generator commissioning

Upload: sam

Post on 05-Apr-2018

239 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/31/2019 Generator Commissioning

    1/90

    Generator

    Commissioning

    - SUBODH KUMAR

  • 7/31/2019 Generator Commissioning

    2/90

    GENERAL INSPECTION AND CHECKS

    Ensure that erection work of the

    Generator and associated equipments are

    completed in all respect.

    Check that no part of Generator, Exciter,

    Bus-duct, CT, PT, Terminal Bushings,

    Marshalling Boxes, equipment is damaged.

    Ensure safe and satisfactory access to the

    equipments.

  • 7/31/2019 Generator Commissioning

    3/90

    Ensure fire protection system is

    adequate.

    Check that painting work is satisfactory.

    Check that Name Plate Details areavailable, labeling and identification is

    permanent and satisfactory.

    Check that permanent and adequate

    lighting arrangements are made.

  • 7/31/2019 Generator Commissioning

    4/90

    Carefully examine the Generator Stator

    core, winding, Rotor body, slip-ringsand all other associated equipment forany kind of abnormality, dents, or any

    physical damage.

    Ensure the quality certificate andfactory inspection and test reports areavailable.

  • 7/31/2019 Generator Commissioning

    5/90

    Ensure that all the RTDs installed are

    functioning properly.

  • 7/31/2019 Generator Commissioning

    6/90

    TESTING OF GENERATOR

    Laboratory tests and

    Field tests to evaluate theinsulation condition of statorwindings of generator.

  • 7/31/2019 Generator Commissioning

    7/90

    Laboratory tests

    Laboratory tests have two functions:

    The first function is to evaluate thequality of coil manufacturing to ensure

    that your machine can achieveexpected service lifetime.

    The second function is to examine

    any faults and defects of your statorcoils to prevent catastrophic machinefailures.

  • 7/31/2019 Generator Commissioning

    8/90

    Field tests

    Field tests provide diagnostic tests andcondition assessment of machine

    insulation at your plant to help you todetermine maintenance requirements toreduce maintenance cost.

  • 7/31/2019 Generator Commissioning

    9/90

    Laboratory Diagnostic

    Tests of Stator WindingInsulation

  • 7/31/2019 Generator Commissioning

    10/90

    Laboratory tests include:

    Voltage Endurance test Thermal Cycling Dissection of Coils

    Insulation Failure Analysis Partial Discharge test Dissipation Factor Turn-to-Turn Multi-Factor Stress Forensic Analysis

  • 7/31/2019 Generator Commissioning

    11/90

    voltage endurance test

    A voltage endurance test is an acceleratedinsulation-aging test. The test is performedon stator bars or coils at much higher thannormal operation stress levels within a shortperiod of time to simulate insulation agingduring machine operation.

    The test can predict the performance of theoverall insulation system and measure the

    manufacturing quality. A number of diagnostic tests on stator

    insulation can be conducted before and aftera voltage endurance test.

  • 7/31/2019 Generator Commissioning

    12/90

    voltage endurance test Manufacturers of stator insulation could

    change its design, type of materials, andthe manufacturing process.

    The voltage endurance test can be done atthe prototype and production stage toensure the quality consistency duringmanufacturing. The test gives objectiveassessment of the quality of stator insulation.

    If coils fail the test, a remedial action may betaken by the manufacturer to improve thequality of coil manufacturing.

  • 7/31/2019 Generator Commissioning

    13/90

    voltage endurance test

    Voltage endurance tests can be applied toboth new coils and spare coils to check

    the quality and performance of theinsulation system. Spare coils have beenstored for a long period of time and need

    to be tested to check their performance.

  • 7/31/2019 Generator Commissioning

    14/90

    A set-up of the voltageendurance testing

  • 7/31/2019 Generator Commissioning

    15/90

    Insulation failure during a voltageendurance test at 280 hours

  • 7/31/2019 Generator Commissioning

    16/90

    Thermal Cycling Tests and

    Multi-Factor Tests Large motors are exposed to

    frequent start/stop operations.

