Green Schools 2.0for Retro-commiss ioning
Introduction of smart
technologies to facilitate RCx
AGENDA
Technology Developmenta. Control T ransformation
b.Data Storage Transformation
c. RCx Technology Development
d. Future Faci l i ty Management (FM)
e. Benef i t of Future Faci l i ty Management (FM) System
Smart Technologies on Campus / Institution Buildingsa. Repai r & Adjust ing/ F ine-Tuning
b. Modif icat ion/ Part ia l Retrof i t
Smart HVAC & Lighting System for Rooms cum Occupant Activity Detection Systema. St rategies
b. Operat ion Mode
c. Season Control St rategy
d. Chi l ler Opt imisat ion as per reserved rooms schedule
e. Advantages of Smart HVAC & L ight ing System for Rooms
Conclusion
1
2
3
4
2G r e e n S c h o o l s 2 . 0
P r o f e s s i o n a l T a l k
Technology Development
ABOUT US
3
Technology Development - Control Transformation
1) Local Control
(On/Off)2) Mimic
Panel4) A.I.
3) BMS/
CCMS
Local Control (On/Off) Mimic Panel BMS/CCMS A.I. Platform
4G r e e n S c h o o l s 2 . 0
P r o f e s s i o n a l T a l k
1) Nil 2) Log sheet 4) Cloud Data3) Data Capture
& Storage
By Manual Data Log
Data Capture & Computer
Storage
Cloud Data [Source: https://inno.emsd.gov.hk/en/it-wish-list/index_id_238.html
https://inno.emsd.gov.hk/tc/it-solutions/index_id_52.html]5
Technology Development - Data Storage Transformation
G r e e n S c h o o l s 2 . 0
P r o f e s s i o n a l T a l k
Control Transformation
Data Storage Transformation
Future Facility Management
(FM)
6G r e e n S c h o o l s 2 . 0
P r o f e s s i o n a l T a l k
RCx Technology Development
FORESEE…
7G r e e n S c h o o l s 2 . 0
P r o f e s s i o n a l T a l k
Future Facility Management (FM)
Predict the trend for further
corrective and preventive action
Monitoring and analysing the
performance of the system
through visualisation from BMS
Extract equipment information/data
through cloud by scanning QR code
Receive pop-up Fault Signal through
Email or mobile devices
Use mobile phone/ tablet for report the
status of equipment/ control the
equipment
8G r e e n S c h o o l s 2 . 0
P r o f e s s i o n a l T a l k
Benefit of Future Facility Management (FM) System
Performance Visualisation
Comprehensive Workflow
Management PlatformStreamline Reporting & Monitoring Process
(Immediate knowing the status)
Off-site Analytic & Diagnosis
User-friendly Interface
Source: https://www.emsd.gov.hk/filemanager/en/content_1148/HVAC_Fault_Reporting_EN.mp4
6D BIM
6D BIM
Campus interactive learning (A.I.)
