    GeneralSpecifications

    Integrated Production ControlSystem CENTUM VPSystem Overview (Vnet/IP Edition)

    Yokogawa Electric Corporation2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 JapanTel.: 81-422-52-5634 Fax.: 81-422-52-9802

    GS 33L01A10-40E

    GS 33L01A10-40ECopyright Feb. 2008 (YK)

    9th Edition Jun. 2, 2010 (YK)

    GENERALThis document provides the overall system specifications of the CENTUM VP Systems with Vnet/IP.

    SYSTEM CONFIGURATION

    F01E.ai

    PC for

    engineering

    (ENG)

    HIS

    Human

    InterfaceStation

    Vnet/IP

    (Subsystem)

    Enclosed

    Display

    Style

    Console

    HIS

    Open

    Display

    Style

    Console

    HIS

    APCSAdvanced

    Process

    Control

    Station

    GSGWGeneric

    Subsystem

    Gateway

    SIOSSystem

    Integration

    OPC Station

    OtherVnet/IP

    domains

    Other

    PCS

    Other

    V net

    domains

    V net router

    Vnet/IP domain

    Bus 1

    Bus 2

    L3SW

    Layer 3 switch

    L3SW

    Layer 3 switch

    SNTPServer SENG

    ProSafe-RS

    Safety

    Instrumented

    System

    Other system

    FCS(for FIO)

    ER bus

    ESB bus

    Remote node

    Local node

    SCS

    Figure Example of System Configuration

    http://localhost/var/www/apps/conversion/tmp/submenu.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/tmp/submenu.htm
  • 7/27/2019 GS33L01A10-40E

    2/12

    2

    All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation

    GS 33L01A10-40E May 1, 2009-00

    SYSTEM COMPONENTS

    Human Interface Station (HIS)An HIS serves as a human machine interface forplant operators. Software packages are installed in ageneral-purpose personal computer (an IBM PC/ATcompatible computer, hereinafter referred to as ageneral-purpose PC). The HIS PC can be assembledin the console box.

    For connections to the Vnet/IP, a VI702 Control BusInterface Card is required.

    For more information on HIS hardware requirements,see the following General Specifications:

    Enclosed Display Style Console Assembly(GS 33M50B40-40E)

    Open Display Style Console Assembly(GS 33M50B50-40E)

    Standard Operation and Monitoring Function(GS 33M05D10-40E)

    Vnet/IP Interface Card (GS 33L50C10-40E)

    PC for Engineering (ENG)This is a PC with engineering functions used to performCENTUM VP system generation and maintenancemanagement.

    It can be the same type as the general-purpose PC forthe HIS, and can even be the same PC as the HIS.

    By having HIS operation and monitoring functions onthe same PC, you can execute virtual test (controlstation emulation) functions to provide an efficient andeasy-to-use engineering environment.

    For connections to the Vnet/IP, a VI702 Control BusInterface Card is required.

    Field Control Station (FCS)An FCS performs process control. Two types of fieldcontrol stations are available:

    AFV10S: Field Control Unit (for Vnet/IP, FIO, rack-mounted)

    AFV10D: Duplexed Field Control Unit (for Vnet/IP,FIO, rack-mounted)

    One field control station has 8 slots for I/O modules,and extra I/O expansion nodes can be also connectedvia ESB bus or via ER bus.

    For more information on the FCS hardwarerequirements, see the following General Specifications:

    Field Control Unit (for Vnet/IP and FIO)

    (GS 33L50E20-40E)ESB Bus Coupler Module (GS 33M50E25-40E)ER Bus Interface Master Module (for FIO)

    (GS 33M50F25-40E)Node Units (for FIO) (GS 33M50F20-40E)FIO System Overview (for AFV10)

    (GS 33L50F10-40E)

    Generic Subsystem Gateway Station(GSGW)

    A GSGW can collect and set data of various types ofsubsystems through OPC DA servers. No dedicatedcommunication program is required.

    GSGW is a general-purpose PC with LFS1250 GenericSubsystem Gateway Package.

    For connections to the Vnet/IP, a VI702 Control BusInterface Card is required.

    For more information, see GSGW Generic SubsystemGateway Package (GS 33M20F10-40E).

    Safety Control Station (SCS)An SCS is a component of Safety InstrumentedSystems (ProSafe-RS). ProSafe-RS has beenapproved by German safety test labs TV (Technischeberwachungs Verein) as the SIS (Safety InstrumentedSystem) that meets SIL (Safety Integrity Levels) 3established by IEC 61508.

