 10KA IC MIN FED FROM LPD VIA TRANSFORMER MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
FREEZER C5 RECEPTS
2
20 1
1 360
20 1
FREEZER C6 RECEPTS
360 2 2
FREEZER C5 RECEPTS
2
20 1
3 360
20 1
FREEZER C6 RECEPTS
360 4 2
FREEZER C5 RECEPTS
2
20 1
5 360
20 1
FREEZER C6 RECEPTS
360 6 2
FREEZER C5 RECEPTS
2
20 1
7 360
20 1
DOCK RECEPTS
360 8 2
FACP 20 1
9 250
20 1
DOCK RECEPTS
360 10 2
DOCK EVAP RECEPTS
1
20 1
11 360
20 1
HEATER RISER ROOM
500 12
DOCK RECEPTS
1
20 1
13 360
20 1
FREEZER C6 DOOR HEATER (MAN)
1000 14
DOCK RECEPTS
1
20 1
15 360
20 1
SPARE
0 16
DOCK RECEPTS
1
20 1
17 360
20 1
SPARE
0 18
DOCK DOOR RECEPT (SWITCHED)
1
20 1
19 180
20 1
DOCK DOOR RECEPT (SWITCHED)
180 20 1
DOCK DOOR RECEPTS
2
20 1
21 360
20 1
DOCK DOOR RECEPT
180 22 1
DOCK DOOR RECEPTS
2
20 1
23 360
20 1
DOCK DOOR RECEPT
180 24 1
DRAIN PIPE HEAT TRACE 20 1
25 1000
20 1
FREEZER C5 SOUTH FAN
500 26
DOOR HEATER C5 NORTH 20 1
27 1000
20 1
FREEZER C6 SOUTH FAN
500 28
RF RECEPT S DOCK
1
20 1
29 180
20 1
PHOTOCELL / CONTACTOR
150 30
DOCK EVAPS RECEPTS
2
20 1
31 360
20 1
FREEZER C5 DOOR FAN
500 32
DOCK EVAPS RECEPTS
2
20 1
33 360
20 1
FREEZER C5 DOOR FAN
500 34
SPARE 20 1
35 0
20 1
FREEZER C5 DOOR HEATER
1000 36
SPARE 30 3
37 0
20 1
FREEZER C5 DOOR HEATER
1000 38
39 0
20 1
RED/GRN DOCK LTS
250 40 1
41 0
20 1
RED/GRN DOCK LTS
250 42 1
15420 VA - 3PH TOTAL CONNECTED 6520 4840 4060
500VA - CONTINUOUS X 0.25 (*)
= 125 VA
6300
VA - GP RECEPTS X (**)
= 6300 VA
8620 VA - NON-CONTIN X 1.00 = 8620 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)19685
FEEDER TOTAL (VA) (***)
(** 100% OF FIRST 10KW + 50% OF BALANCE)
35 TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
54.704869 LARGEST PHASE CURRENT 6/1/2017 9:38
COMMENT:
VOLTS 120/208V PANEL
LVP1
(EXISTING)
MAIN 50A MCB
PHASE 3PH, 4 WIRELOCATION
DRY DOCK (NEAR FD2)
BUS 60A
A.I.C. 10 KA IC MIN FED FROM HVP1 VIA TRANSFORMER MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
LEVEL 02 RECEPTS - OFFICE (DAVE)
3
20 1
1 540
20 1 DOCK RECEPTS - NORTH1
360 2 2
LEVEL 02 RECEPTS - OFFICE (GLENN)
3
20 1
3 540
20 1 DOCK RECEPTS - NORTH2
360 4 2
LEVEL 02 RECEPTS - CSR / REGIONAL
8
20 1
5 1440
20 1 SPARE
540 6 3
LEVEL 02 RECEPTS - FINANCE
4
20 1
7 720
20 1 SPARE
900 8 5
LEVEL 02 RECEPTS - OFFICE (TOM)
3
20 1
9 540
20 1 SPARE
1260 10 7
LEVEL 02 RECEPTS - DSM
4
20 1
11 720
20 1 SPARE
0 12
FREEZER CONTROL BI PART 20 1
13 500
20 1 SPARE
0 14
CONDESATE PUMP RECEPT
4
20 1
15 720
20 1 SPARE
0 16
CONDESATE PUMP RECEPT
4
20 1
17 720
20 1 SPARE
0 18
SPACE
19 --
20 1 SPARE
0 20
SPACE
21 --
20 1 SPARE
0 22
SPACE
23 --
SPACE
-- 24
PANEL MAIN BREAKER 50 3
25 --
-- 26
27 --
SPACE
-- 28
29 --
-- 30
9860 VA - 3PH TOTAL CONNECTED 3020 3420 3420
0
VA - CONTINUOUS X 0.25 (*)
= 0 VA
9360
VA - GP RECEPTS X (**)
= 9360 VA
500 VA - NON-CONTIN X 1.00 = 500 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)
10260
FEEDER TOTAL (VA) (***)
(** 100% OF FIRST 10KW + 50% OF BALANCE)
52 TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
28.5 LARGEST PHASE CURRENT 11/15/2017 7:58
COMMENT:
VOLTS 120/208V PANEL
LVP3
(EXISTING)
MAIN 100A MCB
PHASE 3PH, 4 WIRELOCATION RAIL DOCK BUS 225A
A.I.C. 22 KAIC FED FROM
PNL LPB (VIA TRANSFORMER)
MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
SPARE 20 3
1 0
20 3 SPARE
0 2
3 0
0 4
5 0
0 6
SPARE 20 3
7 0
40 1 120V LINE POWER
0 8
9 0
30 1 SPARE
0 10
11 0
20 1 EAST WALL RECEPTS
900 12 5
DRAIN VALVE 20 1
13 250
30 3 SPARE
0 14
SPARE 20 1
15 0
0 16
SPARE 20 3
17 0
0 18
19 0
50 2 SPARE
0 20
21 0
0 22
SPACE
23 --
20 2 RECEPTACLE
1500 24
SPARE 30 3
25 0
1500 26
27 0
20 2 RECEPTACLE
1500 28
29 0
1500 30
SPARE 30 3
31 0
20 2 RECEPTACLE
1500 32
33 0
1500 34
35 0
20 2 RECEPTACLE
1500 36
MAIN BREAKER 100 3
37 --
1500 38
39 --
20 2 RECEPTACLE
1500 40
41 --
1500 42
16150 VA - 3PH TOTAL CONNECTED 4750 4500 6900
0
VA - CONTINUOUS X 0.25 (*)
= 0 VA
900VA - GP RECEPTS X (**)
= 900 VA
15250 VA - NON-CONTIN X 1.00 = 15250 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)
20700
FEEDER TOTAL (VA) (***)
(** 100% OF FIRST 10KW + 50% OF BALANCE)
5 TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)57.5 LARGEST PHASE CURRENT 11/15/2017 7:58
COMMENT:
VOLTS 120/208V PANEL
LVP2
(EXISTING)
MAIN 100A MCB
PHASE 3PH, 4 WIRELOCATION
DRY DOCK (NEAR STAIRS)
BUS 100A
A.I.C. 10 KA IC MIN FED FROM HVP2 VIA TRANSFORMER MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
SPARE 30 2
1 0
100 3P PANEL MAIN
-- 2
3 0
-- 4
LEVEL 02 RECEPTS - TRAINING / SALES
4
20 1
5 720
-- 6
LEVEL 02 RECEPTS - TRAINING / SALES
5
20 1
7 900
20 1 SPARE
0 8
LEVEL 02 RECEPT - DF 20 1
9 480
20 1 SPARE
0 10
LEVEL 02 COFFEE BAR
1
20 1
11 180
20 1 SPARE
0 12
LEVEL 02 COFFEE BAR
1
20 1
13 180
20 1 SPARE
0 14
SPARE 20 1
15 0
20 1 SPARE
0 16
SPARE 20 1
17 0
20 1 SPARE
0 18
LEVEL 02 RECEPTS - FUTURE (RM 229)
8
20 1
19 1440
20 1 DOCK RECEPTS
360 20 2
SPARE 20 1
21 0
20 1 DOCK RECEPTS
360 22 2
LEVEL 02 FLOOR RECEPTS - TRAINING
6
20 1
23 1080
20 1 DOCK RECEPTS
360 24 2
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
6060 VA - 3PH TOTAL CONNECTED 2880 840 2340
0
VA - CONTINUOUS X 0.25 (*)
= 0 VA
5580
VA - GP RECEPTS X (**)
= 5580 VA
480 VA - NON-CONTIN X 1.00 = 480 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)
8640
FEEDER TOTAL (VA) (***)
(** 100% OF FIRST 10KW + 50% OF BALANCE)
31 TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)24.0 LARGEST PHASE CURRENT 11/15/2017 7:58
COMMENT:
VOLTS 120/208V PANEL
RPE
(EXISTING)
MAIN 100A MCB
PHASE 3PH, 4 WIRELOCATION CHARGING/BATTERY RM BUS 100A
A.I.C. 10KA IC MIN FED FROM LPF VIA TRANSFORMER MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
RECEPTS
3
20 1
1 540
20 1 WATER FILTER RECEPT
180 2 1
RECEPTS
2
20 1
3 360
20 1 WATER HEATER
1600 4
RECEPTS
2
20 1
5 360
20 1 GENERATOR BATTERY CHARGER
100 6
SPARE 30 3
7 0
20 1 EF-10
1180 8
9 0
20 1 SPARE
0 10
11 0
20 1 SPARE
0 12
SPARE 20 1
13 0
20 1 SPARE
0 14
SPARE 20 1
15 0
20 1 SPARE
0 16
SPARE 20 1
17 0
20 1 SPARE
0 18
IRRIGATION CONTROLLER 20 1
19 100
20 1 SPARE
0 20
AMMONIA DUMP 20 1
21 500
20 1 SPARE
0 22
SPARE 20 1
23 0
20 1 SPARE
0 24
SPARE 20 1
25 0
20 3
recepts and lights for USDA room or spare
360 26
SPARE 20 1
27 0
360 28
NH3 DUMP TANK ALARM 20 1
29 100
360 30
SPACE
31 --
SPACE
-- 32
SPACE
33 --
SPACE
-- 34
SPACE
35 --
SPACE
-- 36
SPACE
37 --
SPACE
-- 38
SPACE39 --
SPACE
-- 40
SPACE
41 --
SPACE
-- 42
6100 VA - 3PH TOTAL CONNECTED 2360 2820 920
0
VA - CONTINUOUS X 0.25 (*)
= 0 VA
1440
VA - GP RECEPTS X (**)
= 1440 VA
4660 VA - NON-CONTIN X 1.00 = 4660 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)
8460
FEEDER TOTAL (VA) (***)
(** 100% OF FIRST 10KW + 50% OF BALANCE)
8 TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
23.5 LARGEST PHASE CURRENT 6/1/2017 9:39
COMMENT:
PROJECT NAME: PROJECT NUMBER: 17002
VOLTS 120/208V PANEL
RPB1
(EXISTING) MAIN 150A MCB
PHASE 3PH, 4 WIRE LOCATION DRY DOCK (NEAR FD1) BUS 150A
A.I.C. 10KA IC MIN FED FROM LPB VIA TRANSFORMER MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
LEVEL 02 RECEPTS - CONF RM 5 20 1 1 900
20 1 DOCK RECEPT
360 2 2
LEVEL 02 RECEPTS - FILE 3 20 1 3 540
20 1 DOCK RECEPT
360 4 2
HIGH ROOFTOP GFCI RECEPTS 7 20 1 5 1260
20 1 DOCK RECEPT
360 6 2
LEVEL 02 RECEPTS - OFFICE (RYAN) 6 20 1 7 1080
20 1 DOCK RECEPT
360 8 2
LEVEL 02 RECEPTS - COPY 5 20 1 9 900
20 1 DOCK RECEPT
360 10 2
SPARE 1 11 0
20 1 DOCK RECEPT
360 12 2
EXHAUST FAN (EF-3) 20 1 13 100
20 1 DOCK RECEPT
360 14 2
