generator protection m‑3425 - beckwith electric · pdf filesimple and logical setting and...
TRANSCRIPT
Generator Protection M‑3425Integrated Protection System® for Generators of All Sizes
PROTECTION
• Provides all major protective functions for generator protection, including Field Ground (64F), Out-of-Step (78), and Split-Phase Differential (50DT)
• Expanded IPScom® Communications Software provides simple and logical setting and programming
• Enhanced "pick and choose" functionality provides tailored applications at the lowest possible cost
Unit shown with optional M‑3925 Target Module and M‑3931 HMI (Human‑Machine Interface) Module
–2–
M‑3425 Generator Protection Relay
Standard Protective Functions • Dual‑zone phase distance protection for phase
fault backup (21)
• Overexcitation (V/Hz) protection (24)
• Phase Undervoltage (27) protection
• 100% Stator Ground Fault protection via third harmonic neutral undervoltage (27TN)
• Sensitive dual‑setpoint Reverse Power, Low Forward Power or Overpower detection, one of which can be used for sequential tripping (32)
• Dual‑zone, offset‑mho Loss‑of‑Field protection (40)
• Sensitive Negative Sequence Overcurrent protection and alarm (46)
• Instantaneous Overcurrent (50) protection
• Inadvertent Generator Energizing protection (50/27)
• Generator Breaker Failure protection (50BF)
• Definite Time Overcurrent (50DT) can be used for split phase differential
• Instantaneous Overcurrent (50N) protection
• Neutral Inverse Time Overcurrent (51N)
• Three‑phase Inverse Time Overcurrent (51V)
• Phase Overvoltage (59)
• Generator Ground Fault protection (59N)
• VT Fuse‑Loss detection and blocking (60FL)
• Out‑of‑Step protection (78)
• Four‑step Over/Underfrequency (81) protection
• Two‑step Rate of Change of Frequency (81R)
• Generator Phase Differential protection (87)
• Ground Differential (87GD) protection
• External Function allows external devices to trip through M‑3425 Generator Protection Relay
Optional Protective Functions • Stator Thermal protection using positive
sequence inverse time overcurrent (51T)
• Field Ground protection (64F)
Standard Features • Eight programmable outputs and s ix
programmable inputs
• Oscillography recording
• Time‑stamped target storage for 24 events
• Metering of all measured parameters
• Three communications ports (two RS‑232 and one RS‑485)
• M‑3820C IPScom® Communications Software
• Includes MODBUS and BECO 2200 protocols
• Standard 19" rack‑mount design
• Removable printed circuit board and power supply
• Both 50 and 60 Hz models available
• Both 1A and 5 A rated CT inputs available
• Additional trip inputs for externally connected devices
• IRIG‑B time synchronization
• Operating Temperature: –20° C to +70° C
Optional Features • Redundant power supply
• M‑3925 Target Module
• M‑3931 Human‑Machine Interface (HMI) Module
• M‑3801D IPSplot® PLUS Oscillograph Analysis Software
–3–
M‑3425 Generator Protection Relay
STANDARD PROTECTIVE FUNCTIONSDevice Setpoint Number Function Ranges Increment Accuracy†
Phase Distance (dual‑zone mho characteristic)
Circle Diameter #1, #2 0.1 to 100.0 Ω 0.1 Ω 0.1 Ω or 5% (0.5 to 500.0 Ω) (0.5 Ω or 5%)
Offset #1, #2 –100.0 to 100.0 Ω 0.1 Ω 0.1 Ω or 5% (–500.0 to 500.0 Ω) (0.5 Ω or 5%)
Impedance Angle #1, #2 0° to 90° 1° 1°
Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%
Volts / Hz
Definite Time Pickup #1, #2 100 to 200% 1% 1%
Time Delay #1, #2 30 to 8160 Cycles 1 Cycle 25 Cycles
Inverse Time Characteristic Curves Inverse Time #1–#4 — —
Pickup 100 to 200% 1% 1%
Time Dial: Curve #1 1 to 100 1 Time Dial: Curves #2–#4 0.0 to 9.0 0.1
Reset Rate 1 to 999 Sec. 1 Sec. .02 Sec. or 1% (from threshold of trip)
The percent pickup is based on nominal VT secondary voltage and nominal system frequency settings. The pickup accuracy stated is only applicable from 10 to 80 Hz, 0 to 180 V, 100 to 150% V/Hz and a nominal voltage setting of 120 V.
Third‑Harmonic Undervoltage, Neutral
Pickup #1, #2 0.3 to 20.0 V 0.1 V 0.15 V or 1%
Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%
Undervoltage Inhibit #1,#2 5 to 180 V 1 V 0.5 V or 0.5% (positive sequence)
Underpower Inhibit #1,#2 0.002 to 3.000 PU 0.001 PU 0.002 or 2%
RMS Undervoltage
Pickup #1, #2 5 to 180 V 1 V 0.5 V or 0.5% 0.8 V or 0.75%*
Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 0.5%**
* When both RMS and Line‑Ground to Line‑Line is selected.
