geo thermal heat exchanger
TRANSCRIPT
-
8/13/2019 Geo Thermal Heat Exchanger
1/11
Development of a thermodynamic performance-analysis program for
CO2 geothermal heat pump system
Young-Jae Kima,*, Keun-Sun Chang b
aDepartment of Bio-Chemical Engineering, Sun Moon University, Asan, Chungnam 337-840, Republic of KoreabDepartment of Mechanical Engineering, Sun Moon University, Asan, Chungnam 337-840, Republic of Korea
1. Introduction
In recent years, refrigeration and air-conditioning equipments
have
been
being
developed
for
more
efficient
and
compact
way
inorder to comply with the internationalmovement of energy saving
and regulation reinforcement on environmental protection. This
tendencyhaspromoted thedevelopmentof geothermalheatpump
systems which are able to correspond efficiently to the change of
cooling and heating loads. To develop new environmental-friendly
geothermal heat pump systems, a suitable refrigerant for each
usage must be selected [1].
The fullyhalogenated chlorofluorocarbons (CFCs)havebeen the
most commonly used until 1980s. However, there is currently a
worldwide trend to seek ozone safe alternative refrigerants to
conventional CFCs [1,2]. For the short-term replacement of CFCs,
HFCs have been being considered as zero ozone depletion (ODP)
refrigerants, but they cannot be free from their high potential of
globalwarming (GWP) [2]. In this reason, much attention has been
being paid on natural refrigerants such as carbon dioxide,
ammonia, air, water, and hydrocarbons as a long-term solution
of alternative refrigerantwith zero ozonedepletion and zero global
warming. Natural refrigerants shown in Table 1 are halogen-free
working fluids based on molecules that occur in nature and are
environmentally benign due to their very low or zero ODP and
GWP [3].
Currently, ammonia is widely used as a refrigerant for large-
scale freezers. For usage, it should be noted that ammonia has
toxicity though flammability is less. Propane and butane have
strong
flammability.
Air
is
used
extensively
as
a
refrigerant
inaircraft industry. Its advantages are to require fewer heat
exchangers, but its efficiency is quite poor. Water has the potential
to be a very efficient refrigerant, but it requires operation in a deep
vacuum. This leads to costly large-volume vacuum tanks thatmust
house all themachinery, such asheat exchangers and compressors.
Among natural refrigerants, CO2 is one of the most promising
alternatives, because it has outstanding thermodynamic, trans-
port, and other environmentally friendly properties. As a result of
continuous efforts to improve efficiency, two-stage CO2refrigera-
tor was developed in 1889 and the multiple-effect CO2cycle was
developed in 1905. However, in the early 19th century, CO2 was
replaced by CFCs due to their excellent characteristics as a
refrigerant. CO2 is now becoming attractive again as an environ-
mentally friendly refrigerant. CO2 has a very low global warming
potential compared to traditional CFCs and HCFCs [46].
The geothermal heat pump is known as a highly efficient
renewable device for heating and cooling houses and buildings as
well as for supplying warm water. During the winter it operates so
as to absorb heat from the underground and reject heat into the
building. Refrigerant is evaporated in coils placed underground
and the vapor is compressed for condensation by water, used to
heat the building, at temperatures above the required heating
level. The geothermal heat pump also serves as air conditioning
during the summer. The flow direction of refrigerant is simply
reversed, and heat is transferred out of the building and back into
the underground coils [7].
Journal of Industrial and Engineering Chemistry 19 (2013) 18271837
A R T I C L E I N F O
Article history:
Received 9 October 2012Accepted 23 February 2013
Available online 4 March 2013
Keywords:
CO2Geothermal heat pump systems
Cycle simulation program
Internal heat exchanger
A B S T R A C T
In this research, a steady-state cycle simulation program for thermodynamic performance analysis of
CO2 geothermal heat pumpsystemswasdeveloped.A seriesof case studies were conductedby changing
systemparametersand operationconditionsin order to investigate theeffect of various systemvariables
on the geothermal heat pump cycle including an internal heat exchanger (IHX). The simulation results
were validated by comparing them with experimental data. The mean deviations of the COPs, cooling
capacities, and compressor powers between experimental and simulation results are 4.5%, 3.8%, 6.5%,
respectively at the 5 8C superheated degree and 32% EEV opening.
2013 TheKorean Society of Industrial andEngineering Chemistry. Publishedby Elsevier B.V. All rights
reserved.
* Corresponding author at: Department of Bio-Chemical Engineering, Sun Moon
University, Asan, Chungnam 337-840, Republic of Korea. Tel.: +82 0415302372.
E-mail address: [email protected] (Y.-J. Kim).
Contents lists available at SciVerse ScienceDirect
Journal of Industrial and Engineering Chemistry
journ al homepage: www.elsev ier .co m/ locate / j iec
1226-086X/$ see front matter 2013 The Korean Society of Industrial and Engineering Chemistry. Published by Elsevier B.V. All rights reserved.
http://dx.doi.org/10.1016/j.jiec.2013.02.028
http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028mailto:[email protected]:[email protected]://www.sciencedirect.com/science/journal/1226086Xhttp://www.sciencedirect.com/science/journal/1226086Xhttp://www.sciencedirect.com/science/journal/1226086Xhttp://dx.doi.org/10.1016/j.jiec.2013.02.028http://dx.doi.org/10.1016/j.jiec.2013.02.028http://www.sciencedirect.com/science/journal/1226086Xmailto:[email protected]://dx.doi.org/10.1016/j.jiec.2013.02.028http://crossmark.crossref.org/dialog/?doi=10.1016/j.jiec.2013.02.028&domain=pdfhttp://crossmark.crossref.org/dialog/?doi=10.1016/j.jiec.2013.02.028&domain=pdf -
8/13/2019 Geo Thermal Heat Exchanger
2/11
A large number of studies have been carried out on heat pump
systems using natural refrigerants in the world. In the early 1990s,
Gustav Lorentzen and his colleagues revived research on the CO2refrigeration cycle in order to address the environment problems
of ozone depletion and global warming effect [8]. They have
concentrated on the experimental evaluation and thermodynamic
modeling of mobile air-conditioning systems and developed a
prototype CO2mobile air-conditioning system through successive
studies [9].