2 20 15 360
20 1 DOCK RECEPT
360 16 2
30 17 0
20 2 2POLE DOCK RECEPT
1000 18
19 0
1000 20
SPARE 40 3 21 0
20 1 OUTSIDE RECEPTS
540 22 3
23 0
20 2 2POLE DOCK RECEPT
1000 24
25 0
1000 26
IDF NORTH CABINET RECEPT 1 20 1 27 180
20 1 DOCK RECEPT
180 28 1
LEVEL 02 FLOOR RECEPTS - CONF RM 4 20 1 29 720
50 2 2POLE DOCK RECEPT
2000 30
SPARE 20 1 31 0
2000 32
DOCK RECEPTACLE 30 3 33 1250
SPACE
-- 34
35 1250
SPACE
-- 36
37 1250
SPACE
-- 38
SPACE 39 --
SPACE
-- 40
SPACE 41 --
SPACE
-- 42
21390 VA - 3PH TOTAL CONNECTED 8410 5030 7950
0 VA - CONTINUOUS X 0.25 (*) = 0 VA
9540 VA - GP RECEPTS X (**) = 9540 VA
11850 VA - NON-CONTIN X 1.00 = 11850 VA
(* INCLUDES LIGHTING & LARGEST MOTOR) 25230 FEEDER TOTAL (VA) (***)
(** 100% OF FIRST 10KW + 50% OF BALANCE) 53 TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA) 70.1 LARGEST PHASE CURRENT 11/15/2017 7:59
COMMENT:
VOLTS 120/208V PANEL
RPD
(EXISTING)
MAIN 150A MCB
PHASE 3PH, 4 WIRELOCATION LEVEL 02 - UTILITY ROOM BUS 225A
A.I.C. 10KA IC MIN FED FROM SWBD "TE" MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
EXHAUST FANS (EF-4 & 5) 20 1
1 200
20 1 LEVEL 02 RECEPTS - PROCUREMENT
1080 2 6
SPARE 20 1
3 0
540 4 3
SPARE 20 1
5 0
20 1
LEVEL 02 RECEPTS - OFFICE (ED)
540 6 3
SPARE 20 1
7 0
20 1 SPARE
0 8
SPARE 20 1
9 0
20 1 SPARE
0 10
SPARE 20 1
11 0
20 1 SPARE
0 12
LEVEL 02 HVAC (DSO-1 / DSI-1) 40 2
13 2880
30 2
LEVEL 02 HVAC (HP-8)
(NEW BREAKER)
2316 14
15 2880
2316 16
SPARE 20 1
17 0
SPARE
0 18
4 PLEX FIRE RISER
2
20 1
19 360
20 1 SPARE
0 20
SPARE 20 1
21 0
20 1 SPARE
0 22
EXTERIOR SIGN 20 1
23 500
20 1 SPARE
0 24
LEVEL 02 RECEPTS - COMPUTER RM
1
20 1
25 180
20 1 SPARE
0 26
LEVEL 02 RECEPTS - PROCUREMENT
4
20 1
27 720
20 1 SPARE
0 28
SPARE 20 1
29 0
20 1 SPARE
0 30
SPARE 20 1
31 0
20 1 SPARE
0 32
SPARE 20 1
33 0
20 1 SPARE
0 34
SPARE 20 1
35 0
20 1 SPARE
0 36
SPARE 20 1
37 0
20 1 SPARE
0 38
IDF ROOM RECEPTS
2
20 1
39 360
SPACE
-- 40
IDF ROOM RECEPTS
2
20 1
41 360
SPACE
-- 42
15232 VA - 3PH TOTAL CONNECTED 7016 6816 1400
0VA - CONTINUOUS X 0.25 (*)
= 0 VA
4140
VA - GP RECEPTS X (**)
= 4140 VA
11092 VA - NON-CONTIN X 1.00 = 11092 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)21048
FEEDER TOTAL (VA) (***)
(** 100% OF FIRST 10KW + 50% OF BALANCE)23 TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
58 LARGEST PHASE CURRENT 11/15/2017 8:00
COMMENT:
VOLTS 120/240V PANEL
LVP4
(EXISTING)
MAIN 70A MCB
PHASE 3PH, 4 WIRELOCATION ACCESS CORRIDOR BUS 100A
A.I.C. 22 KAIC FED FROM
SWBD TE (VIA TRANSFORMER)
MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
PANEL RECEPTACLE
1
20 1
1 180
20 1 EXIT SIGN
100 2
SPARE 20 1
3 0
20 1 NORTH RECEPTACLE
180 4 1
SPACE ** HIGH LEG **
5 0
SPACE ** HIGH LEG **
-- 6
SPARE 50 3
7 0
20 1 ROOF RECEPT
180 8 1
9 0
20 1 ROOF RECEPT
180 10 1
11 0
20 1 SPACE ** HIGH LEG **
-- 12
820 VA - 3PH TOTAL CONNECTED 460 360 0
0VA - CONTINUOUS X 0.25 (*)
= 0 VA
720VA - GP RECEPTS X (**)
= 720 VA
100 VA - NON-CONTIN X 1.00 = 100 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)
1380
FEEDER TOTAL (VA) (***)
(** 100% OF FIRST 10KW + 50% OF BALANCE)
4 TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)3.8 LARGEST PHASE CURRENT 6/1/2017 9:39
COMMENT:
DATE:
DRAWN BY:
CHECKED BY:
CEE PROJECT #:
Original drawings remain the property
of the Engineer and as such the
Engineer retains total ownership and
control. The design represented by
these drawings is sold to the client for
a one time use, unless otherwise
agreed upon in writing by the Engineer.
© Controlled Energy Engineers LLC 2017
654321
E
D
C
B
A
CONTROLLED ENERGY
ENGINEERS, LLC
2451 W BIRCHWOOD AVE, #104
MESA, AZ 85202
PHONE: 480.621.5933
Know what's below.before you dig.Call
1-800-782-5348
THIS DRAWING IS A COMPILATION BASED ON INFORMATION FROM, BUT NOT
LIMITED TO, DRAWINGS FROM PREVIOUS PROJECTS:
THIS DRAWING MUST BE FIELD VERIFIED BEFORE USE
DRAWING NOT TO SCALE UNLESS SCALE BAR IS PRESENT
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
# Date Revision
2/2/2017 3:58:55 P
M
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
PERMIT SET
# Date Revision
17002
ZEW
CEE
MAR 13, 2017
,
S
WILSTERMAN
E
n
r
e
ig
e
R
s
t
D
g
O
a
A
e
i
S
t
Z
I
R
e
A
n
N
d
.
U
ZANE E.
P
d
e
I
r
T
R
E
C
s
s
o
f
e
li
n
F
I
o
T
AC
a
E
l
A
.
.
)
e
.
ir
cal
c
t
E
(
O
i
N
g
e
r
e
n
39548
EXPIRES 09-30-2018
3-13-17
1 4-27-17 2ND CITY
SUBMITTAL
2 6-1-17 3RD CITY
SUBMITTAL
3 7-12-17 RAIL DOCK
BATTERY
CHARGING
4 11-15-17 3000A SES
208V
PANEL
SCHEDULES
E151
EXISTING 208V PANEL RPA SCHEDULE
(REVISED CIRCUITS TO REFLECT AS-BUILT CONDITIONS)
EXISTING 208V PANEL RPA2 SCHEDULE
(REVISED CIRCUITS TO REFLECT AS-BUILT CONDITIONS)
(ADDED UPS LOAD)
EXISTING 208V PANEL RPAA SCHEDULE
(REVISED CIRCUITS TO REFLECT AS-BUILT CONDITIONS)
EXISTING 208V PANEL RPE SCHEDULE
(REFERENCE ONLY; NO CHANGES)
EXISTING 208V PANEL RPD SCHEDULE
(REVISED CIRCUITS TO REFLECT AS-BUILT CONDITIONS)
EXISTNG 208V PANEL RPB SCHEDULE
(REFERENCE ONLY; NO CHANGES)
EXISTING 208V PANEL RPC SCHEDULE
(REFERENCE ONLY; NO CHANGES)
EXISTING 208V PANEL RPB1 SCHEDULE
(REVISED CIRCUITS TO REFLECT AS-BUILT CONDITIONS)
EXISTING 208V PANEL LVP1 SCHEDULE
(REVISED CIRCUITS TO REFLECT AS-BUILT CONDITIONS)
EXISTING 208V PANEL LVP2 SCHEDULE
(REVISED CIRCUITS TO REFLECT AS-BUILT CONDITIONS)
EXISTING 208V PANEL LVP3 SCHEDULE
(REFERENCE ONLY; NO CHANGES)
EXISTING 240V PANEL LVP4 SCHEDULE
(REFERENCE ONLY; NO CHANGES)
4
4
4
4
444
EXHAUST FAN (EF-6)
(1.1 FLA PER NEC)
1/2
MCP
480VAC POWER
FROM PANEL HVP3
CKT 31,33,35
H1 H2 H3 H4
X1 X2 X3
CPT
480-120VAC
FUSE FUSE
FUSE
EXHAUST FAN MOTOR CONTROL SCHEMATIC
M EOL
EOL
H
RUNNING
R
M
EOL
H
OVERLOAD
A
30.5mm, 2-POS (Ma-Ma), METAL
KNOB, MAINTAIN TYPE 4 RATING
30.5mm, PUSH-TO-TEST
PILOT LIGHT, LED
FULL-VOLTAGE LAMP,
PLASTIC LENS, METAL
BEZEL, MAINTAIN TYPE 4
RATING (TYPICAL)
RESET
JUMPER
NEMA SIZE 0 CONTACTOR
ON OFF
(XO)
ETM
SWITCHED 120VAC CONTROL
POWER TO CONTACTOR
CONTROL PANEL
BATTERY
CHARGER 1
C1
CONTACTOR CONTROL PANEL SCHEMATIC
H N
BATTERY
CHARGER 2
C2
BATTERY
CHARGER 3
C3
BATTERY
CHARGER 4
C4
BATTERY
CHARGER 5
C5
BATTERY
CHARGER 6
C6
BATTERY
CHARGER 7
C7
BATTERY
CHARGER 8
C8
SWITCHED 120VAC SWITCH POWER
FROM EXHAUST FAN MOTOR STARTER
FUSE
C1
A-PH
B-PH
C-PH
480V
AC
P
OW
ER
F
RO
M
480V
P
AN
EL H
VP
3
CK
T 1,3,5
SW
IT
CH
ED
480V
AC
PO
WE
R T
O B
AT
TE
RY
CH
AR
GE
R R
EC
EP
TA
CLE
C2
A-PH
B-PH
C-PH
480V
AC
P
OW
ER
F
RO
M
480V
P
AN
EL H
VP
3
CK
T 2,4,6
SW
IT
CH
ED
480V
AC
PO
WE
R T
O B
AT
TE
RY
CH
AR
GE
R R
EC
EP
TA
CLE
C3
A-PH
B-PH
C-PH
480V
AC
P
OW
ER
F
RO
M
480V
P
AN
EL H
VP
3
CK
T 7,9,11
SW
IT
CH
ED
480V
AC
PO
WE
R T
O B
AT
TE
RY
CH
AR
GE
R R
EC
EP
TA
CLE
C4
A-PH
B-PH
C-PH
480V
AC
P
OW
ER
F
RO
M
480V
P
AN
EL H
VP
3
CK
T 8,10,12
SW
IT
CH
ED
480V
AC
PO
WE
R T
O B
AT
TE
RY
CH
AR
GE
R R
EC
EP
TA
CLE
C5
A-PH
B-PH
C-PH
480V
AC
P
OW
ER
F
RO
M
480V
P
AN
EL H
VP
3
CK
T 13,15,17
SW
IT
CH
ED
480V
AC
PO
WE
R T
O B
AT
TE
RY
CH
AR
GE
R R
EC
EP
TA
CLE
C6
A-PH
B-PH
C-PH
480V
AC
P
OW
ER
F
RO
M
480V
P
AN
EL H
VP
3
CK
T 14,16,18
SW
IT
CH
ED
480V
AC
PO
WE
R T
O B
AT
TE
RY
CH
AR
GE
R R
EC
EP
TA
CLE
C7
A-PH
B-PH
C-PH
480V
AC
P
OW
ER
F
RO
M
480V
P
AN
EL H
VP
3
CK
T 19,21,23
SW
IT
CH
ED
480V
AC
PO
WE
R T
O B
AT
TE
RY
CH
AR
GE
R R
EC
EP
TA
CLE
C8
A-PH
B-PH
C-PH
480V
AC
P
OW
ER
F
RO
M
480V
P
AN
EL H
VP
3
CK
T 20,22,24
SW
IT
CH
ED
480V
AC
PO
WE
R T
O B
AT
TE
RY
CH
AR
GE
R R
EC
EP
TA
CLE
DEFINITE PURPOSE CONTACTOR
WITH 30A CONTACTS
PR
OO
F-O
F-F
LO
W
CR
1
PROOF-OF-FLOW
CR
1
