grounding[a]

Upload: anonymous-ngxdt2bx

Post on 03-Apr-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 Grounding[a]

    1/31

    Grounding of Electrical

    Systems

    NEW CODE: Grounding andBonding

    Presented ByScott Peele PE

  • 7/28/2019 Grounding[a]

    2/31

    Grounding of Electrical

    Systems Outline

    z Defining the Terms

    z Why should I Ground?

    z Types of Grounding Systems

    z Separately Derive Systemz Grounding Electrode

    z Bonding

    z Ground Fault Protection

    z Ground Reference or Signal Reference

    z Grounding for Lightning Protection

  • 7/28/2019 Grounding[a]

    3/31

    Definitions

    z Review definition as we encounter them.

    z Grounded vs Groundingz Isolated Ground

    z

    Floating Groundz Ground Loop

    z Net Current

  • 7/28/2019 Grounding[a]

    4/31

    Why am I grounding or Not?

    z Safety

    z Grounding for Fault Current Pathsz Grounding for Touch Potential (static)

    z

    Grounding for Lightning Protection SurgeArresters, TVSS (SPD)

    z Grounding for Signal Reference (RF, Data,

    static ,etc.)z Not Grounding Continuous operation

  • 7/28/2019 Grounding[a]

    5/31

    Three reasons for grounding

    FaultProtection

    Lightning

    Protection

    Signal

    Reference

  • 7/28/2019 Grounding[a]

    6/31

    Grounded vs Grounding

    z Grounded vs. grounding in an electricalsystem. Grounded system refers to a

    system where a conductor is groundedand is intended to or may carry current inthe normal operation. The neutral on a

    wye system is a prime example of agrounded conductor.

    zThe grounding conductor system is not

    intended to carry operational current in itsdesign. This path is intended to carryunwanted and fault currents for protection.

  • 7/28/2019 Grounding[a]

    7/31

    Types of AC Grounded Systems

    z Ungrounded system

    z Solidly Grounded Systemz Resistance Grounded

    z Reactance Grounded

    z Ground Fault Neutralizer

  • 7/28/2019 Grounding[a]

    8/31

    Which System to Use??

    z Safety - Who is Operating the System

    z Ground Fault Detectionz Signal Reference

    zTouch Potential (also static)

    z Available Fault Currents?

    z Operation Stability

    z System Response

  • 7/28/2019 Grounding[a]

    9/31

    Ungrounded System

    zType of system typically used on is aDelta service.

    z Some time used on a floating Wye

    z Detection System in Place

    Ground Detection by Lighting

    Zigzag Grounding Transformer

    Ground Relay Ground Fault ???

  • 7/28/2019 Grounding[a]

    10/31

    Detection Devices

  • 7/28/2019 Grounding[a]

    11/31

    Solidly Grounded System

    z Usually use in Wye systems

    z Return Fault current to trip overcurrentprotection device quickly

    z Usually better reference and safer system

    z Much better for lightning protection

    z Can be used in Corner Grounded Delta

    Problems with phase grounded re-grounded Not good on lightning protection equipment

  • 7/28/2019 Grounding[a]

    12/31

    Resistive grounded

    z Low Resistance

    Limit Fault Current

    Minimizes the damage at the fault

    Used usually with multiple sources i.e.transformers, and or generators

    z High Resistance

    Enables system operation with one phasegrounded

    Enables current to flow for detection networks

    Current is low enough so that no damage occurs

  • 7/28/2019 Grounding[a]

    13/31

    Reactance Grounding

    z Reactor connected between systemneutral and ground

    Reduces the ground fault current betweenphase and ground

    Usually higher fault current than lowresistance grounding

    Better coordination with fault currents on

    multi-grounded system. Mostly used onsystem above 5kV.

  • 7/28/2019 Grounding[a]

    14/31

    Ground-Fault Neutalizer

    z Reactor with relatively high value ofreactance.

    z Usually on system above 15kV phase toground air exposed. (overhead

    Transmission and Distribution)z May provide insulator flashover with self-

    extinguishing characteristics.

  • 7/28/2019 Grounding[a]

    15/31

    Separately Derived System

    zThe system grounding conductor for aseparately derived system shall begrounded at only one point.

    z Main system Disconnecting means for a

    main utility feed, or a step down or step uptransformer, or a generator could all beseparately derived systems.

    z When grounded it will be grounded at thenearest grounding electrode.