** When RMS (total waveform) is selected, timing accuracy is +20 cycles or 1%†.
Directional Power
Pickup #1, #2 –3.000 to +3.000 PU 0.001 PU 0.002 PU or 2%
Time Delay #1, #2 1 to 8160 Cycles 1 Cycle +16 Cycles or 1%
The per‑unit pickup is based on nominal VT secondary voltage and nominal CT secondary current settings. The 32 function can be selected as low forward power, reverse power, or overpower function.
†Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.
27
32
21
24
27TN
27
32
–4–
M‑3425 Generator Protection Relay
STANDARD PROTECTIVE FUNCTIONS (cont.)Device Setpoint Number Function Ranges Increment Accuracy†
Loss of Field (dual‑zone offset‑mho characteristic)
Circle Diameter #1, #2 0.1 to 100.0 Ω 0.1 Ω 0.1 Ω or 5%
(0.5 to 500.0 Ω) (0.5 Ω or 5%)
Offset #1, #2 –50.0 to 50.0 Ω 0.1 Ω 0.1 Ω or 5%
(–250.0 to 250.0 Ω) (0.5 Ω or 5%)
Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%
Voltage Control 5 to 180 V 1 V 0.5 V or 0.5% (positive sequence)
Directional Element Fixed at –13° — —
Voltage control for each zone can be individually enabled.
Negative Sequence Overcurrent
Definite Time Pickup 3 to 100% 1% 0.5% of 5 A (0.5% of 1 A)
Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%
Inverse Time Pickup 3 to 100% 1% 0.5 % of 5 A (0.5% of 1 A)
Time Dial Setting 1 to 95 1 3 Cycles or 3% (K= I2
2t)
Definite Maximum Time to Trip 600 to 65,500 Cycles 1 Cycle 1%
Definite Minimum Time 12 Cycles — fixed
Reset Time (Linear) 4 minutes — — (from threshold of trip)
Pickup is based on the generator nominal current setting.
Breaker Failure
Pickup Phase Current 0.10 to 10.00 A 0.01 A 0.1 A or 2% (0.02 to 2.00 A) (0.02 A or 2%)
Neutral Current 0.10 to 10.00 A 0.01 A 0.1 A or 2% (0.02 to 2.00 A) (0.02 A or 2%)
Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%
50BF can be initiated from designated M‑3425 output contacts or programmable inputs.
Instantaneous Overcurrent
Pickup 0.1 to 240.0 A 0.1 A 0.1 A or 3%
(0.1 to 48.0 A) (0.02 A or 3%)
Trip Time Response < 2 Cycles
40
46
50BF
50
50BF‑Ph
50BF‑N
†Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.
–5–
M‑3425 Generator Protection Relay
STANDARD PROTECTIVE FUNCTIONS (cont.)Device Setpoint Number Function Ranges Increment Accuracy†
Instantaneous Overcurrent, Neutral
Pickup 0.1 to 240.0 A 0.1 A 0.1 A or 3%
(0.1 to 48.0 A) (0.02 A or 3%)
Trip Time Response < 2 Cycles
Definite Time Overcurrent
Pickup Phase A #1, #2 0.20 A to 240.00 A 0.01 0.1 A or 3% (0.04 A to 48.00 A) (0.02 A or 3%)
Pickup Phase B #1, #2 (same as above)
Pickup Phase C #1, #2 (same as above)
Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%
When 50DT function is used for split‑phase differential protection, 50BF, 87, and 87GD functions are not available.
Inadvertent Energizing
Overcurrent Pickup 0.5 to 15.00 A 0.01 A 0.1 A or 2%
(0.1 to 3.00 A) (0.02 A or 2%)
Undervoltage Pickup 40 to 130 V 1 V 0.5 V
Pick‑up Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%
Drop‑out Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%
Inverse Time Neutral Overcurrent
Pickup 0.25 to 12.00 A 0.01 A 0.1 A or 1%
(0.05 to 2.40 A) (0.02 A or 1%)
Characteristic Curve Definite Time/Inverse/Very Inverse/Extremely Inverse/IEC Curves
Time Dial 0.5 to 11.0 0.1 3% or 3 Cycles 0.05 to 1.10 (IEC curves) 0.01
Inverse Time Overcurrent, with Voltage Control or Voltage Restraint
Pickup 0.5 to 12.0 A 0.01 A 0.1 A or 1% (0.10 to 2.40 A) (0.02 A or 1%)
Characteristic Curve Definite Time/Inverse/Very Inverse/Extremely Inverse/IEC Curves
Time Dial 0.5 to 11.0 0.1 3% or 3 Cycles 0.05 to 1.10 (IEC curves) 0.01
Voltage Control (VC) 5 to 180 V 1 V 0.5 V or 0.5% or Voltage Restraint (VR) Linear Restraint — —
51V
51N
50/27
50DT
50N
50
27
†Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.