    The SCS for ProSafe-RS monitors the state of plantsand performs predetermined safety operation accordingto each request for safety control.

    For connections to the Vnet/IP, a VI702 Control BusInterface Card is required.

    Safety Engineering PC (SENG)An SENG is a PC with engineering functions forProSafe-RS such as editing, downloading and testingapplications as well as carrying out maintenance taskson safety control stations (SCSs).

    The SENG functions can be installed in a PC that hasHIS or ENG functions.

    For connections to the Vnet/IP, a VI702 Control BusInterface Card is required.

    For more information, see Safety InstrumentedSystems ProSafe-RS System Overview (for Vnet/IP)(GS 32S51B10-01E).

    System Integration OPC Station (SIOS)System Integration OPC Station (SIOS) is a stationused to integrate other venders PCS (Process ControlSystem) to CENTUM VP system. SIOS enables HISsto access the process data, alarms and events of othervenders PCSs through OPC DA and AE.

    The SIOS is a general-purpose PC with LBC2100System Integration OPC Client Package.

    For connections to the Vnet/IP, a VI702 Control BusInterface Card is required.

    For more information, see System Integration OPCClient Package (GS 33M20D10-40E).

    Advanced Process Control Station (APCS)An APCS advanced process control station implementscontrol functions with a general-purpose PC connectedto a Vnet/IP, aimed at improving advanced control andplant efficiency. The APCS requires LFS 1200 APCSControl Functions (GS 33M15U10-40E) to be installed.

    For connections to the Vnet/IP, a VI702 Control BusInterface Card is required.

    For more information, see APCS Control Functions(GS 33M15U10-40E).

    http://localhost/var/www/apps/conversion/tmp/submenu.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/tmp/submenu.htm
  • 7/27/2019 GS33L01A10-40E

    3/12

    3

    All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation GS 33L01A10-40E

    Vnet/IPVnet/IP is the IEEE 802.3 compliant, dual-redundanthigh-speed (1Gbps) control network. All thecomponents of the Vnet/IP network are connected tothe Layer 2 switches. Layer 2 switches are requiredfor each of the dual redundant networks. One of the

    dual-redundant networks (called Bus 1) is exclusivelyused for process control communication. The other(called Bus 2) is used not only for process controlcommunication redundant with Bus 1, but also forthe open communication with the generic Ethernetprotocol.

    Using Layer 3 switches, the Vnet/IP can be divided intoseveral domains. VI702 the NIC (Network InterfaceCard) for Vnet/IP is required for each PC, which isconnected to the Vnet/IP. Commercially availableproducts are used for all other network equipment suchas switches, LAN cables, or repeaters.

    Layer 2 Switch

    This is the COTS (Commercial off-the-shelf) switchequipment. At least two switches are mandatory for oneVnet/IP system. The transmission speed for Vnet/IPhas to be 1 Gbps.

    Jun. 1, 2010-00

    Layer 3 SwitchThis is the COTS switch with the routing function, andcan divide the Vnet/IP network into several domains.

    V net Router

    This is the equipment to connect a Vnet/IP systemand a V net system. This router enables the HIS ofboth Vnet/IP and V net to operate the FCS of the othersystems.

    The following product is available.

    AVR10D: Duplexed V net Router (for redundant useof communications and power supplymodules)

    For information on the hardware specifications, seeDuplexed V net Router (GS 33L50D30-40E).

    SNTP ServerThe time of all the components connected to theVnet/IP network is synchronized. By connecting the

    COTS SNTP server on the Vnet/IP network, the timeof Vnet/IP components can be synchronized with UTC(Coordinated Universal Time).

    Peripherals DevicePlease use compatible models of the peripheraldevices, such as printers, which support the designatedOperation Systems. Consult with a Yokogawasales department for more information about thosecompatible devices with HIS.

    http://localhost/var/www/apps/conversion/tmp/submenu.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/tmp/submenu.htm
  • 7/27/2019 GS33L01A10-40E

    4/12

    4

    All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation

    GS 33L01A10-40E

    SYSTEM SPECIFICATIONS

    Number of TagUp to 100,000 per system (when using LHS4000, up to1,000,000 per system)

    Minimum SystemA minimum system consists of one HIS withengineering function and one FCS.

