government of india ministry of railway...

53
Page 1 of 53 Effective from December,2011 Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2) Prepared by JE/Design Checked by Director/PE&Metro lR;eso t;rs Òkjr ljdkj j¢y ea=ky; GOVERNMENT OF INDIA MINISTRY OF RAILWAY RESEARCH DESIGNS & STANDARDS ORGANISATION MANAK NAGAR, LUCKNOW-226 011 POWER SUPPLY & EMU DIRECTORATE TECHNICAL SPECIFICATION NO. RDSO/PE/SPEC/AC/0013-2011 (REV-2) FOR ELECTRONIC RECTIFIER-CUM-REGULATING UNIT (ERRU) FOR 25 KW & 4.5 KW ALTERNATORS FITTED ON AC & TL COACHES SN DATE OF REVISION NO. OF PAGES VERSION REASON FOR REVISION 1. April 2000 42 Rev. 0 First issue 2. Sept. 2002 36 Rev. 0 with Amdt. 1&2 Second issue 3. 4. July 2008 December 2011 41 53 Rev. 1 Rev. 2 In view of standardization of ERRUs and to increase the reliability of the components Addition of standby circuit, series OVP & tests to improve reliability. APPROVED BY Executive Director / PS & EMU

Upload: lydung

Post on 27-Mar-2018

217 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 1 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

lR;eso t;rs

Òkjr ljdkj

j¢y ea=ky;

GOVERNMENT OF INDIAMINISTRY OF RAILWAY

RESEARCH DESIGNS & STANDARDS ORGANISATIONMANAK NAGAR, LUCKNOW-226 011

POWER SUPPLY & EMU DIRECTORATETECHNICAL SPECIFICATION NO. RDSO/PE/SPEC/AC/0013-2011 (REV-2)

FOR

ELECTRONIC RECTIFIER-CUM-REGULATING UNIT (ERRU) FOR 25KW & 4.5 KW ALTERNATORS FITTED ON AC & TL COACHES

SN DATE OFREVISION

NO. OFPAGES

VERSION REASON FOR REVISION

1. April 2000 42 Rev. 0 First issue

2. Sept. 2002 36 Rev. 0 withAmdt. 1&2

Second issue

3.

4.

July 2008

December 2011

41

53

Rev. 1

Rev. 2

In view of standardizationof ERRUs and to increasethe reliability of thecomponents

Addition of standby circuit,series OVP & tests toimprove reliability.

APPROVED BY

Executive Director / PS & EMU

Page 2: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 2 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

Specification for Electronic Rectifier-cum-Regulating Unit (ERRU) with Voltagecontroller for 25 KW and 4.5 KW Brushless Alternators for Air conditioned andNon AC Conventional Self-generating Coaches

0.0 FOREWORD

0.1 Presently Alternators and Rectifier-cum-Regulating Equipment for AirConditioned and conventional Self-generating coaches are being procuredas per RDSO Specification NO. RDSO/PE/SPEC/AC/0056-2004 (Rev.0)with Amendment No. 1 and RDSO/PE/SPEC/TL/0054-2003 (Rev.0) withamendment No. 1 & 2 for 25 KW and 4.5 KW Alternators respectively. Theexisting design of RRU (Rectifier-cum-Regulating Unit) is based onmagnetic amplifier, with associated electronic control circuitry consisting ofauxiliary diodes, zener diodes, resistors, capacitors etc. This design ofRRU is having its inherent limitations of voltage regulation, which is ±4%and ±5% for 25 kW & 4.5 kW respectively. This also does not have batterycharging feature of charging the VRLA (Valve Regulated Lead Acid)batteries with current limit at constant voltage. Since, the working of theseRRUs is based on magnetic core saturation, the voltage and current ripplein the 110V DC output are varying substantially depending upon the typeof load and speed which may affect performance / life of VRLA batteries.

0.2 Most of the AC coaches are fitted with 25 kw alternators with 1100 Ah andold AC coaches having alternators are fitted with 2V/800 Ah 56conventional lead acid (LA) batteries and underslung AC equipments. ACcoaches with Roof Mounted Package Unit will normally be equipped withtwo sets of 25 kw Alternators suitable for parallel operation. Other types ofAir Conditioned coaches i.e. First Class AC Coaches may be equippedwith only one set of 25 kw brushless alternator, whereas BG 110V non ACcoaches are fitted with 4.5 kw brushless alternators.

DC output of the 25 kw alternator will normally supply load consisting of AirConditioning equipment through 25 KVA Inverters, incandescent &fluorescent light, air circulating fans and in addition, the charging of abank of 56 cells of VRLA batteries of 1100 Ah capacity at a nominalvoltage of 110V DC. DC output of 4.5 kw Alternators will normally supplyload consisting of incandescent and fluorescent light, air circulating fansand in addition charging a bank of 18 monoblock of 6V/120 Ah LAbatteries.

0.3 The battery is connected to the alternators through RRU/ERRU, whichconverts AC output of alternator into regulated DC and prevents reverseflow of current from battery to the alternator during periods of non-generation. The air conditioning unit, coach light and fan circuit are

Page 3: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 3 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

connected across DC output. Some of the coaches are fitted with AC fansand light circuits connected across inverter AC output.

0.4 IGBT based Rectifier-cum-Regulating Unit i.e. Electronic Rectifier-cum-Regulating Unit ERRU shall have additional safety features viz. overloadprotection with fast corrective response, battery charging with current limit,battery charging voltage limit, data downloading on commercial USB pendrive etc. Most of these features are not available in the MA type designi.e. RRU.

1.0 SCOPE

1.1 This specification covers the design, manufacture, testing supply ofElectronic Rectifier-cum-Regulating Unit (ERRU) of 25 kw or 4.5 kwratings with common UVC for 25 kw / 4.5 kw alternators for providing onself-generating air conditioning and conventional coaches for supplyingessential passenger amenities.

1.2 The Electronic Rectifier-cum-Regulating Unit (ERRU) shall work inconjunction with transom mounted alternators of the same rating whichconforms to RDSO Specification as mentioned in clause 0.1 of thisSpecification. It shall also be possible to retrofit the ERRU in the underframe of the BG AC & TL coaches to work satisfactorily in conjunction withthe alternators of same ratings. Important sub-assemblies e.g. UVC anddisplay unit shall be common for 4.5 kW and 25 kW ERRU to reduceinventory.

1.3 The scope of supply shall include the following unless otherwise specified:

i) For AC coacha) Electronic Rectifier cum Regulating Unit (ERRU) of 25kw -- 2 Nos.b) External Coach indication panel -- 1 No.c) Cables along with connectors for additional wiring for ERRUs -- 1 setd) External Hall Sensor Unit, for sensing battery current -- 1 No.e) Deleted.f) Instruction/maintenance manual including trouble shooting details -- 1 no

Page 4: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 4 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

ii) For TL Coacha) Electronic Rectifier-cum-Regulating Unit (ERRU) of 4.5kW with internal display -- 1No.b) Deleted.c) Instruction/maintenance manual including trouble shooting details -- 1No.

Purchaser can specify the items required as per his requirement.

1.4 The design and manufacture shall fulfil the following broad requirements:

i) Long life minimum maintenance

ii) Maximum reliability

iii) Universal application with in the speed range

iv) Self exciting the installation, shall also be able to operate without a battery

v) Well protected against extraneous interference and pilferage

vi) It shall meet requirements of load consisting of fluorescent andincandescent lamps, fans , motors, Inverters, battery etc.

vii) Protection for battery over charging at constant voltage

viii) Protection for over load

ix) Over voltage protection

x) Voltage and current ripple contents as specified

xi) Suitable for parallel operation with a load sharing difference of less than 10amperes.

xii) Modular type for controller

xiii) Adequate rating margin

xiv) The semi conductors and other parts used shall confirm to reliabilityassurance specification for electronic components used in rolling stock.RDSO Specification No. ELRS/SPEC/SI/0015 Oct. 2001

xv) Adequate surge protection

Page 5: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 5 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

xvi) Fail safe

2.0 TERMINOLOGY

For the purpose of this Specification, the following definitions shall apply:

ALTERNATOR: An axle driven power generating machine mounted on thebogie of the coach driven through V-belt drive consisting of axle andalternator pulleys with V-belts. These are approved by RDSO confirming tothe specifications as mentioned in clause 0.1 above.

ERRU: Electronic Rectifier-cum Regulating Unit ERRU.

POWER CIRCUIT: ISO PACKS/Power diode modules, heat sinks, othervoltage and current sensing units, magnetic components, phase fuses,bus bars capacitors etc. except Universal Voltage Control unit.

UNIVERSAL VOLTAGE CONTROLLER (UVC): This is an electroniccontroller unit having micro-processor/micro-controller/PWM controllerwhich is common for all ratings i.e 25 kw & 4.5 kw of alternators andrespective ERRU having different power circuits. UVC should be able toidentify the rating of the alternator and automatically adjust the settingparameters as per this specification according to the rating of thealternator and battery. It shall have the rating corresponding to 25 kwalternator. All the components other than mentioned above, shall form partof UVC.

CUT-IN-SPEED: The alternator speed in rev/min. at which the rectifiedoutput is 110 volts at no load for 25 kw and 108 volts at no load for 4.5 kwalternators.

MINIMUM SPEED FOR FULL OUTPUT (MFO): The minimum alternatorspeed in rev/min at which it gives full rated output at 129 volts, 194 ampsfor 25 kw and 120 volts 37.5 amps. for 4.5 kw Alternators.

NO LOAD CURRENT: No load current means zero load current.

BASE LOAD: 10 amps. load current for 25 kw and 1 amp. load current for4.5 kw.

IGBT: Insulated Gate Bi-polar Transistor – a semi conductor device usedfor switching on and off to control DC input signal to the field for regulatingDC output.

HALL SENSOR: It is an Electronic device to be used for sensing DC/ACcurrent for giving input to control circuit.

Page 6: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 6 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

COACH INDICATION PANEL (CIP): It will be fitted in AC coach powerpanel. Its LCD display will show the set parameters and the recorded data.

3.0 OPERATING SERVICE CONDITIONS

3.1 The ERRU shall function satisfactorily in the ambient temperature rangefrom –5 degree C to 55 degree C and 100% relative humidity. Theequipment shall be designed for mounting on the under-frame and shall besuitable for working in a heavily dust laden atmosphere which may alsocontain brake block dust.

3.2 The coaches are expected to run up to a maximum speed of 130 km/h invarying climatic conditions existing throughout India. All accessories to bemounted on the coach under frame shall be designed to withstand servicevibrations and shunting shocks.

4.0 RATING

The standard rating at the DC output terminals of the Electronic Rectifier-cum- Regulating Unit for different ratings of alternator shall be as under:

i) 25 KW : 130V, 193A

ii) 4.5 KW : 120V, 37.5 A

5.0 PARTICULARS OF DRIVE

The alternators are driven through V-belt drive system consisting ofalternator and axle deep groove pulleys fitted either on both ends ofalternator shaft or at one end for AC and Conventional coachesrespectively. The power transmission is through V-belts of size 3155 LP(C-122). Total 12 nos. (6 on each side) and 4 nos. (Only one side) of C-122 size are provided on AC and TL alternators respectively. The speed ofalternator shall vary from 0 to 2500 rpm. The coach wheel diameter is 915mm when new and 813 mm when fully worn, New wheel dia shall beconsidered for making calculations of speed of the train in KMPHcorresponding to cut-in speed and MFO speeds of alternator.