–6–
M‑3425 Generator Protection Relay
STANDARD PROTECTIVE FUNCTIONS (cont.)Device Setpoint Number Function Ranges Increment Accuracy†
RMS Overvoltage
Pickup #1, #2 5 to 180 V 1 V 0.5 V or 0.5% 0.8 V to 0.75%*
Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%**
* When both RMS and Line‑Ground to Line‑Line is selected.
** When RMS (total waveform) is selected, timing accuracy is +20 cycles or 1%.
RMS Overvoltage, Neutral
Pickup #1, #2 5.0 to 180.0 V 0.1 V 0.5 V to 0.5%
Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%
VT Fuse‑Loss Detection
A VT fuse-loss condition is detected by using the positive and negative sequence components of the voltages and currents. VT fuse-loss output can be initiated from internally generated logic or from input contacts.
Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%
Out of Step (mho characteristic)
Circle Diameter 0.1 to 100.0 Ω 0.1 Ω 0.1 Ω or 5% (0.5 to 500.0 Ω) (0.5 Ω or 5%)
Offset –100.0 to 100.0 Ω 0.1 Ω 0.1 Ω or 5% (–500.0 to 500.0 Ω) (0.5 Ω or 5%)
Impedance Angle 0° to 90° 1° 1°
Blinder 0.1 to 50.0 Ω 0.1 Ω 0.1 Ω or 5% (0.5 to 250.0 Ω) (0.5 Ω or 5%)
Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%
Trip on mho Exit Enable/Disable
Pole Slip Counter 1 to 20 1
Pole Slip Reset 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%
Frequency
Pickup #1,#2,#3,#4 50.00 to 67.00 Hz 0.01 Hz 0.02 Hz 40.00 to 57.00 Hz*
Time Delay #1–#4 2 to 65,500 Cycles 1 Cycle 2 Cycles or 1%
The pickup accuracy applies to 60 Hz models at a range of 57 to 63 Hz, and to 50 Hz models at a range of 47 to 53 Hz. Beyond these ranges, the accuracy is 0.1 Hz.
* This range applies to 50 Hz nominal frequency models.
59
59N
60FL
81
78
†Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.
–7–
M‑3425 Generator Protection Relay
STANDARD PROTECTIVE FUNCTIONS (cont.)Device Setpoint Number Function Ranges Increment Accuracy†
Rate of Change of Frequency
Pickup #1, #2 0.10 to 20.00 Hz/Sec. 0.01 Hz/Sec. 0.05 Hz/Sec. or 5%
Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 20 Cycles
Negative Sequence Voltage Inhibit 0 to 99% 1% 0.5%
Phase Differential Current
Pickup 0.20 A to 3.00 A 0.01 A 0.1 A or 5%
(0.04 to 0.60 A) (0.02 A or 5%)
Percent Slope 1 to 100% 1% 2%
Time Delay* 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%
* When a time delay of 1 cycle is selected, the response time is less than 1–1/2 cycles.
Ground (zero sequence) Differential
Pickup 0.20 to 10.00 A 0.01 A 0.1 A or 5% (0.04 to 2.00 A) (0.02 A or 5%)
Time Delay 1 to 8160 Cycles* 1 Cycle +1 to ‑2 Cycles or 1%
CT Ratio Correction (RC) 0.10 to 7.99 0.01
* The Time Delay setting should not be less than 2 cycles.The 87GD function is provided primarily for low‑impedance grounded generator applications. This function operates as a directional differential. If 3I0 or In is extremely small (less than 0.2 secondary Amps), the directional element is disabled.
External Functions
Two functions are provided for externally connected devices to trip through the relay to provide additional logic and target information. Any one or more of the input contacts (IN1–IN6) can be programmed to activate designated output contacts after a selected time delay.
Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%
Nominal Settings
Nominal Voltage 50 to 140 V 1 V —
Nominal Current 0.50 to 6.00 A 0.01 A —
VT Configuration Line‑Line/Line‑Ground/ Line‑Ground to Line‑Line*
Seal‑In Delay 2 to 8160 Cycles 1 Cycle 1 Cycle or 1%
* When Line‑Ground to Line‑Line is selected, the relay internally calculates the line‑line voltage from the line‑ground voltages for all voltage‑sensitive functions. This Line‑Ground to Line‑Line selection should only be used for a VT nominal secondary voltage of 69 V (not 120 V).
81R
87
87GD
EXT
†Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.
–8–
M‑3425 Generator Protection Relay
OPTIONAL PROTECTIVE FUNCTIONSDevice Setpoint Number Function Ranges Increment Accuracy†
Inverse Time Positive Sequence Overcurrent (I2t=K), for Stator Thermal Protection
Pickup 0.50 to 15.00 A 0.01 A 0.1 A (0.10 to 3.00 A) (0.02 A)
Time Delay @6X* 0.10 to 10.00 Sec 0.01 Sec 3% or 3 Cycles
Reset Characteristics 4 minutes — 3% (Linear) (from threshold of trip)
* This time delay setting is at six times the pickup current.