    Pumped-storage generators andhydro-generators have frequent loadchanges. All of those operations

    cause rapid heating and cooling, i.e.thermal cycling effect on statorinsulation.

  • 7/31/2019 Generator Commissioning

    17/90

    Thermal cycling cancause

    1. Loss of bond between copper andinsulation;

    2. De-lamination and degradation ofground-wall insulation;

    3. Insulation failure.

  • 7/31/2019 Generator Commissioning

    18/90

    A set-up of thermal cycling testing onstator windings

  • 7/31/2019 Generator Commissioning

    19/90

    To assess the insulation performanceunder thermal cycling stress as themachine experiences in service, weperform thermal cycling tests on statorbars and coils according to IEEE

    Standard 1310 -1996 and IECstandards.

    The test insulation system is heatedand cooled at a prescribed rate for a

    number of cycles (e.g. 500 cycles). Anumber of diagnostic tests on statorinsulation can be performed during

    thermal cycling testing.

  • 7/31/2019 Generator Commissioning

    20/90

    When a generator or motor is

    operating, a stator bar or coil is subjectto electrical, mechanical, and thermalstresses simultaneously. Stator winding

    have to test under multifactor(electrical, mechanical, and thermalstresses) stress aging simultaneously tosimulate normal service conditions orconditions as required.

  • 7/31/2019 Generator Commissioning

    21/90

    Thermal cycling test result

  • 7/31/2019 Generator Commissioning

    22/90

    Failure Analysis

    When your stator coils or bars failed

    in service, you want to know whatactually caused insulation failures toprevent future failures. You may need

    expert witness to prove the causes ofinsulation failures.

  • 7/31/2019 Generator Commissioning

    23/90

    Failure Analysis

    Dissections of a bar or coil can determinethe quality of coil manufacturing and the

    causes of insulation failures. The failedcoil or bar will be dissected and examinedunder a computer- controlled microscope.

    The root causes of insulation failures areinvestigated

  • 7/31/2019 Generator Commissioning

    24/90

    Failure Analysis

    The following chemical tests on theinsulation system can be also conductedfor insulation failure analysis:

    Resin content analysis;

    Thermo-gravimetric analysis;

    Thermo-mechanical analysis;

    Fourier transform infraredspectroscopy

  • 7/31/2019 Generator Commissioning

    25/90

    Insulation failure of a 13.8 kV, 44 MWhydro-generator

    ac v y cause e a ove nsu a on

  • 7/31/2019 Generator Commissioning

    26/90

    ac v y cause e a ove nsu a onfailure by dissection and microscopic

    examination

    P i l Di h

  • 7/31/2019 Generator Commissioning

    27/90

    Partial DischargeMeasurements

    Partial discharge (PD), corona inceptionmeasurements provide a non-intrusive indication ofthe void content and other problems, which may bepresent in a stator bar or a coil.

    Partial discharge measurements can identify

    insulation defects which could be caused byimproper impregnation, inadequate resin, voids,or poor consolidation of the insulation.

    These measurements are normally undertaken at the

    rated phase-to-ground voltage. PD specialists canassess insulation condition based on PD test data.

  • 7/31/2019 Generator Commissioning

    28/90

    Generator insulation damage due topartial discharge activity

  • 7/31/2019 Generator Commissioning

    29/90

    FIELD TEST

  • 7/31/2019 Generator Commissioning

    30/90

    TEST PROCEDURE

    1. Generator is disconnected from the

    bus duct.2. Ground all the RTD wires coming

    from the Generator.

    3. Carry out the IR test on the Each

    Phase to Ground separately.(note

    Insulation Tester used and Ambient temp. in deg C.):

  • 7/31/2019 Generator Commissioning

    31/90

    This test is performed injecting a stabilized high DCvoltage and measuring the current after 15seconds to calculate Insulation Resistance (IR).

    We can perform this test between phases orbetween the 3 phases and the ground. IR highlydepends on temperature and must be corrected. Italso depends on the winding class and on thecuring state of the machine.