    Maximum System64 components/domain

    16 domain/system

    256 stations/system

    Components:

    Human Interface Station (HIS)Field Control Station (FCS)

    Advanced Process Control Station (APCS)Generic Subsystem Gateway (GSGW)System Integration OPC Station (SIOS)Safety Instrumented Systems (ProSafe-RS)OPC Interface Package (Exaopc) OPC serverField Communications Server for Plant Resource

    Manager (PRM)V net Router (AVR10D)

    On the bus 2, up to 124 general-use Ethernet devices(including intelligent network devices) other than listedabove can be additionally connected.

    Expanded SystemThe former systems than V net such as HF bus or RLbus can be connected on a Vnet/IP system through abus converter on a V net.

    Vnet/IP domains and V net domains can be managedin the same project, or can be connected with aMultiple Project Connection Package.

    For more information, see Multiple Project ConnectionPackage (GS 33M05K20-40E).

    Installing of Server PCsEach number shown below includes the number of CS3000 PCs.

    CENTUM VP achieves many functions using filesharing function of Windows. The number of PCs toshare files simultaneously is restricted on the WindowsWorkstation OS. Therefore, when there are 9 or morestations (HIS, ENG, Exaopc) in one project, the PC witha server OS may be required.

    Please count the total station number in one projectusing the equations shown below in order to judgewhether server PC is required or not. If the numberis eight or smaller, a server PC is not required. If thenumber is larger than 8, consult with a Yokogawa salesrepresentative for further examination.

    In case of PCs storing master Engineeringdatabase fileWhen not using Engineering Tool for FOUNDATIONfieldbus (SSS5700)

    Total station number =HIS + ((ENG - 1) x 2) + ExaopcWhen using Engineering Tool for FOUNDATION fieldbus(SSS5700)

    Total station number =HIS + ((ENG - 1) x 2) + Exaopc + 2

    HIS : Number of PCs in which StandardOperation and Monitoring Function(LHS1100 or LHM1101) is installed

    ENG: Number of PCs in which Standard BuilderFunction (LHS5100 or LHM5100) isinstalled.

    Exaopc: Number of PCs with Exaopc InterfacePackage (NTPF100)

    When using Multiple Project Connection Package(LHS4450), see Multiple Project Connection Package(GS 33M05K20-40E).

    When using Expanded Test Function (LHS5425),a server PC is always required for storing masterEngineering database.

    In case of PCs storing audit trail dataWhen using LHS5170 Access Administrator Package,one PC which is dedicated for storing audit trail datamust be prepared. When there are 9 or more stations(ENG, Recipe Management PC) in one project, theserver PC may be required for storing audit trail data.

    Please count the total station number in one projectusing the equations shown below in order to judgewhether server PC is required or not. If the numberis eight or smaller, a server PC is not required. If thenumber is larger than 8, consult with a Yokogawa salesrepresentative for further examination.

    Total station number = ENG + Recipe Management

    ENG: Number of PCs in which Standard BuilderFunction (LHS5100 or LHM5100) isinstalled.

    Recipe Management: Number of PCs in which CSBatch 3000 Recipe Management package(LHS5161) is installed

    Jun. 1, 2010-00

    http://localhost/var/www/apps/conversion/tmp/submenu.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/tmp/submenu.htm
  • 7/27/2019 GS33L01A10-40E

    5/12

    5

    All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation GS 33L01A10-40E

    Vnet/IP NETWORK SPECIFICATIONSThe Vnet/IP is a real-time process control network used to connect system components. The Vnet/IP supportstwo types of communications: control-bus communications and open communications. The Vnet/IP is always dual-redundant. Usually, control bus communications are carried out via bus 1. Open communications are carried out viabus 2. If a control communications error occurs on bus 1, control bus communications will be carried out via bus 2.The Vnet/IP uses general-purpose communications devices for network connection.

    F03E.ai

    V net router

    Vnet/IP domain

    Layer 2 switch

    FFCS-L

    Layer 2 switch

    Layer 3switch

    Layer 3switch

    V netdomain

    Vnet/IPdomain

    Vnet/IPdomain

    Wide-area connectionenabled by dedicated-lineconnection

    HF-busdomain

    BCV-H

    1000BASE-TMax. 100 m

    HIS ENGAPCS GSGW

    Exaopc

    Up to seven levels oflayer 2 switch

    Bus 1

    Bus 2

    Figure Network Configuration

    Jul. 1, 2008-00

    http://localhost/var/www/apps/conversion/tmp/submenu.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/tmp/submenu.htm
  • 7/27/2019 GS33L01A10-40E

    6/12

    6

    All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation

    GS 33L01A10-40E

    Communications Specifications

    Control communicationsCommunication Method: Read/write communication,

    message communication, and inter-controller communication

    Inter-Controller Communication Period: 100 msec

    Open communicationsOpen communications are executed via bus 2.Commercially available Ethernet communicationsdevices can be connected.The total bandwidth that can be used for opencommunications on bus 2 is up to 300 Mbps.