Field Ground Protection
Pickup #1, #2 5 to 100 KΩ 1 KΩ 10% or ±1KΩ
Time Delay #1, #2 1 to 8160 Cycles 1 Cycle ( 2IF +1) Sec.
Injection Frequency (IF) 0.10 to 1.00 Hz 0.01 Hz
Brush Lift‑Off Detection (measuring control circuit)
Pickup 0 to 5000 mV 1 mV
Time Delay 1 to 8160 Cycles 1 Cycle ( 2IF +1) Sec.
When 64F is purchased, an external Coupler Module (M‑3921) is provided for isolation from dc field voltages.
Figure 7, Typical Field Ground Connection Diagram, illustrates a typical connection utilizing the M‑3921 Field Ground Coupler. Hardware dimensional and mounting information is shown in Figure 8, M‑3921 Field Ground Cou‑pler Mounting Dimensions.
64F
64B
51T
†Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.
–9–
M‑3425 Generator Protection Relay
DescriptionThe M‑3425 Generator Protection Relay is suitable for all generator ratings and prime movers. Typical con‑nection diagrams are illustrated in Figure 2, M‑3425 Typical One‑Line Connection Diagram, Figure 3, M‑3425 Typical One‑Line Connection Diagram (Configured for Split‑Phase Differential), and Figure 4, M‑3425 Typical Three‑Line Connection Diagram.
Configuration OptionsThe M‑3425 Generator Protection Relay is available with Standard Protective Functions, Optional Protective Functions, and Optional Features. This provides the user flexibility in selecting a protective system to best suit the application. The relay may be purchased as a Protection System which includes all Standard Protective Functions. Additional Optional Protective Functions may be added at the time of purchase at per‑function pricing.
The relay may also be purchased as a Base System, with the user selecting any ten (10) Standard Protective Functions. Additional Standard Functions and/or Premium Protective Functions may be added at the time of purchase at per‑function pricing.
The user can select the Human‑Machine Interface (HMI) Module, Target Module, or redundant power supply at time of purchase for either the Protective System or Base System options.
When the user purchases the Field Ground (64F) Premium Protective Function, an external coupler module (M‑3921) is provided for isolation from the dc field voltages.
MeteringThe relay provides metering of voltages (phase, neutral and sequence quantities), currents (phase, neutral and sequence quantities), real power, reactive power, power factor and impedance measurements.
Metering accuracies are:
Voltage: 0.5 V or 0.5%, whichever is greater 0.8 V or 0.75%, whichever is greater (when both RMS and Line‑Ground to Line‑Line are selected)
Current: 5 A rating, 0.1 A or 3%, whichever is greater 1 A rating, 0.02 A or 3%, whichever is greater
Power: 0.01 PU or 2%, whichever is greater
Frequency: 0.02 Hz (from 57 to 63 Hz for 60 Hz models; from 47 to 53 Hz for 50 Hz models)
Oscillographic RecorderThe oscillographic recorder provides comprehensive data recording of all monitored waveforms, storing up to 170 cycles of data. The total record length is user‑configurable for 1, 2, 3 or 4 partitions. The sampling rate is 16 times the power system nominal frequency (50 or 60 Hz). The recorder may be triggered either via the desig‑nated status inputs, trip outputs, or via serial communications. The recorder continuously stores waveform data, keeping the most recent data in memory. When triggered, the recorder stores pre‑trigger data, then continues to store data in memory for a user‑defined, post‑trigger delay period.
The records may be analyzed or viewed using Beckwith Electric M‑3801D IPSplot® PLUS Oscillograph Analysis software or M‑3813 ComVert software, which converts Beckwith Electric oscillographic files to COMTRADE format.
Target StorageA total of 24 targets can be stored. The information will include the function(s) operated, the functions picked up, input/output status, time stamp, and phase and neutral currents at the time of trip.
CalculationsCurrent and Voltage RMS Values: Uses discrete Fourier transform algorithm on sampled voltage and current signals to extract fundamental frequency phasors for relay calculations. RMS phase voltages for the 59 and 27 functions (when total RMS is selected), and the 24 function are obtained using the time domain approach to obtain accuracy over a wide frequency band. When the RMS option is selected, the magnitude calculation is accurate over a wide frequency range (10 to 80 Hz). When the DFT option is selected, the magnitude calculation is accurate near nominal frequency (50 or 60 Hz).
–10–
M‑3425 Generator Protection Relay
Power Input OptionsNominal 110/120/230/240 V ac, 50/60 Hz, or nominal 110/125/220/250 V dc. UL/CSA rating 85 V ac to 265 V ac and from 80 V dc to 288 V dc. Burden 20 VA at 120 V ac/125 V dc. Withstands 300 V ac or 300 V dc for 1 second.
Nominal 24/48 V dc, operating range from 18 V dc to 56 V dc. Burden 20 VA at 24 V dc and 20 VA at 48 V dc. Withstands 65 V dc for 1 second.An optional redundant power supply is available.
