DESCRIPTION
Grid-Automation-ppt-P741TRANSCRIPT
GRID
MiCOM Alstom P740 Numerical Busbar Protection
Presentation
Feb 2, 2011
P740 Presentation - P 2
MiCOM Alstom P740Numerical Busbar Protection
MiCOM Alstom P740 is: Fast & Constant
Constant sub-cycle tripping time (13 ms typical)
Flexible & Easy to use Centralised or Distributed solution Dynamic substation replica processing Dynamic substation monitoring tool PSL (Programmable Scheme Logic)
Selective Phase segregated low impedance solution
Secure• Differential algorithms supervised by multiple
criteria (CT supervision, Biased Check Zone, etc…)
• CT saturation detection (< 2ms)• Delayed tripping algorithm with CT saturation • Dead zone protection & 50 BF protection
P740 Presentation - P 3
Busbar Protectio
nOvercurr
ent Protectio
n
Commissioning Tools
CB & Isolator
Supervision
Measurements
Disturbance
Recorder
Event & Fault
recordsProgrammab
le Scheme Logic
Dead Zone
Protection
Continuous monitoring
CT & VT Supervisi
on
MiCOM Alstom P740 Numerical Bus Relay Features Check
Zone
Function Keys
CB Failure Protection
Tricolour LEDs
P740 Presentation - P 4
MiCOM Alstom P740 Architecture
A MiCOM Alstom P740 scheme supports a maximum of:
−
No maximum of Central Units
−
1 Central Unit:
− up to 28 Peripheral Units,
− up to 8 zones (with or without SDEF),
− up to 28 feeders.
Architecture can be either distributed, centralised or mixed
Maximum configuration
P740 Presentation - P 5
MiCOM Alstom P740 Numerical Busbar Protection
HardwareHardware
P740 Presentation - P 6
MiCOM Alstom P740 Architecture
The MiCOM Alstom P740 scheme is made of:
− P741 - Central Unit (CU), • Gathers and processes the measurements from the
PUs with Ethernet board slot, hotkeys & function keys and tricolour LEDs
• (comprises all differential protection algorithms)
− P742 - Peripheral Unit (PU), • Measures and trips with hotkeys• (CT saturation detection, local non-directional
overcurrent, local circuit breaker failure protection and Dead Zone protection)
− P743 - Peripheral Unit (PU),• same as P742 but with additional opto inputs, relay
output and Ethernet board slot, hotkeys & function keys and tricolour LEDs
P740 Presentation - P 7
Numerical Busbar Protection P740
• 8 Optically isolated logic inputs*− Plus 16 virtual inputs
• 8 Relay ouputs* (Plus 16 virtual outputs)
• Optional Irig-B board (GPS Time Sync)
• Up to 7 Communication boards− 4 Peripheral Units per communication board
• 1 Main Processor board & 1 Coprocessor board
− 1p DSP-TMS320C-32 bits-150 Mhz & 1p DSP-TMS320C-16 bits-100 Mhz
• LEDs (18 three-coloured programmable LEDs)
• 10 Programmable Function Keys & 2 Hotkeys− Drives 10 associated ddb signals in PSL
• Back lit liquid crystal display
• Ethernet board slot (IEC 61850-8-1 protocol in 2006)
• * Extended Opto inputs / outputs possible using a P742 or a P743
Central Unit Hardware - Size 19 inches - 4U
P741 Central Unit
P740 Presentation - P 8
• Logic inputs: 16 for P742 (24 for P743)− Universal Opto inputs - programmable battery voltages
• Relay outputs: 8 for P742 (16 for P743)
• Current inputs : 3 phase + 1 residual current inputs− Dual rated current inputs (1/5A)
• Voltage Transformers: 80 - 140Vac ph-ph Soon used...
