GYPROCK STRATAWALL INTER-TENANCY WALL SYSTEMS INSTALLATION GUIDE

Upload: others

Post on 11-Oct-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

GYPROCK STRATAWALL™ INTER-TENANCY WALL SYSTEMS

INSTALLATION GUIDE

Page 2: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

CONTENTSIntroduction 2

Applications 2

System Features 2

Components 3 – 5

Design Considerations 6 – 8

System Selection 9 – 13

Installation Details 14 – 17

Junction Details 18 – 20

Penetration Details 21 – 23

Health, Safety & Guarantee 24

Contact Information 24

INTRODUCTIONThe Gyprock StrataWall™ Systems are designed to provide separating walls between units in high rise buildings.

Gyprock StrataWall™ is a range of systems characterised by a fire barrier between the finishing linings. To accommodate services, cavities are formed by separate framing on one or both sides. The finishing linings are fixed to the separate framing, or directly applied to one side of the fire barrier. The fire barrier allows the finishing linings to be installed as per normal decorative linings, and to incorporate services and penetrations.

The basis of the fire performance is the fire barrier which consists of one or two layers of 25mm Gyprock™ Shaft Liner Panel between purpose designed H-studs. The H-studs are installed between a unique folding track (patent pending) at top and bottom. The folding tracks allow the Shaft Liner Panels to be installed rapidly and with little lifting.

The basis of the acoustic performance is the insulated single or double cavity. This provides discontinuous construction for impact isolation.

Additional systems are available for:

• Higher acoustic performance.

• Security rating.

• Impact damage rating.

APPLICATIONSCSR Gyprock StrataWall™ systems are designed as non-loadbearing separating walls for Class 2 & 3 buildings that have concrete floors. Systems are available with FRL –/60/60 to FRL –/120/120 and sound ratings to meet BCA requirements.

System Features• Fire Barrier is created with one or two layers of GYPROCK

SHAFT LINER PANEL in H-studs and tracks.

• Tested fire, acoustic and structural performance.

• Unique folding wall track (patent pending), enables fast installation of fire barrier with little lifting of Shaft Liner Panels.

• Light weight system installed by a single trade.

• Systems available for wet areas.

• Services may be included in wall cavities.

FIG 1: STRATAWALL™ FOLDING TRACK AND H-STUDS

H-Stud

25mm GYPROCK Shaft Liner Panel

Fold line

Restraint tab

H-Stud

25mm GYPROCK Shaft Liner Panel

Fold line

Restraint tab

IBS rod

GYPROCK STRATAWALL™ SYSTEMS 2

Page 3: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

Gyprock™ Plasterboard CD – Recessed Edge

Features• 1.5mm recess on face side

allows formation of shallow channel for joint reinforcement.

• Provides smooth. even and continuous surface once jointed.

• 10mm and 13mm thickness.

• Manufactured to the requirements specified in AS2588 : 1998 – Gypsum Plasterboard.

• Manufactured with CD technology.

Applications• Internal walls and ceilings.

Gyprock™ Shaft Liner Panel

Features• Machine made sheet composed

of a glass fibre reinforced gypsum core encased in a heavy duty liner board.

• 25mm thick with a mass of approximately 19.8kg/m2

Applications• Fire rated separating walls and service shafts.

Gyprock Aquachek™

Features• Specially processed

plasterboard.

• Both the core and linerboard facing are treated in manufacture to withstand the effects of moisture and high humidity.

• Manufactured to the requirements specified in American Society for Testing and Materials C630.

• For use as a wall and ceiling lining in ‘wet areas’ and high moisture areas in residential and commercial applications.

• Recessed edges allow flush jointing to Recessed Edge Plasterboard.

Applications• Gyprock Aquachek™ is a suitable substrate for ceramic tiles.

• Usage areas include bathrooms, kitchens, laundries. garages and ceiling applications such as walkways and verandahs.

• The Gyprock Aquachek™ Wet Area Lining System is suitable for walls in high, medium and low risk level wet areas as defined in AS3740.

Gyprock Soundchek™

Features• Designed to provide enhanced

acoustic resistance in wall and ceiling systems.

• A machine made sheet composed of a high density gypsum core encased in a heavy duty linerboard.

• Long edges are recessed to assist in producing a smooth, even and continuous surface once jointed.

• 13mm thickness.

• Manufactured to the requirements specified in AS2588 : 1998 – Gypsum Plasterboard.

Applications• Internal walls where a higher sound rating is required.

Gyprock Fyrchek™

Features• Suitable for wall and ceiling

systems where a fire rating is to be achieved, or where acoustic performance is required.

• Composed of a specially processed glass fibre reinforced gypsum core encased in a heavy duty pink liner board.

• Long edges are recessed for flush jointing.

Applications• Fire rated walls and ceilings.

• High performance acoustic rated walls and ceilings.

COMPONENTS

Linings

CeminSeal™ Wallboard

Features• CeminSeal™ Wallboard Sheet

conforms to the requirements of AS2908.2 : 1992 ‘Cellulose-cement products Part 2: Flat sheets’. Type B, Category 3.

• Features an embedded micro waterblock technology that prevents water penetrating into the sheet, repelling water and providing a more stable sheet.

• Long edges are recessed to enable seamless jointing.

• In accordance with the Building Code of Australia, Part 3.7.1.2, Cemintel™ fibre cement sheets can be used wherever non-combustible material is required by the code.

Applications• Wet area such as bathrooms, laundries and semi-exposed ceilings and

soffits.

• Impact resistant walls.

GYPROCK STRATAWALL™ SYSTEMS 3

Page 4: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

Fire Barrier • Gyprock™ Shaft Liner Panel One or two layers in H-studs and tracks.

Fasteners• Gyprock™ Plasterboard Laminating Screw: 40mm x Nº10. for fixing plasterboard to Shaft Liner

Panels.

Order Nº Pack Qty

12215 1000

• Drill-point wafer-head screw: 10g x 16mm, for fixing H Stud to tracks.

Order Nº Pack Qty

39367 1000

40914 100

• Needle-point screw: 6g – 18 x 25mm for fixing 13mm plasterboard to

steel studs.