Sensing InputsFour Voltage Inputs: Rated nominal voltage of 60 V ac to 140 V ac at 60 Hz or 50 Hz. Will withstand 240 V continuous voltage and 360 V for 10 seconds. Source voltages may be line‑to‑ground or line‑to‑line connected. Phase sequence ABC or ACB is selectable. Voltage transformer burden less than 0.2 VA at 120 V ac.
Seven Current Inputs: Rated nominal current (IR) of 5.0 A or 1.0 A at 60 Hz or 50 Hz. Will withstand 2IR continuous current and 100IR for 1 second. Current transformer burden is less than 0.5 VA at 5 A, or 0.3 VA at 1 A.
Control/Status InputsThe control/status inputs, INPUT1 through INPUT6, can be programmed to block any relay functions, to trigger the oscillographic recorder, or to operate one or more outputs. The control/status inputs should be dry contacts and are internally connected (wetted) to a 24 V dc power supply. To provide breaker status LED indication on the front panel, the INPUT1 control/status input must be connected to the 52b breaker status contact. The minimum current value to initiate/pickup an Input is >25 mA.
Output ContactsThe eight programmable output contacts (six form ‘a’ and two form ‘c’), the power supply alarm output contact (form ‘b’), and the self‑test alarm output contact (form ‘c’) are all rated per IEEE C37.90 (See Tests and Stan‑dards section for details).
Any of the functions can be individually programmed to activate any one or more of the eight programmable output contacts.
Target/Status Indicators and ControlsThe RELAY OK LED reveals proper cycling of the microcomputer. The BRKR CLOSED LED will turn on when the breaker is closed (when the 52b contact input is open). The OSC TRIG LED indicates that oscillographic data has been recorded in the unit's memory. The TARGET LED will turn on when any of the relay functions operate. Pressing and releasing the TARGET RESET button resets the target LED if the conditions causing the operation have been removed. Holding the TARGET RESET button displays the present pickup status of the relay functions. The PS1 and PS2 LEDs will remain on as long as power is applied to the unit and the power supply is operating properly.
CommunicationCommunications ports include rear panel RS‑232 and RS‑485 ports, a front panel RS‑232 port, and a rear‑panel IRIG‑B port. The communications protocol implements serial, byte‑oriented, asynchronous communication, providing the following functions when used with the Windows™‑compatible M‑3820C IPScom® Communications Software package. MODBUS and BECO 2200 protocols are supported providing:
• Interrogation and modification of setpoints
• Time‑stamped trip target information for the 24 most recent events
• Real‑time metering of all quantities measured
• Downloading of recorded oscillographic data
–11–
M‑3425 Generator Protection Relay
IRIG‑BThe M‑3425 Generator Protection Relay can accept either modulated or demodulated IRIG‑B time clock syn‑chronization signal. The IRIG‑B time synchronization information is used to correct the hour, minutes, seconds, and milliseconds information.
HMI Module (optional)Local access to the relay is provided through an optional M‑3931 HMI (Human‑Machine Interface) Module, allow‑ing for easy‑to‑use, menu‑driven access to all functions via six buttons and a 2‑line by 24 character alphanumeric LED. Features of the HMI Module include :
• User‑definable access codes allow three levels of security
• Interrogation and modification of setpoints
• Time‑stamped trip target information for the 24 most recent events
• Real‑time metering of all quantities measured
Target Module (optional)An optional M‑3925 Target Module provides 24 target and 8 output LEDs. Appropriate target LEDs will light when the corresponding function operates. The targets can be reset with the TARGET RESET pushbutton. The OUTPUT LEDs indicate the status of the programmable output relays.