    Transmission Path SpecificationsNetwork Topology: Star TopologyTransmission Path Redundancy: Available (control

    bus communications only)Transmission Cable: Unshielded twisted pair (UTP) at

    enhanced category 5 or better.

    ConnectionCable

    Standard

    SpeedMaximum

    Distance

    Betweencomponent anda layer 2 switch

    100BASE-TX(IEEE802.3u)

    100 Mbps(*1)

    100 m1000BASE-T(IEEE802.3ab)

    1 Gbps

    Between layer 2switches

    1000BASE-T(IEEE802.3ab)

    1 Gbps 100 m

    1000BASE-LX(IEEE802.3z)

    1 Gbps 5 km

    Between a layer 2switch and a layer3 switch

    1000BASE-T(IEEE802.3ab)

    1 Gbps 100 m

    1000BASE-LX(IEEE802.3z)

    1 Gbps 5 km

    *1: For V net Router, SCS and Open communication

    network.

    Communications between ComponentsMaximum distance between arbitrary stations: 40 kmOnly a couple of media converter betweencomponents can be connected.

    Jul. 1, 2008-00

    RequiredNetwork EquipmentSpecifications

    Layer 2 switchConnection Port: 1000BASE-T, full duplexConnection between switches: 1000BASE-T,

    1000BASE-LX with speed, 1 Gbps (1.5Mpps@64 byte) or faster, full duplex

    Auto-Negotiation: Mandatory

    Layer 3 switchConnection Port: 1000BASE-T, full duplexConnection between switches: 1000BASE-T,

    1000BASE-LX with speed, 1 Gbps (1.5Mpps@64 byte) or faster, full duplex

    Unicast dynamic routing protocol: RIPv2 (RIPv1compatible mode is mandatory)

    Multicast Protocol:IGMP: MandatoryDVMRP or PIM-DM: Mandatory

    Management functionSNMP

    Address Reserved for Vnet/IPClass C private address is used for communicationsfor control and open communications.For Yokogawa equipment supporting Vnet/IP, threeIP addressed are reserved: One for bus 1 controlcommunication; one for bus 2 control communication;one for bus 2 open communication.Make sure that there are no overlaps in IP addresses.Communications for control

    Bus 1: 192.168.(Domain No.).1 to 129 or 254Bus 2: 192.168.(128 + Domain No.).1 to 129 or

    254

    The following addresses are reserved for multicastcommunications.For stations within domains

    Bus 1: 239.192.24.0Bus 2: 239.192.24.1

    For all domainsBus 1: 239.192.24.4Bus 2: 239.192.24.5

    Class B address is reserved for the TCP/IP protocolcommunications on Vnet/IP.

    http://localhost/var/www/apps/conversion/tmp/submenu.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/tmp/submenu.htm
  • 7/27/2019 GS33L01A10-40E

    7/12

    7

    All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation GS 33L01A10-40E

    I/O COMMUNICATIONS BUS

    ESB Bus

    ApplicationAn ESB bus is an I/O communications bus that connects the processing unit of an FCS to the I/O expansion nodes.

    The nodes connected on the ESB bus are named local node.Communication Specifications

    Connectable Devices: Node units (ANB10S and ANB10D)Number of Connectable Devices: The number of local node units that can be connected to an ESB bus varies

    according to the database selected.

    DatabaseMaximum Number of

    Local NodesTotal Number of

    Local and Remote Nodes

    Control Function for Standard Field Control Unit (*1) 3 3

    Control Function for Standard Field Control Unit plus Application CapacityExpansion Package (LFS1530)

    9 14

    *1: If local nodes are connected to an AFV10S or AFV10D FCU, ESB Bus Coupler Modules (EC401) have to be installed inslots 7 and 8.

    Transmission Path Specifications

    Network Topology: Bus topologyTransmission Path Redundancy: AvailableTransmission Speed: 128 MbpsTransmission Cable: Dedicated cable (YCB301)Transmission Distance: 10 m max.

