geo thermal heat exchanger

Upload: nalinsingla95

Post on 04-Jun-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/13/2019 Geo Thermal Heat Exchanger

    1/11

    Development of a thermodynamic performance-analysis program for

    CO2 geothermal heat pump system

    Young-Jae Kima,*, Keun-Sun Chang b

    aDepartment of Bio-Chemical Engineering, Sun Moon University, Asan, Chungnam 337-840, Republic of KoreabDepartment of Mechanical Engineering, Sun Moon University, Asan, Chungnam 337-840, Republic of Korea

    1. Introduction

    In recent years, refrigeration and air-conditioning equipments

    have

    been

    being

    developed

    for

    more

    efficient

    and

    compact

    way

    inorder to comply with the internationalmovement of energy saving

    and regulation reinforcement on environmental protection. This

    tendencyhaspromoted thedevelopmentof geothermalheatpump

    systems which are able to correspond efficiently to the change of

    cooling and heating loads. To develop new environmental-friendly

    geothermal heat pump systems, a suitable refrigerant for each

    usage must be selected [1].

    The fullyhalogenated chlorofluorocarbons (CFCs)havebeen the

    most commonly used until 1980s. However, there is currently a

    worldwide trend to seek ozone safe alternative refrigerants to

    conventional CFCs [1,2]. For the short-term replacement of CFCs,

    HFCs have been being considered as zero ozone depletion (ODP)

    refrigerants, but they cannot be free from their high potential of

    globalwarming (GWP) [2]. In this reason, much attention has been

    being paid on natural refrigerants such as carbon dioxide,

    ammonia, air, water, and hydrocarbons as a long-term solution

    of alternative refrigerantwith zero ozonedepletion and zero global

    warming. Natural refrigerants shown in Table 1 are halogen-free

    working fluids based on molecules that occur in nature and are

    environmentally benign due to their very low or zero ODP and

    GWP [3].

    Currently, ammonia is widely used as a refrigerant for large-

    scale freezers. For usage, it should be noted that ammonia has

    toxicity though flammability is less. Propane and butane have

    strong

    flammability.

    Air

    is

    used

    extensively

    as

    a

    refrigerant

    inaircraft industry. Its advantages are to require fewer heat

    exchangers, but its efficiency is quite poor. Water has the potential

    to be a very efficient refrigerant, but it requires operation in a deep

    vacuum. This leads to costly large-volume vacuum tanks thatmust

    house all themachinery, such asheat exchangers and compressors.

    Among natural refrigerants, CO2 is one of the most promising

    alternatives, because it has outstanding thermodynamic, trans-

    port, and other environmentally friendly properties. As a result of

    continuous efforts to improve efficiency, two-stage CO2refrigera-

    tor was developed in 1889 and the multiple-effect CO2cycle was

    developed in 1905. However, in the early 19th century, CO2 was

    replaced by CFCs due to their excellent characteristics as a

    refrigerant. CO2 is now becoming attractive again as an environ-

    mentally friendly refrigerant. CO2 has a very low global warming

    potential compared to traditional CFCs and HCFCs [46].

    The geothermal heat pump is known as a highly efficient

    renewable device for heating and cooling houses and buildings as

    well as for supplying warm water. During the winter it operates so

    as to absorb heat from the underground and reject heat into the

    building. Refrigerant is evaporated in coils placed underground

    and the vapor is compressed for condensation by water, used to

    heat the building, at temperatures above the required heating

    level. The geothermal heat pump also serves as air conditioning

    during the summer. The flow direction of refrigerant is simply

    reversed, and heat is transferred out of the building and back into

    the underground coils [7].

    Journal of Industrial and Engineering Chemistry 19 (2013) 18271837

    A R T I C L E I N F O

    Article history:

    Received 9 October 2012Accepted 23 February 2013

    Available online 4 March 2013

    Keywords:

    CO2Geothermal heat pump systems

    Cycle simulation program

    Internal heat exchanger

    A B S T R A C T

    In this research, a steady-state cycle simulation program for thermodynamic performance analysis of

    CO2 geothermal heat pumpsystemswasdeveloped.A seriesof case studies were conductedby changing

    systemparametersand operationconditionsin order to investigate theeffect of various systemvariables

    on the geothermal heat pump cycle including an internal heat exchanger (IHX). The simulation results

    were validated by comparing them with experimental data. The mean deviations of the COPs, cooling

    capacities, and compressor powers between experimental and simulation results are 4.5%, 3.8%, 6.5%,

    respectively at the 5 8C superheated degree and 32% EEV opening.

    2013 TheKorean Society of Industrial andEngineering Chemistry. Publishedby Elsevier B.V. All rights

    reserved.

    * Corresponding author at: Department of Bio-Chemical Engineering, Sun Moon

    University, Asan, Chungnam 337-840, Republic of Korea. Tel.: +82 0415302372.

    E-mail address: [email protected] (Y.-J. Kim).

    Contents lists available at SciVerse ScienceDirect

    Journal of Industrial and Engineering Chemistry

    journ al homepage: www.elsev ier .co m/ locate / j iec

    1226-086X/$ see front matter 2013 The Korean Society of Industrial and Engineering Chemistry. Published by Elsevier B.V. All rights reserved.

    http://dx.doi.org/10.1016/j.jiec.2013.02.028

    http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028mailto:[email protected]:[email protected]://www.sciencedirect.com/science/journal/1226086Xhttp://www.sciencedirect.com/science/journal/1226086Xhttp://www.sciencedirect.com/science/journal/1226086Xhttp://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://www.sciencedirect.com/science/journal/1226086Xmailto:[email protected]://dx.doi.org/10.1016/j.jiec.2013.02.028http://crossmark.crossref.org/dialog/?doi=10.1016/j.jiec.2013.02.028&domain=pdfhttp://crossmark.crossref.org/dialog/?doi=10.1016/j.jiec.2013.02.028&domain=pdf
  • 8/13/2019 Geo Thermal Heat Exchanger

    2/11

    A large number of studies have been carried out on heat pump

    systems using natural refrigerants in the world. In the early 1990s,

    Gustav Lorentzen and his colleagues revived research on the CO2refrigeration cycle in order to address the environment problems

    of ozone depletion and global warming effect [8]. They have

    concentrated on the experimental evaluation and thermodynamic

    modeling of mobile air-conditioning systems and developed a

    prototype CO2mobile air-conditioning system through successive

    studies [9].