Bullock [10] carried out theoretical performance analysis of
carbon dioxide as a refrigerant in subcritical and transcritical
cycles in a vapor compression cycle. He concluded that the CO2heat pump system would require an efficient expander or
significantly improved compressor and heat exchangers because
it is less efficient than the HCFC-22 (CHClF2) system by 30% in the
cooling mode and 25% in the heating mode.
Hwang and Radermacher [11] theoretically evaluated carbon
dioxide refrigeration cycle by comparing the performance of CO2with HCFC-22 for water heating and chilling modes. They showed
that CO2 is amore desirable refrigerant in the case ofwaterheating
since its performance is about 10% better than HCFC-22.
Brown et al. [12], McEnaney et al. [13,14], and Preissner et al.
[15] explored experimental results for prototype CO2automotive
air conditioner (AC) and compared the results with conventional
HFC-134a (C2H2F4). Hermann and Rene [16] and Hanfner [17]
performed experimental study on water heating CO2 mobile airconditioning system. They studied the performance of the CO2cycle with an internal heat exchanger, and compared their results
with other refrigerant cycle. Adriansyah [18] theoretically and
experimentally investigated a combined air conditioning and tap
water heating plant using CO2. He concluded that the optimum
condition at which the system reaches the highest coefficient of
performance (COP) for cooling is determined by component
parameters such as gas cooler configuration and percentage of
heat recovery. The results showed the total COP of the combined
system is higher than that of the air conditioning system without
heat recovery.
CO2 is a refrigerant that operates at very high pressures in a
transcritical cycle in most operating conditions compared to HFC
refrigerants.
Therefore
the
piping
needs
to
be
25%
thicker
for
a
CO2refrigeration system than for an HFC system in order to withstand
the higher pressure. For the successful replacement and use of
natural refrigerants such as CO2, thermodynamic performance
evaluations of geothermal heat pump systems must be carried out
since CO2 has significantly different thermodynamic properties
from those of conventional refrigerants. For such evaluations, it is
important to develop a thermodynamic performance-analysis
program for predicting the performance of geothermal heat pump
systems. In addition, development of the geothermal heat pump
system requires complex experiments because it includes various
complex variables and their interactions. Therefore, a thermody-
namic performance-analysis program for geothermal heat pump
systems can be effectively used for saving time and reducing the
risk,
which
may
take
place
during
experiment
[19].
In this study, a thermodynamic performance-analysis program
to predict the steady-state performance of the CO2 geothermal
heat pump has been developed and was tested using a series of
case studies to validate the program accuracy. It can simulate the
thermodynamic performance parameters such as COP, cooling and
heating capacities of the indoor and outdoor heat exchangers,
compressor power consumption, etc. This program utilized Visual
Basic for the graphic user interface (GUI), consisted of pre-
processor for inputdata andpost-processor for the output data and
Digital Visual Fortran for the main analysis code. The National
Institute of Standards and Technology (NIST) REFPROP V6.01 was
used for estimating the CO2 thermodynamic and transportproperties and equilibrium behaviors.
2. Modeling of the CO2 geothermal heat pump cycle
The CO2geothermal heat pump system in this study is mainly
composed of thewater cooled indoor andoutdoorheatexchangers,
an internalheat exchanger, a compressor, an expansiondevice, and
a 4-way valve as shown in Fig. 1. The concept shown in Fig. 1
basically represents a vapor compression heat pump cycle.
Depending on the mode of operation (cooling or heating), either
heat exchanger can serve as the evaporator or gas cooler. The
indoor unit serves as an evaporator in cooling mode and as a gas
cooler in heating mode, but the outdoor unit serves as a gas cooler
in cooling mode and an evaporator in heating mode.The word of cooling mode in heat pumping implies a system
managing the indoor temperature below that of the surroundings.
This requires continuous absorption of heat from a low tempera-
ture level,usually accomplishedby evaporation of a refrigerant in a
steady-stateflow process. The vapor formed in the evaporatormay
be returned to its original liquid state for reevaporation. The
refrigerant vapor leaves the evaporator and enters the compressor
at the vaporizing temperature and pressure and it is simply
compressed and then cooled in the gas cooler without condensa-
tion in the case of the transcritical CO2 cycle as shown in Fig. 2. The
cooled liquid leaves the gas cooler and enters the expansiondevice.
The pressure of the liquid is reduced to the evaporating pressure as
the liquid passes through the expansion device. In the CO2 heat
pump
cycle
a
liquid
evaporating
at
constant
pressure
provides
ameans for heat absorption at constant temperature. Likewise,
cooling of the vapor in the transcritical state,after compression to a
higher pressure, provides for the rejection of heat. The liquid from
the gas cooler is returned to its original state by an expansion
process.