6.0 FOR AC COACH APPLICATION:

i) 25 KW: Alternator with ERRU

The cut-in speed and MFO speed of the alternator working in conjunctionwith ERRU shall be as low as possible consistent with economical design.The cut-in and MFO speeds shall be less than 400 and 800 rpmrespectively for AC Alternators. The regulator shall be capable of working

Page 7: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 7 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

at maximum speed of 2500 rpm. No negative tolerance is permitted on thevoltage and current for measuring cut-in speed and minimum speed for fulloutput.The ERRU shall meet the following requirements:

OUTPUT CHARACTERISTICS

25 KW ERRU:

No load DC Output voltage: 135 V (Maximum)DC Output Voltage setting* : 129 ±0.5 V, 97 A at 1500 rpmVoltage regulation: ±2% of set voltageEfficiency at full load at 1800 rpm: 95% (minimum)Voltage ripple: within 2%Current ripple: within 10%

Load variation: 10 A to 193 ASpeed variation: 800 rpm to 2500 rpmVoltage at 15% over load: 120 V (minimum) at 222 ACurrent limiting* : 230 A (maximum)Battery charging current limits* (max): 220 A

* It shall be possible to set these limits from UVC as well as CIP

The DC output voltage at full load shall be suitable for setting from 120 Vto 130 V. Similarly, the current limiting setting of DC output current, batterycharging limit shall also be possible to adjust within 20% of above values.Normally the above settings shall be adopted for the ERRU of 25 kwratings.

ii) FOR TL COACH APPLICATION

4.5 kW: Alternator with ERRU

The cut-in speed and MFO speed of the alternator in conjunction withERRU shall be as low as possible consistent with economical design. Thecut-in and MFO speeds shall not be higher than 350 and 600 rpmrespectively for conventional Alternators. The regulator shall be capable ofworking at maximum speed of 2500 rpm. No negative tolerance ispermitted on the voltage and current for measuring cut-in speed andminimum speed for full output. The ERRU shall meet the followingrequirements:

Page 8: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 8 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

OUTPUT CHARACTERISTICS

4.5 kW ERRU:

No load DC Output voltage: 130 V (Maximum)DC output voltage setting* 128.5 +0.5 V at 19 A at 1500 rpmVoltage regulation: ±2% of set voltageEfficiency at full load at 1800 rpm: 95% (minimum)Voltage ripple: within 2%Current ripple: within 10%Load variation: 1 A to 37.5 ASpeed variation: 600 rpm to 2500 rpmVoltage at over load of 40 A: 115 V (minimum)Current limiting*: 43 A (maximum)Battery charging current limits* (max.): 24 A

* It shall be possible to set these limits from UVC / Display Unit

The DC output voltage at full load shall be suitable for setting from 120 Vto 130 V. Similarly DC output current limit and battery charging currentlimit shall also be adjustable within 20% of above values. Normally theabove settings shall be adopted for the ERRU of 4.5 kw ratings.

7.0 CONSTRUCTION DETAILS

7.1 A) Housing

The housing of electronic rectifier-cum-regulating equipment shallgenerally be as per Drg. No. SKEL-2260/A Alt.1 andRDSO/PE/SK/AC/0060-2011(Rev-“1”) latest alteration for 4.5 kw and 25kw respectively and shall be approved by RDSO. The enclosure shall beof IP65 protection level as per IEC 60529.

B) UVC

Universal Voltage Controller shall be equipped with micro-processor/micro-controller/PWM controller to meet the variousrequirements laid down in clause 6.0 of this specification. Whereverpossible there should be adequate design redundancy to take care ofcontroller failure from total system failure/hanging. The design of everyUVC shall have provision to ensure proper load sharing between two

Page 9: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 9 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

alternators provided on the same AC coach and the difference of loadsharing shall not be more than 10 A enabling to achieve high reliability ofalternators avoiding continuous overloading of one alternator. There shallalso be a provision of communication between two ERRU running inparallel. The UVC of ERRU of different rating i.e. 4.5 kw, and 25 kw shallhave universal application with a common design to achieve inter-changeability among the same make.

The manufacturer shall have to declare their design and its capacity. TheUVC shall be suitable to work with 25 kw & 4.5 kw capacity alternators inthe existing field conditions.

UVC shall have following features:-

i) UVC shall be equipped with minimum of 16 bit industrialmicroprocessor/microcontroller with inbuilt USB and PWM control ports.

ii) No through hole type of microprocessor/microcontroller should be used forhigh reliability.

iii) External programme memory should not be used with microprocessor /microcontroller for highest reliability of memory fetching.

iv) The PCB design of UVC shall be done only on single card to eliminate theinterconnection between PCB and easy service on card replacementbasis.

v) Only sealed membrane key pads should be used alongwith UVC forhighest reliability.

vi) The discrete power supply for powering the UVC microprocessor / microcontroller must be electrically isolated on both Positive and Negative sidefrom coach battery DC power.

Following indication shall be available on UVC / Display unit in case of 4.5kW, whereas for 25 kW ERRU on UVC and CIP

vii) Capacity of Alternatorviii) Healthiness of UVC

7.2 Power Circuit:

For 25kw, ISO-PACKs bridges/Power Block modules with adequatetemperature margins shall be provided for converting AC output ofalternator to DC voltage. The power block diode modules shall not havePIV of less than 1200 V and 350 Amp. mean forward current at 100 deg Ccase temperature with 180 deg.C sine wave conduction for AC coachapplication.

For 4.5 kw ERRU the ISO-PACK/Power Block diode modules shall nothave PIV of less than 1200V and 50A averaged forward current at 180deg. C conduction. Preferably, Power Block Diode Modules may be used

Page 10: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 10 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

for converting AC to DC. Torque wrench shall be used to fix the powerblock diode modules base and for making diodes main connections withrecommended torques. Torque values should be displayed on the ERRUbox inside.

For all devices in the power circuit and field circuit, PIV shall be not lessthan 1200V. In case, manufacturer provides snubber capacitors/circuits, itsrating shall have peak rating matching to PIV rating of diodes with safetemperature margins. Similarly, diodes used in excitation circuit and freewheeling diodes shall have adequate thermal margin.

The surface of the heat sink for diode/devices mounting shall have aproper finish to match with its base for better heat conduction.Recommended machining tolerances over the device/diode mounting areaof the heat sink shall be as follows:-

- Flatness 0.03 mm- Roughness 1.6 µ metres.

The alternator manufacturers shall have the requisite equipment/measuring instruments to ensure the heat sink surface finish as mentionedabove.

Power circuit and UVC shall have separate heat sinks as per encloseddrawings to meet the requirements of heat dissipation such that thetemperatures of the electronic devices remain within the laid down limits.

7.3 Electronic Components:

The semi-conductors and other electronic components used shall be ofproven designs with high reliability confirming to relevant InternationalStandards (IEC) and shall be suitable to work satisfactory under thestringent service conditions for this Rolling Stock application. Commercialgrade components shall not be used. All these components shall bescreened as per “Reliability Assurance Specification for ElectronicComponents used in Rolling Stock” – RDSO specification No.ELPS/SPEC/SI/0015 - Oct. 2001, unless otherwise approved by RDSO.

All the electronics/control card should be designed to withstand at least600 volts.

7.4 Protection/Special Features

The ERRU shall be provided with the following protection/special features:

i) Over-voltage/surge protection

Page 11: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 11 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

ii) DC Output Short circuit protection

iii) Protection from over-charging the battery with current limit

iv) Sensing of AC/DC current and battery charging current shall be madeusing Hall Sensors of proven design having high reliability as per tablegiven below:-

Item Description No. of HallSensor perERRU

Ratings

Load current 1 50 Amps4.5 kW ERRUBattery chargingcurrent

1 50 Amps

Load current 1 300 Amps25 kW ERRUBattery ChargingCurrent

1 300 Amps

v) Bolted type HRC fuse shall be used in power and field circuit.

7.5 The voltage and current ripple in DC output voltage under different loadand speed conditions shall not exceed 2% and 10% respectively.

7.6 For the purpose of universal application when used with other makes ofalternators, the MFO speed can be permitted a tolerance of +50 rev/min.on speeds specified in Clause 6.0.

ERRU of one make/type shall work satisfactorily with alternators of othermakes. UVC of one make/type shall work satisfactorily with any otherrating of ERRU of the same make.

7.7 Over-voltage Protection & Surge Protection: Detailed in annexure -A

7.8 Electronic-Rectifier-cum-Regulating Unit box shall be made of stainlesssteel of grade SS 304 or mild steel with zinc sprayed confirming to IS-5905.

7.9 The electronic power devices shall be well protected from surges andspikes caused during working condition of the ac coaches. All electroniccomponents including condensers, capacitors and resistance used in thecontroller shall be de rated sufficiently for safe working during over loads,no loads, at maximum temperatures and highly humid conditions.

7.10 The printed circuit boards (PCBs) shall be protected against dust andhighly humid atmospheric conditions. The PCBs shall be properly fixed

Page 12: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 12 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

with proper rubber bushes at the fixing areas so that due to vibration andshocks the PCBs will not damage. A good quality of PCB with minimum1.6 mm thick shall be used. Each PCB shall be provided with terminalboard with wago type preferably or similar reputed make connectors, sothat external connections shall be easily provided.

7.11 Anodised name plates shall be provided for the following

i) All fuses with rating

ii) Current sensors with ratings

iii) Terminal Boards

iv) Inside the regulator terminal box U, V, W, F+, F-, DC+, DC-, BC+, andOVP reset switch.( BC+ in case of 4.5 kW ERRU only).

iv) Inside the cover block circuit diagram

v) Aux. Equipment

Terminal identification marking shall also be provided on an anodisedname plate in line with the existing design of Electronic Rectifier-cum-Regulator terminal box.

In addition, identification marks for phases, field connections etc. i.e. U, V,W, F+, F-, DC+, DC- and BC+ shall be punched on the respective terminalposts.

7.12 The bus bar holes shall be punched to the proper sizes of holes. Thesharp corners and burs shall be removed. The holes shall be provided atthe centre of the bus bars. The size of the copper bus-bar shall beminimum 90 sq. mm preferably 18 mm x 5 mm cross-section of electrolyticcopper or use of elastomeric cable of equivalent size for 25 kw. Whereasthe bus bar size of 16 sq. mm or use of elastomeric cable of equivalentsize may be used for 4.5 kw ERRU. Suitable bi-metallic washers shall beused wherever required for making connections at aluminium and coppercontacts.

As far as possible number of bends on the bus bars shall be minimised.The design of bus bars shall be with “L” bends. The bar flat wise ‘C’ bendsshall be avoided. Bus bar bends shall be done on jigs. Only approved busbar lay out shall be provided.

