gexol marine 12/03 - amercable · type mmv medium power cable single conductor: 5kv ... medium...
TRANSCRIPT
37-105
Type MMV Medium Power CableSingle Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°CMulti-Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°C
www. amercable.com • e-mail: [email protected]
ApplicationsNexans AmerCable’s Type MMV marinemedium voltage cables are for useaboard commercial ships, mobile offshoredrilling units (MODUs), and fixed orfloating offshore facilities.
Featuresn These cables utilize flexiblestranded conductors, braided shieldsand a braided armor (when armored)which make them very suitable forapplications involving repeated flexingand high vibration.
n These cables have a small minimumbending radius (6xOD for unarmoredcables and 8xOD for armored cables) for easy installation.
n Optional uninsulated groundingconductors sized per UL 1072.
n The increased flexibility of this cableallows for termination of one end and coiling on multiple module offshore platforms. Then coiling andterminating other end when modulesare mated at sea thereby reducinginstallation time.
n Passes IEC 332-3 Category A and IEEE 1202 flame tests.
Conductor ShieldA combination of semi-conducting tape andextruded thermosetting semi-conducting materialmeeting UL 1309, IEEE 1580 and UL1072.
Armor (optional)(Optional) 0.0126" bronze braid providing 88%minimum coverage meeting UL 1309 and IEEEStd. 45-1998.
JacketA black, arctic grade, flame retardant, oil, abrasion,chemical and sunlight resistant thermosettingcompound meeting UL 1309, IEEE 1580 and UL 1072. Colored jackets for signifying differentvoltage levels are also available on special request(ie. yellow = 5kV, orange = 8kV and red = 15kV).
Sheath (optional)A black, arctic grade, flame retardant, oil, abrasion,chemical, and sunlight resistant thermosettingcompound meeting UL 1309, IEEE 1580 and UL 1072. Colored jackets for signifying differentvoltage levels is also available on special request(ie. yellow = 5kV, orange = 8kv and red = 15kV).
Metallic ShieldComposite shieldconsisting of 0.0126" tinned copper braided with nylon providing 60% copper Shieldedcoverage meeting UL 1309, IEEE Std. 1580 and UL 1072. The nylon is colored for easy phase identification (three conductor = black, blue, red) without the need toremove the shield to findan underlying colored tape.
Insulation ShieldSemi-conducting tape, with overlap, for fast andeasy termination meeting UL 1309, IEEE 1580 and UL 1072.
ConductorsSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.
InsulationExtruded thermosetting90°C Ethylene PropyleneRubber (EPR), meeting UL 1309 (Type E), IEEE 1580 (Type E) and UL 1072.
Grounding Conductor (optional)One uninsulated soft annealed flexible strandedtinned copper conductor per ASTM B 33 andsized according to Table 21.1 of UL 1072.
Ratings & Approvals� UL Listed as Marine Shipboard Cable (E111461)� American Bureau of Shipping (ABS)� Det Norske Veritas (DNV) Pending� Lloyd’s Register of Shipping (LRS) Pending� 90˚C Temperature Rating� Voltage Rating – 5kV to 15kV(25kV available on request)
HawkeGland Types Unarmored Armored & Sheathed
Industrial & Safe Area (IP68) 121 153-XIncreased Safety 501/421 501/453/U“EExe”Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U(2 liter or > enclosures)
Zone 1 & 2
Inductive Voltage Inductive Voltage Single DC ACSize Part Nominal Weight Reactance Drop Nominal Weight Reactance Drop In Free Triangular Banked Resistance ResistanceAWG/ No. Diameter (Lbs./ (ohms/ (Volts/amp/ Diameter (Lbs./ (ohms/ (Volts/amp/ Air Configuration in Tray at 25°C at 90°C, 60 Hzkcmil mm2 37-105 (inches) 1000 ft.) 1000 ft.) 1000 ft.) (inches) 1000 ft.) 1000 ft.) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.)
