1. VB Series PLC : An Overview
2. Main Components of the Master
3. Display Function
4. Number, Specification and Routing of Input / Output
5. Diagram of Input / Output for Every Model
6. Installation Method and Dimension Diagram
Appendix A (5×7 Font)
Appendix B (Instruction on Connection with HMI)
1-1 VB Series PLC Key Features1-2 Specification of VB Series PLC Function1-3 Regular Specification of VB Series PLC1-4 Instruction Table of VB Series PLC1-5 VB Series PLC Model Table
4-1 Input / Output Number and Precautions for Expansion4-2 Input Specification and Routing4-3 Output Specification and Routing
6-1 Installation Method6-2 Dimension Diagram
1
1
2
3
3
5
6
9
15
15
16
18
20
22
23
23
24
26
1
1. VB Series PLC: An Overview1-1 VB Series PLC Key Features
To be used as an indicator lamp for the input, output status of a controllerTo be used as an LED display showing numeric, characters and figures subject to users' requirements and preferences.A multi function display can be used to display a machine's status as an error message, a program's processing, etc., which, incorporated with the DAP-100 setting panel, would further become a parameter modification unit.
Combined systematic functionsThe maximum program capacity allows for 8K Steps, using Flash ROM storage programs, without replacing batteries.To be expanded up to 256 I/O points.To provide encryption, where intellectual properties can be duly protected.An expansion card with real time clock can be fitted additionally where a timed, periodical automatic control is needed.The master embedded a with multi-function display shows information in an instant, convenient manner.
Perfect communication functionsThe master integrated with the RS-232C standard interface can be directly connected to computers, Human-Machine Interfaces, and graphic control systems, as well as perform remote program compilation and modification through a MODEM. Communication expansion slots can be installed with a RS-232 or a RS-485/RS-422 communication expansion card, at its option, to perform various communication functions, such as Computer Link, CPU Link, Easy Link, MODEM Communication and RS Instruction Communication, etc.The master has a telephone dialing function, which may perform status reports and data collection remotely through telecommunication networks.
Diverse models meet a variety of control needsThe master offers more optional models from 14 points to 32 points.There are all-inclusive types of expansion modules including 4 IN/4 OUT module, 8 IN module, 8 OUT module, 16 IN module, 8 IN/8 OUT module and 16 IN/16 OUT expansion unit, providing complete expansion functions.Offering two I/O connection modes of terminal blocks and connectors. Providing two types of power input: AC 85V - 264V and DC 24V.Output type options: Relay, NPN Transistor, and PNP Transistors.Input types: Sinking/Sourcing sharing mode.To be incorporated with more special function modules like analog input/output, temperature input, position control.
Compact and efficient design saves installation space
Apply Ladder Master, Chinese-based Windows programming software
A leading feature in manipulating PDA as the programming tool
1. 2.
3.
A. 1.
2. 3. 4.
5.
B. 1.
2.
3.
C. 1. 2.
3. 4. 5.6. 7.
D.
E.
F.
A state-of-the-art multi function display.
2
1-2 Specification of VB Series PLC Function
Item VB0 Series VB2 Series Control Approach Programmed Storage, Circulating Scan
Programming Language Ladder Chart + Stepladder Chart
Control Method of Input / Output Processing
Basic instruction 0.375 – 12.56 µS Execution Velocity Applied Instruction Some µS – hundreds of µS
Basic instruction 27(including LDP, LDF, ANDP, ORP, ORF, NOT)
Stepladder Instruction 2 Number of Instructions
Applied Instruction 93
Program capacity 2.5K Steps Flash ROM 8K Steps Flash ROM
Component Comment Capacity 2730 (8 Chinese characters or 16 English characters for each comment)
Memory Capacity
Program Comment Capacity 10,000 Chinese characters or 20,000 English characters
Max. Input / Output Points 128 points: X0 – X77, Y0 – Y77
256 points: X0 – X177, Y0 – Y177
General 3120 points: M0 – M1999, M4000 – M5119
Latched 2000 points: M2000 – M3999 Auxiliary Relay (M)
For Special Use 256 points: M9000 – M9255
For Initiation 10 points: S0 – S9
General 490 points: S10 – S499
Latched 400 points: S500 – S899
Internal Relay
Stepladder Relay (S)
For Annunciator 100 points: S900 – S999(Latched)
100mS 200 points: T0 – T199 (Timer range: 0.1 – 3276.7 Sec.)