FLOW SWITCH
PROOF-OF-FLOW
(PER MECH PLANS)
PROOF-OF-FLOW
CR1
PROOF-OF-FLOW SIGNAL
TO CONTACTOR
CABINET
4
SHORT CIRCUIT CALCULATION
Fault
Point
Panel/Transformer Description
Source
(Fault
Point)
I (Source
Current)
(amps)
Conduit
Type Cable Type
Wire/Bus Size "C" Value
EL-L
(Volts)
L
(Length)
(FT)
XFMR KVA XFMR %Z f M ISCA
F0 SES
43,490 43,490
F1 MDP F0
43,490
NM 600V 8
SET(S) OF
500 26706 480 19 -- -- 0.014 0.99
42,891
F2 SWBB F1
42,891
NM 600V 2
SET(S) OF
500 26706 480 35 -- -- 0.101 0.91
38,942
F3 480V PANEL HPV1 F2
38,942
NM 600V 1
SET(S) OF
1 7493 480 192 -- -- 3.605 0.22
8,456
F4 208V PANEL LVP1 XFMR PRIMARY F3
8,456
M 600V 1
SET(S) OF
12 617 480 7 -- -- 0.346 0.74
6,282
F5 208V PANEL LVP1 XFMR SECONDARY F4
6,282
-- --
SET(S) OF
208 -- 15 2 6.963 0.13 789
F6 480V PANEL HPV2 F2
38,942
NM 600V 1
SET(S) OF
1 7493 480 78 -- -- 1.463 0.41
15,813
F7 208V PANEL LVP2 XFMR PRIMARY F6
15,813
M 600V 1
SET(S) OF
8 1557 480 7 -- -- 0.257 0.80
12,584
F8 208V PANEL LVP2 XFMR SECONDARY F7
12,584
-- --
SET(S) OF
208 -- 30 2 6.975 0.13
1,578
F9 480V PANEL LPB F2
38,942
NM 600V 1
SET(S) OF
1 7493 480 236 -- -- 4.429 0.18
7,173
F10 208V PANEL RPB1 XFMR PRIMARY F9
7,173
M 600V 1
SET(S) OF
4 3806 480 5 -- -- 0.034 0.97
6,937
F11 208V PANEL RPB1 XFMR SECONDARY F10
6,937
-- --
SET(S) OF
208 -- 30 5.2 9.997 0.09 631
F12 208V PANEL LVP3 XFMR PRI DISCO F9
7,173
NM 600V 1
SET(S) OF
6 2430 480 250 -- -- 2.663 0.27
1,958
F13 208V PANEL LVP3 XFMR SECONDARY F12
1,958
-- --
SET(S) OF
208 -- 45 4.5 1.628 0.38 745
F14 208V PANEL RPD XFMR PRI DISCO F2
38,942
M 600V 1
SET(S) OF
4 3806 480 180 -- -- 6.646 0.13
5,093
F15 208V PANEL RPD XFMR SECONDARY F14
5,093
-- --
SET(S) OF
208 -- 45 6.3 5.928 0.14 735
F16 208V PANEL LVP4 XFMR PRI DISCO F2
38,942
M 600V 1
SET(S) OF
2/0 10755 480 310 -- -- 4.050 0.20
7,711
F17 208V PANEL LVP4 XFMR SECONDARY F16
7,711
-- --
SET(S) OF
208 -- 30 2 4.274 0.19
1,462
F18 480V PANEL HVP3 F2
38,942
M 600V 2
SET(S) OF
3/0 12844 480 595 -- -- 3.255 0.24
9,153
F19 480V PANEL LPC F2
38,942
NM 600V 1
SET(S) OF
4/0 16673 480 160 -- -- 1.352 0.43
16,557
F20 208V PANEL RPB XFMR PRIMARY F19
16,557
M 600V 1
SET(S) OF
6 2425 480 10 -- -- 0.246 0.80
13,284
F21 208V PANEL RPB XFMR SECONDARY F20
13,284
-- --
SET(S) OF
208 -- 30 2 7.363 0.12
1,589
F22 480V PANEL LPCA F19
16,557
M 600V 1
SET(S) OF
6 2425 480 7 -- -- 0.172 0.85
14,122
F23 480V PANEL LPD F2
38,942
M 600V 1
SET(S) OF
4/0 15082 480 228 -- -- 2.124 0.32
12,465
F24 208V PANEL RPC XFMR PRIMARY F23
12,465
M 600V 1
SET(S) OF
4 3806 480 10 -- -- 0.118 0.89
11,147
F25 208V PANEL RPC XFMR SECONDARY F24
11,147
-- --
SET(S) OF
208 -- 45 2 4.119 0.20
2,178
F26 SWBA1/SWBA2 F1
42,891
NM 600V 2
SET(S) OF
500 26706 480 35 -- -- 0.101 0.91
38,942
F27 480V PANEL LPA2 F26
38,942
M 600V 1
SET(S) OF
3/0 12844 480 35 -- -- 0.383 0.72
28,160
F28 208V PANEL RPA2 XFMR PRIMARY F27
28,160
M 600V 1
SET(S) OF
2 5907 480 10 -- -- 0.172 0.85
24,027
F29 208V PANEL RPA2 XFMR SECONDARY F28
24,027
-- --
SET(S) OF
208 -- 75 5.19 13.823 0.07
1,621
F30 480V PANEL LPA F26
38,942
M 600V 1
SET(S) OF
3/0 12844 480 37 -- -- 0.405 0.71
27,721
F31 208V PANEL RPA XFMR PRIMARY F30
27,721
M 600V 1
SET(S) OF
2 5907 480 5 -- -- 0.085 0.92
25,557
F32 208V PANEL RPA XFMR SECONDARY F31
25,557
-- --
SET(S) OF
208 -- 75 3.6 10.199 0.09
2,282
F33
F34 480V PANEL LPE F26
38,942
M 600V 1
SET(S) OF
4/0 15082 480 228 -- -- 2.124 0.32
12,465
F35 480V PANEL LPF F26
38,942
M 600V 1
SET(S) OF
500 22185 480 120 -- -- 0.760 0.57
22,125
F36 208V PANEL RPE XFMR PRIMARY F35
22,125
M 600V 1
SET(S) OF
6 2425 480 8 -- -- 0.263 0.79
17,513
F37 208V PANEL RPE XFMR SECONDARY F36
17,513
-- --
SET(S) OF
208 -- 30 2 9.706 0.09
1,636
F38 TRANSFER SWITCH F35
22,125
M 600V 1
SET(S) OF
6 2425 480 70 -- -- 2.305 0.30
6,695
F39 208V PANEL EM XFMR PRI DISCO F38
6,695
M 600V 1
SET(S) OF
10 981 480 10 -- -- 0.246 0.80
5,372
F40 FUSE PANEL EM XFMR SECONDARY F39
5,372
-- --
SET(S) OF
208 -- 9 2.5 12.407 0.07 401
F41 480V PANEL EM F38
6,695
M 600V 1
SET(S) OF
6 2425 480 5 -- -- 0.050 0.95
6,378
F42 MCCA F26
38,942
NM 600V 1
SET(S) OF
500 26706 480 18 -- -- 0.095 0.91
35,573
F43 MCCB F1
42,891
NM 600V 2
SET(S) OF
500 26706 480 30 -- -- 0.087 0.92
39,461
F44 MCCC F1
42,891
NM 600V 2
SET(S) OF
500 26706 480 23 -- -- 0.067 0.94
40,212
F45 MCCD F1
42,891
M 600V 2
SET(S) OF
350 19704 480 30 -- -- 0.118 0.89
38,371
F46 FIRE PUMP CONTROLLER F0
43,490
NM 600V 2
SET(S) OF
3/0 13923 480 300 -- -- 1.691 0.37
16,163
F47 208V PANEL UPS1 F29
1,621
M 600V 1
SET(S) OF
1 7293 208 170 -- -- 0.315 0.76
1,233
F48 BATTERY CONTACTOR PANEL F18
9,153
M 600V 1
SET(S) OF
10 981 480 5 -- -- 0.168 0.86
7,834
VOLTS 120/208V PANEL
UPS1
MAINS: 125A MIB / 110A MIS / 110A MBP
PHASE 3PH, 4 WIRELOCATION LEVEL 02 - COMP/TELCO RM BUS 225A
A.I.C. 10KA IC MIN FED FROM LPA2 VIA TRANSFORMER MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
NORTH IDF PDU 20 2
1 1250
20 2 EAST IDF PDU
1250 2
3 1250
1250 4
SOUTH IDF PDU 20 2
5 1250
20 2 MDF PDU - 2
1250 6
7 1250
1250 8
SPACE
9 --
20 1 RECEPT - TELCO
360 10 2
SPACE
11 --
20 1 RECEPT - ACCESS CONTROL
360 12
MDF PDU - 1 20 2
13 1250
20 2 MDF PDU - 3
1250 14
15 1250
1250 16
SPACE
17 --
20 2 MDF PDU - 4
1250 18
SPACE
19 --
1250 20
SPACE
21 --
SPACE
-- 22
SPACE
23 --
SPACE
-- 24
SPACE
25 --
SPACE
-- 26
SPACE
27 --
SPACE
-- 28
SPACE
29 --
SPACE
-- 30
SPACE
31 --
SPACE
-- 32
SPACE
33 --
SPACE
-- 34
SPACE
35 --
SPACE
-- 36
18220 VA - 3PH TOTAL CONNECTED 8750 5360 4110
0
VA - CONTINUOUS X 0.25 (*)
= 0 VA
360
VA - GP RECEPTS X (**)
= 360 VA
17860 VA - NON-CONTIN X 1.00 = 17860 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)
26250
FEEDER TOTAL (VA) (***)
(** 100% OF FIRST 10KW + 50% OF BALANCE)
2 TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
73 LARGEST PHASE CURRENT 11/15/2017 8:16
COMMENT:
MIB
208VAC, 3-PHASE
POWER FROM PANEL
RPA2 CKT 18,20,22
MBP MBOUPS
120/208V LOADS (REFER TO
208V PANEL UPS1
SCHEDULE
DATE:
DRAWN BY:
CHECKED BY:
CEE PROJECT #:
Original drawings remain the property
of the Engineer and as such the
Engineer retains total ownership and
control. The design represented by
these drawings is sold to the client for
a one time use, unless otherwise
agreed upon in writing by the Engineer.
© Controlled Energy Engineers LLC 2017
654321
E
D
C
B
A
CONTROLLED ENERGY
ENGINEERS, LLC
2451 W BIRCHWOOD AVE, #104
MESA, AZ 85202
PHONE: 480.621.5933
Know what's below.before you dig.Call
1-800-782-5348
THIS DRAWING IS A COMPILATION BASED ON INFORMATION FROM, BUT NOT
LIMITED TO, DRAWINGS FROM PREVIOUS PROJECTS:
THIS DRAWING MUST BE FIELD VERIFIED BEFORE USE
DRAWING NOT TO SCALE UNLESS SCALE BAR IS PRESENT
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
# Date Revision
2/2/2017 3:58:55 P
M
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
NE
W P
HO
EN
IX
A
Z. F
AC
IL
IT
Y R
EM
OD
EL
PERMIT SET
# Date Revision
17002
ZEW
CEE
MAR 13, 2017
,
S
WILSTERMAN
E
n
r
e
ig
e
R
s
t
D
g
O
a
A
e
i
S
t
Z
I
R
e
A
n
N
d
.
U
ZANE E.
P
d
e
I
r
T
R
E
C
s
s
o
f
e
li
n
F
I
o
T
AC
a
E
l
A
.
.
)
e
.
ir
cal
c
t
E
(
O
i
N
g
e
r
e
n
39548
EXPIRES 09-30-2018
3-13-17
1 4-27-17 2ND CITY
SUBMITTAL
2 6-1-17 3RD CITY
SUBMITTAL
3 7-12-17 RAIL DOCK
BATTERY
CHARGING
4 11-15-17 3000A SES
CONTROL
SCHEMATICS
E160
OVERSIZED CPT TO
SIMULTANEOUSLY CLOSE ALL
DEFINITE PURPOSE CONTACTORS
A. CONTRACTOR SHALL OBTAIN NECESSARY PERMITS AND INSPECTIONS REQUIRED BY THE GOVERNING
AUTHORITIES.
B. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ADOPTED (OR CURRENT WHERE NONE HAVE
BEEN ADOPTED) BUILDING CODES: 2012 IBC, 2012 IECC, 2012 IRC, 2012 IFC, 2012 IMC, 2012 IPMC, 2012 IPC,
2012 IFGC, 2011 NEC, ALL APPLICABLE LOCAL CODES, ORDINANCES AND AMENDMENTS.
C. ALL WORK SHALL BE DONE IN A NEAT, WORKMANLIKE, FINISHED AND SAFE MANNER UNDER COMPETENT
SUPERVISION.
D. ALL MATERIALS SHALL BE NEW AND OF THE BEST QUALITY, MANUFACTURED IN ACCORDANCE WITH
NEMA, ANSI, U.L. OR OTHER APPLICABLE STANDARDS. THE USE OF MANUFACTURER'S NAMES, MODELS
AND NUMBERS IS INTENDED TO ESTABLISH STYLE, QUALITY, APPEARANCE, USEFULNESS AND BID PRICE.
PROPOSED SUBSTITUTIONS SHALL BE SUBMITTED IN WRITING AND REVIEWED BY THE ENGINEER PRIOR
TO MATERIAL PROCUREMENT.
E. ALL ELECTRICAL EQUIPMENT SHALL BE CAPABLE OF OPERATING SUCCESSFULLY AT FULL-RATED LOAD,
WITHOUT FAILURE, AT AN AMBIENT AIR TEMPERATURE OF 0°F TO 120°F AND AN ELEVATION OF 1,200 FEET
(ABOVE SEA LEVEL). WHERE THESE CRITERIA CANNOT BE MET, ANCILLARY EQUIPMENT AND/OR SPECIAL
DERATING FACTORS AS APPROVED BY THE ENGINEER SHALL BE UTILIZED.
F. PROTECT ALL ELECTRICAL MATERIAL AND EQUIPMENT INSTALLED UNDER THIS CONTRACT AGAINST
DAMAGE BY OTHER TRADES, WEATHER CONDITIONS OR ANY OTHER CAUSES. EQUIPMENT FOUND
DAMAGED OR IN OTHER THAN NEW CONDITION WILL BE REJECTED AS DEFECTIVE.
G. LEAVE THE SITE CLEAN. REMOVE ALL DEBRIS, EMPTY CARTONS, TOOLS, CONDUIT, WIRE SCRAPS AND
ALL MISCELLANEOUS SPARE EQUIPMENT AND MATERIALS USED IN THE WORK DURING CONSTRUCTION.
ALL COMPONENTS SHALL BE FREE OF DUST, GRIT AND FOREIGN MATERIALS BEFORE FINAL
ACCEPTANCE OF WORK.
H. THESE CONSTRUCTION DRAWINGS ARE SUBJECT TO THE INTERPRETATION OF THE DESIGN ENGINEER.
ALL QUESTIONS REGARDING THESE CONSTRUCTION DOCUMENTS SHALL BE BROUGHT TO THE
ENGINEER. ANYONE WHO TAKES UPON THEMSELF THE INTERPRETATION OF THESE CONSTRUCTION
DOCUMENTS OR MAKES REVISIONS TO THE SAME WITHOUT CONFERRING WITH THE DESIGN ENGINEER
SHALL BE RESPONSIBLE FOR THE CONSEQUENCES THEREOF.
I. REFER TO OTHER PLANS FOR EXACT LOCATION OF EQUIPMENT AND ARCHITECTURAL FEATURES.
J. ALL WIRING SHALL BE COPPER UNLESS OTHERWISE NOTED. INSULATION SHALL BE TYPE XHHW OR
THWN. NONMETALIC-SHEATHED CABLE WILL NOT BE PERMITTED.
K. ALL WIRING DEVICES AND ELECTRICAL EQUIPMENT SHALL BE COMMERCIAL GRADE.
L. VERIFY EXACT LOCATION, MOUNTING HEIGHT AND ELECTRICAL REQUIREMENTS OF ALL EQUIPMENT
PROVIDED BY OTHERS PRIOR TO ROUGH-IN. PROVIDE ALL ASSOCIATED EQUIPMENT FOR PROPER
OPERATION AND FINAL CONNECTIONS TO EQUIPMENT PER OWNER.
M. PROVIDE GROUND WIRE IN ALL RACEWAYS SIZED PER NEC ARTICLE 250. INSTALL 250-LB PULL CORD IN
ALL EMPTY CONDUITS INSTALLED AS PART OF THIS PROJECT.
N. ALL UNDERGROUND CONDUIT TO BE SCHEDULE 40 PVC. MINIMUM DEPTH SHALL BE 24", MINIMUM SIZE
3/4". ALL EXPOSED CONDUIT SHALL BE TYPE GRS OR IMC, MINIMUM SIZE 3/4".
O. CONDUIT SHALL BE BURIED A MINIMUM OF 24-INCHES BELOW FINISHED GRADE TO TOP OF CONDUIT(S).
WHERE CONDUIT STUBS UP OUT OF THE EARTH TO ELECTRICAL EQUIPMENT, THE CONDUIT SWEEP AND
CONDUIT LEAVING THE EARTH MUST BE PVC COATED GRS CONDUIT OR RIGID STEEL CONDUIT WRAPPED
WITH 20-MIL RUBBER TAPE HALF-LAPPED TO A THICKNESS OF 40-MILS.
P. ALL CIRCUIT CONDUCTORS, #6 AWG OR SMALLER, SHALL BE "THHN/THWN-2" OR "XHHW" STRANDED
COPPER. ALL OTHER CONDUCTORS SHALL BE "XHHW" STRANDED COPPER. MINIMUM CONDUCTOR SIZE
SHALL BE #12 AWG WITH #12 AWG GROUND FOR POWER CIRCUITS.
GENERAL NOTES
ELECTRICAL ABBREVIATIONS
A, AMP AMP(S), AMPERE(S)
AC ALTERNATING CURRENT MC MANUFACTURER CABLE
AIC AMPS INTERRUPTING CAPACITY MCC MOTOR CONTROL CENTER
AFF ABOVE FINISHED FLOOR MCP MOTOR CIRCUIT PROTECTOR
AFG ABOVE FINISHED GRADE MECH MECHANICAL
AICAMPS INTERRUPTING CAPACITY, SYMM. MFR(S) MANUFACTURER(S)
AL ALUMINUM MH MANHOLE
ARCH
ARCHITECT(URAL)
MIC MICROPHONE
ASYM ASYMMETRICAL MIN MINIMUM
ATS AUTOMATIC TRANSFER SWITCH MISC MISCELLANEOUS
AUTO AUTOMATIC MLO MAIN LUG ONLY
AUX AUXILIARY MOV MOTOR OPERATED VALVE
AWG AMERICAN WIRE GAUGE MPC MINI-POWER CENTER
BC BARE COPPER MPR MOTOR PROTECTION RELAY
BLDG BUILDINGMV, mV MEDIUM VOLTAGE, MILLIVOLT
BOT BOTTOM MVMC MEDIUM VOLTAGE MOTOR CONTROL
CCONDUCTOR, CONDUIT
N.C. NORMALLY CLOSED
CB CIRCUIT BREAKER N.O. NORMALLY OPEN
CKT CIRCUIT N/A NOT APPLICABLE
CLG CEILINGNEUT, N
NEUTRAL
CMU CONCRETE MASONRY UNIT NF NON-FUSED
CNTL CONTROL NG NATURAL GAS
CONC CONCRETE NIC NOT IN CONTRACT
CPT CONTROL POWER TRANSFORMER No. NUMBER
CSI COMMUNICATION SYSTEM INSTALLER NOM NOMINAL
CT CURRENT TRANSFORMER NP NAMEPLATE
Cu COPPER NTS NOT TO SCALE
CV CONTROL VALVE OD OUTSIDE DIAMETER
DB DIRECT BURIAL OH OVERHEAD
DCDIRECT CURRENT, DATA CABLE
OIT OPERATOR INTERFACE TERMINAL
DET DETAIL OL OVERLOAD
DIAG DIAGRAM OWS OPERATOR WORKSTATION
DISC DISCONNECT PBPUSHBUTTON, PULLBOX
DIST DISTRIBUTION PKG'D PACKAGED
DWG DRAWING PMM POWER MONITORING MODULE
(E), (N)
EXISTING / NEW PNL PANEL
EA EACH PP POWER PANEL
EDB ELECTRICAL DUCTBANK PR PAIR
ELECELECTRIC, ELECTRICAL
PRI PRIMARY
ELP EXTRA LONG POND PT POTENTIAL TRANSFORMER
EMH ELECTRICAL MANHOLE PVC POLYVINYL CHLORIDE
ENCLENCLOSURE, ENCLOSED
PWR POWER
EP EXPLOSION PROOF RCPT RECEPTACLE
EPB ELECTRICAL PULLBOX PVC POLYVINYL CHLORIDE
EQUIP EQUIPMENT PW POTABLE WATER
FFUSE, FUSED
PWR POWER
FDR FEEDER RCPT RECEPTACLE
FL FLUORESCENT REF REFERENCE
FLA FULL LOAD AMPS REQ'D REQUIRED
FO FIBER OPTIC REQ'TS REQUIREMENTS
FVNR FULL VOLTAGE NON-REVERSING RMS ROOT MEAN SQUARE
FVR FULL VOLTAGE REVERSING RTU REMOTE TERMINAL UNIT
GDR GROUNDING RESISTOR RVNS REDUCED VOLTAGE NON-REVERSING
GEC GROUNDING ELECTRODE CONDUCTOR RVSS REDUCED VOLTAGE SOFT STARTER
GF GROUND FAULT SA SURGE ARRESTOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER SCR SILICON CONTROLLED RECTIFIER
GFP GROUND FAULT PROTECTION SD SMOKE DETECTOR
GND GROUND SEC SECONDARY
GRS GALVANIZED RIGID STEEL SES SERVICE ENTRANCE SECTION
H, HIHIGH SPEC SPECIFICATION
HMI HUMAN MACHINE INTERFACE SPC SPARE CONDUIT
HP HORSEPOWER SPD SURGE PROTECTION DEVICE
HTR HEATER SSI SECURITY SYSTEM INSTALLER
HTU HEAT TRACE UNIT SSS SOLID-STATE SOFT STARTER
HZ
HERTZ (CYCLES PER SECOND)
ST SHORT TIME
ICOM INTERCOM SWBD SWITCHBOARD
ID INSIDE DIAMETER SWGR SWITCHGEAR
INSTINSTANTANEOUS, INSTRUMENT
SYMM SYMMETRICAL
INTLK INTERLOCK SYS SYSTEM
IPB INSTRUMENT PULLBOX TELCO TELEPHONE COMPANY
JB JUNCTION BOX TEMP TEMPERATURE
KCMIL 1000 CIRCULAR MILS TSP TWISTED SHIELDED PAIR
kV KILOVOLT TST TWISTED SHIELDED TRIAD
kVA KILOVOLT-AMPERE TTB TELEPHONE TERMINAL BOARD
Kvar KILOVOLT-AMPERE REACTIVE TYP TYPICAL
KW KILOWATT UG U/G UNDERGROUND
KWH KILOWATT-HOUR UPS UNINTERRUPTIBLE POWER SUPPLY
LLONG, LENGTH
V VOLT
LAN LOCAL AREA NETWORK VA VOLT-AMPERE
LCP LOCAL CONTROL PANEL VAR VOLT-AMPERE REACTIVE
LCS LOCAL CONTROL STATION VC VACUUM CONTACTOR
LFMC LIQUIDTIGHT FLEXIBLE METAL CONDUT VD VOLTAGE DROP
LT LONG TIME WWATT, WIRE, WIDE
LTG LIGHTING WAN WIDE AREA NETWORK
LV LOW VOLTAGE WP WEATHERPROOF
mA MILLIAMPERE WPWIU WEATHERPROOF WHILE-IN-USE
MAG MAGNETIC XMTR TRANSMITTER
MBJ MAIN BONDING JUMPER Z IMPEDANCE
ELECTRICAL PLAN SYMBOLS
IDENTIFICATION SYMBOLS
XX
#
#
#X
INDICATES KEY NOTE # REFERENCED,
(APPLICABLE ONLY TO SHEET WITH NOTE
IS FOUND)
INDICATES BILL OF MATERIAL #
REFERENCED, (MAY BE APPLICABLE
ACROSS ALL PROJECT SHEETS)
INDICATES BRIEF INSTRUMENT
REFERENCE
INDICATES MISCELLANEOUS REFERENCE
NUMBER OR LETTER (DESCRIBED
FURTHER WITHIN PLANSET WHERE
APPLICABLE)
CXXXX
CONDUIT IDENTIFICATION
(#### = CONDUIT NUMBER,
REFER TO CONDUIT SCHEDULE)
RACEWAYS AND LINETYPES
GROUNDING SYSTEM CONDUCTOR
EXPOSED CONDUIT
UTILITY CONDUIT DUCTBANK
CONDUIT TURNED DOWN
CONDUIT STUBUP
EXISTING CONCEALED CONDUIT
CONDUIT RUN CONCEALED IN
CEILING, FLOOR, OR IN WALLS
GGG
XXXX
XXXX
EXISTING EXPOSED CONDUIT
UNDERGROUND CONDUIT
DUCTBANK
EXISTING UNDERGROUND CONDUIT
DUCTBANK
EXISTING UTILITY CONDUIT
DUCTBANK
OHEOHE
OHEOHE
CHAIN LINK FENCE
EXISTING CHAIN LINK FENCE
UTILITY OVERHEAD ELECTRIC
EXISTING UTILITY OVERHEAD
ELECTRIC
GROUNDING
GROUND SYSTEM CONNECTION
GGG
G
LIGHTNING ROD
GROUND ROD AND WELL
GROUND ROD WITHOUT WELL
RECEPTACLES
SWITCH AND SIMPLEX RECEPTACLE
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE
DUPLEX RECEPTACLE WITH SPLIT WIRE
QUADRAPLEX RECEPTACLE
RECESSED FLOOR DUPLEX RECEPTACLE
RECESSED FLOOR QUADRAPLEX RECEPTACLE
SPECIALTY PURPOSE RECEPTACLE
480V RECEPTACLE
WELDING OR APPLIANCE RECEPTACLE
#
x
S
#
x
#
x
#
x
#
x
#
x
#
x
#
x
#
x
#
x
WHERE,
# = CIRCUIT DESIGNATION
x = DEVICE TYPE DESIGNATION, WHERE
GF = GROUND FAULT CIRCUIT INTERRUPTER
WP = WEATHERPROOF
WPWIU = WP WHILE-IN-USE
SWITCHES
SINGLE POLE SWITCH
SINGLE POLE SWITCH WITH MODIFIER
WHERE,
# = CIRCUIT DESIGNATION
x1 = DESIGNATION OF DEVICE SWITCHED (I.E. a, b, c, etc.)
