generator protection
TRANSCRIPT
![Page 1: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/1.jpg)
GENERATOR PROTECTION
Prepared ByPriten Vasa
![Page 2: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/2.jpg)
Introduction:In a generating station the generator and transformer are the most
expensive equipments and hence it is desirable to employ a protective system to isolate the faulty equipment as quickly as possible to keep the healthy section in normal operation and to ensure uninterruptable power supply.
The basic electrical quantities those are likely to change during abnormal fault conditions are current, voltage, phase angle and frequency . Protective relays utilizes one or more of these quantities to detect abnormal conditions in a power system.
Protective system cost is 4-5%of the total cost
![Page 3: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/3.jpg)
Switchgear • Switchgear is a general term covering a wide
range of equipments concerned with switching and protection.
• Eg: Circuit breaker, Isolator, Earth switch etc.
•Desirable Protection Attributes• Reliability• Selectivity• Speed • Simplicity
![Page 4: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/4.jpg)
RELAYS & CIRCUIT BREAKERS
• TYPES OF RELAYS1. Reed relay2. Latching relay3. Solid state relay4. Solid state contact relay5. Ratchet relay6. Coaxial relay7. Overload protection relay8. Forced guided contact relay9. Buchholz relay
• CIRCUIT BREAKERS TYPES BASED ON VOLTAGE CLASS AND CURRENT RATING1.Air breaker circuit breaker2.Miniature circuit breaker3.Air blast circuit breaker4.SF6 circuit breaker5.Low oil circuit breaker 6.Vaccum circuit breaker
![Page 5: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/5.jpg)
Advantages Of Digital Relay
MultifunctionalCompatibility withdigital integrated
systems
Low maintenance(self-supervision)
Highly sensitive,secure, and
selectiveAdaptive
Highly reliable(self-supervision)
Reduced burden on
CTs and VTs
ProgrammableVersatile
Low Cost
![Page 6: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/6.jpg)
GEN
UAT
AVR
220 kv HVCB
6.6 KV CB
NGT
10.5 KV
220 KV
GT
EXT TR
SER TR
440 V AC
LA
Single line Diagram of generator connection
![Page 7: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/7.jpg)
Protection Zones Protection Zones
7GE Consumer & Industrial
Multilin
1. Generator or Generator-Transformer Units
2. Transformers
3. Buses
4. Lines (transmission and distribution)
5. Utilization equipment (motors, static loads, etc.)
6. Capacitor or reactor (when separately protected)
Unit Generator-Tx zone
Bus zone
Line zone
Bus zone
Transformer zoneTransformer zone
Bus zone
Generator
~
XFMR Bus Line Bus XFMR Bus Motor
Motor zone
![Page 8: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/8.jpg)
SCHEME OF GENERATOR PROTECTION• CLASS A TRIPPING This is adopted for those electrical faults of Generator and Generator transformer unit
auxiliary transformer for which tripping can not be delayed.· This leads to simultaneous tripping of - Generator Transformer HV side CB - Field Circuit Breaker - LV side incomer breakers of UAT - Auto changeover from unit to station for unit auxiliaries and tripping of turbine
• CLASS B TRIPPING This is adopted for all turbine faults (Mechanical) and for some Electrical faults of Generator,
Generator transformer and unit Auxiliary transformer for which it is safe to trip the turbine. ·Subsequently the Generator is tripped through low forward powerInterlock Ensures that unit does not over speed due to trapped steam in the Turbine during the
shutdown and also the loss of power to the grid From the generator is not sudden.
![Page 9: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/9.jpg)
CLASS C TRIPPING
• This is adopted for all faults beyond the Generator system which can be cleared by tripping of Generator transformer HV side CB alone.
• In this case the TG set runs with HP-LP bypass system in operation and the Generator continues to feed the unit auxiliary load through unit auxiliary transformers.
![Page 10: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/10.jpg)
![Page 11: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/11.jpg)
The "Wild"PowerSystem
G
Exciter
Loss of FieldLoss of Field
Overexcitation
Overexcitation
Overexcitation
OpenCircuits
Loss ofSynchronism
InadvertentEnergizing,Pole Flashover
AbnormalFrequency
AbnormalFrequency
BreakerFailure
ReversePower
OverPower
Abnormal Operating Conditions
![Page 12: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/12.jpg)
![Page 13: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/13.jpg)
FAULT OCURRENCE & FAULT CLASSIFICATION
• Insulation failure.
• Tends to deteriate with rising temp.
• Insulation failure may cause inter-turn fault, ph to ph or earth fault.
• Bring winding in to direct contact with core plates.
