1 DataLink Technologies Gateways, Inc. www.datalink-gateways.com (360) 306-5878 / (866) 709-6390 GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup This application note provides an example of setting up RSLINX/LOGIX via the Allen Bradley Ethernet Driver to DH+. Additional information is available in the GW1000 User Manual at www.datalink-gateways.com or contact our Technical Support at (360) 306-5878 / (866) 709-6390. Set the IP address of the GW1000. Connect the GW1000 ethernet port to a switch or hub on the same network as your PC using a CAT5 network patch cord. Power on the GW1000 and wait 30 seconds for the bootup sequence to complete. Note the LAN LINK indicator LED should be on and the LAN ACTIVITY LED may be blinking. Open a web browser such as Firefox or Internet Explorer. In the address bar, type the IP address of the GW1000. (The default IP address is 192.168.1.111). (note: if you have changed the default IP address of the GW1000, enter the new address in the address bar. If you do not know the IP address programmed into the GW1000, first restore factory defaults.)

Upload: lynhi

Post on 03-Jul-2018

316 views

Category:

Documents


15 download

TRANSCRIPT

Page 1: GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup€¦ · 1 DataLink Technologies Gateways, Inc.  (360) 306-5878 / (866) 709-6390 GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup

1 DataLink Technologies Gateways, Inc. www.datalink-gateways.com (360) 306-5878 / (866) 709-6390

GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup

This application note provides an example of setting up RSLINX/LOGIX via the Allen Bradley Ethernet Driver to DH+.

Additional information is available in the GW1000 User Manual at www.datalink-gateways.com or contact our Technical Support at (360) 306-5878 / (866) 709-6390.

Set the IP address of the GW1000.

Connect the GW1000 ethernet port to a switch or hub on the same network as your PC using a CAT5 network patch cord. Power on the GW1000 and wait 30 seconds for the bootup sequence to complete. Note the LAN LINK indicator LED should be on and the LAN ACTIVITY LED may be blinking.

Open a web browser such as Firefox or Internet Explorer. In the address bar, type the IP address of the GW1000. (The default IP address is 192.168.1.111). (note: if you have changed the default IP address of the GW1000, enter the new address in the address bar. If you do not know the IP address programmed into the GW1000, first restore factory defaults.)

Page 2: GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup€¦ · 1 DataLink Technologies Gateways, Inc.  (360) 306-5878 / (866) 709-6390 GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup

2 DataLink Technologies Gateways, Inc. www.datalink-gateways.com (360) 306-5878 / (866) 709-6390

At the login prompt, type User Name “root” and Password “Netsilicon”. Please note logins and passwords are case-sensitive. If you do not see the login window appear, please see additional detail in the user manual. You may need to adjust your network settings.

The Home page is displayed...

Page 3: GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup€¦ · 1 DataLink Technologies Gateways, Inc.  (360) 306-5878 / (866) 709-6390 GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup

3 DataLink Technologies Gateways, Inc. www.datalink-gateways.com (360) 306-5878 / (866) 709-6390

Click “Network IP Settings” to display the current IP address and subnet mask...

Change the IP address and subnet mask to any values desired, and click APPLY.

If you would like to change the DH+ node address of the GW1000 at this time, click “Standard Parameters” and choose a different node address. Be sure to click APPLY.

For settings to take effect, you must click “Reboot” in the left margin and Click the “Reboot” button to confirm.

Page 4: GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup€¦ · 1 DataLink Technologies Gateways, Inc.  (360) 306-5878 / (866) 709-6390 GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup

4 DataLink Technologies Gateways, Inc. www.datalink-gateways.com (360) 306-5878 / (866) 709-6390

RSLINX Allen Bradley Ethernet Driver Setup

Open RSLINX by clicking the icon in the system tray or clicking Start -> All Programs -> Rockwell Software -> RSLINX.

Click Communications -> Configure Drivers

Choose “Ethernet devices” and click “Add New.”