    Bullock [10] carried out theoretical performance analysis of

    carbon dioxide as a refrigerant in subcritical and transcritical

    cycles in a vapor compression cycle. He concluded that the CO2heat pump system would require an efficient expander or

    significantly improved compressor and heat exchangers because

    it is less efficient than the HCFC-22 (CHClF2) system by 30% in the

    cooling mode and 25% in the heating mode.

    Hwang and Radermacher [11] theoretically evaluated carbon

    dioxide refrigeration cycle by comparing the performance of CO2with HCFC-22 for water heating and chilling modes. They showed

    that CO2 is amore desirable refrigerant in the case ofwaterheating

    since its performance is about 10% better than HCFC-22.

    Brown et al. [12], McEnaney et al. [13,14], and Preissner et al.

    [15] explored experimental results for prototype CO2automotive

    air conditioner (AC) and compared the results with conventional

    HFC-134a (C2H2F4). Hermann and Rene [16] and Hanfner [17]

    performed experimental study on water heating CO2 mobile airconditioning system. They studied the performance of the CO2cycle with an internal heat exchanger, and compared their results

    with other refrigerant cycle. Adriansyah [18] theoretically and

    experimentally investigated a combined air conditioning and tap

    water heating plant using CO2. He concluded that the optimum

    condition at which the system reaches the highest coefficient of

    performance (COP) for cooling is determined by component

    parameters such as gas cooler configuration and percentage of

    heat recovery. The results showed the total COP of the combined

    system is higher than that of the air conditioning system without

    heat recovery.

    CO2 is a refrigerant that operates at very high pressures in a

    transcritical cycle in most operating conditions compared to HFC

    refrigerants.

    Therefore

    the

    piping

    needs

    to

    be

    25%

    thicker

    for

    a

    CO2refrigeration system than for an HFC system in order to withstand

    the higher pressure. For the successful replacement and use of

    natural refrigerants such as CO2, thermodynamic performance

    evaluations of geothermal heat pump systems must be carried out

    since CO2 has significantly different thermodynamic properties

    from those of conventional refrigerants. For such evaluations, it is

    important to develop a thermodynamic performance-analysis

    program for predicting the performance of geothermal heat pump

    systems. In addition, development of the geothermal heat pump

    system requires complex experiments because it includes various

    complex variables and their interactions. Therefore, a thermody-

    namic performance-analysis program for geothermal heat pump

    systems can be effectively used for saving time and reducing the

    risk,

    which

    may

    take

    place

    during

    experiment

    [19].

    In this study, a thermodynamic performance-analysis program

    to predict the steady-state performance of the CO2 geothermal

    heat pump has been developed and was tested using a series of

    case studies to validate the program accuracy. It can simulate the

    thermodynamic performance parameters such as COP, cooling and

    heating capacities of the indoor and outdoor heat exchangers,

    compressor power consumption, etc. This program utilized Visual

    Basic for the graphic user interface (GUI), consisted of pre-

    processor for inputdata andpost-processor for the output data and

    Digital Visual Fortran for the main analysis code. The National

    Institute of Standards and Technology (NIST) REFPROP V6.01 was

    used for estimating the CO2 thermodynamic and transportproperties and equilibrium behaviors.

    2. Modeling of the CO2 geothermal heat pump cycle

    The CO2geothermal heat pump system in this study is mainly

    composed of thewater cooled indoor andoutdoorheatexchangers,

    an internalheat exchanger, a compressor, an expansiondevice, and

    a 4-way valve as shown in Fig. 1. The concept shown in Fig. 1

    basically represents a vapor compression heat pump cycle.

    Depending on the mode of operation (cooling or heating), either

    heat exchanger can serve as the evaporator or gas cooler. The

    indoor unit serves as an evaporator in cooling mode and as a gas

    cooler in heating mode, but the outdoor unit serves as a gas cooler

    in cooling mode and an evaporator in heating mode.The word of cooling mode in heat pumping implies a system

    managing the indoor temperature below that of the surroundings.

    This requires continuous absorption of heat from a low tempera-

    ture level,usually accomplishedby evaporation of a refrigerant in a

    steady-stateflow process. The vapor formed in the evaporatormay

    be returned to its original liquid state for reevaporation. The

    refrigerant vapor leaves the evaporator and enters the compressor

    at the vaporizing temperature and pressure and it is simply

    compressed and then cooled in the gas cooler without condensa-

    tion in the case of the transcritical CO2 cycle as shown in Fig. 2. The

    cooled liquid leaves the gas cooler and enters the expansiondevice.

    The pressure of the liquid is reduced to the evaporating pressure as

    the liquid passes through the expansion device. In the CO2 heat

    pump

    cycle

    a

    liquid

    evaporating

    at

    constant

    pressure

    provides

    ameans for heat absorption at constant temperature. Likewise,

    cooling of the vapor in the transcritical state,after compression to a

    higher pressure, provides for the rejection of heat. The liquid from

    the gas cooler is returned to its original state by an expansion

    process.

    3. Heat exchangers

    In the present study, a multi-tube heat exchanger, which

    contains a number of parallel smaller tubes enclosed in a larger

    tube, was used for the gas cooler, evaporator, and internal heat

    exchanger. The high pressure CO2 flows through the inner tubes

    and the low-pressure water flows through the annular space

    between

    the

    inner

    tubes

    and

    the

    outer

    tube.