10mS 46 points: T200 – T245 (Timer range: 0.01 – 327.67 Sec.)
1mS (Retentive) 4 points: T246 – T249 (Timer range: 0.001 – 32.767 Sec.) Timer (T)
100mS (Retentive) 6 points: T250 – T255 (Timer range: 0.1 – 3276.7 Sec.)
General 100 points: C0 – C99 16-bit Up
Latched 100 points: C100 – C199
General 20 points: C200 – C219 Counter (C)
32-bit Up/Down Latched 15 points: C220 – C234
1-phase Counter 11 points: C235 – C245 (Max. Counter Frequency: 10KHz)
2-phase Counter 5 points: C246 – C250 (Max. Counter Frequency: 10KHz) High Speed Counter (C)
32-bit Up/Down, Latched
A/B Phase Counter 5 points: C251 – C255 (Max. Counter Frequency: 5KHz)
General 7680 points: D0 – D6999, D7512 – D8191
Latched 512 points: D7000 – D7511
File Register 7000 points: D1000 – D7999
For Special Use 256 points: D9000 – D9255
Register (D)
For Index 16 points: V0 – V7, Z0 – Z7
Branch Level (P) 256 points: P0 – P255
Interrupt Level (I) 15 points: 6 points for external interrupt, 3 points for timer interrupt, and 6 points for counter interrupt
Level
Nest Level (N) 8 points: N0 – N7
16 Bits -32768 – 32767 Decimal (K)
32 Bits -2147483648 – 2147483647
16 Bits 0H – FFFFH Numerical System
Hexadecimal (H) 32 Bits 0H – FFFFFFFFH
Pulse Output 2 points; Max. Output Pulse Frequency: 7KHz
Programming Device Link Interface RS-232C, directly connected to computer, Human-Machine Interface and MODEM
Communication Link Interface (Optional) RS-232C or RS-422 / RS-485
Real Time Clock (Optional) To indicate year, month, day, hour, min., sec. and week
Number of Special Modules Linked 2 (Max.) 8 (Max.)
Multi-function Display 128 display points, displaying input/output status and a varietyinformation.
Analog Knob 2 analog knobs, readings: 0 – 255
General
3
1-3 Regular Specification of VB Series PLC
Regular Specification
1-4 Instruction Table of VB Series PLC
Basic Instruction Table
Stepladder Instruction
Item AC Power Supply DC Power Supply
Input Voltage AC100~24V-15%/+10% DC24V-15%/+20%
Power Frequency 50/60Hz —
Allowable Interrupt Below 10ms 1ms
DC 24V Output 420mA —
Operation Ambient Temperature 0~55℃
Storage Ambient Temperature -20~70℃
Operation Ambient Humidity 10 – 90% RH, without mist/condensation
Storage Ambient Humidity 10 – 90% RH, without mist/condensation
Vibration Proofing Amplitude of 0.075mm at 10 – 55Hz; Acceleration of 1G at 55 – 150Hz; 80 minutes for each direction of X, Y and Z (8 min. of each scan time × 10 times = 80 min.)