ABOUT US
9
Smart Technologies on Campus / Institution Buildings
10G r e e n S c h o o l s 2 . 0
P r o f e s s i o n a l T a l k
Smart Technologies on Campus / Institution Buildings
Smart HVAC System & Lighting System
Occupant activity detection system
(OADC)
Wireless door lock and ID card-key
system
Tablets and mobile apps devices
Attendance tracking system
(counterchecking system)
Auto supply and demand forecasting
and adjustment control system
11G r e e n S c h o o l s 2 . 0
P r o f e s s i o n a l T a l k
Smart Technologies on Campus / Institution Buildings
Auto/Manual supply and demand
forecasting and adjustment control
Detection/Control Devices
Occupant activity detection system (Auto)
Wireless door lock and ID card-key system (Auto)
Tablets and mobile apps devices (Manual)
Response Devices
VSD for AHU/FCU
T CHW control for floor branches
Auto-reset set-point strategy
for vacant rooms
Auto-standby / auto-partial shut down
strategy for vacant rooms
Inter-operable and detection
between HVAV, lighting and
small power appliances
With photo / daylight sensor for
perimeter zone lighting control
Hz
T
TSPACE SP CO2SPv
v
HVAC ELE
Perimeter
Interior
12G r e e n S c h o o l s 2 . 0
P r o f e s s i o n a l T a l k
Smart Technologies on Campus / Institution Buildings
Tablets and mobile
apps
Wireless door lock and ID
card-key system
Facilities booking system
Campus map
RFID/QR Code
• Library books
• Portable instrumentation
• NB / tablets
•……
Detection/Control Devices
Campus Information Database
Facial recognition
Central Processing System
13G r e e n S c h o o l s 2 . 0
P r o f e s s i o n a l T a l k
Repair & Adjusting/ Fine-Tuning
Auto supply and demand forecasting
and adjustment control
Auto-reset set-point strategy
Auto-standby / auto-partial shut down strategy
For Vacant
Rooms
For Cool
Season
For Non-Peak
Period
(Weekend,
Sem-break)
14G r e e n S c h o o l s 2 . 0
P r o f e s s i o n a l T a l k
Modification/ Partial Retrofit
Indoor AC unit with VSD FCU and ON/OFF adjustable control
valve
Photo / daylight sensor
window
doorFAUs
corridorCHWS and CHWR floor branch pipe
T
Thermal & audio sensor
Wireless door lock and ID card-key system
T chilled water modulating control unit
Perimeter zone
interior zone
Photo / daylight sensor
corridor
Smart & Dimmable lighting
system control by Tablets/Apps
Smart lighting system control
by Tablets/Apps
Photo / daylight sensor with lighting
dimmer control function for
perimeter zone lighting control
Wireless door lock and ID
card-key systemT CHW control for floor
branches
VSD for AHU/FCU
Occupant activity
detection system
Tablets and mobile apps
devices
Inter-operable and detection
between HVAC, lighting and
small power appliances
Smart HVAC & Lighting System for Rooms cum Occupant Activity Detection System
ABOUT US
15
16G r e e n S c h o o l s 2 . 0
P r o f e s s i o n a l T a l k
Strategies
1. Auto-reset set-point strategy
for Vacant rooms
2. Auto-standby / auto-partial
shut down strategy
For Vacant
Rooms
3. Inter-operable and detection
between HVAC, lighting and
small power appliances
Occupied
Rooms
For Vacant
RoomsOccupied
Rooms
For Vacant
RoomsOccupied
Rooms
4. Chiller Optimisation as per reserved rooms schedule
A B
C
17G r e e n S c h o o l s 2 . 0
P r o f e s s i o n a l T a l k
Operation Mode
Occupant Activity Detection System
Mode of Operation
Name of Sensor “Occupancy” Mode “Standby” Mode “Sleep” Mode
Motion Sensor
Any two sensors receive signal “H”
Receive signal “L” Receive signal “0”
Thermal SensorEither Thermal Sensor or CO2
Sensor receives signal “L”
Receive signal “0”
CO2 Sensor Receive signal “L”
Audio Sensor Receive signal “L” Receive signal “L”
1. Determine the mode of operation
2. Countercheck the appointment schedule with the operation mode
Reserved
Occupancy Standby Sleep
Vacant Reserved
Occupancy Standby
Shut-down
Off
20:00 8:008:00
Appointment schedule
Operation Mode
18G r e e n S c h o o l s 2 . 0
P r o f e s s i o n a l T a l k
Season Control Strategy
Operation Parameter Occupancy Standby Sleep Off
* Space temperature setpoint 24-26°C 26-27°C 27°C Floating
Lighting Normal On Light Level as 50% of
rated by 5 mins.
/Normal Off
Normal Off Normal Off
PC Computer /Projector Normal On
/ Manual Off
Normal Off/ Manual On Normal Off Normal Off
Air-conditioners & fan Normal On Low Low>26 / Normal Off Normal Off
**Fresh air fan Max.>800ppm / Min. Min. Normal Off Normal Off
*** Chilled Water Control valve Normal On>24°C /
Min.
Min.