Order Nº Pack Qty

10606 1000

• Track fasteners: Must be steel e.g. power actuated concrete nails, flat or round head expansion anchors.

Sealants• Gyprock™ Wet Area Acrylic Sealant:

Order Nº Pack Qty

10902 450g tube

• Gyprock™ Fire Mastic:

Order Nº Pack Qty

10924 600ml tube

Promat™ IBS RodUsed at the top of the fire barrier.

Nom. Size Order Nº Length

22mmø 51632 100m

29mmø 29243 60m

NOTE: Use 22mmø rod for gaps up to 19mm.Use 29mmø rod for gaps up to 26mm.

TABLE 1: GYPROCK™ PRODUCT WEIGHTS

Colour shading behind each product approximates the colour of the product face liner sheets. For detailed sheet sizes and availability, contact the CSR Gyprock Sales Centre in your region or refer to www.gyprock.com.au

Gyprock™ Lining Products Thickness mm

Mass kg/m2

CD RECESSED EDGE10 6.5

13 8.5

CD SQUARE EDGE10 6.5

13 8.5

CD RECESSED EDGE/SQUARE EDGE 10 6.5

SUPACEIL™ 10 7.2

SOUNDCHEK™ 13 13.0

AQUACHEK™10 8.0

13 10.4

IMPACTCHEK™ 13 10.3

SUPERCHEK™ 10 10.4

EC08™ PARTITION 13 9.3

EC08™ FIRE 13 10.5

EC08™ IMPACT 13 12.1

FLEXIBLE 6.5 4.25

FYRCHEK™13 10.5

16 12.5

FYRCHEK™ MR13 10.7

16 13.5

PERFORATED SHEET 13 10.0

SHAFT LINER PANEL 25 19.8

Cemintel™ Fibre Cement Product Thickness mm

Mass kg/m2

CeminSeal™ Wallboard 9 14.3

GYPROCK STRATAWALL™ SYSTEMS 4

Page 5: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

Steel H-studGyprock StrataWall™ systems incorporate 25mm or 50mm H-studs to support the SHAFT LINER PANELS at vertical joints. They are made from 0.55mm BMT G275 galvanised steel.

Nom. Size Order Nº Length

25mm 39156 3000mm

50mm 74016 3000mm

Folding Wall TrackFolding Wall Track is used in the following applications:

• To locate and support H-studs and SHAFT LINER PANELS at the top and the bottom of wall.

• Support of SHAFT LINER PANELS at the ends of wall.

Nom. Size Order Nº Length

25mm 74014 3000mm

50mm 74015 3000mm

Fold line

Restraint tab

Slot for screw fixing (where noted)

50

5050

Fold line

Restraint tab

Slot for screw fixing(where noted)

50

5025

Insulation Product Abbreviation used in system tables

50mm Bradford Glasswool Partition batts, 450 or 600mm – 11kg/m3 50 GW Partition 11kg

75mm Bradford Glasswool Partition batts, 450 or 600mm – 11kg/m3 75 GW Partition 11kg

50mm Bradford Glasswool Partition batts, 450 or 600mm – 14kg/m3 50 GW Partition 14kg

75mm Bradford Glasswool Partition batts, 450 or 600mm – 14kg/m3 75 GW Partition 14kg

100mm Bradford Glasswool Partition batts, 450 or 600mm – 14kg/m3 100 GW Partition 14kg

110mm Bradford Glasswool Partition batts, 600mm – 11kg/m3 110 GW Partition 11kg

88mm Bradford SoundScreen R2.5 Wall batts – 30kg/m3 88mm RW SoundScreen R2.5

Tontine TSB 2 (50mm) Polyester Insulation TSB2 Polyester batts

Tontine TSB 3 (65mm) Polyester Insulation TSB3 Polyester batts

Tontine TSB 5 (85mm) Polyester Insulation TSB5 Polyester batts

Insulation

25mm

34mm

50mm

34mm

GYPROCK STRATAWALL™ SYSTEMS 5

Page 6: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

DESIGN CONSIDERATIONS

Structural DesignGyprock StrataWall™ systems are non-loadbearing. The walls are designed to BCA Specification C1.8 Clause 3.4 Walls Generally, including pressure of 0.25kPa.

Shelf loads and internal wind pressures must be determined by the project structural engineer and the studs must be designed to suit. H-studs are not suitable for shelf loading.

Wall tracks are to be fixed to the structure at 600mm maximum centres. Each fixing is to be designed for a minimum shear load of 0.75kN and to suit the design pressure.

Fire ResistanceThe Gyprock StrataWall™ systems in this manual have been tested and assessed by Warrington Fire Research in accordance with the principles of AS1530.4. They are suitable for the stated FRL when designed in accordance with the structural considerations above. Report Nº21241.

Acoustic PerformanceThe acoustic performance of wall systems is expressed in terms of Rw and Rw+Ctr. They have been assessed by Norman Disney Young (Report NºRP 02267S), and the ratings refer to expected laboratory performance. Laboratory testing to AS/NZS1276.1 has been performed by National Acoustic Laboratories. Reports ATF–1910, ATF–1912, ATF-1932.

Some systems rely on cavities that are completely filled with insulation. Contact CSR Gyprock for performance values where there is any change to the system specification. The site performance of the systems may be affected by sound flanking, the effectiveness of workmanship, and the inclusion of structural elements and bridging items. The building designer must pay special attention to airborne and structural flanking paths to minimise the difference between laboratory and field performance.

SubstitutionPlasterboard linings and barriers, and fibre cement linings, must be as specified in the system and be supplied by CSR Gyprock and Fibre Cement. No statement of performance will be provided by CSR when other product brands are used.

Wallboard & Plasterboard FixingWalls may be built to achieve a particular ‘Level of Finish’ as defined in AS/NZS2589.1. The Level of Finish specified can have requirements for frame alignment, jointing, back-blocking methods and sheet orientation. Cemintel™ Wallboard and Gyprock™ plasterboard may be installed vertically or horizontally, although for some Levels of Finish, horizontal sheeting must be used.