86421
1/02/03/04/0
262313373444535646777
1111
7.612.5
213443547086
109132159189227273326394562
-101-102-103-104-105-106-107-108-109-110-111-112-113-114-115-116-117
0.5640.6040.6860.7500.7900.8770.9370.9801.0421.1211.1871.2521.3271.4081.4961.5991.883
204252344449528659787910
108612721467169219682294267231544414
1.2820.8220.5660.3610.2960.2450.2020.2780.1410.1220.1080.0950.0860.0770.0700.0650.054
0.0540.0500.0440.0410.0400.0390.0380.0370.0350.0340.0330.0320.0320.0310.0300.0300.029
0.7510.8360.9180.9811.0641.1081.1681.2121.2741.3531.4191.4841.5591.7061.7931.8812.169
401502622748894
100411601298149617081926217424762949336138595255
0.0610.0580.0510.0470.0470.0450.0430.0420.0400.0380.0370.0360.0350.0350.0340.0330.033
1.2880.8300.5730.3670.3030.2500.2070.1730.1460.1270.1120.0990.0900.0820.0750.0690.057
80107141186214247285328381435486544606682767865
1084
6992
121159184212244281325371413460510570635709853
6891
120158182210242279324370413462515580652735921
0.6940.4360.2860.1750.1400.1110.0890.0700.0560.0460.0380.0320.0270.0220.0190.0150.011
0.8850.5560.3760.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.0250.017
Unarmored
Single Conductor Type MMV Marine Medium Voltage – 5kV, 100/133% Insulation LevelArmored &
Sheathed (BS) Ampacity
Inductive Voltage Inductive Voltage Single DC ACSize Part Nominal Weight Reactance Drop Nominal Weight Reactance Drop In Free Triangular Banked Resistance ResistanceAWG/ No. Diameter (Lbs./ (ohms/ (Volts/amp/ Diameter (Lbs./ (ohms/ (Volts/amp/ Air Configuration in Tray at 25°C at 90°C, 60 Hzkcmil mm2 37-105 (inches) 1000 ft.) 1000 ft.) 1000 ft.) (inches) 1000 ft.) 1000 ft.) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.)
6421
1/02/03/04/0
262313373444535646777
1111
12.5213443547086
109132159189227273326394562
-118-119-120-121-122-123-124-125-126-127-128-129-130-131-132-133
0.6560.7380.8010.8840.9290.9891.0321.0941.1731.2391.3041.3791.4601.5481.6511.935
283378486604702835956
113513241522175020292359274131864498
0.8240.5670.3620.2980.2460.2030.1690.1420.1230.1090.0960.0870.0780.0710.0660.055
0.0520.0460.0430.0420.0410.0390.0380.0360.0350.0340.0330.0330.0320.0310.0300.030
0.8880.9701.0331.1081.1601.2201.2641.3261.4051.4711.5361.6031.7461.8331.9492.233
549673806942
107212261363156317791999225025383012342839445388
0.0590.0520.0480.0470.0460.0440.0430.0410.0390.0380.0370.0360.0360.0350.0340.033
0.8310.5740.3680.3040.2510.2080.1740.1470.1280.1130.1000.0910.0820.0750.0700.058
107141186214247285328381435486544606682767865
1084
92121159184212244281325371413460510570635709853
91120158182210242279324370413462515580652735921
0.4360.2860.1750.1400.1110.0890.0700.0560.0460.0380.0320.0270.0220.0190.0150.011
0.5560.3760.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.0250.017
Unarmored
Single Conductor Type MMV Marine Medium Voltage – 8kV, 100% Insulation LevelArmored &
Sheathed (BS) Ampacity
Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
See page 28 for MMV
Stranding Profile
www. amercable.com • e-mail: [email protected]
Inductive Voltage Inductive Voltage Single DC ACSize Part Nominal Weight Reactance Drop Nominal Weight Reactance Drop In Free Triangular Banked Resistance ResistanceAWG/ No. Diameter (Lbs./ (ohms/ (Volts/amp/ Diameter (Lbs./ (ohms/ (Volts/amp/ Air Configuration in Tray at 25°C at 90°C, 60 Hzkcmil mm2 37-105 (inches) 1000 ft.) 1000 ft.) 1000 ft.) (inches) 1000 ft.) 1000 ft.) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.)
