generator excation system

Upload: shaiju-baby

Post on 05-Apr-2018

224 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/2/2019 Generator Excation System

    1/15

  • 8/2/2019 Generator Excation System

    2/15

    1. D.C EXCETATION SYSTEM(i) ROTATING

    RECTIFITED A.C.SYSTEM

    (i) ROTATING (HIGH FREQUENCY(ii) STATIC

  • 8/2/2019 Generator Excation System

    3/15

    USE IN MOST OF OLDER UNIT IN THE COUNTRY. D.C. EXCITERS ARE BASICALLY ROTATING SHUNT

    WOUND MACINES &COMPOUNDING CAN BE INCLUDEDRESPONSE.THE EXCITER CAN BE DRIVEN FROM MAINGENER.SHAFT EITHER BY DIRECT COUPLING ORTHROUGH REDUCTION GEARS.

    THE GENERATION OF D.C. SUPPLY IS ACHIVED INTWO STAGES,FIRSTLEY A RELATIELY SMALL RATED O/PPIOLET EXCITER WHICH SUPPLIES THE EXCITATION FORMAIN EXCITATIOR.THE MAIN EXCITOR SUPPLY THEEXCITION TO THE MAIN GENERATOR ROTOR VIA SLIP

    RINGS & ITS BRUSHGEAR. THE PIOLOT EXCITOR O/P IS REGULATED BY A VARIABLERESISTANCE,USUALLY A MOTOR DRIVENREHEOSTATE,WHICH IS

  • 8/2/2019 Generator Excation System

    4/15

    Controlled either manually or via an AUTOMATICVoltage Regulator(AVR)

    The AVR measure the generator terminal voltage &compares it to desired set value. The difference in

    value is used to give signal that will alter therheostat to change the rotor d.c. current which is inturn will be restore the voltage to its set value.

    This system shown in fig. bellow

  • 8/2/2019 Generator Excation System

    5/15

  • 8/2/2019 Generator Excation System

    6/15

    The A.C. exciter gained favour of the problems &constraints associated with DC excitor.

    Commutator & DC brush gear were eliminatedgiving place to simple rotor slip rings &

    associated brush gear. Two types A.C. excitation system

    Rotating System : This is high frequencyexcitation system with an AC exciter, permanentmagnet piolt exciter & an uncontrolled rectifier.

    Static Excitation : This is generator potential fedstatic excitation system with controlled rectifier(SCR) & a rectifier transformer.

  • 8/2/2019 Generator Excation System

    7/15

    In order to maintain system stability,it is tonecesarry to have fast excitation system for largesynchrunous machine whoch means the fieldcurrent must be adjusted extremelt fast tochaning operational condition.

    Due to above reasons, s.e is preffered & in thisall components are solid state & no moving parts.

    S.E. following equipment consists:

    i. Rectifier Transformer

    ii. Thyristor Rectifier Banksiii. Excitation start up and field discharge

    equipment

  • 8/2/2019 Generator Excation System

    8/15

    iv. Regulator and operation control circuit.1. Rectifier Transformer: The excitation power is taken from generator

    o/p & fed to the e.t(rectifier ) which is step

    dowen to the required voltage for SCR bridge &fed through the field breaker to generator field.

    Its dry type cast coil type transformer.

    Its provide c.t for o.c protection also its capable

    of suppling ceilling currents at the ceilingexcitations for a short period of ten seconds.

  • 8/2/2019 Generator Excation System

    9/15

    2. Thyristor Rectifier Banks The thyristor Rectifier Bank consists of a

    suitable number of bridges connected inparallel. Each thyristor bridge comprises sixthyristors , fuses and snubber ckt for

    protection.by changing the firing angle ofthyristors,variable o/p is obtained.Each bridgeis controlled by one finel plusu stage &is cooledby a fan.

    3. Excitation start up and field discharge equipment As residual magnetism of generator os not

    sufficient to start voltage built up,this type ofsystem needs separate equipment for excitationstart up( Field Flashing).the field

  • 8/2/2019 Generator Excation System

    10/15

    4.Regulation and operation control circuits This is the heart of the system.This system regulates

    the generator voltage by controlling the firing pluses tothe thyristors. The system components are discussed

    bellow:A. Error Detector & Amplifier The generator terminal voltage is step dowen by a 3

    phase PT& fed to the AVR. The a.c. input thus obtainedrectificed,filtered& comprated against a highly

    stabilised value and difference is amplified in differentstages of amplification.three CTs sensing the o/pcurrent of the generator,fed propostional currennt

  • 8/2/2019 Generator Excation System

    11/15

    Variable registers in the AVR.The voltageacrros the resistors,can be added vectoriallyeither for compounding or for transformerdrop compensation.

    b. Grid- control unit

    The o/p of the AVR is fed to the grid controlunit.It gets its synchoronous a.c. reference

    through a filter circuit and generates a doublepulse spaced 60 el.apart whose positiondepends on the o/p of the AVR.

  • 8/2/2019 Generator Excation System

    12/15

    c. Plus- Amplifier The pluse o/p of the grid control system is

    amplified further at an intermediate stageamplification.its known as pluse intrrmediate

    stage.its has d.c supplywhich operate from a threephase 380v and delivers +15v,-15,+0v and coarsestabiliesed voltage Vl.also relay is provied forblocking 6 pluse channel. In two channel system (

    like AUTO/MANUAL) the change over is affecetedby energizing/ de- energizing the relay.

    d. Pluse Final Stage

  • 8/2/2019 Generator Excation System

    13/15

    This unit receives input pluses from the pluseamplifier and transmits them though plusetransformer to gate of the thyristor.A bluit inpower supply provieds. The required powersupply to final pluse and amplifier.each thyrisor

    bridge has owen finel pluse stage.if one thyristorfail the remaining bridge to continoue to cater tofull load requirement of the machine.

    e. Manual control channel

    A separate manual control is taken from astabiliesed d.c volt through a motor operatedpotentiometer.the d.c. is fed to a separate gridcontrol unit whose o/p

  • 8/2/2019 Generator Excation System

    14/15

    the finel pluse stage. When one channel is working &generating thr required pluses,the other remainblocked.therefore AUTO TO MANUAL control or viceversa.

    A pluse supervision unit detects spurious the pluses or

    loss of pluses at the busbar and transfer control fromautomatic channel to manual channel

    f. Follow up unit

    To smooth changeover from Auto to manual control,it isnecessary thet the position of the pulses on the both

    channel should be identical, a pluse compration unitdetects in any difference in position of the pluses andwith the help of follow up unit actuates the motor

  • 8/2/2019 Generator Excation System

    15/15

    Potentimeter on the manual channel to turn in adirection so as to eliminate the difference.