• 1 Main board - 1p DSP-TMS320C-32 bits-150 Mhz
• 1 Coprocessor board - 1p DSP-TMS320C-16 bits-100 Mhz
• 2 Hotkeys
• NO Ethernet board slot (NO IEC 61850-8-1 protocol)
• 12 LEDs (Red)
• Back lit liquid crystal display
Numerical Busbar Protection P742
Peripheral Unit‘s Hardware - Size 8 inches - 4U
P742 & P743 Peripheral Units
P740 Presentation - P 9
Numerical Busbar Protection P743
Peripheral Unit‘s Hardware - Size 12 inches - 4U• Logic inputs: 24 for P743 (16 for P742)
− Universal Opto inputs - programmable battery voltages
• Relay outputs: 16 for P743 (8 for P742)
• Current inputs : 3 ph + 1 residual current inputs− Dual rated current inputs (1/5A)
• Voltage Transformers: 80 - 140Vac ph-ph Soon used...
• 1 Main board - 1p DSP-TMS320C-32 bits-150 Mhz
• 1 Coprocessor board - 1p DSP-TMS320C-16 bits-100 Mhz
• Ethernet board slot (IEC 61850-8-1 protocol in 2006)
• 22 LEDs (18 three-coloured programmable LEDs)
• 10 Programmable Function Keys & 2 Hotkeys− Drives 10 associated ddb signals in PSL
• Back lit liquid crystal display
P742 & P743 Peripheral Units
P740 Presentation - P 10
MiCOM Alstom P740Central Unit
Main Scheme Differential ElementsMain Scheme Differential Elements
Check Zone Differential ElementCheck Zone Differential Element
Communication MasterCommunication Master
Scheme Stability and Signal ProcessingScheme Stability and Signal Processing
Commissioning FacilitiesCommissioning Facilities
P741
CT Supervision (Circuitry Fault)CT Supervision (Circuitry Fault)
P740 Presentation - P 11
MiCOM Alstom P740Central Unit
Phase segregation +
Sensitive Differential Earth Fault
ABCN
SDEF sensitivity iscontrolled by phase
elements
ibiasph
idiffph
ibiasN
idiffN
Check Zone biased element
[ iinfeed + ioutfeed ]
Main Differential ElementsMain Differential Elements
Optional Voltage criteriaSoon...
Vx< or Vo> iT
iD
P740 Presentation - P 12
MiCOM Alstom P740 Central Unit
Sampling control by saturation detectors
(in Peripheral Unit)
Algorithm tripping decision before CTs saturation
(Max 2 ms)
t
Biased characteristic against differential errors due
to different CTs responses in transient behaviour
(before saturation)
iT
iD
Multiple Confirmation Tripping Criteria
&1
4
Circuitry fault detection
Stability and Signal ProcessingStability and Signal Processing
P740 Presentation - P 13
MiCOM Alstom P740 Central Unit: Trip Logic
CU Tripping Logic decisions (for Zone and Check Zone):
• “Instantaneous Algorithm”:If 2 consecutive samples verify tripping condition
(are above (ID>2) and k x Ibias) AND no CT Saturation detected
• “Delayed Algorithm”*:If all samples verify tripping condition (are all
above (ID>2) and k x IBias) during 5.8 ms AND at least one sample does not verify it in the previous 3.3 ms AND at least one sample verified it in the previous 4,2 ms (i.e. an internal fault is detected if a differential current is detected on 2 consecutive half-periods)
*: never affected by the CT saturation blocking information. This logic is used especially for evolving fault (external to internal bus fault)
P740 Presentation - P 14
MiCOM Alstom P740 Central Unit
Central loading of the topology and setting
software(specific tool)
Up to 4 separate setting groups
Local and remote rear communications
(Courier, IEC 103 via Kitz 2740 (and IEC 61850
soon...))