Page 5: GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup€¦ · 1 DataLink Technologies Gateways, Inc.  (360) 306-5878 / (866) 709-6390 GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup

5 DataLink Technologies Gateways, Inc. www.datalink-gateways.com (360) 306-5878 / (866) 709-6390

Choose a name for the new driver, or accept the default and click OK.

Page 6: GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup€¦ · 1 DataLink Technologies Gateways, Inc.  (360) 306-5878 / (866) 709-6390 GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup

6 DataLink Technologies Gateways, Inc. www.datalink-gateways.com (360) 306-5878 / (866) 709-6390

Station Mapping

Under the “Station” column, enter the node addresses (in decimal) of all known nodes on the DH+ network. To the right of each node address, enter the IP address for the GW1000. The default node address of the GW1000 is 01 decimal and the default IP address is 192.168.1.111. For the GW1000 node, leave the “Host Name” as “Driver.”

In the following example, the GW1000 is at DH+ node 01 decimal, and there are two SLC 5/04 PLCs at nodes 02 decimal and 06 decimal. (See enclosed conversion table to convert Octal to decimal.)

Click Apply, then OK.

Page 7: GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup€¦ · 1 DataLink Technologies Gateways, Inc.  (360) 306-5878 / (866) 709-6390 GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup

7 DataLink Technologies Gateways, Inc. www.datalink-gateways.com (360) 306-5878 / (866) 709-6390

The driver is now running... Click “Close.”

Now, right-click the newly-created driver and select “Properties.”

Page 8: GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup€¦ · 1 DataLink Technologies Gateways, Inc.  (360) 306-5878 / (866) 709-6390 GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup

8 DataLink Technologies Gateways, Inc. www.datalink-gateways.com (360) 306-5878 / (866) 709-6390

Click the “Advanced Browse Tab” and check the “Force Network Type” box. Select “Data Highway Plus” from the dropdown list. Click “Apply” and then “OK.”

Page 9: GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup€¦ · 1 DataLink Technologies Gateways, Inc.  (360) 306-5878 / (866) 709-6390 GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup

9 DataLink Technologies Gateways, Inc. www.datalink-gateways.com (360) 306-5878 / (866) 709-6390

Now ensure that the DH+ connection of the GW1000 is attached to your network and verify that the DH+ LED is glowing solid GREEN. Click “Refresh” and the nodes defined in the Station Mapping Table will be displayed. (note: nodes not defined in the station mapping table will not be automatically displayed.)

Page 10: GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup€¦ · 1 DataLink Technologies Gateways, Inc.  (360) 306-5878 / (866) 709-6390 GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup

10 DataLink Technologies Gateways, Inc. www.datalink-gateways.com (360) 306-5878 / (866) 709-6390

GW1000-ABEIP RSLinx Troubleshooting

You must use the "Ethernet devices" driver, not the Ethernet/IP driver.

In the "Configure Driver" "Station Mapping" table, the word "Driver" must appear next to the

station assigned to the GW1000.

There must be an entry for each PLC station that you want to communicate with. List the IP address of the respective GW1000 in the hostname column.

The station numbers in the mapping table are in decimal, but the RsWho window displays stations in octal.

Be sure to set the Advanced Browse properties to "Force network type to DH+". (right click the driver, and select "Properties")

Page 11: GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup€¦ · 1 DataLink Technologies Gateways, Inc.  (360) 306-5878 / (866) 709-6390 GW1000-ABEIP RSLINX AB Ethernet to DH+ Setup

11 DataLink Technologies Gateways, Inc. www.datalink-gateways.com (360) 306-5878 / (866) 709-6390

Octal to Decimal Conversion Table

Octal Decimal Octal Decimal

0 00 40 321 01 41 332 02 42 343 03 43 354 04 44 365 05 45 376 06 46 387 07 47 3910 08 50 4011 09 51 4112 10 52 4213 11 53 4314 12 54 4415 13 55 4516 14 56 4617 15 57 4720 16 60 4821 17 61 4922 18 62 5023 19 63 5124 20 64 5225 21 65 5326 22 66 5427 23 67 5530 24 70 5631 25 71 5732 26 72 5833 27 73 5934 28 74 6035 29 75 61