    IR should be above a minimum value related withthe rated voltage of the generator.

    The Polarization Index (PI) is the ratio between IRafter 10 and after 1. As a ratio, it is almost no

    temperature dependant. The results indicateinsulation contamination, moisture, cracks orfissures in the insulation.

    Standards indicate that this test should be carried

    out before more aggressive tests like Hipot orSur e tests.

  • 7/31/2019 Generator Commissioning

    32/90

    D.C. winding resistance:

    Carry out the D.C. winding resistance

    test of the Stator Winding (each

    phase separately)

  • 7/31/2019 Generator Commissioning

    33/90

    Winding Resistance (DC) [m]- The

    test injects a current and measures theterminal voltage in eachphase. The resultis the pure resistance of each phase andmust be temperature corrected.

    The resistance per phase should be verysimilar between them.

    It gives an indication of the integrity ofthe windings and the connections,indicating shorted turns, looseconnections, wrong connections and open

    circuits.

  • 7/31/2019 Generator Commissioning

    34/90

    FEILD TEST INCLUDE:

    Visual Inspection test Digital ELCID

    PD Data Interpretation and Analysis

    Corona Probe TEST Dissipation Factor (tan delta test)

    AC and DC Hi-pot test

    Wedge Tightness test Core repair, if loose

    Insulation Condition Assessment

  • 7/31/2019 Generator Commissioning

    35/90

    EL CID Test

    Electromagnetic Core ImperfectionDetection (EL CID) is used to checkthe integrity of inter-laminar insulation

    for stator cores of generators.A fault current occurring within the

    laminated stator core results in a hot

    spot and can cause a catastrophicfailure of a generator and motor inservice.

  • 7/31/2019 Generator Commissioning

    36/90

    An EL CID test can

    detect faults and defects in the statorcore;

    check effectiveness of core repairs;test the stator core before and after astator rewind to check any damagescaused by rewind;

    check the quality of a new statorcore;trend the stator core condition.

  • 7/31/2019 Generator Commissioning

    37/90

    EL CID testing on 80 MW hydro-generator

  • 7/31/2019 Generator Commissioning

    38/90

    EL CID testing on a Turbo-generator

  • 7/31/2019 Generator Commissioning

    39/90

  • 7/31/2019 Generator Commissioning

    40/90

  • 7/31/2019 Generator Commissioning

    41/90

  • 7/31/2019 Generator Commissioning

    42/90

  • 7/31/2019 Generator Commissioning

    43/90

  • 7/31/2019 Generator Commissioning

    44/90

  • 7/31/2019 Generator Commissioning

    45/90

    ADVANTAGE OF ELCID TEST

    In comparison with a traditional loop (ringflux) test, an EL CID test offers the followingbenefits:

    Uses a portable excitation transformer

    instead of a large excitation transformer in aloop test to considerably reduce testcost;Saves 30% of test time and labor cost of a

    loop test.

    Conducts low power testing (EL CID usesonly 4% of the rated magnetic flux) to

    avoid further damage to fault areas;

  • 7/31/2019 Generator Commissioning

    46/90

    Does not have safety concerns to

    test personnel;Records test data by a computer

    for trending of test results.

    Provides an easy and in-expensivetest method to check the quality

    of a core repair or a re-wedgingoperation.

  • 7/31/2019 Generator Commissioning

    47/90

    EL CID testing requires goodknowledge of the EL CIDinstrument and stator cores togive a reliable test result.

    O li / ff li PD t t d PD

  • 7/31/2019 Generator Commissioning

    48/90

    On-line/off-line PD tests and PDdata analysis;

    Partial discharge (PD) testing is a recognizedtool to diagnose stator insulationdeterioration and the other related problems.

    The tests can be performed under the on-line condition (when a machine is running) orthe off-line condition (when a machine isstand still).

    On-line PD testing can give early warning ofpotential machine failures and providemachine condition information for predictive

    maintenance.

