glenn spurlock june 10, 2013
DESCRIPTION
FECA Engineers Conference SEMINOLE UPDATE. Glenn Spurlock June 10, 2013. June 10, 2013. S EMINOLE UPDATE. 2013 – New General Manager 2014 – LCEC exit 2017 – Peaking needed ( PPA vs. Build) 2020s – Combined Cycle and Peaking needed (PPA vs. Build). - PowerPoint PPT PresentationTRANSCRIPT
![Page 1: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/1.jpg)
Glenn SpurlockJune 10, 2013
1 June 10, 2013
FECA Engineers ConferenceSEMINOLE UPDATE
![Page 2: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/2.jpg)
SEMINOLE UPDATE
2013 – New General Manager
2014 – LCEC exit
2017 – Peaking needed (PPA vs. Build)
2020s – Combined Cycle and Peaking needed (PPA vs. Build)
2
![Page 3: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/3.jpg)
SEMINOLE UPDATENEW MEMBER INTERCONNECTS CFEC – <2 MW Biogas (operational 2012) TCEC – 2 MW Solar CEC – 3.2 MW Landfill Gas SECO – 5 MW Solar (removed from
queue) CEC – 12 MW Solar GEC – 25 MW Co-Generation TEC – 60 MW Solar PRECO/SECI 160 MW IPP3
![Page 4: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/4.jpg)
SEMINOLE UPDATE
FERC Order 1000– Regional & Interregional Transmission Planning– FERC Jurisdiction Entities Must Comply– Details:
Project Qualification Criteria Cost Allocation Process Project Justification:
– Reliability– Cost Effective/Efficient– Public Policy
Implementation thru OATT Attachment K Process4
![Page 5: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/5.jpg)
OTHER INTERESTING FACTS
2013 – Duke Crystal River 3 decommission announcement
2016 – Duke Crystal River 1 shutdown 2016 – Duke Crystal River 2 shutdown
FRCC does not have models available for utilities to perform transmission planning studies5
![Page 6: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/6.jpg)
QUESTIONS?
6
![Page 7: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/7.jpg)
Glenn SpurlockJune 10, 2013
7 June 10, 2013
FECA Engineers ConferenceSWECKER VS. MIDLAND
![Page 8: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/8.jpg)
BACKGROUND
In 1998, the Sweckers, retail customers of Midland Power Cooperative in Iowa, purchased a 65 kW wind generator for their farm. The wind generator was a renewable resource which met the requirements of a qualifying facility (QF).
8 FECA ConferenceJune XX, 2013
![Page 9: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/9.jpg)
9
DISPUTES
Almost immediately after being connected to Midland’s system, the Sweckers began to have disputes with Midland concerning:(1) What connection fee the Sweckers need to pay, as a
qualifying facility (QF) or as a farm/residential connection;
(2) What avoided cost amount Midland should pay the Sweckers for purchasing electricity; and
(3) What venue certain legal actions must commence within, and more…
FECA ConferenceJune XX, 2013
![Page 10: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/10.jpg)
10
SWECKER POSITION
The Sweckers argue that the avoided cost that Midland is paying the Sweckers for the electricity produced by their wind generator is too low, and that Midland owes the Sweckers money.
The Sweckers stopped making payments for electric service to Midland, pending resolution of the issues.
FECA ConferenceJune XX, 2013
![Page 11: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/11.jpg)
11
SWECKER POSITION
The Sweckers argue that because they have filed the avoided cost complaint, that the issue is still on going and thus Midland cannot disconnect the Sweckers until the issue has been fully vetted.
FECA ConferenceJune XX, 2013
![Page 12: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/12.jpg)
MIDLAND ACTIONS
In 2011: FERC published its intent not to take action on the
avoided cost dispute between the parties. Midland disconnected the Sweckers due to non-
payment of electric bills. Midland stated that the Sweckers could be
reconnected if the Sweckers paid their electric bill.
12 FECA ConferenceJune XX, 2013
![Page 13: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/13.jpg)
13
PROPER DISCONNECT (?)