3. Heat exchangers
In the present study, a multi-tube heat exchanger, which
contains a number of parallel smaller tubes enclosed in a larger
tube, was used for the gas cooler, evaporator, and internal heat
exchanger. The high pressure CO2 flows through the inner tubes
and the low-pressure water flows through the annular space
between
the
inner
tubes
and
the
outer
tube.
The
heat
exchangers
Table 1
Characteristics of some natural refrigerants [4].
Refrigerant R744 R717 R290 R600 R600a R1270
Chemical formula CO2 NH3 C3H8 n-C4H10 i-C4H10 C3H6Molar mass 44.01 17.03 44.10 58.12 58.12 42.08
Critical temp. (8C) 30.98 132.25 96.68 152.0 134.67 92.40
Boiling point (8C) 78.40 33.33 42.09 0.5 11.67 47.7
Critical pres. (kPa) 7384 11,333 4247 3796 3640 4665
ODP 0 0 0 0 0 0
GWP 1
0
3
3
3
3Toxicity No Yes No No No No
Y.-J. Kim, K.-S. Chang/Journal of Industrial and Engineering Chemistry 19 (2013) 182718371828
-
8/13/2019 Geo Thermal Heat Exchanger
3/11
were designedwith the counter-flow patternwhereCO2 andwater
streams areflowing in oppositedirections in order tomaximize the
heat transfer efficiency. In the case of the gas cooler, CO2 inthe transcritical state enters the inner tubes and then is cooled by
the countercurrentlyflowing coldwater through theannulusof the
gas cooler.
The section-by-section method [21,22] shown in Fig. 3 was
used for performance analysis of a countercurrent multi-tube heat
exchanger. Performance analysis using the section-by-sectionmethod can be applied to very complex refrigerant circuits
including superheated phase, two-phase, and subcooled region
as well as transcritical region. The energy balance equation that
describes the flow of CO2and water for each discretized node via
the section-by-section method may be written as
D Qn mcHc;j Hc;j1 mwHw;j Hw;j1 (1)
In thecase of thegas cooler, the CO2inlet temperature (Tc,1) of
the first section (n = 1) is known from the compressor outlet
conditions estimated through compressor simulation. Therefore,
Fig. 1. Schematic diagram of the CO2 geothermal heat pump system.
Fig. 2. Temperatureentropy diagram of the CO2 heat pump cycle [20]. Fig. 3. Control section for section-by-section method.
Y.-J. Kim, K.-S. Chang/Journal of Industrial and Engineering Chemistry 19 (2013) 18271837 1829
-
8/13/2019 Geo Thermal Heat Exchanger
4/11
if thewater inlettemperature (Tw,2) at thefirstsection is assumed
as the initial guess, the outlet temperaturesof CO2 andwater flow
are calculated through the above energy balance equation
including quantity of heat transfer calculated by e-Ntu method.
At every control section (nth) after the first section, the CO2inlet
temperature (Tc,j) is known from the previous simulation at the
(n 1)th control section and then, the water inlet temperature
(Tw,j+1) can be iteratively calculated by finding the value of
convergence to the target value (Tw,j) known from simulation at
the previous control section. In the last control section the
iteratively estimated water inlet temperature is compared to the
water inlet temperature given as input data. If the difference
between two values is not fall within the error limit, the water
inlet temperature (Tw,2) assumed at the first control section as an
initial guess is iteratively changed until the convergence is
reached.
In e-Ntu method, quantity of heat transfer ( Qn) in a control
section can be obtained using heat exchanger effectiveness (e) and
the number of transfer units (Ntu).
Qn eCminTc;in Tw;in (2)
NtuUnAn
Cmin(3)
where C is heat capacity mCp, Cminmeans the smaller value among
heat capacities of the water and CO2.
Heat transfer effectiveness (e) for the countercurrentflow in the
gas cooler without phase change is estimated with the number of
transfer units (Ntu) as follows:
e 1 expNtu1 Cr
1 CrexpNtu1 Cr (4)
CrCminCmax
If the CO2 flow in a control section at the evaporator is a two-phase
fluid,
Crbecomes
zero.
Therefore,
Eq.
(4)
can
be
written
as
Eq.
(5).e 1 expNtu (5)
The equation to calculate overall heat transfer coefficient, Un, of
each control section is given as follows:
1
Un
DAo
DAihn;c
DAolnro=ri
2pkDz
1
hn;w(6)
where k is the thermal conductivity of tube wall.
The heat transfer rate in a control section can be determined
from an energy balance on the CO2 and water flows and can be
expressed as:
Qn;CO2 mCO2 CpCO2 TCO2i TCO2j1 (7)
Qn;H2O mH2O CpH2O TH2Oj TH2Oj1 (8)
Therefore, the outlet temperatures of the CO2and the water flows
are determined to be
TCO2j1 TCO2j Qn;CO2
mCO2:CpCO2(9)
TH2Oj TH2Oj1 Qn;H2O
mH2O CpH2O(10)
The CO2 geothermal heatpump system incorporates an internal
heat exchanger (IHX) which is installed between the outlet of the
gas cooler and the evaporator. Thus, the CO2 flow at the high-
pressure
side
of
the
gas
cooler
is
liquefied
from
the
transcritical
state due to heat rejection through IHX and the CO2 flow at the
low-pressure side of the evaporator becomes a superheated gas
state by heat absorption. One purpose of the internal heat
exchanger is to further cool the CO2 flow from the gas cooler by
exchanging heat with the CO2 flowing out from the evaporator.