6421
1/02/03/04/0
262313373444535646777
1111
12.5213443547086
109132159189227273326394562
-134-135-136-137-138-139-140-141-142-143-144-145-146-147-148-149
0.7100.7920.8980.9380.9831.0431.0861.1481.2271.2931.3581.4331.4601.6021.7671.989
317417565648751884
1007118913811584181320952359281433764587
0.8260.5690.3650.3000.2470.2040.1710.1430.1240.1100.0970.0880.0780.0720.0670.055
0.0540.0470.0450.0440.0420.0400.0390.0380.0360.0350.0340.0330.0320.0320.0320.031
0.9421.0161.1291.1701.2141.2741.3181.3801.4591.5241.5821.7191.7581.8882.0652.275
603725916
1022114012931432163518542081231827343034352941815470
0.0600.0530.0500.0490.0470.0450.0440.0420.0400.0390.0380.0380.0360.0360.0360.034
0.8320.5750.3700.3050.2520.2090.1750.1480.1290.1140.1010.0930.0830.0760.0710.058
107141186214247285328381435486544606682767865
1084
92121159184212244281325371413460510570635709853
91120158182210242279324370413462515580652735921
0.4360.2860.1750.1400.1110.0890.0700.0560.0460.0380.0320.0270.0220.0190.0150.011
0.5560.3760.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.0250.017
Unarmored
Single Conductor Type MMV Marine Medium Voltage – 8kV, 133% Insulation LevelArmored &
Sheathed (BS) Ampacity
Inductive Voltage Inductive Voltage Single DC ACSize Part Nominal Weight Reactance Drop Nominal Weight Reactance Drop In Free Triangular Banked Resistance ResistanceAWG/ No. Diameter (Lbs./ (ohms/ (Volts/amp/ Diameter (Lbs./ (ohms/ (Volts/amp/ Air Configuration in Tray at 25°C at 90°C, 60 Hzkcmil mm2 37-105 (inches) 1000 ft.) 1000 ft.) 1000 ft.) (inches) 1000 ft.) 1000 ft.) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.)
21
1/02/03/04/0
262313373444535646777
1111
3443547086
109132159189227273326394562
-150-151-152-153-154-155-156-157-158-159-160-161-162-163
1.0501.0881.1331.1911.2361.2981.3971.4631.5281.6031.7421.8301.9652.187
692778883
10241154134315681778201523132762316537294930
0.3690.3030.2510.2080.1740.1460.1280.1130.1000.0910.0820.0750.0700.057
0.0490.0470.0450.0440.0420.0400.0390.0380.0370.0360.0360.0350.0340.033
1.2691.3081.3521.4101.4561.5181.6161.7441.8091.8842.0242.1122.2462.468
10881186130114621608181720772422268530143520396045785870
0.0530.0510.0490.0470.0460.0440.0420.0420.0410.0400.0390.0380.0370.036
0.3730.3080.2550.2120.1780.1500.1310.1170.1040.0950.0860.0790.0730.060
186214247284327378431481536598672754848
1061
164189217250288332377418464514574638709857
158182210241278321366409456508571641721902
0.1750.1400.1110.0890.0700.0560.0460.0380.0320.0270.0220.0190.0150.011
0.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.0250.017
Unarmored
Single Conductor Type MMV Marine Medium Voltage – 15kV, 100% Insulation LevelArmored &
Sheathed (BS) Ampacity
Ordering Type MMV Medium Voltage CablesExample:
• 3 conductor power cable• 8kV 100%• #2 AWG• ground• bronze armored & sheathed
Nexans AmerCableType MMV Prefix
Specific Cable Number(from charts)
Armor RequirementBS – armored &
sheathedBlank – no armor
Ground ConductorG – with groundBlank – no ground
37–105 – 319 BS G
37-105
Type MMV Medium Voltage CableSingle Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°CMulti-Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°C
See page 28 for MMV
Stranding Profile
Inductive Voltage Inductive Voltage Single DC ACSize Part Nominal Weight Reactance Drop Nominal Weight Reactance Drop In Free Triangular Banked Resistance ResistanceAWG/ No. Diameter (Lbs./ (ohms/ (Volts/amp/ Diameter (Lbs./ (ohms/ (Volts/amp/ Air Configuration in Tray at 25°C at 90°C, 60 Hzkcmil mm2 37-105 (inches) 1000 ft.) 1000 ft.) 1000 ft.) (inches) 1000 ft.) 1000 ft.) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.)