Tests and StandardsThe relay complies with the following type tests and standards:
Voltage Withstand
Dielectric WithstandIEC 255‑5 3,500 V dc for 1 minute applied to each independent circuit to earth 3,500 V dc for 1 minute applied between each independent circuit 1,500 V dc for 1 minute applied to IRIG‑B circuit to earth 1,500 V dc for 1 minute applied between IRIG‑B to each independent circuit 1,500 V dc for 1 minute applied between RS‑485 to each independent circuit
Impulse VoltageIEC 255‑5 5,000 V pk, +/‑ polarity applied to each independent circuit to earth 5,000 V pk, +/‑ polarity applied between each independent circuit 1.2 by 50 µs, 500 ohms impedance, three surges at 1 every 5 seconds
Insulation ResistanceIEC 255‑5 > 40 Megaohms
Electrical Environment
Electrostatic Discharge TestIEC 1000‑4‑2 Class 4 (8 kV)—point contact discharge
Fast Transient Disturbance TestIEC 1000‑4‑4 Class 4 (4 kV, 2.5 kHz)
–12–
M‑3425 Generator Protection Relay
Surge Withstand CapabilityANSI/IEEE 2,500 V pk‑pk oscillatory applied to each independent circuit to earthC37.90.1 2,500 V pk‑pk applied between each independent circuit 5,000 V pk Fast Transient applied to each independent circuit to earth 5,000 V pk Fast Transient applied between each independent circuit
Radiated SusceptibilityANSI/IEEE 25‑1000 Mhz @ 35 V/m (with 64F option, 20 V/m)C37.90.2
Output Contacts RatingsIEEE C37.90 30 A make for 0.2 seconds at 250 Vdc resistiveUL 508 8 A carry at 120 Vac, 50/60 HzCSA C22.2 No. 14 6 A break at 120 Vac, 50/60 Hz 0.1 A break at 125 Vdc 0.1 A break at 120 Vac
Atmospheric Environment
TemperatureIEC 68‑2‑1 Cold, –20° C for 96 hoursIEC 68‑2‑2 Dry Heat, +70° C for 96 hoursIEC 68‑2‑3 Damp Heat, +40° C @ 93% RH, for 96 hours
Mechanical Environment
VibrationIEC 255‑21‑1 Vibration response Class 1, 0.5 g Vibration endurance Class 1, 1.0 g
Compliance UL‑Listed per 508 – Industrial Control Equipment
CSA‑Certified per C22.2 No. 14‑95 – Industrial Control Equipment
PhysicalSize: 19.00" wide x 5.21" high x 10.20" deep (48.3 cm x 13.2 cm x 25.9 cm)
Mounting: The unit is a standard 19", semiflush, three‑unit high, rack‑mount panel design, conforming to ANSI/EIA RS‑310C and DIN 41494 Part 5 specifications. Vertical or horizontal panel‑mount options are available.
Approximate Weight: 17 lbs (7.7 kg)
Approximate Shipping Weight: 25 lbs (11.3 kg)
Recommended Storage Parameters
Temperature: 5° C to 40° C
Humidity: Maximum relative humidity 80% for temperatures up to 31° C, decreasing to 31° C lin‑early to 50% relative humidity at 40° C.
Environment: Storage area to be free of dust, corrosive gases, flammable materials, dew, percolating water, rain and solar radiation.
See M‑3425 Instruction Book, Appendix E, Layup and Storage for additional information.
–13–
M‑3425 Generator Protection Relay
Patent & WarrantyThe M‑3425 Generator Protection Relay is covered by U.S. Patents 5,592,393 and 5,224,011.
The M‑3425 Generator Protection Relay is covered by a five year warranty from date of shipment.
External ConnectionsM‑3425 external connection points are illustrated in Figure 1, External Connections, on the facing page.
–14–
M‑3425 Generator Protection Relay
s CAUTION: Application of external voltages to the IN‑PUTS terminals may result in damage to the unit.
NOTES:
1. All relays are shown in the de‑energized state.
2. Output contacts #1 through #4 are high speed operation contacts.
3. The power supply relay (P/S) is energized when the power supply is OK.
4. The self‑test relay is energized when the relay has performed all self‑tests successfully.
To fulfill requirements for UL and CSA listing, terminal block connections must be made with No. 22–12 AWG solid or stranded copper wire inserted in an AMP #324915 (or equivalent) connector and wire insulation used must be rated at 75° C minimum.
Torque Requirements:
• Terminals 1–34: 12.0 in‑lbs
• Terminals 35–63: 8.0 in‑lbs, minimum, and 9.0 in‑lbs, maximum.
s CAUTION: Over torquing may result in terminal damage.
8(5
2b
)
V
CO
M3
RS
48
5
V AFI
ELD
GN
DV
VA B
CBV
B
INP
UT
S
NA
CVC
VI A
C
ALA
RM
S
BII
I N
-+
6ININ
IN4
5IN
IN2
31IN
SE
LF
-TE
ST
INR
TN
P/S
OU
TP
UT
S
aII b
Ic
-2P +
S
-1P +
S
3A
MP
,25
0V
(3A
B)
3A
MP
,25
0V
(3A
B)
PS
2P
S1
76
54
32
1
CO
UP
LER
+-
+-
64
F
12
63
45
78
910
1112
1314
1615
1718
1920
2123
2224
2526
2728
3029
3132
3334
5135
3837
3641
4039
4544
4342
4847
4650
4963
5754
5352
5655
6059
5862
61
619
011
8th
AV
EN
O.
LA
RG
O,
FL
33
77
3
BE
CK
WIT
HE
LE
CT
RIC
CO
.IN
C.
WA
RN
ING
!C
ON
TA
CT
WIT
HT
ER
MIN
AL
SM
AY
CA
US
EE
LE
CT
RIC
SH
OC
K
50
Hz
60
Hz
SE
RIA
LN
O.
MO
DE
L: M
-342
5
FIR
MW
AR
E: D
-007
0
!
!
