    Update on Green Mark v4.0for new commercial buildings

    Steven KangCertified Energy Manager,

    Certified Green Mark Professional

    LEED Accredited Professional

  • 8/7/2019 GMv4 for Power Breakfast (9Dec2010)

    2/19

    Green Mark Rating System

    2 Confidential and Proprietary Property of Trane

    or ew u ngsNRNB V4.0

    Effective 1-Dec-2010

  • 8/7/2019 GMv4 for Power Breakfast (9Dec2010)

    3/19

    Building control legislation on environmental

    sustainability Mandatory to attain GM certification for

    All new building with GFA equal or greater than 2000

    m2 and Existing buildings with GFA equal or greater than 2000

    m2 undergoing major retrofitting works

    3 Confidential and Proprietary Property of Trane

    Major retrofitting worksdefined as works involving majoroverhauling of air conditioning system and significantmodifications to building faade along with other buildingservices.

    Legislation

  • 8/7/2019 GMv4 for Power Breakfast (9Dec2010)

    4/19

    Overall frameworkNon residential Bldg. Part 1: Energy Related section

    4 Confidential and Proprietary Property of Trane

  • 8/7/2019 GMv4 for Power Breakfast (9Dec2010)

    5/19

    Overall frameworkNon residential Bldg. Part 2-5: Other green requirements

    5 Confidential and Proprietary Property of Trane

  • 8/7/2019 GMv4 for Power Breakfast (9Dec2010)

    6/19

    Green Mark RatingNon residential Bldg

    6 Confidential and Proprietary Property of Trane

    Out of a possible 190 pts

  • 8/7/2019 GMv4 for Power Breakfast (9Dec2010)

    7/19

    PrerequisitesFor air-conditioned bldg

    1. ETTV

    2. Building Energy Efficiency Index (EEI)

    3. Air conditioning system Efficiency

    7 Confidential and Proprietary Property of Trane

    4. Water cooled chiller plant energy efficiency monitoring

    Permanent monitoring system to accuracy of +/- 5%

  • 8/7/2019 GMv4 for Power Breakfast (9Dec2010)

    8/19

    GMv4.0 Versus GMv3.0

    Summary of key differences

    Pre-requisites for min chiller plant & unitary systemefficiency.

    Pre-requisite for accurate M&V for water cooled chiller plantperformance.

    Heat balance for water cooled chiller plant (1 point)

    Reference building ACMV performance will be referenced to

    8 Confidential and Proprietary Property of Trane

    (SS553 + SS530) instead (CP13 + SS530) making theReference Building ACMV system more efficient.

    Maximum cap of 50pts for Energy & other greenrequirements is removed.

    Full details of GMv4.0 are available athttp://www.bca.gov.sg/EnvSusLegislation/others/GM_Certification_

    Std2010.pdf

  • 8/7/2019 GMv4 for Power Breakfast (9Dec2010)

    9/19

    NRB 1-1 ETTV Baseline: ETTV= 50 W/m2

    Pre-requisite requirements

    Gold plus: ETTV

  • 8/7/2019 GMv4 for Power Breakfast (9Dec2010)

    10/19

    NRB 1-2 Air conditioning system efficiency

    1-2) Cooling plant system efficiency(Max 20pts)

    1-2a) Water-cooledchiller plant

    1-2b) Air-cooled chiller plant/Unitary air conditioner

    10 Confidential and Proprietary Property of Trane

    Certified 0.80

    Gold 0.80

    Goldplus

    0.70

    Platinum 0.70

    < >=

    Certified 0.70

    Gold 0.70

    Goldplus

    0.65

    Platinum 0.65

    < >=

    Certified 0.90

    Gold 0.90

    Goldplus

    0.85

    Platinum 0.78

    Certified 0.80

    Gold

    Goldplus

    Platinum

    Not

    applicable

    12pts for baseline of0.80KW/RT

    0.45pts for every %improvement overbaseline

    Max: 20 pts

    (= 0.66KW/RT)

    15pts for baseline of0.70KW/RT

    0.25pts for every %improvement overbaseline

    Max: 20 pts

    (= 0.56KW/RT)

    10pts for baseline of0.90KW/RT

    0.6pts for every %improvement overbaseline

    Max: 20 pts

    (= 0.75KW/RT)

    12pts for baseline of0.80KW/RT

    1.3pts for every %improvement overbaseline

    Max: 20 pts

    (= 0.75KW/RT)

  • 8/7/2019 GMv4 for Power Breakfast (9Dec2010)

    11/19

    NRB 1-2 Air conditioning system efficiency

    1-2C Airside energy efficiency(Max 6pts)

    Constant volume Variable volume

    Baseline

    11 Confidential and Proprietary Property of Trane

    1.7 KW / m3/s0.47 W/CMH

    2.4 KW / m3/s

    0.67 W/CMH

    0.2 pts for every %improvement over the

    baseline

    Max 6 pts

    =0.33 W/CMH

    0.2 pts for every %improvement over thebaseline

    Max 6 pts

    =0.47 W/CMH

  • 8/7/2019 GMv4 for Power Breakfast (9Dec2010)

    12/19

    NRB 1-2d Permanent water cooled chiller plant M&V

    Pre-requisite for all water cooled chiller plant.

    Overall KW/RT measurement accuracy of +/-5% per Ashare 22 &

    AHRI550. Temperature sensor accuracy of +/- 0.05C

    Install 2 spare thermo-wells on each side of the temperaturesensor for verification of the KW/RT measurement accuracy.