x2 = SWITCH SUBSCRIPT MODIFIER, WHERE
2 = GROUND FAULT CIRCUIT INTERRUPTER
3 = WEATHERPROOF
4 = WP WHILE-IN-USE
K = KEY OPERATED
M = HORSEPOWER RATED MANUAL STARTER
MC = MOMENTARY CONTACT, THREE POSITION
MO = SWITCH WITH MOTION SENSOR
MS = MANUAL (MOTOR) STARTER OR SWITCH
TC/P = TIME CLOCK / PROGRAMMABLE
R = RHEOSTAT (DIMMER OR SPEED CONTROL)
F = FLUSH MOUNTED
WP = WEATHERPROOF
HOMERUN
MISCELLANEOUS
xx UNDERGROUND BOX
xx = BOX TYPE/DESIGNATION (I.E. EMH, EPB, IPB)
SAFETY SWITCH
xx = DISCONNECT TYPE (I.E. F, NF, CB)
#A = CURRENT RATING OF SWITCH
xx
#A
COMBINATION MOTOR STARTER
LOCAL/PUSHBUTTON CONTROL STATION
IDENTIFICATION SYMBOLS
a
b
c
d
e
f
LOW VOLTAGE CIRCUIT BREAKER
a = BREAKER DESIGNATION
b = AMPS & TRIP SETTING
(AT - AMP TRIP)
(AC - CONTINUOUS RATING)
c = FRAME SIZE (MFR TO
DETERMINE FRAME SIZE UNLESS
INDICATED)
d = BREAKER TYPE
MCP - MOTOR CIRCUIT
PROTECTOR
SS - SOLID-STATE
TM - THERMAL MAGNETIC
e = NUMBER OF POLES
f = WITHSTAND RATING
LOW VOLTAGE DISCONNECT SWITCH
a = DISCONNECT DESIGNATION
b = AMPS RATING
c = NUMBER OF POLES
d = ENCLOSURE RATING (IF
MOUNTED IN SEPARATE ENCL) (I.E.
NEMA 1, 12, 3R, 4X, 7)
e = WITHSTAND RATING
a
b
c
d
f
a
b
FUSE
a = AMPS RATING
b = FUSE TYPE
MOTOR STARTER
a = STARTER SIZE
b = STARTER TYPE (NEMA/IEC)
a
b
OVERLOAD RELAY
a = OVERLOAD TYPE (I.E. OL, EOL)
a
M <UTILITY>
POWER
METER
UTILITY
METER
HP
MOTOR
HP = HORSEPOWER RATING
ONE LINE DIAGRAM
SYMBOLS
DESCRIPTION
120V, 2'x4' FLUORESCENT LUMINAIRE, GRID/LAY-IN MOUNT,
SPECIFICATION GRADE T8 TROFFER, FLAT WHITE STEEL DOOR,
UNIVERSAL VOLTAGE, ELECTRONIC START BALLAST.
** IN KITCHEN, PROVIDE WITH A125INV LENS, G2 GASKET (INVERTED
LENS WITH FRAME).
LUMINAIRE SCHEDULE
SYMBOL LAMP(S) FIXTURE MANUFACTURER
METALUX (2GC8-232A-UNV-EB81 + FRAME/LENS OPTIONS
IN KITCHEN)
(2) 32W T8
FLUORESCENT
LAMPS
120V, 2'x4' FLUORESCENT LUMINAIRE, GRID/LAY-IN MOUNT,
SPECIFICATION GRADE T8 TROFFER, FLAT WHITE STEEL DOOR,
UNIVERSAL VOLTAGE, ELECTRONIC START BALLAST. INCLUDE
EMERGENCY BATTERY PACK.
** PROVIDE WITH A125INV LENS, G2 GASKET (INVERTED LENS WITH
FRAME).
METALUX (2GC8-232A-UNV-EB81 + BATTERY PACK +
FRAME/LENS OPTIONS)
x1 #
x1 #
x2
A
B
BP
(2) 2W
AC LED
LAMPS
OS OCCUPANCY SENSOR
SP SWITCHPACK / POWER SUPPLY
SURE-LITES (APX6-R)120V, AC ONLY LED, ALL-PRO EXIT, RED.
EXIT
(2) 32W T8
FLUORESCENT
LAMPS
(3) 32W T8
FLUORESCENT
LAMPS
METALUX (2GC8-332A-UNV-EB81 + FRAME/LENS OPTIONS IN
KITCHEN)
C
120V, 2'x4' FLUORESCENT LUMINAIRE, GRID/LAY-IN MOUNT,
SPECIFICATION GRADE T8 TROFFER, FLAT WHITE STEEL DOOR,
UNIVERSAL VOLTAGE, ELECTRONIC START BALLAST.
** IN KITCHEN, PROVIDE WITH A125INV LENS, G2 GASKET (INVERTED
LENS WITH FRAME).
DATE:
DRAWN BY:
CHECKED BY:
CEE PROJECT #:
Original drawings remain the property
of the Engineer and as such the
Engineer retains total ownership and
control. The design represented by
these drawings is sold to the client for
a one time use, unless otherwise
agreed upon in writing by the Engineer.
© Controlled Energy Engineers LLC 2017
654321
E
D
C
B
A
CONTROLLED ENERGY
ENGINEERS, LLC
2451 W BIRCHWOOD AVE, #104
MESA, AZ 85202
PHONE: 480.621.5933
Know what's below.before you dig.Call
1-800-782-5348
THIS DRAWING IS A COMPILATION BASED ON INFORMATION FROM, BUT NOT
LIMITED TO, DRAWINGS FROM PREVIOUS PROJECTS:
THIS DRAWING MUST BE FIELD VERIFIED BEFORE USE
DRAWING NOT TO SCALE UNLESS SCALE BAR IS PRESENT
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
PH
OE
NIX
, A
Z. K
IT
CH
EN
B
UIL
D-O
UT
# Date Revision
2/2/2017 3:58:55 P
M
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
PERMIT SET
# Date Revision
17002
ZEW
CEE
AUG 21, 2017
,
S
WILSTERMAN
E
n
r
e
ig
e
R
s
t
D
g
O
a
A
e
i
S
t
Z
I
R
e
A
n
N
d
.
U
ZANE E.
P
d
e
I
r
T
R
E
C
s
s
o
f
e
li
n
F
I
o
T
AC
a
E
l
A
.
.
)
e
.
ir
cal
c
t
E
(
O
i
N
g
e
r
e
n
39548
EXPIRES 09-30-2018
10-17-17
1 10-17-17 2ND CITY
SUBMITTAL
ELECTRICAL
COVER
SHEET
E100
ELECTRICAL SHEET INDEX
E100 ELECTRICAL COVER SHEET
E101 ELECTRICAL BUILDING PLAN
E102 LEVEL 02 - ELECTRICAL KITCHEN PLAN
E103 SINGLE LINE DIAGRAM
E104 PANEL SCHEDULES
1
1
1
3
3
4
4
B4
B
5
5
7
7
6
6
8
8
9
9
10
10
11
11 12 13 14 15 16 17 18 19 20 21 22
23
23
23.2
23.2
24
24
25
25
26
26
26.6 27
27
29
29
30
30
31
31
32
3222.8 23.6" 26.2 26.9 28 30.6 31.4
B1
B7
B8
B9
C
D1
E
F
G
H
I
J
K1
L1
F-01
C2 C1
C3C3
RB
RC RD
RE
C1
C1
C1
C2 C2
C2 C2
C2 C2
C1 C2 C2
C1 C2 C2
C1 C2 C2
C1 C2 C2
C1 C2 C2
C1 C2 C2
C1
C1
P5
P5
P5
P5
P5
P5
P3P3
P3P3
P3P3
P3P3
P3P3
P3P3
P3P3
P3P3
P3P3
P3P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P3
P5
P5
P5
P5
P5
P5
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P5
P5
P5
P5
P5
P5
P5
P5
P5
P5
P5
P5
P5
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
FA FB FC FD FE FF
C3 C3C3
C2C2 C2 C2
C2 C2
C2 C2
C1
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C2 C2
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C2 C2 C2 C3
C4
C1
C2 C2 C2 C3
C4
C1
C2 C2 C2 C3
C4
C1
C2 C2 C2 C3
C4
C1
C4
C2 C2 C2 C3
C4
C1
C2 C2 C2 C3
C4
C1
C2 C2 C2 C3
C4
C1
C2 C2 C2 C3
C4
C1
C2 C2 C2 C3
C4
C1
C2 C2 C2 C3
C4
C1
C2 C2 C2 C3
C4
C1
C4
C4
C2 C2 C2 C3C1
C4
C4
C2 C2 C2 C3C1 C4
C2 C2 C2 C3C1 C4
C2 C2 C2 C3C1 C4
C2 C2 C2 C3C1 C4
C2 C2 C2 C3C1 C4
C2 C2 C2 C3C1 C4
C2 C2 C2 C3C1 C4
C2 C2 C2 C3C1 C4
C2 C2 C2 C3C1 C4
C4
C4
RARF
C2 C1
C2 C1
C2 C1
C2 C1
C2 C1
C2 C1
C2 C1
C2 C1
C2 C1
C2
C3
C1
C2 C1 C1
C2 C1 C1
C2 C1 C1
C2 C1 C1
C2 C1 C1
C2 C1 C1
C2 C1 C1
C2 C1 C1
C2 C1 C1
C2 C1 C1
C2 C1 C1
DR
C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3
DQDPDNDMDLDKDJDHDGDFDDDCDBDA DEC4C1C1C2C2
C2C2C2
C2C2C2C2C1C1C2C2C2C2C2C2C2C2C2
P4
C4C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2C2C2C2C2C2C2
C4C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2C2C2C2C2C2C2
C4C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2C2C2C2C2C2C2
C4C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2C2C2C2C2C2C2
C4C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2C2C2C2C2C2C2
C4C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2C2C2C2C2C2C2
C4C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2C2C2C2C2C2C2
C4C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2C2C2C2C2C2C2
C4C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2C2C2C2C2C2C2
C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2
C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2
C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2
C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2
C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2
C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2
C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2
C1C1C2C2C2
C2C2C2
C2C2C2C1C1C2C2C2
C1C1C2C2
C1C1C2C2
C1C1C2C2
C1C1C2C2
C1C1C2C2
C2
C2
C2
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C1C1
C1C1
C1C1
C1C1
C1C1
C1C1
C1C1
C1C1
C1C1
C1C1
C2C2C2C2C2C2
C2C2C2C2C2C2
C1C1
C2C2C2C2C2C2
C1C1
C2C2C2C2C2C2
C1C1
C2C2C2C2C2C2
C1C1
C2C2C2C2C2C2
C1C1
C2C2C2C2C2C2
C1C1
C2C2C2C2C2C2
C1C1
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C3 C3 C3 C3 C3C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3 C3
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
P5
P5
PIR
C1C1
PIR
PIRPIR
PIRPIR
PIRPIR
PIRPIR
PIRPIR
PIRPIR
PIRPIR
PIRPIR
PIRPIR
PIRPIR
PIRPIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
PIR
C3C3
C3C3
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
C2
C2
C2
C2
C2
C2
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C2
P3
P4
P4
C1
DATE:
DRAWN BY:
CHECKED BY:
CEE PROJECT #:
Original drawings remain the property
of the Engineer and as such the
Engineer retains total ownership and
control. The design represented by
these drawings is sold to the client for
a one time use, unless otherwise
agreed upon in writing by the Engineer.