Page 13: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 13 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

7.13 The three phase bus-bars U, V, W shall be provided with yellow colour,DC (+ve)-Red, DC (-ve)-Blue and BC (+)ve-Black coloured heat shrinkablesleeves shall be provided as per above scheme.

7.14 Inside the regulator except fuses all the power connections shall beprovided with locking washers to avoid loose connections andunnecessary tampering on the power connection.

The internal control wiring shall be done with PTFE cable size 0.96 sq. mm/ 1.5 kV for both 25 kW & 4.5 kW regulators. 1.23 sq. mm/1.5 KV PTFEcable shall be used for field circuit. For capacitor circuit 2.5 sq.mm cableshall be used. Proper stiffener arrangement for cable securing shall bedone for wiring with ferrule markers with nos. to avoid any loose hangingof cables and ease of terminal identification during maintenance.

For external control wiring for 25 KW ERRU, 12 wire control cable shall beused between one ERRU and coach indication panel. Similar cable shallbe used for another ERRU. Cable shall be flexible PVC insulated TinnedCopper Strands and Twisted Pair, screened, 12 core with each core of1sq. mm. Control cables shall be connected to ERRU and coachindication panel end with the help of L type 12 pin connector of followingtype:

(a) MS 3102E 28-18 for panel side(b) MS 3108F 28-18 for cable side

The control cable should be rugged and shielded to protect it from EMI /EMC interferences.

Proper stiffener arrangement for control cable securing shall be done forinternal wiring of ERRU with ferrule markers with numbers to avoid anyloose hanging of cables and ease of terminal identification duringmaintenance.

7.15 All the auxiliary equipment like choke, transformers, filter condenser,bleeder resistance shall be preferably mounted on the auxiliary equipmentfixing base with a terminal board. If the auxiliary equipment fixing board(AEB) has been provided, it shall be possible to be removed withequipment and re-fixed. The equipment mounted on the board shall notfoul or infringe with power blocks or power circuit.

7.16 For the better cooling of UVC, a cast aluminium heat sink may be providedon the regulator backside. The bottom side of UVC may be provided with6 mm thick machined aluminium in flush with heat sink. The IGBT,Transistors etc. may be mounted on the aluminium inside the box. TheUVC may be fixed at the bottom right corner of regulator. The heat sink

Page 14: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 14 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

provided at the back of UVC box, shall be provided with suitable fixingarrangement.

7.17 The cast aluminium/alloy heat sink cooling fins shall be black anodised forbetter cooling. For fixing screw metal inserts with knurling / helicoil shall beprovided so that the fixing screws can be provided from inside theregulator box. The depth of tapped portion shall be adequate in side themetal insert. No hole or tapped screw is visible from the cooling fin side toavoid water entry.

7.18 Fuse mounting shall be such that it is clearly visible and easilyreplaceable. Fuse blown indication shall be available on UVC.

7.19 The DC current and battery current sensors shall be mounted on insulatedboard and then fixed so that the heat transfer from the heat sink can beavoided.

7.20 Testing kit for ERRU testing shall be designed to test the circuits atworkshop before assembly. The testing kit shall be able to test fullregulator circuit and also its main components like UVC IGBT, Diodes etc.

7.21 Stand by Unit for Electronic-Rectifier-cum-Regulating Unit (ERRU) shall beprovided as detailed in annexure -B

8.0 INTER CHANGEABILITY/UNIVERSAL APPLICATION

The UVC of one make for a rating shall be interchangeable with otherratings of ERRU of same make. The mounting dimension of the UVC in allratings of ERRU of a make shall be same for making it interchangeable.ERRU of a rating shall be capable to work satisfactorily in conjunction withall other make of alternators having same rating. For 25kw, both ERRUs &CIP as a set shall be interchangeable.

9.0 ANTI-PILFERAGE MEASURES

Design of ERRU shall incorporate anti-theft arrangement to avoid thepilferage of components of ERRU during service. The detailed drawingsfor this shall be approved by RDSO.

10.0 MARKING

The ERRU shall be provided with suitable name plates on which thefollowing shall be marked:

i) Maker’s name and trade marks

ii) Rated capacity of the ERRU

Page 15: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 15 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

iii) Maximum Voltage and current rating

iv) Specification number

v) Serial No. of the ERRU in which first two digits shall indicate year ofmanufacture, next two digits the month of manufacturing and next 3 digitsthe number of machine manufactured during the particular month.Necessary drawing for the same shall be approved from RDSO. Punchingof serial numbers along with name of manufacturer on ERRU box outsideand inside shall also be done.

Space shall also be provided on the name plates for the purchaser to markthe Railway Administration’s Code initials.

vi) The rectifier-regulator housing shall have a red coloured plate of approveddesign marked “Caution-Keep the cover tightly closed”.

vii) Light Brown colour band 50 mm width shall be provided on the cover forvisual identification of “Universal-Voltage Controller” The light Brown codeNo. 410 of IS: 5-1994. The 50 mm band across all the sides shall beprovided 50 mm above the bottom side of the cover.

viii) UVC box shall be marked with the name of manufacturer.

11.0 TESTS AND PERFORMANCE

11.1 Classification of tests

11.1.1 Prototype Tests: A prototype test is the test which is to be carried out onan ERRU declared as a prototype under the following conditions:-

a) A manufacturer undertakings to manufacture for the first time ORb) A fundamental change in design is introduced.

11.1.1.1 The prototype tests shall be carried out at the works of the manufacturersby RDSO. Manufacturer shall submit the details of ERRU and internal typetest results before offering the equipment for prototype testing.

11.1.1.2 All the following tests on the ERRU shall be conducted in conjunction withalternator of the same rating of approved make. Similarly, UVC of a makeshall be tested for its performance with other capacity of ERRU inconjunction with alternator of the same rating.

The following shall constitute prototype tests:

Page 16: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 16 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

i) Verification of overall dimensions and visual check

ii) Temperature rise test

iii) High voltage test

iv) Insulation resistance test

v) *load test

vi) *Current Limiting characteristic test

vii) *Battery Charging current limiting test.

viii) Over Voltage Protection test

ix) *Parallel operation test

x) Indication Board performance test

xi) Hose proof test

xii) Data shall be down loaded

xiii) Special Tests:a) Ripple content testb) Shorting of power block diodes modulesc) Open circuiting of power block diodesd) Computation of junction temperaturee) *Measurement of (MFO) minimum speed for full output at cold and

hot condition of alternatorf) *Measurement of (MHO) minimum speed for half outputg) *Measurement of cut-in speedh) Efficiency testi) Short circuit protection for DC output voltagej) Fire retardant test for terminal insulatorsk) System testl) Environmental tests

m) In order to ensure compatibility of the equipment (ERRU), thefollowing tests shall be carried out as per relevant IEC.

Page 17: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 17 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

i) Electrical Fast Transient / Burst immunity test.

The test shall be carried out as per IEC: 61000-4-4.

Power lines Communication and signal linesPulse repetition rate 2.5 KHz 5 KHzVoltage peak 4 KV 2 KV

ii) Surge Test.

The test shall be carried out as per IEC: 61000-4-5. Installation class: 4,Test level: 4 KV

iii) Electrostatic discharge:

The test shall be carried out as per IEC-61000-4-2.

a) Enclosure conductive part – contact discharge test at 6 KVb) Enclosure insulated part – air discharge test at 8 KV.

iv) Radiated susceptibility test – As per IEC 61000-4-3

NOTE: * These tests shall be carried out in both directions of alternators.

xiv) Earth Potential testBody of the ERRU shall be given external voltage of 110V DC/AC.Performance of ERRU shall not get affected.

xv) 600 Volt pulse test as type (Detailed in annexure –C)

xvi) Test for SMPS

xvii) ERRU to CIP wire shorting test. (Detailed in annexure –D)

xviii) Total DC isolation test (both positive & negative) for SMPS

xix) Battery charging hall effect sensor wire removal/shorting test.(Detailed inannexure –E)

11.1.1.3 PROTOTYPE APPROVAL: After successful completion of the Proto-typetests as specified above, at firms’ premises, the clearance shall be givenby RDSO for its fitment on the coach for extensive field trails for minimumperiod of three months. For field trial the requisite minimum modifications

Page 18: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 18 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

in the cabling layout shall be done by the firm in consultation withRailways.

Two units of 25 kw and one unit of 4.5 kw rating shall be put on the AC &TL coaches respectively for conducting field trials.

After successful completion of field trials as reported by the Railways, theprototype approval shall be considered. The initial prototype approval ofERRU shall remain valid for two years. In case of unsatisfactoryperformance in the field re-prototype testing either in full or part can alsobe done earlier at any time by RDSO for which all the necessary facilitiesshall be provided by the ERRU manufacturer free of cost.

11.1.2 TYPE TESTS: A type test is to be carried out by the manufacturer and theinspection authority on electronic rectifying-cum-regulating equipmentpicked up at random at the rate specified in clause 14.0 to ensurecompliance with specifications in details as declared by the manufacturerand approved by RDSO.

These tests are to be carried out at manufacturer’s premises. Thefollowing shall constitute type test:

i) Verification of overall dimensions and visual check

ii) Temperature rise test

iii) High voltage test

iv) Insulation resistance test

v) *Load test

vi) *Current Limiting characteristic test

vii) Battery Charging current limiting test

viii) Over voltage/Surge protection test

ix) *Parallel Operation test

x) Indication board performance test

xi) Data shall be down loaded

xii) Hose proof test

Page 19: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 19 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

xiii) 600 Volt pulse test as type (Detailed in annexure –C)

xiv) Test for SMPS

xv) ERRU to CIP wire shorting test. (Detailed in annexure –D)

xvi) Total DC isolation test (both positive & negative) for SMPS

xvii) Battery charging Hall Effect sensor wire removal/shorting test.(Annexure-E)

11.1.3 ROUTINE TESTS: The routine tests are to be carried out by themanufacturers at their premises on every ERRU in conjunction withalternator of the same rating to ensure compliance with specification andreliability in service.

The following shall constitute routine tests:-

i) Verification of overall dimensions and visual check

ii) Load test

iii) Battery Charging current limiting test

iv) Over voltage/Surge protection test

v) High voltage test

vi) Insulation resistance test

vii) Hose Proof test

vii) Indication board performance test

viii) Data shall be down loaded

ix) 600 Volt pulse test (Detailed in annexure –C)

x) Total DC isolation test (both positive & negative) for SMPS

11.1.4 ACCEPTANCE TEST: These tests are to be carried out by an inspectingauthority nominated by the Purchaser at Manufacturer’s premises toensure compliance with the specification. Before offering the ERRU forinspection to the purchaser/inspecting officer, the in house routine test

Page 20: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 20 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

shall be sent, well in advance to the purchaser/inspecting officer by themanufacturer for scrutiny.