/ Normal Close<25°C
Min.>26°C
/Normal Close
Normal Close
* For Dry-Bulb Temperature >24°C
** For the subscript, it describes the condition of the environment (i.e. Max>800ppm means turn to maximum level if the CO2 level is >800ppm).
*** For the subscript, it describes the condition of the environment (i.e. Normal On>24°C means normal on if the temperature is >24°C).
Summer mode for different operation mode
19G r e e n S c h o o l s 2 . 0
P r o f e s s i o n a l T a l k
Season Control Strategy
Operation Parameter Occupancy Standby Sleep Off
* Space temperature setpoint 20-21°C Floating Floating Floating
Lighting Normal On Light Level as 50% of
rated by 5 mins. /Normal
Off
Normal Off Normal Off
PC Computer /Projector Normal On
/ Manual Off
Normal Off/ Manual On Normal Off Normal Off
Air-conditioners & fan Normal On Normal Off Normal Off Normal Off
**Fresh air fan Max.>800ppm / Min. Min. Normal Off Normal Off
*** Chilled Water Control valve Normal On>24°C /
Min. >21°C
Normal Close Normal Close Normal Close
* For Dry-Bulb Temperature <22°C
** For the subscript, it describes the condition of the environment (i.e. Max>800ppm means turn to maximum level if the CO2 level is >800ppm).
*** For the subscript, it describes the condition of the environment (i.e. Normal On>24°C means normal on if the temperature is >24°C).
Winter mode for different operation mode
20G r e e n S c h o o l s 2 . 0
P r o f e s s i o n a l T a l k
Chiller Optimisation as per reserved rooms schedule
TDB
Co
olin
g lo
ad
/sq
m
22C
Chiller plant A
COPA
3 chillers2 chillers
Chiller plant B
COPB
2 chillers
1. Determine the cooling load
by the reserved rooms schedule
2. Determine the optimal efficiency
21G r e e n S c h o o l s 2 . 0
P r o f e s s i o n a l T a l k
Advantages of Smart HVAC & Lighting System for Rooms
Connectivity, Mobility,
Availability & AccountabilityPhysical
Security
Energy Efficiency
ABOUT US
22
Conclusion
23G r e e n S c h o o l s 2 . 0
P r o f e s s i o n a l T a l k
Conclusion
Technology Development
•Control Transformation
•Data Storage Transformation
• Future Facility Management (FM)
• Benefit of Future Facility Management (FM)
Smart Technologies on
Campus / Institution Buildings
•Detection/Control Devices
• Response Devices
• Repair & Adjusting/ Fine-Tuning
•Modification/ Partial Retrofit
Smart HVAC & lighting system for rooms cum
occupant activity detection system
• Strategies
•Operation Mode
• Season Control Strategy
•Chiller Optimisation as per reserved rooms schedule
•Advantages of smart HVAC & lightingsystem for rooms
Green Schools 2.0 for Retro-commissioning
24G r e e n S c h o o l s 2 . 0
P r o f e s s i o n a l T a l k
REGISTER NOW FOR FREE
In you are interested, please refer to our website for
details and registration:
http://greenschools2.hkgbc.org.hk/
Engagement Meeting (Pre-recorded video)
Induction Talks (Pre-recorded video)
Professional Talks
Workshop cum Seminars
Green Schools 2.0fo r Ret ro-commiss ion ing
25G r e e n S c h o o l s 2 . 0
P r o f e s s i o n a l T a l k
EMSD RCxResources Centre
HKGBC RCxTraining and Registration Scheme
Enquiry: 3994 8818
Energy Saving Charter & 4T Charter Schemes
Utilities Funding Scheme- RCx
26G r e e n S c h o o l s 2 . 0
P r o f e s s i o n a l T a l k
Electricity
Supplier
Funding
Name
HKECLP
Eco-Building Fund Smart Power Building Fund
Energy Efficiency
Projects
•Subsidised amount is depended on the types and scale of projects and
determined based on expenditure, saving and duration of projects but
subject to a cap
•Disbursed on a reimbursement basis
•Provide subsidies for energy-saving improvement works of:-
Retrofitting
RCx
Smart building technologies
Subsidy
Brief