On December 9, 2011, the Sweckers filed a complaint that Midland trespassed on their property and locked the Sweckers’ disconnect switch without permission, thereby shutting off electric service to the Sweckers’ QF and residence.
![Page 14: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/14.jpg)
PROPER DISCONNECT (?)
The Sheriff was called and Midland admitted that the disconnect switch was property owned by the Sweckers.
Midland’s crew, in the presence of the Sheriff, removed the lock on the disconnect switch.
14
![Page 15: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/15.jpg)
15
ISSUE PRESENTED
Can an electric utility unilaterally disconnect a QF for non-payment of past bills?
FECA ConferenceJune XX, 2013
![Page 16: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/16.jpg)
EXPLANATION
Answer: No
FERC reasons that termination, even a temporary termination, may only be accomplished by following the FERC’s rules for termination, i.e., applying to FERC for the ability to terminate.
16 FECA ConferenceJune XX, 2013
![Page 17: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/17.jpg)
17
DEC. 15, 2011 FERC ORDERHOLDING AND ANALYSIS
“[W]e find Midland’s disconnection of the Sweckers’ QF to be inconsistent with its obligations under PURPA.”
Under section 210(a) of the Public Utility Regulatory Policies Act (PURPA,) Midland has an obligation to purchase from QFs and to sell electricity to QFs.
FECA ConferenceJune XX, 2013
![Page 18: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/18.jpg)
18
DEC. 15, 2011 FERC ORDERHOLDING AND ANALYSIS
Before the Energy Policy Act of 2005 (EPAct 2005), disconnection of QFs for non-payment of bills was left to State regulatory authorities.
In implementing EPAct 2005, however, this issue was addressed, and provided specific FERC regulations on, how an electric utility may terminate its obligations to purchase from and sell to QFs.
FECA ConferenceJune XX, 2013
![Page 19: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/19.jpg)
19
DEC. 15, 2011 FERC ORDERHOLDING AND ANALYSIS
The Sweckers receive retail service from Midland, which is usually beyond the reach of FERC authority to regulate. However, the Sweckers also own a QF onsite with certain FERC buying and selling requirements.
PURPA does not allow services to a QF to be disconnected unilaterally by and at the sole discretion of the interconnected purchasing/selling electric utility, here Midland, merely because that electric utility also happened to be selling retail service.
FECA ConferenceJune XX, 2013
![Page 20: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/20.jpg)
20
RECOMMENDATION
Seek legal advice prior to disconnection of a QF.
![Page 21: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/21.jpg)
QUESTIONS
21 FECA ConferenceJune XX, 2013
![Page 22: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/22.jpg)
Glenn SpurlockJune 10, 2013
22 June 10, 2013
FECA Engineers ConferenceLOOPED DELIVERY POINTS
![Page 23: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/23.jpg)
23
LOOPED DELIVERY POINTS
Transmission facilities are deemed “integrated” if they meet any one of the Mansfield Test criteria
AND
Integrated transmission facility capital costs are rolled-in to transmission Rate-Base
![Page 24: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/24.jpg)
LOOPED DELIVERY POINTS
Mansfield Test for Integrated Trans. Facilities– Facilities are looped– Energy can flow in both directions– Transmission Owner provides services over the
facility to other customers– Facility provides for higher system reliability– An outage of the facilities would have an adverse
effect on the system and to other customers
24
![Page 25: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/25.jpg)
LOOPED DELIVERY POINTS
25
![Page 26: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/26.jpg)
WHAT DOES THIS MEAN TO US?
TDU cooperatives may want higher reliability that comes from looped Delivery Points
TOs are responsible for controlling their Rate Base charges and therefore determine when facilities are to be looped on their system (w/costs rolled into Rate Base)
FERC has no mechanism for TOs to accept CIAC for looping Delivery Points
26
![Page 27: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/27.jpg)
QUESTIONS
27 FECA ConferenceJune XX, 2013
![Page 28: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/28.jpg)
Glenn SpurlockJune 10, 2013
28 June 10, 2013
FECA Engineers ConferenceDUKE ENERGY FLORIDA
![Page 29: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/29.jpg)
DUKE ENERGY FLORIDA
Seminole has 60-65% of its Member load imbedded in the Duke Florida transmission system.