    The

    heat

    exchangers

    Table 1

    Characteristics of some natural refrigerants [4].

    Refrigerant R744 R717 R290 R600 R600a R1270

    Chemical formula CO2 NH3 C3H8 n-C4H10 i-C4H10 C3H6Molar mass 44.01 17.03 44.10 58.12 58.12 42.08

    Critical temp. (8C) 30.98 132.25 96.68 152.0 134.67 92.40

    Boiling point (8C) 78.40 33.33 42.09 0.5 11.67 47.7

    Critical pres. (kPa) 7384 11,333 4247 3796 3640 4665

    ODP 0 0 0 0 0 0

    GWP 1

    0

    3

    3

    3

    3Toxicity No Yes No No No No

    Y.-J. Kim, K.-S. Chang/Journal of Industrial and Engineering Chemistry 19 (2013) 182718371828

  • 8/13/2019 Geo Thermal Heat Exchanger

    3/11

    were designedwith the counter-flow patternwhereCO2 andwater

    streams areflowing in oppositedirections in order tomaximize the

    heat transfer efficiency. In the case of the gas cooler, CO2 inthe transcritical state enters the inner tubes and then is cooled by

    the countercurrentlyflowing coldwater through theannulusof the

    gas cooler.

    The section-by-section method [21,22] shown in Fig. 3 was

    used for performance analysis of a countercurrent multi-tube heat

    exchanger. Performance analysis using the section-by-sectionmethod can be applied to very complex refrigerant circuits

    including superheated phase, two-phase, and subcooled region

    as well as transcritical region. The energy balance equation that

    describes the flow of CO2and water for each discretized node via

    the section-by-section method may be written as

    D Qn mcHc;j Hc;j1 mwHw;j Hw;j1 (1)

    In thecase of thegas cooler, the CO2inlet temperature (Tc,1) of

    the first section (n = 1) is known from the compressor outlet

    conditions estimated through compressor simulation. Therefore,

    Fig. 1. Schematic diagram of the CO2 geothermal heat pump system.

    Fig. 2. Temperatureentropy diagram of the CO2 heat pump cycle [20]. Fig. 3. Control section for section-by-section method.

    Y.-J. Kim, K.-S. Chang/Journal of Industrial and Engineering Chemistry 19 (2013) 18271837 1829

  • 8/13/2019 Geo Thermal Heat Exchanger

    4/11

    if thewater inlettemperature (Tw,2) at thefirstsection is assumed

    as the initial guess, the outlet temperaturesof CO2 andwater flow

    are calculated through the above energy balance equation

    including quantity of heat transfer calculated by e-Ntu method.

    At every control section (nth) after the first section, the CO2inlet

    temperature (Tc,j) is known from the previous simulation at the

    (n 1)th control section and then, the water inlet temperature

    (Tw,j+1) can be iteratively calculated by finding the value of

    convergence to the target value (Tw,j) known from simulation at

    the previous control section. In the last control section the

    iteratively estimated water inlet temperature is compared to the

    water inlet temperature given as input data. If the difference

    between two values is not fall within the error limit, the water

    inlet temperature (Tw,2) assumed at the first control section as an

    initial guess is iteratively changed until the convergence is

    reached.

    In e-Ntu method, quantity of heat transfer ( Qn) in a control

    section can be obtained using heat exchanger effectiveness (e) and

    the number of transfer units (Ntu).

    Qn eCminTc;in Tw;in (2)

    NtuUnAn

    Cmin(3)

    where C is heat capacity mCp, Cminmeans the smaller value among

    heat capacities of the water and CO2.

    Heat transfer effectiveness (e) for the countercurrentflow in the

    gas cooler without phase change is estimated with the number of

    transfer units (Ntu) as follows:

    e 1 expNtu1 Cr

    1 CrexpNtu1 Cr (4)

    CrCminCmax

    If the CO2 flow in a control section at the evaporator is a two-phase

    fluid,

    Crbecomes

    zero.

    Therefore,

    Eq.

    (4)

    can

    be

    written

    as

    Eq.

    (5).e 1 expNtu (5)

    The equation to calculate overall heat transfer coefficient, Un, of

    each control section is given as follows:

    1

    Un

    DAo

    DAihn;c

    DAolnro=ri

    2pkDz

    1

    hn;w(6)

    where k is the thermal conductivity of tube wall.

    The heat transfer rate in a control section can be determined

    from an energy balance on the CO2 and water flows and can be

    expressed as:

    Qn;CO2 mCO2 CpCO2 TCO2i TCO2j1 (7)

    Qn;H2O mH2O CpH2O TH2Oj TH2Oj1 (8)

    Therefore, the outlet temperatures of the CO2and the water flows

    are determined to be

    TCO2j1 TCO2j Qn;CO2

    mCO2:CpCO2(9)

    TH2Oj TH2Oj1 Qn;H2O

    mH2O CpH2O(10)

    The CO2 geothermal heatpump system incorporates an internal

    heat exchanger (IHX) which is installed between the outlet of the

    gas cooler and the evaporator. Thus, the CO2 flow at the high-

    pressure

    side

    of

    the

    gas

    cooler

    is

    liquefied

    from

    the

    transcritical

    state due to heat rejection through IHX and the CO2 flow at the

    low-pressure side of the evaporator becomes a superheated gas

    state by heat absorption. One purpose of the internal heat

    exchanger is to further cool the CO2 flow from the gas cooler by

    exchanging heat with the CO2 flowing out from the evaporator.

    This increases the amount of CO2 in liquid phase (lower quality)

    flowing into the evaporator, and thus increases the cooling

    performance, which in turn results in increase of the COP of the

    geothermal heat pump system. In this research, a countercurrent

    multi-tube heat exchanger was used as an internal heat exchanger

    and the performance of the internal heat exchanger was also

    analyzed by section-by-section method.