In wet areas, Gyprock Aquachek™ of the same thickness shall be used in lieu of Gyprock™ Plasterboard CD. Walls lined with Gyprock™ plasterboard or Cemintel™ Wallboard may be finished with tiles. For tiles greater than 32kg/m2 or over 6.5mm thickness, specific installation details apply. Refer to the appropriate installation manual.

Control JointsControl joints must be installed to allow for structural movement. Allowance for movement must be made through the frame, lining and any tiles. Refer to construction details in this guide.

Control joints must be installed at the following locations:

• At all construction joints in the building.

• At changes of the structural support system.

• At junctions with other building elements.

• At changes of the lining material.

• For walls with plasterboard outer layer – at 12m maximum centres.

• For non-tiled internal walls with fibre cement outer layer – at 7.2m maximum centres.

• For tiled internal walls with fibre cement outer layer – at 4.2m maximum centres.

Fixing & JointingRefer to publication GYP544 Gyprock™ Steel Frame Wall Systems Installation Guide for details on sheet fixing and jointing.

Refer to publication GYP546 Gyprock™ Shaft Systems for laminated service systems fixing details.

GYPROCK STRATAWALL™ SYSTEMS 6

Page 7: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES

Wall TypeWind Loading

PservicekPa

Maximum Wall Height (m)

25H55 H-studs at 600mm ctrs 50H55 H-studs at 600mm ctrs

0.25 3.0 –

or or

0.25 – 3.0

TABLE 2: MAXIMUM WALL HEIGHT WITH C-STUDS AT 600mm CENTRES – WALL SYSTEM FRL –/60/60

Wall TypeFRL–/60/60

Wind LoadingPservice

kPa

Wall Lining(both sides)

Maximum Wall Height (m) with Rondo C-Studs at 600mm centres

Stud – C64 Stud – C76 Stud – C92

0.50 0.75 1.15 0.55 0.75 0.55 0.75

0.25

13mm GYPROCK plasterboards 2.72 3.13 3.53 3.20 3.30* 3.30* 3.30*

13mm FYRCHEK 2.72 3.13 3.53 3.20 3.58 3.60* 3.60*

6 or 9mm Cemintel™ Wallboard 2.72 3.00* 3.00* 3.00* 3.00* 3.00* 3.00*

0.35

13mm GYPROCK plasterboards 2.34 2.80 3.15 2.76 3.20 3.06 3.30*

13mm FYRCHEK 2.34 2.80 3.15 2.76 3.20 3.06 3.60*

6 or 9mm Cemintel™ Wallboard 2.34 2.80 3.00* 2.76 3.00* 3.00* 3.00*

0.50

13mm GYPROCK plasterboards 1.95 2.47 2.80 2.32 2.73 2.56 2.96

13mm FYRCHEK 1.95 2.47 2.80 2.32 2.73 2.56 2.96

6 or 9mm Cemintel™ Wallboard 1.95 2.47 2.80 2.32 2.73 2.56 2.96

TABLE 3: MAXIMUM WALL HEIGHT WITH C-STUDS AT 600mm CENTRES – WALL SYSTEM FRL –/90/90 (FRL –/120/120 SYSTEMS MUST USE 13mm FYRCHEK™ BOTH SIDES AND HEIGHTS MARKED * ARE LIMITED TO 3.20m)

Wall TypeFRL –/90/90

Wind LoadingPservice

kPa

Wall Lining(both sides)

Maximum Wall Height (m) with Rondo C-Studs at 600mm centres

Stud – C64 Stud – C76 Stud – C92

0.50 0.75 1.15 0.55 0.75 0.55 0.75

0.25

13mm GYPROCK plasterboards 2.72 3.13 3.20* 3.20 3.20* 3.20* 3.20*

13mm FYRCHEK 2.72 3.13 3.30* 3.20 3.30* 3.30* 3.30*

6 or 9mm Cemintel™ Wallboard 2.72 3.00* 3.00* 3.00* 3.00* 3.00* 3.00*

0.35

13mm GYPROCK plasterboards 2.34 2.80 3.15 2.76 3.20 3.06 3.20*

13mm FYRCHEK 2.34 2.80 3.15 2.76 3.20 3.06 3.30*

6 or 9mm Cemintel™ Wallboard 2.34 2.80 3.00* 2.76 3.00* 3.00* 3.00*

0.50

13mm GYPROCK plasterboards – 2.47 2.80 2.32 2.73 2.56 2.96

13mm FYRCHEK – 2.47 2.80 2.32 2.73 2.56 2.96

6 or 9mm Cemintel™ Wallboard – 2.47 2.80 2.32 2.73 2.56 2.96

NOTES for Tables 1, 2 and 3:• Height marked with * are limited by the 50mm H-stud.• Deflection limit is Span/240 to a maximum of 30mm, in accordance

with BCA Specification C1.8.• Refer to table 5 for nogging requirements.• Tabulated heights do not include axial loads (except self weight) or

shelf loading.

• Loadings: Pultimate = 0.375 kPa, Pservice = 0.25 kPa.Pultimate = 0.525 kPa, Pservice = 0.35 kPa.Pultimate = 0.750 kPa, Pservice = 0.50 kPa.

• Walls are not for external applications. • All loadings in accordance with AS1170:2002.• Walls analysed in accordance with AS4600:1996.

GYPROCK STRATAWALL™ SYSTEMS 7

Page 8: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

TABLE 5: MINIMUM NUMBER OF NOGGINGSLining Configuration Wall Height (m) Rows of Noggings

Lined One Side0.0 – 3.0 1

3.0 – 6.0 2

NOTE: Noggings in accordance with Table 5, are in addition to head nogging track required in Rondo stud wall systems, and are to be equally spread over the wall.

TABLE 4: MAXIMUM PERMITTED WALL HEIGHT/WIDTH FOR LAMINATED SERVICES SYSTEMS. (LOAD UDL = 0.35 kPa).