Collision Proofing 10G; Three times for each direction of X, Y and Z
Noise Proofing Noise simulator: 1500Vp-p; Wave width: 1 µS; Frequency: 25 – 60Hz
Voltage Proofing 1500VAC , 1 min. between AC Terminal and the terminal of the ground line/500VAC , 1 min. between DC Terminal and the terminal of the ground line
Insulation Resistance 500VDC , 5M above between AC Terminal and the terminal of the ground line
Grounding The third grounding
Operation Surroundings No corrosive vapor or dusts present
Instruction Title
Function Device Instruction
Title Function Device
LD Initial logical operation contact type NO(normally open)
X,Y,M,S,T,C Denotes the start of a master control block
N0 – N7
LDI Initial logical operation contact type NC(normally closed)
X,Y,M,S,T,CDenotes the end of a master control block
N0 – N7
AND Serial link of NO(normally open) contacts
X,Y,M,S,T,CStores the current result of the internal PLC operations
–
ANI Serial link of NC(normally closed) contacts
X,Y,M,S,T,C Reads the current result of the internal PLC operations
–
OR Parallel link of NO(normally open) contacts
X,Y,M,S,T,CPops (recalls and removes) the currently stored result
–
ORI Parallel link of NC(normally closed) contacts
X,Y,M,S,T,C No operation or null step –
ANB Serial link of multiple parallel circuits
– Force the current program scan to end
–
ORB Parallel link of multiple contact circuits
– Initial logical operationcontact Rising edge pulse
X,Y,M,S,T,C
OUT Final logical operation type coil drive
Y,M,S,T,CInitial logical operationcontact Falling edge pulse
X,Y,M,S,T,C
SET Sets component permanently ON
Y,M,SSerial link of Rising edgecontacts
X,Y,M,S,T,C
RST Resets component permanentlyOFF
Y,M,S,T,C,DSerial link of Falling edgecontacts
X,Y,M,S,T,C
PLS Rising edge pulse Y,M Parallel link of Rising edge contacts
X,Y,M,S,T,C
PLF Falling edge pulse Y,M Parallel link of Falling edge contacts
X,Y,M,S,T,C
Contradictory Result
MC
MCR
MPS
MRD
MPP
NOP
END
LDP
LDF
ANDP
ANDF
ORP
ORF
NOT
Instruction Title Function Device
STL Initiation of Stepladder S
RET End of Stepladder Nil
Below
4
Applied Instruction Table
Instruction Title Instruction
Title Type FNC No.
D P
Function FNCNo.
D P
Function
00 CJ P Conditional Jump 61 D SER P Search
01 CALL P Call subroutine 62 D ABSD Absolute Drum
02 SRET Subroutine Return 63 INCD Incremental Drum
03 IRET Interrupt Return 64 TTMR Teaching Timer
04 EI Enable Interrupt 65 STMR Special Timer
05 DI Disable Interrupt 66 ALT Alternate state
06 FEND First End 67 RAMP Ramp –variable value
07 WDT P Watch Dog Timer refresh 69 SORT Sort data
08 FOR Start of a FOR-NEXT loop
Pro
gra
m F
ow
09 NEXT End of a FOR-NEXT loop
Handy In
stru
ctio
n
10 D CMP P Compare 70 D TKY Ten Key input
11 D ZCP P Zone Compare 71 D HKY Hexadecimal Key input
12 D MOV P Move 72 DSW Digital Switch (thumbwheel input)
13 SMOV P Shift Move 73 SEGD P Seven Segment Decoder
14 D CML P Compliment 74 SEGL Seven Segment with Latch
15 BMOV P Block Move 76 ASC ASCII code Convert
16 D FMOV P Fill Move 77 PR Print
17 D XCH P Exchange 78 D FROM P Read from a special function block
18 D BCD P Converts BIN to BCD 79 D TO P Write to a special function block
Com
pare
and M
ove
19 D BIN P Converts BCD to BIN
Exte
rnal D
efa
ult a
nd
Dis
pla
y
20 D ADD P Addition 80 RS Serial communication instruction
21 D SUB P Subtraction 81 D PRUN P Parallel Run
22 D MUL P Multiplication 82 ASCI P Converts HEX to ASCII