    The overall heat transfer coefficient (U) shown in Eq. (6) was

    calculated based on the waterside and CO2-side heat transfer

    coefficients. The Gnielinski [23] or Petukhov [24] equations were

    used for estimating the CO2-side heat transfer coefficient at

    transcritical region in the gas cooler. The Gnielinski correlation

    shown in Eq. (11) is used for 2300 Re 104.

    hi f =2Re 1000Pr

    1 12:7ffiffiffiffiffiffiffiffiffif=2

    p Pr2=3 1

    kiDi

    (11)

    where f 1:58lnRe 3:282.

    The

    Petukhov

    correlation

    for

    104

    Re

    5

    106

    is

    expressed

    as

    hi f =8RePr

    1:07 12:7ffiffiffiffiffiffiffiffiffif =8

    p Pr2=3 1

    k iDi

    (12)

    where f = (0.79 ln(Re) 1.64)2.

    The waterside heat transfer coefficient for the gas cooler was

    calculated by using the DittusBoelter correlation [25] for as

    shown in Eq. (13).

    ho 0:023R0:8e Pr

    0:4koDh

    heating (13)

    The CO2-side heat transfer coefficient in two-phase region at

    the evaporator was estimated with the Gungor and Winterton

    correlation

    [26]

    and

    the

    waterside

    heat

    transfer

    coefficient

    wascalculated by using DittusBoelter correlation expressed in

    Eq. (14).

    ho 0:023R0:8e Pr

    0:3koDh

    cooling (14)

    In the case of the internal heat exchanger, the CO2-side heat

    transfer coefficient in high pressure was calculated with the

    Gnielinski or Petukhov equations and that in low pressure was

    estimated by using the DittusBoelter correlation for heating.

    4. Compressor

    The compressor simulation was carried out on the basis of the

    loss

    and

    efficiency-based

    compressor

    model

    [27]. The

    loss

    andefficiency-based compressor model estimates the internal energy

    balances in a compressor fromdesign, internalefficiency,andheat-

    loss values specified by user. A schematic diagram of the loss and

    efficiency compressor model is represented in Fig. 4. Ten unknown

    variables shown in Fig. 4 are: (1) CO2 mass flow rate ( mc), (2)

    enthalpy at the suction port (hsuction port), (3) enthalpy at the

    discharge port (hdischarge port), (4) enthalpy at the shell outlet

    (houtlet), (5) work done on the CO2( Wc), (6) work done on the shaft

    ( Ws), (7) work input to the compressor ( Wcm), (8) rate of heat loss

    due to cooling of compressor and motor ( Qcooling), (9) rate of

    compressor shellheat loss ( Qcan),and (10) rate ofheat transfer from

    the discharge gas to the suction gas ( Qhillo). These ten unknowns

    are iteratively calculated from the following 10 independent

    equations:

    Y.-J. Kim, K.-S. Chang/Journal of Industrial and Engineering Chemistry 19 (2013) 182718371830

  • 8/13/2019 Geo Thermal Heat Exchanger

    5/11

    energy balance equations

    (1) energy balance between the compressor shell inlet and

    suction port

    input = output

    mchsuctionport hinlet Qhilo Qcooling Qcan (15)

    (2) energy balance between the suction port and discharge port

    mchdischargeport hsuctionport Wc (16)

    (3) energy balance between the discharge port and compressor

    shell outlet

    mchoutlet hdischargeport Qhilo (17)

    seven defining equations

    (4)

    Qhilo ahilo Wcm; actual (18)

    where ahilois the fraction of compressor power consump-

    tion transferred from the discharge line to the suction line

    (specified by user or 0.03 as a default value)

    (5)

    Qcan acan Wcm; actual (19)

    where acan is the fraction of the compressor power

    consumption which is rejected from the shell to the

    ambient air (specified by user or 0.9 (1.0 hmotorhmech))

    (6)

    Qcooling 1 hmotor hmech Wcm (20)

    (7) energy balance between the suction port and discharge port

    Wc mchisen;discharge port hsuction port

    3413 hisen(21)

    where hisenis the isentropic efficiency based on the suction

    port

    (8)

    hmechWcWs

    ; Ws Wc

    hmech(22)

    (9)

    hmotorWsWcm

    ; Wcm Ws

    hmotor(23)

    (10) hvol,suction port: volumetric efficiency based on the suction

    port

    mc hvol; suction port D Soper=ysuction port (24)

    hvol; suction port mc;actualysuction port

    D Soper

    where D is the total compressor displacement [in3]; Soper is the

    actual compressor motor speed [rpm]; ysuction port is the

    specific volume at suction port.

    Fig. 4. Schematic diagram of compressor energy balance.

    Y.-J. Kim, K.-S. Chang/Journal of Industrial and Engineering Chemistry 19 (2013) 18271837 1831

  • 8/13/2019 Geo Thermal Heat Exchanger

    6/11

    5. Expansion device

    One important device in the geothermal heat pump cycle is the

    expansion device. The purpose of the expansion device is to reduce

    the pressure of the refrigerant and to control refrigerant mass flow

    rate in the system. The common expansion devices widely utilized

    in geothermal heat pump systems are capillary tubes, short tube

    orifices, thermostatic expansion valve (TXV), and electronic

    expansion valve (EEV). Among the expansion devices, the EEV

    genders attention recently due to a wide range of operating

    condition and high capability of load control.