System Nº

Wall Height (maximum)

2400 3000 3600 7200

Wall Width (maximum)

CSR967–S 1200 1200 1200 NA

CSR968–S 1200 1200 1200 1200

CSR967–SA 2200 2100 2000 NA

CSR968–SA 3100 2700 2600 1200

CSR969–SA 4200 3200 3000 NA

–S = Screw ONLY plasterboard fixing–SA = Screw and Adhesive plasterboard fixingNA = Not Applicable

FIG 2: HEAD NOGGING DETAIL FOR RONDO C-STUD WALLS

100mm max. to Head Nogging Track

100mm max. to first row of fasteners

Head nogging track required by RONDO in C-stud walls lined one side. (In addition to noggings required in Table 5).

GYPROCK STRATAWALL™ SYSTEMS 8

Page 9: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

StrataWall™ – Single Cavity

SYSTEM SELECTION

• Intertenancy Walls • Corridors • Wet Area Options • Narrow Footprint

SYSTEM SPECIFICATION TYPICAL LAYOUT (CSR 222a shown) ACOUSTICOPINION

orTEST

① Test ATF 1912

② Test ATF 19322

OpinionRP 02267S

Discontinuous Construction

• Lining material as per system table laminated to Shaft Liner Panel.

• 2 x 25mm GYPROCK Shaft Liner Panel in H-studs at 600mm maximum centres.

• Minimum 12mm gap.

• Steel studs at 600mm maximum centres.

• Cavity insulation as per system table.

• Lining material as per system table, fixed to studs.

FRLReport/Opinion

SYSTEM Nº

WALL LININGSGAP + STUD DEPTH mm 76 100

CAVITY INFILL (Refer to Components) Rw / Rw+Ctr

–/120/120

WFRA 21241

CSR 222SHAFT LINER PANEL SIDE

• 1 x 13mm GYPROCK plasterboard CD.

STUD SIDE

• 1 x 13mm GYPROCK plasterboard CD.

(a) Nil

(b) 75 GW Partition 11kg

(c) 100 GW Partition 14kg

(d) TSB5 Polyester batts

52/44

56/48①

56/48

53/45

59/51②

WALL THICKNESS mm 153 177

–/120/120

WFRA 21241

CSR 223SHAFT LINER PANEL SIDE

• 1 x 13mm GYPROCK plasterboard CD.

STUD SIDE

• 1 x 13mm GYPROCK SOUNDCHEK.

(a) Nil

(b) 75 GW Partition 11kg

(c) 100 GW Partition 14kg

(d) TSB5 Polyester batts

53/45

58/50

58/50

54/46

59/51

WALL THICKNESS mm 153 177

WET AREA SYSTEMS

–/120/90

WFRA 21241

CSR 225 SHAFT LINER PANEL SIDE

• 1 x 13mm GYPROCK plasterboard CD.

STUD SIDE

• 1 x 6mm CeminSeal™ Wallboard.

(a) Nil

(b) 75 GW Partition 11kg

(c) 100 GW Partition 14kg

(d) TSB5 Polyester batts

53/45

58/50

58/50

53/45

58/50

WALL THICKNESS mm 146 170

–/120/90

WFRA 21241

CSR 226SHAFT LINER PANEL SIDE

• 1 x 13mm GYPROCK plasterboard CD.

STUD SIDE

• 1 x 9mm CeminSeal™ Wallboard.

(a) Nil

(b) 75 GW Partition 11kg

(c) 100 GW Partition 14kg

(d) TSB5 Polyester batts

54/46

59/51

59/51

55/47

60/52

WALL THICKNESS mm 149 173

GYPROCK STRATAWALL™ SYSTEMS 9

Page 10: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

StrataWall™ – Services Cavity

• Intertenancy Walls • Additional Services Cavity • Medium Footprint

SYSTEM SPECIFICATION TYPICAL LAYOUT (CSR 230 shown) ACOUSTIC OPINION

orTEST

OpinionRP 02267S

Discontinuous Construction

• Lining material as per system table fixed to furring channels.

• Cavity insulation as per system table.

• Furring channel fixed to all H-studs with Rondo Beta Fix Clips at 600mm max.vertical centres, in 50mm cavity.

• 2 x 25mm GYPROCK Shaft Liner Panel in H-studs at 600mm maximum centres.

• 20mm gap.

• Steel studs at 600mm maximum centres.

• Cavity insulation as per system table.

• Lining material as per system table, fixed to studs.

FRLReport/Opinion

SYSTEM Nº

WALL LININGSSTUD DEPTH mm 64 92

CAVITY INFILL (Refer to Components)Rw / Rw+Ctr

STUD CAVITY FURRING CAVITY

–/120/120

WFRA 21241

CSR 230STUD SIDE

• 1 x 13mm GYPROCK plasterboard CD.

FURRING CHANNEL SIDE

• 1 x 13mm GYPROCK plasterboard CD.

(a) 75 GW Partition 11kg 50 GW Partition 11kg 60/50 60/50

(b) 100 GW Partition 14kg 50 GW Partition 11kg 61/51 61/51

(c) TSB5 Polyester batts TSB2 Polyester batts 60/50 60/50

MINIMUM WALL THICKNESS mm 211 239

–/120/120

WFRA 21241

CSR 231STUD SIDE

• 1 x 13mm GYPROCK SOUNDCHEK.

FURRING CHANNEL SIDE

• 1 x 13mm GYPROCK SOUNDCHEK.

(a) 75 GW Partition 11kg 50 GW Partition 11kg 62/53 62/53

(b) 100 GW Partition 14kg 50 GW Partition 11kg 62/53 62/53

(c) TSB5 Polyester batts TSB2 Polyester batts 61/52 62/53

MINIMUM WALL THICKNESS mm 211 239

WET AREA SYSTEMS

–/120/120

WFRA 21241

CSR 235STUD SIDE

• 1 x 13mm GYPROCK AQUACHEK.

FURRING CHANNEL SIDE

• 1 x 13mm GYPROCK AQUACHEK.

