GR/PRINTO Variable area flowmeters Vortex flowmeters Flow controllers Electromagnetic flowmeters Ultrasonic flowmeters Mass flowmeters Level measuring instruments Communications engineering Engineering systems & solutions © KROHNE 08/2000 7.02343.21.00 UFM 800 W, C Ultrasonic flowmeter for water and wastewater . . . with weld-in sensors for metal pipelines . . . with built-on or built-in sensors for open channels

Upload: others

Post on 01-Oct-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: GR/PRINTO UFM 800W,C Ultrasonic flowmeter for water and ... · UFM 800 W Ultrasonic flowmeters with UFS 800 W sensors for measuring the volumetric flowrate in metal pipelines. The

GR/PRINTO

Variable area flowmeters

Vortex flowmeters

Flow controllers

Electromagnetic flowmeters

Ultrasonic flowmeters

Mass flowmeters

Level measuring instruments

Communications engineering

Engineering systems & solutions

© KROHNE 08/2000 7.02343.21.00

UFM 800 W, CUltrasonic flowmeter

for water and wastewater.. .with weld-in sensors for metal pipelines

. . .with built-on or built-in sensors for open channels

Page 2: GR/PRINTO UFM 800W,C Ultrasonic flowmeter for water and ... · UFM 800 W Ultrasonic flowmeters with UFS 800 W sensors for measuring the volumetric flowrate in metal pipelines. The

2

UFM 800 W, CUltrasonic flowmeterfor water and wastewater.. .with weld-in sensors for metal pipelines. . .with built-on or built-in sensors for open channels

Efficient flow measurement and volumecounting of all types of water and waste-water in closed pipelines or in open channels and raceways.

Advantages No constriction of the pipe cross-section No additional pressure drop Electrical conductivity, pressure, density,

etc. have no effect on measurements Easy to install from the outside or the

inside No maintenance requirement Low power consumption Low operating costs

UFM 800 WUltrasonic flowmeters with UFS 800 W sensors for measuring the volumetric flowrate in metal pipelines.The sensors are welded to the outside of the pipelines.

UFM 800 CUltrasonic flowmeter with UFS 800 Csensors for measuring flow velocityin open channels. The sensors canbe installed or mounted from theinside or outside of the channel.

UFC 500 F signal converter Digital signal processing Easy to operate Current, pulse and status

outputs Low power consumption Large clear text LC display, easy

to read

Page 3: GR/PRINTO UFM 800W,C Ultrasonic flowmeter for water and ... · UFM 800 W Ultrasonic flowmeters with UFS 800 W sensors for measuring the volumetric flowrate in metal pipelines. The

Backgro

und

Flow

tube

sU

FM 5

00

Clam

p-on

UFM

600/

610

Weld-o

mU

FM 8

00

WO

pen channe

lU

FM 8

00 C

Gas-

flow

tube

GFM

700

Custo

dytransfe

rA

LTOS

ON

IC V

Calibratio

nInstallatio

nno

tes

Sizing gu

ideO

rdering

guide

UFM 800 W / UFM 800 C 3

UFM 800

Systems

VersionsSensorsSingle-beam measurement Double-beam measurementSignal converterHazardous-duty version

Application/Measurement

AccuraciesMeasurementLinearityRepeatability

UFC 500 F signal convertersWeight: approx. 4.2 kg (9.3 lb)

UFS 800 W sensors UFS 800 C sensors

Dimensions in mm and (inch)

Dimensions and weights

UFM 800 Wfor measuring process liquidsin metal pipelinesDN 500–5000 / 20”–200”

2 x UFS 800 W4 x UFS 800 W (option)UFC 500pending

Volumetric flowrate Direction of flowVolume counts Transit time measurement

typical values, dependent upon application± 3% of measured value± 0.5% of measured value (v > 0.5 m/s or > 1.6 ft/s)± 0.2% of measured value

UFM 800 Cfor measuring process liquidsin open channelsWidth: 400–8000 mm

2 x UFS 800 C–UFC 500 / M 4.1–

Flow velocityDirection of flow

typical values, dependent upon application± 5% of measured value± 0.5% of measured value± 0.2% of measured value

208 (8.19”)

Ø 1

22 (

4.80

”)

Page 4: GR/PRINTO UFM 800W,C Ultrasonic flowmeter for water and ... · UFM 800 W Ultrasonic flowmeters with UFS 800 W sensors for measuring the volumetric flowrate in metal pipelines. The

UFM 800

4 UFM 800 W / UFM 800 C

Responsibility for suitability and intended use of our instruments rests solely with the purchaser.

