genset_testlog
DESCRIPTION
This paper contains Genset inspection checklistTRANSCRIPT
ANY TOWN NURSING HOMEEmergency Generator Monthly Test LogGenerator Model: Caterpillar Engine Model: C18 Date installed: July 21, 2003Standby kW nameplate rating: 600 kW 30% of standby rating = 180 kW Fuel type: Diesel Normal operating temp: 180 to 200 FMonth
Test Date
Time Meter Reading Transfer Switch Battery
Specific
Gravity Oil Pressure
Operating
Temp.
Load kW
Tested
By Comments
Start EndInspection
Test
January1/3/09147147.8OKOK*125547 psi191231JJS*8 seconds to load transfer
February
2/1/09153.1153.9OKOK*125049 psi193238JJS*7 seconds to load transfer
March
3/2/09162.2163OKOK*126046 psi190234JJS*8 seconds to load transfer
April
May
June
July
August
September
October
November
December
Emergency Generator Monthly Test Log
Generator Model: ________________________ Engine Model: ________________________ Date installed: ____________Standby kW nameplate rating: _________ 30% of standby rating = _________ Fuel type: _________ Normal operating temp: ______
Month
Test Date
Time Meter Reading Transfer Switch Battery
Specific
Gravity Oil Pressure
Operating
Temp.
Load kW
Tested
By Comments
Start EndInspection
Test
January
February
March
April
May
June
July
August
September
October
November
December