The following shall constitute acceptance tests:

i) Verification of overall dimensions and visual check.

ii) Temperature rise test

iii) High voltage test

iv) Insulation resistance test

v) *Load test

vi) *Current Limiting characteristic

vii) Over voltage/Surge protection test

viii) Indication board performance test

ix) 600 Volt pulse test(Detailed in annexure –C)

x) Total DC isolation test (both positive & negative) for SMPS

Note: Tests marked * are to be conducted in both directions of rotation.

11.1.5 The following shall constitute the in-house tests results:

i) Type test results

ii) Routine test results

The Type tests shall be done as per the sampling clause no.14.0 of thisspecification. The routine test shall be done on each and every ERRU bythe manufacturer.

The inspecting officer can ask for repetition of any /all type/routine tests, ifhe so desires. Manufacturer shall furnish the details of variouscomponents used in manufacturing of ERRU and as also asked byinspecting official.

As per the declaration of the manufacturer of the ERRU rating, the abovetests shall be repeated for every rating in conjunction with alternator of thesame capacity. For every rating, the manufacturer shall submit in-housetest results accordingly.

Page 21: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 21 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

11.1.6 ERRU in conjunction with alternator of the same rating shall be used onair-conditioned and conventional coaches where high reliability is to beensured. Therefore, every equipment is to be accepted after completing allacceptance tests. The temperature rise at 2500 rev/min. will also be doneon every machine. However, conducting the temperature rise test onlesser number of machines can be considered by RDSO if the productionhas stabilised and proper quality control is being ensured by the firm asper RDSO approved Quality Assurance Plan – Without specific permissionfrom RDSO, this test shall not be deleted.

11.1.7 Renewal of type test approval

After successful prototype testing, type test approval shall be generallygiven for 2 years and maximum for 3 years. Manufacturer shall apply forrenewal of type test approval, six months in advance before expiry of theapproval. During type test renewal following information shall be given bymanufacturer:

i) Any deviations from bill of material and QAP approved by RDSO earlier.

ii) Implementation confirmation of modifications issued by RDSO if any.

iii) Addition/Deletion of Machinery and Plant.

iv) Supply orders executed by the manufacturer in last 3 years. Followingdetails should be given:a) P.O. No./Dateb) Consignee and date of supplyc) Quantity

d) Rate (inclusive of all taxes)e) Warranty failures reported (nature of failure and action taken)

v) Following tests shall be carried out for revalidation of type test approval.a) Temperature rise testb) High voltage testc) Insulation resistance testd) *Load teste) *Current Limiting characteristicf) Battery charging current limiting testg) Over voltage/surge protection test

Page 22: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 22 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

h) Indication Board performance testi) *Parallel operation test.j) Data shall be down loaded

NOTE * I) These tests shall be carried out in both directions of alternators. II) Verification of electronic component test details shall be made as per

clause no 13.11.4(B).After successful completion of the above tests renewal of type approvalshall be given.

12.0 TEST INSTRUMENT: The indicating instruments used in electricalmeasurement shall confirm to IS: 1248-1958 (Specification for ElectricalIndicating instruments). Instruments with the following accuracy shall beused:

i) For prototype, acceptance and routine tests instrument of class 0.5accuracy

ii) For surge protection test, the amplitude and duration of the surge voltageshall be measured by using digital storage oscilloscope having suitableinterface with printer/PC for down loading voltage and current waveformsdirectly from the Oscilloscope.

iii) ERRU and specifically its control power supply modules should be suitablefor noisy supply system. Wave form of 110Volt DC at DC busbar of ACcoach may be taken by the manufacturer, if required.

13.0 TESTS

13.1 VERIFICATION FOR DIMENSIONS AND VISUAL CHECK:

This is to check the dimensions of assemblies and sub-assemblies i.e.overall dimensions of ERRU box, terminal arrangement and layout of aux.Equipment as per specifications and constructional details thereof toensure that they are consistent with good engineering practice. Inter-changeability aspects shall also be ensured.

“Sound engineering practices should be followed in the manufacturing ofERRU. Care should be taken for avoiding sharp bend to cables, ensuregood welding quality with smooth finish, Use of standard hardware,avoiding sharp edges, proper bunching, routing and support to the cables.”

13.2 TEMPERATURE RISE TEST:

Page 23: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 23 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

13.2.1 The temperature rise test shall be conducted with the same capacityalternator and ERRU, with forced air cooling of 6m/sec. for alternator and4m/sec. for regulator.

13.2.2 The temperature rise test shall be conducted on ERRU in conjunction withalternator of different capacities at MFO and at 2500 rpm speed at ratedcapacity until the body temperature of alternator gets stabilised as evidentfrom three consecutive readings of frame temperature at half an hourinterval. The air velocity at location where the alternator and ERRU are tobe located for tests shall be adjusted as mentioned in clause 13.2.1 priorto mounting of equipment in position. For 25 kw after each temperaturerise test at MFO and 2500 rpm speed, one hour over load test shall beconducted at 222 Amps.

While conducting acceptance test, in case of 25 kw ERRU, only at 2500rpm at rated output and one hour overload test at 222A shall be conductedwhereas temperature rise test in case of 4.5 kw shall be at 2500 rpm atrated condition.

Capacitykw

Maximumspeed rpm

Minimumspeed rpm

Rated voltageVolts.

Rated currentAmps.

One hourO/L Amps.

25kw 2500 MFO 130 193 2224.5kw 2500 MFO 120 37.5 --

13.2.3 ERRU components temperature shall be recorded for every one hour up tofour hours and there after for every half an hour readings shall berecorded. Three consecutive half an hour readings indicate stabilisation ofthe body temperature of alternator.

13.2.4 In the ERRU the following temperature shall be recorded

i) Diode base temperature

ii) Transformer

iii) Hall effect sensors

iv) HRC fuse

v) Bleeder Resistance

vi) Heat sink of controller

vii) Bus bar

viii) I.G.B.T. inside the Control box

Page 24: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 24 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

ix) Ambient inside the Regular box

x) Ambient inside the UVC

13.2.5 In regard to ERRU equipment, the temperature rise of main diodes, Hallsensors, HRC fuses, bleeder resisters, current transformer, bus bars etc.,shall be less than designed temperature limits of each component underworst operating conditions. The temp. Rise of electronic devices beingused in UVC i.e. IGBT, auxiliary diodes, auxiliary power supply moduleetc. Shall not increase more than 30 deg. C above the ambient of 55degree C. Inside ambient of the UVC box shall also be recorded and itshall not exceeding 30.

13.2.6 The temperature rise of power diodes, ISO-Packs, Hall Sensors, ExcitationTransformer (if used), bus-bars etc. Shall not be more than 50 deg. Cabove the ambient of 55 deg.C. There shall be consistency in the qualityduring lot production of the equipment whereby achieving consistency invarious test parameters such as regulation, temp. Rise etc.

13.3 INSULATION RESISTANCE TEST:

The insulation resistance shall be measured before and after high voltagetest between all live terminals shorted together and body with a 500 V DCmegger and these values shall not be less than 20 meg ohm for ERRU.

13.4 HIGH VOLTAGE TEST

Immediately after completion of heat run/performance tests, an ACpotential of 1500 V rms at 50 Hz shall be applied between all live terminalsshorted together and housing of the equipment. The test shall becommenced at a voltage of less than one third the test voltage and shallbe increased gradually to the full test voltage. The test voltage of 1500 Vfor a period of 60 seconds shall be applied after conducting temperaturerise test. The leakage current shall not exceed 10 mA for the above tests.

Note: During HV test, UVC may be disconnected.

13.5 LOAD TEST:

13.5.1 The alternator shall be run in conjunction with the ERRU of same capacity.The test shall be conducted with a resistive load and with battery.Preferably this test shall be conducted with resistive load and a batterybank of adequate capacity.

Page 25: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 25 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

13.5.2 All performance tests shall be conducted at the set voltage of 129 V at halfload of 97 A and at 128.5 V, at half load of 19 Amps for 25 kw and 4.5 kwrespectively. The voltage setting of the ERRU shall be done at 1500 rpmafter the heat run test. The alternator frame temperature shall be 40 deg.C above the ambient.

13.5.3 The test shall consist of the following:a) No load testb) Speed versus output voltage characteristic testc) Current versus voltage characteristic test

13.5.4 BASE LOAD:

In this test, the speed shall be varied covering the entire working range ofspeed and corresponding DC voltage available at equipment outputterminals shall be noted. The voltage variation shall not exceed +2% ofpre-set voltage for the speed range from the MFO speed to 2500 rpm.The cut-in-speed shall also be noted in this test. The speed shall beadjusted at 800, 1000, 1200, 1500, 2000 and 2500 rev/min. For 4.5 kw inaddition to these speeds the test at 600 rpm as MFO shall also be done.This test shall be conducted at 10A and 1 A for 25 kw and 4.5 kwAlternator respectively as base load.

13.5.4.1 No load test at 0 A shall be conducted for the above conditions and the noload voltage shall not exceed 135 V for 25 kw and 130 V for 4.5 kw ERRUrespectively.

13.5.4.2 Speed versus DC output voltage graph shall be plotted for ‘Base Load’and ‘o’ A.

13.5.5 SPEED VERSUS OUTPUT VOLTAGE CHARACTERISTIC TEST:

It shall be done at overload, full rated current, 75%, 50% and 25% of fullrated current. The speed shall be varied from MFO to maximum speed asper speeds mentioned Cl.13.5.4. The voltage shall not vary more than+2% of pre-set voltage for the range from the MFO speed to 2500 rpm atthese loads.

Speed versus DC Output voltage graph shall be plotted for all these loads.

The overloading of ERRU shall be done as per Cl.6 of this specification.

13.5.6 CURRENT VERSUS VOLTAGE CHARACTERISTIC TEST:

Page 26: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 26 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

Current versus voltage characteristic test shall be done at 1800 rev/min.The current shall be varied from 0A to rated value of 193 A for 25 kw and 0A to rated value of 37.5 A for 4.5 kw alternators keeping the speedconstant. The voltage variation shall be within +2% of the pre-set value.

The current –Vs-voltage shall be plotted for the load variation.

13.6 CURRENT LIMITING CHARACTERISTIC TEST OF ALTERNATOR ANDREGULATOR:

13.6.1 After the current voltage characteristics test, current limiting test shall bedone. At the point when the load is increased and current does notincrease, the value of current shall be treated as the limit of current setting.The DC out put voltage shall not be less than 120 V at 222A load, 115 V at40A for 25 kw and 4.5 kw respectively. The current limiting shall notexceed 230 A and 42 A for 25 kw, and 4.5 kW ratings.

The current-vs-voltage shall be plotted for the load variation includingoverloading of the ERRU.

Note: The difference in voltage developed in clockwise and anticlockwisedirection shall not be more than 1 V during all conditions of load test andcurrent vs voltage characteristic test..