    In this research, the electronic expansion valvewasused and its

    performance was evaluated with the equation given by Hwang

    et al. [28]. The mass flow rate for CO2at the EEV can be estimated

    with following equations:

    p1 c1p2c2 p3

    c3p4c4p5

    c5 (25)

    Five dimensionless p-numbers and the coefficients used in this

    correlation are shown in Table 2. The parameters in Table 2 are

    defined as follows:

    m, mass flow rate, At,m, minimum area of orifice, rin, density at

    the

    EEV

    inlet, Dp,

    pressure

    drop

    across

    expansion

    valve,

    L,effective orifice length, Dm, minimum orifice diameter, Do,

    orifice diameter, pin, pressure at the EEV inlet, pc, critical

    pressure of CO2, Tin, temperature at the EEV inlet, Tc, critical

    temperature of CO2. It was reported that this empirical

    correlation derived from Buckingham p-theorem predicts the

    CO2 mass flow rate through the EEV within 5.4% errors.

    6. Thermodynamic performance analysis for the CO2geothermal heat pump cycle

    6.1. Procedures for thermodynamic performance analysis

    Fig. 5 shows the flow diagram for the thermodynamic

    performance-analysis

    program

    developed

    in

    the

    present

    study.The input data required to start the program are as follows: tube

    diameter and length for outer and inner tubes, number of inner

    tubes,flow rateand inlet temperature ofwater asa secondaryfluid,

    expansion device specifications, and the degree of superheat at the

    inlet of the compressor. Furthermore, the performance-analysis

    program requires the geometric dimensions (diameter and length)

    of thepipes in the cycle in order topredict thepressuredrops in the

    geothermal heat pump cycle. Thermodynamic performance

    analysis is based on the following assumptions:

    (1) steady state operation;

    (2) countercurrent flow in all type of heat exchangers;

    (3) neglecting the heat loss through the heat exchangers and

    expansion

    devices;

    (4) neglecting the change of kinetic and potential energy;

    (5) neglecting pressure drop of thewater flow as a secondary fluid.

    The compressor suction and discharge pressure are assumed to

    be the main iterative variables as shown in Fig. 5. Based on

    assumed compressor suction anddischargepressures, theCO2 flow

    rate at the compressor and the conditions at compressor outlet are

    estimated using the compressor module. The compressor inlet

    conditions are also estimated by the degree of superheat given in

    input datum. The gas cooler inlet conditions are calculated from

    the compressor outlet conditions by considering the pressure drop

    between the compressor outlet and the gas cooler inlet. And then,

    the outlet conditions of the gas cooler including heat duty in the

    gas cooler are estimated by using the gas cooler module on the

    basis of the conditions atgas cooler inlet.Based on gas cooler outlet

    and compressor inlet conditions estimated earlier, the inlet

    conditions of the expansion device and the outlet conditions of

    the evaporator are calculated using the internal heat exchanger

    module. CO2flow rate in the expansion device is computed using

    expansiondevicemodule and it is compared with theCO2 flow rate

    estimated at the compressor module. The compressor discharge

    pressure is iteratively adjusted using Secant method until the

    difference between the CO2 flow rate at the compressor and the

    CO2 flow rate in the expansion device is within a prescribedtolerance. After simulating the evaporator on the basis of outlet

    conditions at the expansion device and evaporator specifications

    given as input data, the compressor suction pressure is iteratively

    adjusted using Secant method until the difference between the

    evaporator outlet enthalpy computed at evaporator simulation

    and enthalpy estimated at internal heat exchanger simulation is

    within a prescribed limit.

    The output of the thermodynamic-performance program

    includes the COP, the CO2flow rate, compressor power consump-

    tion, cooling capacity in the evaporator, heating capacity in the gas

    cooler, line pressure drops, etc.

    7. Experimental apparatus

    The experimental apparatus as shown in Fig. 6 is comprised of a

    compressor, indoor and outdoor heat exchangers, an internal heat

    exchanger, an expansion device, an oil separator recovering the oil

    from the compressor, and accumulator located at the exit of the

    evaporator. In addition, aby-pass linewas installed to carry out the

    comparative experimentsaccording to the existence of the internal

    heat exchanger. The specifications for the CO2 geothermal heat

    pump system are summarized in Table 3. A 4-way valve was also

    equipped to choose the operation mode such as cooling and

    heating. As shown in Table 3, all the equipment in the cycle was

    designed to withstand 40 MPa pressure and all instruments and

    fittings are able to safely operate at more than 20 MPa pressure.

    The temperatures, pressures, flow rates, and power consump-

    tions

    at

    the

    important

    points

    of

    the

    cycle

    were

    measured

    using

    T-type thermocouple probes, pressure transducers, and a mass flow

    meter. The uncertainties for the instruments are estimated as

    0.2% for the pressure measurements, 0.2 8C for the temperature

    measurements, 0.2% for the flow measurements, and 0.01% for the

    integrating W-m.

    Before operating the experiment, the system was vacuumed

    first by the vacuum pump, and then proper amount of CO2 was

    charged. Optimum amount of refrigerant charge was determined

    at the highest COP, and found to be 2200 g without the internal

    heat exchanger and 2400 g with the internal heat exchanger. All

    data were collected when they reached the steady state. After

    receiving sufficient amount of data, the EEV opening was changed

    for the next test condition. A set of experiments for various EEV

    openings

    were

    performed,

    in

    order

    to

    analyze

    the

    thermodynamic

    Table 2

    Five dimensionless p-numbers and coefficients in the correlation.

    p1 p2 p3 p4 p5

    m

    At;m

    ffiffiffiffiffiffiffiffiffiffiffiffi ffiffirinDp

    q LDm

    DmD0

    pinpe

    TinTc

    Constant Value

    C1 1.17100

    C2 3.99102

    C3 7.27

    102

    C4 3.86101

    C5 4.55100

    Units: m (kg/s),At,m (m2), rin (kg/m

    3), Dp (Pa), L (m), Dm (m), Do (m), pin(Pa),pc(Pa),

    Tin(K), Tc (K).

    Y.-J. Kim, K.-S. Chang/Journal of Industrial and Engineering Chemistry 19 (2013) 182718371832

  • 8/13/2019 Geo Thermal Heat Exchanger

    7/11

    performance parameters of the geothermal CO2 heat pump system

    such as COP, compressor power, and the CO2 flow rate.