FO
RC
ON
TA
CT
RA
TIN
GS
SE
EIN
ST
RU
CT
ION
MA
NU
AL
61
-8
5 28
55
65
82
65
65
8-
16
0-1
40
,50
/60
Hz
RA
TE
DV
OL
TA
GE
RA
TE
DC
UR
RE
NT
1A,N
OM
5A
,NO
M
IRIG
BC
OM
2R
S2
32
F2
F4
F3F1
U.S
. PA
TEN
T 5,
592,
393,
5,2
24,0
11N
RTL
/CLR
894
64RU L
LIS
TED
IND
.CO
NT.
EQ
.83
F4
US
C
1
3A
MP
,2
50
V(
3A
B)
3A
MP
,2
50
V(
3A
B)
PS
2P
S1
-
12
63
45
78
910
61
90
11
8t
hA
VE
NO
.
F2
F4
F3
F1
-
Dan
ger!
Con
tact
ave
c le
s te
rmin
aux
peut
cau
ser u
n ch
oc e
lect
rique
Figure 1 External Connections
–15–
M‑3425 Generator Protection Relay
50DT
Utility System
52Unit
52Gen
50BFPh
87
5050/2740 51T 4651V60FL 21 78 32
27
81R 81 27 59 24
64F 64B
M-3921+
-
CT
VT
CT
M-3425
87GD 50N50
BFN 51N
R
CT
VT
59N27TN
27
32
R
M-3425 M-3425
High‑impedance Grounding with ThirdHarmonic 100% Ground Fault Protection
Low‑impedance Grounding withOvercurrent Stator Ground Fault Protection
This function is available as astandard protective function.
This function is available as aoptional protective function.
This function provides control forthe function to which it points.
NOTE: Some functions aremutually exclusive; seeInstruction Book for details.
M-3425 TypicalConnection Diagram
Figure 2 One‑Line Connection Diagram
–16–
M‑3425 Generator Protection Relay
50DT
Utility System
52Unit
52Gen
5050/2740 51T 4651V60FL 21 78 32
27
81R 81 27 59 24
64F 64B
M-3921+
-
CT
VT
CT
M-3425
50N 51N
R
CT
VT
59N27TN
27
32
R
M-3425 M-3425
High‑impedance Grounding with ThirdHarmonic 100% Ground Fault Protection
Low‑impedance Grounding withOvercurrent Stator Ground Fault Protection
This function is available as astandard protective function.
This function is available as aoptional protective function.
This function provides control forthe function to which it points.
NOTE: Some functions aremutually exclusive; seeInstruction Book for details.
M-3425 TypicalConnection Diagram(Configured for Split-Phase Differential)
Figure 3 Typical One‑Line Connection Diagram (configured for split‑phase differential)
–17–
M‑3425 Generator Protection Relay
Example of Control / Output Connections
+
‑61 11 10
60
16 15
52b 60FL
POWERSUPPLY
SELF‑TESTFAILUREALARM
+
‑
DC: 24 V 48 V
EXTERNAL INPUTS ALARM OUTPUTS CONTROLOUTPUTS
TRIPALARM
12 13
POWEROK
STATUSALARM
VT FUSE LOSS
TRIP
52G
TRIP OUTPUT
OSCILLOGRAPHRECORDERINITIATE
BREAKERFAILUREINITIATE
M-3425
ORDC: 110 V 125 V 220 V 250 VAC: 110 V 120 V 230 V 240 V
62
63
UTILITY SYSTEM
ABC
48 49
46 47
OtherRelays M-3425
50 51
Generator
OtherRelays
52Gen
A B C
Three VT Wye-WyeConnection
40
41
38
39
42
43
M-3
425
OR
OR
45
44
High Impedance Grounding
M-3425
58 59
56 57
54 55
M-3425
57 56
55 54
M-3425
59 58
57 56
55 54
M-3425
59 58
OR OR
M-34255352
A B C
A B C A B CA B C
M‑3921Field Ground
CouplerModule
10
1152b
M-3425
OR
Low Impedance Grounding
M-3
42542
43
40
41
38
39
Two VT Open-DeltaConnection
A B C
40
41
38
39
42
43
M-3
425
Three VT Wye-WyeConnection - Alternate
A B C
Figure 4 M‑3425 Typical Three‑Line Connection Diagram
NOTE: M‑3425 current terminal polarity marks (•) indicate "entering" current direction when primary current is "from" the generator. If CT connections differ from those shown, adjust input terminals.
NOTE: Wire to split phase differential CTs for use with 50DT split phase function.
–18–
M‑3425 Generator Protection Relay
Figure 5 Horizontal Mounting Dimensions
NOTE: Panels for vertical mounting are available. When mounted vertically, the target module will be located at the top and all front‑panel text will be horizontally aligned. Consult Beckwith Electric Co. for details.
Standard 19" Horizontal Mount Chassis
19.00[48.26]
17.50[44.45]
17.50[44.45]
ACTUAL
5.21[13.23]
ACTUAL
0.40 [1.02] X 0.27[0.68] Slot (4X)
10.20[25.91]
18.31[46.51]
0.35[0.89]
1.48[3.76]
2.25[5.72]
17.68[44.91]
RECOMMENDED CUTOUT WHEN RELAY ISNOT USED AS STANDARD RACK MOUNT
5.28[13.41]
NOTE: Dimensions in brackets are in centimeters.
