hadeed standards
DESCRIPTION
Engineering Standards for HADEED, Saudi ArabiaTRANSCRIPT
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 1 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
FFIIRREE PPRROOTTEECCTTIIOONN SSYYSSTTEEMM
GGEENNEERRAALL SSPPEECCIIFFIICCAATTIIOONN
RREEQQUUIIRREEMMEENNTTSS
FFOORR
HHAADDEEEEDD
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 2 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
TABLE OF CONTENTS
1. INTRODUCTION 3
2. SCOPE OF WORK 3
A. GENERAL 3
B. COMPLETENESS OF WORK 4
C. PROJECT OBJECTIVE 4
D. SCOPE OF WORK ACTIVITIES 5
3. MAINTENANCE 10
4. MATERIAL DELIVERY, STORAGE & PROTECTION 10
5. SUBMITTALS 10
6. TEST AND ACCEPTANCE 15
7. WORKMANSHIP, MATERIAL AND INSPECTION 15
8. PAINTING AND PACKAGING 15
9. SAFETY DEVICES 15
10. ELECTRICAL EQUIPMENT CRITERIA 15
11. WARRANTY 16
12. FIRE PROTECTION SYSTEM 16
12.1 PREVENTIVE FIRE SAFEY MEASURES
12.2 FIRE FIGHTING SYSTEM 17
13. CODES AND STANDARDS 55
14. APPROVAL AND CERTIFICATIONS 56
15. APPENDIX A 57
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 3 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
1. INTRODUCTION
HADEED TSD SFM/ ISD Fire Section intended to cover the unprotected areas as well
as to upgrade the existing systems and new constructions to assure Fire Safety and
Fire Loss Prevention. It is important to insure that the safety measures shall be
imparted to avoid any probable loss or fire accident in the entire plant.
The reviewed documents provided for the construction of HADEED as per at HADEED,
the Industrial Security Department (TSD SFM/ ISD ) Fire Section requirement is
accordingly define the needs and necessity of the fire protection coverage criteria
based on the APPENDIX A (System to be installed). Other unforeseen hazard areas
not included in the APPENDIX A shall be identified by the contractor and notify the
TSD SFM/ ISD Fire Section to extend verification of applicable fire protection
constituents to complete the overall design.
Further, the Contractor shall conduct a site survey to observe the existing system
and to report independently and define the corresponding requirements for the Life
Safety and Lost Prevention in accordance with National Fire Code (NFC) of the
proposed project.
The Contractor shall be solely responsible for the technical completeness and
accuracy of all contract documents and taking due account of preference codes and
standards being practice in HADEED with TSD SFM/ ISD Fire Section Guidelines
TSD SFM/ ISD Fires Section has the intention to proceed with various type of fire
protection in accordance with National Fire Protection Association (NFPA) codes and
standards to be applied in the premises and find out the most effective system(s).
However, TSD SFM/ ISD Fire Section defined an outlined schedule with the required
protection system, and the final design will be upon approved site survey and
research report conducted by the Contractor that will be included in the applicable
system schedule. (See Appendix A)
2. SCOPE OF WORK
A. GENERAL
The Fire Protection Design shall be undertaken on a turn-key basis, which means
that CONTRACTOR shall provide a total overall solution for supply, installation and
commissioning of systems as per HADEED requirements. The requirements shall be
based on the conducted site survey for proper application, design and engineering
with proper application, equipment and materials supply, installation and
construction, testing and commissioning, training and familiarization of the proposed
fire protection systems in accordance with NFPA and appropriate outlined HADEED
Site Condition & Engineering Standards as life safety and loss prevention.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 4 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Any future advances in fire protection technology shall be reviewed by the HADEED
TSD SFM/ ISD on an on-going basis and probably incorporated into this specification
if proven appropriate for HADEED Fire Protection Requirements.
B. COMPLETENESS OF WORK
The conceptual drawings and the brief specifications are based on the ultimate
requirements and end use of the facilities. The requirements shall be reviewed and if
any changes due to technical/environmental requirements shall be incorporated in
accordance to an official approval of the concerned department. Changes due to
detailed calculations and design shall be included.
The work shall be completed in the services to be provided by the contractor but not
limited to the following:
1. Provide wherever it is required.
2. Perform/do wherever it is to be done.
3. Design wherever it needs to be designed.
4. Inspect and test wherever necessary to be inspected and tested.
5. Provide spare parts/spares wherever.
6. Investigate and study wherever needed.
7. Dispose of it wherever necessary.
8. Provide special treatment wherever needed.
The scope of works, specifications and drawings provide technical and other details
that shall be followed in the design and execution of the work. These details cover a
range from general to specific of work upon completion.
However, this is only serve as reference and guide specifications and not detailed or
construction specification, but are the basis for the same. The additional details
necessary to actually complete all works shall be determined, filled out and specified
by the contractor.
C. PROJECT OBJECTIVES
The following objectives shall include but not limited:
1. Provide a first rate quality system project in all respect
2. All works shall be in accordance with NFPA, HADEED Site Condition &
Engineering Standards and TSD SFM/ ISD Fire Section Requirements.
3. Meet all design requirements as per specified in item no. 2.
4. Meet the schedule requirements.
5. Develop and implement designs based on actual site conditions.
6. Properly manage all project design activities.
7. Provide complete and effective QA/QC for the project.
8. Keep HADEED TSD SFM/ ISD Representatives properly informed of the
project activities at all times.
9. Provide all things required under these contract documents for the completion
and full functional operation of the facilities upon completion.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 5 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
D. SCOPE OF WORK ACTIVITIES
The design of Fire Protection must be divided into phases of development that
HADEED to ensure that the contractor has achieved all of the projects goal and
objectives including all technical and functional requirements.
The Contactor shall perform professional services in accordance with the terms of
EPC Agreement. The Contractor shall commence the work obtaining HADEED
acceptance and approval in all aspects of the design and work disciplines rendering
of 20 years service as per concession agreement.
The Contractor shall prepare and submit a Work Schedule to HADEED for approval,
outlining the activities to accomplish the Work.
The Work Schedule shall establish all project milestones pertaining to data collection,
field survey/site inspection, preliminary and final design submission, including plans,
specifications and construction phasing plans, if appropriate.
The Contractor shall deliver the following documents as follows:
A. Work Schedule
B. Existing Condition Reports
C. Site Inspection Results
D. Final Alternatives Report
E. Design Submittals at 30%, 60% and 100% including construction
schedules/phasing plans and technical specifications
F. Technical Specifications (hard copy and electronic copy format.
G. Design calculations: Original plus 4 copies (bound sets)
H. Minutes of Meetings (MOM): Copies to all attendees and others identified
by the HADEED Authority.
I. Record Drawings
The Contractor shall deliver both a hard copy and an electronic copy of each design
submittal. The design documents shall be appear in Intergraph Micro-station *.DGN
format or when drawn via another system such as AutoCAD, they shall be converted
in *.DGN format on CD‟s. Specification shall appear in MS Word. The drawing format
and presentation shall be in accordance with HADEED Engineering Document
Specification latest revision.
Design Phase Requirements
During the preparation of preliminary design services, the following shall be
submitted through the development of Preliminary Design Report including:
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 6 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
1. Condition Survey shall be reported that will describe and verify the existing
fire protection and elements of all other applicable disciplines for life safety
and fire prevention at the project site and/or in subject building pertinent to
the proposed project.
2. Building Code Analysis as per NFPA 5000 and NFPA 101.
3. Preparation of Schematic drawings showing the work‟s magnitude, scope, and
character, and the essential basic elements of fire protection.
4. Outline specifications consist of a comprehensive description of the scope of
work, major systems, equipment and materials including major components.
5. Prepare preliminary plans and an outline of technical specifications.
Upon receiving HADEED‟s approval of the preliminary design submission, the
contractor can proceed with the design by preparing final design phase
requirements. The contractor shall prepare and deliver two (2) Final Design
submissions. The first submission shall be 60% complete and the second shall be
100% complete. The contractor shall provide four (4) copies of each submission
which shall be include design drawings showing the detail the work to be performed
including final plans, drawings, specifications and technical specifications required by
the HADEED to engage construction contractors and comply with the HADEED
Bidding Agreement. Such submissions shall incorporate all relevant comments and
suggestions received from the related preliminary design report and each previous
submission. The contractor shall provide the electronic files for each final design
submission.
a. Site Survey
Although TSD SFM/ ISD Fire Section has to approve the required systems to be
applied in this project, it is the contractor responsibility to conduct a site survey and
investigate the existing fire protection systems which are acceptable to TSD SFM/
ISD Fire Section and identify the requirements to apply a proper system in
accordance to the NFPA and other related codes and standards before any design of
the required system.
Application contract documents should be submitted to HADEED Project Coordinator
and TSD SFM/ ISD Fire Section as an authority having jurTSD SFM/ ISD iction for
approval prior to start design and engineering.
B Design and Engineering
Once systems application survey approved or otherwise, the contractor will start
designing the required system in accordance to the herein after specifications and
the NFPA standards and HADEED site condition.
A complete set of design, study, calculation and drawings shall be supplied. The
design should include the following:
1. Proposed Systems description and protection philosophy
2. Hydraulic Calculations
3. System General Layout
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 7 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
4 Isometric Diagrams
5. Equipment and piping layout
6. Pipes and Fittings Schedule
7. Control System Description and the Method of detection, Detection philosophy
8. Method of determining detectors location and type
9. Battery and power supply size calculation
10. Control and detection system Layout
11. Wiring and Cabling Diagrams and type of cables to be used
12. Wiring and Cable Schedule
13. System Operation
14. Software used (operating system, Data Base, Application software) for system
monitoring and control. Screen development (Text, Graphic).
15. Hardware used for supervisory system (and workstations)
16. Network topology for Fire alarm panels a computer system (including
redundancy).
17. Equipment and materials Bill of Quantity
18. Spare capacity in panels and loops
20. System functionality, integration philosophy and performance factors
21. System security
22. Etc.
The format and supply of all documentation shall be in accordance with HADEED
Engineering Document Specification rev. B. This includes that the as-built drawings
shall be submitted as electronic files in Intergraph Micro-station *.DGN format or
when drawn via another system such as AutoCAD, they shall be converted in *.DGN
format.
The as-built drawings will be issued upon system commissioning completion and 4
sets of hard copies A 1 size for layouts and A3 size for isometrics and wiring
diagrams should be handed over to the project management of HADEED with one set
of electronic protected version on a CD ROM as HADEED copyright property.
c. Equipment Procurement and Materials Supply
The equipment and materials of the approved proposed systems shall be procured
from the qualified and HADEED preference manufacturers within the field of fire
protection applying the latest fire protection & detection technology (e.g. equipment,
devices, procedures, testing, etc).
The proposed equipment and materials should be submitted to the HADEED Project
Coordinator and TSD SFM/ ISD Fire Section for approval before any procurement
will be proceeds.
As appropriate, all system components shall be listed by Underwriter‟s Laboratories,
Inc. (UL) and approved by Factory Mutual (FM) if the component is from a category
of devices that are listed/approved by the same.
Components requiring approval shall be delivered to the project site with factory
applied UL and FM labels. System components, which do not meet these
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 8 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
requirements, are not acceptable unless specifically approved by the HADEED TSD
SFM/ ISD Fire Section.
The procurement procedure will be defined as follows:
1. Equipment and material submittal
2. Bill of materials submittal
3. Approval of the materials
4. Proposing a delivery schedule
5. Placing of orders
6. Start of fabrication
7. Factory inspection and certification
8. Packaging
9. Transportation
10. On-site delivery
11. On-site inspection
Manufacturers
The supplier shall have sufficient stock on hand and have a fully equipped service. All
Fire Fighting/Detection Equipments shall be under the following manufacturers.
A. Water based suppression system
1. Reliable (USA)
2. ANSUL USA for Foam Water Sprinkler equipment.
3. ANSUL (USA) for Dry chemical powder fixed piping suppression system
4. Pyrochem (USA) for Wet chemical agent suppression system
B. Clean agent gas suppression and Carbon dioxide suppression systems
1. Novec-1230 ANSUL Incorporated SAPPHIRE(USA)
2. FM- 200 PYRO CHEM (USA)
3. CO2 (Low Pressure and High Pressure) ANSUL Incorporated (USA)
C. Standpipe Fire Hose Cabinet Equipment
1. Fire Hose Cabinet "REDA or SFFECO" as per approved sample
2. Class III Type Fire Hose rack cabinet
1 1/2 Ø Potter Roemer nozzle with Model # 2972 (USA)
1 1/2 Ø 100 feet Potter Roemer Double Jacket Hose (100 feet )with UL
listed & FM approved
Hose Rack(USA)
1 1/2 Ø Angle valve Potter Roemer with Model # 4070 (USA)
2 1/2 Ø Angle valve Potter Roemer with Model # 4065 (USA)
D. Fire Hydrant
1. AVK (USA)
2. GRATZ-BOHM (Austria)
E. Fire Extinguisher
1. Fire extinguisher Cabinet "REDA or SFFECO" as per approved sample
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 9 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
2. ANSUL (USA)
F. Self Contained Breathing apparatus
1. SCOTT Safety (USA) Model Air-Pak 50
G. Fire Detection and Alarm System Equipment
1. SIEMENS SINTESO(SWITZERLAND) “Latest Version” (FPF network)
2. NOTIFIER ONYX SERIES(USA)” Latest Version” (LPF network)
d. Construction and Installation
Since this project is a life safety and fire loss prevention project, it has to be
executed by very professional and qualified personnel; therefore the Contractor shall
be aware for all HADEED TSD SFM/ ISD Safety Regulations as per HADEED Site
Condition and Engineering Standard .
The contractor shall start preparation the sites to accept and accommodate the
systems to be installed; certain safety precautions should be taken thereof. Also,
shop drawings according to the approved design should be used; the complete
detailed design has to be ready and approved prior to start installations. These shop
and installation detailed drawings are the main guide for installations.
HADEED has the right to reject any type of materials used or installations completed
without drawings guidance or materials approval.
It is understood that contractor has to complete the mechanical works and then the
electrical works prior to start testing and commissioning.
e. Testing and Commissioning
Factory inspection and plant test for equipment shall be part of the systems testing.
The in-house test reports have to be attached to the on-site test report for each part
of the system.
Prior for testing, the systems have to be announced completed and the certificate of
mechanical completion has to be presented with testing procedure. Also, the
operation and system function has to be submitted.
The testing procedure shall be approved and shall be in accordance to the NFPA
codes and standards.
Operation and maintenance manual should be prepared in 4 sets, Arabic and English,
and submitted to the HADEED TSD SFM/ ISD Fire Section before issuance of the
provisional completion certificate.
Once the functional test is completed, the system will be left operational for 10 days
under supervision of the contractor without any defect or fault, then the warranty
period will start thereof.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 10 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
E. TRAINING AND FAMILIARIZATION
The Contractor shall provide operation training. Each training session shall include
emergency procedures; abort functions, system control panel operation, trouble
procedures and safety requirements. Each session include a complete demonstration
of the system. Dates and times of the training period shall be coordinated through
the Owner (HADEED) not less than two weeks prior to the session.