This increases the amount of CO2 in liquid phase (lower quality)
flowing into the evaporator, and thus increases the cooling
performance, which in turn results in increase of the COP of the
geothermal heat pump system. In this research, a countercurrent
multi-tube heat exchanger was used as an internal heat exchanger
and the performance of the internal heat exchanger was also
analyzed by section-by-section method.
The overall heat transfer coefficient (U) shown in Eq. (6) was
calculated based on the waterside and CO2-side heat transfer
coefficients. The Gnielinski [23] or Petukhov [24] equations were
used for estimating the CO2-side heat transfer coefficient at
transcritical region in the gas cooler. The Gnielinski correlation
shown in Eq. (11) is used for 2300 Re 104.
hi f =2Re 1000Pr
1 12:7ffiffiffiffiffiffiffiffiffif=2
p Pr2=3 1
kiDi
(11)
where f 1:58lnRe 3:282.
The
Petukhov
correlation
for
104
Re
5
106
is
expressed
as
hi f =8RePr
1:07 12:7ffiffiffiffiffiffiffiffiffif =8
p Pr2=3 1
k iDi
(12)
where f = (0.79 ln(Re) 1.64)2.
The waterside heat transfer coefficient for the gas cooler was
calculated by using the DittusBoelter correlation [25] for as
shown in Eq. (13).
ho 0:023R0:8e Pr
0:4koDh
heating (13)
The CO2-side heat transfer coefficient in two-phase region at
the evaporator was estimated with the Gungor and Winterton
correlation
[26]
and
the
waterside
heat
transfer
coefficient
wascalculated by using DittusBoelter correlation expressed in
Eq. (14).
ho 0:023R0:8e Pr
0:3koDh
cooling (14)
In the case of the internal heat exchanger, the CO2-side heat
transfer coefficient in high pressure was calculated with the
Gnielinski or Petukhov equations and that in low pressure was
estimated by using the DittusBoelter correlation for heating.
4. Compressor
The compressor simulation was carried out on the basis of the
loss
and
efficiency-based
compressor
model
[27]. The
loss
andefficiency-based compressor model estimates the internal energy
balances in a compressor fromdesign, internalefficiency,andheat-
loss values specified by user. A schematic diagram of the loss and
efficiency compressor model is represented in Fig. 4. Ten unknown
variables shown in Fig. 4 are: (1) CO2 mass flow rate ( mc), (2)
enthalpy at the suction port (hsuction port), (3) enthalpy at the
discharge port (hdischarge port), (4) enthalpy at the shell outlet
(houtlet), (5) work done on the CO2( Wc), (6) work done on the shaft
( Ws), (7) work input to the compressor ( Wcm), (8) rate of heat loss
due to cooling of compressor and motor ( Qcooling), (9) rate of
compressor shellheat loss ( Qcan),and (10) rate ofheat transfer from
the discharge gas to the suction gas ( Qhillo). These ten unknowns
are iteratively calculated from the following 10 independent
equations:
Y.-J. Kim, K.-S. Chang/Journal of Industrial and Engineering Chemistry 19 (2013) 182718371830
-
8/13/2019 Geo Thermal Heat Exchanger
5/11
energy balance equations
(1) energy balance between the compressor shell inlet and
suction port
input = output
mchsuctionport hinlet Qhilo Qcooling Qcan (15)
(2) energy balance between the suction port and discharge port
mchdischargeport hsuctionport Wc (16)
(3) energy balance between the discharge port and compressor
shell outlet
mchoutlet hdischargeport Qhilo (17)
seven defining equations
(4)
Qhilo ahilo Wcm; actual (18)
where ahilois the fraction of compressor power consump-
tion transferred from the discharge line to the suction line
(specified by user or 0.03 as a default value)
(5)
Qcan acan Wcm; actual (19)
where acan is the fraction of the compressor power
consumption which is rejected from the shell to the
ambient air (specified by user or 0.9 (1.0 hmotorhmech))
(6)
Qcooling 1 hmotor hmech Wcm (20)
(7) energy balance between the suction port and discharge port
Wc mchisen;discharge port hsuction port
3413 hisen(21)
where hisenis the isentropic efficiency based on the suction
port
(8)
hmechWcWs
; Ws Wc
hmech(22)
(9)
hmotorWsWcm
; Wcm Ws
hmotor(23)
(10) hvol,suction port: volumetric efficiency based on the suction
port
mc hvol; suction port D Soper=ysuction port (24)
hvol; suction port mc;actualysuction port
D Soper
where D is the total compressor displacement [in3]; Soper is the
actual compressor motor speed [rpm]; ysuction port is the
specific volume at suction port.
Fig. 4. Schematic diagram of compressor energy balance.
Y.-J. Kim, K.-S. Chang/Journal of Industrial and Engineering Chemistry 19 (2013) 18271837 1831
-
8/13/2019 Geo Thermal Heat Exchanger
6/11
5. Expansion device
One important device in the geothermal heat pump cycle is the
expansion device. The purpose of the expansion device is to reduce
the pressure of the refrigerant and to control refrigerant mass flow
rate in the system. The common expansion devices widely utilized
in geothermal heat pump systems are capillary tubes, short tube
orifices, thermostatic expansion valve (TXV), and electronic
expansion valve (EEV). Among the expansion devices, the EEV
genders attention recently due to a wide range of operating
condition and high capability of load control.