(a) 75 GW Partition 11kg 50 GW Partition 11kg 60/50 60/50

(b) 100 GW Partition 14kg 50 GW Partition 11kg 61/51 61/51

(c) TSB5 Tontine Polyester TSB2 Tontine Polyester 60/50 60/50

MINIMUM WALL THICKNESS mm 211 239

GYPROCK STRATAWALL™ SYSTEMS 10

Page 11: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

StrataWall™ – Double Cavity

• Intertenancy Walls • Services Both Sides • Wet Area Options • High Acoustic Performance

SYSTEM SPECIFICATION TYPICAL LAYOUT (CSR 240a shown) ACOUSTIC OPINION

or TEST

OpinionRP 02267S

Discontinuous Construction

• Lining material as per system table fixed to studs – Side 1.

• Steel studs at 600mm maximum centres.

• Cavity insulation as per system table.

• 20mm gap.

• 2 x 25mm GYPROCK Shaft Liner Panel in H-studs at 600mm maximum centres.

• 20mm gap.

• Cavity insulation as per system table.

• Steel studs at 600mm maximum centres

• Lining material as per system table fixed to studs – Side 2.

FRLReport/Opinion

SYSTEM Nº

WALL LININGSSTUD DEPTH mm 64 76

CAVITY INFILL (Refer to Components) Rw / Rw+Ctr

–/120/120

WFRA 21241

CSR 240

SIDE 1 AND 2

• 1 x 13mm GYPROCK plasterboard CD.

(a) Nil

(b) 75 GW Partition 11kg - both sides

(c) 100 GW Partition 14kg - both sides

(d) TSB5 Polyester - both sides

58/47

62/53

62/53

58/47

62/53

63/54

62/53

MINIMUM WALL THICKNESS mm 245 269

–/120/120

WFRA 21241

CSR 241

SIDE 1 AND 2

• 1 x 13mm GYPROCK SOUNDCHEK.

(a) Nil

(b) 75 GW Partition 11kg - both sides

(d) TSB5 Polyester - both sides

59/48

64/55

63/54

60/49

65/56

63/54

MINIMUM WALL THICKNESS mm 245 269

WET AREA SYSTEMS

–/120/120

WFRA 21241

CSR 243

SIDE 1 AND 2

• 1 x 13mm GYPROCK AQUACHEK.

(a) Nil

(b) 75 GW Partition 11kg - both sides

(c) 100 GW Partition 14kg - both sides

(d) TSB5 Polyester - both sides

58/47

62/53

62/53

58/47

63/54

63/54

63/54

MINIMUM WALL THICKNESS mm 245 269

–/60/60

SF 45743

CSR 244

SIDE 1 AND 2

• 1 x 9mm CeminSeal™ Wallboard.

(b) 75 GW Partition 11kg - both sides

(c) 100 GW Partition 14kg - both sides

62/53

62/53

63/54

MINIMUM WALL THICKNESS mm 237 261

GYPROCK STRATAWALL™ SYSTEMS 11

Page 12: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

StrataWall™ – Double Cavity (25mm Fire Barrier)

• Intertenancy Walls • Low Cost • Double Cavity • 3.0m Maximum Wall Height

SYSTEM SPECIFICATION TYPICAL LAYOUT (CSR 100 shown) ACOUSTIC OPINION

PKA-052

Discontinuous Construction

• Lining material as per system table.

• Steel studs at 600mm maximum centres.

• Cavity insulation as per system table.

• 20-40mm separation between frame and GYPROCK SHAFT LINER PANEL.

• 25mm GYPROCK SHAFT LINER PANEL between steel H-studs at 600mm maximum centres.

• 20-40mm separation between frame and GYPROCK SHAFT LINER PANEL.

• Cavity insulation as per system table.

• Steel studs at 600mm maximum centres.

• Lining material as per system table.

FRLReport/Opinion

SYSTEM Nº

WALL LININGSSTUD DEPTH mm 64 76

CAVITY INFILL (Both Sides)(Refer to Components)

Rw / Rw+Ctr

60/60/60

EWFA 45743

CSR 100

BOTH SIDES

• 2 x 10mm GYPROCK Plasterboard CD.

(a) 75 GW Partition 14kg

(b) 110 GW Partition 11kg

(c) 88 RW Soundscreen R2.5

60/48

62/50

61/49

61/49

62/50

62/50

MINIMUM WALL THICKNESS mm 257 289

60/60/60

EWFA 45743

CSR 101

BOTH SIDES

• 2 x 13mm GYPROCK Plasterboard CD.

(a) 75 GW Partition 14kg

(b) 110 GW Partition 11kg

(c) 88 RW Soundscreen R2.5

62/50

63/52

63/51

62/51

63/52

63/52

MINIMUM WALL THICKNESS mm 269 301

60/60/60

EWFA 45743

CSR 102

BOTH SIDES

• 1 x 13mm GYPROCK SOUNDCHEK.

(a) 75 GW Partition 14kg

(b) 110 GW Partition 11kg

(c) 88 RW Soundscreen R2.5

60/48

62/50

61/49

61/49

62/50

62/50

MINIMUM WALL THICKNESS mm 243 275

WET AREA SYSTEMS

60/60/60

EWFA 45743

CSR 103

BOTH SIDES

• 1 x 6mm CeminSeal™ Wallboard.

• 1 x 10mm GYPROCK AQUACHEK.

(a) 75 GW Partition 11kg

(b) 75 GW Partition 14kg

(c) 88 RW Soundscreen R2.5

61/49

62/50

63/51

61/50

62/51

63/52

MINIMUM WALL THICKNESS mm 249 281

GYPROCK STRATAWALL™ SYSTEMS 12

Page 13: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

• Services Systems

SYSTEM SPECIFICATION TYPICAL LAYOUT ACOUSTIC OPINION

orTEST

RP 02267S

• 2 x 25mm GYPROCK SHAFT LINER PANEL between steel H-studs at 600mm maximum centres.

• Lining material as per system table laminated to Shaft Liner Panel.

FRLReport/Opinion

SYSTEM Nº

WALL LININGS CAVITY INFILL Rw/Rw + Ctr

–/90/30

WFRA 21241CSR 248

FACE SIDE

• 1 x 13mm GYPROCK Plasterboard CD.