The automatic fire protection fixed extinguishing systems are self controlled systems
which are designed to extinguish and control the fire within the protected hazard, i.e.
operators are not required at the initial time of fire unless otherwise system failed.
Therefore, the contractor has to include in his offer training package program for
HADEED TSD SFM/ ISD Fire Section and Plant operators. This program shall be
carried out immediately after the systems commissioning and put in full operational
automatic mode. The program should contain the following:
1. Systems Description, the purpose of each system and the extinguishing
method.
2. Systems operation.
3. Systems inspection procedure.
4. Systems troubleshooting in case of failure.
5. Systems resetting restoring into operation after operation.
6. Any other technical or special feature.
7. On-site familiarization.
8. Practicing the complete activities.
The instructor for each attended trainees should issue a training certificate.
3. MAINTENANCE
The contractor shall ready to perform the preventive maintenance as recommended
by NFPA, applicable codes and manufacturer‟s installation, operation and
maintenance manuals to keep all fire protection systems (e.g. fixed extinguishing
systems, fire detection and alarm systems, etc.) equipment operable and functional
if contracted. Repair service of the equipments must be made immediately to assure
the system will operate properly when needed.
4. MATERIAL DELIVERY, STORAGE AND PROTECTION
All items, equipments and materials shall be handled, stored, and protected in such
a manner as to prevent damage to materials, coatings, and finishes. All fittings and
joints shall be kept free from dirt, oil, and grease.
All accessories shall be delivered in a clean, undamaged condition and stored off the
ground, to provide protection against oxidation caused by direct ground contact. All
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 11 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
defective or damaged materials shall be replaced with new materials at no cost to
HADEED.
5. SUBMITTALS
After verifying all field measurements and after complying with the applicable
procedure specified in the contract documents, the contractor shall submit a review
and approval, with such promptness as to cause no delay in the work, all technical
Submittals, as specified. The Submittals shall be submitted in accordance with
appropriate HADEED Standard.
1. A preliminary schedule of Shop Drawings, sample, product data and proposed
substitutes or “or-equal” submittals if any.
2. A complete progress schedule for all phases of the Project.
3. Material Safety Data Sheets (MSDS) on products used on the Project.
4. A traffic maintenance plan, as required.
5. A letter designating the Contractor‟s safety representative
A. Data
Water Flow Tests: For each building or structure, Contractors shall perform a
hydraulic flow test to confirm the available water supply for the fire protection
systems within the area.
Hydraulic Calculations: Contractors will submit hydraulic calculations based on site
water supply information gathered in water flow test and the fire protection system
design densities identified in this specification to protect specific hazards. Hydraulic
calculations with comprehensive hydraulic data sheets shall comply with NFPA.
Verification of adequacy of water pressure and other pertinent water supply data
shall be the responsibility of the contractor.
No work shall be performed until the shop drawings, calculations and data sheets
have been approved.
Manufacturer Catalog Data: Submit data including catalog cuts, brochures,
specifications, product data and information regarding UL Listings and Factory Mutual
Approvals in sufficient details and scope to verify compliance with the requirements
of the contract documents. When multiple products are shown on the single sheet,
Contractor will clearly identify the selected product.
Material, equipment and fixture lists: A complete itemized listing of equipment and
materials proposed for incorporation into the work shall be submitted. Each entry
shall include an item number, the quantity and the name of the manufacturer or
supplier of each item.
Product Data:
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 12 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
1. Piping materials, including dielectric fittings, flexible connections, and
sprinkler special fittings.
2. Pipe hangers and supports.
3. Valves, including listed fire-protection valves, unlisted general-duty valves,
and specialty valves and trim.
4. Air compressors, including electrical data.
5. Discharge nozzles and sprinklers, escutcheons, and guards. Include sprinkler
flow characteristics, mounting, finish, and other pertinent data.
6. Hose connections, including size, type, and finish.
7. Hose stations, including size, type, and finish of hose connections; type and
length of fire hoses; finis of fire hose couplings; type, material, and finish of
nozzles; and finish of rack.
8. Hose cabinets.
9. Fire hydrants.
10. Fire Extinguishers
11. Fire department connections, including type; number, size, and arrangement
of inlets; caps and chains; size and direction of outlet; escutcheon and
marking; and finish.
12. Alarm devices, including electrical data.
13. Extinguishing-agent containers
14. Extinguishing agent
15. Control panels
16. Detection devices
17. Manual-release stations
18. Switches
19. Alarm devices
20. Audible/visual notification appliances,
21. etc.
a. Shop Drawings:
Shop drawings shall be provided in the HADEED Standard format. Drawings shall
contain no irrelevant information. Drawing information should meet or exceed the
requirements of NFPA. Mark-up copies of catalog data sheets or manufacturer‟s
“typical” diagrams are not acceptable in lieu of the required drawings or diagrams.
Plans for system testing shall be submitted for approval with shop drawings.
Wherever called for in the Contract Documents, or where required by HADEED, the
CONTRACTOR shall furnish to HADEED, for review, five (5) copies of each Shop
Drawing submittal. The term “Shop Drawings” as used herein shall be understood to
include detail design calculations, Shop Drawings, fabrication drawings, installation
drawings, erection drawings, lists, graphs, operating instructions, catalog sheets,
data sheets, and similar items.
All shop drawing submittals shall be accompanied by HADEED standard submittal
transmittal form as per HADEED Engineering Document Specification. Any submittal
not accompanied by such a form, or where all applicable items on the form are not
completed, will be returned for re-submittal.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 13 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Normally, a separate transmittal form shall be used for each specific item or class of
material or equipment for which a submittal is required. Transmittal of a submittal of
various items using a single transmittal form will be permitted only when the items
taken together constitute a manufacturer‟s “package” or are so functionally related
that expediency indicates review of the group or package as a whole. A multiple-
page submittal shall be collated into sets, and each set shall be stapled or bound, as
appropriate, prior to transmittal to HADEED.
Fabrication of an item may be initiated only after the HADEED Project Coordinator
has reviewed the pertinent submittal and returned copies to the CONTRACTOR with
attached comment(s). Corrections of the submittals shall be considered as changes
necessary to meet the requirements of the Contract Documents and shall not be
taken as the basis for changes to the Contract requirements only a Change Order
can alter the Contract Price, Contract Time, or Specifications.
HADEED‟s review of CONTRACTOR Shop Drawing submittals shall not relieve the
CONTRACTOR of the entire responsibility for the correctness of details and
dimensions. The CONTRACTOR shall be responsible for the dimensions and the
design of adequate connections and details.
Shop drawings shall include a drawing legend sheet identifying:
1. All symbols used on the drawings, by type of devices or equipment,
manufacturer and manufacturer‟s part number. This information shall
correspond to the manufacturer‟s data catalog data sheets required as part of
the equipment list.
2. All conventions, abbreviations and specialized terminology used on the
drawings, as necessary to understand and interpret the information shall be
contained.
3. Reference drawing number
4. All color codes and device numbering systems.
5. A complete drawing list/index identifying all drawings in the shop drawing
package by title, drawing number and specification cross-reference.
Plan view drawings based upon the project architectural plans and drawn to scale as
per HSC&ES.
Working plans, prepared according to NFPA that have been approved by TSD SFM/
ISD Fire Section including hydraulic calculations, if applicable.
AS-BUILT DRAWINGS
Upon completion of each system, the contractor shall provide four (4) copies of as-
built drawings showing actual installation details.
b. Material Samples:
Material sample shall be provided concurrent with the shop drawing submittal.
Contractor shall provide samples in accordance with the requirements of the HSC&ES
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 14 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
as specified. In addition, sample shall be submitted in original factory cartons (if
applicable) with factory documentation. Such documentation shall include evidence
of UL Listing and FM Approval, as required. One sample of each filed connected
device shall be provided for approval.
c. Record Drawings:
The CONTRACTOR shall keep and maintain, at the job site, one record set of
Drawings. On these, it shall mark all project conditions, locations, configurations,
and any other changes or deviations which may vary from the details represented on
the original Contract Drawings, including buried or concealed construction and utility
features which are revealed during the course of construction. Special attention shall
be given to recording the horizontal and vertical location of all buried utilities that
differ from the locations indicated, or which were not indicated on the Contract
Drawings. Said record drawings shall be supplemented by any detailed sketches as
necessary or directed to indicate, fully, the WORK as actually constructed. These
master record Drawings, of the Contractor‟s representation of as-built conditions,
including all revisions made necessary shall be maintained up-to-date during the
progress of the WORK.
In the case of those Drawings, which illustrate the detail requirement for equipment
to be assembled and wired in the factory, the record drawings shall be updated by
indicating those portions which are superseded by Change Order Drawings or final
Shop Drawings, and by including appropriate reference information describing the
Change Orders by number and the Shop Drawings by manufacturer, Drawing, and
revision numbers.
Record drawings shall be accessible to the HADEED Project Coordinator at all times
during the construction period and shall be delivered to the HADEED Project
Coordinator on the working day in which the Notice to Proceed is given as well as
upon completion of the WORK.
d. Operation and Maintenance (O&M) Manuals
Preliminary O&M Manuals shall be provided with the shop drawings. The manuals will
be reviewed for required contents and approved or disapproved on that basis. Upon
completion of the project, the Contractor shall revise the approved, preliminary
manual to be consistent with the system as installed and specifically to coordinate
the testing and maintenance schedule with the approved Contractor testing protocols
and with the device numbers indicated on the Contractor‟s Record Drawings.
Final O&M Manuals (including Final Record Drawings) shall constitute the basis for
the on-site training sessions required and such, shall be both specific to the system,
containing a minimum of an excessive information, and suitable for that purpose.
This manual shall be written, compiled and edited specifically for this project and the
system installed. The Final O&M manual shall include copies of appropriate Record
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 15 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Drawings. Unedited manufacturer‟s catalog data sheets and/or equipment manuals
are unacceptable as content for the submittal.
The CONTRACTOR shall include in the Operations and Maintenance Manuals for each
item of mechanical, electrical, and instrumentation equipment in accordance with
HADEED Engineering Document Specification latest version.
e. Reports and Certificates
Field Test Reports and Certificates: Indicate and interpret test results for compliance
with performance requirements and as described in NFPA.
Test reports (procedures and checklists for all required test shall be submitted with
the appropriate requirements of HSC&ES and TSD SFM/ ISD Fire Section unless
otherwise specified in accordance with NFPA.
The test report shall include a detailed narrative description of/verification performed
(consistent with the approved test protocols required elsewhere in these
specifications), the date and time, results and the initials of the parties performing
and witnessing each test/verification.
The test report shall become a part of the permanent record and contain signatures
of contractor‟s representative involved in each phase of testing.
HADEED may permit the use, prior to sampling, inspection and testing, of certain
materials or assemblies when accompanied by manufacturer's material certifications
stating that such materials or assemblies fully comply with the requirements of the
Contract. The certification shall be signed by the manufacturer, and will specifically
reference the material's compliance with NFPA and HADEED Standards specified in
the applicable Contract Documents.
Material certifications shall be submitted to the HADEED prior to incorporating the
item into the WORK.
Materials or assemblies used on the basis of material certifications may be sampled,
inspected and/or tested at any time, and if found not in conformity with these
specifications, will be subject to rejection whether in place or not.
f. Spare Parts
CONTRACTOR shall provide a comprehensive list of spares to operate and maintain
the plant. The following information shall be provided for each item: Item
description, Detail drawings, Reference drawing number, Part description, Reference
number, Catalogue number, Manufacturer, Supplier, Delivery time, Unit weight,
Price.
The CONTRACTOR shall furnish to the HADEED Project Coordinator five (5) identical
sets of spare parts information for all mechanical, electrical, and instrumentation
equipment. The spare parts list shall include the current list price of each spare part.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 16 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
The spare parts list shall be limited to those spare parts which each manufacturer
recommends be maintained by the HADEED in the inventory at the plant site. The
CONTRACTOR shall cross-reference all spare parts lists to the equipment numbers.
The spare parts lists shall be bound in standard size, loose leaf, vinyl plastic hard
cover binders suitable for bookshelf storage. Refer to HADEED Engineering Document
Specification latest Revision.
6. TESTS AND ACCEPTANCE
Tests shall be made as specified on this work of scope; otherwise, the
manufacturer‟s standard tests shall be made. Acceptance shall be subject to
compliance with this Report, to be determined by inspection after delivery, by results
of tests required above.
Fire protection systems shall be tested and commissioned prior to startup of the
plant.
Fire protection system acceptance shall be based on functional testing of all systems
and components. Random sampling /testing shall not be accepted.
Documental proof shall be submitted about the successful transmission and
recording of events stimulated during acceptance test at Hadeed Base.
System shall be handed over in perfect operational manner with 0% fault condition.
7. WORKMANSHIP, MATERIAL AND INSPECTION
Workmanship and material shall be first class in every respect, and subject to the
inspection of HADEED representative at all times.
8. PAINTING AND PACKAGING
CONTRACTOR shall comply as per required in this document.
9. SAFETY DEVICES
CONTRACTOR must furnish all machinery or equipment to be provided under this
Report with all safety devices and clearances to comply with the HADEED safety
requirements.
10. ELECTRICAL EQUIPMENT CRITERIA
CONTRACTOR shall comply with the requirements of SECTION 5 – Electrical
Equipment of HADEED SITE CONDITIONS AND ENGINEERING STANDARDS.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 17 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
CONTRACTOR shall engineer and provide all necessary electrical systems required to
make the installation complete and fully integrate it with the existing system.
Where possible and logical, the existing system shall be modified and/or extended to
accommodate the new requirements. All equipment supplied shall be from
internationally recognized reputable suppliers and adequately rated for operation in a
steelworks environment and for continuous duty.
All equipment shall be protected to minimum rating of IP 66.
In addition to the applicable requirements of the National Electrical Code (NFPA 70),
transformer installations shall comply with FM Data Sheet 5-4/14-8.
Where there is no “listed” equipment or materials of the type, special one-of-a-kind
equipment can be accepted if HADEED can verify that all components meet the high-
quality control standards, installation methods should be in accordance with the
manufacturer‟s instructions, and NFPA 70, and other applicable requirements
obtaining HADEED approval.
Where multi-tiered cable trays are installed in configurations that represent a
significant fire hazard (as determined by the Fire Hazard Analysis) they should be
provided with fire protection and suppression as determined by HADEED.
11. WARRANTY
All equipment, materials, installation and workmanship are under new warranty basis
according to manufacturer‟s maximum warranty period from the date of acceptance.
A copy of the manufacturer‟s warranty shall be provided with the closed-out
documentation and included with the operation/installation manual in English and
Arabic.
12. FIRE PROTECTION SYSTEM
12.1 PREVENTIVE FIRE SAFETY MEASURES
GENERAL
The construction of HADEED shall be consider the influence of location, occupancy,
exterior exposure, possibility of mechanical and physical damage to fire-resistant
material, and other features that could impose additional requirements for
safeguarding life and property, as commonly covered in building codes.