In this research, the electronic expansion valvewasused and its
performance was evaluated with the equation given by Hwang
et al. [28]. The mass flow rate for CO2at the EEV can be estimated
with following equations:
p1 c1p2c2 p3
c3p4c4p5
c5 (25)
Five dimensionless p-numbers and the coefficients used in this
correlation are shown in Table 2. The parameters in Table 2 are
defined as follows:
m, mass flow rate, At,m, minimum area of orifice, rin, density at
the
EEV
inlet, Dp,
pressure
drop
across
expansion
valve,
L,effective orifice length, Dm, minimum orifice diameter, Do,
orifice diameter, pin, pressure at the EEV inlet, pc, critical
pressure of CO2, Tin, temperature at the EEV inlet, Tc, critical
temperature of CO2. It was reported that this empirical
correlation derived from Buckingham p-theorem predicts the
CO2 mass flow rate through the EEV within 5.4% errors.
6. Thermodynamic performance analysis for the CO2geothermal heat pump cycle
6.1. Procedures for thermodynamic performance analysis
Fig. 5 shows the flow diagram for the thermodynamic
performance-analysis
program
developed
in
the
present
study.The input data required to start the program are as follows: tube
diameter and length for outer and inner tubes, number of inner
tubes,flow rateand inlet temperature ofwater asa secondaryfluid,
expansion device specifications, and the degree of superheat at the
inlet of the compressor. Furthermore, the performance-analysis
program requires the geometric dimensions (diameter and length)
of thepipes in the cycle in order topredict thepressuredrops in the
geothermal heat pump cycle. Thermodynamic performance
analysis is based on the following assumptions:
(1) steady state operation;
(2) countercurrent flow in all type of heat exchangers;
(3) neglecting the heat loss through the heat exchangers and
expansion
devices;
(4) neglecting the change of kinetic and potential energy;
(5) neglecting pressure drop of thewater flow as a secondary fluid.
The compressor suction and discharge pressure are assumed to
be the main iterative variables as shown in Fig. 5. Based on
assumed compressor suction anddischargepressures, theCO2 flow
rate at the compressor and the conditions at compressor outlet are
estimated using the compressor module. The compressor inlet
conditions are also estimated by the degree of superheat given in
input datum. The gas cooler inlet conditions are calculated from
the compressor outlet conditions by considering the pressure drop
between the compressor outlet and the gas cooler inlet. And then,
the outlet conditions of the gas cooler including heat duty in the
gas cooler are estimated by using the gas cooler module on the
basis of the conditions atgas cooler inlet.Based on gas cooler outlet
and compressor inlet conditions estimated earlier, the inlet
conditions of the expansion device and the outlet conditions of
the evaporator are calculated using the internal heat exchanger
module. CO2flow rate in the expansion device is computed using
expansiondevicemodule and it is compared with theCO2 flow rate
estimated at the compressor module. The compressor discharge
pressure is iteratively adjusted using Secant method until the
difference between the CO2 flow rate at the compressor and the
CO2 flow rate in the expansion device is within a prescribedtolerance. After simulating the evaporator on the basis of outlet
conditions at the expansion device and evaporator specifications
given as input data, the compressor suction pressure is iteratively
adjusted using Secant method until the difference between the
evaporator outlet enthalpy computed at evaporator simulation
and enthalpy estimated at internal heat exchanger simulation is
within a prescribed limit.
The output of the thermodynamic-performance program
includes the COP, the CO2flow rate, compressor power consump-
tion, cooling capacity in the evaporator, heating capacity in the gas
cooler, line pressure drops, etc.
7. Experimental apparatus
The experimental apparatus as shown in Fig. 6 is comprised of a
compressor, indoor and outdoor heat exchangers, an internal heat
exchanger, an expansion device, an oil separator recovering the oil
from the compressor, and accumulator located at the exit of the
evaporator. In addition, aby-pass linewas installed to carry out the
comparative experimentsaccording to the existence of the internal
heat exchanger. The specifications for the CO2 geothermal heat
pump system are summarized in Table 3. A 4-way valve was also
equipped to choose the operation mode such as cooling and
heating. As shown in Table 3, all the equipment in the cycle was
designed to withstand 40 MPa pressure and all instruments and
fittings are able to safely operate at more than 20 MPa pressure.
The temperatures, pressures, flow rates, and power consump-
tions
at
the
important
points
of
the
cycle
were
measured
using
T-type thermocouple probes, pressure transducers, and a mass flow
meter. The uncertainties for the instruments are estimated as
0.2% for the pressure measurements, 0.2 8C for the temperature
measurements, 0.2% for the flow measurements, and 0.01% for the
integrating W-m.
Before operating the experiment, the system was vacuumed
first by the vacuum pump, and then proper amount of CO2 was
charged. Optimum amount of refrigerant charge was determined
at the highest COP, and found to be 2200 g without the internal
heat exchanger and 2400 g with the internal heat exchanger. All
data were collected when they reached the steady state. After
receiving sufficient amount of data, the EEV opening was changed
for the next test condition. A set of experiments for various EEV
openings
were
performed,
in
order
to
analyze
the
thermodynamic
Table 2
Five dimensionless p-numbers and coefficients in the correlation.
p1 p2 p3 p4 p5
m
At;m
ffiffiffiffiffiffiffiffiffiffiffiffi ffiffirinDp
q LDm
DmD0
pinpe
TinTc
Constant Value
C1 1.17100
C2 3.99102
C3 7.27
102
C4 3.86101
C5 4.55100
Units: m (kg/s),At,m (m2), rin (kg/m
3), Dp (Pa), L (m), Dm (m), Do (m), pin(Pa),pc(Pa),
Tin(K), Tc (K).
Y.-J. Kim, K.-S. Chang/Journal of Industrial and Engineering Chemistry 19 (2013) 182718371832
-
8/13/2019 Geo Thermal Heat Exchanger
7/11
performance parameters of the geothermal CO2 heat pump system
such as COP, compressor power, and the CO2 flow rate.