  • 7/28/2019 Grounding[a]

    16/31

    Grounding Electrode System and

    Grounding Electrode Conductor Part IIIz NEC 250.50 (Grounding Electrode System) 250.52 Electrodes

    Water Pipe if 10 ft. or more of metal water pipe is in contactwith the earth.

    Metal Frame of the Building or Structure where the followingmethods are used to make an earth connection: (1,2,3,4)

    Concrete-Encased Electrode in at least 2 of concretelocated within and near the bottom of a concrete foundationor footing that is in indirect contact with the earth.

    Ground Ring encircling the building or structure in directcontact with the earth

    Rod or Pipe electrode not less than 8 ft in length Plate Electrode not less than 2 square ft.

    Other Local underground systems such as piping,underground tanks and underground metal well casing NOT Permitted

    Metal underground gas piping

    Aluminum electrode

  • 7/28/2019 Grounding[a]

    17/31

  • 7/28/2019 Grounding[a]

    18/31

    Grounding Electrode System

    z Installation NEC 250.53

    This requirement clarifies that thesupplemental electrode system must beinstalled as if it were the sole groundingelectrode

    z Bonding NEC 250.53 C

    This requirement is for bonding of

    multiple electrodes.

  • 7/28/2019 Grounding[a]

    19/31

    Bonding

    z Bonding for

    Main Bonding J umper System Bonding J umper

    Electrode Bonding

    Part V Bonding

    Where necessary to ensure electrical continuityand the capacity to conduct safely and faultcurrent likely imposed.

  • 7/28/2019 Grounding[a]

    20/31

    Ground ?

    HotNeutralGround

  • 7/28/2019 Grounding[a]

    21/31

    Review Ohms Law

    Voltage = Current X Resistance

    (ohms)(Potential) (amps)

    DevelopVOLTAGE

    DevelopVOLTAGE

    BONDING

    GroundRod

    GroundRod

    Current Source Lightning

    Average current 30,000 amps

  • 7/28/2019 Grounding[a]

    22/31

    Grounding and Bonding

    Transient voltages andTransient voltages andcurrentscurrents at data port orcable connections

    Voltage Difference

  • 7/28/2019 Grounding[a]

    23/31

    Isolated Ground

    z NEC 250.146 (D) Isolated groundreceptacle (orange triangle) NEC 406.2(D)

    z NEC 250.96 (B) Isolated GroundingCircuits

    z NEC 647 Section Sensitive ElectronicEquipment.

    z NEC 647.6 Grounding.

    Technical Equipment Ground

  • 7/28/2019 Grounding[a]

    24/31

    Isolated Ground

    Isolated grounded receptacle has an isolated terminal from the yoke to the groundLug. These receptacle are usually marked with an orange triangle or all orange.

    Sub Panel

    Ground Bus

    Neutral Bus

  • 7/28/2019 Grounding[a]

    25/31

    Floating Ground

    zThe neutral on a wye system is notintentionally grounded

    z Signal conductor shielding is notintentionally grounded

    z Problem is high transient voltage orovervoltages may exist causing damage.

    z Not a good way for lightning protection

    G d L

  • 7/28/2019 Grounding[a]

    26/31

    Ground Loop

    z Grounds from two different derived systemare connected

    z Open ground loops. Grounds are notbonded properly and cause damage.

    z Ground loops cause circulating currentbetween systems and cause transformercoupling (CTs)

    z Signal reference can be compromisedcausing data errors.

    G di f Si l R f

  • 7/28/2019 Grounding[a]

    27/31

    Grounding for Signal Reference

    z Dont Burst the Bubble.

    z

    Ground on one endz Ground on both ends

    z Ground on neither end

    z Fiber Optic Best Answer

    z Optical Coupler

    D t B t th B bbl

  • 7/28/2019 Grounding[a]

    28/31

    Dont Burst the Bubble

    G d F lt I t t F ti

  • 7/28/2019 Grounding[a]

    29/31

    Ground Fault Interrupter Function

    Net Current

  • 7/28/2019 Grounding[a]

    30/31

    Net Current

    z Currents that are not apart of the normaloperation of a derive electrical system.

    All positive, negative, and zero sequencecurrents added and the resultant currentare net currents.

    Books On Grounding

  • 7/28/2019 Grounding[a]

    31/31

    Books On Grounding

    z NEC

    z IEEE Green Book 142-1991Recommended Practice for

    Grounding of Industrial and Commercial Power

    Systems Emerald Book 1100-1999 Recommended

    Practice for Powering and Grounding SensitiveElectronic Equipment

    z Industrial and Commercial Power systemHandbook