13.7 BATTERY CHARGING CURRENT LIMIT TEST:

i) Total battery charging current (BCC) in AC coach shall be limited to 220+5amps corresponding 20% of the C10 capacity of charging current i.e. 1100x 0.2 = 220 Amps maximum, when two ERRUs are in parallel.

ii) Battery Charging Current (BCC) shall be limited to 24+ 2 Amps for 4.5 kwRegulator.

iii) BC +ve terminal shall be loaded with resistive load to check the batterycharging current limits.

iv) The total load connected across the DC output and BC +ve terminal of theERRU shall not exceed the overload rating of the alternator at any giventime enroute.

v) The BC terminal voltage shall be recorded for the load variation from 0A tothe battery charging limits keeping the DC +ve terminal without any load.The battery charging current versus DC output voltage shall be plotted.

vi) Total DC output current versus DC output voltage shall also be plotted.

Page 27: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 27 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

13.8 PARALLEL OPERATION: (Only for 25 kW ERRU)

13.8.1 This test shall be done at 800, 1800 and 2500 rpm at 25%, 50% and 100%of full loads i.e. 386 amperes.

13.8.2 Two alternators shall run in parallel with interconnections between ERRUs.

13.8.3 Individual alternator loads & total load and bus bar voltage shall berecorded.

13.8.4 The difference of current between ERRUs shall not exceed 10 amps.

13.9 INDICATION BOARD TEST:

13.9.1 The indication board working shall be checked for the following:i) Capacity of alternator

ii) Healthiness of UVC (failure status)

iii) Over voltage Protection

iv) Fuse failure

v) Overload fault

vi) Downloading of recorded data as per format given in Clause 13.9.8

* If stoppage is more than one hour – non-generation time shall not becounted and generation and non-generation time in hours shall berecorded in three digit.

13.9.2 During battery charging/discharging test, check shall be conducted toverify the Amp. Hours of discharge/charge indicated on the indicationboard. A discharged battery of a battery set, preferably of 1100 Ahcapacity shall be charged/discharged for five hours. The indicated readingshall not vary +3% over the calculated reading.

13.9.3 Faults shall be created and failure indication shall be checked.

13.9.4 The attachment and detachment of the indication board should bechecked for ease of maintenance and proper contacts. If the indicationboard is removed performance shall not be affected.

13.9.5 Data shall be downloaded by USB Pen Drive of reputed make. Downloading data should be directly openable in MS Office applications likeExcel/Word. It should be possible to down load data of at least 24 coachesin one go i.e. without the need to copy the data on laptop.

Page 28: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 28 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

13.9.6 Memory shall have sufficient capacity to contain minimum 7 days data witha resolution of one minute apart from cumulative data of last 7 days andfault data.

13.9.7 Transferring of the Journey data: Normally, the data stored in the portableUSB pen drive unit shall be transferred directly to the PC or laptop havingUSB port.

13.9.8 Reporting Format: Recording interval shall be one minute and minimumduration of recording shall be seven days. The format of reporting shall beas follows:

Format A

ERRU1 ERRU2Date TimeOutputVoltage

OutputCurrent

OutputVoltage

OutputCurrent

Format B

Date Time CumulativeChargingAh

CumulativeDischargingAh

Generationtime

NonGenerationtime

Distancetravelled

Format C for failures

Date Time Type of Faults Remarks

Types of faults which shall be recorded, preferably are as follows:

No supply from alternator or alternator failureOver voltage generationUVC FailurePower circuit failureOVP Tripped, OVP ResetOver loadShort circuitBattery voltage low

ChargingCurrent

DischargingCurrent

AlternatorRPM

Page 29: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 29 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

DISPLAY UNIT

The design of the UVC shall be provided with a provision of data logger tolog both alternators DC output currents, DC voltage/battery voltage,battery charging/discharging current with respect to real time. USBinterface shall be available enabling to down load in any commercial pendrive and analyse recorded data directly in MS Office application. TheUVC shall also be provided with a LCD/alpha-numeric display to indicateits various parameters as given below:

Following parameters should also be stored in the memory:

Parameter Recordingfrequency

Cumulative

Total distance travelled by theparticular coach

1 hour Yes

Alternator rpm 1 minute NoTotal generation and non generationtime

1 hour Yes

Last 32 faults recording Actual time NoOutput voltage ERRU1 1 minute NoOutput current ERRU1 1 minute NoOutput voltage ERRU2 1 minute NoOutput current ERRU2 1 minute NoBattery charging current 1 minute NoBattery discharging current 1 minute NoCharging Ah 1 hour YesDischarging Ah 1 hour Yes

Please note the following points:

i) Cumulative data summary must be available at the end of journey.

ii) Output voltage will display battery voltage when train is not running.

iii) At the end of journey if waiting period is more than one hour, then thatperiod shall not be counted as non generation time.

iv) If external charging is done, then, it should not be counted towardscumulative charging ampere hour.

Page 30: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 30 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

It shall be possible to download the data using any commercial USB pendrive from ERRU to PC. In case memory becomes full, earlier data shouldbe automatically deleted and data for last seven days should be retained.

It should be possible to downloaded data of at least 24 coach train withoutneed of laptop. Downloading data should open directly in MS-Office.

All the above parameters shall be displayed by manual selectionarrangement on the display unit.

“The display should be available with the UVC inside ERRU box. For 25KW ERRU, mounting bracket dimensions of coach indication panel shallbe as per sketch No. RDSO/PE/SK/AC/0059-2012 (Rev. 1) or latest” For4.5 kW ERRU coach indication panel is not required. For 25KW CIP isrequired besides internal display. Field current monitoring and controlshould be implemented to limit the field current at set value.

Field excitation control circuit design shall be IGBT with driver controlcircuit to give controlled feed to the field of alternator to meet therequirements. IGBT shall be of proven design with high reliability withadequate thermal margins as mentioned above. It shall have separateheat sink for better heat dissipation.

ERRU circuit design shall not include Electro-Mechanical Static relays.Moreover Potentiometers, change over switches for voltage and currentsettings should not be used to achieve higher reliability. Use of ExcitationTransformer/control transformer/choke etc. Shall be minimum possible.

13.9.9 Evaluation Software: The retrieved data should be possible to read andprinted through Microsoft EXCEL. However for further complete analysispurpose special software can be supplied. If special software is supplied,it has to be installed with every depot / workshop. Software shall give asummary of exceptions in the recorded data i.e.:-

i) How many times voltage regulation crossing 2%?ii) How many times total current / battery charging current limit reached?iii) Any other filter asked by IR & felt necessary by manufacturer.

13.10 Hose Proof Test:

The enclosure of rectifier-regulating equipment shall be protected againstingress of solid foreign bodies and water in accordance with IS: 13947.After these tests the equipment shall work satisfactorily. This shall beconducted in accordance with IP-65 as per IEC 60529 with latestamendment and worked satisfactorily.

Page 31: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 31 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

13.11 Special Test

13.11.1 Ripple content test: The voltage and current ripple content in dc outputshall not exceed 2% and 10% respectively in the battery charging load andDC output at 800, 1800, 2500 rpm for 25% load, half load and full load.Ripple content shall be computed from digital storage oscilloscope havinginterface with the printer/PC. It shall be calculated as under:Ripple content = (V max – V min)/ (V max + V min) x 100Where V max = Maximum voltage V min = Minimum voltageTo arrest the ripple, suitable filter circuit may be incorporated in regulatorwith electronic component of highest reliability.

13.11.2 SHORTING OF POWER DIODE: The Alternator with Electronic RectifierRegulator shall be run at 1800 rpm at full load with pre-setting the full load.Stop the alternator, any one power diode of the ISO-Packs shall beshorted and the alternator with rectifier regulator shall be run at 1800rev./min. The pre-set full load shall be connected across DC outputterminals for 2 minutes. After the test, no component of alternator orrectifier regulator shall get damaged. DC output voltage & current shall berecorded.

13.11.3 OPENING OF POWER DIODE: The alternator with electronic regulatorshall be run at 1800 rpm and pre set the full load in three steps. Stop thealternator. Then any one power diode of any of the Power block diodemodules shall be opened and alternator with rectifier regulator shall be runat 1800 rev./min at no load for 2 minutes and then the full load resistanceshall be applied gradually in three steps and run for 2 minutes. After thetest, no component of alternator or rectifier regulator shall get damaged.

13.11.4 COMPUTATION OF JUNCTION TEMPERATURE OF SEMI-CONDUCTORS USED IN ERRU:

A) The junction temperature of power diode/ISO-Packs and auxiliary diodesshall be computed. The temperature of the junction shall not exceed 110degree centigrade as specified in Specification No. ELRS/SPEC/SI/0015-Oct. 2001. The loading of the various electronic components and othertests shall be as per this specification.

B) Clause No. 4.1 to 4.6, 6.1 & 6.2, 7.1 to 7.11 and Annexure 7 of thespecification no. ELRS/SPEC/SI/0015-Oct. 2001 shall also be complied.

13.11.5 MEASUREMENT OF MFO SPEED AT COLD AND HOT CONDITION OFALTERNATOR: The Minimum speed for full output of the alternator bothin cold and hot condition shall not be more than 800 rev/min and 600 rpm

Page 32: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 32 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

for 25 kw and 4.5 kw respectively. The test shall be done in both clock-wise and anti-clock-wise directions. Apart from measuring the cut-inspeed, MHO and MFO, the characteristic curve between speed and outputshall be plotted by increasing the load current at various speeds till thevoltage drops to 129 V – 2 % i.e. 126.4 V.

13.11.6 MEASUREMENT OF MINIMUM SPEED FOR HALF OUTPUT (MHOSPEED):

i) For 25 kW ERRU –The alternator shall be run at a speed of 600 rev/min.The current at 130 V output setting shall be measured. It shall not be lessthan 50% of rated current at 600 rpm and efforts shall be made to achieve60% of rated current. Output voltage shall be maintained within theregulation tolerance rang shall be acceptable.

ii) For 4.5 kW ERRU – The alternator shall be run at a speed of 500 rev/min.The current at 120 V, output setting shall be measured. It shall not be lessthan 50% of rated current at 500 rpm and efforts shall be made to achieve60% of rated current. The speed at which 50% rated current is availableshall also be measured and it should not be more than 500 rpm. Outputvoltage shall be maintained within the regulation tolerance range shall beacceptable.

13.11.7 MEASUREMENT OF CUT-IN SPEED: The minimum speed of alternatorfor cut in speed in both the directions shall be recorded. The speed shallnot be more than 400 rpm (110V) for 25 kw alternator and 350 rpm (108V)for 4.5 kw alternator.

13.11.8 EFFICIENCY TEST: The efficiency test shall be conducted at the 800,1800 and 2500 rpm at rated load, half load and quarter load for outputterminals of ERRU. Load versus efficiency curve shall be plotted fordifferent speeds as mentioned above. The efficiency at 1800 rev/min. Atfull load shall not be less than 95%.

13.11.9 Efficiency test shall be done by measurement of input and output powersat the ERRU input and output terminals.

13.11.10 OVER CURRENT (SHORT CIRCUIT) PROTECTION: Short the DC+ DC-and BCC terminals at the Electronic Rectifier-cum-Regulator-Unit output.Run the alternator at 1800 rpm for two minutes and then increase thespeed to 2500 rpm and run for two minutes.

During the test AC fuses or field fuses may blow. No damage to alternator,ERRU or UVC should occur.