© Controlled Energy Engineers LLC 2017
654321
E
D
C
B
A
CONTROLLED ENERGY
ENGINEERS, LLC
2451 W BIRCHWOOD AVE, #104
MESA, AZ 85202
PHONE: 480.621.5933
Know what's below.before you dig.Call
1-800-782-5348
THIS DRAWING IS A COMPILATION BASED ON INFORMATION FROM, BUT NOT
LIMITED TO, DRAWINGS FROM PREVIOUS PROJECTS:
THIS DRAWING MUST BE FIELD VERIFIED BEFORE USE
DRAWING NOT TO SCALE UNLESS SCALE BAR IS PRESENT
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
PH
OE
NIX
, A
Z. K
IT
CH
EN
B
UIL
D-O
UT
# Date Revision
2/2/2017 3:58:55 P
M
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
PERMIT SET
# Date Revision
17002
ZEW
CEE
AUG 21, 2017
,
S
WILSTERMAN
E
n
r
e
ig
e
R
s
t
D
g
O
a
A
e
i
S
t
Z
I
R
e
A
n
N
d
.
U
ZANE E.
P
d
e
I
r
T
R
E
C
s
s
o
f
e
li
n
F
I
o
T
AC
a
E
l
A
.
.
)
e
.
ir
cal
c
t
E
(
O
i
N
g
e
r
e
n
39548
EXPIRES 09-30-2018
10-17-17
1 10-17-17 2ND CITY
SUBMITTAL
ELECTRICAL
BUILDING
PLAN
E101
N
0 2 1
SCALE 1/16" = 1'
1
GENERAL NOTES KEY NOTES
1
2
EXISTING 480V PANEL "LPCA" (LEVEL 01)
EXISTING 480V PANEL "HVP2" (LEVEL 01) AND 208V PANEL "LVP2" (LEVEL 01)
A. CONTRACTOR SHALL SUBMIT AS-BUILT DRAWINGS TO ENGINEER AND OWNER.
B. REFER TO SHEET E100 FOR ADDITIONAL GENERAL NOTES.
C. REFER TO SHEET E100 FOR LUMINAIRE SCHEDULE.
D. REFER TO SHEET E102 FOR LEVEL 02 KITCHEN POWER AND LIGHTING PLANS.
E. REFER TO SHEET E103 FOR SINGLE LINE DIAGRAM.
F. REFER TO SHEET E104 FOR PANEL SCHEDULES.
LEVEL 01 EXISTING
ELECTRICAL EQUIPMENT
INDICATED ON THIS SHEET
REFER TO SHEET E102 FOR
LEVEL 02 KITCHEN REMODEL
LIGHTING AND POWER PLANS
1
2
Utility
Cabinet
DATE:
DRAWN BY:
CHECKED BY:
CEE PROJECT #:
Original drawings remain the property
of the Engineer and as such the
Engineer retains total ownership and
control. The design represented by
these drawings is sold to the client for
a one time use, unless otherwise
agreed upon in writing by the Engineer.
© Controlled Energy Engineers LLC 2017
654321
E
D
C
B
A
CONTROLLED ENERGY
ENGINEERS, LLC
2451 W BIRCHWOOD AVE, #104
MESA, AZ 85202
PHONE: 480.621.5933
Know what's below.before you dig.Call
1-800-782-5348
THIS DRAWING IS A COMPILATION BASED ON INFORMATION FROM, BUT NOT
LIMITED TO, DRAWINGS FROM PREVIOUS PROJECTS:
THIS DRAWING MUST BE FIELD VERIFIED BEFORE USE
DRAWING NOT TO SCALE UNLESS SCALE BAR IS PRESENT
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
PH
OE
NIX
, A
Z. K
IT
CH
EN
B
UIL
D-O
UT
# Date Revision
2/2/2017 3:58:55 P
M
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
PERMIT SET
# Date Revision
17002
ZEW
CEE
AUG 21, 2017
,
S
WILSTERMAN
E
n
r
e
ig
e
R
s
t
D
g
O
a
A
e
i
S
t
Z
I
R
e
A
n
N
d
.
U
ZANE E.
P
d
e
I
r
T
R
E
C
s
s
o
f
e
li
n
F
I
o
T
AC
a
E
l
A
.
.
)
e.
ir
cal
c
t
E
(
O
i
N
g
e
r
e
n
39548
EXPIRES 09-30-2018
10-17-17
1 10-17-17 2ND CITY
SUBMITTAL
LEVEL 02 -
KITCHEN
ELECTRICAL
PLAN
E102
N
0 2 1
SCALE 1/4" = 1'
1
PROCUREMENT
STORAGE
TEST
KITCHEN
MENS WOMENS JAN.
TRAINING
SALES MTG.
LVP2-12
GFCI
KEY NOTES
GENERAL NOTES
A. CONTRACTOR SHALL SUBMIT AS-BUILT DRAWINGS TO ENGINEER AND OWNER.
B. REFER TO SHEET E100 FOR ADDITIONAL GENERAL NOTES.
C. REFER TO SHEET E100 FOR LUMINAIRE SCHEDULE.
D. REFER TO SHEET E103 FOR SINGLE LINE DIAGRAM.
E. REFER TO SHEET E104 FOR PANEL SCHEDULES.
F. REFER TO SHEET E101 FOR PANEL LOCATIONS THAT MAY BE REFERRED TO ON THIS
SHEET BUT NOT INDICATED.
G. FURNISH AND INSTALL CONDUITS, FITTINGS, PULL BOXES, ETC. AS REQUIRED FOR
LIGHTING AND RECEPTACLE BRANCH CIRCUIT NUMBERS INDICATED. USE #12 AWG
CONDUCTORS WITH #12 AWG GROUND FOR 20A AND 15A CIRCUITS. USE #10 AWG
CONDUCTORS WITH #10 AWG GROUND FOR 30A CIRCUITS. DO NOT EXCEED SIX
CURRENT CARRYING CONDUCTORS PER CONDUIT.
H. CONDUITS SHALL BE CONCEALED WHERE POSSIBLE.
I. LIGHT SWITCHES SHALL BE FLUSH MOUNTED AT 42" ABOVE FINISHED FLOOR.
J. RECEPTACLES SHALL BE MOUNTED FLUSH MOUNTED AT 18" ABOVE FINISHED FLOOR.
1ROOF MOUNTED HP-9. INSTALL 600VAC, 30A FUSED DISCONNECT SWITCH.
DISCONNECT SWITCH ENCLOSURE SHALL HAVE TYPE 3R RATING. INSTALL FUSES
SIZED PER HVAC MFR RECOMMENDATIONS. INSTALL 3-#10, #10 GND, 1"C. CIRCUIT TO
PANEL HPV2-12,14,16.
F
30A
1
3ROOF MOUNTED EXHAUST FAN (EF-K1 / EXH-1). REFER TO POWER LINE DIAGRAM ON
THIS SHEET FOR CONDUIT AND CONDUCTOR REQUIREMENTS. REFER TO
MECHANICAL PLANS FOR ADDITIONAL INFORMATION.
4ROOF MOUNTED EXHAUST FAN (EF-K2 / EXH-2). REFER TO POWER LINE DIAGRAM ON
THIS SHEET FOR CONDUIT AND CONDUCTOR REQUIREMENTS. REFER TO
MECHANICAL PLANS FOR ADDITIONAL INFORMATION.
LOBBY
HALL
LVP2-15
LV
P2-15 HP-9
2MOUNTED ON ROOF NEXT TO AIR CONDITIONING UNIT.
SHADED AREA REPRESENTS
LEVEL 02 AREA BEING
REMODELED ABOVE
EXISTING BUILDING FOOTPRINT
2
LVP2-10
GFCI
RPD-15
GFCI
PROCUREMENT
STORAGE
KITCHEN
MEN
WOMEN
JAN.
TRAINING
SALES MTG.
44
MO
B
LPC-28BP
45
A
LPCA-28
47
A
LPCA-28
47
B
LPC-32BP
47
A
LPCA-28
47
43
MO
45
MO
42
MO
46
MO
A
LP
CA
-28
42
LOBBY
HALL
A
LPCA-28
47
C
LPCA-28
45
A
LPCA-28
47
LP
C-3
2
EX
IT
A
LP
CA
-28
46
A
LPCA-28
43
A
LPCA-28
44
LP
C-3
2
EX
IT
LEVEL 02 KITCHEN
AND STORAGE
AREAS REMODEL
INDICATED
ON THIS SHEET
LIGHTING AND RECEPTACLES IN
PROCUREMENT, RESTROOMS,
JANITOR CLOSET, LOBBY, HALL
AND TRAINING AREAS PROVIDED
UNDER SEPARATE PERMIT
HOOD
5ROOF MOUNTED EVAPORATIVE COOLER / MAKEUP AIR UNIT (BLOWER AND
SOLENOID)(MAU-K3 / SUP-1). REFER TO POWER LINE DIAGRAM ON THIS SHEET FOR
CONDUIT AND CONDUCTOR REQUIREMENTS. REFER TO MECHANICAL PLANS FOR
ADDITIONAL INFORMATION.
MAU-K3
6HOOD SYSTEM CONTROL PANEL. REFER TO POWER LINE DIAGRAM ON THIS SHEET
FOR ADDITIONAL WIRING REQUIREMENTS. REFER TO MECHANICAL PLANS FOR
ADDITIONAL INFORMATION.
7INSTALL 240V, 30A, 2P, TYPE 1 DISCONNECT SWITCH FOR CONVEYOR OVEN. CIRCUIT
TO PANEL RPD-20,22.
8SNAP SWITCH FOR HOOD LIGHTS AND FAN(S).
CONTROL
POWER
(RPD-38)
EF-K1 / EXH-1
POWER
RPD-31,33,35
EF-K2 / EXH-2
POWER
RPD-37,39,41
MAU-K3 / SUP-1
POWER
RPD-32,34,36
HOOD SYSTEM CONTROL PANEL
VFD VFD VFD
1.5 1 1.5
S
2-#12, #12 GND, 3/4"C 3-#12, #12 GND, 3/4"C 3-#12, #12 GND, 3/4"C 5-#12, #12 GND, 3/4"C
6-#12, #12 GND, 3/4"C5-#12, #12 GND, 3/4"C
TO HOOD
LIGHTS
8
7
8
2-#12, #12 GND, 3/4"C
6
6
6
5
3
4
RPD-7
GFCI
RPD-5
GFCI
RPD-3
GFCI
EXHAUST FAN
EF-K1
(EXH-1)
EXHAUST FAN
EF-K2
(EXH-2)
EXHAUST FAN
MAU-K3
(SUP-1)
MAKEUP AIR UNIT
REFER TO M604 FOR
ADDITIONAL SIGNAL
REQUIREMENTS
HOOD SYSTEM POWER LINE DIAGRAM
KITCHEN POWER PLAN
KITCHEN LIGHTING PLAN
C
LP
CA
-28
42
9INSTALL 120V, 20A SNAP SWITCH NEXT TO WATER HEATER TO SERVE AS
DISCONNECTING MEANS.
9
WH-2
(RPD-1)
10
(TYP 9)
10EXISTING LUMINAIRE PROVIDED UNDER SEPARATE PERMIT.
11HOOD LIGHT - PACKAGED WITH HOOD (REFER TO MECHANICAL PLANS FOR
ADDITIONAL INFORMATION)
11
(TYP)
LVP2-8
GFCI
1
12INSTALL 240V, 30A, 2P, TYPE 1 DISCONNECT SWITCH FOR ICE MAKER. CIRCUIT TO
PANEL RPD-8,10.