    Experimental test conditions are presented in Table 4. The

    experimental data were collected by averaging data measured

    at every 10 s for 5 min, and decided to be valid when the

    uncertainties were simultaneously maintainedwithin the limits of

    range for temperatures with 0.1 8C, pressures with 5 kPa, and

    flow rate with 0.2 g/s error bound.

    8.

    Results

    and

    discussion

    In the present study, thermodynamic performance character-

    istics of theCO2 geothermalheatpumpwere investigatedusing the

    computer simulation. A number of case studies were carried out to

    validate the simulation program. System performance character-

    istics such as COP, cooling and heating capacities, CO2flow rates,

    and compressor powers were expressed for various EEV openings

    and for over a range of compressor frequencies.

    In Fig. 7, simulation results are compared with experimental

    data for the COP, cooling capacity, and compressor power in

    coolingmode tovalidate the thermodynamicperformance analysis

    of the simulation program. The mean deviations of the COPs,

    cooling capacities, and compressor powers between experimental

    and

    simulation

    results

    are

    4.5%,

    3.8%,

    6.5%,

    respectively

    at

    the

    5 8C

    superheated degree and 32% EEV opening. The comparison

    indicated that the simulation results were in good agreement

    with those from the experiment with reasonable accuracy.

    Variations of COP and cooling capacity with respect to

    compressor frequencies ranged from 30 Hz to 55 Hz for 4 different

    EEV opening positions at 5 8C of superheated degree in cooling

    mode are shown in Fig. 8, and for compressor power in Fig. 9. As

    shown in Figs. 8 and 9, the cooling capacity and compressor power

    increase as compressor frequency increases as generally expected.

    However,

    the

    consistent

    linearity

    of

    the

    increasing

    rate

    indicatesthe stable operability of the heat pump system. On the contrary,

    the COP decreases upon increasing compressor frequency. In

    general, the increase of compressor frequency induces an increase

    of the refrigerant flow rate and pressure difference or compression

    ratio. Increasing rate of high-pressure side due to frequency

    increase is more noticeable than the decreasing rate of the low-

    pressure side. The refrigerant flow rate increase leads to cooling

    capacity increase, whereas the increase of pressure difference or

    compression ratio results in required compressor power increase.

    Since the increasing rate of compressorpower ishigher than thatof

    cooling capacity, the consequent calculation of COP becomes

    smaller with the compressor frequency increase in most cases.

    In the case of EEV opening, itwas observed that theCOP, cooling

    capacity,

    and

    compressor

    power

    all

    decrease

    with

    increasing

    EEV

    Fig. 5. Flow chart of the thermodynamic-performance analysis program.

    Y.-J. Kim, K.-S. Chang/Journal of Industrial and Engineering Chemistry 19 (2013) 18271837 1833

  • 8/13/2019 Geo Thermal Heat Exchanger

    8/11

    opening. The CO2 inlet temperature at the evaporator increases

    with increasing EEV opening and the heat exchanging rate is

    reduced due to the decrease in the inlet temperature difference

    between CO2and secondary fluid of water. On the other hand, CO2flow rate increases with the increase of EEV opening, and

    consequently

    cooling

    capacity

    increases

    with

    the

    increase

    of

    flow

    rate. For the just given operating conditions in this study, these

    combined effects result in the decrease of the COP and cooling

    capacity with increasing EEV opening.

    Fig. 10 shows variations of CO2 flow rate with respect to

    compressor frequency and EEV opening at the 5 8C superheated

    degree

    in

    cooling

    mode.

    As

    seen

    in

    Fig.

    10, CO2flow

    rate

    increaseswith increasing compressor frequency and EEV opening. As

    explained earlier, CO2 flow rates increase with the increase of

    compressor frequency and EEV opening due to expansion of the

    throat area of EEV.

    Variation of COP with respect to superheated degree and

    compressor frequency at 20% EEV opening in cooling mode is

    represented in Fig. 11. It is indicated that the COP decreases

    linearlywith respect to the increment of the superheateddegree in

    the range of39 8Cwhen EEV opening is kept at a value of20%. This

    can be interpreted from the fact that COPs of the cycle are reduced

    because compressor power increases more rapidly than cooling

    capacity with an increase in the superheated degree.

    Fig. 12 represents the comparison ofCOPs of the systemwith an

    IHX

    (internal

    heat

    exchanger)

    and

    a

    basic

    cycle

    without

    the

    IHX.

    Fig. 6. Schematic diagram of experimental apparatus.

    Table 3

    Specifications of the geothermal heat pump system.

    Compressor Rotary type

    Maximum pressure: 45MPa

    Power requirement: 10.5kW

    Frequency response: 3070Hz

    Expansion valve Maximum pressure: 40MPa

    Allowable flow rate: 0100g/s4-way valve Maximum pressure: 40MPa

    Heat exchangers Types Outer tube Inner tube Path

    OD/thickness (mm) OD/thickness (mm) No. No. L (m)

    Outdoor exchanger Multitube 25.4/1.2 4/0.5 8 2 1.7

    Indoor exchanger Multitube 19.05/1.2 4/0.5 8 2 1.65

    Internal exchanger Multitube 19.05/1.2 4/0.5 8 2 1

    Table 4

    Test conditions for the geothermal heat pump system.