23 D DIV P Division 83 HEX P Converts ASCII to HEX
24 D INC P Increment 84 CCD P Check Code
25 D DEC P Decrement 85 VRRD P VR volume read
26 D WAND P Logic Word AND 86 VRSC P VR volume scale
27 D WOR P Logic Word OR 89 LINK Easy Link communication
28 D WXOR P Logic Word exclusive OR
Arith
metic
and L
ogic
al
Opera
tio
29 D NEG P Negation
30 D ROR P Rotation Right
Seria
l Com
munic
atio
n
31 D ROL P Rotation Left 90 DBRD P Read Data Bank
32 D RCR P Rotation Right with Carry 91 DBWR P Write Data Bank
33 D RCL P Rotation Left with Carry 147 D SWAP P Byte Swap
34 SFTR P Bit Shift Right 176 TFT 10mS Timer
35 SFTL P Bit Shift Left 177 TFH 100mS Timer
36 WSFR P Word Shift Right 178 TFK 1Sec. Timer
37 WSFL P Word Shift Left
38 SFWR P Shift register Write (FIFO Write)
Rota
ry a
nd S
hift
39 SFRD P Shift register Read (FIFO Read)
Mis
cella
ne
ous
Instru
ctio
ns
40 ERST P one Reset 147 D SWAP P Byte Swap
41 DECO P Decode 160 TCMP P Time Compare
42 ENCO P Encode 161 TZCP P Time Zone Compare
43 D SUM P he Sum of active bits 162 TADD P Time Add
44 D BON P Check specified bit status TSUB P Time Subtract
45 D MEAN P Mean 166 TRD P Read RTC data
46 ANS Timed Annunciator set 167 TWR P Set RTC data
47 ANR P Annunciator Reset 170 D GRY P Converts BIN to Gray code
48 D SQR P Square Root
Tim
e &
Convert
171 D GBIN P Converts Gray code to BIN
Data
Opera
tion
50 REF P I/O Refresh
51 REFF P I/O Refresh and filter adjust
52 MTR Input Matrix
53 D HSCS High Speed Counter Set
54 D HSCR High Speed Counter Reset
55 D HSZ High Speed Counter Zone compare
56 SPD Speed Detection
57 D PLSY Pulse Y output
58 PWM Pulse Width Modulation
Hig
h S
pee
d P
rocessin
g
Type
163
5
1-5 VB Series PLC Model Table
Item Model Main Specification
VB0 Series Main Unit
VB2 Series Main Unit
Expansion Unit
ExpansionModule
Special Module
CommunicationModule
CommunicationCard
ExpansionCard
Data BankConnection
Cable
Power Supplier
Setting Panel
VB0-14M★-◆
VB0-20M★-◆
VB0-28M★-◆
VB0-32M★-◆
VB0-32M★-◆C
VB2-16M★-◆
VB2-32M★-◆
VB2-32M★-◆C
VB-32E★-◆
VB-32E★-◆C
VB-16XY★
VB-16X
VB-8XY★
VB-8X
VB-8Y★
VB-16XY★-C
VB-16X-C
VB-8X-C
VB-8Y★-C
VB-4AD
VB-2DA
VB-4DA
VB-3A
VB-6A
VB-4TC
VB-8TC
VB-1PG
VB-1HC
VB-1COM
VB-PWR
VB-485A
VB-CADP
VB-232
VB-485
VB-MP1R
VB-RTC
VB-DB1R
MWPC-200
MWMD-200
MWPC25-200
VBPC09-200
VBMD09-200
VBPC25-200
VBEC-050
VBEC-100
VB-30PS
DAP-100
8 points, DC24V Input; 6 points output; offering 420mA of DC24V output; connecting input/output with terminal blocks
12 points, DC24V Input; 8 points output; offering 420mA of DC24V output; connecting input/output with terminal blocks
16 points, DC24V Input; 12 points output; offering 420mA of DC24V output; connecting input/output with terminal blocks
16 points, DC24V Input; 16 points output; offering 420mA of DC24V output; connecting input/output with terminal blocks
16 points, DC24V Input; 16 points output; offering 420mA of DC24V output; connecting input/output with ATX connector(with wire)
8 points, DC24V Input; 8 points output; offering 420mA of DC24V output; connecting input/output with terminal blocks
16 points, DC24V Input;16 points output; offering 420mA of DC24V output; connecting input/output with terminal blocks
16 points, DC24V Input; 16 points output; offering 420mA of DC24V output; connecting input/output with ATX connector (with wire)
16 points, DC24V Input; 16 points output; offering 420mA of DC24V output; connecting input/output with terminal blocks