(a) Nil 36/33

WALL THICKNESS mm 64

–/120/90

WFRA 21241CSR 249

FACE SIDE

• 1 x 13mm GYPROCK FYRCHEK.

(a) Nil 36/33

WALL THICKNESS mm 64

StrataWall™ – Services Systems

Steel Frame Laminated Services Systems

SYSTEM SPECIFICATION TYPICAL LAYOUT ACOUSTIC OPINION

orTEST

PKA-A025

• Perimeter framing 25/50 x 50 x 0.7mm BMT steel angle.

• 3 x GYPROCK FYRCHEK laminated with screws and/or

adhesive.

FRLReport/Opinion

SYSTEM Nº

WALL LININGS CAVITY INFILL Rw

–/90/90

RIR 21898

CSR 967S

• 3 x 13mm GYPROCK FYRCHEK plasterboard.

(a) Nil 35

WALL THICKNESS mm 39

–/120/120

RIR 21898

CSR 968S

• 3 x 16mm GYPROCK FYRCHEK plasterboard.

(a) Nil 36

WALL THICKNESS mm 48

GYPROCK STRATAWALL™ SYSTEMS 13

Page 14: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

INSTALLATION DETAILSFIG 3: STRATAWALL™ INSTALLATION STEPS 1, 2, 3

Install Folding Track to floor, soffit, and end wall

Install Shaft Liner Panels

Install H-Studs to restraint tabs in head and foot tracks 1

1

2

3

FIG 4: STRATAWALL™ INSTALLATION STEPS 4, 5

Fold track

5

Fold track

5

Install IBS Rod4

FIG 5: STRATAWALL™ INSTALLATION STEPS 6, 7, 8

Install stud frame or furring channel as per system specifications

6

Install wall linings as per system specifications to outer sides of the wall system

8

8

Install insulation

7

FIG 6: LAMINATING DETAIL – PLASTERBOARD TO SHAFT LINER PANEL

600mm StrataWall Module

30mm

100mm30mm

100mm

400mm

1200mm outer layerof Plasterboard

400mm

GYPROCK STRATAWALL™ SYSTEMS 14

Page 15: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

FIG 7: HEAD & BASE DETAIL – SINGLE CAVITY –C-STUDS ONE SIDE

Steel studs

Flexible sealant

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

IBS rod

15mm deflection gap nom.

Refer to system table for wall liningand insulation

Concrete slab

100mm max. to first row of lining fasteners

Gyprock Fire Mastic to seal all gaps above folding wall track where slab is uneven

100mm max. to head nogging track required in Rondo C-stud walls

Folding Wall Track

FIG 8: HEAD & BASE DETAIL – SERVICES CAVITY –C-STUDS ONE SIDE, FURRING CHANNEL ONE SIDE

Steel studs

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Rondo Beta Fix Clip at 600mm max vertical centres on every H-Stud

Furring channel

IBS rod

Concrete slab

Refer to system table for wall lining and insulation

Flexible sealant

Gyprock Fire Mastic to seal all gaps above folding wall track where slab is uneven

100mm max. to head nogging track required in Rondo C-stud walls

Screw fix folding wall track to all H-studs through slotted holes

15mm deflection gap nom.

100mm max. to first row of lining fasteners

Folding Wall Track

Steel studs

Flexible sealant Flexible

sealant

Concrete slab

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Gyprock Fire Mastic to seal all gaps under steel angle where slab is uneven

Laminating screws

Refer to system table for wall lining and insulation

Folding Wall Track

Steel studs

Flexible sealant Flexible

sealant

Concrete slab

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Gyprock Fire Mastic to seal all gaps under steel angle where slab is uneven

Rondo Beta Fix Clip

Furring channel

Refer to system table for wall liningand insulation

Screw fix folding wall track to all H-studs through slotted holes

GYPROCK STRATAWALL™ SYSTEMS 15

Page 16: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

FIG 9: HEAD & BASE DETAIL – DOUBLE CAVITY – C-STUDS TWO SIDES

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Steel studs

Concrete slab

Refer to system table for wall liningand insulation

Flexible sealant

Gyprock Fire Mastic to seal all gaps above folding wall track where slab is uneven

Folding Wall Track

100mm max. to head nogging track required in Rondo C-stud walls

10mm deflection gap nom.

100mm max. to first row of lining fasteners

FIG 10: HEAD & BASE DETAIL – SINGLE LAYER FIRE BARRIER – C-STUDS TWO SIDES

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Steel studs

Concrete slab

Refer to system table for wall liningand insulation

Flexible sealant

Gyprock Fire Mastic to seal all gaps above folding wall track where slab is uneven

Folding Wall Track

IBS rod

100mm max. to head nogging track required in Rondo C-stud walls

15mm deflection gap nom.

100mm max. to first row of lining fasteners

Steel studs

Flexible sealant Flexible

sealant

Concrete slab

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Gyprock Fire Mastic to seal all gaps under steel angle where slab is uneven

Refer to system table for wall liningand insulation

Folding Wall Track

Steel studs

Flexible sealant Flexible

sealant

Concrete slab

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Gyprock Fire Mastic to seal all gaps under steel angle where slab is uneven

Refer to system table for wall liningand insulation

Folding Wall Track

GYPROCK STRATAWALL™ SYSTEMS 16

Page 17: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

TABLE 6: REDUCED FRL FOR HEAD DETAILS FIG 11 & 12 (I.E. WITHOUT IBS ROD)System Number Head Detail FRL

CSR 225CSR 226 FIG 11 –/60/60

CSR 222CSR 223 FIG 11 –/90/90

CSR 230CSR 231CSR 235

FIG 12 –/90/90

FIG 13: HEAD & BASE DETAIL – SERVICES SYSTEM

Folding wall track (fold this side)

25mm GYPROCK SHAFT LINER PANEL with 50mm H-studs at vertical panel joints

IBS rod

15mm deflection gap nom.