FacilitiesFacilities
P740 Presentation - P 15
MiCOM Alstom P740 Numerical Busbar Protection
Peripheral UnitsPeripheral Units
P740 Presentation - P 16
MiCOM Alstom P740 Peripheral Units
FacilitiesFacilities
Local AcquisitionLocal Acquisition
Local signal processing (Amplitude and Angle values)Local signal processing (Amplitude and Angle values)
Continuous supervisionContinuous supervision
Saturation detectionSaturation detection
P742/P743
Local ProtectionsLocal Protections
P740 Presentation - P 17
MiCOM Alstom P740 Peripheral Unit
Fault analysisevents, fault & disturbance
records
Programmable Scheme Logic(PSL)
&
& t0
Communication to CU(optical fibre)
PUPUPUPUPU
CU
Up to 4 setting groups
Facilities
CT mixing features
P740 Presentation - P 18
MiCOM Alstom P740Peripheral Units
Current acquisition
Digitalconversion
Sampling 2,400 Hz
A N
Isolatorsand CB statusacquisition
+ supervision
CT supervision(3xIo - IN ) & ID>1 & I
Zero sequencecurrent calculation and other thresholds (PU)
Local AcquisitionLocal Acquisition
VT supervision
(Soon…)
P740 Presentation - P 19
MiCOM Alstom P740Peripheral Units
I > 2 IN > 2
High set O/C detection=
Fast external fault detection
CT magnetic flux calculation
Ø = R idt + ØM
i calculation CT saturation
detection
Instantaneous Signal ProcessingInstantaneous Signal Processing
Optional Voltage criteriaSoon...
Vx< or Vo>
P740 Presentation - P 20
Peripheral UnitLocal Protection
O/C and E/F protections(IDMT or Definite time)
T
t
Dead zone elementPhase & Neutral
Dead ZoneDead Zone
Local ProtectionsLocal Protections
Breaker failure element (1/pole)
with local single pole re-trip
3 x 50 BF3 x 50 BF
P740 Presentation - P 21
MiCOM Alstom P740 Numerical Busbar Protection
SoftwareSoftware
P740 Presentation - P 22
MiCOM Alstom P740Features
Differential protection
• Check zone element with bias characteristic• Circuitry fault criterion with slope : alarm when Idiff is
greater than ID>1 and greater than slope k1.Ibias• One set of parameters for check zone element and an
other one for all the zones (ID>2, k2, IDN>2, kN)• Single setting for IbiasPh> and circuitry fault
supervision (ID>1, IDN>1, and timers) for all zones and check zone elements
• Slopes start from 0 (Is = 0)
P740 Presentation - P 23
MiCOM Alstom P740Excel Spreadsheet tool
P740 Presentation - P 24
MiCOM Alstom P740Excel Spreadsheet tool
P740 Presentation - P 25
MiCOM Alstom P740 Trip Logic in CU
CU Tripping Logic decisions (for Zone and Check Zone):
“Instantaneous Algorithm”:If 2 consecutive samples verify tripping condition (are
above (ID>2) and k x Ibias) AND no CT Saturation detected
“Delayed Algorithm”* (patented algorithm):If all samples verify tripping condition (are all above
(ID>2) and k x IBias) during 5.8 ms AND at least one sample does not verify it in the previous 3.3 ms AND at least one sample verified it in the previous 4,2 ms (i.e. an internal fault is detected if a differential current is detected on 2 consecutive half-periods (20 (60 Hz) or 24 (50 Hz) samples))
*: never affected by the CT saturation blocking information. This logic is used especially for evolving fault (external to internal bus fault)
P740 Presentation - P 26
MiCOM Alstom P740Features
Protection− Dead zone threshold independent of
differential element parameters and to set separately in each PU
− For Single and Phase to Phase Faults with independent time delay
P740 Presentation - P 27
MiCOM Alstom P740 Rear communication
Rear CommunicationRear Communication
P740 Presentation - P 28
P740Rear communication Phase 1
Idiff (A,B,C) + Ibias (A,B,C) + Inputs + Outputs + Events + Disturbance Records…P741
IEC 103 / Fibre/RS 485/RS 232
P743 Kbus/courier Port 3
Kitz274
P742 Per PU connection: I (A,B,C) + Inputs + Outputs + Events + Disturbance Records…
P742
P742