21
1/02/03/04/0
262313373444535646777
1111
3443547086
109132159189227273326394562
-164-165-166-167-168-169-170-171-172-173-174-175-176-177
1.1321.1701.2151.2731.3381.4001.4791.5451.6101.7471.8241.9442.0472.269
771863970
11121267146116701884213225412889335038705083
0.3700.3050.2520.2090.1760.1480.1290.1140.1010.0930.0840.0770.0710.058
0.0500.0490.0470.0450.0440.0420.0400.0390.0380.0380.0370.0360.0350.034
1.3521.3901.4341.4921.5581.6201.7611.8271.8922.0292.1062.2262.3292.551
11941299141615781756197123202561283633013680419147536057
0.0550.0530.0510.0490.0470.0460.0440.0430.0420.0410.0400.0390.0380.036
0.3750.3090.2560.2130.1790.1510.1330.1180.1050.0960.0870.0800.0740.061
186214247284327378431481536598672754848
1061
164189217250288332377418464514574638709857
158182210241278321366409456508571641721902
0.1750.1400.1110.0890.0700.0560.0460.0380.0320.0270.0220.0190.0150.011
0.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.0250.017
Unarmored
Single Conductor Type MMV Marine Medium Voltage – 15kV, 133% Insulation LevelArmored &
Sheathed (BS) Ampacity
Single InductiveSize Nominal Weight Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Voltage Drop OptionalAWG/ Part No. Diameter (Lbs./ Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Groundingkcmil mm2 37-105 (inches) 1000 ft.) (inches) 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor
86421
1/02/03/04/0
262313373444535646777
7.612.5
213443547086
109132159189227273326394
-301-302-303-304-305-306-307-308-309-310-311-312-313-314-315-316
1.1371.2261.4021.5381.6261.7831.9132.0072.1402.3102.4532.5892.8182.9743.1643.385
781955
1307169019742423288433153937461953196107728084639814
11526
12181424182423722692323237494220489956546549740286849964
1140713226
1.3691.4571.6251.8241.9112.0812.2102.3052.4382.6082.7963.0003.1613.3173.5073.729
6688
116152175201232266306348386429455528584647
567599
129149171197226260296328365387449496550
0.7080.4450.3000.1840.1470.1170.0930.0740.0580.0480.0400.0340.0280.0240.0200.016
0.8850.5560.3760.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.025
0.0480.0440.0390.0360.0350.0340.0330.0320.0310.0300.0290.0290.0280.0280.0270.027
1.2750.8150.5600.3560.2910.2390.1960.1630.1360.1180.1040.0920.0830.0740.0670.062
866644433322111
1/0
Unarmored
Three Conductor Type MMV Marine Medium Voltage – 5kV, 100/133% Insulation LevelArmored &
Sheathed (BS) Ampacity
Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
See page 28 for MMV
Stranding Profile
www. amercable.com • e-mail: [email protected]
Single InductiveSize Nominal Weight Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Voltage Drop OptionalAWG/ Part No. Diameter (Lbs./ Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Groundingkcmil mm2 37-105 (inches) 1000 ft.) (inches) 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor
6421
1/02/03/04/0
262313373444535646
12.5213443547086
109132159189227273326
-332-333-334-335-336-337-338-339-340-341-342-343-344-345
1.4541.6301.8291.9162.0122.1412.2362.3692.5392.6802.8853.0363.2103.400
1249163921622467283833273763441751335870688479599167
10554
189623592964330637174259473454436422722783409491
1078212261
1.7401.9162.1142.2022.2972.4272.5212.6542.8883.0313.2353.3803.5523.742
88116152175201232266306348386429455528584
7599
129149171197226260296328365387449496
0.4450.3000.1840.1470.1170.0930.0740.0580.0480.0400.0340.0280.0240.020
0.5560.3760.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.028
0.0480.0430.0400.0380.0370.0360.0350.0330.0320.0320.0310.0300.0300.029
0.8200.5640.3590.2940.2420.1990.1660.1390.1210.1060.0940.0850.0760.069
66644433322111
Unarmored
Three Conductor Type MMV Marine Medium Voltage – 8kV, 133% Insulation LevelArmored &
Sheathed (BS) Ampacity
Single InductiveSize Nominal Weight Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Voltage Drop OptionalAWG/ Part No. Diameter (Lbs./ Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Groundingkcmil mm2 37-105 (inches) 1000 ft.) (inches) 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor
6421
1/02/03/04/0
262313373444535646777
12.5213443547086
109132159189227273326394
-317-318-319-320-321-322-323-324-325-326-327-328-329-330-331
