ground fault protection isolated neutral
TRANSCRIPT
-
7/28/2019 Ground Fault Protection Isolated Neutral
1/18
1
Power System Protection
systems
-
7/28/2019 Ground Fault Protection Isolated Neutral
2/18
2
Professor at Norwegian Univ. Science and
Technology Dept. Electrical Engineering Power system transients and protection
g vo age engneerng, s ress cacua ons
Recent focus on Power Transformers
Sabbatical at MTU
-
7/28/2019 Ground Fault Protection Isolated Neutral
3/18
3
Solid vs. isolated neutral
+ No over-voltages in faultsituations
- Undefined voltages toground. Sqrt(3) rise
- g au curren
+ Easy fault detection
+ Ground faults ersist
.MOV dimensioning.
+ Low fault current
Fast trip and reclosing
- Poor power quality
- Difficult faultdetection/location
+ Can continue to o erate- Extra stress
during ground fault.Increased power quality
down/broken conductors
-
7/28/2019 Ground Fault Protection Isolated Neutral
4/18
4
Why is the fault current low insoate neutra systems
capacitances. High return impedance.
The most common fault
Often temporary rees ranc es,
snow/ice/wind,
Birds
Simultaneous faults.
3 V
1 2 03
f
fZ Z Z R
-
7/28/2019 Ground Fault Protection Isolated Neutral
5/18
5
In Norway DyDy
LV system 230 V IT MV system 12-24 kV
-
The 230 V IT system is gradually replaced by400 V TN solidl rounded due to risk ofundetected ground faults, double ground faults,and lower loss in a 400 V TN system.
n ; requremen s o e ec a groun au Power quality is very important to the industry
-
7/28/2019 Ground Fault Protection Isolated Neutral
6/18
6
CurrentI0: SumIa,Ib,Ic
Summing the current numerically
I0Loweraccuracy
Residual connection
Summation transformer
3I0
differences
3I0
(Toroidal/Rogowski coil)
a, ,
c
Open delta 3U0
Neutral point (isolated or resonance earth)U0
-
7/28/2019 Ground Fault Protection Isolated Neutral
7/18
7
Normal to only consider ground capacitance
symmetrical system,
ignore conductive line charging no voltage drop along line
imbalance in loads canceled b D-cou led transformers
Fault current mainly returns in the two healthy phases
Fault resistance important
hVpa h = ej120VN
Vpa
h2Vpa
gff
-
7/28/2019 Ground Fault Protection Isolated Neutral
8/18
8
occurs For calculation of feeder current and volta es
capacitances can be concentrated
The volta e to round will rise for the healthphases
Easy to detect that there is a ground fault (by
looking atV0), difficult to detect where (bylooking at I0 in various feeders)
-
7/28/2019 Ground Fault Protection Isolated Neutral
9/18
9
N A
V
+If
3pa gV j CI
fg 1 3 g fj C R
V I C0
1 3 3N
g f g
V Vj C R j C
f
A
UN
Rf=Rf=0
BBefore
Line-voltages
unchanged
B After
-
7/28/2019 Ground Fault Protection Isolated Neutral
10/18
10
Same zero-sequence voltage in the entire
system; selectivity is challenging The fault is traditionally located by
sectionalizing (often manual)
Z r n rr ntv ri l n th lin :I0
If
3I0U0 constant
Rf
pos.
-
7/28/2019 Ground Fault Protection Isolated Neutral
11/18
11
From fault to zero sequence current
VpaVN
x l-x
h2Vpa
hVpa
CgxCg(l-x)
2
( ) ( ) ' ( )a N pa gI x V V j C l x
Fault locationx=dx
( ) ( ) ' ( ) ( )
3 '
b N pa g
c N pa g f
x xI x V h V j C l x I H d x
V C x x d
03 ( ) ( ) 3 ' ( ) ( )
3 ' ( ),a b c N g f
N g
I x I I I V j C l x I H d xV j C l x x d
ignore voltage drop, no load-effect
-
7/28/2019 Ground Fault Protection Isolated Neutral
12/18
12
Three radials fed by the same transformer
Fault current in the faulty feeder is the negative sumof the current in the two healthy feeders
01 1N gI V j C
02 2N gI V j C
03 01 02( )I I I
With two radials the currents are equal in size sodirectional protection is required
-
current protection becomes possible
-
7/28/2019 Ground Fault Protection Isolated Neutral
13/18
13
- Often the preferred solution
Measure zero sequence voltage and zerose uence current in each radial
Then for each radial:
01
I02
Healthyfeeder
V0 03 V0
I0nForward
rppng zoneFaulty feeder
direction
-
7/28/2019 Ground Fault Protection Isolated Neutral
14/18
14
V0>Vlim (type 59G over-voltage relay)
and in correct quadrant (3rd)? > m ype rec ona ove -curren re ay
+
67N (I0>Ilim)
52 trip-
-
7/28/2019 Ground Fault Protection Isolated Neutral
15/18
15
-22 kV
y28 mi
50 miles line in totalTotal capacitance is50 miCg [F/mi]
14 mi
8 mi
5 nF/mi assumed in
this case.
Fault current inde endent on location
cable systems.
Depends on fault resistance
2.44 54.7 A 3 kIU ,'
,max 3.0 90 A @ 042441/ ( 3 50 )f
fff g
IIR jR j mi C
-
7/28/2019 Ground Fault Protection Isolated Neutral
16/18
16
ar on o e ear au curren measure oreach radial
28 mi
22/5050/50
14 mi
8 mi8/50
-
7/28/2019 Ground Fault Protection Isolated Neutral
17/18
17
Partition of the earth fault current measured for
each radial Health lines 1&3 feed 28 + 8 arts into line 2
28/5028 mi
8 mi
36/50
8/50
50/50
-
7/28/2019 Ground Fault Protection Isolated Neutral
18/18
18
Partition of the earth fault current measured for
each radial Health lines 1&2 feed 28 + 14 arts into line 3
28/5028 mi
14 mi
14/50
8 mi
42/50