Page 33: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 33 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

13.11.11 FIRE RETARDANT TEST FOR TERMINAL INSULATORS: The terminalinsulators of ERRU shall be tested for resistance to spread of flame in themanner given below:

A terminal post insulator shall be subjected to the luminous bat swingflame, preferably supplied by a Bunsen burner. The specimen shall beheld at an angle of 45 degree to the horizontal. The flame shall be 25 mmin width across the tips. The flame shall be applied to the specimen at thelower end for 30 seconds and removed for similar period and then appliedagain to the same end for a second period of 30 seconds and then againremoved. Should the specimen get ignited, it shall not continue to burn formore than 50 seconds after the flame has been finally removed.

13.11.11.1 SYSTEM TESTS: System test shall be tested conducted at ICF inpresence of RDSO’s representative in line with the coach condition whichwill help the testing and rectification of ERRU by simulating faults. Thesesystem tests shall be done during prototype testing of the ERRU.

13.11.12 ENVIRONMENT TESTS: The test shall be conducted on rectifier-regulating equipment only as per IEC-60571-SECTION FIVE-TESTS”, thisshall include following tests:-

a. Temperature rise test (dry heat)b. Temperature rise test (damp heat)c. Vibration, shock and bump test.

13.11.12.1 Dry heat and damp heat test: - The dry heat and damp heat test shallbe conducted on all PCBs as per latest IEC-60571.

13.11.12.2 The ERRU shall be subjected to vibration and shock testing as per IEC61373 – 1999.

a) Random vibration test as per clause 8 Table-1 , category 1 Class Bb) Simulated long life test as per clause 9, Table-2 , category 1 Class Bc) Shock test as per clause 10, Table-3, category 1 Class B

13.12 Tests for SMPS

• Alternator is run & IGBT gate pulse is monitored and load increasedso that voltage is dropped to 60 Volts.

Alternator is run in this condition for 30 minutes.

Page 34: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 34 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

• Run the alternator from zero speed and external supply is given tofield until 55 Volt achieved and further increased to 250 V maximum.Behaviour of the SMPS value shall be recorded with graph.

Speed(rpm) SMPS ON (ERRUoutput voltage)

SMPS cut-off ( ERRUoutput voltage

Remarks

80018002500

After completion of all above tests final performance shall be conductedas per clause no.13.5.3 of RDSO Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev.2). After test, recorded data shall be downloaded from UVC aswell as from CIP by USB Pen drive to observe the recorded parameters.The printouts of the data shall be enclosed with the test results.

13.13 Total DC isolation test for SMPS

This test shall be performed by a 500Volts megger instrument, connectingbetween DC negative and positive shorted together at one end and UVCSMPS ground shorted together with all terminals of SMPS together.

The minimum permissible insulation resistance shall be more than 20Mega Ohms.

Note: test shall be performed during power off condition.

14.0 SAMPLING AND REJECTION

The sampling for conducting various tests shall be done as per thefollowing table:

Qty. Of each type of alternator covered in Purchase Order.Classification of TestQty. Upto 49 From 50 to

149From 150 to299

300 andabove

(a) Prototype As specified by RDSO(b) Renewal of

type approvalAs specified by RDSO

(c) Type 1 2 3 4(d) Routine All All All All(e) Acceptance All All All All

The rejection procedure shall be adopted as given below:

Page 35: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 35 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

StageClassificationof Test I II IIPrototype The machines shall not be cleared for regular manufacturing till it

passes all the tests. Quantity as specified by RDSO.Type Quantity as per

Cl.14Twice the number ofAlternators whichfailed in any of thetests at Stage I

If any alternator failsin 2nd stage. Theentire lot shall berejected.

Renewal oftype approval

Quantity as perCl.14

Twice the number ofAlternators whichfailed in any of thetests at Stage I

If any alternator failsin 2nd stage. Theentire lot shall berejected.

Acceptance All All All

If any machine fails in any of the tests and if it is considered that the natureof defect does not effect carrying out of further tests, the other tests shallbe conducted. The failed machine shall be re-offered for inspection in thesubsequent lot after rectification.

15.0 DRAWINGS/DESIGN DETAILS:

The quality documents (2 sets spiral bond booklet) shall be sent to RDSOfor taking approval of prototype. Quality documents will consist of:-

• Design details and Circuit diagram

• Prototype test results

• ISO 9001 certificate

• Operation / Maintenance Manual

• Bill of material

• Quality Assurance Plan. This should cover following aspects

a. Organisation chart bringing out the quality control set up.b. Qualification log sheets of the personnel manning the quality

control set up.

Page 36: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 36 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

c. Quality Assurance System: This shall cover the inspection andtesting plan of following.

i. Incoming materialii. Process controliii. Product control

d. Details of sub-vendors.e. Field trial report etc. f. ERRU components’ nomenclature, rating and loading.

16.0 APPROVAL BY RDSO:

16.1 The prototype ERRU shall have the approval of RDSO (Research,Designs & Standards Organisation, Lucknow-226011) beforecommencement of supply to Railways by manufacturing units. For thispurpose the manufacturer shall submit to RDSO the results of the in housetest results carried out at their works or in a recognised testing institutionalong with other details as per Clause 12. Notwithstanding the approval,manufacturer is wholly responsible for satisfactory service performance,life and reliability of ERRU.

The approval shall normally be valid for two years subject to satisfactoryperformance during the period as reported from the field. Themanufacturer shall make all arrangements for undertaking field trials attheir cost, if considered necessary by RDSO. For revalidation of theapproval the inspecting agency may pick up/select a ERRU sample atrandom from the regular production at firm’s premises or from the fieldjointly associating firm’s representative.

The manufacturer shall afford all facilities to RDSO for conducting theprototype tests as per Clause 11. In case it is necessary to conduct any ofthe prototype tests at a testing house/institution, the full cost of such testsshall be borne by the manufacturer.

16.2 The manufacturer shall submit assembly and part drawings to RDSO forapproval.

16.3 Manufacturer shall submit the details as asked for by RDSO.

16.4 Manufacturers shall not make any changes in the design of components ofERRU without approval of RDSO, Lucknow after a prototype approval of adesign has been given by RDSO failing which the firm’s approval may bewithdrawn/withheld.

17.0 GUARANTEE AND AFTER SALES SERVICE:

Page 37: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 37 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

17.1 Guarantee shall be as per standard IRS conditions of contract or specialconditions given in the tender.

17.2 Parts failing during the guarantee period shall be repaired/replaced by thesupplier free of cost within the shortest possible time after receipt ofintimation. For affecting such prompt replacement, the supplier shallmaintain with his service engineers posted at various stations, sufficientquantity of components and sub-assemblies. For each and every failure, ajoint failure report shall be prepared by manufacturer with the Railway’srepresentative for sending the same to RDSO’s scrutiny and takingnecessary inputs at their end to improve the design. Six monthly reportscontaining analysis of the failures and remedial measures proposed shallbe circulated by the manufacturer to RDSO for which format shall beobtained from RDSO. Such failures will also be periodically reviewed byRDSO.

17.3 Type defects will continue to attract the guarantee till such type defects arefully overcome. Accordingly, the guarantee period shall get extended.

18.0 Standardisation

i) Inter-changeability of UVC of different ratings of same make.

ii) Inter-changeability of 4.5 kW ERRU of any make.

iii) Inter-changeability of 25 kW ERRU along with display unit of any makewith standardisation of mounting and control cable.

iv) Standard arrangement for retrieval of data from the data logger.

v) Standard wiring arrangement for 25 KW ERRU I and ERRU II as perSketch No. RDSO/PE/SK/AC/0061-2003 (Rev. 0)

19.0 SCHEDULED MAINTENANCE: Being an electronic system, no scheduledmaintenance should be prescribed. The ERRU shall be termed as‘maintenance free’ and the manufacturer shall give declaration that noscheduled maintenance is required except visual check for mounting andexternal damages.

20.0 TRAINING: The manufacturer shall provide free of cost training to thesupervisors of the Indian Railways for operation, maintenance, faultfinding, repair of the offered equipment under guidance of skilledengineers, during the first three yeas of the service of the equipment.

21.0 INFRINGEMENT OF PATENT RIGHTS/ISO-9000 ACCREDITATION:“Indian Railways shall not be responsible for infringement of patent rights

Page 38: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 38 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

arising due to similarity in design, manufacturing process, use of similarcomponents in the design & development of this item and any other factornot mentioned herein which may cause such a dispute. The entireresponsibility to settle any such disputes/matters lies with themanufacturer/supplier.

Details/design/documents given by manufacturer/supplier are notinfringing any IPR and they are responsible in absolute and full measureinstead of Railways for any such violations. Data, specifications and otherIP as generated out of interaction with Railways shall not be unilaterallyused without the consent of RDSO and right of Railways /RDSO on suchIP is acceptable to manufacturer/supplier.”

The firm seeking RDSO’s approval for manufacture and supply of ERRUsconfirming to this Specification shall have ISO-9001 accreditation orequivalent certification to ensure its conformance to Quality Systems laiddown in the standard for design, manufacturing processes, raw material,testing, and quality control at different stages etc.

----------------------------------

Page 39: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 39 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

Bill of material of 25 KW ERRU specifying make of important itemsS.N. Description Specification Make

1. ISO Packs bridge / powerblock diode

350 A, VRRM 1200V • M/s IXYS• M/s International Rectifier Ltd.• M/s Hind Rectifiers Ltd.• M/s. Semikron.• M/s. Ruttonsha International

Rectifier Ltd.2. Field Diode 16A VRRM 1200V • M/s IXYS

• M/s International Rectifier Ltd.• M/s Hind Rectifiers Ltd.• M/s. Semikron• M/s. Ruttonsha International

Rectifier Ltd.3. Thyristor - • M/s IXYS

• M/s. Semikron• M/s International Rectifier Ltd.