Some Seminole Members seek a higher level of reliability via looped delivery systems.
29
![Page 30: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/30.jpg)
DUKE ENERGY FLORIDA
Progress Energy Florida has permitted the looping of wholesale-customer Delivery Points under limited circumstances
Seminole is strongly encouraging Duke to permit looping of cooperative Delivery Points
Seminole is strongly encouraging Duke to develop a written Looping Criteria Guideline document to assure equity of treatment
30
![Page 31: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/31.jpg)
DUKE ENERGY FLORIDA
If Duke agrees to loop delivery points:– Duke must role the costs into the Rate
Base– Duke must develop rules & regulations on
how looping will be done
31
![Page 32: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/32.jpg)
DUKE ENERGY FLORIDA
Duke Risk– A transmission customer may challenge
the looped facilities are “Gold Plated” reliability and should not be paid by all transmission customers.
– If Duke were to lose such a challenge, Duke shareholders may be on the hook to pay for all such loop facilities
32
![Page 33: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/33.jpg)
DUKE ENERGY FLORIDA
Possible Duke requirements:– Ownership of transmission line continuity
Duke owned transmission circuits (in & out) Duke owned substation facilities (in series with line)
– Duke standards for design/construction– Duke Facility Ratings– Duke approves all future connections and
modifications– Duke approves all maintenance and switching
operations33
![Page 34: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/34.jpg)
34
DUKE ENERGY FLORIDA
Under limited circumstances, Members may be permitted to perform necessary construction of Duke facilities (as a Duke contractor)
If existing cooperative owned line/substation facility is to be used to complete the transmission loop, Duke may buy facilities or pay credits for use of facilities
![Page 35: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/35.jpg)
DUKE ENERGY FLORIDA
35
![Page 36: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/36.jpg)
36
Glenn SpurlockJune 10, 2013
June 10, 2013
FECA Engineers ConferenceLooped Substation Configurations
![Page 37: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/37.jpg)
37
Single Bus Configuration
The single bus substation configuration is the simplest of configurations, but is also the least reliable.
In the arrangement shown, the circuit must be de-energized to perform breaker maintenance, which can be overcome by the addition of breaker bypass switches, but this may then disable protection systems.
![Page 38: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/38.jpg)
38
Single Bus ConfigurationAdvantages & Disadvantages
Single Bus Advantages:• Lowest cost• Small land area• Easily expandable• Simple in concept and operation• Relatively simple for the application of protective relaying
Single Bus Disadvantages:• Single bus arrangement has the lowest reliability• Failure of a circuit breaker or a bus fault causes loss of entire substation• Maintenance switching can
![Page 39: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/39.jpg)
39
Sectionalized Bus Configuration
The sectionalized bus configuration is merely an extension of the single bus layout. The single bus arrangements are now connected together with a center breaker that may be normally open or closed. Now, in the event of a breaker failure or bus bar fault, the entire station is not shut down. Breaker bypass operation can also be included in the sectionalized bus configuration.
![Page 40: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/40.jpg)
40
Sectionalized Bus ConfigurationAdvantages & Disadvantages
Sectionalized Bus Advantages:• Flexible operation• Isolation of bus sections for maintenance• Loss of only part of the substation for a breaker failure or bus fault
Sectionalized Bus Disadvantages:• Additional circuit breakers needed for sectionalizing, thus higher cost• Sectionalizing may cause interruption of non-faulted circuits
![Page 41: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/41.jpg)
41
Main & Transfer Bus Configuration
A main and transfer bus configuration means there are two separate and independent buses; a main and a transfer. Normally, all circuits, incoming and outgoing, are connecting the main bus. If maintenance or repair is required on a circuit breaker, the associatedcircuit can be then fed and protected from the transfer bus, while the original breaker is isolated from the system.