    ER Bus

    ApplicationAn ER bus is a remote I/O communications bus to connect an FCU or local node unit to the I/O expansion nodesremotely. The nodes connected on the ER bus are named remote node.

    Communication SpecificationsConnectable Devices: Remote node units (ANR10S, ANR10D)Number of ER buses: Max. 4 per FCUNumber of Connectable Devices: The number of remote node units that can be connected to an ER bus varies

    according to the model and database selected.

    DatabaseMaximum Number of

    Remote NodesTotal Number of

    Local and Remote Nodes

    Control Function for Standard Field Control Unit 3 3

    Control Function for Standard Field Control Unit plus Application CapacityExpansion Package (LFS1530)

    14 (*1) 14

    *1: Up to eight remote nodes per ER bus can be connected.

    Mar. 14, 2008-00

    http://localhost/var/www/apps/conversion/tmp/submenu.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/tmp/submenu.htm
  • 7/27/2019 GS33L01A10-40E

    8/12

    8

    All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation

    GS 33L01A10-40E

    Transmission Path SpecificationsNetwork Topology: Bus topologyTransmission Path Redundancy: AvailableTransmission Speed: 10 MbpsTransmission Cable: Coaxial cable (YCB141, YCB311). Use YCB147 ER-bus Adapter and YCB149 ER Bus

    Converter Unit for connecting YCB141 and YCB311 cables.

    One grounding unit (YCB117) per segment (*1) should be used when connecting YCB311 cable.Transmission Distance:YCB141: Max.185 mWhen mixing YCB141 and YCB311:

    Length of YCB141 + (185/500) x Length of YCB311 185Number of Bus Adapter Units: Max. 4 per segment (*1)

    General-purpose Ethernet Repeater:The total transmission distance is limited by the number of repeaters.L 4 - 0.5 n

    L: total transmission distance (km)n: the number of the general-purpose Ethernet repeater (Max. 4 repeaters)

    *1: If repeaters are used on ER bus, each part of the ER bus segregated by a repeater is referred to as a segment.

    AFV10D (Nod e1)

    Repeater Repeater

    Repeater Repeater

    ANR10D (Nod e2)

    ANR10D (Nod e3)

    ANR10D (Node 4)

    EB401

    Repeater Repeater

    Repeater Repeater

    ER bus

    EB501

    EB501

    EB501

    Optical Fiber

    Cable

    Optical Fiber

    Cable

    Optical Fiber

    Cable

    Optical Fiber

    Cable

    AFV10D

    (Node1)

    Repeater Repeater

    Repeater Repeater

    ANR10D (Nod e2)

    ANR1 0D (Node3)

    Optical Fiber

    Cable

    ER bus

    Repeater Repeater

    Repeater Repeater

    ANR10D (Nod e4)

    EB401

    EB501

    EB501 EB501

    Optical Fiber

    Cable

    Optical Fiber

    Cable

    Optical Fiber

    Cable

    F04.ai

    Figure Example of ER Bus connection

    Feb. 1, 2009-00

    http://localhost/var/www/apps/conversion/tmp/submenu.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/tmp/submenu.htm
  • 7/27/2019 GS33L01A10-40E

    9/12

    9

    All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation GS 33L01A10-40E

    SOFTWARE

    Operation and Monitoring SoftwareLHS1100 Standard Operation and Monitoring

    FunctionLHS1120 Console HIS Support Package for

    Enclosed Display StyleLHS1130 Console HIS Support Package for Open

    Display StyleLHS1150 Server for Remote Operation and

    Monitoring FunctionLHS2411 Exaopc OPC Interface Package (for HIS)LHS2412 CENTUM Data Access LibraryLHS4000 Million Tag Handling PackageLHS4100 Configured Information Reference

    PackageLHS4150 Recorder Output PackageLHS4190 Line Printer Support PackageLHS4200 Consolidated Historical Message Viewer

    (Meeting FDA)LHS4410 Control Drawing Status Display PackageLHS4420 Logic Chart Status Display PackageLHS4450 Multiple Project Connection PackageLHS4600 Multiple-monitor PackageLHS4700 Advanced Alarm Filter PackageLHS6510 Long-term Data Archive PackageLHS6530 Report PackageLHS6600 CS Batch 3000 Process Management

    PackageLHS6710 FCS Data Setting/Acquisition Package

    (PICOT)For more information on the above functions, see therespective GSs.

    The following operating systems can be used on HISwhich supports operation, monitoring, and engineering.