Plant Room shall be separated from other operations, materials, or occupancies by
location, firewalls, fire partitions, or other means acceptable as fire protection. NFPA
221, Standard for Fire Walls and Fire Barrier Walls shall be reference for information
on the construction of firewalls and fire barrier walls.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 18 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
For the installation of opening protection, NFPA 80, Standard for Fire Doors and Fire
Windows, and NFPA 90A, Standard for the Installation of Air Conditioning and
Ventilating Systems.
The fire resistance of building construction varies with the susceptibility to damage
by fire of the building materials used and the degree of fire protection, if any,
provided for the structural members.
The general types of building response design elements for the prevention of
propagation of fires taking into account to fire safety measures in response to life
safety and property damages.
Fire stops provide a fire resistant seal around electrical or mechanical service items
that penetrate or pass through a fire resistant wall or floor.
The performance of a fire stop is measured by subjecting it to a standard time-
temperature fire exposure and hose stream according to ASTM E 814. The hourly
rating is established based on the period of resistance to the fire exposure.
Site access for emergency and fire vehicles shall be design in accordance with NFPA
1.
12.2 FIRE FIGHTING SYSTEM
GENERAL
The proposed project shall be protected by fire protection system in connection to
the submitted requirements. The HADEED project shall be protected with efficient
and effective fire fighting system taking into account the provision of an engineered
design and installation of the same, according to the guidance out lined in NFPA with
the acknowledgement of TSD SFM/ ISD Fire Section.
A. FIRE WATER SUPPLY AND DISTRIBUTION
The new fire water supply distribution scheme shall be designed and installed in
accordance with NFPA 24 standards and tie with the existing fire water ring mains .
B. FIRE WATER DISTRIBUTION PIPING
GENERAL
Generally, installation of fire water mains shall be in accordance with NFPA 24. All
piping shall be a carbonsteel ASTM A53 Grade B SCH 40 steel piping, internally and
externally coated with wrapping. Fire water lines shall be aboveground or in pipe
rack as much as possible with protection against mechanical damage and HADEED
environmental condition.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 19 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Fire water mains lay underground shall not be installed underneath tanks, process
vessels, structures or permanent buildings and where potential leakage could contact
molten steel or slag.
Generally, ring main pressure at the HADEED where the mains pressures shall be
sustained at 12.1 bars.
Testing requirements are as below
Flushing: Flow the required rate until water is clear as indicated by no collection of
foreign material at outlets such as hydrants and blow-offs.
Hydrostatic: Hydrostatic tests shall be made at not less than 200 psi (13.8 bar) for 2
hours .
Leakage: New pipe laid with rubber gasketed joints shall, if the workmanship is
satisfactory, have little or no leakage at the joints.
The firewater can flow through all sections of fire grid with no portion being out of
service at the time of fire.
Fire water mains may be extended for future expansion Blind flange should be used
as for future connection.
System Arrangement
Whenever feasible, all water distribution systems should be of the looped grid type
providing two-way flow with sectional valving arranged to provide water flow
supplies in any point in the system. In addition, sectional control valves should be
provided to limit the number of hydrants and sprinkler systems inoperative during a
single break of a total of five (5). Dead-end runs utilized as a single supply to fire
hydrants shall not be exceed 90-m (300-ft).
Sprinkler system water supply lead-ins shall not be run under buildings. The
Sprinkler system risers and alarm valves shall be provided a suitable enclosure.
PIPE SELECTION
Piping shall be listed for fire protection service and comply NFPA and HSC&ES as per
approval of TSD SFM/ ISD Fire Section.
FIRE WATER PIPING MATERIAL
All fire fighting water lines should be of carbon steel piping and located above
ground. If for reason of safety, or plant requirements, the piping has to be
underground.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 20 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Underground firewater piping shall be carbon steel, coated and wrapped, with joints
field coated and wrapped and/or with cathodic protection or equally efficient cathodic
protective device after assembly in accordance with HADEED Site Condition and
Engineering Standards.
Above ground firewater, piping shall be painted red along its entire length and at
every joint bearing "Fire Fighting Water" with flow water direction as to be easily
visible. The language shall be English and Arabic.
C. DRAINAGE
Drainage of all buildings shall be assessed to ensure acceptable runoff or retention of
fire protection water and to minimize damage. Provision of drainage and disposal
facility to control the spread of flammable and hazardous liquids shall be suitable to
areas adjacent to the fire. These liquids should be seized in controlled areas until
they can be disposed of safely. Fire water system drain lines shall be located in
drainage pit.
D. BLOCK VALVES
Block valves in underground fire water lines and laterals shall be operable from
grade with the valve stem and packing permanently protected from contact with
earth rocks etc. and shall be provided with post indicator valve to indicate the open
and closed position.
Outside screw and yoke (OS&Y) shall be installed as gate valves in above ground
water lines.
OS&Y valves are recommended for service indoors and in pits outdoors. They are not
recommended for throttling service.
E. FIRE EXTINGUISHING SYSTEM
The fire fighting systems have been requested to protect areas/rooms as mentioned
on the table in Appendix A.
GENERAL
This specification does not relieve CONTRACTOR from full responsibility for the
operational safety and serviceability of the system. CONTRACTOR shall be fully
responsible to supply at his own cost any engineering, component, parts and
materials essential for the system to operate to the full satisfaction of HADEED
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 21 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Complete set of all installation materials and general constructional items including
any tools, lifting devices for mechanical and electrical installation. Supply all
necessary items, parts, equipments, materials & general requirements for full
functioning of the fire fighting system according to NFPA.
Contractor shall be responsible to perform the design, Computer flow calculations,
layout, as-built drawings, material supply, installation and testing of the entire fire
fighting work system. Contractor must submit his propose system catalogues,
drawings and samples of all materials prior to procurement for HADEED approval.
Computer flow calculations shall detail pressure changes, flow rates, pipe and
nozzle size.
All design, materials, construction, items of plant, procedures and instructions shall
conform in all aspects to the requirements of this specification, NFPA and TSD SFM/
ISD / FIRE REQUIREMENT. CONTRACTOR shall ensure that he is in possession of and
working with latest revision of the document.
CONTRACTOR is responsible for the correct and safe operation of the Fire Protection
System and its components before acceptance of system. The CONTRACTOR shall be
responsible for the dimensions and the design of adequate connections and details.
CONTRACTOR should be fully aware of the existing conditions, presence of lines,
pipes, cables etc. to avoid damages of the facilities. Any mistakes due to
CONTRACTOR must be rectified/ repaired at his cost.
Lockout switch should be provided, installed & integrated with any new fire
suppression system for maintenance & inspection purposes.
CONTRACTOR should guarantee the AVAILABILITY of spare part for at least 10 years
after the concession agreement.
The entire system shall be designed & installed in a skillful manner in accordance
with approved manufacturers' manuals and approved detailed design. CONTRACTOR
shall furnish all piping, fittings, coupling, pipe supports and hangers, conduit, wiring,
outlet boxes, junction boxes, cabinets and similar devices necessary for the complete
installation. All piping and fittings shall be in accordance to ANSI standards as per
stipulated in NFPA. Wiring shall be of the type recommended by the NEC, approved
by local authorities having jurisdiction (TSD SFM/ ISD) for the purpose, and shall be
installed in dedicated conduit throughout.
All welding procedure, welders and welding operators shall be qualified in accordance
with AWS.
In all area where explosion of fire is classified, the fire suppression system should be
explosion proof & heavy-duty mechanisms.
System containing components, which have a dated life span and must be
periodically replaced shall not be applied and/or used.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 22 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
All supply & return dampers on the area of alarm shall be closed. Also, All HVAC
units serving the area of alarm shall be shutdown.
Operate control relay contacts to release all magnetically held smoke doors, closing
fire dampers & shutdown HVAC units throughout the building should be provided &
installed for all necessary areas.
Electrical Grounding system should be design & provided for suppression system to
dissipate possible electrostatic charges.
All control, drain, and test connection valves shall be provided with permanently
marked weatherproof metal or rigid plastic identification signs.
The Fire Suppression Control system shall be provided with battery back up.
Releasing panel principle can be applied to suppression system, but each panel
should have dry contacts for connecting to alarm fire panels by contractor.
The firewater for new suppression systems should be taken from the nearest Fire
Water Valve Pit. CONTRACTOR should consider, civil activities, pipe‟s trench &
include all necessary fittings, valves, accessories, hydro jetting, excavation, backfill
and the like.
The installation contractor shall identify a hydraulically designed system with a
permanently marked weatherproof metal or rigid plastic sign, which should be posted
near valves/cylinders station.
DANGER, WARNING and CAUTION posters, should be used to alert the Operator/user
to special instructions concerning a particular service or operation that may be
hazardous if performed incorrectly or carelessly.
Any cylinder should be also equipped with nameplate on which the main cylinder
data are reported. Cylinder is of steel construction and painted in red.
Steel straps and brackets must be used to mount the cylinders in vertical position.
Agent (Co2 or FM-200) in cylinders is routed from the storage cylinders to the
discharge piping by a flexible hose as per NFPA. The hose is connected to the
discharge outlet of the cylinder valve and terminates at the system piping or
discharge manifold.
All agent storage containers (main and reserve) shall be activated by an electrical
manual discharge station, an automatic device and by direct mechanical actuation.
The storage cylinders shall be provided with a safety device allowing the content to
vent in case high internal pressure due to high temperature. The contents shall not
be vented through the discharge piping and nozzles
The specific & detail requirements of Suppression System will be as follows:
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 23 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
E.1 Piping System & components for Fire Suppression System
All devices shall be located, installed, or suitably protected so that they are not
subject to mechanical, chemical, or other damages that would render them
inoperative.
The releasing device for mechanical actuation shall be provided & located for easy
accessibility at all times including the time of fire. The device should provide a means
of discharge in the event of total electrical malfunction. The device shall be provided
with a manual level and a faceplate with clear instructions on how to mechanically
activate the system
Distribution Piping to meet the requirements of ASTM [A53]/ [A106] specifications.
Distribution piping up to ¾ in. diameter shall be Schedule 40 seamless steel
[galvanized] pipe. Distribution piping larger than ¾ in. diameter shall be Schedule 80
seamless steel [galvanized] pipe. For pipe sizes up to 2 in. diameter, Class 300
[malleable] iron fittings shall be used. For pipe larger than 2 in. diameter, IPS and
forged steel fittings shall be used. All pipes shall be painted red with primary and
final coating as standard practice followed in Hadeed.
All valves shall be suitable for the intended use, particularly regarding flow capacity
and operation. They shall be used only under temperatures and other conditions for
which they are listed and approved.
O.S.&Y. gate valve shall be provided for water based system with lock and chain.
The water system control valves shall be of the flanged, outside screw and yoke
(OS&Y) type.
The piping system & its components shall have a minimum 175 PSI (12,1 Bar) as
working pressure
Rigid metal conduit shall be used for any wires & cable under all atmospheric
conditions and occupancies. The minimum size of rigid metal conduit to be used is ½
in.
Flanged joints should be applicable for all valves & strainer.
All reduction in pipes size must be made using concentric reducing fittings.
Reducing bushings are not acceptable.
All sprinklers/ nozzles heads subject to mechanical damage shall be provided with
standard sprinklers guards.
Where there is more than one source of water supply, a check valve shall be
installed in each connection.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 24 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
For under ground service, the pipe & fittings can be carbon steel with corrosion
protected.
For above ground service, the pipes & fittings should be carbon steel.
Mechanical grooved piping and valves not to be utilized. Flanged valve/butt welded
piping joints only shall be used.
All Pipe fittings shall be Flange, butt-welded and threaded as per HADEED approval,
while, grooved fitting is not acceptable..
Each riser room shall be provided with automatic pressure regulator installed at the
main feeder incomer
E.2 Pipes Supports and Hangers:
System piping shall be adequately supported so as to be expected to maintain its
integrity under fire conditions. Piping shall be supported from steel or concrete
structural members or pipe stands.
The components of hanger assemblies that directly attach to the pipe or to the
building structure shall be listed.
The piping system shall be securely supported with due allowance for agent thrust
forces, thermal expansion and contraction, and shall not be subject to mechanical,
chemical, or other damage. Where explosions are possible, the piping system shall
be hung from supports that are least likely to be displaced.
E.3 Fire Suppression System Station (Enclosure):
Concrete enclosure shall be provided to protect the Main valves riser station, CO2 ,
FM-200 , NOVEC-1230 cylinders , fire pumps station and its components against the
severe injury that may caused dusty and rusty environment. CONTRACTOR shall
consider same as standard height office room, lockable door, electrical outlet,
lighting, emergency light, proper ventilation, A/C for CO2, FM-200 and NOVEC 1230
cylinders, foam water tanks and Red painted door enclosure. Suitable drainage
arrangement shall be arranged for all valve stations.
CO2,FM-200 and NOVEC-1230 Storage facility and its accessories shall be so located
and arranged to facilitate inspection, maintenance, and recharging. Interruption to
protection shall be held to a minimum.
The releasing device shall be easily removable from the cylinder without emptying
the cylinder.
Valve stations(riser rooms )shall have proper drainage provision and shall be
connected with Industrial effluent drainage system.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 25 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
F. FIRE WATER HOSE ANS STANDPIPE SYSTEM
General Requirements
The design and installation of fire hose cabinets (FHC) shall be in accordance with
NFPA 14. All FHC shall be Class III type.
FHC shall be located in central areas such as corridors and exit locations (e.g. at
each intermediate landing between floor levels in every required exit stairway, on
each side of the wall adjacent to the exit openings of horizontal exits and in exit
passageways), where they are clearly visible and readily accessible. In any
building/structure, that has much as two-floor; standpipe systems shall be provided
at each floor level. The FHC shall not exceed 30 meter between each cabinet in every
floor level of the Building/structure. However if there a need of additional FHC
connection depend on the site condition where required by the Fire section it shall be
provided by the CONTRACTOR without cost impact to HADEED.
Hose valves shall be listed. Hose connections shall have external National Hose
Standard (NHS) threads, for the valve size specified, in accordance with NFPA 1963,
Standard for Fire Hose Connections.
Hose connections shall be equipped with caps to protect the hose threads.
Hose connections and hose stations shall be unobstructed and Hose Cabinet shall be
installed with the height of 650mm from the bottom of Cabinet to the finished floor.
Fire Hose Cabinet located inside the furnished Building shall be recessed type as per
approval by Fire Section.
Each 1 ½ in. (38-mm) hose shall be equipped with hose rack.
Listed isolation valves for each Hose Cabinet shall be gate valve O.S.&Y type &
installed with the height of 2000mm from the center of valve to the finished floor.
Listed Pressure Gauges for each Hose Cabinet shall be provided with UL & FM
approved.
Piping penetrations shall be provided with sleeves.
Signs shall be permanently marked and shall be constructed of weather-resistant
metal or rigid plastic materials.
G. FIRE HYDRANTS (DRY BARREL TYPE)
General Requirement
Fire hydrants shall be UL listed and FM approved dry barrel type complying with
ANSI/AWWA C502 (latest). Installation of hydrants shall be in accordance with NFPA
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 26 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
1, 24 and AWWA M 17. Materials used in the construction of dry barrel fire hydrants
shall conform to AWWA C502. All new fire hydrants must be designed, installed,
tested, and flushed in accordance with NFPA 24.