16 points, DC24V Input; 16 points output; offering 420mA of DC24V output; connecting input/output with ATX connector (with wire)
8 points, DC24V Input; 8 points output; connecting input/output with terminal blocks
16 points, DC24V Input; connecting input with terminal blocks
4 points, DC24V Input; 4 points output; connecting input/output with terminal blocks
8 points, DC24V Input; connecting input with terminal blocks
8 points output; connecting output with terminal blocks
8 points, DC24V Input; 8 points output; connecting input/output with ATX connector (with wire)
16 points, DC24V Input; connecting input with ATX connector (with wire)
8 points, DC24V Input; connecting input with ATX connector (with wire)
8 points output; connecting output with ATX connector (with wire)
Analog Input Module; four 12-bit points; arbitrary option of Voltage or Circuit type
Analog Output Module; two 12-bit points; arbitrary option of Voltage or Circuit type
Analog Output Module; four 8-bit points; arbitrary option of Voltage or Circuit type
Analog Input/Output Module; two 12-bit points for input and one 12-bit point for output; arbitrary option of Voltage or Circuit type
Analog Input/Output Module; four 12-bit points for input and two 12-bit points for output; arbitrary option of Voltage or Circuit type
Temperature Input Module; four J/K Thermo Couple points for input; input range:-100~1200℃; resolution: 0.1~0.3℃
Temperature Input Module; eight J/K Thermo Couple points for input; input range:-100~1200℃; resolution: 0.1~0.3℃
Single-axle Pulse Output Position Module; Output Pulse Frequency: 10 - 100Kpps
High Speed Counter Module; one point 45KHz High Speed Count input;
Serial Link Communication Module; RS-232/RS485 Interface; Photocoupler Isolation; Communication Distance 1000M
Power Expansion Module;Input AC85~264V,Output for PLC DC5V 0.4A/DC12V 0.8A, DC24V 0.5A for sensors
RS-485 Communication Module; Photocoupler Isolation; Communication Distance 1000M
Dual Communication Port Expansion Module;1 Port Isolation RS-422/RS-485;1 Port Isolation RS-485; Communication Distance 1000M
RS-232 Communication Expansion Card
RS-422/RS-485 Communication Expansion Card
8K Steps Flash ROM Memory Cartridge (Only 2.5K Steps programs stored for VB0 Master); including RTC function
RTC (Real Time Clock) Expansion Card
128K Words Data Storage Expansion Card; including RTC (Real Time Clock) function
Connection cable of PLC Writer Slot and Computer (9-pin female connector) with a length of 200 cm
Connection cable of PLC Writer Slot and Modem (9-pin male connector) with a length of 200 cm
Connection cable of PLC Writer Slot and Computer (25-pin female connector) with a length of 200 cm
Connection cable of PLC Writer Auxiliary Slot and Computer (9-pin female connector) with a length of 200 cm
Connection cable of PLC Writer Auxiliary Slot and Modem (9-pin male connector) with a length of 200cm
Connection cable of PLC Writer Auxiliary Slot and Computer (25-pin female connector) with a length of 200 cm
VB Series PLC Expansion cable with a length of 50 cm
VB Series PLC Expansion cable with a length of 100 cm
30W power supply; power input: AC 110V or AC 220V (optional); power output: DC 24V 1.2A and DC 5V 0.2A
4-key data setting panel, can be incorporated with multifunction display for multiple sets of parameter data settings