• Any failure to restrict earth fault may result into core plate damage.
• Insulation of rotor winding is also important
• Stator Fault• Rotor fault• Abnormal Running Condition
1) Unbalanced Loading2) Over loading3) Over Speed4) Over Voltage5) Failure of Primer Mover6) Loss Of Excitation7) Excessive vibration8) Difference in expansion between
rotating and stationary parts9) Loss of synchronism
![Page 14: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/14.jpg)
![Page 15: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/15.jpg)
![Page 16: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/16.jpg)
• Limits overvoltages• Limits difference in electric potential through local area
conducting objects• Several methods
i. Ungroundedii. Reactance Coil Grounded iii. High Z Groundediv. Low Z Groundedv. Solidly Grounded
System Grounding
![Page 17: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/17.jpg)
1. Ungrounded: There is no intentional ground applied to the system-however it’s grounded through natural capacitance. Found in 2.4-15kV systems.
2.Reactance Grounded: Total system capacitance is cancelled by equal inductance. This decreases the current at the fault and limits voltage across the arc at the fault to decrease damage.
X0 <= 10 * X1
4.High Resistance Grounded: Limits ground fault current to 10A-20A. Used to limit transient overvoltages due to arcing ground faults.
5.Low Resistance Grounded: To limit current to
25-400A
3.Solidly Grounded: There is a connection of transformer or generator neutral directly to station ground
![Page 18: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/18.jpg)
Protection Relay – ANSI Standards1.Current protection functions ANSI 50/51 – Phase overcurrent ANSI 50N/51N or 50G/51G – Earth fault or sensitive earth fault ANSI 50BF – Breaker failure ANSI 46 -Negative sequence / unbalance ANSI 49RMS – Thermal overload
2.Directional power protection functions• ANSI 32P – Directional active overpower• ANSI 32Q/40 – Directional reactive overpower
3.Voltage protection functions ANSI 79 – Reclose the circuit breaker after tripping
4.Machine protection functions ANSI 37 – Phase undercurrent ANSI 48/51LR/14 – Locked rotor / excessive starting time ANSI 66 – Starts per hour ANSI 50V/51V – Voltage-restrained overcurrent ANSI 26/63 – Thermostat, Buchholz, gas, pressure, temperature detection ANSI 38/49T – Temperature monitoring by RTD
![Page 19: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/19.jpg)
Stator protectionStator faults include the following-i. Phase-to-earth faultsii. Phase-to-phase faultsiii. Inter-turn faultsFrom these phase faults and inter turn
faults are less common ,these usually develop into an earth faults.
This causes-I. Arcing to coreII. Damage of conductor and insulation
Generator Stator Ground Fault Protection
87N, 51N, 59N & 27-3N
Generator Stator Phase Fault Protection
87G
![Page 20: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/20.jpg)
•Inter-turn fault on the same phase of the stator winding cannot be detected by transverse differential protection as it does not disturb the balance between the currents in neutral and high voltage CTs.•For protection against inter-turn faults the following protection schemes are used. (1)Cross differential protection. (2)Residual voltage protection.
Stator inter-turn fault protection
![Page 21: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/21.jpg)
Stator Earth Fault Relay
![Page 22: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/22.jpg)
Typical Example Stator Earth Fault
![Page 23: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/23.jpg)
Rotor Earth Fault E/F Protection
•DC injection method or AC injection method.•The dc or ac voltage is impressed between the field circuit and ground through a sensitive overvoltage relay and current limiting resistor or capacitor(in case of ac).•But dc source is generally used as over-current relay in case of dc is more sensitive than ac.
•A single earth fault in rotor circuit will complete the path and the fault is sensed by the relay.
![Page 24: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/24.jpg)
LOSS OF EXCITATION
CAUSES• Field open circuit• Field short circuit• AVR control Failure• Accidental tripping of field Breaker• Loss of supply to main Exciter• Poor Brush contact in Exciter• Field Current Breaker Latch Failure• Slip ring Flash Over
Consequences• With mechanical power remaining
intact and field excitation is loss it would attempt to remain in synchronization by acting as a INDUCTION GENERATOR
• This phenomenon can be explained by following energy flows
![Page 25: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/25.jpg)
![Page 26: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/26.jpg)
![Page 27: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/27.jpg)
Exciter
FUSE T1
T2
FUSE
TRIP
SHUNT
FILED WDG
Field failure protection
![Page 28: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/28.jpg)
Types of Differential Protection.