    Windows Vista Business EditionWindows XP Professional EditionWindows Server 2003 Standard EditionWindows Server 2008 Standard Edition

    As for Windows OS and Service Pack, see StandardOperation and Monitoring Function (GS 33M05D10-40E) and Standard Builder Function (GS 33M10D10-40E).

    If it is necessary to run other third-party software onthe HIS, consult with a Yokogawa sales department toconfirm that it is supported.

    Engineering SoftwareLHS5100 Standard Builder Function

    LHS5110 Access Control PackageLHS5150 Graphic BuilderLHS5160 CS Batch 3000 BuilderLHS5161 CS Batch 3000 Recipe Management

    PackageLHS5170 Access Administrator Package (FDA: 21

    CFR Part 11 compliant)LHS5420 Test FunctionLHS5425 Expanded Test FunctionsLHS5426 FCS Simulator PackageLHS5427 HIS Simulator PackageLHS5450 Multiple Project Connection BuilderLHS5490 Self-documentation PackageLHS5800 Turbomachinery I/O Module Logic Builder

    Package

    For more information on the above functions, see therespective GSs.

    Standard FCS SoftwareLFS1500 Control Function for Standard Field

    Control Unit (for FIO, Vnet/IP)LFS1530 Application Capacity Expansion Package

    (for AFV10)For more information, see Control Function for Basic

    Field Control Unit, Application Capacity ExpansionPackage (GS 33L15C20-40E).

    Optional FCS SoftwareLFS3132 Valve Pattern Monitor PackageLFS8620 Off-site Block Package

    For more information, see the respective GSs.

    Subsystem Communication SoftwareFor each subsystem, optional communications softwareis available.

    LFS2410 FA-M3 Communication Package (forALR111, ALR121)

    LFS2420 YS Communication Package (for ALR121)LFS2421 YS Communication Package with Direct

    Connection (for ALR121)LFS2430 MELSEC Communication Package (for

    ALE111)LFS2431 FA-M3 Communication Package (for

    ALE111)LFS2432 DARWIN/DAQSTATION Communication

    Package (for ALE111)LFS2433 PLC-5/SLC500 Communication Package

    (for ALE111)LFS2453 Modbus Communication Package (for

    ALE111)LFS2456 SLC500 Communication Package (for

    ALR111, ALR121)

    LFS2457 PLC-5 Communication Package (forALR111, ALR121)LFS2542 PROFIBUS Communication Package (for

    ALP111)LFS2610 Foundation Fieldbus Communication

    Package (for ALF111)LFS2710 HART Communication Package (for

    AI-H)LFS2753 YFGW Communication Package (for

    ALE111) (*1)LFS9153 Modbus Communication Package (for

    ALR111, ALR121)LFS9162 MELSEC-A Communication Package (for

    ALR111, ALR121)For more information, see the respective GSs.

    *1: Supported by R4.02.30 or later versions

    Jun. 2, 2010-00

    http://localhost/var/www/apps/conversion/tmp/submenu.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/tmp/submenu.htm
  • 7/27/2019 GS33L01A10-40E

    10/12

    10

    All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation

    GS 33L01A10-40E

    Sequence of Events Manager SoftwareLPC6900 SOE Server PackageLPC6910 SOE Server Configurator PackageLPC6920 SOE Viewer PackageLPC6930 SEM OPC Interface Package

    For more information, see SEM Sequence of Events

    Manager (for FIO and Vnet/IP) (GS 33L30D10-40E).

    DocumentsLHS5495 Electronic Document

    For more information, see Electronic InstructionManual (GS 33M01W10-40E).

    Plant Resource ManagementSSS7700 Plant Resource Management ServerSSS7710 Plant Resource Management ClientSSS7720 Field Communications Server

    For more information, see Plant Resource Manager(GS 33Y05Q10-32E).

    Operation Support Software (for HIS)NTPS100 Exaplog Event Analysis PackageNTPS200 Exapilot Operation Efficiency

    Improvement PackageFor more information, see NTPS100 Exaplog Event

    Analysis Package (GS 36J06A10-01E) and NTPS200Exapilot Operation Efficiency Improvement Package(GS 36J06B20-01E).

    Safety Instrumented SystemCHS5100 Safety System Generation and

    Maintenance PackageCFS1100 Safety Control Functions Package

    For more information, see ProSafe-RS Safety

    Instrumented System Overview (for Vnet/IP) (GS32S51B10-01E).