12
1
1
1
13
1
13INSTALL 240V, 30A, 2P, TYPE 4 DISCONNECT SWITCH FOR DISH WASHER. CIRCUIT
TO PANEL RPD-11.
1 10
1 10
1 10
1
1
T-3
45KVA
480V
208V
3PH
EXISTING
208V PANEL
"RPD"
100A
3P
45KVA
480V
208V
3PH
EXISTING
208V PANEL
"LVP3"
60A
3P
15KVA
480V
208V
3PH
EXISTING
208V PANEL
"LVP1"
EXISTING
480V PANEL
"HVP1"
15KVA
480V
208V
3PH
EXISTING
208V PANEL
"RPB1"
EXISTING
480V PANEL
"LPB"
XFMR-T2
30KVA
480V
208V
3PH
EXISTING
208V PANEL
"RPB"
EXISTING
480V PANEL
"LPC"
EXISTING
480V PANEL
"LPCA"
(E) 480V, 3∅, 4W, 3000A
SERVICE FROM SRP
(SCA = 43,490A)
N
G
(E) SES
M
(E) SRP METER #
SPD
(E) GROUNDING
SYSTEM
1200A
3P
800A
3P
800A
3P
800A
3P
800A
3P
800A
3P
TO FIRE PUMP
(407HP)
MCCD
(CB-5)
SWBB MCCC SWBA MCCB
EXISTING
480V PANEL
"EM"
(E
) S
TA
ND
BY
G
EN
ER
AT
OR
FROM SES
(E) SWBD "SWBB"
M
100A
3P
100A
3P
100A
3P
100A
3P
100A
3P
400A
3P
M M M M M
MLO
400A
3P
200A
3P
200A
3P
SPACE
(E) SWBD "TE"
EXISTING
480V PANEL
"LPE"
EXISTING
480V PANEL
"LPD"
EXISTING
208V PANEL
"RPC"
RPA2-XFMR
75KVA
480V
208V
3PH
EXISTING
208V PANEL
"RPA2"
EXISTING
480V PANEL
"LPA2"
FROM SES
(E) SWBD "SWBA1"
200A
3P
200A
3P
200A
3P
(E) SWBD "SWBA2"
SPACE SPACE
400A
3P
MCCA
400A
3P
45KVA
480V
208V
3PH
30KVA
480V
208V
3PH
EXISTING
208V PANEL
"LVP2"
EXISTING
480V PANEL
"HVP2"
EXISTING
480V PANEL
"LPF"
T-4
30KVA
480V
208V
3PH
EXISTING
208V PANEL
"RPE"
SPARE
F3
F4
F0
F2 F5
F6
F1
REFER TO PANEL
SCHEDULE FOR
MODIFICATIONS
REFER TO PANEL
SCHEDULE FOR
MODIFICATIONS
REFER TO PANEL
SCHEDULE FOR
MODIFICATIONS
NOTE: ALL EQUIPMENT INDICATED
ON THIS SHEET IS EXISTING.
MODIFICATIONS TO PANELBOARDS
HAVE BEEN INDICATED HEREIN.
SPACE SPACE
T-4
9KVA
480V
208V
3PH
EXISTING
FUSE PANEL
"EM"
30A
3P
10A
3P
T-4
30KVA
480V
240V
3PH
EXISTING
240V PANEL
"LVP4"
60A
3P
50A
100A
3P
EXISTING TRANSFER
SWITCH
75KVA
480V
208V
3PH
EXISTING
208V PANEL
"RPA"
EXISTING
480V PANEL
"LPA"
EXISTING
208V PANEL
"RPAA"
EXISTING
480V PANEL
"HPV3"
REFER TO PANEL
SCHEDULE FOR
MODIFICATIONS
F7
F8
F9
EXISTING #8
CONDUCTORS
EXISTING #2
CONDUCTORS
EXISTING #1
CONDUCTORS
EXISTING #1
CONDUCTORS
100A
EXISTING #2/0
CONDUCTORS
EXISTING #3/0
CONDUCTORS
EXISTING #6
CONDUCTORS
SHORT CIRCUIT CALCULATION
Fault
Point
Panel/Transformer Description
Source
(Fault
Point)
I (Source
Current)
(amps)
Conduit
Type Cable Type
Wire/Bus Size "C" Value
EL-L
(Volts)
L
(Length)
(FT)
XFMR KVA XFMR %Z f M ISCA
F0 SES
43,490 43,490
F1 SWBB F0
43,490
NM 600V 2
SET(S) OF
500 26706 480 35 -- -- 0.103 0.91
39,435
F2 480V PANEL HPV2 F1
39,435
NM 600V 1
SET(S) OF
1 7493 480 86 -- -- 1.635 0.38
14,967
F3 208V PANEL LVP2 XFMR PRIMARY F2
14,967
M 600V 1
SET(S) OF
8 1557 480 10 -- -- 0.347 0.74
11,113
F4 208V PANEL LVP2 XFMR SECONDARY F3
11,113
-- --
SET(S) OF
208 -- 30 4.5 13.858 0.07 748
F5 480V PANEL LPC F1
39,435
NM 600V 1
SET(S) OF
3/0 13923 480 160 -- -- 1.639 0.38
14,940
F6 480V PANEL LPCA F5
14,940
M 600V 1
SET(S) OF
6 2425 480 10 -- -- 0.222 0.82
12,223
F7 RPD XFMR DISCO F1
39,435
M 600V 1
SET(S) OF
1 7293 480 188 -- -- 3.668 0.21
8,448
F8 208V PANEL RPD XFMR PRIMARY F7
8,448
M 600V 1
SET(S) OF
1 7293 480 10 -- -- 0.042 0.96
8,109
F9 208V PANEL RPD XFMR SECONDARY F8
8,109
-- --
SET(S) OF
208 -- 45 4.5 6.741 0.13
1,047
1
1
1
1
1
1
1
DATE:
DRAWN BY:
CHECKED BY:
CEE PROJECT #:
Original drawings remain the property
of the Engineer and as such the
Engineer retains total ownership and
control. The design represented by
these drawings is sold to the client for
a one time use, unless otherwise
agreed upon in writing by the Engineer.
© Controlled Energy Engineers LLC 2017
654321
E
D
C
B
A
CONTROLLED ENERGY
ENGINEERS, LLC
2451 W BIRCHWOOD AVE, #104
MESA, AZ 85202
PHONE: 480.621.5933
Know what's below.before you dig.Call
1-800-782-5348
THIS DRAWING IS A COMPILATION BASED ON INFORMATION FROM, BUT NOT
LIMITED TO, DRAWINGS FROM PREVIOUS PROJECTS:
THIS DRAWING MUST BE FIELD VERIFIED BEFORE USE
DRAWING NOT TO SCALE UNLESS SCALE BAR IS PRESENT
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
PH
OE
NIX
, A
Z. K
IT
CH
EN
B
UIL
D-O
UT
# Date Revision
2/2/2017 3:58:55 P
M
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
PERMIT SET
# Date Revision
17002
ZEW
CEE
AUG 21, 2017
,
S
WILSTERMAN
E
n
r
e
ig
e
R
s
t
D
g
O
a
A
e
i
S
t
Z
I
R
e
A
n
N
d
.
U
ZANE E.
P
d
e
I
r
T
R
E
C
s
s
o
f
e
li
n
F
I
o
T
AC
a
E
l
A
.
.
)
e
.
ir
cal
c
t
E
(
O
i
N
g
e
r
e
n
39548
EXPIRES 09-30-2018
10-17-17
1 10-17-17 2ND CITY
SUBMITTAL
SINGLE
LINE
DIAGRAM
E103
1
1
VOLTS 120/208V PANEL
RPD
(EXISTING)
MAIN 150A MCB
PHASE 3PH, 4 WIRELOCATION LEVEL 02 - UTILITY ROOM BUS 225A
A.I.C. 10KA IC MIN FED FROM SWBD "TE" MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
WATER HEATER (WH-2)
(CONNECT TO EXISTING
BREAKER)
20 1
1 240
30 2
LEVEL 02 HVAC (HP-8)
2316 2
GRIDDLE
(CONNECT TO EXISTING
BREAKER)
20 1
3 120
2316 4
LEVEL 02 FREEZER
(CONNECT TO EXISTING
BREAKER)
20 1
5 1164
20 1
HVAC (HP-8) RECEPT
180 6 1
LEVEL 02 REGRIG
(CONNECT TO EXISTING
BREAKER)
20 1
7 1404
20 2
ICE MAKER
(NEW BREAKER)
1620 8
SPARE 20 1
9 0
1620 10
LEVEL 02 DISH WASHER
(CONNECT TO EXISTING
BREAKER)
20 1
11 1920
20 1 SPARE
0 12
HVAC (HP-5) RECEPT
1
20 2
13 180
20 3
HVAC (HP-1 / 2) RECEPT
180 14 1
HVAC (HP-6, HP-7 & HP-9)
RECEPTS
(ADDED LOAD)
3 15 540
HVAC (HP-3) RECEPT
180 16 1
EXHAUST FANS (EF-3, 4 & 5) 20 1
17 300
HVAC (HP-4) RECEPT
180 18 1
4 PLEX FIRE RISER
2
20 1
19 360
20 2
CONVEYOR OVEN
(NEW BREAKER)
180 20
LEVEL 02 RECEPTS - TELEPHONE
1
20 1
21 180
180 22
LEVEL 02 RECEPTS - FINANCE
4
20 1
23 720
20 1 SPARE
0 24
LEVEL 02 RECEPTS - COMPUTER RM
1
20 1
25 180
20 1 SPARE
0 26
LEVEL 02 RECEPTS - COMPUTER RM
1
20 1
27 180
20 1 SPARE
0 28
SPARE 20 1
29 0
20 1 SPARE
0 30
KITCHEN EXHAUST FAN (EF-K1)
(NEW BREAKER)
15 3
31 828
15 3
KITCHEN MAU FAN (MAU-K3)
(NEW BREAKER)
828 32
33 828
828 34
35 828
828 36
KITCHEN EXHAUST FAN (EF-K2)
(NEW BREAKER)
15 3
37 576
15 1
HOOD SYS CONTROL PANEL
(NEW BREAKER)
250 38
39 576
40 2
LEVEL 02 HVAC (DSO-1 / DSI-1)
2880 40
41 576
2880 42
29146 VA - 3PH TOTAL CONNECTED 9142 10428 9576
0
VA - CONTINUOUS X 0.25 (*)
= 0 VA
3060
VA - GP RECEPTS X (**)
= 3060 VA
26086 VA - NON-CONTIN X 1.00 = 26086 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)
31284
FEEDER TOTAL (VA) (***)
(** 100% OF FIRST 10KW + 50% OF BALANCE)
17 TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
87 LARGEST PHASE CURRENT 10/16/2017 8:03
COMMENT:
EXISTING 208V PANEL RPD SCHEDULE
EXISTING 480V PANEL LPCA SCHEDULE
EXISTING 480V PANEL HVP2 SCHEDULE
VOLTS 277/480V PANEL
LPCA
(EXISTING)
MAIN MLO
PHASE 3PH, 4 WIRELOCATION MAINT ROOM BUS 225A
A.I.C. 14KA IC MIN FED FROM LPC MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
LEVEL 02 HVAC (HP-4) 15 3
1 3019
15 3
FREEZER DOOR - (FD3)
368 2 1
3 3019
506 4 1
5 3019
506 6 1
LEVEL 02 HVAC (HP-5) 15 3
7 2853
15 3
FREEZER DOOR - (FD4)
506 8
9 2853
506 10
11 2853
506 12
SPARE 15 3
13 0
15 3
FREEZER DOOR - (FD5)
506 14
15 0
506 16
17 0
506 18
SPARE 15 3
19 0
15 3
FREEZER DOOR - BACK (SE DOCK)
506 20
21 0
506 22
23 0
506 24
SPACE
25 --
15 3
LEVEL 02 LTS - MID
2560 26 1
27 --
LEVEL 02 LTS - SOUTH
(REDUCED LOAD)
3040 28 1
29 --
LEVEL 02 LTS - NORTH
2480 30 1
SPACE
31 --
SPACE
0 32
33 --
0 34
35 --
0 36
SPACE
37 --
SPACE
-- 38
SPACE
39 --
SPACE
-- 40
SPACE
41 --
SPACE
-- 42