Refer to system table for wall lining

Concrete slab

SHAFT SIDE

100mm max. to first row of laminating screws

Gyprock Fire Mastic to seal all gaps under folding head track where slab is uneven

Flexible sealant

Concrete slab

25mm GYPROCK SHAFT LINER PANEL with 50mm H-studs at vertical panel joints

Gyprock Fire Mastic to seal all gaps under steel angle where slab is uneven

Laminating screws

SHAFT SIDE

Refer to system table for wall lining

FIG 11: ALTERNATIVE HEAD DETAIL – SINGLE CAVITY – C-STUDS ONE SIDE (REDUCED FRL)

Steel studs

Flexible sealant

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

10mm deflection gap nom.

Refer to system table for wall lining and insulation

Concrete soffit

100mm max. to first row of lining fasteners

Gyprock Fire Mastic to seal all gaps above folding wall track where slab is uneven

100mm max. to head nogging track required in Rondo C-stud walls

Folding Wall Track

FIG 12: ALTERNATIVE HEAD DETAIL – SERVICES CAVITY – C-STUDS ONE SIDE, FURRING CHANNEL ONE SIDE (REDUCED FRL)

Steel studs

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Rondo Beta Fix Clip at 600mm max vertical centres on every H-Stud

Furring channel

Concrete soffit

Refer to system table for wall liningand insulation

Flexible sealant

Gyprock Fire Mastic to seal all gaps above folding wall track where slab is uneven

100mm max. to head nogging track required in Rondo C-stud walls

Screw fix folding wall track to all H-studs through slotted holes

10mm deflection gap nom.

100mm max. to first row of lining fasteners

GYPROCK STRATAWALL™ SYSTEMS 17

Page 18: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

JUNCTION DETAILSFIG 14: TYPICAL JUNCTION OF STRATAWALL™ WITH MASONRY WALL

Folding wall track

H-Stud

Steel studs

UNIT 1 UNIT 2

Flexible Sealant Flexible

Sealant

Masonry Wall

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Gyprock Fire Mastic to seal all gaps under steel angle where slab is uneven

Refer to system table for wall liningand insulation

Refer to system table for wall liningand insulation

FIG 16: CORNER DETAIL FOR STRATAWALL™

Steel studs

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints and folding wall track top and bottom

Folding wall track

Pan head screws at 600mm centres

Tape and set corner

Refer to system table for wall liningand insulation

Laminating screws

External angle bead and set

FIG 15: TYPICAL JUNCTION OF STRATAWALL™ WITH CORRIDOR WALL.

H-Stud

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Tape and set wall joints

Plasterboard screws at 600mm centres

GYPROCK Plasterboard CD

CSR Gyprock Fire Mastic

GYPROCK FYRCHEK Plasterboard to suit fire and sound requirement

UNIT 1 UNIT 2

CORRIDOR

FIG 17: CORNER DETAIL FOR STRATAWALL™

Tape and set corner

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints and folding wall track top and bottom

Refer to system table for wall liningand insulation

Pan head screws at 600mm centres

External angle bead and set

GYPROCK STRATAWALL™ SYSTEMS 18

Page 19: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

FIG 18: JUNCTION OF STRATAWALL WITH NON-FIRE RATED WALLS

H-Stud

Tape and set wall joints

Refer to system table for wall lining and insulation

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

UNIT 1

UNIT 2

UNIT 1

UNIT 2

FIG 20: HEAD AND JAMB DETAIL FOR TRAFALGAR E-CORE DOOR INSTALLATION (–/120/30 FRL)

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Trafalgar door frame backfilled to test details RIR2124104

Refer to system table for plasterboard wall lining and insulation

38mm (nom) Trafalgar E core door with acoustic sealing to manuafcturer’s detail

Door Closer

FIG 19: CONTROL JOINT DETAIL (FRL –/120/120)

Gyprock Fire Mastic as acoustic sealant

15mm min.Refer to system table for wall liningand insulation

Backing rod

Rondo P35 control joint

Rondo P35 control joint

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

SIDE ELEVATION VIEW

PLAN VIEW

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Trafalgar door frame backfilled to test details RIR2124104

Refer to system table for plasterboard wall lining and insulation

Refer to system table for plasterboard wall lining and insulation

38mm (nom) Trafalgar E core door with acoustic sealing to manuafcturer’s detail

GYPROCK STRATAWALL™ SYSTEMS 19

Page 20: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

FIG 21: TYPICAL DETAIL AT JUNCTION OF STRATAWALL™ AND ROOF

Gyprock ceiling to system specifications

Cornice or tape and set finish

Wall track fixed to studs

Bradford insulation to system specifications

Bradford Rockwool

Refer to system table for wall liningand insulation

FIG 22: TYPICAL DETAIL FOR BALCONY DIVIDING WALL – PLAN VIEW

H-Stud

Refer to system table for wall lining and insulation

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Framing designed for site wind loads

Exterior cladding system

Exterior cladding system

Exterior cladding system

Folding wall track

UNIT 1 BALCONY

UNIT 2 BALCONY

UNIT 1 INTERIOR

UNIT 2 INTERIOR

GYPROCK STRATAWALL™ SYSTEMS 20

Page 21: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

PENETRATION DETAILS

FIG 23: PLUMBING SERVICES IN STUD WALL ONE SIDE (FRL –/120/120)

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Refer to system table for wall liningand insulation

Taps arranged vertically, mixer, shower rose or GPO’s

Flexible sealant

Gyprock Silencer

FIG 24: PLUMBING SERVICES IN FIRE BARRIER SIDE (FRL AS NOTED)

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Refer to system table for wall liningand insulation

NOTE: 200mm wide strip of GYPROCK FYRCHEK fixed at 200mm centres.

(For FRL -/60/60 1 x 16mm FYRCHEK).