    NRB 1-2 Air conditioning system efficiency

    12 Confidential and Proprietary Property of Trane

    ow meter s a e nsta e on t e an oop an s abe ultrasonic or full bore electromagnetic type. An additional 1%to be included in the computation of measurement error for flowmeter.

    Location and installation of measuring devices to meet

    manufacturer's recommendation. Data acquisition system to have a resolution of 16bit.

    All data logging with capability to trend at 1 minute samplinginterval.

  • 8/7/2019 GMv4 for Power Breakfast (9Dec2010)

    13/19

    NRB 1-2 Air conditioning system efficiency

    NRB 1-2e Heat balance for w/c chiller plant1 point for completing the verification of chilled water plant instrument usingthe heat balance substantiating test in accordance to AHRI550/590. The

    heat balance shall be conducted over the entire normal operating hours withmore than 80% of the computed heat balance within +/- 5% over a one (1)

    week period.

    13 Confidential and Proprietary Property of Trane

    - s or c er p an

    1 point for use of variable speed controls for chilled water plant equipmentsuch as chilled water pumps and cooling tower fans to ensure better part load

    plant efficiency.

    NRB 1-2g CO2 controlled ventilation

    1 point for use of controls to regulate outdoor airflow rate to maintain indoorCO2 concentration of

  • 8/7/2019 GMv4 for Power Breakfast (9Dec2010)

    14/19

    Other Air-conditioning related items

    NRB 1-10C Use of energy efficient features.Examples:Heat recovery systemHeat pumpsSun pipesLift with gearless driveRe-generative liftLight shelves etc

    3 points for every 1% energy savings over thetotal building energy consumption.Max: 7.5pts

    14 Confidential and Proprietary Property of Trane

    NRB 3-6 Refrigerantsa) 1 point for using refrigerants with Ozone Depletion Potential (ODP) =0 OR Global

    Warming Potential (GWP)

  • 8/7/2019 GMv4 for Power Breakfast (9Dec2010)

    15/19

    Pre-requisite for Gold Plus and Platinum

    15 Confidential and Proprietary Property of Trane

    GM reference building

    Building energy consumptionwith all the minimumrequirement of SS530 and

    SS553

    Proposed building

    Building energy consumptionwith all the GREEN featuresapplied.

  • 8/7/2019 GMv4 for Power Breakfast (9Dec2010)

    16/19

    Reference building ACMV performanceMinimum Chiller Plant Performance (CP13+SS530) Minimum Chiller Plant Performance (SS553+SS530)

    Type Condition Min eff Units Remarks Type Condition Min eff Units Remarks

    Chillers Full load @ ARI

    std condn

    6.1 COP Chillers Full load @

    ARI std condn

    6.1 COP

    0.58 Kwi / RT 0.58 Kwi / RT

    Part load - No requirement for part load

    performance

    Part load - No requirement for part load performance

    - -

    CHWP Full load 30 KWc / Kwi CHWP Full load 349 KW/cms

    (SS553 + SS530)

    Reference building

    GMv3 (CP13 + SS530)

    Reference building

    56% more

    16 Confidential and Proprietary Property of Trane

    . w . w

    Part load - No requirement for part loadperformance

    Part load - Motors exceeding 15KW must modulate to50% of design flow @ no more than 30%

    of design KWi

    CWP Full load 40 KWct / Kwi CWP Full load 301 KW/cms

    0.09 Kwi / RT 0.057 Kwi / RT

    Part load - No requirement for part load

    performance

    Part load - Motors exceeding 15KW must modulate to

    50% of design flow @ no more than 30%

    of design KWiCT Full load 3.23 L/S / Kwi CT Full load 3.23 L/S / Kwi

    0.06 Kwi / RT 0.06 Kwi / RT

    Part load - No requirement for part load

    performance

    Part load - No requirement for part load performance

    0.85 Kwi / RT 0.75 Kwi / RT

    4.16 COP 4.71 COP

    Chilled water plant minimum

    system efficiency

    Chilled water plant minimum

    system efficiency

    11.8% moreefficient

    efficient

    37% moreefficient

  • 8/7/2019 GMv4 for Power Breakfast (9Dec2010)

    17/19

    Type Condition Min Eff Units Remarks Type Condition Min Eff Units Remarks

    Constant volume

    system

    Full load 0.47 W / CMH Constant

    volume system

    Full load 0.47 W / CMH Allowable nameplate motor KW

    GreenMark v3

    Reference building (SS553)

    GreenMark v3

    Reference building (CP13)

    Reference building ACMV performance

    17 Confidential and Proprietary Property of Trane

    Variable volume

    s stem

    Full load 0.74 W/ CMH Variable

    volume s stem

    Full load 0.67 W/ CMH Allowable nameplate motor KW

    Part load - No requirement for part

    load performance

    Part load - Motor >= 11kw must able to

    modulate to 50% design flow at less

    than 30% of design KW

    For VAVsystem, 9.5%more eff thanCP13

  • 8/7/2019 GMv4 for Power Breakfast (9Dec2010)

    18/19

    Simple Guide to Green Mark success

    Ask for 0.60 kW/RT or better for chiller plant.

    Ask for performance guarantee backed by clear

    financial penalties in event of performanceshortfall.

    Ask for accurate Measurement & Verification

    18 Confidential and Proprietary Property of Trane

    system of at least +-5% accuracy in accordanceto international standards of ARI-550 & ASHRAEguides 14P & 22.

    Ask for online internet access to monitor theplant performance.

    Ask for track record.

  • 8/7/2019 GMv4 for Power Breakfast (9Dec2010)

    19/19

    Thank you for your attention.Thank you for your attention.