  • 7/31/2019 Generator Commissioning

    49/90

    WHAT IS PARTIAL DISCHARGE

    PD is a localized electrical discharge( spark) in an electrical system thatdoes not completely bridge the

    electrode.

    Partial discharge (PD) corresponds

    to ionization of gas around or withinsolid insulation.

  • 7/31/2019 Generator Commissioning

    50/90

    This phenomena only occurs at

    higher AC voltage (specially > 3KV).

    Higher the voltage, the more

    destructive the activity. PD is a leading indicator of insulation

    breakdown.

    OFF LINE PD MEASUREMENT

  • 7/31/2019 Generator Commissioning

    51/90

    OFF-LINE PD MEASUREMENT

  • 7/31/2019 Generator Commissioning

    52/90

    OFF LINE PD TESTINGLIMITATION

    Testing does not observe loadchanges

    Testing does not occur atoperating voltage.

    Equipment will not be at ratedtemperature.

  • 7/31/2019 Generator Commissioning

    53/90

    ONLINE PD MEASUREMENT

    The HV couplers are connected to themachine terminals to detect partial

    discharges from the stator winding. A computer-controlled instrument

    measures PD signals detected by the HV

    couplers. PD specialist then analyzes thetest data to provide an insulationdiagnostics report .

  • 7/31/2019 Generator Commissioning

    54/90

  • 7/31/2019 Generator Commissioning

    55/90

    RFCT

    l

  • 7/31/2019 Generator Commissioning

    56/90

    Coupling Capacitor

  • 7/31/2019 Generator Commissioning

    57/90

    The nature, type, region, and severityof PD activity can be identified asfollows through data analysis:

    Slot discharge

    De-laminations

    Internal partial discharge fromvoids

    Grading paint discharge

    Loose windings End winding discharge

    PD Corona

  • 7/31/2019 Generator Commissioning

    58/90

    PD - Corona

  • 7/31/2019 Generator Commissioning

    59/90

    PD t ki

  • 7/31/2019 Generator Commissioning

    60/90

    PD - tracking

  • 7/31/2019 Generator Commissioning

    61/90

    PD- slot Discharge

  • 7/31/2019 Generator Commissioning

    62/90

    EFECT OF PD

    Rise to ozone

    Nascent oxygen (strong oxidizingagent)

    Power loss

    Intense heat in the dischargechannel

  • 7/31/2019 Generator Commissioning

    63/90

    PD ANALYSIS

    Magnitude

    Number density

    Polarity

    Phase angle of occurrence

    Quadratic rate

  • 7/31/2019 Generator Commissioning

    64/90

    WEDGE TIGHTNESS TEST

    This test is done to check the tightness ofslot wedges of stator winding.

    Looseness of wedge due to - shrinkage of slot packing material.

    High mechanical stress

    vibration

  • 7/31/2019 Generator Commissioning

    65/90

    Corona probe measurements

    Corona probe testing can pinpoint partialdischarge location in each slot.

    It supplements on- line/off-line partialdischarge tests by precisely locating partialdischarge to a particular coil or a spot.

    The corona probe can also be used as a

    testing tool to measure levels of PD activity.Corona probe testing can be performed eitherwith the rotor in or out of the machine.

  • 7/31/2019 Generator Commissioning

    66/90

    it is normally a requirement that the rotorsare removed from the stators so that the

    electromagnetic probe can be inserted intothe stator frame. The stator winding isenergized at various voltages up to phase

    voltage. The probe is moved along eachindividual slot and the levels of dischargecurrent are recorded from the peak milli

    ammeter.

  • 7/31/2019 Generator Commissioning

    67/90

    Corona probe testing to pinpoint theexact location of partial discharge activity

  • 7/31/2019 Generator Commissioning

    68/90

    HI POT (DC Leakage currentmeasurement)

    This test applies to the insulation a voltage for 1minute above nominal values. Maintenance testvoltage is less than the factory test voltage. Theresult is generally pass or fail. This test willinsure that the machine will supportextraordinary service conditions but because of

    its aggressiveness, its usually not carried out asa predictive maintenance tool.