★ indicates the input type R: Relay Output T: NPN Transistor P: PNP Transistor
◆ indicates the power type A: AC100~240V-15%/+10% D: DC24V-15%/+20%
6
2. Main Components of the Master
3. Power Input Terminal
2. DC24V Output Terminal1. System Grounding Terminal
16. Analog Knob15. Dipswitch
14. Communication Expansion Card Slot
13. Program Writer Auxiliary Slot
12. Program Writer Slot
11. Indicator LED
10. Input Indicator LED
Multi Function Display
9. Output Indicator LED
5. Input Terminal
6. I/O Expansion Slot
7. Memory Cartridge Slot
8. Output Terminal
System Grounding TerminalTo reinforce noise proofing and produce against electrical shocks; apply the third grounding (grounding resistance: below 100 Ω)DC24V Output TerminalTo provide 420mA of DC 24V output; power used in input contacts and input sensors features over-loading, short-circuit protectionPower Input TerminalPLC Operation Power (AC Type: AC 100 - 240V; DC Type: DC 24V)Bucket (Installation Hole Φ4.5mm)Used for installation of DIN35mm aluminum tracks; to be outstretched as an installation hole with a safety distance of 100mmInput TerminalUsed for wiring of external input contacts; this series also offers connector wiring to save wiring labor hoursI/O Expansion SlotInstalling diverse I/O expansion modules and special modules
1.
2.
3.
4.
5.
6.
Memory Cartridge Slot
To be fitted with a memory cartridge, a RTC (Real Time Clock) and a data bank expansion card.
Program capacity of Memory Cartridge: 2.5K Steps Flash ROM (VB0)
8.0K Steps Flash ROM (VB2)
Output Terminal
Used for routing external output contacts. This series of products also offers connector routing to
effectively save routing labor hours.
Output Indicator LED
The LED turns on while the output contact is ON.
Input Indicator LED
The LED turns on while the input contact is ON.
Status Indicator LED
Program Writer Slot (1st COM Port)
Used with a USB Type-A connector for programming purposes.
Program Writer Auxiliary Slot (1st COM Port)
Used with a JST 2.0mm connector for human-computer interfaces and graphic control systems.
Completely parallel linked with prongs of the USB Type-A connector of Program Writer Slot, only one
can be used.
Communication Expansion Card Slot
To be fitted with VB-232 or VB-485 communication expansion cards.
Before installation, remove securing bolts on the upper left side first, insert a communication expan-
sion card, and then screw the securing bolts.
Remove the type side panel on the left while installing VB-485
The function of a JST 2.0mm 4-pin socket on the communication expansion card is comparable to
that of the program writer socket.
7
7.
8.
9.
10.
11.
12.
13.
14.
LED Indication Status
PWR (Green)
RUN (Green)
ERR (Red)
ON
OFF
ON
OFF
ON
Flash
OFF
Power Input
Power Cut off
Run
Stop
Failure (Shutdown)
Discrepancy (Shutdown)
Normal
8
Dipswitch
Analog Knob
Read the knob volume, 0 - 255, with the VRRD instruction and read the knob scale, 0 - 10, with
the VRSC instruction.
The adjustment will be set much easilier with the numeric shown in the display.
Dipswitch OFF ON
SW1-1
SW1-2
SW1-3
SW1-4
Stop
Display I/O
Display I/O Range:X0~X77Y0~Y77
NC
Run
Display messages
Display I/O Range:X100~X177Y100~Y177
NC
SW1-1: Change-over Switch of Run/Stop; the device operates as the status indicated while power
is ON.Run/Stop controls, while the system is booted, and operates with the latest command
of SW1-1 and Ladder Master (programming software).