Differential Protection protection using Balancing Resistors
![Page 29: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/29.jpg)
Biased Differential Protection
![Page 30: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/30.jpg)
Over Voltage ProtectionOvervoltage protection is required in case of hydro-electric or gas
turbine generators but not in case of turbo generators.Over voltage may be caused due to- Transient over voltage in the transmission line due to lightening. Defective operation of the voltage regulator. Sudden loss of load due to line tripping.The protection is provided with an over voltage relay.It is usually of induction pattern with an IDMT(Inverse Definite Minimum
Time) Here current is Inversely proportional to timeMore the rise off current or voltage faster the relay will be operated
![Page 31: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/31.jpg)
Overcurrent protection:
• Overloading of the machine causes overheating in the stator winding.
• This can be prevented by using over-current relay with time delay adjustment.
• But overheating not only depends on over-current but also the failure of the cooling system in the generator.
• So temperature detector coils such as thermistors or thermocouples are used at various points in stator winding for indication of the temperature.
![Page 32: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/32.jpg)
Over /Under Frequency Protection 81 O/U
• Causes:Significant load additionSudden reduction in mechanical input
powerLoss of generationLoss of load•Underfrequency can cause:Higher generator load currentsOverexcitationTurbine blade fatigue•Overfrequency can cause: Overvoltage on hydro turbines
Abnormal frequency presents hazards to other parts of the plant such as:
Steam turbine vibrations and increased stresses on blades
Reduced capacity of auxiliary equipment
High temperatures caused by increased excitation current
Overexcitation of transformers
![Page 33: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/33.jpg)
Out of step Protection(78)
• High peak currents and off-frequency operation can occur when a generator losses synchronism• Causes winding stress, high rotor iron currents, pulsating torques and mechanical resonances• Conventional relaying approach – analyzing variations in apparent impedance as viewed at generator terminals• Variation in impedance can be detected by impedance relaying and generator separated before the completion of one slip cycle
![Page 34: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/34.jpg)
Impedance Variation Detection
![Page 35: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/35.jpg)
m
m
46
mm
Zc ZA
A
BC
Ia
IbIc
VZC
VZA
POSITIVE SEQ
Ia
IbIc
VZC
VZAVZA+VZC
X Y
NEGATIVE SEQUENCE
Negative phase sequence protection
![Page 36: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/36.jpg)
Inadvertent Energization Protection(27, 50, 60, 81U, 62 and 86)
Protects against closing of the generator breaker while machine is not spinning / on turning gear
Caused by operator error, breaker flash-over, control circuit malfunction.
Two schemes illustrated: Frequency supervised overcurrent Voltage supervised overcurrent
![Page 37: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/37.jpg)
Inadvertent Energization ProtectionFrequency Supervised Overcurrent
![Page 38: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/38.jpg)
Frequency Supervised Overcurrent &
• Uses an underfrequency relay (81U) to enable a sensitive instantaneous overcurrent relay (50)
• Overcurrent relay picks up at 50% or less of expected inadvertent energizing current. • Frequency relay contacts must remain closed if sensing voltage goes to zero• Voltage balance relay (60) protects against loss of sensing• Time delay relay (62) protects against sudden application of nominal voltage during inadvertent energization,allowing overcurrent to trip lockout relay (86)• Lockout relay must be manually reset
Same illustration as frequency supervised overcurrent except 81U replaced by 27
• Undervoltage setpoint of 85% of the lowest expected emergency operating level
Voltage Supervised Overcurrent
![Page 39: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/39.jpg)
Loss of Voltage Transformer Protection (60)
Common practice on large systems to use two or more VTs• One used for relays and metering• The other used for AVR• VTs normally fused• Most common cause of failure is fuse failure• Loss of VT protection blocks voltage based protectivefunctions (21, 32, 40 …etc)• Loss of VT protection measure voltage unbalance, typical setting is 15%
![Page 40: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/40.jpg)
When prime-mover fails machine starts motoring and draws electrical power from the system and this is known as inverted operation .
The generator can be protected from inverted operation by using single-element directional power relay(reverse power relay) which senses the direction of power flow.
Failure of the prime mover of a generator set ,will keep the set running as a synchronous compensator, taking the necessary active power from the net work and could be detrimental to to the safety of the set, if maintained for any length of time. The amount of power taken will depend on the type of prime mover involved. It ranges from 5% to 25%.
Reverse Power Protection
![Page 41: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/41.jpg)
STEAM VALVE
C.B TRIP
Protective relay
Reverse power relay
Reverse power relay scheme
![Page 42: Generator Protection](https://reader036.vdocument.in/reader036/viewer/2022081501/55d0e20fbb61eb09538b4703/html5/thumbnails/42.jpg)
Thank You