Sensors

VersionsSingle-beam measurement Double-beam measurement

Hazardous-duty version toEuropean Standard

Application dataMounting location

Sensor alignment

Operating dataProcess temperaturePressureAmbient temperatureStorage temperature (electronics)(electronics)

Protection category(IEC529/EN 60529)StandardOptional

MaterialSensorSensor mount

UFS 800 W

2 x FS 500 W4 x FS 500 W (option)replaceable at operating pressure

Ex de ib, pending

on metal pipelinesmeter size DN 500–5000 / 20”–200”

DN ≤ 1000 / ≤ 40”acoustic alignment (water only)DN > 1000 / > 40”by KROHNE technicians using laser alignment set

– 50 to +170°C / – 58 to +338°Fmax. 40 bar / max. 580 psig– 25 to +60°C / – 13 to +140°F

– 40 to +60°C / – 40 to +140°F

(IEC529/EN 60529)IP 65 equivalent to NEMA 12 and 13IP 67, IP 68 equivalent to NEMA 6

stainless steel 1.4404 equivalent to SS 316 Lstainless steel 1.4301 equivalent to SS 304others on request

UFS 800 C

2 x FS 500 C–

Installation in open channels,Mounted from the outside or the insideWidth: 400–8000 mm / 16”–320”by KROHNE technicians with laser alignment set

– 25 to +120°C / – 13 to +248°Fmax. 10 bar / max. 150 psig– 25 to +60°C / – 13 to +140°F

– 40 to +60°C / – 40 to +140°F

IP 65 equivalent to NEMA 12 and 13IP 67, IP 68 equivalent to NEMA 6

stainless steel 1.4301 or SS 304, Pyrex and Vitonstainless steel 1.4301 or SS 304 and Vitonothers on request

Technical data

Page 5: GR/PRINTO UFM 800W,C Ultrasonic flowmeter for water and ... · UFM 800 W Ultrasonic flowmeters with UFS 800 W sensors for measuring the volumetric flowrate in metal pipelines. The

5UFM 800 W / UFM 800 C

UFM 800

Backgro

und

Flow

tube

sU

FM 5

00

Clam

p-on

UFM

600/

610

Weld-o

mU

FM 8

00

WO

pen channe

lU

FM 8

00 C

Gas-

flow

tube

GFM

700

Custo

dytransfe

rA

LTOS

ON

IC V

Calibratio

nInstallatio

nno

tes

Sizing gu

ideO

rdering

guide

UFC 500 F Signal converters

VersionsStandard UFC 500 FOption UFC 500 F / MP, settable via magnetic sensors and bar magnetHazardous- duty version UFC 500 F-EEx

Full-scale range Volumetric flowrate Q100%Setting range 355–1250000 m3/hr

1560 – 5500000 US gal/minUnits any

Current outputFunction – continuous flowrate measurement or measurement of sound velocity

– to determine (composition of) liquid product– all operating data configuration– galvanically isolated– for active and passive mode– useable as internal power supply for the binary outputs

Current for Q = 0%: 0 – 16 mAfor Q = 100%: 4 – 20 mA settings in 1 mA increments (Imax = 22 mA)

Active mode load max. 680 OhmPassive mode external voltage: ≤ 18 V DC

load ≤ 680 ΩLow-flow cutoff cutoff “on” value: 1 – 19%

cutoff “off” value: 2 – 20% of Q100%, setting in 1% incrementsTime constant 0.04 – 3600 s, setting in increments of 1, 0.1 or 0.01 sForward / reverse measurement direction identified via status output (or pulse output)Internal power supply for binary outputs Uint = 19 – 32 V DC / I ≤ 50 mAPulse outputFunction – continuous flow counting or measurement of sound velocity

– to determine (composition of) liquid product– all operating data configurable– galvanically isolated– for active and passive mode

Pulse rate for Q = 100% 10 – 3 600 000 pulses/h0.167 – 60 000 pulses/min optionally in pulse per liter, m3, US gallons0.0028 – 1 000 pulses/s (= Hz) or user-defined unit

Pulse width automatic: pulse duty cycle 1:1, max. 1000 pulses/s = max. 1000 Hzvariable: 30, 50, 100, 200, 500 ms, ≤ 10 pulses/s ≤ 10 Hz

Active mode connection: electronic counterinternal voltage: 19 – 32 V DC, from current outputload current: Imax < 50 mA, operation without status output

Passive mode connection: electronic or electromechanical counterexternal voltage: Uext ≤ 32 V DC / ≤ 24 V ACcurrent load: Imax ≤ 150 mA

Low-flow cutoff cutoff “on” value: 1 – 19%cutoff “off” value: 2 – 20% of Q100%, setting in 1% increments

Time constant 0.04 s or same as current outputForward / reverse measurement direction identified via status output (or current output)Status outputFunction configure as indicator for flow direction, errors or operating modeActive mode internal voltage: Uint 19 – 32 V DC, from current output

current load: Imax < 50 mA, operation without pulse outputPassive mode external voltage: Uext ≤ 32 V DC / ≤ 24 V AC

current load: Imax ≤ 150 mAPower supply 1. AC Version 2. AC Version AC / DC Version

Standard Option Option1. Rated voltage 230 / 240 V 200 V 24 V AC 24 V DC

Tolerance band 200 – 260 V 170 – 220 V 20 – 27 V AC 18 – 32 V DC2. Rated voltage 115 / 120 V 100 V – –

Tolerance band 100–130 V 85 – 110 V – –Frequency 48 – 63 Hz 48 – 63 Hz –Power consumption (incl. primary head) approx. 10 VA approx. 10 VA approx. 8 WWhen connected to functional extra-low voltage (24 V) safety separation (PELV) is essential (to VDE 0100 / VDE 0106 and IEC 364 / IEC 536 or equivalent national standards).