–19–
M‑3425 Generator Protection Relay
Figure 6 Vertical Mounting Dimensions
1.97[5.0]
19.00[48.26]
18.30[46.51]
2.25[5.72]
0.28 [0.71]Dia. (4X)
17.68[44.91]
5.59[14.20]Actual
1.67[4.24]
2.25[5.72]
10.20[25.91]
COM 1
TARGETS
OUT 1
OUT 2
OUT 3
OUT 4
OUT 5
OUT 6
OUTPUTSOUT 7
OUT 8
EXIT ENTER
TARGET DIAG
TIME
OSC.TRIG
SYNC
BRKRCLOSED
OKRELAY
TARGETRESET
PS 2 PS 1
17.5[44.45]
ACTUAL
5.65[14.40]
Recommended cutout when relay is not used asstandard rack mount and is panel cut out mounted.
19.00[48.26]
17.50[44.45]
0.35[0.89]
0.03[0.076]
NOTE: Dimensions in brackets are in centimeters.
6.19[15.7]
–20–
M‑3425 Generator Protection Relay
M‑3921 Field Ground Coupler NOTES: 1. The above circuit measures insulation resistance (Rf) between rotor field winding and ground (64F).
2. Relay injects 15 V squarewave (Vout) and measures return signal (Vf) to calculate Rf.
3. The injection frequency can be set (0.1 to 1.0 Hz) based on the rotor capacitance, in order to improve accuracy.
4. Analyzing signal rise time can determine if shaft brushes are open (64B).
Function SpecificationField/Exciter Supply Voltage Rating (Terminal (3) to (2)):
• 60 to 1200 V dc, continuous
• 1500 V dc, 1 minute
Operating Temperature: –20° to +70°, Centigrade
Patent & WarrantyThe M‑3921 Field Ground Coupler is covered by a five year warranty from date of shipment.
Tests and StandardsM‑3921 Field Ground Coupler complies with the following tests and standards:
Voltage Withstand
Isolation4 kV ac for 1 minute, all terminals to case
Impulse VoltageIEC 255–5, 5,000 V pk, 1.2 by 50 ms, 0.5 J, 3 positive and 3 negative impulses at 5 second part 5 intervals per minute
–21–
M‑3425 Generator Protection Relay
Electrical Interference
Electrostatic Discharge TestIEC 1000‑4‑2 Class 4 (8 kV)—point contact discharge
Fast Transient Disturbance TestsIEC 1000‑4‑4 Class 4 (4 kV, 2.5 kHz)
Surge Withstand CapabilityANSI/IEEE 2,500 V pk‑pk oscillatory applied to each independent circuit to earthC37.90.1 2,500 V pk‑pk applied between each independent circuit 5,000 V pk Fast Transient applied to each independent circuit to earth 5,000 V pk Fast Transient applied between each independent circuit
Radiated SusceptibilityANSI/IEEE 25‑1000 Mhz @ 20 V/mC37.90.2
Atmospheric EnvironmentIEC 68–2–1 Cold, –20° C for 96 hoursIEC 68–2–2 Dry Heat, +70° C for 96 hoursIEC 68–2–3 Damp Heat, +40° C @ 93% RH, for 96 hours
Enclosure ProtectionNEMA 1, IEC IPC‑65
–22–
M‑3425 Generator Protection Relay
PR
OT
EC
TIO
N R
ELA
YM
-3425
PR
OC
ES
SO
R
Field G
roundD
etection
Squarew
aveG
enerator
Signal
Measurem
entand P
rocessingR
f.Cf
CO
UP
LING
NE
TW
OR
K(M
-3921)
Ground/M
achine Fram
e
Shaft
Ground
Brush
SU
PP
LYV
OLT
AG
E
Gen.
Rotor
3735
36
TB
5
Rear T
erminal
Block P
in No.
Shield
Cable
TB
4
TB
1T
B1
Vf
Vout
Brushes
TB
3
TB
2
Figure 7 Typical Field Ground Connection Diagram
–23–
M‑3425 Generator Protection Relay
.18
DIA
[0.4
6] 4
HO
LES
MO
UN
TIN
G P
AT
TE
RN
WIT
HO
UT
TA
BS
Fie
ld G
roun
dC
oupl
er4.
72 [1
1.99
]
7.87
[19.
99]
2.96
RE
F [7
.52]
3.54
[9.0
]
N
OT
E: D
imen
sion
s in
bra
cket
s ar
e in
cen
timet
ers.
7.40
[18.
79]
9.06
[23.
01]
3.54
[9.0
]
.18
DIA
[0.4
6] 4
X
M-3
921
Figure 8 M‑3921 Field Ground Coupler Mounting Dimensions
800‑3425‑SP‑13MC7 08/15© 1998 Beckwith Electric Co.Printed in U.S.A. (10.16.02)