    Test conditions Operation

    Cooling Heating

    Compressor freq. (Hz) 3060

    Compressor (rpm) 18003600

    CO2charge (g) 18002400

    EEV opening (%) 1050

    Water inlet temperature at the evaporator (8C) 17 12

    Water flow rate at the evaporator (kg/s) 0.283 0.217

    Water inlet temperature at the gas cooler (8C) 25 30

    Water flow rate at the gas cooler (kg/s) 0.333 0.283

    Y.-J. Kim, K.-S. Chang/Journal of Industrial and Engineering Chemistry 19 (2013) 182718371834

  • 8/13/2019 Geo Thermal Heat Exchanger

    9/11

  • 8/13/2019 Geo Thermal Heat Exchanger

    10/11

    inlet temperature at the evaporator just after the EEV increases

    with increasing EEV opening, so that the heating capacity is

    decreased due to the increase of the inlet temperature difference

    between CO2 and water. However, in the case of heating mode,compressor power was kept almost constant as the EEV opening

    increased. As a result, the COPs were reduced as the EEV opening

    increased.

    The CO2 flow rate as a function of various EEV openings and

    compressor frequencies at the 5 8C superheated degree in heating

    mode is represented in Fig. 15. As shown in Fig. 15, the CO2flow

    rate has a tendency to increase as the compressor frequency andEEV opening increase.

    Fig. 16 shows variation of COPs with respect to superheated

    degree and compressor frequency at the 16% EEV opening in

    heating mode. The COPs in heating mode decrease as the

    superheated degree increases in the range of 39 8C due to the

    same reason mentioned for cooling mode. However, COPs in

    heatingmode more steeply decrease than the case of coolingmode

    with the increase of compressor frequencies.

    Fig. 17 indicates the comparison of COPs as a function of

    compressor frequency for the cycle with IHX (internal heat

    exchanger) and a basic cycle without IHX in heating mode. The

    22% EEV opening was determined to be optimum value for the

    basic cycle and 16% EEV opening for the cycle with the IHX in

    heating mode. In contrast to the cooling mode, the COPs of theheating cyclewith the IHXwere slightly smaller than those of basic

    cycle at all compressor frequencies (1.32.4% smaller with IHX in

    the frequency range of 3055 Hz). With the use of IHX, the heating

    capacity increases due to the decrease of CO2 quality at the

    evaporator inlet resulting from the lowered temperature of CO2leaving from the gas cooler. On the contrary, the heating capacity

    2.5

    2.7

    2.9

    3.1

    3.3

    3.5

    3.7

    3.9

    4.1

    4.3

    4.5

    25 30 35 40 45 50 55 60

    COP

    cooling

    Compressor frequency[Hz]

    no internal heat exchanger

    with internal heat exchanger

    (EEV opening : 32%)

    (EEV opening : 20%)

    Fig. 12. Cooling performance with compressor frequency for IHX.

    1

    2

    3

    4

    5

    6

    7

    8

    9

    1.8

    2.0

    2.2

    2.4

    2.6

    2.8

    3.0

    3.2

    3.4

    3.6

    3.8

    25 30 35 40 45 50 55 60

    COPheating

    Compressor frequency[Hz]

    Heatingcapacity&Po

    wer[kW]

    COP_heating

    Heating capacity

    Compressor power

    EEV opening: 14%

    Superheated degree: 5C

    Fig. 13. Variation of COPheating, heating capacity and compressor power for

    compressor frequency (heating, superheated degree: 5 8C, EEV opening: 14%).

    1

    2

    3

    4

    5

    6

    7

    8

    9

    2.5

    2.6

    2.7

    2.8

    2.9

    3.0

    25 30 35 40 45 50 55 60

    COPheating

    Compressor frequency[Hz]

    Heatingcapacity&Power[kW]

    COP_heating

    Heating capacity

    Compressor power

    EEV opening 20%

    Superheated degree: 5C

    Fig. 14. Variation of COPheating, heating capacity and compressor power for

    compressor frequency (heating, superheated degree: 5 8C, EEV opening: 20%).

    0.02

    0.025

    0.03

    0.035

    0.04

    0.045

    0.05

    25 30 35 40 45 50 55 60

    CO2flowrate[Kg/s]

    Compressor frequency[Hz]

    EEV 16%

    EEV 20%

    EEV 24%

    EEV 28%

    Superheated degree: 5C

    Fig. 15. CO2 flow rate with EEV opening and compressor frequency (heating,

    superheated degree: 5 8C).

    2.7

    2.8

    2.9

    3

    3.1

    3.2

    3.3

    25 30 35 40 45 50 55 60

    COPheating

    Compressor frequency[Hz]

    3C

    5C

    7C

    9C

    EEV opening: 16%

    Superheated degree

    Fig. 16. Variation of COPheatingfor superheated degree and compressor frequency

    (EEV opening: 16%).

    Y.-J. Kim, K.-S. Chang/Journal of Industrial and Engineering Chemistry 19 (2013) 182718371836

  • 8/13/2019 Geo Thermal Heat Exchanger

    11/11

    decreaseswith thedecreaseofCO2flow rate due to the reduction of

    the EEV opening from22%without IHX to16%with IHX. As a result,

    the heating capacity increases by about 8.7% with the use of IHX,

    whereas the required compression power increasesby about10.6%due to the increase of the compressor outletpressure resulted from

    the reduction of EEV opening. In overall, it was founded that the

    use of IHX in heatingmode is not helpful to increase the COP of the

    CO2geothermal heat pump system.

    9. Conclusions

    In the present study, a thermodynamic-performance analysis

    program for CO2 geothermal heat pump system incorporating the

    internal heat exchanger was developed. It consists of several

    subroutines for modeling an evaporator, gas cooler, internal heat

    exchanger, compressor, and electronic expansion valve and

    estimating the thermodynamic and transport properties of CO2

    and water. This program can be used to simulate the steady-statethermodynamic performances ofCO2geothermal heat pumpsystem

    such as COP, heating and cooling capacity, power consumption, etc.