All materials and equipment installed as part of this work shall be new and listed
under specified manufacturer model.
Hydrants shall be designed for a minimum working pressure of 200-psi.
Fire hydrants shall be the three-way type with one (1) pumper nozzle and two (2)
hose nozzles. Each fire hydrant shall have two (2) 2-½-in hose nozzles. The fire
hydrant‟s pumper nozzle shall be 4-½-in diameter. Pumper nozzle is at the same
plane as the hose nozzles.
Hydrant outlet threads shall have the NH standard external threads for the size
outlet(s) supplied as specified in NFPA 1963, Standard for Fire Hose Connections.
Nozzle caps shall be attached to the hydrant with non-kinking type steel chains.
Nozzles must be replaceable in the field.
All fire hydrants shall have a bottom main valve opening size of 5-¼ inches. Valve
shall be cast permanently on the hydrant. All barrel component connections shall be
bolted flange type. Shoe inlets shall be provided with a flange end joint inlet to
accommodate 6-inch (150-mm) diameter pipe.
Joint restraint between the hydrant inlet and the distribution system isolation valve
shall be as shown and specified.
Shut-off Valve: each fire hydrant shall be provided with individual shut-off valves –
OS&Y type located in pits. The valve supervision shall be provided with lock and
chain.
Installation
Spacing between fire hydrants shall be of 133-ft (40-m) along roadways or access
ways.
Hydrants shall be positioned at least 6-ft (1.8 m) away from the edge of the road
providing not less than 3-ft (1-m) of clearance in all directions from the hydrant
centerline, and not less than 40-ft (12-m) from the building. Maximum distance from
any point on street or road frontage to a Hydrant shall be 120-ft (36-m). Number
and distribution of fire hydrant in such conditions shall be in accordance with Table
I.3, NFPA 1.
Nominal distance between a fire hydrant and the building fire department connection
shall be ranging from 50-ft (15 m) to 100-ft (30-m).
Fire hydrants on the street or roadside shall be located so that the distance between
the hydrant and fire truck will not exceed 3 m. Hydrants shall be positioned such that
the fire truck (pumper) connection faces the roadway.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 27 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Material handling and protection
Fire hydrants shall be handled, stored, and protected in such a manner as to prevent
damage to materials, coatings, and finishes. All fittings and joints shall be kept free
from dirt, oil, and grease.
Fire hydrants and accessories shall be delivered in a clean, undamaged condition and
stored off the ground, to provide protection against oxidation caused by direct
ground contact. All defective or damaged materials shall be replaced with new
materials at no cost to HADEED.
Test Requirements
Tests shall be made by the contractor in the presence of the HADEED Project
Coordinator and/or TSD SFM/ ISD Fire Section designated representatives. The
following work and/or test shall be inspected and as per NFPA:
a. Thrust blocks and anchorage.
b. Flushing and hydrostatic testing as per NFPA 24 of the fire hydrant laterals.
c. All joints must be exposed to ensure no unacceptable amount of leakage as
per NFPA 24.
d. Additives, corrosive chemicals such as sodium silicate, brine, or other
chemicals shall not be used while hydrostatically testing systems or for
stopping leaks.
e. No leakage shall be allowed through the castings, main valve, joints, or stem
packing.
f. The assembled hydrants shall be tested at the factory to 400-psi in both the
open and closed positions.
Guard Post
Fire hydrant shall be protected by guard post – bollards type. The means of
protection shall be arranged in a manner that will not interfere with the connection
to, or operation of, hydrants. Bollards shall be installed 3-ft (1-m) clearance in all
directions away from the fire hydrant. Bollards shall be of 4-in. (Schedule 40 pipe),
filled with concrete rounded on top. Bollards shall be finished with gloss paint (yellow
and black stripes).
H. FIRE EXTINGUISHERS
General Requirements
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 28 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Portable and wheeled fire extinguishers shall be selected, installed, inspected,
maintained, and tested in accordance with NFPA 10, Standard for Portable Fire
Extinguishers, and shall be FM approved or UL listed for their purpose.
All fire extinguishers shall be type - „ANSUL‟ brand, model REDLINE and SENTRY.
Generally, portable and wheeled extinguishers (indoor/outdoor) shall be:
Class ABC ANSUL portable multi-purpose shall be of mono-ammonium phosphate
base (Foray), Red Line (cartridge type) Red Line 20 l-A-20-G.
Class BC portable CO2 shall be 15 and 20 lbs, Sentry CD15A/ Sentry CD20A.
All portable fire extinguishers shall be mounted and protected in a propriety red steel
lockable cabinet with breakable glass panel sized for a single fire extinguisher.
Wheeled extinguishers shall be 125 lbs ANSUL Red Line 150 (Compact) CR-I-A-150-
D
Wheeled extinguishers located outdoors must be protected by naturally ventilated
enclosures and roofs against direct solar irradiation and against excessive permanent
temperature (>60°C) and protected by a suitably identified, heavy-duty vinyl or
vinyl coated canvas cover.
Fire Extinguisher Cabinets
All fire extinguishers located as per drawings. Fire extinguisher cabinets shall be
similar as existing, and minimum requirement is as follows:
1. Cabinets shall be weather resistant 20-gauge steel painted in red baked enamel.
2. Cabinet doors shall be with breakable glass window mounted on piano hinges.
The door shall be provided with a handle lock.
3. The dimensions shall be 400-mm in width, 750-mm in height, and 250-mm in
length.
Installation
Fire extinguisher shall be provided in sufficient number and location as per NFPA 10,
however if there a need of additional fire extinguishers required by the ISD Fire
section it shall be provided by the CONTRACTOR.
Cabinets shall be located at highly visible, accessible and unobstructed by open
doors or other objects. Cabinets shall be located below or adjacent to manual fire
alarm stations. Cabinets shall be designed and installed so that the top is not more
than 1.5-m from the floor and the bottom of the cabinet no lower than 101.6-mm
above the floor. Each fire extinguisher shall be given sequence number painted on
the shell with white paint for proper identification in every designated area.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 29 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
I. FIXED EXTINGUISHING SYSTEM
Automatic Wet pipe sprinkler System contains water under pressure at all times. The
water discharges by breaking of glass-bulb sprinkler heads within the hazard area
due to heat. NFPA standards provided sprinklers temperature ratings and
corresponding color codes.
The wet system shall be complying with the requirements of NFPA 13. The system
should provide engineered automatic water wet systems include design, installation,
testing, maintenance and commissioning.
Alarm valve main manifold shall be provided with shutoff valves to enable testing
and system riser shall have isolation valve after the alarm valve.
Automatic Pre-action System (double interlock) is similar to the deluge sprinkler
system except that the sprinkler heads are not open; they are closed sprinklers with
the glass bulb. The pre-action valve is normally closed and operated by a separate
detection system. Activation of fire detectors will open the pre-action valve allowing
the water to enter the system piping and signal will send to fire alarm control panel.
However, the water will not flow from the sprinkler heads until the heat from the fire
activates the operating element in individual sprinklers. Opening of the deluge valve
effectively converts the system to a wet pipe sprinkler system.
The pre-action system shall be complying with the requirements of NFPA 13. The
system should provide engineered automatic water pre-action type systems include
design, installation, testing, maintenance and commissioning.
Deluge valve main manifold shall be provided with shutoff valves to enable testing
and system riser shall have isolation valve before and after the deluge valve.
Deluge system provided with supervisory air shall be arranged with plant air as main
source and portable compressor unit as standby.
Air compressor power supply shall be fed from emergency power supply panel.
Deluge valve utilized for pre-action system shall be of Reliable make and model -
DDX only.
Pre-action valve interlock shall utilize electric actuation /Hydraulic wet pilot actuation
type .
Valve room construction shall be of fire rated with adequate ventilation
arrangements.
Compressed air supply for Hydraulicdetection shall have general plant air as backup.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 30 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Deluge valve trim shall be of electric actuation type and shall be arranged to activate
by cross zoning.
WATER SPRAY SYSTEM (double interlock)
Water Spray System is designed to protect areas that may have a fast spreading fire
engulfing the entire area. All of its sprinkler heads are already open, without any
fusible elements in the heads, and when the systems operates water flows to all
heads, allowing total coverage. The system uses the deluge valve that opens when
the separate fire detection system (double interlock) senses the fire and sends a
signal to trip the valve open. Hydraulic wet pilot detection system in addition with
electrical detection (vertical heat detectors) shall be considered.
Spray systems may also apply foam instead of water. The valve trips open and water
or foam flows through the piping and out all of the open sprinkler heads
simultaneously. Because deluge systems are designed so that all of the heads flow,
the piping requirements are much larger than for other systems.
Most deluge systems are such of size as to require a fire pump to supply the system
with adequate volume and pressure. A foam system would also require a foam
generation device.
The water spray deluge system shall be complying with the requirements of NFPA
15. The system should provide an engineered fixed water spray deluge systems
include design, installation, testing, maintenance and commissioning. Installation
and location of tapping test valve or discharge valve for deluge upstream side.
Deluge valve shall be of Reliable make and model shall be DDX.
Deluge valve trim shall be of electric actuation type and shall be arranged to activate
by cross zoning of vertical heat detector.
Deluge valve main manifold shall be provided with shutoff valves to enable testing
and system riser shall have isolation valve before and after the deluge valve.
FOAM-WATER SPRAY SYSTEM (double interlock)
Foam Water Spray System is a special fixed pipe system connected to a reliable
source of fire protection foam tank and water supply through a mixing proportioner
to provide 3% AFFF foam concentration, and equipped with water spray nozzles for
specific water discharge and distribution over the surface or area to be protected.
The piping system is connected to the water supply through an automatically
operated and manually actuated valve, which initiates the flow of water. An
automatic valve shall be actuated by operations of automatic detection (double
interlock) equipment installed. Hydraulic wet pilot detection system in addition with
electrical detection (vertical heat detectors) shall be considered.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 31 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Reserve foam storage shall be in a hot standby that shall be included in contractors
supply.
The foam-water spray system shall be complying with the requirements of NFPA 16.
The system should provide an engineered fixed water spray deluge systems include
design, installation, testing, maintenance and commissioning.
Foam Water Spray/Deluge system provided with supervisory air shall be arranged
with plant air as main source and portable compressor unit as standby.
Air compressor power supply shall be fed from emergency power supply panel.
Deluge valve main manifold shall be provided with shutoff valves to enable testing
and system riser shall have isolation valve before and after the deluge valve.
Deluge valve shall be of Reliable make and model shall be DDX only.
Deluge valve trim shall be of electric actuation type and shall be arranged to activate
by cross zoning.
Automatic Sprinkler and Water Spray (Deluge System) SYSTEM
This specification provides the main requirements for the design and installation
testing and commissioning complete automatic water sprinkler & Deluge System for
areas as mentioned on the table. The main points of scope will be:
The water density required shall be determined in accordance to the hazard
classification as mentioned on NFPA 13 & 15.
System components shall be rated for the maximum system working pressure to
which they are exposed but shall not be rated at less than 175 psi (12.1 bar).
The strainers shall be used to protect spray nozzles, sprinklers, or other type
discharge out-lets from obstruction by debris that may be in the water supply.
The Baskets of Strainers should be stainless steel material.
The Water flow Detectors shall be generally used to actuate electrical alarms and/or
operate electrical equipment (such as fire pumps & switching off the transformer) in
automatic sprinkler/ Deluge System systems.
Listed corrosion-resistant sprinklers shall be installed in locations where chemicals,
moisture, or other corrosive vapors sufficient to cause corrosion of such devices
exist.
Water spray system shall be equipped with a suitable drainage and disposal facility
to control the spread of flammable and hazardous liquids to areas adjacent to the
fire. These liquids should be impounded in controlled areas until they can be
disposed of safely.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 32 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Fire Department Connections shall be provided, installed & 2 ½” x 2 ½” x 4” Siamese
type connections. They shall be also provided with Swivel Plugs/Chains
The Check Valves shall be provided with each automatic water sprinkler/deluge
System and connected to the fire department.
Deluge valve main manifold shall be provided with shutoff valves to enable testing
and system riser shall have isolation valve before and after the deluge valve.
The installing contractor shall identify a hydraulically designed sprinkler system with
a permanently marked weatherproof metal or rigid plastic sign
The sign shall include at least the following information:
1. Location of the design area or areas
2. Discharge densities over the design area or areas
3. Required flow and residual pressure demand at the base of the riser
4. Occupancy classification or commodity classification and maximum
permitted storage height and configuration
5. Hose stream demand included in addition to the sprinkler demand
Proper hydraulic calculation should be established upon proper nozzles distribution
and piping. The design density for extinguishments shall be tested upon completion
of installation to prove the design accuracy and reliability.
A written acceptance test procedure (ATP) for testing the deluge water spray system
components and installation shall be prepared in accordance with NFPA
Full system discharge test shall be performed to monitor all the system functions and
prove the system reliability. The record of test should include
1. Discharge time.
2. Pressure reading.
3. Water flow rate.
B. Carbon Dioxide (CO2) Extinguishing System
This specification provides the main requirements for the design and installation,
testing and commissioning, a complete Carbon Dioxide Fire automatic Suppression
System for rooms as mentioned on table. The main requirements are:
The systems shall be designed, installed, tested, and maintained according to
NFPA12 as a total flooding suppression system.
The total flooding system shall consist of a fixed supply of carbon dioxide
permanently connected to fixed piping, with fixed nozzles arranged to discharge
carbon dioxide into an enclosed space or enclosure about the hazard.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 33 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Operate control relay contacts to release all magnetically held smoke doors
throughout the building.(carbon dioxide system)
The carbon dioxide system shall be engineered designed and calculated to protect
the hazard at 50% concentration.
The carbon dioxide system shall be design & built to provide Main and Reserve
storage containers.
The carbon dioxide systems should have feature for fuel shut-off where required.
Types of Fires are deep-seated fires involving solids subject to smoldering.
Leakage of gas from the space shall be kept to a minimum and compensated for by
applying extra gas.
Where possible, openings such as doorways, windows, and so forth, shall be
arranged to close automatically before or simultaneously with the start of the carbon
dioxide discharge.
Forced-air ventilating systems shall be shut down or closed, or both, before or
simultaneously with the start of the carbon dioxide discharge or additional
compensating gas shall be provided.
The protected area compartment shall be sealed properly to avoid any CO2 leakage
for 20 minutes minimum.
The system shall be able to be actuated by detection and control equipment for
automatic system operation along with providing local and remote manual operation
as back up.
Accessories such as weighing devices, alarms provider, delay discharge, ventilation
control, door closures, or other auxiliary shutdown or functions should be included in
scope.
Two or more hazard areas can be protected with a single group of agent storage
containers (cylinders) by means of directional or selector valves.
The agent can be distributed and discharged into the hazards area through a
network of piping and nozzles.
The amount of the main supply of carbon dioxide in the system shall be at least
sufficient for the largest single hazard protected or group of hazards that are to be
protected simultaneously. Quantity of CO2 shall be provided to maintain minimum
50% concentration in the protected area.