4. Hall Effect Sensor 300 Amps • M/s ABB• M/s LEM

5. LCD Display - • M/s. Oriole Electronics• M/s. Lampex• M/s. Noritek

6. IGBT - • M/s IXYS• M/s Semikron• M/s International Rectifier Ltd.• M/s. Siemens• M/s. ABB• M/s. Infineon• M/s. Mitsubishi

7. Capacitor 4700 µF/450 V • M/s EPCOS• M/s Alcon• M/s. Kendeil• M/s. Nippon Chemi-Con• M/s. Hitachi

8. Connector 12 pinMS 3102 F 28-18E or

equivalentMS 3102 R 28-18F or

equivalent

• M/s Allied• M/s. Amphenol

9. Deleted10. HRC Fuse 160A ,16A, 10A

& 6 A- • M/s Cooper Bussman

• M/s English Electric Co.• M/s.ABB

11. Thimble Copper all sizes - • M/s. Klipon• M/s. Tyco• M/s. Jenson• M/s. Dowell

12. Control cables (SealedCable)

- • M/s. Huber & Suhner• M/s. NEXAN• M/s. TEFKOT• Any RDSO approved source

Page 40: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 40 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

Bill of material of 4.5 KW ERRU specifying make of important itemsS.N. Description Specification Make

1. ISO Packs bridge /power block diode

50 A, VRRM 1200V • M/s IXYS• M/s International Rectifier Ltd.• M/s Hind Rectifiers Ltd.• M/s. Semikron• M/s. Ruttonsha International

Rectifier Ltd.2. Field Diode 16A VRRM 1200V • M/s IXYS

• M/s International Rectifier Ltd.• M/s Hind Rectifiers Ltd.• M/s. Semikron• M/s. Ruttonsha International

Rectifier Ltd.3. Thyristor - • M/s IXYS

• M/s. Semikron• M/s International Rectifier Ltd

4. Hall Effect Sensor 50 Amps • M/s ABB• M/s LEM

5. LCD Display - • M/s. Oriole Electronics• M/s. Lampex• M/s. Noritek

6. IGBT - • M/s IXYS,• M/s Semikron• M/s International Rectifier Ltd• M/s. Siemens• M/s. ABB• M/s. Infineon• M/s. Mitsubishi

7. Capacitor 2500 µF/450 V • M/s EPCOS• M/s Alcon• M/s. Kendeil• M/s. Nippon Chemi-Con• M/s. Hitachi

8. Deleted9. HRC Fuse 32A , 10A &

6 A- • M/s Cooper Bussman

• M/s English Electric Co.• M/s.ABB

10. Thimble Copper allsizes (U Type) 7003insulated

- • M/s. Klipon• M/s. Tyco• M/s. Jenson• M/s. Dowell• Any RDSO approved source

Page 41: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 41 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

Annexure-A(Clause no. 7.7)

1.0 This Annexure covers the design, manufacture, testing and supply of OverVoltage Protection (OVP) Unit used in Electrical Rectifier-cum-RegulatingUnit(ERRU) for 25 kW or 4.5 kW brushless alternators with common UVCfor providing on self-generating air conditioning and conventional coachesfor supplying essential passenger amenities.

2.0 DESIGN AND MANUFACTURING REQUIREMENTS:-

2.1 Long life and minimum maintenance.2.2 Maximum reliability.2.3 Universal application within the speed range.2.4 Well protected against extraneous interference and pilferage.2.5 Modular type.2.6 The semi conductors and other parts used shall, confirm to reliability

assurance specification for electronic components used in rolling stockRDSO specification no. ELRS/SPEC/SI/0015 Oct.-2001.

2.7 Adequate surge protection.2.8 Fail safe.2.9 The printed circuit board (PCB) shall be protected against dust and humid

atmospheric conditions. The PCBs shall be properly fixed with properrubber bushes at the fixing areas so that due to vibration and buffershocks the PCBs will not damage. Good quality of PCB with minimum 1.6mm thick shall be used. Each PCB shall be provided with terminal boardwith wago type preferably or similar reputed make connectors, so thatexternal connections shall be easily provided.

2.10 The electronic devices shall be well protected from surges and spikescaused during working condition of the AC & TL coaches. All electroniccomponents used in OVP unit shall be rated sufficiently for safe workingduring over loads, no-load, at maximum temperatures and highly humidconditions.

2.11 OVP shall be set at 141±1 V & 138±1 V for 25 kW & 4.5 kW ERRUsrespectively.

2.12 OVP reset switch should be located inside the terminal box. The resetswitch shall be normally open type switch.

2.13 Series type of OVP shall be used having terminals U1, V, W, U, DC+ andDC- of OVP.

2.14 OVP trip shall incorporate a delay of 2 seconds before tripping.2.15 10 way single side screw terminal block (6 connections for U1,V,W,U,DC+

& DC- and 4 connection for UVC communication) shall be used.

Page 42: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 42 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

3.0 OVER VOLTAGE PROTECTION GENERAL

Due to component failure/open circuit in ERRU, static over voltageprotection circuit should be provided with no spurious trippings under no-load or when the system running with VRLA /conventional lead acidbattery connected at the output. During sudden throwing of load (withoutbattery connected), the over voltage static relay may trip but must reset byitself automatically. Latching of the static relay may be achieved underfault condition with battery supply available at the DC output. A certaintime delay may be provided for static relay operation so that the staticrelay does not trip when load is thrown off suddenly. However, the timedelay provided should be 2 sec. in order to protect the system undergenuine fault conditions. The tripping voltage of relays may be set at141±1 V & 138±1 V for 25 kW & 4.5 kW ERRUs respectively.

4.0 TESTING OF OVP

Testing of OVP shall be done as per format given below:-

4.1 25 kW ERRU

ERRU SET VOLTAGE: 129.5 V, 97.0 A at alternator speed of 1500 rpm.

OVP SET VOLTAGE: 141±1 V.

Sl.No. Load (Amp.) Speedoftesting(rpm)

Conditionof ERRU

Specifiedstatus relay(Tripped/not-tripped)

Observedstatus relay(Tripped/not-tripped)

Transient/Stabilizedvoltage to berecorded(Volt)

Batterystatus

1. 8002. 15003.

02500

ERRUworkingnormal

Not-trippedBattery notconnectedat Output

4. 8005. 15006.

102500

Opening/Shorting ofcontrol

TrippedBatteryconnectedat Output

7. 8008. 15009.

96.52500

Opening/Shorting ofcontrol

TrippedBatteryconnectedat Output

10. 800

11. 150012.

1932500

Opening/Shorting ofcontrol

TrippedBatteryconnectedat Output

13. 80015. 150016.

Throwing offfull load fromfull load i.e.193 A to 0.0 A. 2500

ERRUworkingnormal

Not-tripped Battery notconnectedat Output

17. Sudden 800 ERRU Not-tripped Battery not

Page 43: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 43 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

18. 150019.

loading from0A to full loadi.e. 193 A.

2500workingnormal

connectedat Output

4.2 4.5 kW ERRU

ERRU SET VOLTAGE: 128.5 V, 19.0 A at alternator speed of 1500 rpm.

OVP SET VOLTAGE: 138 ±1 V.

Sl.No.

Load (Amp.) Speedoftesting(rpm)

Conditionof ERRU

Specifiedstatus relay(Tripped/not-tripped)

Observedstatus relay(Tripped/not-tripped)

Transient/Stabilizedvoltage to berecorded(Volt)

Batterystatus

1. 8002. 15003.

02500

ERRUworkingnormal

Not-trippedBattery notconnectedat Output

4. 8005. 15006.

12500

Opening/Shorting ofcontrol

TrippedBatteryconnectedat Output

7. 8008. 15009.

192500

Opening/Shorting ofcontrol

TrippedBatteryconnectedat Output

10. 80011. 150012.

37.52500

Opening/Shorting ofcontrol

TrippedBatteryconnectedat Output

13. 80015. 150016.

Throwing off fullload from full loadi.e. 37.5 A to 0.0 A. 2500

ERRUworkingnormal

Not-trippedBattery notconnectedat Output

17. 80018. 150019.

Sudden loadingfrom 0A to full loadi.e. 37.5 A. 2500

ERRUworkingnormal

Not-trippedBattery notconnectedat Output

Note (Applicable for both 4.5 & 25 kW ERRU):-• During the testing of OVP, the status of static relay (tripping/not tripping) and DC output

voltage shall be recorded under the above conditions.• However, for prototype test machines the transient/steady state DC output voltage along

with rise/all time shall be recorded using digital storage oscilloscope having suitableinterface with PC/Printer for down loading the wave form.

• Battery bank used should be of adequate capacity and the same shall be kept in perfecthealthy condition.

• If output voltage increases beyond the set-voltage i.e. 135±2 V and remains for morethan 2 seconds, it should latch.

Page 44: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 44 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

Annexure-B(Clause no. 7.21)

1.0 This Annexure covers the design, manufacture, testing and supply ofStandby Unit to be provided in Electrical Rectifier-cum-Regulating Unit(ERRU) and RRU for 25 kW or 4.5 kW brushless alternators for providingon self-generating air conditioning and conventional coaches for supplyingessential passenger amenities.

2.0 OBJECTIVE OF STANDBY UNIT:

Stand by circuit will be switched on in case of failure of UVC, IGBT, fielddiode or ET inside the ERRU so that generation of power continues.

3.0 WORKING PRINCIPLE OF STANDBY UNIT:

The Stand-by circuit is in operation when there is a failure in ERRU/RRUand it stops generating the output. It is switched on when there isgeneration failure in ERRU. After switching on ,it starts feeding current toalternator field +ve and –ve terminal as a result of which alternator startsgeneration and it control the output voltage at 112 V-120 V. The Stand-by-circuit has been designed to monitor and thereby control the field currentthrough the alternator field coil.

4.0 DESIGN AND MANUFACTURING REQUIREMENTS:-

4.1 Long life and minimum maintenance.4.2 Maximum reliability.4.3 Universal application within the speed range.4.4 Well protected against extraneous interference and pilferage.4.5 It shall meet requirements of load consisting of fluorescent and

incandescent lamps, fans, motors, inverters, battery etc.4.6 The semi conductors and other parts used shall, confirm to reliability

assurance specification for electronic components used in rolling stockRDSO specification no. ELRS/SPEC/SI/0015 Oct.2001.

4.7 Any component failure of standby module shall be fail safe.4.8 The printed circuit board (PCB) shall be protected against dust and humid

atmospheric conditions. The PCBs shall be properly fixed with properrubber bushes at the fixing areas so that due to vibration and buffershocks the PCBs will not damage. Good quality of PCB with minimum 1.6mm thick shall be used. Each PCB shall be provided with terminal boardwith wago type preferably or similar reputed make connectors, so thatexternal connections shall be easily provided.

4.9 The electronic devices shall be well protected from surges and spikescaused during working condition of the AC & TL coaches. All electronic

Page 45: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 45 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

components used in Standby Unit shall be rated sufficiently for safeworking during over loads, no-load, at maximum temperatures and highlyhumid conditions.

4.10 This circuit shall be made with minimum possible components.4.11 The standby regulator module shall be able to work without battery.4.12 The standby regulator module output shall be connected to change over

switch and field terminal F-.4.13 The standby regulator module shall have DC+,DC-,F+,F-,Two AC

terminals only for functioning and control.4.14 All the above 6-connections shall be provided on a 6-way single side 4mm

screw type terminals.4.15 Individual built in sensors shall be used for field control.4.16 The standby regulator module shall be able to work with all the capacities

of ERRUs/RRUs.4.17 The internal power supply of standby regulator module shall be electrically

isolated with regulator DC circuit.4.18 The standby regulator module shall start voltage drooping after 75 %

loading for 800 to 2500 rpm range.4.19 It shall be compatible for 300 V test for one hour and 600 V pulse test for

one hour as done in case of ERRUs.4.20 It shall be possible to mount the standby regulator module inside the

ERRUs/RRUs.4.21 Other than 6-terminals specified no external terminals or modules shall be

used.

5.0 ISOLATION/SELECTION SWITCH

There will be an isolation/selection switch at DC terminals as per sketch inAnnexure-F the following characteristics:-(i) Toggle switch in 4.5 kW ERRU and change over/rotary switch

for 25 kW ERRU in CIP.(ii) Single pole double throw switch(iii) Rating: 16 Amps. (minimum)(iv) Location of switch: CIP Box for 25 kW ERRU & ERRU Box for

4.5 kW ERRU.