    INSTALLATION ANDENVIRONMENTAL CONDITIONS

    The installation and environmental conditions forYokogawas components (not including the general-purpose PCs, General-Purpose Network Device,console HISs, node units for FIO and I/O modules) areshown below.

    For a general-purpose PC and Network equipment,see their specifications. For an Enclosed display styleconsole HIS, an Open display style console HIS, anode unit for FIO, or an I/O module, see the generalspecifications for each device (GS 33M50B40-40E, GS33M50B50-40E or GS 33M50F10-40E).

    Ambient Temperature:5 to 40 C (YAX101, YAX801)0 to 50 C (FCS)

    Ambient Humidity:20 to 80 %RH10 to 90 %RH (FCS)Non-condensation

    Temperature Change Rate: 10 C per hour

    Power Requirements:100 to 120 V AC 10 %, 50 or 60 Hz 3 Hz220 to 240 V AC 10 %, 50 or 60 Hz 3Hz24 V DC 10 %

    Withstanding Voltage:1500 V AC for 1 minute (for 100-120 and220-240 V AC model)500 V AC for 1 minute (for 24 V DCmodel)

    Insulation Resistance:20 M at 500 V DC10 M at 500 V DC (YAX101, YAX801)

    Grounding:Independent ground of up to 100

    Noise:Electric Field: Up to 3 V/m (26 MHz to 1.0 GHz)

    Up to 3 V/m (1.4 to 2.0 GHz)Up to 1 V/m (2.0 to 2.7 GHz)

    Magnetic Field: Up to 30 A/m (AC), up to 400 A/m(DC)

    Static: Up to 4 kV (direct discharge), up to 8 kV(aerial discharge)

    Continuous Vibration: Displacement amplitude: Up to 0.25 mm

    (1 to 14 Hz)

    Acceleration: Up to 2 m/s2

    (14 to 100 Hz)

    Nov. 1, 2008-00

    http://localhost/var/www/apps/conversion/tmp/submenu.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/tmp/submenu.htm
  • 7/27/2019 GS33L01A10-40E

    11/12

    11

    All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation GS 33L01A10-40E

    CENTUM VP Entry ClassThe CENTUM VP Entry Class is available for small-scale systems. Up to 8,000 tag names can be used in a CENTUMVP Entry Class system.

    Components and Software

    The CENTUM VP Entry Class uses specific Entry Class packages such as built-in HIS packages. There is norestriction on FCS models.

    Operation and Monitoring SoftwareThe following software packages are provided for the Entry Class. Except for the packages listed below, currentCENTUM VP system operation and monitoring software packages can be used. But, the LHS4000 Million TagHandling Package cannot be used in an HIS with the built-in LHM1101 Standard Operation and Monitoring Function.

    Operation and Monitoring Software

    Entry Class Model Product Remarks

    LHM1101 Standard Operation and Monitoring Function Number of operation and monitoring tags : up to 8000

    LHM1150 Server for Remote Operation and Monitoring Function

    LHM4410 Control Drawing Status Display Package

    LHM4420 Logic Chart Status Display Package

    LHM6600

    CS Batch 3000 Process Management Package Maximum number of active recipes:Type A: 4Type B: 10Type C: 999

    LHM6710 FCS Data Setting/Acquisition Package (PICOT)

    Engineering Software

    Entry Class Model Product Remarks

    LHM5100 Standard Builder Function

    LHM5150 Test Function

    LHM5490 Self-documentation Package

    RestrictionsFor CENTUM VP Entry Class, the following restrictions apply.

    Only one domain per system The HIS in a CENTUM VP Entry Class project cannot access the FCSs in other projects of CENTUM VP, CENTUM

    VP Entry Class, CENTUM CS 3000 and CENTUM CS 3000 Entry Class. The HIS in a CENTUM VP Entry Class project can access the FCSs in the Micro-XL system ,but not other former

    CENTUM systems.

    Mar. 14, 2008-00

    http://localhost/var/www/apps/conversion/tmp/submenu.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/tmp/submenu.htm
  • 7/27/2019 GS33L01A10-40E

    12/12

    12

    All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation

    GS 33L01A10-40E

    REGULATORY COMPLIANCECENTUM VP hardware components conform tothe following standards. See the applicable generalspecifications to ensure each devices compliance.