Reserve quantity shall be available and ready to accomplish the protection once the
main quantity discharged.
Both main and reserve supplies for fixed storage systems shall be permanently
connected to the piping and arranged for easy changeover.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 34 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Cylinder shall be shipped with maintenance record card and shipping cap attached.
The cap is attached to the threaded collar on the neck of each cylinder to protect the
valve while in transit.
CO2 cylinders shall be adequately mounted and suitably supported in a rack provided
for the purpose, including facilities for convenient individual servicing and content
weighing.
Manifold basic needed, automatic means shall be provided to prevent the loss of
carbon dioxide from the manifold if the system is operated when any cylinder is
removed for maintenance.
Where excessive climatic or mechanical exposures are expected, suitable guards or
enclosures shall be provided for Discharge nozzles.
All valves controlling the release and distribution of carbon dioxide shall be provided
with an emergency manual control. This shall not apply to slave high-pressure
cylinders. The emergency means shall be easily accessible and located close to the
valves controlled. The time delay and pre-discharge alarm for emergency manual
control shall be required based on the nature of the hazard and safety requirements.
Pre-discharge Audible alarms shall be provided to give positive warning of a
discharge where hazard to personnel could exist. Such alarms shall function to warn
personnel against entry into hazardous areas as long as such hazards exist or until
such hazards are properly recognized.
Visual alarm shall be provided to show that the hazard is in fire condition and the
CO2 system is operated to suppress the fire.
The entire fire detection and suppression control system wiring shall be electrically
supervised to automatically detect and report trouble conditions to the fire
suppression control panel.
System discharge should be based on Cross-Zone philosophy of detectors as
mentioned on NFPA 72, National Fire Alarm Code.
Electromagnetic door holders (Floor / Wall Mounted) should be provided & installed
for room‟s doors (single or double door)
A Factory Trained and Authorized Engineered Systems Distributor shall install CO2
System specified herein.
The main and reserve group of cylinders shall be located in an enclosed dust free air-
conditioned area.
Each group of cylinders shall be connected to the manifold thorough high-pressure
hoses and check valve.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 35 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Releasing the door holders & shutting down the HVAC and Fire dampers prior to CO2
discharge will be part of scope. A suitable control module shall be provided for this
purpose.
Room integrity test shall be conducted in accordance with NFPA.
A full discharge test shall be performed on all systems. Where multiple hazards are
protected from a common supply, then a full discharge test shall be performed for
each hazard.
Full discharge of entire design quantity of carbon dioxide through system piping to
ensure that carbon dioxide is discharged into the hazard and the concentration is
achieved and maintained in the period of time required by the design specifications
and all pressure-operated devices function as intended.
During test, a systematic record shall be maintained of all readings using schedules
or charts of tests and measurements. Areas shall be provided on the logging form for
readings, dates and witnesses.
The acceptance inspector shall be notified before the start of the required tests. All
items found at variance with the drawings or this specification during testing or
inspection by the acceptance inspector shall be corrected.
Test reports shall be delivered to the acceptance inspector as completed.
The design plate of CO2 system, nameplate on main & reserved cylinders, entrance
& exit warning sign should be posted.
Protected area shall equip with Purging Fan System to extract the smoke & CO2 in
the premises.
Concrete pedestal for Co2/FM-200 Cylinder storage shall be considered.
The CO2 system shall provide sufficient amount of extinguishing agent to saturate
the immediate area with minimum concentration (30 percent by volume) within 2
minutes of actuating the system, and also to achieve the design concentration (50
percent by volume) within 7 minutes. The concentration is to be maintained in the
area for 10 minutes.
Activate an adjustable time delay that will delay the release of agent as required for
up to 30 seconds. The agent shall be released at the end of this time period unless a
manual release station is pulled. If the manual release station is pulled the agent
shall be released immediately by-passing any remaining time delay.
There is 20 sec as minimum delay in case of cross-zone (smoke detector) alarm.
The pressure switch should be installed on the distribution line & should act in case
of agent discharging. Pressure switch will send an electric signal to the fire control
panel when the agent is discharged.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 36 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
C. Clean Agent (FM 200) Fire Extinguishing System
General Requirements
The specification provides the main requirements for providing, designing,
engineering, installation, testing and commissioning, complete clean agent automatic
suppression system using FM 200.
The system is required for the control rooms and manned electrical rooms of the
Plant.
The systems shall be designed, installed, tested, and maintained according to NFPA
2001 as a total flooding suppression system.
The amount of agent in the main agent supply shall be at least sufficient for the
largest single hazard protected or group of hazards to be protected simultaneously.
The amount of clean agent to be provided shall be the amount required to obtain a
uniform 7% design concentration or higher as recommended by the system/ agent
manufacturers for minimum of 10 minutes in the protected area. However, the
highest concentration at which no adverse toxicological or physiological effect has
been observed.
The system shall be consisted with main and reserve agent supply where reserve
shall be provided as many as the main agent supply.
Operate control relay contacts to release all magnetically held smoke doors
throughout the area/room protected by FM-200
During volume calculations, consideration must be taken to such factor as: un-
enclosable openings, run-down time of fans, time required for dampers, doors or
windows to close, crakes around doors, windows and wall
Where possible, openings such as doorways, windows, and so forth, shall be
arranged to close automatically before or simultaneously with the start of the agent
discharge
Forced-air ventilating systems shall be shut down or closed, or both, before or
simultaneously with the start of the agent discharge / additional compensating gas
shall be provided.
The system shall be able to be actuated by detection and control equipment for
automatic system operation along with providing local and remote manual operation
as back up.
Accessories such as weighing devices, alarms provider, delay discharge, ventilation
control, door closures, or other auxiliary shutdown or functions should be included in
scope.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 37 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Two or more hazard areas can be protected with a single group of agent storage
containers (cylinders) by means of directional or selector valves.
Reserve quantity shall be available and ready to accomplish the protection once the
main quantity discharged.
Both main and reserve supplies for fixed storage systems shall be permanently
connected to the piping and arranged for easy changeover
Manifold basic needed, automatic means shall be provided to prevent the loss of
carbon dioxide from the manifold if the system is operated when any cylinder is
removed for maintenance.
Manual/Hydraulic actuators shall be installed providing manual/Hydraulic actuation of
cylinder valve.
Pre-discharge Audible alarms shall be provided to give positive warning of a
discharge where hazard to personnel could exist. Such alarms shall function to warn
personnel against entry into hazardous areas as long as such hazards exist or until
such hazards are properly recognized.
Visual alarm shall be provided to show that the hazard is in fire condition.
Detectors shall be Cross-Zoned detection requiring two detectors to be in alarm
before release. System discharge should be based on Cross-Zone philosophy of
detectors as mentioned on NFPA 72, National Fire Alarm Code.
The use of explosive devices to actuate agent discharge shall not be permitted
The high velocity discharge should not be significant enough to dislodge objects
located directly in the discharge path
Electromagnetic door holders (Floor / Wall Mounted) should be provided & installed
for room‟s doors (single or double door).
Each group of cylinders shall be connected to the manifold thorough high-pressure
hoses and check valve.
Releasing the door holders & shutting down the HVAC and Fire dampers prior to
discharge will be part of scope. A suitable control module shall be provided for this
purpose.
Room integrity test shall be conducted in accordance with NFPA.
A full discharge test shall be performed on all systems. Where multiple hazards are
protected from a common supply, then a full discharge test shall be performed for
each hazard.
Full discharge of entire design quantity of FM-200 through system piping to ensure
that agent is discharged into the hazard and the concentration is achieved and
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 38 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
maintained in the period of time required by the design specifications and all
pressure-operated devices function as intended.
During test, a systematic record shall be maintained of all readings using schedules
or charts of tests and measurements. Areas shall be provided on the logging form for
readings, dates and witnesses.
The acceptance inspector shall be notified before the start of the required tests. All
items found at variance with the drawings or this specification during testing or
inspection by the acceptance inspector shall be corrected.
Test reports shall be delivered to the acceptance inspector as completed.
The design plate of FM-200 system, nameplate on main & reserved cylinders,
entrance & exit warning sign should be posted.
Abort switches should be installed at each doors of the protected area.
Activate an adjustable time delay that will delay the release of agent as required
for up to 30-seconds. The agent shall be released at the end of this time period
unless a manual release station is pulled. If the manual release station is pulled
the agent shall be released immediately by-passing any remaining time delay.
There is 20 sec as minimum. Delay in case of cross-zone (smoke detector) alarm.
Discharge of the system may be delayed by the activation of abort station
The pressure switch should be installed on the distribution line & should act in case
of discharging FM-200. Pressure switch will send an electric signal to the fire control
panel when the agent is discharged.
Concrete pedestal for Co2/FM-200 Cylinder storage shall be considered.
The cylinder valve assembly should be equipped with pressure gauge and a safety
burst disc.
Storage Container Arrangement
Storage containers and accessories shall be located and arranged so that inspection,
testing, recharging, and other maintenance activities are facilitated and interruption
of protection is held to a minimum.
Storage containers shall be located as close as possible to or within the hazard or
hazards they protect. Agent storage containers shall be located in suitable
enclosures.
Storage containers shall be securely installed and secured according to the
manufacturer‟s listed installation manual and in a manner that provides for
convenient individual servicing or content weighing.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 39 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Where storage containers are connected to a manifold, automatic means, such as a
check valve, shall be provided to prevent agent loss and to ensure personnel safety if
the system is operated when any containers are removed for maintenance.
Piping, Valves, and Discharge Nozzles: Comply with types and standards listed in
NFPA 2001, Section "Distribution," and Appendix A, for charging pressure of system.
Caution/Advisory Signs: Provide labeling on entrances, piping, extinguishing-agent
containers, other equipment, and panels according to NFPA 2001, including:
1. Entrance sign at each entrance to a protected space.
2. Manual Discharge sign at each manual discharge station.
3. Flashing Light sign required at each flashing light over each exit from a
protected space.
Warranty
All system components furnished and installed shall be guaranteed against defects in
design, materials, and workmanship for the full warranty period which is standard for
the manufacturer, but in no case less than two years from the date of systems
acceptance.
D. Clean Agent (NOVEC 1230) Fire Extinguishing System
This Section covers a fire protection system of the total flooding type utilizing a
NOVEC 1230 clean agent fire extinguishing system. System is a fixed installation
where equipment is designed and installed to provide fire extinguishing capability for
hazards described.
The system is required for the control pulpits, server rooms ,computer rooms and
other sensitive electronic equipment rooms and manned electrical rooms of the
Plant. The systems shall be designed, installed, tested, and maintained according to
NFPA 2001 as a total flooding suppression system.
The installing contractor shall be trained by the supplier to design, install, test, and
maintain NOVEC 1230 fire suppression systems. Complete hydraulic flow calculations,
from a UL listed computer program, shall be provided for engineered NOVEC 1230
clean agent systems. Calculation sheet(s) must include the manufacturer‟s name and
UL listing number for verification.
The individual sections of pipe and each fitting to be used, as shown on the
isometrics, must be identified and included in the calculation. Total agent discharge
time must be shown and detailed by zone.
Drawings, calculations and system component sheets shall be submitted for
approval.
The system shall provide a Novec 1230 minimum design concentration of 4.2% by
volume for Class A hazards and a minimum of 5.85% by volume for Class B hazards
in all areas and/or protected spaces, at the minimum anticipated temperature within
the protected area. System design shall not exceed 10% for normally occupied
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 40 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
spaces, adjusted for maximum space temperature anticipated, with provisions for
room evacuation before agent release.
The amount of agent in the main agent supply shall be at least sufficient for the
largest single hazard protected or group of hazards to be protected simultaneously.
The system shall be complete in all ways. It shall include a mechanical and electrical
installation, all detection and control equipment, agent storage containers, Novec
1230 agent, discharge nozzles, pipe and fittings, manual release and abort stations,
audible and visual alarm devices, auxiliary devices and controls, shutdowns, alarm
interface, advisory signs,functional checkout and testing, training and any other
operations necessary for a functional
UL listed NOVEC 1230 Clean Agent suppression system.
The system(s) shall be actuated by a combination of multisensory type photoelectric
Smoke detectors with rate of rise heat detectors . The detectors shall be installed for
maximum area coverage of 250 sq. ft. (23.2 m) per detector, in both the room,
under floor and above ceiling protected spaces. If the airflow is one air change per
minute, photoelectric detectors only shall be installed for maximum area coverage of
125 sq. ft. (11.6 m) per detector. (NFPA 72.)
The system shall be capable of being actuated by manual discharge devices located
at each hazard exit. Operation of a manual device shall duplicate the sequence
description above except that the time delay and abort functions shall be bypassed.
The manual discharge station shall be of the electrical actuation type and shall be
supervised at the main control panel.
Each supply shall be located within the hazard area, or as near as possible, to reduce
the amount of pipe and fittings required to install the system.
The NOVEC 1230 clean agent shall be stored in storage tanks. Tanks shall be
super-pressurized with dry nitrogen to an operating pressure of 360 psi @ 70 °F
(24.8 bar at 21 °C). Tanks shall be of high-strength low alloy steel construction and
conforming to NFPA 2001.
Tanks (master ) shall be actuated by either a resettable electric actuator
located in the releasing device.
Each tank shall have a pressure gauge and low pressure switch to provide
visual and electrical supervision of the container pressure. The low-pressure switch
shall be wired to the control panel to provide audible and visual "Trouble" alarms in
the event the container pressure drops below 290 psi (20 bar). The pressure gauge
shall be color coded to provide an easy, visual indication of container pressure.
Tanks shall have a pressure relief provision that automatically operates before the
internal nominal pressure exceeds 730 psi (50 bar).
Engineered discharge nozzles shall be provided within the manufacturer's guidelines
to distribute the NOVEC 1230 agent throughout the protected spaces. The nozzles
shall be designed to provide proper agent quantity and distribution. Nozzles shall be
available in 1/2 in. through 2 in. pipe sizes.
Each size shall be available in 180° and 360° distribution patterns.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 41 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Distribution piping and fittings shall be installed in accordance with the
manufacturer's requirements, NFPA 2001, and approved piping standards and
guidelines. All distribution piping shall be installed by qualified individuals using
accepted practices and quality procedures. All piping shall be adequately supported
and anchored at all directional changes and nozzle locations.
12.3 FIRE DETECTION AND ALARM SYSTEMS (FDAS)
GENERAL
HADEED is looking for qualified and experienced CONTRACTOR to handle the Fire
Detection/Alarm System (FDAS) on a turn-key basis, providing the total overall
solution for the design, supply and installation, and commissioning of systems
hardware, software, cabling and functionality as per HADEED requirements. He has to
provide all required fire alarm control and monitoring facilities to system users and
administrators (or additional) during system implementation similar to those in
existing system functionality.
CONTRACTOR shall be responsible for the required system with new proven up-to-
date analog addressable intelligent microprocessor based system in accordance to
the latest version of NFPA standards in design; equipment‟s, installation,
implementation, testing, commissioning and performance to be provided.