In case of 25 kW ERRU, wires from output of UVC & Standby Unit toRotary Switch will run through 12-pin connector. Details of numbers ofwires to Rotary Switch are given below:-

(a) UVC to rotary switch-3 wires(b) Switch to field terminal-3 wires and(c) Standby unit to rotary switch-2 wires

4.0 OPERATING SERVICE CONDITIONS

Page 46: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 46 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

The Standby Unit should function satisfactorily in the ambient temperaturerange from -5ºC to 55ºC and relative humidity 100 %. The equipment shallbe designed for fitting inside ERRU’s main box. The ERRU shall bedesigned for mounting on under-frame and shall be suitable for working ina heavily dust laden atmosphere which may also contain brake block dust.

5.0 TERMINALS

(i) DC+ and DC-(ii) F+ and F-(iii) U and V

6.0 TESTS

In this test, the speed shall be varied covering the entire working range ofspeed and corresponding DC voltage available at equipment outputterminals shall be noted. The voltage variation shall not exceed +3 Volt ofpre-set voltage i.e.116 Volt. The cut-in-speed shall also be noted in thistest. The speed shall be adjusted at 800, 1500 and 2500 rev/min. Thistest shall be done at 800, 1500 and 2500 rev/min at base load (10A and 1A for 25 kw and 4.5 kw ERRU respectively) 25%, 50% and 75% of fullloads and output voltage and field current of ERRU should be noted.

7.0 RATING

(i) 4.5 kWDC Output Voltage setting: 116 V, 19 A at 1500 rpmVoltage regulation: ± 3 Volt of set voltage(ii) 25 kWDC Output Voltage setting: 116 V, 97 A at 1500 rpmVoltage regulation: ± 3 Volt of set voltage

Page 47: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 47 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

Annexure-C(Clause 11.1.1.2-xv, 11.1.2-xiii, 11.1.3-ix and 11.1.4-ix)

Test Procedure for 600 Volts Test Compliance

This test shall be conducted on all the PCBs and modules used in UVC includingStarting circuit module of ERRU with all the power devices (IGBTs and Transistors)connected in the field circuit. The ERRU under test shall be connected withalternator and performance test shall be conducted as per Clause No. 13.5.3 ofRDSO spec. No.RDSO/PE/SPEC/AC/0013-2011 (Rev.2).

a) After the above performance test, all the ERRU Modules i.e. except ET & filtercapacitor shall be disconnected electrically from ERRU power rectifier wiringand 600 Volts DC shall be applied from an external variable DC source atDC+,DC- & across field circuit after rectification keeping F+ & F- shorted. Theexternal dc voltage source connected to the power input of all the modules shallbe varied gradually from 0 to 600 volts to observe the behaviour of SMPSstarting and overvoltage shut down voltage conditions. After reaching 600 volts,the set up shall be kept in this condition for 1-hour.

S.No External variable DC source (V) Status of OVPshall be recorded

Remarks

0 25 50 55 60 100 200 300 400 500 600

b) The filter capacitor and any other field capacitor (not mounted on PCB) ifprovided in ERRU shall be removed. 600V, 3KHz with 20% duty cycle shall besuperimposed at output of DC+ and DC- and output of ET from externalsource. The unit is kept in this condition for one hour.

.Remarks:- There shall be no sign of electrical or physical damage in any of thecomponents of modules under test during or after the test in (a) & (b)conditions above.

Page 48: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 48 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

Annexure-D(Clause 11.1.1.2-xvii and 11.1.2-xv)

Test Procedure for ERRU to Coach Indication Panel (CIP) Wire Shorting TestCompliance

Two ERRU with respective Alternators of 25KW each shall be installed onalternator test bed. Both the alternator with ERRU and CIP shall be testedfor Parallel operation test as per Clause 13.8 of RDSO Spec. No.RDSO/PE/SPEC/AC/0013-2011 (Rev.2). The Display of CIP shall also berecorded. Now all the 12 wires going from ERRU to CIP shall be shortedtogether at 800 RPM in system running condition and increase the speed to1800 rpm & 2500 rpm. Parallel operation test shall be re-conducted in thiscondition. There shall be no change in the performance of both the ERRUsexcept bypassing of battery charging current control and load sharingoperation.

A) Run the alternator with ERRU with CIP shorted at 1800 rpm at no-load

Alternator ‘A’ Alternator ‘B’Speed(rpm) Output

voltage(Volt)

Outputcurrent(Amp)

Fieldcurrent(Amp)

Output voltage(Volt)

Output current(Amp)

Fieldcurrent(Amp)

18002500

B) Run the alternator with ERRU with CIP shorted at 1800 rpm at 97A load

Alternator ‘A’ Alternator ‘B’Speed(rpm) Output

voltage(Volt)

Outputcurrent(Amp)

Field current(Amp)

Outputvoltage(Volt)

Outputcurrent(Amp)

Field current(Amp)

18002500

C) Run the alternator with ERRU with CIP shorted at 1800 rpm at 193A load

Alternator ‘A’ Alternator ‘B’Speed(rpm) Output

voltage(Volt)

Outputcurrent(Amp)

Field current(Amp)

Outputvoltage(Volt)

Outputcurrent(Amp)

Field current(Amp)

1800

Page 49: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 49 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

2500

D) Starting of Alternator with wire shorted

Alternator ‘A’ Alternator ‘B’Speed(rpm)

Outputvoltage(Volt)

Outputcurrent(Amp)

Field current(Amp)

Outputvoltage(Volt)

Outputcurrent(Amp)

Field current(Amp)

18002500

E) Starting of Alternator with wire shorted & earthed

Alternator ‘A’ Alternator ‘B’Speed(rpm) Output

voltage(Volt)

Outputcurrent(Amp)

Field current(Amp)

Outputvoltage(Volt)

Outputcurrent(Amp)

Field current(Amp)

18002500

------------------

Page 50: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 50 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

Annexure-E(Clause no. 11.1.1.2-xix and 11.1.2-xvii)

Procedure for Battery charging hall effect sensor wire removal/shorting test

The ERRU with CIP shall be tested for performance test as Clause 13.8 of RDSOSpec. No. RDSO/PE/SPEC/AC/0013-2011 (Rev.2).

The above test shall be done in following steps as under:

a. All the wires from CIP to Battery current sensor shall be shorted together andthe performance test shall be performed in this condition. The ERRU shallwork normally after shorting of the wires except no battery current control ispresent.

b. After ‘a’ above, positive supply wire of battery current sensor shall be openedand the performance test shall be performed in this condition. The ERRUshall work normally after opening of the wires except no battery currentcontrol is present.

c. After ‘b’ above, sensor output wire of battery current sensor shall be openedand the performance test shall be performed in this condition. The ERRU shallwork normally after opening of the wires except no battery current control ispresent.

d. After ‘c’ above, negative supply wire of battery current sensor shall be openedand the above test shall be performed in this condition. The ERRU shall worknormally after opening of the wires except no battery current control ispresent.

At the end of above, all the tests the data shall be downloaded in all conditions fromUVC as well as from CIP by using commercially available USB Pen drive. Theprintouts of the data shall be enclosed with the test results.

Data shall be recorded in following format

A) CIP to battery hall effect sensor +12V shall be removedAlternator ‘A’ Alternator ‘B’Speed

(rpm) Outputvoltage(Volt)

Output current(Amp)

Output voltage(Volt)

Output current(Amp)

18002500

B) CIP to battery hall effect sensor -12 V shall be removed

Page 51: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 51 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

Alternator ‘A’ Alternator ‘B’Speed(rpm) Output

voltage(Volt)

Output current(Amp)

Output voltage(Volt)

Output current(Amp)

18002500

C) Hall effect sensor +12 & -12 both shall be removedAlternator ‘A’ Alternator ‘B’Speed

(rpm) Outputvoltage(Volt)

Output current(Amp)

Output voltage(Volt)

Output current(Amp)

18002500

D) Output wire removedAlternator ‘A’ Alternator ‘B’Speed

(rpm) Outputvoltage(Volt)

Output current(Amp)

Output voltage(Volt)

Output current(Amp)

18002500

E) All wire shortedAlternator ‘A’ Alternator ‘B’Speed

(rpm) Outputvoltage(Volt)

Output current(Amp)

Output voltage(Volt)

Output current(Amp)

18002500

------------------

Page 52: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 52 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

Annexure-F(Clause no. 5.0)

DC+

DC-

F+

F-

Scheme for Standby circuit module and Isolation/Selection Switch

--------------------

Alternator

SeriesOVP Diode Rectifier Capacitor

Excitationtransformer UVC

Toggle switch in 4.5kW ERRU and changeover/rotary switch for25 kW ERRU in CIP. Field

Standby circuit module

Page 53: GOVERNMENT OF INDIA MINISTRY OF RAILWAY …rdso.indianrailways.gov.in/works/uploads/File/spec_001… ·  · 2012-04-10... whereas BG 110V non AC coaches are fitted with 4.5 kw brushless

Page 53 of 53 Effective fromDecember,2011

Spec. No. RDSO/PE/SPEC/AC/0013-2011(Rev-2)

Prepared by JE/Design

Checked by Director/PE&Metro

Annexure-G

LIST OF DRAWINGS

Sl.No. Description Drawing No. Size1. TERMINAL ARRANGEMENT OF

25KW ERRURDSO/PE/SK/AC/0011-2000(Rev.-0)

A4

2. TERMINAL ARRANGEMENT OF4.5KW ERRU

RDSO/PE/SK/AC/0012-2012(Rev.-1)

A4

3. HEAT SINK FOR POWERDEVICES OF 25KW ERRU

RDSO/PE/SK/AC/0013-2000(Rev-0)

A4

4. HEAT SINK FOR POWERDEVICES OF 4.5KW ERRU

RDSO/PE/SK/AC/0014-2000(Rev-0)

A4

5. LAYOUT OF 25KW ERRU RDSO/PE/SK/AC/0015-2000(Rev.-0)

A4

6. LAYOUT OF 4.5KW ERRU RDSO/PE/SK/AC/0016-2000(Rev.-0)

A4

7. UVC BOX FOR ERRU25KW/18KW

RDSO/PE/SK/AC/0017-2000(Rev.-0)

A4

8. MOUNTING ARRANGEMENTOF COACH INDICATIONPANEL FOR 25 KW ERRU

RDSO/PE/SK/AC/0059-2012(Rev-1)

A4

9. ELECTRONIC RECTIFIERREGULATOR UNIT (ERRU)FOR 25 KW ALTERNATOR

RDSO/PE/SK/AC/0060-2011(Rev.1)

A4

10. AC COACH WIRING FOR ERRU& DISPLAY UNIT

RDSO/PE/SK/AC/0061- 2003(Rev-0)

A2

11. RECTIFIER CUM REGULATINGUNIT FOR 110V, BRUSHLESSALTERNATOR

SKEL 2260/A Alt.-1 A4

12. TERMINAL ARRANGEMENT SKEL-3549 A1