Experimental test conditions are presented in Table 4. The
experimental data were collected by averaging data measured
at every 10 s for 5 min, and decided to be valid when the
uncertainties were simultaneously maintainedwithin the limits of
range for temperatures with 0.1 8C, pressures with 5 kPa, and
flow rate with 0.2 g/s error bound.
8.
Results
and
discussion
In the present study, thermodynamic performance character-
istics of theCO2 geothermalheatpumpwere investigatedusing the
computer simulation. A number of case studies were carried out to
validate the simulation program. System performance character-
istics such as COP, cooling and heating capacities, CO2flow rates,
and compressor powers were expressed for various EEV openings
and for over a range of compressor frequencies.
In Fig. 7, simulation results are compared with experimental
data for the COP, cooling capacity, and compressor power in
coolingmode tovalidate the thermodynamicperformance analysis
of the simulation program. The mean deviations of the COPs,
cooling capacities, and compressor powers between experimental
and
simulation
results
are
4.5%,
3.8%,
6.5%,
respectively
at
the
5 8C
superheated degree and 32% EEV opening. The comparison
indicated that the simulation results were in good agreement
with those from the experiment with reasonable accuracy.
Variations of COP and cooling capacity with respect to
compressor frequencies ranged from 30 Hz to 55 Hz for 4 different
EEV opening positions at 5 8C of superheated degree in cooling
mode are shown in Fig. 8, and for compressor power in Fig. 9. As
shown in Figs. 8 and 9, the cooling capacity and compressor power
increase as compressor frequency increases as generally expected.
However,
the
consistent
linearity
of
the
increasing
rate
indicatesthe stable operability of the heat pump system. On the contrary,
the COP decreases upon increasing compressor frequency. In
general, the increase of compressor frequency induces an increase
of the refrigerant flow rate and pressure difference or compression
ratio. Increasing rate of high-pressure side due to frequency
increase is more noticeable than the decreasing rate of the low-
pressure side. The refrigerant flow rate increase leads to cooling
capacity increase, whereas the increase of pressure difference or
compression ratio results in required compressor power increase.
Since the increasing rate of compressorpower ishigher than thatof
cooling capacity, the consequent calculation of COP becomes
smaller with the compressor frequency increase in most cases.
In the case of EEV opening, itwas observed that theCOP, cooling
capacity,
and
compressor
power
all
decrease
with
increasing
EEV
Fig. 5. Flow chart of the thermodynamic-performance analysis program.
Y.-J. Kim, K.-S. Chang/Journal of Industrial and Engineering Chemistry 19 (2013) 18271837 1833
-
8/13/2019 Geo Thermal Heat Exchanger
8/11
opening. The CO2 inlet temperature at the evaporator increases
with increasing EEV opening and the heat exchanging rate is
reduced due to the decrease in the inlet temperature difference
between CO2and secondary fluid of water. On the other hand, CO2flow rate increases with the increase of EEV opening, and
consequently
cooling
capacity
increases
with
the
increase
of
flow
rate. For the just given operating conditions in this study, these
combined effects result in the decrease of the COP and cooling
capacity with increasing EEV opening.
Fig. 10 shows variations of CO2 flow rate with respect to
compressor frequency and EEV opening at the 5 8C superheated
degree
in
cooling
mode.
As
seen
in
Fig.
10, CO2flow
rate
increaseswith increasing compressor frequency and EEV opening. As
explained earlier, CO2 flow rates increase with the increase of
compressor frequency and EEV opening due to expansion of the
throat area of EEV.
Variation of COP with respect to superheated degree and
compressor frequency at 20% EEV opening in cooling mode is
represented in Fig. 11. It is indicated that the COP decreases
linearlywith respect to the increment of the superheateddegree in
the range of39 8Cwhen EEV opening is kept at a value of20%. This
can be interpreted from the fact that COPs of the cycle are reduced
because compressor power increases more rapidly than cooling
capacity with an increase in the superheated degree.
Fig. 12 represents the comparison ofCOPs of the systemwith an
IHX
(internal
heat
exchanger)
and
a
basic
cycle
without
the
IHX.
Fig. 6. Schematic diagram of experimental apparatus.
Table 3
Specifications of the geothermal heat pump system.
Compressor Rotary type
Maximum pressure: 45MPa
Power requirement: 10.5kW
Frequency response: 3070Hz
Expansion valve Maximum pressure: 40MPa
Allowable flow rate: 0100g/s4-way valve Maximum pressure: 40MPa
Heat exchangers Types Outer tube Inner tube Path
OD/thickness (mm) OD/thickness (mm) No. No. L (m)
Outdoor exchanger Multitube 25.4/1.2 4/0.5 8 2 1.7
Indoor exchanger Multitube 19.05/1.2 4/0.5 8 2 1.65
Internal exchanger Multitube 19.05/1.2 4/0.5 8 2 1
Table 4
Test conditions for the geothermal heat pump system.