The new FDAS shall meet the required overall performance; provide high availability,
reliability, high intelligence, powerful, secure and safe in functional operation and
design with sufficient acceptable redundancies (100% redundancy) and spare
capacity (at least 20%). Highest level of reliability is required in design, equipment,
installation, commissioning and maintenance of the offered system. Manufacturer
guarantee shall be also provided from the main equipment manufacturer and
software developer.
In order to have the new FDAS operated in all designated areas with the required
functionality, the operation of the system network must be available and optimized
for each mode in centralized and decentralized functional system mode according to
the offered CONTRACTOR solution and existing Fire alarm network topology in
HADEED.
CONTRACTOR shall have fire alarm system professionals with experience in
Hardware & Software design, implementation, configuration and customization.
CONTRACTOR shall be familiar with existing HADEED system technological
environment (software, hardware, functionality and operation). CONTRACTOR shall
be capable to support HADEED for future system upgrades and modifications.
CONTRACTOR shall clearly define the application and functionality, analyze the
operational requirements, prepare preliminary architecture and provide overall
detailed solution according to HADEED Scope of work. CONTRACTOR shall visit the
site, conduct detailed surveys and study all factors related to the existing system and
its technological environment and discuss with HADEED team the details of existing
and proposed systems.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 42 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Field fire alarm control modules, Linear heat detector contact couplers & panels shall
be installed inside concrete enclosures free from dust /moisture ingress.
The proper system engineering is required to minimize the risk of system failure and
matching the system to the risk assessment to provide HADEED with a proven
system. It has to be considered that the required system shall be designed in the
way that is easy to operate, to maintain and to manage.
SCOPE OF WORK
A. DESIGN OF THE NEW FIRE DETECTION SYSTEM:
The offered design shall be based on latest and proven technology of fully ANALOG
ADDRESSABLE AND INTELIGENT COMPUTER (MICROPROCESSOR) DRIVEN FIRE
ALARM DETECTION TECHNOLOGY (Hardware, software, network, cabling, detection
devices, etc.) with capability of supporting conventional, addressable and analog
addressable detection devices and with the capability of integration and interfacing
with other systems with the same management and control platform. The system
shall be from the type that automatically programs itself upon initiation. The system
shall determine number and types of modules, number of analog addressable loops
and all devices integrated in the system. It shall also determine the type of devices,
device number, and record of the devices analog reading and setting. Suitable Style
(according to NFPA standards) for signaling line circuits and indicating appliance
circuits with individual device supervision and annunciation with primary and
secondary supervision shall be used.
The new system shall be as much as possible based on latest version of with multi-
user/multi-tasking features and capable to be fully remotely managed, controlled,
monitored, operated and configured of any system equipment linked to the Fire
alarm network (up to the lowest level of devices) from a ISD Hadeed base
centralized console .Decentralized management and control features shall be
additionally considered in design of the system and network.
The system shall be capable of generating the programming necessary to establish a
fully functional general alarm system upon initialization. Software operations are to
be stored in a non-volatile programmable memory. Loss of primary and secondary
power shall not erase instructions stored in the memory. Selective input/output
control functions and special coded operations shall be incorporated in the resident
software programming of the system. CONTRACTOR shall perform detailed study of
existing system considering required performance factors and software environment.
The new design shall meet specifications and requirements according to latest
version of NFPA standards (70, 71, 72 and 72E) to provide an overall quality system
with best performance figures. The system components shall be modular in design,
supporting single as well double loop of main system network, which has to carry
both detection and command signals to main system in Hadeed Base central control
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 43 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
room. The new system shall be powerful and reliable system capable of managing
(Control and monitoring) all assigned Fire alarm elements and equipment‟s as per
the approved design. All zone areas shall be covered with the new system. Response
time shall be very high [maximum (1) second from detection of alarm by the sensor
in the field until it is displayed and printed in TSD SFM/ ISD control room].
Based on offered design, CONTRACTOR shall specify in details the following:
Number of intelligent analog addressable circuits (loops), number of
intelligent analog addressable devices (detection devices: smoke detectors,
heat detectors, vertical heat detectors, thermal detectors, flame detectors,
duct detectors, linear heat cable sensors, UV detectors, water-flow and
tamper sensors, pull stations, bells, horn/strobes, sirens, modules, etc.) per
loop (+ number of conventional zones per loop) and conventional circuits,
number of addressable modules per loop, number of intelligent detectors
(sensors) per system, number of addressable modules per system, total
addressable / intelligent devices per system, display points per annunciator
and total number of annunciation points per system and Remote Repeater
panels.
Initiating device circuits, notification appliance circuits and signaling line
circuits of the new system.
All system modules including communication and control interfaces and
number of expansion capacity (I/O, cards, etc.)
Addressable input devices: Manual pull stations, point identification devices,
conventional zone interface modules, analog detectors (sensors, switches,
etc.), line isolator devices, annunciation devices, etc.
Addressable control devices, building control elements, addressable Relay
control elements, addressable signal control elements, isolation devices,
analog addressable loop modules, audio/visual devices, cabinets, batteries,
battery chargers, power sources, wiring conductors and connectors, outlet
boxes, junction boxes and electromagnetic door hold-open devices, etc.
System programming methods and database capabilities
Types of alarms and the way to handle this alarms
Number and types of power supplies and switching between main and hot
stand-by power.
Cabling methods including redundancy
Integration of the new system with existing system of plant in zone areas
Interface with Fire Fighting systems
Contractor should consider cross-zoning philosophy for areas with fire fighting
systems as mentioned in latest version of NFPA standards. Photo and Ionization
Smoke detectors or smoke ,combination detector and heat detectors to be used
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 44 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
according to nature of the area (Based on HADEED approval for type of detectors
and spacing). Vertical heat detectors should be used for transformers. Beam
detectors to be used for workshops and workshops. Linear heat detectors shall be
used for conveyor belts, cable tunnels and cable and overhead trays. Flame
detectors shall be used in areas with flames and fires (welding & grinding
workshops). Duct detectors should be installed for all A/C ducts around the plant.
The design shall provide highest system integration capability, scalability and
expansions with minimum reconfiguration. All material and equipment shall be
standard components, regularly manufactured and available and not custom
designed especially for this project. All new Fire Alarm system components (except
special application software for the system) shall have previously been thoroughly
tested and proven in actual use prior to installation on this project.
New system shall match harsh HADEED environment in design, equipment‟s and
installation. All system devices have to be monitored on existing system screen in
the TSD SFM/ ISD control room (and new fire station) with the same graphic and
texts structure (Arabic/English) to avoid confusion and duplication for the operators.
New FDAS should be considered as part of the whole overall system of HADEED in
design, performance and functionality.
System shall be capable to interface with other protective fire fighting systems such
as fire extinguishing or suppression systems (sprinkler, CO2, Deluge, FM200, etc.),
unlocking of doors, door release service, closing of smoke barriers doors, control of
heating, HVAC, operation of smoke control systems, Ventilation, fan control, fire
dampers, Access control systems, Emergency Voice/alarm systems (evacuation,
siren or public address systems, etc.), etc. All detection devices used to cause
operation of above mentioned systems should be monitored for integrity with new
fire alarm system (as per CONTRACTOR design and HADEED approval). New Fire
Alarm System shall be permitted to share components, equipment, circuitry,
installation wiring, management software and database with existing non-fire alarm
systems (in case required by HADEED).
All detectors, panels, switches, Manual Pull Stations, Annunciation devices, etc. in
the new system shall be intelligent analog addressable and controlled and monitored
from supervisory system TSD SFM/ ISD control room and Fire station.
Room indicators are required to be installed for room, false ceiling and raised floor
detectors.
Types of installed sensors and equipment‟s shall match the environment of its area in
design, protection, functionality and set-up of sensitivity (According to HADEED
approval).
Cabling of system components shall be specially manufactured for fire alarm
systems. All cables shall be fire proof. All outdoor cables shall be installed in steel
rigged pipes according to latest version of NFPA standards.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 45 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Armored cables (buried or U/G mineral insulated fire proof cables) shall be used for
outside installation.
Labeling of cables shall be done according to HADEED designation procedure
(According to HADEED approval).
HADEED requires optical fiber cables to transmit light for control, signaling, and
communications through an optical fiber. Fusion splicing will be only acceptable. All
required fiber tests such as Optical Time Domain Reflectometer (OTDR), attenuation,
bandwidth, continuity, etc. shall be done in professional way using proper testing
equipment and software. Only AVAYA SYSTIMAX cabling system (for cables, splice
kits, patch panels, patch cords, connectors, cable heads, sockets, face plates, pig
tails, accessories, etc.) shall be used by the CONTRACTOR and will be only
acceptable by HADEED for fiber and UTP cabling installation. All AT&T fiber cables to
be used shall be 3DSX OSP type.
The way of integration of the new systems with existing SIEMENS devices shall be
explained in details. All software and hardware required (at both sides plant and
HADEED Base / Fire station supervisory system) for the proper integration is fully
CONTRACTOR responsibility and should match the new recommended technology of
manufacturer.
CONTRACTOR shall submit detailed design to HADEED including time schedule,
detailed design drawings, project description including flowcharts, training program,
and spare parts availability.
In case of any failure or problem with the design during the design stage,
installation/implementation stage, testing stage, warranty stage or the 10 years
stability requirement stage, it is CONTRACTOR responsibility to rectify by
modification, adding of material or upgrade of software without any additional charge
to HADEED.
HADEED emphasized that the approval of design drawings and/or technical
documents by HADEED doesn‟t mean approval of accuracy of the system. Any
deviation from NFPA is design or installation material (even, if it is approved by
HADEED) should be CONTRACTOR responsibility to correct it without any cost impact
to HADEED.
B. SYSTEM HARDWARE AND EQUIPMENT:
CONTRACTOR should supply, install and commission all required equipment and
modules (fire alarm devices, interface equipment‟s and/or modules, controllers,
UPS‟s, power supplies, etc.) as per HADEED requirement and as specified in
CONTRACTOR design and scope of work and supply, and to match all HADEED
requirements for high performance intelligent and analog addressable Fire Alarm
System.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 46 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
All supplied equipment and devices must support the required real time optimized
Fire Alarm and detection functionality and operation with very high performance
factor. Any additional requirement to match HADEED environment is fully
CONTRACTOR responsibility to provide and install (such as plastic covers for the
Manual Pull Stations, Explosive proof devices, rigged pipes, Heat resistant pipes /
devices, etc.). All required testing equipment‟s should be proposed and provided by
CONTRACTOR. The list of required spare parts to be on-site and/or by CONTRACTOR
during two years warranty and maintenance time shall be specified.
CONTRACOR shall provide detailed list of proposed hardware for the new Fire Alarm
and detection system. The Document shall include the type of hardware used,
manufacturer, model, etc. All hardware supplied should be internationally recognized
as per HADEED request.
Fire Control Panels:
CONTRACTOR shall provide and install suitable fire alarm control panels in different
areas of the HADEED to monitor and control all types of fire alarm messages as per
his approved design. The minimum requirements shall be as following:
Fire control panel shall be intelligent analog addressable compatible and integratable
with existing SIEMENS in HADEED Base and plant area. The CONTRACTOR is
responsible for any changes required in all panels involved in the upgrade to match
the requirement of HADEED (CPU cards, control modules, I/O modules, power
supply, cabling system, etc.). Detailed design and proposal should be submitted to
HADEED for approval. It shall be capable to upload/download all programs &
information to / from a PC compatible computer.
Each Fire alarm panel shall be capable of automatic updating of initial system
program to accommodate added / deleted devices on any analog circuit, capable of
identifying and programming any general alarm condition for all installed devices.).
Capable to control and monitor maximum number of analog addressable,
addressable and conventional fire alarm devices (sensors, switches, detectors, MPS,
annunciation devices, etc.) and maximum number of inputs and outputs points. It
shall be possible to adjust the sensitivity of sensor / detector devices through the
control panel manually and / or automatically (day / night) with user-selectable
sensitivity settings per detector.
To have a bi-directional two-way communication with devices connected to it, other
fire alarm control panels in the fire alarm network and with the main system servers
and workstations.
To have the maximum suitable number of modular control cards such as
input/output cards, relay cards, analog cards, digital cards, indicating circuit
modules, initiating zone modules, release / pre-signal modules, time control
modules, interface cards (serial, parallel, RS232, RS485, SIB2048, audio, video,
etc.) and network communication cards, converter cards, transceiver cards, power
supply cards, etc. It shall also support two wire communications.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 47 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
To have at least two power supplies & 24 hours battery back-up. Battery back up
shall be sized in accordance with NFPA 72.
With alphanumeric digital display, local memory and possibly small local printer to
display, store and print as a minimum in case of alarms/events the building number,
floor, type of devices, and device address with the date and time of the alarm.
Fire control panel shall have control functional keys on keypad to be programmed as
required. All functions shall be programmable from the front keypad panel. It shall
have access restriction through passwords and/or codes. Priorities to type of
detectors, circuits or groups of detectors shall be possible to be assigned at fire
control panel.
Fire alarm panel shall indicate when the sensors connected and controlled through it
need cleaning. Dirty condition shall not decrease the detection sensitivity of the
sensor.
Shall have self-test routine feature for panel functionality and for each sensor linked
to it. Sensitivity and accuracy values shall be tested.
To have audible capability to announce alarms and to have the capability to be
interfaced with local announce systems such as horns, sirens, public address loud
speakers and flashing lights.
CONTRACTOR shall specify fire control panel physical size, installation and site
requirements, power requirements, etc.
Fire control panel shall be suitable to the area of installation, with minimum of IP66
enclosure protection, shall have compact housing design, surface-mounted steel
cabinet with dead front design, with hinged door and cylinder locks, sufficient space
for cables and to allow proper clearance between enclosure and live parts of the
panel equipment, one power socket shall be inside panel, panel shall be grounded
properly.
Panel shall have door contact for access control and has to be monitored in the main
system display in case of intrusion.
Shall have RESET button to be used for return of system to its normal state after
alarm condition has been remedied. Display shall step the user through reset
process. When alarm conditions continue, panel audible signal and alarm LED shall
be on. Display shall indicate total number of alarms and troubles present in the
system along with prompting to review the points.
Control panel shall have ability to store high number of events in a log. The events
shall be stored in battery-protected memory.
All faults of the panel (power, intrusion, battery low, connections, maintenance to be
monitored on system display.
Suitable means shall be provided (integrated in the panel) for testing the visual
indicating devices (meter or lamps).
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 48 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Each initiating circuit shall be powered and supervised so that a signal on one zone
doesn‟t prevent the receipt of signals from other zones.
Fire alarm control panel switches shall allow authorized persons to execute following
independent from main console in Hadeed Base control room/Fire station:
1. Trouble silencing switch
2. Evacuation alarm silencing
3. Transmitter disconnect switch to disconnect transmitting device and
cause operation of trouble signal.
4. Reset zones after initiating devices have been turned to normal
5. Perform complete operation and simulation test of control and
communication of each panel board.
6. Loss of power including any batteries shall not require the reloading of
a program from any source. Upon restoration of power, start-up shall
be immediate, automatic and shall not require manual operation. Loss
of primary power or sequence of applying primary or emergency power
shall not effect the transmission of alarm, supervisory or trouble
signals.
