green campus feasibility study for korea university - mwftruniversity(seoul) latitude : 37.5846...
TRANSCRIPT
![Page 1: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/1.jpg)
Green Campus Feasibility Study for Korea University
Hyun Wook KimKorea University
Yong Tack Oh Korea University of Technology and Education
25 Jan 2013
![Page 2: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/2.jpg)
Goal and Scope
Goal
Estimation of the grid electricity cost for renewable
energy penetration to college campuses
Scope
HOMER simulation by estimated load profile
Selection of most effective renewable system
configuration
Calculation of the portion of the renewables
Sensitivity analysis on Grid Electricity Price
Additionally, capital cost of the renewable sources
2
![Page 3: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/3.jpg)
Campus Load Profile
Available data: Real time measurement and
display of the Campus
Average Power Demand = 10,435 kW
Peak Power Demand = 15,637 kW
11:00 pm Jan 24, 2013 Ref) http://kugc.korea.ac.kr/
3
![Page 4: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/4.jpg)
Campus Load Profile
4
![Page 5: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/5.jpg)
Site Information
Location:
Main campus of Korea
University (Seoul)
Latitude : 37.5846
Longitude : 127.02538
SWERA:
Solar & Wind data
5
![Page 6: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/6.jpg)
HOMER Input for Solar Radiation
Solar data
6
![Page 7: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/7.jpg)
HOMER Input for Wind Speed
Wind data
7
![Page 8: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/8.jpg)
HOMER Input for Grid
Grid power price : $0.8/kWh
Sellback rate : $0.25/kWh
Ref) 전기요금, 2013, 한국전력
Ref) 신재생에너지이용 발전전력의 기준가격 지침, 2010, 지식경제부
![Page 9: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/9.jpg)
HOMER Input for Cost
Capital + O&M costs
Photovoltaic $5000 /kW
Wind $8000 /kW
Battery $400 /kW
Fuel Cell (Electrolyzer + Hydrogen Tank) $8000 /kW
Converter $0 /kW
Sensitivity Analysis values
Grid power price : 0.4 0.8 1.0 2.0 3.0 4.0 5.0
[$/kWh]
cf ) Converter costs are included with the sources
9
![Page 10: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/10.jpg)
Optimal Configuration
Grid alone is found to be the best
Under any and every condition
10
![Page 11: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/11.jpg)
Optimal Configuration
(optimization analysis)
11
![Page 12: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/12.jpg)
Renewable Portion
Total load
About 15 MW peak
143 MWh/day
Generator
Wind 1.5MW * 5 = 7.5MW
PV 10MW
12
![Page 13: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/13.jpg)
Basic condition
Wind Turbine
Capacity : 1.5MW * 5 = 7.5MW
Price : $8,000 /kW * 7.5MW = $ 60,000,000
Photovoltaic
Capacity : 10MW
Price : $5,000 /kW * 10MW = $ 50,000,000
cf) Sensitivity Analysis
Grid power cost 0.4 1 2 3 ($/kWh)
Wind speed 3.65 7.0 11.0 (m/s)
13
![Page 14: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/14.jpg)
Basic condition – grid price
14
![Page 15: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/15.jpg)
Condition 1
Wind Turbine
Capacity : 1.5MW * 5 = 7.5MW
Price : $4,000 /kW * 7.5MW = $ 30,000,000
Photovoltaic
Capacity : 10MW
Price : $2,500 /kW * 10MW = $ 25,000,000
cf) Sensitivity Analysis
Grid power cost 0.4 1 2 3 ($/kWh)
Wind speed 3.65 7.0 11.0 (m/s)
15
![Page 16: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/16.jpg)
Condition 1
16
![Page 17: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/17.jpg)
Condition 2
Wind Turbine
Capacity : 1.5MW * 5 = 7.5MW
Price : $4,000 /kW * 7.5MW = $ 30,000,000
Photovoltaic
Capacity : 10MW
Price : $1,000 /kW * 10MW = $ 10,000,000
cf) Sensitivity Analysis
Grid power cost 0.4 1 2 3 ($/kWh)
Wind speed 3.65 7.0 11.0 (m/s)
17
![Page 18: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/18.jpg)
Condition 2
18
![Page 19: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/19.jpg)
Condition 3 (dump case)
Wind Turbine
Capacity : 1.5MW * 5 = 7.5MW
Price : $8,000 /kW * 7.5MW = $ 60,000,000
Photovoltaic
Capacity : 10MW
Price : $100 /kW * 10MW = $ 1,000,000
cf) Sensitivity Analysis
Grid power cost 0.4 1 2 3 ($/kWh)
Wind speed 3.65 7.0 11.0 (m/s)
19
![Page 20: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/20.jpg)
Condition 3 (dump case)
20
![Page 21: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/21.jpg)
Conclusions
Unless the grid electricity price is $3.00/kWh,
installation of renewable energy sources to Korea
University is economically NOT viable (cf. the
present price = $0.4/kWh)
Government subsidy of renewable energy initial
cost and of tax credits and other benefits would
lower the barrier of renewable energy
penetration to university campuses.
Carbon Emission Penalty and Tax policy would
may further lower the barrier. (see the Conditions
1 and 2)
21
![Page 22: Green Campus Feasibility Study for Korea University - MWFTRUniversity(Seoul) Latitude : 37.5846 Longitude : 127.02538 SWERA: Solar & Wind data 5 HOMER Input for Solar Radiation Solar](https://reader035.vdocument.in/reader035/viewer/2022081620/61050e7e2adb0e2c6676c206/html5/thumbnails/22.jpg)
THANK YOU.