Test conditions Operation
Cooling Heating
Compressor freq. (Hz) 3060
Compressor (rpm) 18003600
CO2charge (g) 18002400
EEV opening (%) 1050
Water inlet temperature at the evaporator (8C) 17 12
Water flow rate at the evaporator (kg/s) 0.283 0.217
Water inlet temperature at the gas cooler (8C) 25 30
Water flow rate at the gas cooler (kg/s) 0.333 0.283
Y.-J. Kim, K.-S. Chang/Journal of Industrial and Engineering Chemistry 19 (2013) 182718371834
-
8/13/2019 Geo Thermal Heat Exchanger
9/11
-
8/13/2019 Geo Thermal Heat Exchanger
10/11
inlet temperature at the evaporator just after the EEV increases
with increasing EEV opening, so that the heating capacity is
decreased due to the increase of the inlet temperature difference
between CO2 and water. However, in the case of heating mode,compressor power was kept almost constant as the EEV opening
increased. As a result, the COPs were reduced as the EEV opening
increased.
The CO2 flow rate as a function of various EEV openings and
compressor frequencies at the 5 8C superheated degree in heating
mode is represented in Fig. 15. As shown in Fig. 15, the CO2flow
rate has a tendency to increase as the compressor frequency andEEV opening increase.
Fig. 16 shows variation of COPs with respect to superheated
degree and compressor frequency at the 16% EEV opening in
heating mode. The COPs in heating mode decrease as the
superheated degree increases in the range of 39 8C due to the
same reason mentioned for cooling mode. However, COPs in
heatingmode more steeply decrease than the case of coolingmode
with the increase of compressor frequencies.
Fig. 17 indicates the comparison of COPs as a function of
compressor frequency for the cycle with IHX (internal heat
exchanger) and a basic cycle without IHX in heating mode. The
22% EEV opening was determined to be optimum value for the
basic cycle and 16% EEV opening for the cycle with the IHX in
heating mode. In contrast to the cooling mode, the COPs of theheating cyclewith the IHXwere slightly smaller than those of basic
cycle at all compressor frequencies (1.32.4% smaller with IHX in
the frequency range of 3055 Hz). With the use of IHX, the heating
capacity increases due to the decrease of CO2 quality at the
evaporator inlet resulting from the lowered temperature of CO2leaving from the gas cooler. On the contrary, the heating capacity
2.5
2.7
2.9
3.1
3.3
3.5
3.7
3.9
4.1
4.3
4.5
25 30 35 40 45 50 55 60
COP
cooling
Compressor frequency[Hz]
no internal heat exchanger
with internal heat exchanger
(EEV opening : 32%)
(EEV opening : 20%)
Fig. 12. Cooling performance with compressor frequency for IHX.
1
2
3
4
5
6
7
8
9
1.8
2.0
2.2
2.4
2.6
2.8
3.0
3.2
3.4
3.6
3.8
25 30 35 40 45 50 55 60
COPheating
Compressor frequency[Hz]
Heatingcapacity&Po
wer[kW]
COP_heating
Heating capacity
Compressor power
EEV opening: 14%
Superheated degree: 5C
Fig. 13. Variation of COPheating, heating capacity and compressor power for
compressor frequency (heating, superheated degree: 5 8C, EEV opening: 14%).
1
2
3
4
5
6
7
8
9
2.5
2.6
2.7
2.8
2.9
3.0
25 30 35 40 45 50 55 60
COPheating
Compressor frequency[Hz]
Heatingcapacity&Power[kW]
COP_heating
Heating capacity
Compressor power
EEV opening 20%
Superheated degree: 5C
Fig. 14. Variation of COPheating, heating capacity and compressor power for
compressor frequency (heating, superheated degree: 5 8C, EEV opening: 20%).
0.02
0.025
0.03
0.035
0.04
0.045
0.05
25 30 35 40 45 50 55 60
CO2flowrate[Kg/s]
Compressor frequency[Hz]
EEV 16%
EEV 20%
EEV 24%
EEV 28%
Superheated degree: 5C
Fig. 15. CO2 flow rate with EEV opening and compressor frequency (heating,
superheated degree: 5 8C).
2.7
2.8
2.9
3
3.1
3.2
3.3
25 30 35 40 45 50 55 60
COPheating
Compressor frequency[Hz]
3C
5C
7C
9C
EEV opening: 16%
Superheated degree
Fig. 16. Variation of COPheatingfor superheated degree and compressor frequency
(EEV opening: 16%).
Y.-J. Kim, K.-S. Chang/Journal of Industrial and Engineering Chemistry 19 (2013) 182718371836
-
8/13/2019 Geo Thermal Heat Exchanger
11/11
decreaseswith thedecreaseofCO2flow rate due to the reduction of
the EEV opening from22%without IHX to16%with IHX. As a result,
the heating capacity increases by about 8.7% with the use of IHX,
whereas the required compression power increasesby about10.6%due to the increase of the compressor outletpressure resulted from
the reduction of EEV opening. In overall, it was founded that the
use of IHX in heatingmode is not helpful to increase the COP of the
CO2geothermal heat pump system.
9. Conclusions
In the present study, a thermodynamic-performance analysis
program for CO2 geothermal heat pump system incorporating the
internal heat exchanger was developed. It consists of several
subroutines for modeling an evaporator, gas cooler, internal heat
exchanger, compressor, and electronic expansion valve and
estimating the thermodynamic and transport properties of CO2
and water. This program can be used to simulate the steady-statethermodynamic performances ofCO2geothermal heat pumpsystem
such as COP, heating and cooling capacity, power consumption, etc.
A number of case studies were carried out in order to validate the
thermodynamic analysis program and the simulation results were
compared with the experimental results. It was found that this
programmaybehighly advantageous to save time and to reduce the
risk, whichmaytakeplace inexperiment. This simulation program is
intended to serve as auseful tool fora thermodynamic performance
analysis when optimizing complex system variables and establish-
ing efficient operating conditions in the CO2 geothermal heat pump
systems. In the future the capabilities of this program will be more
improved for geothermal heat pump systems using natural
refrigerants such as ammonia and hydrocarbons. The following
important
results
were
obtained
in
this
study:
(1) e-Ntumethodwasused for simulating theheat exchangers such
as the evaporator, gas cooler, and internal heat exchanger.