Initiating and Detection Devices:
CONTRACTOR shall supply and install all required manual and automatic initiating
detection devices, which are suitable to the area as per CONTRACTOR design and
HADEED approval. All detection devices shall be intelligent analog addressable
devices. It has to be possible as an example for the fire detection sensors to signal to
the main system how much heat (temperature) or how much smoke (present
obscuration) is being sensed by heat (thermal) or smoke detection devices or by
flame detector to recognize the type of flame (infrared, ultraviolet, visible radiation)
created by a fire.
CONTRACTOR shall specify in details the following required analog addressable
initiating devices which shall be installed as per the design of the system, Minimum
requirement are:
Manual Pull Station (MPS):
Analog addressable non-coded double action type with mechanical reset features. It
has to be high visible, easy to operate with attractive shape and textured finish and
with die cast aluminum semi-flush or surface mounted. With screw type terminals
Pull-lever or break-glass rod type boxes. Handle latches shall be in down position to
indicate that station has been operated. Require with a key for reset or test
If the area is dusty, the MPS should have a heavy-duty plastic cover to protect it
from dust.
MPS shall be installed in highly visible locations, on exit access routes and mounted
as per NFPA 72.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 49 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
When shown on drawings near doorways, the MPS shall be on latch side of the door
immediately adjacent to the doorframe wherever possible, and shall be provided with
a cover (dual action accessory) to prevent inadvertent false alarms.
Smoke Detectors:
Analog addressable of photoelectric and/or ionization (depends on area of
installation) microprocessor based type which sense and measure analog values of
smoke chamber and report to fire alarm panel and main system. Sensor shall clearly
differentiate between dust and smoke particles. Sensor shall be capable to be set for
different sensitivity settings dependent on the environment on its location.
Shall have optical sensing chamber, stable operation, built-in device identification,
built-in functional test switch. It shall be also compatible to the fire alarm control
panel and the fire detection system.
Shall be listed for ceiling and wall mounted applications.
Shall have bi-directional communication with fire alarm panel and main system
(using standard network protocol) for remotely configuration, set-up, calibration,
testing, control and monitoring of sensor status. It shall have two-wire loop
connection, integratable in the local addressable loop and of the main network as
analog addressable node.
Shall have separate base for ease of installation and maintenance and to allow
interchange of sensing elements. Each sensor base shall contain LED‟s for monitoring
the sensor status with 360C field viewing angle.
Sensors electronic shall be immune from false alarms caused by electromagnetic or
radio interference. Maintenance indication for clean up the sensor shall be monitored
on the sensor (LED), the panel and the main system.
Duct smoke detectors shall be installed in ducts with approved duct housing and with
perforated sampling cubes extending across the width of the duct. By activation the
duct sensor, all air-handling units shall be deactivated.
Sensor shall be nominal 24 Vdc powered by initiating circuit.
Heat (Thermal) Detector:
Shall be analog addressable heat (thermal) dual thermistor microprocessor based
sensors providing combination of rate-of-rise and fixed temperature type to sense
and measure actual analog heat values which shall be reported to fire alarm panel
and main system. Sensor shall be capable to be set for different sensitivity
dependent on the environment on its location.
Heat sensor shall be compatible to Fire alarm control equipment‟s and panels and to
main system. Sensors shall be listed for ceiling applications.
With bi-directional communication (using network standard protocol) with the fire
alarm panel and the system for remotely set-up, configuration, calibration, testing
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 50 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
and reporting of events/alarms. It shall have two wire loop connection, integratable
in the local addressable loop and in the main network as analog addressable node.
Sensor shall have 360 field viewing angle of visual alarm indicator with compact
style design, easy to install, to test and to maintain, and with built-in functional test
switch and tamper resistant feature.
With plug-in separate base for ease of installation and maintenance. Base shall
include LED‟s and sounder for local alarm or trouble indication. Maintenance
indication for clean-up the sensor shall be monitored on the sensor (LED), the panel
and the main system.
Sensors electronic shall be immune from false alarms caused by electromagnetic
interference and/or radio frequency interference. All sensor addressing information
shall be stored in fixed base.
Sensor shall be nominal 24 Vdc powered by initiating circuit.
Heat Sensitive Linear Heat Detection Cables:
Shall be installed at over-head trays, tunnel cable trays, belt conveyors and other
trays or areas as required by HADEED and as per approved CONTRACTORS design.
The HEAT-Sensitive-cable shall be analog addressable line-type device whose
sensing element comprises, in one type, two current carrying wires separated by
heat-sensitive insulation, which softens at the rated temperature, thus allowing the
wires to make electrical contact. Or another type, a single wire is centered in
metallic tube and the intervening space filled with substance, which, at critical
temperature, becomes conductive, thus establishing electrical contact between tube
and wire. Heat sensitive cables sensitivity shall be adjustable remotely from control
panel or system. Cable trays where heat sensitive cable is installed shall be
distributed in zones (variable lengths) with identification in the system for the zone
and the sensor.
Flame Detectors:
To be analog addressable microprocessor based sensor which detects and measured
the amount infrared, ultraviolet or visible radiation produced by fire and report to fire
control panel and main system.
To be installed as per CONTRACTOR design and suitable to installation locations.
Flame detectors shall be compatible to Fire alarm control equipment‟s and panels
and to main system.
With bi-directional communication (using network standard protocol) with the fire
alarm panel and the system for remotely set-up, configuration, calibration, testing
and reporting of events/alarms. It shall have two-wire loop connection, integratable
in the local addressable loop and in the main network as analog addressable node.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 51 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Sensor shall have 360 field viewing angle of visual alarm indicator, shall be compact
style design, easy to install, to test and to maintain, and with built-in functional test
switch and tamper resistant feature.
With plug-in separate base for ease of installation and maintenance. Base shall
include LED‟s and sounder for local alarm/trouble indication. Maintenance indication
for clean-up the sensor to be monitored on sensor (LED), panel and system.
Sensors electronic shall be immune from false alarms caused by electromagnetic
interference and/or R/F interference. All sensors addressing information shall be
stored in the fixed base.
Sensor shall be nominal 24 Vdc powered by initiating circuit.
Addressable Point Identification Device:
Point Identification devices shall be analog addressable to connect single supervised
conventional initiating contact type device such as Water flow switches on sprinkler
systems, Alarm switches on fire suppression systems (FM200, CO2, Dry chemical,
Foam, deluge, etc.), tamper switches, single detectors, and other devices to any of
two wire intelligent analog loop cards.
CONTRACTOR shall specify physical sizes of point identification devices to match
location of installation as per CONTRACTOR approved design.
It shall be capable of class “A” supervised wiring to the initiating devices.
It shall have integral LED‟s to annunciate module activation. Remote indicator shall
be position at eye-level installation when monitoring detector devices in false ceilings
and raise floors.
It shall provide an address setting means switches and store an internal identifying
code. The control panel shall identify location and type of the device.
It shall have bi-directional communication with control panel and system for
reporting, testing, calibration and set-up.
Other devices:
CONTRACROR shall specify any other type of analog addressable, switches, control
elements, announcement elements etc. required for new system as per his approved
design, such as:
Electrical conductivity sensors
Beam Detectors
Duct Detectors
Vertical Heat Detectors
Explosion proof Detectors
Rate compensation Detector
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 52 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
Rate-of-Rise Detectors
Addressable collective zone interface
Addressable control elements
Audio / visual alarm notification appliances (individual/combination)
such as Bells, Horns, Chimes,
Buzzers, sirens, speakers, PA, lamps, strobe lights, etc.
Electromagnetic door holder and door unlocking devices
HVAC interface devices
Emergency/Evacuation devices etc.
C. NETWORK ENVIRONMENT:
CONTRACTOR shall specify in details maximum number of nodes (panels) and
number of devices (points) managed through the network. He has to specify also all
interface modules required for the network. He has to specify the data throughput,
speed and restrictions of the network. The Network management shall be
independent from other systems. All main Fire alarm control panels will build the
core of the Fire alarm network. They shall be linked to the network in a double ring
topology, which means communication through the shortest way of the network.
The analog addressable detection devices and sensors shall be linked to the main fire
alarm control panel either in ring or star topology (bending on HADEED approval)
using proper type of fire alarm cable (fire proof). The response time in the main ring
shall be high.
Each control panel shall be capable to build its own sub-network to monitor and
control locally all devices connected to it in case of malfunction in the main network.
All data shall be stored in its local memory and transmitted to main server after
clearing the fault.
Full redundancy shall be considered in network design, cabling method, number of
wire strands, interface devices and power supplies. Remote stations (Fire station)
shall be part of the main network and shall be configured as nodes in the network to
monitor and control the system as assigned configuration.
D. POWER SUPPLY:
Sizing of power requirement is totally CONTRACTOR responsibility. He has to
calculate power requirement, find-out proper power sources in the location of
installation and provide and install all power panels, cables and installation
accessories required.
The power supply modules shall be integrated in the supplied equipment. Power
failure including the back-up power (UPS, Battery) shall cause the control modules of
the main system equipment (servers, control panels, etc.) to go into an orderly
shutdown with no loss of system program memory and / or data. Each Fire control
panel shall have a rechargeable stand-by battery for back-up power of at least 24
hours, which is suitable for the panel and the connected devices with LED for battery
status indication. All Main control panels shall have two internal power supplies, one
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 53 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
main (primary) and one hot-stand-by (secondary). The CONTRACOR is fully
responsible for the proper grounding of all system components in proper way.
Upon resumption of power, the control modules shall automatically restart and record
the time and date of the power failure and restoration at the respective site system.
The restart program shall automatically restart affected system equipment. The
operator shall be able to define an automatic power up time delay for each piece of the
system equipment under control.
All supplied equipment and the MANUFACTURER shall test modules before they are
shipped to HADEED. HADEED has the right to attend the Factory Acceptance Test at
CONTRACTOR or Manufacturer site without any cost impact to HADEED. A FACTORY
TEST CERTIFICATE with all Test results shall be handed over to HADEED before
starting with the installation.
The Fire Alarm System is an essential service and shall be operational at all times
without interruption. All requirements for power and connectivity including cables,
installation material and manpower are CONTRACTOR responsibility.
CONTRACTOR shall supply to HADEED all required test and measuring equipment‟s
including latest version of LAP TOP PC equipped with all data loggers‟ software.
E. SYSTEM SOFTWARE (SW):
CONTRACTOR shall be use new software of manufacturer.CONTRACTOR is also
responsible to provide all new software and train (to include in training program) HADEED staff on the new software package to be able to program, set-up, configure
and reconfigure of all fire alarm devices and equipment. The cost of this requirement
should be included in the quotation. Detailed technical documents and CD‟s shall be
provided to HADEED.
Any additional software packages (programs, operating systems, etc.) required for
new configuration and programming of the Fire alarm system is CONTRACTOR
responsibility to provide and implement. The SW packages shall support all
functional, user, maintenance and administration requirement of new system. The
SW shall match the hardware and network environment of the system. The used
software packages shall be approved and certified by the manufacturer of the Fire
Alarm System and shall be according to NFPA standards. CONTRACTOR shall
guarantee during alarm display process the quality and accuracy of the text and
drawings related to the alarm, message or event.
All SW packages supplied shall be with latest release at time of P.O. and error free
revision at time of final acceptance. Any sub-segment error fixes and revision
changes in software shall be provided free of charge. CONTRACTOR shall provide all
licenses required.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 54 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
CONTRACTOR shall provide to HADEED all required CONSULTANCY services for the
software configuration and customization of the new Fire Alarm System upgrade.
CONTRACTOR shall advice HADEED all software development to optimize the system
performance and endorse the basic solution.
CONTRACTOR shall clearly define in his quotation related to Fire Alarm System
software components his, HADEED, and Joint task responsibilities.
CONTRACTOR shall consider in overall project plan the importance of system
database back up. Frequency of back-ups needs to be included. CONTRACTOR shall
include best procedure for periodic system back up.
Configuration and testing software for all supplied equipment‟s shall be provided and
executed by the CONTRACTOR (for servers, workstations, printers, control panels,
detectors and sensors, network equipment‟s, etc.). The system control software shall
allow quick and easy configuration on standard and modular system features.
CONTRACTOR shall explain his proposed software packages including Operating
System, Relational Database, System distribution, Data management, User
interfaces, Inter-process communication systems, Visual display system, Graphics
software, Application programming software and interface, Simulation software,
Diagnostic software, etc.
CONTRACTOR shall hand over all programming source codes to HADEED without any
restrictions or additional charge.
CONTRACTOR shall include all required system simulation software, system
diagnostic software, trouble shooting software, maintenance management software
and network management software, etc.
System security management such as user passwords restrictions for operation and
maintenance, lockout tables, many programmable time event functions, etc. shall be
included.
The system shall be capable of reporting and archiving all system messages and all
system collected information including the degree and the day and time history of
this information. The reports shall be capable of being viewed and printed at
operator‟s workstation or any another specified station and printers connected to the
system.
F. SYSTEM INSTALLATION:
CONTRACTOR shall inspect and make detailed survey (before quoting), he shall
study all submitted drawings and check all available areas in HADEED which are in
touch with the new system. He should also study environment and resources (power,
communication, cable routing, etc.). Installation of Fire alarm equipment and cables
shall be according to latest NFPA standards version. Environment (hot, humid, dust,
electromagnetic fields, etc.) should be considered.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 55 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
CONTRACTOR shall follow TSD SFM/ ISD /Fire Section General Specification
Requirement as basis for design and installation of the whole Fire Alarm System as
additional to NFPA standards.
All cables to be used for connecting the systems shall be approved by TSD SFM/ ISD
/Fire Section before installation. All required installation accessories such as
closures, connectors, couplings, cable assemblies, assembly tools, grounding
material , etc. shall be supplied and installed by the CONTRACTOR . They shall be
approved by HADEED before installation .
It is CONTRACTOR responsibility to complete all installations to HADEED satisfaction.
Suitable installation tools and accessories shall be used. Installation team and
installation procedure shall be approved by HADEED in advance.
CONTRACTOR shall be responsible for supply of all necessary equipment and
materials, services and manpower to complete the work in orderly, efficient manner
to full satisfaction of HADEED and to comply with specifications set out in this scope
of work.
CONTRACTOR shall ensure that, upon completion of installation and prior to
acceptance of the new system, system performs all required Fire Alarm System and
its network operating functions detailed in his design and specification requested by
HADEED. CONTRACTOR shall ensure that during installation, implementation and
commissioning stages that no interruption or disturbance of HADEED existing Fire
alarm system and the activities or systems in HADEED. He will be responsible for any
disturbance or damage he may cause during his work in the project.
In case of Sub-Contracting any part of the installation, the SUB-CONTRACTOR shall
be professional in his field and shall at HADEED vendor list and approved by
HADEED.
CONTRACTOR shall follow HADEED standards for labeling of all installed equipment,
cables and material to match HADEED designation and labeling procedure. Types,
size of labels & characters and how to be fixed shall be discussed with HADEED.
Cables shall be installed according to approved CONTRACTOR design by HADEED.