31631 VA - 3PH TOTAL CONNECTED 10318 10936 10376
9460
VA - CONTINUOUS X 0.25 (*)
= 2365 VA
22171 VA - NON-CONTIN X 1.00 = 22171 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)
35174FEEDER TOTAL (VA) (***)
0
TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
42
LARGEST PHASE CURRENT
10/16/2017 8:04
COMMENT:
VOLTS 277/480V PANEL
HVP2
(EXISTING)
MAIN 100A MCB
PHASE 3PH, 4 WIRELOCATION
COLD DOCK (NEAR STAIRS)
BUS 100A
A.I.C. 35KA IC MIN FED FROM SWBD "TE" MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
PANEL MAIN BREAKER 100 3
1 --
SPACE
-- 2
3 --
20 2 SPARE
0 4
5 --
0 6
SPARE 20 1
7 0
20 1
DRY WH LTS (ROWS DQ/DR)
1440 8 1
SPARE 20 1
9 0
20 1 SPARE
0 10 1
FREEZER DOOR
1
15 3
11 1000
20 3
LEVEL 02 HVAC (HP-9)
(CONNECT TO EXISTING
SPARE BREAKER)
3435 12
1 13 1000
3435 14
1 15 1000
3435 16
SPARE 20 3
17 0
40 3 PANEL LVP2 TRANSFORMER
4440 18
19 0
4440 20
21 0
4440 22
SPARE 20 3
23 0
15 3
LEVEL 02 HVAC (HP-7)
2853 24
25 0
2853 26
27 0
2853 28
SPACE
29 --
SPACE
-- 30
36624 VA - 3PH TOTAL CONNECTED 13168 11728 11728
4440
VA - CONTINUOUS X 0.25 (*)
= 1110 VA
32184 VA - NON-CONTIN X 1.00 = 32184 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)
40614
FEEDER TOTAL (VA) (***)
0 TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
49 LARGEST PHASE CURRENT 10/16/2017 8:03
COMMENT:
480V, 3PH LOAD CALCULATIONS
LOAD DESCRIPTION KVA H.P. AMPS
FIRE PUMP -- 250 302.0
SWITCHBOARD (SWBA)
727.8
480V PANEL LPA2 66.0 -- 79.4
480V PANEL LPA 55.6 -- 66.9
480V PANEL LPE ** EXISTING - NO CHANGES ** 18.0 -- 21.7
480V PANEL LPF ** EXISTING - NO CHANGES ** 217.3 -- 261.4
MOTOR CONTROL CENTER (MCCA) ** EXISTING - NO CHANGES **
298.5
FREEZER FAN D2-A -- 2 3.4
FREEZER FAN D2-A -- 2 3.4
FREEZER FAN D2-B -- 2 3.4
FREEZER FAN D2-B -- 2 3.4
FREEZER FAN D3-A -- 2 3.4
FREEZER FAN D3-A -- 2 3.4
FREEZER FAN D3-B -- 2 3.4
FREEZER FAN D3-B -- 2 3.4
FREEZER FAN D4-A -- 2 3.4
FREEZER FAN D4-A -- 2 3.4
FREEZER FAN D4-B -- 2 3.4
FREEZER FAN D4-B -- 2 3.4
FREEZER FAN D5-A -- 2 3.4
FREEZER FAN D5-A -- 2 3.4
FREEZER FAN D5-B -- 2 3.4
FREEZER FAN D5-B -- 2 3.4
FREEZER FAN D6-A -- 2 3.4
FREEZER FAN D6-A -- 2 3.4
FREEZER FAN D6-B -- 2 3.4
FREEZER FAN D6-B -- 2 3.4
FREEZER FAN D1-C -- 2 3.4
FREEZER FAN D1-B -- 1 1.8
FREEZER FAN D1-A -- 1 1.8
UNDER FLR VENT FAN -- 2 3.4
EF-2 VENT FAN -- 1 1.8
MAINTENANCE ROOM EXHAUST FAN -- 0.5 1.0
GLYCOL PUMP 1 -- 1.5 2.6
GLYCOL PUMP 2 -- 1.5 2.6
PURGE PUMP -- 3 4.8
AMMONIA PUMP 1 -- 3 4.8
WATER JACKET PUMP 1 -- 3 4.8
WATER JACKET PUMP 2 (BACKUP)
-- 3 0.0
AMMONIA PUMP -- 5 7.6
AMMONIA PUMP -- 5 7.6
CONDENSOR PUMP -- 5 7.6
CONDENSOR PUMP -- 5 7.6
DOCK HOLDING COND FAN (AC-1)
-- 1 1.8
DOCK HOLDING COND FAN (AC-2)
-- 1 1.8
DOCK HOLDING COND FAN (AC-3)
-- 1 1.8
DOCK HOLDING COND FAN (AC-4)
-- 1 1.8
DOCK HOLDING COND FAN (AC-5)
-- 1 1.8
DOCK HOLDING COND FAN (AC-6)
-- 1 1.8
BLAST FREEZER (B-1) (7.5 HP) <REMOVED>
-- 0 0.0
BLAST FREEZER (B-1) (7.5 HP) <REMOVED>
-- 0 0.0
BLAST FREEZER (B-2) (7.5 HP) <REMOVED>
-- 0 0.0
BLAST FREEZER (B-2) (7.5 HP) <REMOVED>
-- 0 0.0
ROOF CONDENSOR FAN -- 10 14.0
ROOF CONDENSOR FAN -- 10 14.0
AMMONIA PUMP -- 3 4.8
ROOF CONDENSOR HEATER 18 -- 21.7
ROOF CONDENSOR HEATER 18 -- 21.7
BLAST FREEZER #3 (2 X 7.5 HP) <REMOVED>
-- 0 0.0
BLAST FREEZER #4 (2 X 7.5 HP) <REMOVED>
-- 0 0.0
FREEZER EVAPORATOR #1 -- 7.5 11.0
FREEZER EVAPORATOR #2 -- 7.5 11.0
FREEZER EVAPORATOR #3 -- 7.5 11.0
FREEZER EVAPORATOR #4 -- 7.5 11.0
FREEZER EVAPORATOR #5 -- 7.5 11.0
DOCK EVAPORATOR #1 -- 3 4.8
DOCK EVAPORATOR #2 -- 3 4.8
DOCK EVAPORATOR #3 -- 3 4.8
FREEZER EVAPORATOR #6 -- 7.5 11.0
SWITCHBOARD (SWBB)
580.6
480V PANEL LPC 109.2 -- 131.4
480V PANEL LPD 37.4 -- 45.0
480V PANEL HVP3 197.9 -- 238.0
208V PANEL LVP4 TRANSFORMER 1.5 -- 1.8
SWITCHBOARD (TE)
164.5
480V PANEL HVP1 19.5 -- 23.4
480V PANEL HVP2 36.6 -- 44.1
480V PANEL LPB 50.6 -- 60.9
208V PANEL RPD TRANSFORMER 30.0 -- 36.1
MOTOR CONTROL CENTER (MCCB) ** EXISTING - NO CHANGES **
0.0
CP-3B (STANDBY)
-- 100 0.0
CP-4B (STANDBY)
-- 100 0.0
CP-3 (STANDBY)
-- 150 0.0
CP-4 (STANDBY)
-- 150 0.0
MOTOR CONTROL CENTER (MCCC) ** EXISTING - NO CHANGES **
608.0
CP-1B (DUTY)
-- 100 124.0
CP-2B (DUTY)
-- 100 124.0
CP-1 (DUTY)
-- 150 180.0
CP-2 (DUTY)
-- 150 180.0
MOTOR CONTROL CENTER (MCCD) ** EXISTING - NO CHANGES **
0.0
CP-5 (STANDBY)
-- 407 0.0
SURGE PROTECTION DEVICE 0 -- 0.0
SUBTOTAL = 2252.4
+25% OF CONTINUOUS LIGHTING LOADS = 45.2
+25% OF LARGEST MOTOR (407HP) =
75.5
MINIMUM SERVICE SIZE = 2373.1
EXISTING SERVICE SIZE = 3000A
EXISTING 208V PANEL LVP2 SCHEDULE
VOLTS 120/208V PANEL
LVP2
(EXISTING)
MAIN 50A MCB
PHASE 3PH, 4 WIRELOCATION
COLD DOCK (NEAR STAIRS)
BUS 60A
A.I.C. 10 KA IC MIN FED FROM HVP2 VIA TRANSFORMER MOUNTING SURFACE
LOAD
DESCRIPTION
VA LOAD
LOAD
DESCRIPTION
LTG REC MTR AMP P NO. A B C NO. AMP P MTR REC LTG
SPARE 30 2
1 0
100 3P PANEL MAIN
480 2
3 0
900 4
LEVEL 02 RECEPTS - TRAINING / SALES
8
20 1
5 1440
0 6
LEVEL 02 RECEPTS - TRAINING / SALES
8
20 1
7 1260
20 1
LEVEL 02 RECEPT - DF
(RE-PURPOSED BREAKER)
180 8
1
LEVEL 02 RECEPTS - PROCUREMENT
4
20 1
9 720
20 1
LEVEL 02 RECEPT
(RE-PURPOSED BREAKER)
180 10
1
LEVEL 02 RECEPTS - OFFICE (ED)
3
20 1
11 540
20 1
LEVEL 02 RECEPT
(RE-PURPOSED BREAKER)
180 12
1
LEVEL 02 RECEPTS - PROCUREMENT
6
20 1
13 1080
20 1 SPARE
0 14
STORAGE ROOM RECEPTS
(RE-PURPOSED BREAKER)
2
20 1
15 360
20 1 SPARE
0 16
LEVEL 02 RECEPTS - DSM
4
20 1
17 720
20 1 SPARE
0 18
LEVEL 02 RECEPTS - FUTURE (RM 229)
8
20 1
19 1440
20 1 SPARE
0 20
SPARE 20 1
21 0
20 1 SPARE
0 22
SPARE 20 1
23 0
20 1 SPARE
0 24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
9480 VA - 3PH TOTAL CONNECTED 4440 2160 2880
0
VA - CONTINUOUS X 0.25 (*)
= 0 VA
8280
VA - GP RECEPTS X (**)
= 8280 VA
1200 VA - NON-CONTIN X 1.00 = 1200 VA
(* INCLUDES LIGHTING & LARGEST MOTOR)
13320
FEEDER TOTAL (VA) (***)
(** 100% OF FIRST 10KW + 50% OF BALANCE)
46 TOTAL RECEPTACLES
(*** THREE TIMES LARGEST PHASE + 25% OF CONTINUOUS - 50% OF REC VA OVER 10KVA)
37.0 LARGEST PHASE CURRENT 10/16/2017 8:03
COMMENT:
1
DATE:
DRAWN BY:
CHECKED BY:
CEE PROJECT #:
Original drawings remain the property
of the Engineer and as such the
Engineer retains total ownership and
control. The design represented by
these drawings is sold to the client for
a one time use, unless otherwise
agreed upon in writing by the Engineer.
© Controlled Energy Engineers LLC 2017
654321
E
D
C
B
A
CONTROLLED ENERGY
ENGINEERS, LLC
2451 W BIRCHWOOD AVE, #104
MESA, AZ 85202
PHONE: 480.621.5933
Know what's below.before you dig.Call
1-800-782-5348
THIS DRAWING IS A COMPILATION BASED ON INFORMATION FROM, BUT NOT
LIMITED TO, DRAWINGS FROM PREVIOUS PROJECTS:
THIS DRAWING MUST BE FIELD VERIFIED BEFORE USE
DRAWING NOT TO SCALE UNLESS SCALE BAR IS PRESENT
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
PH
OE
NIX
, A
Z. K
IT
CH
EN
B
UIL
D-O
UT
# Date Revision
2/2/2017 3:58:55 P
M
455 S
OU
TH
75T
H A
VE
.
PH
OE
NIX
, A
Z 85043
PE
RF
OR
MA
NC
E F
OO
D G
RO
UP
PERMIT SET
# Date Revision
17002
ZEW
CEE
AUG 21, 2017
,
S
WILSTERMAN
E
n
r
e
ig
e
R
s
t
D
g
O
a
A
e
i
S
t
Z
I
R
e
A
n
N
d
.
U
ZANE E.
P
d
e
I
r
T
R
E
C
s
s
o
f
e
li
n
F
I
o
T
AC
a
E
l
A
.
.
)
e
.
ir
cal
c
t
E
(
O
i
N
g
e
r
e
n
39548
EXPIRES 09-30-2018
10-17-17
1 10-17-17 2ND CITY
SUBMITTAL
PANEL
SCHEDULES
E104
1
1
1