(2) The compressor simulation was carried out on the basis of the
loss and efficiency-based compressor model which estimates
the internal energy balances in a compressor from design,
internal efficiency, and heat-loss values specified by user.
(3) The performance of the electronic expansion valve was
evaluated with the empirical equation derived from Bucking-
ham p-theorem.
(4) The mean deviations of the COPs, cooling capacities, and
compressor powers between experimental and simulation
results are 4.5%, 3.8%, 6.5%, respectively. The comparison
indicated that the simulation results were in agreement with
those from the experiment with reasonable accuracy.
(5) It was found that the COPs of the cycle with the IHX were
improved than those of the basic cycle by 26% in cooling
mode.
(6) In contrast with the cooling mode, the COPs of the heating
cycle with the IHX were slightly smaller than those of basic
cycle. It indicated that the use of IHX in heating mode has no
effect to increase the COP of the CO2 geothermal heat pump
system.
References
[1] R.J. Dossat, Principles of Refrigeration, 4th edition, Prentice-Hall, 1997.[2] M.P. Desai, Design Optimization and Development of an Energy-Efficiency Vapor
Compression Cooling System, 1997, p. 1.[3] S.B.Riffat, C.F.Afonso,A.C. Oliveira,D.A. Reay,AppliedThermalEngineering 17 (1)(1997) 33.
[4] N. Kagawa, International Journal of Air-Conditioning and Refrigeration 15 (4)(2007) 182.
[5] M.S. Kim, J.S. Lee, M.S. Kim, International Journal of Air-Conditioning andRefrig-eration 17 (3) (2009) 100.
[6] Y. Hwang, M. Ohadi, R. Radermacher, Feature Article, The American Society ofMechanical Engineers, 1988.
[7] J.M. Smith, H.C. Vaness, M.M. Abbott, Introduction to Chemical EngineeringThermodynamics, 5th edition, McGraw-Hill, 1996,, p. 307.
[8] G. Lorentzen, J. Pettersen, in: Proceedings of the IIR International Symposium onRefrigeration, Energy, and Environment, Trondheim, Norway, (1992), p. 147.
[9] J.S. Brown, et al. International Journal of Refrigeration 25 (2002) 19.[10] C.E. Bullock, in: Proceedings of ASHARE/NIST Refrigerants Conference, Gaithers-
burg, MD, (1997), p. 20.[11] Y. Hwang, R. Radermacher, HVAC&R Research 4 (3) (1998) 245.[12] J.S. Brown, F. Samuel, Y. Motta, P.A. Domanski, International Journal of Refrigera-
tion 25 (2002) 19.
[13] R.P. McEnaney, D.E. Boewe, J.M. Yin, Y.V. Park, in: Proceedings of the SeventhInternational Refrigeration Conference at Purdue University, West Lafayette,Indiana, (1998), p. 145.
[14] R.P. McEnaney, Y.C. Park, J.M. Yin, P.S. Hrnjak, SAE International Congress andExposition, Detroit, Michigan, 1999 (Paper No. 1999-01-0872).
[15] M. Preissner, B. Cutler, S. Singanamalla, Y. Hwang, R. Radermacher, in: Proceed-ings of4th IIR-GustavLorentzenConferenceonNaturalWorkingFluids at Purdue,West Lafayette, IN, (2000), p. 185.
[16] H. Hermann, R. Rene, 4th IIR-Gustav Lorentzen Conference, 2000, p. 43.[17] A. Hanfner, 4th IIR-Gustav Lorentzen Conference, 2000, p. 177.[18] W. Adriansyah, Energy and Buildings 36 (2004) 690.[19] Y.J. Kim, K.S. Chang,H.H. Kim, Journal of Industrial Engineeringand Chemistry 13
(5) (2007) 674.[20] S.G. Kim, M.S. Kim, Korean Journal of Air-conditioning and Refrigeration Engi-
neering 15 (6) (2003) 471.[21] P.A. Domanski, NISTIR 89-4133, NIST, 1989.[22] B. Youn, H.Y. Park, Y.S. Kim, Proceedings of the SAREK 1996 25 (2) (1996) 151.[23] V. Gnielinski, International Chemical Engineering 16 (2) (1976) 359.[24] B.S. Petukhov, Advances in Heat Transfer 6 (1970) 503.[25] P.W. Dittus, L.M.K. Boelter, University of California Publication in Engineering 2
(13) (1930) 443.[26] K. Gungor, R. Winterton, International Journal of Heat and Mass Transfer 29
(1986) 351.[27] S.K. Fischer, C.K. Rice, ORNL/CON-80/R1, Oak Ridge National Lab, 1980.[28] Y.W. Hwang, O.J . Kim, in: Proceedings of the SAREK 2007 Summer Annual
Conference, 2007, p. 1237.
2.5
2.6
2.7
2.8
2.9
3
3.1
3.2
3.3
3.4
3.5
25 30 35 40 45 50 55 60
COPheating
Compressor frequency[Hz]
no internal heat exchanger
with internal heat exchanger
(EEV opening : 22%)
(EEV opening :
Fig. 17. Heating performance with compressor frequency for IHX.
Y.-J. Kim, K.-S. Chang/Journal of Industrial and Engineering Chemistry 19 (2013) 18271837 1837