Page 6: GR/PRINTO UFM 800W,C Ultrasonic flowmeter for water and ... · UFM 800 W Ultrasonic flowmeters with UFS 800 W sensors for measuring the volumetric flowrate in metal pipelines. The

UFM 800

6 UFM 800 W / UFM 800 C

Local display 3-field LCDDisplay function actual flowrate, measurement of sound velocity to determine

(composition of) liquid product, forward, reverse and sum totalizer (7-digit) and statusmessages, each can be configured for continuous or sequential display

Units: actual flowrate m3, liter, US gallons per second, minute or hour,or in user-defined unit, e.g. liter/h or US gallon/day

counter m3, liter, US gallons or in user-defined unit, e.g. hecto liter or US million gallon(min. 1 year overflow time)

Language of plain texts English, French, German, Dutch, others on requestDisplay: 1st line (top) 8-character, 7-segment numeral and sign display, and symbols for key acknowledgement

2nd line (middle) 10-character, 14-segment text display3rd line (bottom) 5 markers to identify display in measuring mode

Housing Field housingMaterial aluminium with polyurethane finishProtection category(IEC 529/EN 60529) IP 67 equivalent to NEMA 6 (option IP 68)

Sensor leadselectrical connection betweensensors and signal converter max. length: 50 m / 160 ft

Page 7: GR/PRINTO UFM 800W,C Ultrasonic flowmeter for water and ... · UFM 800 W Ultrasonic flowmeters with UFS 800 W sensors for measuring the volumetric flowrate in metal pipelines. The

7UFM 800 W / UFM 800 C

UFM 800

Backgro

und

Flow

tube

sU

FM 5

00

Clam

p-on

UFM

600/

610

Weld-o

mU

FM 8

00

WO

pen channe

lU

FM 8

00 C

Gas-

flow

tube

GFM

700

Custo

dytransfe

rA

LTOS

ON

IC V

Calibratio

nInstallatio

nno

tes

Sizing gu

ideO

rdering

guide

UFM 800 W for pipelines

UFM 800 C for open channels

UFS 800 WMounting location and installation

Position the UFM 800 W in the pipeline such that the measuringtube is completely filled with the process liquid at all times, even at “zero” flow velocity. Make sure that the measuring beam is approximately horizontal.

Installation and alignment of FS 800 W ultrasonic sensors can becompleted by KROHNE technicians.

Install UFC 500 F signal converter in the vicinity of the measuringpoint (UFS 800 W sensors).

Gas contentThe gas content in the process liquid must not exceed a maximumof 0.2% by volume at flowing conditions.

Please note:Even in liquids that are virtually gas-free, large quantities of gas mayform if the liquid is allowed to expand before reaching the measur-ing point, e.g. downstream of partially closed valves or small pumpoutlets.

Inlet and outlet runs Single-beam Double-beamInlet 20 x DN 10 x DNOutlet 5 x DN 10 x DN(DN = meter size, pipe diameter)

UFS 800 CMounting location and installation,

Inlet run: 10 x BOutlet run: 5 x B(B = width of channel)

Sensors can be installed either from the inside or the outsideof the channel.

Sensors aligned by KROHNE technicians are precisely set usinglaser alignment.

Page 8: GR/PRINTO UFM 800W,C Ultrasonic flowmeter for water and ... · UFM 800 W Ultrasonic flowmeters with UFS 800 W sensors for measuring the volumetric flowrate in metal pipelines. The

UFM 800

8 UFM 800 W / UFM 800 C

Electrical connection, UFC 500 F (M 4.1)

Power supply, power consumption and load rating of outputs:see “Technical data” (page 5)

Current and pulse outputs (I + P) are galvanically isolated fromall input and output circuits, when used in passive mode.

Use the supplied signal cables (coaxial), length 5 m /16 ft,max. length 50 m /160 ft (optional), for the electrical connectionbetween sensors and signal converter.

Ambient temperature must be from –25 to +60°C (–13 to +140°F),therefore do not cover signal converter with heat-insulating materials,and do not expose to strong sunlight or other heat sources.

Avoid intensive vibration.

Current output Iactive Current output Ipassive Pulse output Pactivefor passive ECwith internal voltagefrom current output

Pulse output Ppassive andstatus output Spassivewith external voltage

UextUext

Uint. ≤ 19 – 32 V DCI ≤ 50 mAR ≥ 650 Ω

Uext ≤ 18 V DCRi ≤ 680 Ω

Ri ≤ 680 Ω EC or relayEMC (e.g. Siemens D1)

Uext ≤ 32 V DC/≤ 24 V AC

I ≤ 150 mA

binaryoutputs

currentoutput

for internal use only

85 - 260 V AC

24 V AC / DC

(PE = protective conductor)(FE = functional ground)

Power supply