    Safety Standards (*1)

    [CSA]CSA C22.2 No. 61010-1

    [CE Marking] Low Voltage Directive

    EN 61010-1 (*2)

    EMC Conformity Standards (*1)[CE Marking] EMC Directive

    EN 55011 Class A Group 1 (*3)EN 61000-6-2 (*4)EN 61000-3-2 (*5)EN 61000-3-3 (*6)

    [C-Tick Marking]

    EN 55011 Class A Group 1 (*3)

    Standards for Hazardous Location Equipment

    [CSA Non-Incendive] (*7)Class I, Division 2, Groups A, B, C and DTemperature code T4

    CSA Standard C22.2 No. 157-92CSA Standard C22.2 No. 213-M1987ISA Standard ISA-S12.12 1994(for 100-120 V AC and 24 V DC power supply)

    [FM Non-Incendive] (*8)

    Class I, Division 2, Groups A, B, C and DTemperature code T4

    FM Class Number 3600: 1998FM Class Number 3611: 2004FM Class Number 3810: 2005(for 100-120 V AC, 220-240 V AC and 24 V DC

    power supply)

    [Type n] (*9)II 3G Ex nC [nL] II C T4EN 60079-15: 2005IEC 60079-0: 2004IEC 60079-11: 1999(for 24 V DC power supply)II 3G EEx nA II T4EN 50021: 1999(I/O Module with built-in barrier, for 24 V DC power

    supply)[Type i (Intrinsic Safety)]

    II (1) G D [EEx ia] II CEN 50014: 1997 +A1 +A2EN 50020: 1994

    [FM Intrinsic Safety]Associated intrinsically safe apparatus for

    connection toClass I, II and III, Division 1, Groups A, B, C, D, E,

    F and G orClass I, Zone 0, Group II CFM Class Number 3600: 1998FM Class Number 3610: 1999

    ANSI/ISA-12.12.02: 2003

    *1: To conform to safety standards and EMCconformity standards, install 19-inch rack-mounted devices in a keyed metallic cabinet.

    *2: The analog input side of this equipment ismeasurement category 1.

    For details, see CENTUM VP InstallationGuidance (TI 33L01J10-40E).

    Subject to change without notice.

    *3: A Class A hardware device is designed for use inthe industrial environment.Please use this device in the industrialenvironment only.

    *4: A lightning arrestor or its equivalent is required tomeet this surge immunity standard.The length of the cable to feed the external power

    supply for AGS813 AO channels should notexceed 30 meters.

    *5: An external device such as a power unit withharmonic current neutralizer and an activeharmonics conditioner must be connected to meetthis harmonic current emission standard.

    *6: The specified limits of voltage drops across wiringmust be satisfied to meet this standard.

    *7: To meet the standard for hazardous locationequipment, 19-inch rack-mounted devices mustbe installed in a keyed metallic cabinet approvedby CSA or non-incendive regulator in your area.

    *8: To meet the standard for hazardous locationequipment, 19-inch rack-mounted devices mustbe installed in a keyed metallic cabinet approvedby FM or non-incendive regulator in your area.

    *9: To be compatible with Type n, the specificationrequirements of EN 61010-1 and EN 60079-15must be met, and a keyed metallic cabinet, whosedegree of protection is IP 54 or above, prescribedby IEC 60529 must be used for housing.

    Note: According to the New Approach Directive, themanufacturer and the representative office in EUare indicated below:Manufacturer: Yokogawa Electric Corporation (2-9-32 Nakacho, Musashino-shi, Tokyo 180-8750,Japan).Representative office in EU Community:Yokogawa Europe B.V. (Euroweg 2, 3825 HD

    Amersfoort, The Netherlands).

    TRADEMARKS CENTUM, Vnet/IP, DARWIN, DAQSTATION ProSafe

    and Exaopc are registered trademarks of YokogawaElectric Corporation.

    Exaplog and Exapilot are trademarks of YokogawaElectric Corporation.

    Windows is a registered trademark of MicrosoftCorporation in the United States and/or othercountries.

    Ethernet is a registered trademark of XEROXCorporation.

    Modbus is a registered trademark of SchneiderElectric and/or such related companies.

    PLC, PLC-5 and SLC500 are trademarks orregistered trademarks of Rockwell Automation, Inc.

    MELSEC and MELSEC-A are registered trademarksof Mitsubishi Electric Corporation.

    SYSMAC is a registered trademark of OmronCorporation.

    FOUNDATION of FOUNDATION fieldbus is a registeredtrademark of Fieldbus Foundation.

    Other product and company names appearing in thisdocument are trademarks or registered trademarks oftheir respective holders.