    A number of case studies were carried out in order to validate the

    thermodynamic analysis program and the simulation results were

    compared with the experimental results. It was found that this

    programmaybehighly advantageous to save time and to reduce the

    risk, whichmaytakeplace inexperiment. This simulation program is

    intended to serve as auseful tool fora thermodynamic performance

    analysis when optimizing complex system variables and establish-

    ing efficient operating conditions in the CO2 geothermal heat pump

    systems. In the future the capabilities of this program will be more

    improved for geothermal heat pump systems using natural

    refrigerants such as ammonia and hydrocarbons. The following

    important

    results

    were

    obtained

    in

    this

    study:

    (1) e-Ntumethodwasused for simulating theheat exchangers such

    as the evaporator, gas cooler, and internal heat exchanger.

    (2) The compressor simulation was carried out on the basis of the

    loss and efficiency-based compressor model which estimates

    the internal energy balances in a compressor from design,

    internal efficiency, and heat-loss values specified by user.

    (3) The performance of the electronic expansion valve was

    evaluated with the empirical equation derived from Bucking-

    ham p-theorem.

    (4) The mean deviations of the COPs, cooling capacities, and

    compressor powers between experimental and simulation

    results are 4.5%, 3.8%, 6.5%, respectively. The comparison

    indicated that the simulation results were in agreement with

    those from the experiment with reasonable accuracy.

    (5) It was found that the COPs of the cycle with the IHX were

    improved than those of the basic cycle by 26% in cooling

    mode.

    (6) In contrast with the cooling mode, the COPs of the heating

    cycle with the IHX were slightly smaller than those of basic

    cycle. It indicated that the use of IHX in heating mode has no

    effect to increase the COP of the CO2 geothermal heat pump

    system.

    References

    [1] R.J. Dossat, Principles of Refrigeration, 4th edition, Prentice-Hall, 1997.[2] M.P. Desai, Design Optimization and Development of an Energy-Efficiency Vapor

    Compression Cooling System, 1997, p. 1.[3] S.B.Riffat, C.F.Afonso,A.C. Oliveira,D.A. Reay,AppliedThermalEngineering 17 (1)(1997) 33.

    [4] N. Kagawa, International Journal of Air-Conditioning and Refrigeration 15 (4)(2007) 182.

    [5] M.S. Kim, J.S. Lee, M.S. Kim, International Journal of Air-Conditioning andRefrig-eration 17 (3) (2009) 100.

    [6] Y. Hwang, M. Ohadi, R. Radermacher, Feature Article, The American Society ofMechanical Engineers, 1988.

    [7] J.M. Smith, H.C. Vaness, M.M. Abbott, Introduction to Chemical EngineeringThermodynamics, 5th edition, McGraw-Hill, 1996,, p. 307.

    [8] G. Lorentzen, J. Pettersen, in: Proceedings of the IIR International Symposium onRefrigeration, Energy, and Environment, Trondheim, Norway, (1992), p. 147.

    [9] J.S. Brown, et al. International Journal of Refrigeration 25 (2002) 19.[10] C.E. Bullock, in: Proceedings of ASHARE/NIST Refrigerants Conference, Gaithers-

    burg, MD, (1997), p. 20.[11] Y. Hwang, R. Radermacher, HVAC&R Research 4 (3) (1998) 245.[12] J.S. Brown, F. Samuel, Y. Motta, P.A. Domanski, International Journal of Refrigera-

    tion 25 (2002) 19.

    [13] R.P. McEnaney, D.E. Boewe, J.M. Yin, Y.V. Park, in: Proceedings of the SeventhInternational Refrigeration Conference at Purdue University, West Lafayette,Indiana, (1998), p. 145.

    [14] R.P. McEnaney, Y.C. Park, J.M. Yin, P.S. Hrnjak, SAE International Congress andExposition, Detroit, Michigan, 1999 (Paper No. 1999-01-0872).

    [15] M. Preissner, B. Cutler, S. Singanamalla, Y. Hwang, R. Radermacher, in: Proceed-ings of4th IIR-GustavLorentzenConferenceonNaturalWorkingFluids at Purdue,West Lafayette, IN, (2000), p. 185.

    [16] H. Hermann, R. Rene, 4th IIR-Gustav Lorentzen Conference, 2000, p. 43.[17] A. Hanfner, 4th IIR-Gustav Lorentzen Conference, 2000, p. 177.[18] W. Adriansyah, Energy and Buildings 36 (2004) 690.[19] Y.J. Kim, K.S. Chang,H.H. Kim, Journal of Industrial Engineeringand Chemistry 13

    (5) (2007) 674.[20] S.G. Kim, M.S. Kim, Korean Journal of Air-conditioning and Refrigeration Engi-

    neering 15 (6) (2003) 471.[21] P.A. Domanski, NISTIR 89-4133, NIST, 1989.[22] B. Youn, H.Y. Park, Y.S. Kim, Proceedings of the SAREK 1996 25 (2) (1996) 151.[23] V. Gnielinski, International Chemical Engineering 16 (2) (1976) 359.[24] B.S. Petukhov, Advances in Heat Transfer 6 (1970) 503.[25] P.W. Dittus, L.M.K. Boelter, University of California Publication in Engineering 2

    (13) (1930) 443.[26] K. Gungor, R. Winterton, International Journal of Heat and Mass Transfer 29

    (1986) 351.[27] S.K. Fischer, C.K. Rice, ORNL/CON-80/R1, Oak Ridge National Lab, 1980.[28] Y.W. Hwang, O.J . Kim, in: Proceedings of the SAREK 2007 Summer Annual

    Conference, 2007, p. 1237.

    2.5

    2.6

    2.7

    2.8

    2.9

    3

    3.1

    3.2

    3.3

    3.4

    3.5

    25 30 35 40 45 50 55 60

    COPheating

    Compressor frequency[Hz]

    no internal heat exchanger

    with internal heat exchanger

    (EEV opening : 22%)

    (EEV opening :

    Fig. 17. Heating performance with compressor frequency for IHX.

    Y.-J. Kim, K.-S. Chang/Journal of Industrial and Engineering Chemistry 19 (2013) 18271837 1837