![Page 42: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/42.jpg)
42
Main & Transfer Bus ConfigurationAdvantages & Disadvantages
Main and Transfer Bus Advantages:• Maintain service and protection during circuit breaker maintenance• Reasonable in cost• Fairly small land area• Easily expandable
Main and Transfer Bus Disadvantages:• Additional circuit breaker needed for bus tie• Protection and relaying may become complicated• Bus fault causes loss of the entire substation
![Page 43: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/43.jpg)
43
Ring Bus Configuration
The ring bus configuration is an extension of the sectionalized bus. In the ring bus, a sectionalizing breaker has been added between the two open bus ends.Now there is a closed loop on the bus with each section separated by a circuit breaker. This provides greater reliability and allows for flexible operation. The ring bus can easily adapted to a breaker-and-a-half scheme, which will be looked at next.
![Page 44: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/44.jpg)
44
Ring Bus Advantages & Disadvantages
Ring Bus Advantages:• Flexible operation• High reliability• Double feed to each circuit• No main buses• Expandable to breaker-and-a-half configuration• Isolation of bus sections and circuit breakers for maintenance without circuit disruptionSubstation Configuration Reliability 7
Ring Bus Disadvantages:• During fault, splitting of the ring may leave undesirable circuit combinations• Each circuit has to have its own potential source for relaying• Usually limited to 4 circuit positions, although larger sizes up to 10 are in service. 6 isusually the maximum terminals for a ring bus
![Page 45: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/45.jpg)
45
Breaker-and-a-Half Configuration
A breaker-and-a-half configuration has two buses but unlike the main and transfer scheme, both busses are energized during normal operation. For every 2 circuits there are 3 circuit breakers with each circuit sharing a common center breaker.Any breaker can be removed for maintenance without affecting the service on the corresponding exiting feeder, and a fault on either bus can be isolated without interrupting service to the outgoing lines. If a center breaker should fail, this will cause the loss of 2 circuits, while the loss of an outside breaker would disrupt only one. The breaker-and-a-half scheme is a popular choice when upgrading a ring bus to provide more terminals.
![Page 46: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/46.jpg)
46
Breaker-and-a-Half ConfigurationAdvantages & Disadvantages
Breaker-and-a-Half Advantages:• Flexible operation and high reliability• Isolation of either bus without service disruption• Isolation of any breaker for maintenance without service disruption• Double feed to each circuit• Bus fault does not interrupt service to any circuits• All switching is done with circuit breakers
Breaker-and-a-Half Disadvantages:• One-and-a-half breakers needed for each circuit• More complicated relaying as the center breaker has to act on faults for either of
the 2 circuits it is associated with• Each circuit should have its own potential source for relaying
![Page 47: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/47.jpg)
47
Double Breaker-Double Bus Configuration
Like the breaker-and-a-half, the double breaker-double bus configuration has two main buses that are both normally energized. Here though, each circuit requires two breakers, not one-and-a-half.With the addition of the extra breaker per circuit, any of the breakers can fail and only affect one circuit. This added reliability comes at the cost of additional breakers, and thus is typically only used at large generating stations.
![Page 48: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/48.jpg)
48
Double Breaker-Double Bus Advantages & Disadvantages
Double Breaker-Double Bus Advantages:• Flexible operation and very high reliability• Isolation of either bus, or any breaker without disrupting service• Double feed to each circuit• No interruption of service to any circuit from a bus fault• Loss of one circuit per breaker failure• All switching with circuit breakers
Double Breaker-Double Bus Disadvantages:• Very high cost – 2 breakers per circuit
![Page 49: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/49.jpg)
49
Comparison of Bus Configuration Costs
If one assumes that the Single Bus configuration costs $100k, then the math can easily be done by using the relative cost comparison.
![Page 50: Glenn Spurlock June 10, 2013](https://reader036.vdocument.in/reader036/viewer/2022062521/5681690f550346895de026db/html5/thumbnails/50.jpg)
50