    O ( k

  • 7/31/2019 Generator Commissioning

    69/90

    HI POT (DC Leakage currentmeasurement)

    Vdc= 1.6 x (AC test voltage)

    or 1.5 Vph

    (d f )

  • 7/31/2019 Generator Commissioning

    70/90

    Dissipation factor (Tan-Delta) is one of the mostpowerful off-line nondestructive diagnostic toolto monitor the condition of solid insulation ofvarious high voltage equipment.

    By measuring the electrical properties such as

    capacitance and Tan-Delta regularly onperiodical basis, it is possible to ensure theoperational unexpected breakdown.

    TAN DELTA (dissipation factor)TEST

  • 7/31/2019 Generator Commissioning

    71/90

    WHAT IS TAN DELTA

    It represents Di- electric losses concept ofthe insulating material.

    HV

    LV

    INSULATIONELECTRODES

  • 7/31/2019 Generator Commissioning

    72/90

    Perfect Insulation between the two

    electrodes will act as a perfectcapacitor.

    V

    I

    Cp

  • 7/31/2019 Generator Commissioning

    73/90

    Tan = Ir/Ic= loss angle

    = phase angle

    Max allowable

    Tan = 0.03For new machine Ir

    Ic

    V

    I

    T d lt t d

  • 7/31/2019 Generator Commissioning

    74/90

    Tan delta measurement procedure

    Suitable KVA rating transformer

    Equipment should be disconnected

    Kit to be grounded and test voltage israised in steps up to rated phase voltage.

  • 7/31/2019 Generator Commissioning

    75/90

    Measurement Analysis:

    Change in above quantities with machineage.

    Statically variation of the quantities of thesimilar machine.

    CORE LOOSENESS & REPAIR

  • 7/31/2019 Generator Commissioning

    76/90

    CORE LOOSENESS & REPAIR

  • 7/31/2019 Generator Commissioning

    77/90

    TESTING ON ROTOR

  • 7/31/2019 Generator Commissioning

    78/90

    RSO TEST

    AIR PURGE TEST

    INSULATION RESISTANCE TEST

    WINDING RESISTANCE IMPEDENCE TEST

    CC BOLT AIR TIGHTNESS TEST

    DPT & UT OF RETAINING RING

    RSO TEST

  • 7/31/2019 Generator Commissioning

    79/90

    RSO TEST

    RSO test is performed to detect faults inrotor winding.

    Electrical faults in the rotor fall into twomain categories:

    Fault from the winding to the rotor body (Earth fault)

    Fault between parts of the windings ( Inter

    turn winding faults)

  • 7/31/2019 Generator Commissioning

    80/90

  • 7/31/2019 Generator Commissioning

    81/90

  • 7/31/2019 Generator Commissioning

    82/90

  • 7/31/2019 Generator Commissioning

    83/90

    RSO TEST (SIMULATE EARTH FAULT ) ON

  • 7/31/2019 Generator Commissioning

    84/90

    RSO TEST (SIMULATE EARTH FAULT ) ON

    GENERATOR ROTOR UNIT 9

    RSO TEST(SIMULATE INTERTURN FAULT ) IN

  • 7/31/2019 Generator Commissioning

    85/90

    RSO TEST(SIMULATE INTERTURN FAULT ) INGENERATOR ROTOR UNIT 9

    ROTOR AIR PURGE TEST

  • 7/31/2019 Generator Commissioning

    86/90

  • 7/31/2019 Generator Commissioning

    87/90

  • 7/31/2019 Generator Commissioning

    88/90

    DPT/UT of retaining ring

    These test are performed tocheck the internal cracks of the

    retaining ring.

    CC Bolt Air Tightness test

  • 7/31/2019 Generator Commissioning

    89/90

    CC Bolt Air Tightness test

  • 7/31/2019 Generator Commissioning

    90/90

    THANK YOU