P740 Presentation - P 29
P740Rear communication
P740 Presentation - P 30
MiCOM Alstom P740 Numerical Busbar Protection
OptionsOptions
P740 Presentation - P 31
P740Busbar options
P740 Presentation - P 32
MiCOM Alstom P740 Features
Differential protection− Self-reset of circuitry fault blocking after a
settable delay under normal conditions (option) alarm and blocking zone independently latchable:
• Option to reset automatically or latch independently the Circuitry Fault Alarm
• Option to unblock automatically or block definitively the faulty zone under circuitry fault conditions
− Independent setting for Check Zone and Zone Differential Elements
Independent 87B Blocking Signal in case of circuitry fault or CU-PU communication error or failed PU
P740 Presentation - P 33
P740Busbar options
P740 Presentation - P 34
P740Busbar options
Check Zone Circuitry Fault Mode− Blocking Latched :
• The CZ is blocked and latched until manual reset (and no more circuitry fault) via front panel, opto input, hot key or function key,
• The CZ alarm is latched until manual reset (and no more circuitry fault) via front panel, opto input, hot key or function key.
− Alarm Latched :• The CZ is blocked until automatic reset (when
no more circuitry fault) but• The CZ alarm is latched until manual reset (and
no more circuitry fault) via front panel, opto input, hot key or function key.
P740 Presentation - P 35
P740Busbar options
Check Zone Circuitry Fault Mode− Self-Reset :
• The CZ is blocked until automatic reset (when no more circuitry fault) and
• The CZ alarm is reset automatically at the same time.
− Alarm & No Block :• The CZ is not blocked but• The alarm is latched until manual reset (and no
more circuitry fault) via front panel, opto input, hot key or function key.
− AlarmSR&No Block :• The CZ is not blocked and• The CZ alarm is reset automatically (when no
more circuitry fault)
P740 Presentation - P 36
P740Busbar options
P740 Presentation - P 37
P740Busbar options
Circuitry Fault Mode− Blocking Latched :
• The Zone X is blocked and latched until manual reset (and no more circuitry fault) via front panel, opto input, hot key or function key,
• The Zone X alarm is latched until manual reset (and no more circuitry fault) via front panel, opto input, hot key or function key.
− Alarm Latched :• The Zone X is blocked until automatic reset (when no more
circuitry fault) but• The Zone X alarm is latched until manual reset (and no more
circuitry fault) via front panel, opto input, hot key or function key.
− Self-Reset :• The Zone X is blocked until automatic reset (when no more
circuitry fault) and• The Zone X alarm is reset automatically at the same time.
P740 Presentation - P 38
P740Busbar options
P740 Presentation - P 39
P740Busbar options
Circuitry Blocking Mode− 3phase Blocking:
• A circuitry fault on one phase blocks the three phases
− Blocking / phase:• A circuitry fault on one phase blocks only the
faulty phase• A internal fault on any of the two other phases
will be cleared.
P740 Presentation - P 40
P740Busbar options
P740 Presentation - P 41
P740Busbar options
Check Zone PU error Mode− Blocking Latched :
• The CZ is blocked and latched until manual reset via front panel, opto input, hot key or function key,
• The CZ alarm is latched until manual reset via front panel, opto input, hot key or function key.
− Alarm Latched :• The CZ is blocked until automatic reset (when
the PU communication reappears) but• The CZ alarm is latched until manual reset via
front panel, opto input, hot key or function key.
P740 Presentation - P 42
P740Busbar options
Check Zone PU error Mode− Self-Reset :
• The CZ is blocked until automatic reset (when the PU communication reappears) and
• The CZ alarm is reset automatically at the same time.