1.3381.5141.6501.8001.8952.0252.1192.2522.4222.5652.7042.9303.0963.2673.512
1094146219702263261731003531416248645581639275828806
1013711959
158921342725305434543989445851405913688477609059
103661178013708
1.5611.7991.9982.0852.1812.3102.4042.5372.7072.9143.0543.2803.4393.6113.855
88116152175201232266306348386429455528584647
7599
129149171197226260296328365387449496550
0.4450.3000.1840.1470.1170.0930.0740.0580.0480.0400.0340.0280.0240.0200.016
0.5560.3760.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.025
0.0460.0410.0380.0370.0360.0340.0330.0320.0310.0300.0300.0290.0290.0280.028
0.8180.5620.3570.2930.2410.1980.1650.1380.1190.1050.0930.0840.0750.0680.063
66644433322111
1/0
Unarmored
Three Conductor Type MMV Marine Medium Voltage – 8kV, 100% Insulation LevelArmored &
Sheathed (BS) Ampacity
37-105
Type MMV Medium Voltage CableSingle Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°CMulti-Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°C
Ordering Type MMV Medium Voltage CablesExample:
• 3 conductor power cable• 8kV 100%• #2 AWG• ground• bronze armored & sheathed
Nexans AmerCableType MMV Prefix
Specific Cable Number(from charts)
Armor RequirementBS – armored &
sheathedBlank – no armor
Ground ConductorG – with groundBlank – no ground
37–105 – 319 BS G
See page 28 for MMV
Stranding Profile
Single InductiveSize Nominal Weight Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Voltage Drop OptionalAWG/ Part No. Diameter (Lbs./ Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Groundingkcmil mm2 37-105 (inches) 1000 ft.) (inches 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor
21
1/02/03/04/0
262313373444535
3443547086
109132159189227273
-346-347-348-349-350-351-352-353-354-355-356
2.1572.2392.3352.4612.5592.6912.7492.8813.0213.1833.357
27593073346639914466515057496483733183809599
3697404544775242576465137348818488569983
11285
2.4432.5242.6202.8102.9103.0413.1523.2873.3653.5273.701
156178205234269309352389432456528
133151174199229263299331367388449
0.1840.1470.1170.0930.0740.0580.0480.0400.0340.0280.024
0.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.033
0.0420.0400.0390.0370.0360.0350.0340.0330.0320.0310.031
0.3610.2960.2440.2010.1680.1410.1220.1070.0950.0860.077
64443332211
Unarmored
Three Conductor Type MMV Marine Medium Voltage – 15kV, 100% Insulation LevelArmored &
Sheathed (BS) Ampacity
Single InductiveSize Nominal Weight Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Voltage Drop OptionalAWG/ Part No. Diameter (Lbs./ Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Groundingkcmil mm2 37-105 (inches) 1000 ft.) (inches) 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor
21
1/02/03/04/0
262313373444535
3443547086
109132159189227273
-357-358-359-360-361-362-363-364-365-366-367
2.3342.4162.5122.6372.8422.9762.9893.0913.2043.3473.521
3125347038744411520659306412699078978879
10144
413745155150574866407430783185299510
1056011910
2.6192.7012.8612.9873.1923.3253.3403.3943.5483.6903.865
156178205234269309352389432456528
133151174199229263299331367388449
0.1840.1470.1170.0930.0740.0580.0480.0400.0340.0280.024
0.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.033
0.0440.0430.0410.0390.0380.0370.0350.0340.0340.0330.033
0.3640.2990.2460.2030.1700.1420.1240.1090.0970.0880.079
64443332211
Unarmored
Three Conductor Type MMV Marine Medium Voltage – 15kV, 133% Insulation LevelArmored &
Sheathed (BS) Ampacity
Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
Ordering Type MMV Medium Voltage CablesExample:
• 3 conductor power cable• 8kV 100%• #2 AWG• ground• bronze armored & sheathed
Nexans AmerCableType MMV Prefix
Specific Cable Number(from charts)
Armor RequirementBS – armored &
sheathedBlank – no armor
Ground ConductorG – with groundBlank – no ground
37–105 – 319 BS G
See page 28 for MMV
Stranding Profile
www. amercable.com • e-mail: [email protected]
37-105VFD
Type MMV-VFDPower CableThree Conductor: 8kV –15kV • 133% Insulation Level • Rated 90°C
ApplicationsA flexible, braid and foil shielded,power cable specifically engineered for use in medium voltage variable frequency AC drive (VFD) applications.