(For FRL -/120/120 1 x 25mm SHAFT LINER PANEL)

Flexible sealant

Gyprock Silencer

Taps, mixer, shower rose or GPO’s

FIG 25: PLUMBING SERVICES IN FURRING CHANNEL CAVITY (FRL –/60/60)

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Refer to system table for wall liningand insulation

Taps, mixer, shower rose or GPOs

12mm plywood fixed to H-studs for tap fixings

Rondo Beta-Fix clip and furring channel

Flexible sealant

FIG 26: PLUMBING OR ELECTRICAL SERVICES IN STUD WALL TWO SIDES (FRL –/90/90)

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Refer to system table for wall liningand insulation

Flexible sealant

Taps, mixer, shower rose or GPO’s

GYPROCK STRATAWALL™ SYSTEMS 21

Page 22: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

FIG 27: BATHS BACK-TO-BACK IN STUD WALL ONE SIDE (FRL –/90/90)

BathBath

Additional layer of GYPROCK AQUACHEK

Refer to system table for wall lining and insulation

Refer to system table for wall lining and insulation

Additional layer of GYPROCK AQUACHEK

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

FIG 29: PVC PIPE THROUGH STRATAWALL™

(FRL –/120/30) NOTE: System acoustic performance may be reduced.

Refer to system table for wall liningand insulation

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

100mm max. PVC pipe

3-4mm Promaseal sealant

FCW Promaseal wall collar

Ceiling

FIG 30: COPPER OR STEEL PIPE THROUGH STRATAWALL™ (FRL – REFER TO BCA SPEC C3.15)NOTE: System acoustic performance may be reduced.

152mmmax.

Refer to system table for wall liningand insulation

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Gyprock Fire Mastic

Copper or steel pipe

30mm min

Backing rodAcoustic sealant

Ceiling

FIG 28: INSTALLATION OF LORIENT LVH-O FIRE DAMPER (FRL –/120/–)NOTE: System acoustic performance may be reduced.

Refer to system table for wall lining and insulation

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Backing rod where required

Lorient LVH-O type damper supplied in spigot available from 100mm to 450mm diameter, weight 5.95kg max.

Spigot to terminate with break away joint as detailed in AS1882.2

Two 35 x 35mm Rondo angles mechanically fixed to studs with Nº6 Type ‘S’ drill point screws

6 to 12mm perimeter gaps sealed with Gyprock Fire Mastic, or 12 to 20mm perimeter gaps filled with backing rod and Gyprock Fire Mastic min. 20mm deep

Steel H-studs at 600mm centres

GYPROCK STRATAWALL™ SYSTEMS 22

Page 23: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

FIG 31: GPO/SWITCH INSTALLATION IN FURRING CHANNEL SIDE WITH PENETRATION THROUGH FIRE WALL (FRL –/120/90)

Steel studs

Gyprock Fire Mastic to seal penetration min. 25mm depth

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Rondo Beta Fix Clip at 600mm max vertical centres on every H-Stud

Furring channel Refer to system

table for wall lining and insulation

Refer to system table for wall lining and insulation

Standard GPO or switch

FIG 32: CABLE PENETRATION THROUGH FIRE BARRIER (FRL –/120/30)

Refer to system table for wall liningand insulation

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Cable, up to 3 x twin flex

Gyprock Fire Mastic 30mm min. depth in Shaft Liner Panel

38mm max. ø

FIG 33: GPO/SWITCH INSTALLATION IN STUD WALL (FRL –/120/90)

Refer to system table for wall lining and insulation

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

NOTE: Offset penetration minimum of 600mm on opposite sides of the wall

Acoustic rated GPO or switch

FIG 34: GPO/SWITCH AND PENETRATION IN FIRE BARRIER (FRL –/120/90)

Refer to system table for wall lining and insulation

25mm GYPROCK SHAFT LINER PANEL with steel H-studs at vertical panel joints

Standard GPO or switch

Gyprock Fire Mastic to seal penetration min. 25mm depth NOTE: Offset

penetration minimum of 600mm on opposite sides of the wall

FIG 35: GPO/SWITCH INSTALLATION IN GYPROCK SILENCER™ (FRL –/120/90)

H-Stud

Refer to system table for wall liningand insulation

Gyprock Silencer™

SHAFT LINER PANEL with steel H-studs at vertical panel joints

Optional hole for cable 25mm ø max.

Optional hole for cable 25mm ø max. Standard

GPO or switch NOTE: Gyprock Silencer™ may be vertical

and accommodate multiple services

GYPROCK STRATAWALL™ SYSTEMS 23

Page 24: GYPROCK STRATAWALL INTER-TENANCY WALL ......TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES Wall Type Wind Loading Pservice kPa Maximum Wall Height (m) 25H55 H-studs at

GYP949 February 2012CSR Gyprock, CSR Building Products A.B.N. 55 008 631 356.The following are trade marks of CSR Limited and are under license. CSR™, Gyprock™, Soundchek™, Aquachek™, Fyrchek™, CeminSeal™, Bradford™, designLINK™. GYP949.BMS9851.0212

Health & SafetyInformation on any known health risks of our products and how to handle them safely is on their package and/or the documentation accompanying them.

Additional information is listed in the Material Safety Data sheet. To obtain a copy, telephone 1800 807 668.

WarrantyGyprock™ products are manufactured for life, with all CSR products designed to achieve optimal performance when part of a CSR integrated system.

Gyprock™ continues to lead the market with premium quality products which are the preferred choice of plastering professionals.

Gyprock™ plasterboard products are manufactured to the Australian Standard AS2588 providing confi dence in quality of product and support. For details on our product warranty, please log onto www.gyprock.com.au, or contact us on 1300 306 556.

Contact DetailsCSR Gyprock™ Web Site

www.gyprock.com.au

CSR Gyprock Sales Support

Telephone: 13 17 44Facsimile: 1800 646 364

CSR designLINK™ Technical Support Service

Telephone: 1800 621 117Facsimile: 1800 069 904Email: [email protected]

New South Wales and ACT

376 Victoria Street, Wetherill Park NSW 2164

Queensland

768 Boundary Road, Coopers Plains QLD 4108

Victoria

277 Whitehall Street, Yarraville VIC 3013

South Australia

Lot 100 Sharp Court, Mawson Lakes SA 5095

Western Australia

21 Sheffi eld Road, Welshpool WA 6106

Tasmania

PO Box 61, Glenorchy TAS 7010

Northern Territory

Cnr Stuart Hwy & Angliss St, Berrimah NT 0828

MAN

UFACTURED

FOR LIFE