CONTRACTOR shall provide to HADEED before installation all cable layouts and single
line diagrams including sizing, calculation and specifications for review, comments
and approval.
CONTRACTOR shall be responsible for pulling and installation of cables in
professional manner through HADEED existing and/or new cable routing networks
(ducts, trays, conduits and manholes). Any new cable routing or manholes required
for installation are CONTRACTOR responsibility to construct and install.
All civil work required for the installation including, excavation, foundation, towers or
poles, piping for cables, etc. will be CONTRACTOR responsibility. Warning tapes and
red tiles shall be used for cable recognition in case of excavation for new cable ducts.
All new cable ducts between manholes shall have only 6” PVC pipes embedded in
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 56 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
reinforced concrete. The final cable routing design with suitable method and material
shall be submitted by CONTRACTOR and approved by HADEED coordinator before
starting with the excavation.
All network cables shall be installed inside galvanized pipes. Inside manholes, they
shall be installed in flexible conduits and tighten with sufficient lose length on metal
support at manhole wall. Pull boxes shall be provided for each 50 m and marked with
“FDAS”. All outside cables shall be armored shielded cables with very good
mechanical protection. Cables shall be labeled in each manhole/ hand hole and at
each opening.
CONTRACTOR is responsible for exact measurements of proper cable lengths of the
used cables. For power cabling, CONTRACTOR is responsible to provide suitable
material such as cables, electrical panels, and breakers, installation accessories
according to HADEED and NFPA standards. Sizing / calculations are CONTRACTOR
responsibility. He has to check the exact power source in the zone area and
coordinate with the assigned electrical engineer.
Installation of any system or network equipment in plant area shall be inside IP66
enclosures with sufficient protection level. It is CONTRACTOR responsibility to study
location of the installation and provide the proper protection enclosure level against
environment effect (sun, rain, dust, etc.). It is his responsibility to connect to
suitable area power supplies. Grounding and lightning protection of all installations
are CONTRACTOR responsibility
A detailed installation, implementation and commissioning plan shall be provided to
HADEED in advance including time schedule and manpower requirement.
CONTRACTOR shall be responsible for supervision of the whole work. One project
manager shall be assigned to be full time in HADEED during project execution and
reporting every day to HADEED. Quality control of project execution (hardware,
software, functionality, integration and migration work) is totally CONTRACTOR
responsibility. Only qualified personnel shall be assigned during project execution.
G. PROJECT EXECUTION AND MANAGEMENT:
CONTRACTOR is request to study all submitted drawings and visit the site to
investigate, inspect and to observe equipment topology, environments, resources
and site conditions.
CONTRACTOR shall prepare a project schedule, which shows clearly the start of the
work, the milestones and the paths, which depend on HADEED. A list of all required
equipment, tools, and manpower and details of the required time for supply,
installation and commissioning with project organization chart shall be attached
concerning each area.
The development cycle of the required Fire Alarm System shall be as outlined in the
following points. The sequence of events and scope of work shall be described for
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 57 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
consecutive project stages. The phases of the project development shall be as
following:
System specification
System design (basic, detail)
System development (programming, test, etc.)
System delivery and installation
System integration (individual and overall) System acceptance (initial and
final)
Each phase shall be discussed and approved by HADEED before starting with the
next phase (stage). Proposals for time schedule shall be made in the bid to suit the
project installation and commissioning of the disciplines.
a. System Specification:
Detailed specifications of the Fire Alarm System shall be developed in close
cooperation with HADEED project team. At the end of this phase a memorandum of
consensus of detailed specification will be submitted to HADEED including detailed
project description, design layouts and As-built drawings for approval. The technical
specification shall include:
1. Functional description
2. Operating Concept:
3. Hardware description
b. System Acceptance:
After completion of the total system integration, the agreed system acceptance
process shall be performed. In the test the successful realization of the specified Fire
Alarm functions must be demonstrated. The system has to run at least one month
after the clearance of all deficiencies and CONTRACTOR shall confirm (in writing) that
the system is full operational without system failure. When the system performance
after one-month failure free operation is deemed satisfactory and acceptable to
HADEED project team, the system will be accepted for beneficial use and placed
under warranty. The successful proof of the overall functionality of this part will be
the signing of the Acceptance Certificate by CONTRACTOR and HADEED project
managers.
H. SITE TEST, COMMISSIONING AND FINAL ACCEPTANCE:
Upon completion of installation and implementation of the new FDAS, CONTRACTOR
shall start up the new system and perform all necessary calibration, testing, and
debugging operation and functions of all system modules, components and
equipment. CONTRACTOR shall functionally test the new system prior to new system
assembly, design and software upgrade. CONTRACTOR shall perform an ACCEPTANCE
TEST in presence of HADEED projects team. The new system components shall be
assembled as per job requirement to give complete functional test (hardware,
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 58 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
software, operation, communication, integration, etc.). The commissioning shall
include as a minimum:
Testing all hardware, links and connections
Testing of all functions (passive, active, etc.)
Tuning on the system until the required availability and performance are determined.
Switching on of the new Fire alarm system until required availability is determined.
Integration tests with existing system (Notifier or SIEMENS)
A trial run shall be done at the end of commissioning.
During trial run, optimization work to be carried out until new system features are
achieved as defined in HADEED requirements and CONTRACTOR design.
When the new system performance is deemed satisfactory to HADEED, it will be kept
running in for at least one month. If new system runs failure free for one month
(from date of clearance of all deficiencies), the new system will be accepted for
beneficial use and will be placed under warranty. COMPLETION and ACCEPTANCE
Certificate will be issued and signed by HADEED and CONTRACTOR project
managers. The warranty of the new Fire alarm system will begin from the date of the
last signature of the certificate.
TRAINING:
CONTRACTOR shall provide full instructions to train designated personnel in
HADEED for the operation, maintenance, programming and administration of
the system. The training shall be specifically oriented to cover the whole
Fire Alarm System. The provided training for HADEED staff shall be sufficient
(time and material) for proper operation, programming, set-up, simulation,
configuration, customization, calibration, administration and hardware repair,
trouble shooting & etc of the whole system. Training courses shall be
listed by the in details in his bid.
Training schedule shall be dedicated to system software engineer who is
responsible for managing and programming of system software,
communication network, hardware, and maintenance engineer who is
responsible for maintenance of supplied systems (including all equipment,
control panels, electronic modules, power supplies, UPS, etc.), and to the
user of the new system in TSD SFM/ ISD control room and fire station.
CONTRACTOR has to provide a detailed plan including training topics and
contents, time schedule, number of trainees, minimum required
qualification of the trainees, location of the training and training cost.
All training documents and material (including hard and soft copies) shall be
provided to HADEED by CONTRACTOR in advance (without additional charge
to HADEED).
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 59 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
System specific training and familiarization session shall include real practical
session for programming, modifying the existing program with new devices
and administration access management .
I. REGISTRATION OF EQUIPMENT:
Hardware and Software shall be fully licensed and; all components and
configurations shall be registered by the supplier of the system. All parts of the
complete assemblies shall carry type and serial numbers to spares to be easily
identified.
It is CONTRACTOR responsibility to arrange for any license required in the KSA (such
as ministry of interior, civil defense, royal commission, PTT, etc.), and the custom
clearance of the system components when received in KSA.
J. DOCUMENTATION AND MANUALS
CONTRACTOR shall supply following documentation in ENGLISH language:
Complete set of documentation to enable HADEED to review and approve (where
necessary), design software, operate and maintain the system and equipment
supplied. This shall include but not limited to:
1. Construction program
2. Arrangement and detail drawings (2 PCs)
3. Modified existing drawings (2 PCs)
4. Electrical drawings (2 PCs)
5. Block diagrams (2 PCs)
6. Wiring diagrams (2 PCs)
7. Functional design specification
8. Operating and maintenance manuals (2 PCs)
9. Complete spares list
10. Calculations
11. Specifications of equipment
All documentation shall be submitted for approval by HADEED prior to manufacture.
Failure to do so shall be at the cost of CONTRACTOR if deficiencies are found with the
design.
K. WARRANTY AND MAINTENANCE SUPPORT
CONTRACTOR shall, with high speed, rectify all defects arising from defective design,
materials or workmanship of CONTRACTOR or his sub-CONTRACTORS or from any
act of omission of CONTRACTOR that may appear during period, called WARRANTY
Period. Warranty period begins at date of acceptance of new fire alarm & fighting
system and expires (24) months thereafter. During aforementioned Warranty period,
CONTRACTOR shall promptly correct at his own cost any deficiency appearing in any
item supplied. A correction in the sense of this sub-item includes replacement of
deficient parts. For the replaced parts the Warranty Period shall be (24) months
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 60 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
starting from the date such parts are accepted by HADEED. Warranty period shall be
extended by a period equal period during which equipment or that portion thereof in
which a defect has developed cannot be used due to that defect. If any such defects
as aforesaid cannot be made good by CONTRACTOR within a reasonable time after
receiving a written notice form HADEED, HADEED has a right to correct the
deficiency of have it corrected by a third party in either case at CONTRACTOR risk
and expense.
WARRANTY for Fire Alarm System:
CONTRACTOR shall provide (2) year warranty for whole Fire alarm system including
performance, operation, functionality, equipment, software and installation. He shall
guarantee overall performance and stability of whole system. Following warranties
shall be provided:
All supplied equipment and installation for 2 years
Fiber cabling system (in case installed for 15 years
Availability of spare parts for 10 years
Overall performance guarantee for 10 years
CONTRACTOR shall fully maintain the whole system during the warranty time by
providing preventive maintenance, repair or replace of any defective material and
provide software consultancy and customization to HADEED (without additional cost).
CONTRACTOR shall provide to HADEED his maintenance strategy in details during
the warranty time.
MAINTENANCE & SUPPORT for Fire Alarm System:
CONTRACTOR will be responsible for maintenance of whole Fire Alarm system
including system during the agreed warranty period. The maintenance should be
preventive and corrective cover and should cover software, equipment and hardware,
cabling, etc. of the system to operate failure free with the required functionality and
performance. HADEED has the right to sign a maintenance contract with
CONTRACTOR after the end of the warranty time (They shall be ready to sign the
maintenance CONTRACT if HADEED interested).
13. CODES AND STANDARDS
All works, equipments and materials initiated to the expansion project shall be in
accordance with the latest version of the following standards:
NFPA codes and standards,
NFPA 1, Uniform Fire Code.
NFPA 10, Standards for Portable Extinguisher NFPA 12, Standards for Carbon Dioxide Extinguishing Systems
NFPA 13, Standard for the Installation of Sprinkler Systems
NFPA 14, Standard for the Installation of Standpipe and Hose Systems
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 61 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
NFPA 15, Standard for Water Spray Fixed Systems
NFPA 16, Standard for Deluge Foam-Water Sprinkler Systems and Foam-Water Spray Systems
NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection
NFPA 22, Standard for the Water Tanks for Private Fire Protection
NFPA 24, Standard for the Installation of Private Fire Mains and their Appurtenances NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-
Bases Fire Protection Systems NFPA 70, National Electrical Code NFPA 72, National Fire Alarm Code
NFPA 80, Standard for Fire Doors and Fire Windows
NFPA 101, Life Safety Code NFPA 221, Standard for Fire Walls and Fire Barrier Walls
NFPA 1961, Standard for Fire Hose NFPA 1963, Standard for Fire Hose Connections NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems
NFPA 5000, Building Construction and Safety Code
Other NFPA applicable Codes of practice
Hadeed Fire Section requirement
Underwriters Laboratories, Inc. (UL)
Factory Mutual Insurance (FM) Approval Guide
International Standard Organization (ISO) - ISO 9001
Other related International Codes, Regulations and Standards
Ministry of Interior, HCIS (High Commission for Industrial Security) Safety
and Fire Protection Directives for Industrial Facilities (SAFs).
14. APPROVAL AND CERTIFICATION
All equipment furnished for this project shall be new and unused. The proposed
equipment shall be subject to the approval of the HADEED Fire Section and no
equipment shall be ordered or installed without prior approval.
Other approvals or certifications will require supporting documentation that the
equipment needs or exceeds the requirements of the relevant NFPA code and be
individually approved by HADEED Fire Section before procurement. Fire Section shall
be consulted for the proposal and systems design and specifications. Also, system
specifications are available at the Fire Section for reference.
All the fire protection system design, installation ,testing and commissioning shall be
certified by Certified Fire protection Specialist (NFPA) from the third party
certification agency.
APPENDIX A
APPLICABLE SYSTEM (SAMPLE)
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 62 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
S/
N Area / Location
AU
TO
MATIC
DETECTIO
N
MAN
UAL A
LARM
FIR
E E
XTIN
GU
ISH
ER
WET T
YPE
AU
TO
MATIC
SPRIN
KLER S
YSTEM
PREA-A
CTIO
N TYPE
AU
TO
MATIC
SPRIN
KLER S
YSTEM
WATER
SPRAY/D
ELU
GE
SYSTEM
CO
2 S
YSTEM
NO
VEC1230/F
M2O
O
SYSTEM
FO
AM
-WATER S
PRAY
/DELU
GE S
YSTEM
FIR
E H
OSE C
ABIN
ET,
CLASS I
II
REM
ARKS
1 Outdoor
Transformer 0 0 0 0
2 Indoor
Transformer 0 0 0 0
1
3 Switch Room 0 0 0 0 1
4 MCC Room 0 0 0 0 1
5
Cable/Rooms/Floor
s/Trays/Tunnels/br
idge
0 0 0 0
1
6 Control/Computer
Rooms 0 0 0 0
2
7 PLC Room 0 0 0 0 1
8 Workshops 0 0 0 0 0
9 Offices 0 0 0 0 0
10 Production or
Process Area 0 0 0
0
11 LV& HV Rooms 0 0 0 0 1
12 Pump Rooms 0 0 0 0
13
Lubrication and
Hydraulic
Rooms/units
0 0 0 0
14 HVAC Rooms 0 0 0
15 Platforms 0 0 0
16 Substations 0 0 0 0 0 1
17 Cranes 0 0 0
18 Others x x x x X x x x x x x
Note: Contractor shall fill-out this table to include all facilities to be covered under
the scope of work. Any facilities discovered not being protected during construction
shall be contractor's full responsibility to assume all risk at his cost.
1 – Provision of at least two (2) Self-Contained Breathing Apparatus (SCBA) within
perimeter of protected area
*SCBA shall be Scott Air-Pak 50 with 60 minutes for industrial application with
EBSS (Emergency Breathing Support System).
2 - Manned gas Protected area shall be provided by airlock.
SSAAUUDDII IIRROONN && SSTTEEEELL CCOOMMPPAANNYY ((HHAADDEEEEDD))
TTSSDD SSFFMM// IISSDD FFIIRREE SSEECCTTIIOONN
HADEED FIRE PROTECTION SYSTEM SPECIFICATION REQUIREMENT 63 of 63
__________________________________________________________________________________ TSD SFM/ ISD Fire Section Specification Requirement 2010
X –Unforeseen areas shall be under the responsibility of the contractor, and shall be
provided with appropriate Fire Detection and Protection system in accordance
with HADEED Fire Section Requirement, without cost impact to HADEED.