Featuresn Flexible stranded conductors andbraided shields. Suitable for applications involving repeated flexing and high vibration.
n Small minimum bending radius (8x OD) for easy installation.
n Insulation has a very low dielectricconstant. This allows for longeroutput cable distances andminimizes common mode current.
n Overall braid plus foil shield is engineered with 100% coverage anda surface transfer impedance <50milliohms at 10MHz to contain EMI.
n Symmetrical insulated ground conductors reduce induced voltageimbalances and carry common mode noise back to the drive.
n High strand count conductors andbraid shield design is much more flexible, easier to install and moreresistant to vibration than Type MC cable.
n Severe cold durability: exceeds CSA cold bend/cold impact (-40˚C/-35˚C).
n Flame retardant: IEC 332-3 Category A and IEEE 1202.
n Suitable for use in Class I, Division 1, and Zone 1 environments.
Conductors (3)Soft annealed flexible strandedtinned copper per IEEE 1580 Table 11.
Conductor ShieldA combination of semi-conducting tape andextruded thermosetting semi-conducting materialmeeting UL 1309, IEEE 1580 and UL1072.
Armor/EMI ShieldOverall tinned copper braid plus aluminum/polyester tape provides 100% coverage. This braid serves as both an armor and EMI shield meeting both IEEE 1580 and UL 1307/CSA 245.
JacketA black, arctic grade, flame retardant, oil, abrasion, chemical and sunlight resistant thermosetting compound meeting UL 1309/CSA 245, IEEE 1580, and UL 1072. This jacket allows for isolation between the insulation shields and overall shield. Shieldscan then be terminated on opposite ends tominimize circulating currents.
Sheath (optional)A black, arctic grade, flame retardant, oil,abrasion, chemical and sunlight resistant thermosetting compound meeting UL 1309/CSA 245, IEEE 1580, and UL 1072.Colored jackets for signifying different voltage levels are also available on specialrequest (orange = 8kV and red = 15kV).
Insulation ShieldComposite shieldconsisting of 0.0126"tinned copper braidedwith nylon providing60% copper Shieldedcoverage meeting UL 1309, IEEE Std.1580, and UL 1072.The nylon is coloredfor easy phase identification (three conductor = black,blue, red) without the need to removethe shield to find an underlying colored tape.
Insulation ShieldSemi-conducting layer meeting UL 1309, IEEE 1580 and UL 1072.
InsulationExtruded thermosetting90°C EthylenePropylene Rubber(EPR), meetingUL 1309 (Type E), IEEE 1580 (Type E)and UL 1072.
Symmetrical InsulatedGrounding Conductors (3)Soft annealed flexible stranded tinned copper conductor per IEEE 1580 Table 11. GexolInsulation sized per Table 23.2 of UL1072.Color: Green
Ratings & Approvalsn UL Listed as Marine Shipboard Cable(E111461)
n American Bureau of Shipping (ABS)n Det Norske Veritas (DNV) Pendingn Lloyd’s Register of Shipping (LRS) Pendingn 90˚C Temperature Ratingn Voltage Rating – 8kV to 15kV(25kV available on request)
Low smokehalogen-free
jacket availableon request.
Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
Three Conductor Type MMV-VFD Marine Medium Voltage8kV • 133% Insulation Level
Ampacity
Ampacity
Three Conductor Type MMV-VFD Marine Medium Voltage15kV • 133% Insulation Level
Ordering Type MMV-VFD Medium Voltage CablesExample:
• 3 conductor MMV-VFD power cable• 15kV• #2 AWG
Nexans AmerCableType MMV-VFD
Prefix
Specific CableNumber (from charts)
37–105 – 357TSVFD
Stranding Profile:See Page 28
Single Inductive Voltage Green InsulatedSize Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Drop GroundingAWG/ Part No. Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (Ohms/ (Volts/Amp/ Conductor (3x)kcmil mm2 37-105 (Inches) 1000 Ft.) (Amps) (Amps) (Ohms/1000 Ft.) (Ohms/1000 Ft.) 1000 Ft.) 1000 Ft.) Size (AWG)
6421
1/02/03/04/0262313373444535
12.5213443547086109132159189227273
-332TSVFD-333TSVFD-334TSVFD-335TSVFD-336TSVFD-337TSVFD-338TSVFD-339TSVFD-340TSVFD-341TSVFD-342TSVFD-343TSVFD-344TSVFD
1634207426253022337338264411509359936867781088559905
1.6871.8682.0712.1612.2622.3812.4892.6313.8573.0303.1643.3193.492
88116152175201232266306348386429455528
7599129149171197226260296328365387449
0.4450.3000.1840.1470.1170.0930.0740.0580.0480.0400.0340.0280.024
0.5560.3760.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.033
0.0480.0430.0400.0380.0370.0360.0350.0330.0320.0320.0310.0300.030
0.8200.5640.3590.2940.2420.1990.1660.1390.1210.1060.0940.0850.076
1010108886666444
Single Inductive Voltage Green InsulatedSize Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Drop GroundingAWG/ Part No. Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (Ohms/ (Volts/Amp/ Conductor (3x)kcmil mm2 37-105 (Inches) 1000 Ft.) (Amps) (Amps) (Ohms/1000 Ft.) (Ohms/1000 Ft.) 1000 Ft.) 1000 Ft.) Size (AWG)
21
1/02/03/04/0262313373444
3443547086109132159189227
-357TSVFD-358TSVFD-359TSVFD-360TSVFD-361TSVFD-362TSVFD-363TSVFD-364TSVFD-365TSVFD-366TSVFD
3231295940904615530661317074778787039912
2.4032.4682.5962.7142.8753.0283.2603.3633.5003.652
156178205234269309352389432456
133151174199229263299331367388
0.1840.1470.1170.0930.0740.0580.0480.0400.0340.028
0.2300.1840.1470.1170.0940.0750.0630.0530.0450.039
0.0440.0430.041
0.0390.0380.0370.0350.0340.0340.033
0.3640.2990.2460.2030.1700.1420.1240.1090.0970.080
10888666644
www. amercable.com • e-mail: [email protected]
Ampacities are based on API RP 14F (June 1999)Table 4 or 5 for single conductor cables and Table3 for multi-conductor cables. The notes to thesetables are also applicable. Ampacities are alsobased on a 90°C conductor temperature and a45°C ambient temperature.
Inductive reactance and voltage drop values are based on a 90°C conductor temperature and 60 Hz operation. Values for single conductor cables are based on a symmetrical triangular configuration.
Please consult Nexans AmerCable on values for other configurations.
MMV Ampacities & Electrical Data
Individual Closest Equivalent UninsulatedSize Number Strand Dia. IEEE 45 Metric Size Conductor
AWG/kcmil of Strands (inches) Std. Size (mm2) Dia. (inches)
86421
1/02/03/04/0
262313373444535646777
1111
3761
133133209266342418532646777925
11101332159119242745
0.0201 0.0201 0.0177 0.0223 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201
1626416683
106133168212262313373444535646777
1111
7.57 12.49 21.11 33.51 42.79 54.45 70.01 85.57
108.91 132.25 159.06 189.36 227.23 272.68 325.70 393.87 561.94
0.136 0.175 0.258 0.324 0.361 0.407 0.461 0.510 0.575 0.654 0.720 0.785 0.860 0.941 1.029 1.132 1.354
MMV Bend RadiusUnarmored Armored Armored & Sheathed
IEEE 45 6X Diameter 8X Diameter 8X Diameter
IEC 92 <1" (25mm) 6X Diameter 8X Diameter4 x Diameter>1" (25mm)6X Diameter
Transport <1" (25mm) 6X Diameter 6X DiameterCanada 4X Diameter
>1" (25mm)6X Diameter
37-105
Type MMV Medium Voltage CableSingle Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°CMulti-Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°C
MMV Stranding Profile