− Alarm & No Block :• The CZ is not blocked but• The alarm is latched until manual reset via front
panel, opto input, hot key or function key.− AlarmSR&No Block :
• The CZ is not blocked and• The CZ alarm is reset automatically (when the
PU communication reappears)
P740 Presentation - P 43
P740Busbar options
P740 Presentation - P 44
P740Busbar options
PU error Mode− Blocking Latched :
• The Zone X is blocked and latched until manual reset via front panel, opto input, hot key or function key,
• The Zone X alarm is latched until manual reset via front panel, opto input, hot key or function key.
− Alarm Latched :• The Zone X is blocked until automatic reset (when the
PU communication reappears) but• The Zone X alarm is latched until manual reset via front
panel, opto input, hot key or function key.− Self-Reset :
• The Zone X is blocked until automatic reset (when the PU communication reappears) and
• The Zone X alarm is reset automatically at the same time.
P740 Presentation - P 45
Virtual I/OVirtual I/O
P740 Presentation - P 46
Virtual Inputs/Outputs
16 Virtual Outputs can be used to send information from a PU to the CU− PU->CU Virtual Signal N°n in the CU is a logical OR of the PU->CU Virtual Signals N°n in the PUs
16 Virtual Outputs can be used to send information from the CU to the PUs− CU->PU Virtual Signal N°n in the PU is the CU->PU Virtual Signal N°n in the CU
P74xFeeder
AnyP74x
P741
CU & PU - Virtual Inputs / Outputs
SchemePeripheral Units
Fixed information exchanged between the CU & the PUs: (Busbar Zone 1 … 8 ON/OFF, Busbar Trip 1 … 8 )
P740 Presentation - P 47
DisturbanceDisturbanceRecordsRecords
P740 Presentation - P 48
Disturbance Recorder: Default Setting in CU
MiCOM Alstom P740 Numerical Bus RelayFeature Enhancement
P740 Presentation - P 49
Disturbance Recorder: Default Setting in PU
MiCOM Alstom P740 Numerical Bus RelayFeature Enhancement
P740 Presentation - P 50
MiCOM Alstom P740Numerical Busbar Protection
MaintenanceMaintenance
P740 Presentation - P 51
Maintenance ModesCentral Unit
2 Levels of maintenance in the CU:− 87BB trip blocked but 50BF (back trip) enable
(level 1)− 87BB and 50BF trip blocked (level 2)
It’s a per zone selection
Selectable via front panel, hotkey, function key and opto-coupler
Additional maintenance features selectable via hotkey, function key or opto-coupler:− All the protections (87BB, Dead Zone, General
50BF, Local 50BF, O/C) disabled− 87BB disable but 50BF (back trip) enable for all
zones
P740 Presentation - P 52
2 distinct maintenance levels in the PU:− Local 50BF Trip Blocked (maintenance on an
other bay protection)− Overhaul (maintenance on the PU)
Selectable via front panel, hotkey, function key and opto-coupler
Maintenance ModesPeripheral Units
P740 Presentation - P 53
MiCOM Alstom P740 Numerical Busbar Protection
ToolsTools
P740 Presentation - P 54
MonitoringDynamic Synoptic from CU
P740 Presentation - P 55
MonitoringDynamic Synoptic from PU
P740 Presentation - P 56
MiCOM Alstom P740 Numerical Busbar Protection
ConclusionConclusion
P740 Presentation - P 57
MiCOM Alstom P740Why ?
This product in the MiCOM range offers:This product in the MiCOM range offers:−a complete communicating MiCOM solution
• Courier, IEC 103 and IEC 61850-8-1 (end of 2006)−a new technology
• Dynamic topology• Fast CT saturation detection
−a greater reliability• Constant tripping time independent of type of fault
and number of feeders with or without Voltage criteria• Plant monitoring (CT, VT, CB & Isolator status)• MiCOM Dynamic Synoptic
−a more competitive solution with the reduction of associated costs (engineering and hardwiring)