SW1-2: Change-over Switch of the display, selecting to display I/O or messages.
SW1-3: Change-over Switch displaying the I/O range
Sw1-4: NC
The ON/OFF status of SW1-2~SW1-4 will be displayed in Special Relay M9080 - M9082
15.
16.
9
3. Display FunctionThe display can be used for multi-functional display when SW1-2 turns ON. The display mode is set by
D9080 while D9081 becomes the auxiliary register. Data is displayed with a decimal system; only
effective numbers are displayed while the data exceeds the display range. Should the data be
negative, the data will be displayed as a positive number.
For instance, when the data in Mode 3 is K-32767, the display shows 2767.
The function of the display is specified as in the table below when SW1-2 turns ON.
Mode 0
Mode 1
Mode 2
Mode 3
Mode 4
Mode 5
Mode 6
Mode 7
D9080
K0
K1
K2
K3
K4
K5
K6
K7
D9081
N/A
Indicator(Kn)
Indicator(Kn)
Indicator(Kn)
Indicator(Kn)
Indicator(Kn)
See Instructions
Indicator(Kn)
Display
I/O
Number, Character, Graph
E123
1234
1256
1123
A123
12345
Effective I/O ON/OFF status
ON/OFF status of the bit in Dn - Dn+7
E, a 3-digit number of Dn
A 4-digit number of Dn
A 2-digit number of Dn+1, a 2-digit number of Dn
A 1-digit alphanumeric of Dn+1, a 3-digit number of Dn
A 1-digit alphanumeric, a 3-digit number
A 5-digit number of Dn
Display Content
Display Mode 0: I/O ON/OFF Status Display
SW1-2=ON (display messages)
D9080=K0 (Mode 0)
The display shows the I/O ON/OFF status.
This mode is used in combination with other modes, so as to be more flexible.
For example, the I/O ON/OFF status is shown permanently under the machine, and Mode 2 of
Error Code is displayed when any discrepancy occurs.
Display Mode 1: Display of Number, Character and GraphThis mode assigns D9081 to be the indicator register. Its content value Kn directs the indicator to
Register Dn. The data content (16×8=128 [bits]) of 8 registers, Dn - Dn+7, will be displayed in bit-form
on 128 LEDs of the display.
(1)
(2)
Example:
(displays messages)
(Mode 1)
(displays the data content of D100 - D107)
indicated as 201F in a hexadecimal system
The font in the example is 5X7. For more information on alphanumeric data, please refer to Appendix A.
Approach to displaying information for the LED display:
1. First of all, list the strings that are to be displayed and direct the content value of D9081 to the
heading position;
2. Then, increase the content value of D9081 with a regular time interval (e.g. 0.2 Sec); and
3. Exhibit the listed strings in LED-form on the display.
10
Display Mode 2: Display of Error Code This mode assigns D9081 to be the indicator register. Its content value Kn directs the indicator to Register Dn. The lower three digits of Dn will be shown on the right side of the display, and the character "E", shown on the left side, indicates an error code. Please refer to the following example for details.
Display Mode 3: Display of A Four-digit (0 - 9999) Numeric This mode assigns D9081 to be the indicator register. Its content value Kn directs the indicator to Register Dn. The lower four digits of Dn will be shown on the display. Please refer to the following example for details.
Display Mode 4: Display of Two Two-digit (0 - 99) Number This mode assigns D9081 to be the indicator register. Its content value Kn directs the indicator to Dn. The lower two digits of Dn will be shown on the right side of the display, and the lower two digits of Dn+1, on the left side. Please refer to the following example for details.
Example
Example
Example
SW1-2 = ON (displays messages)D9080 = K2 (Mode 2)D9081 = K100 (displays lower three digits of D100)D100 = K123
SW1-2 = ON (displays messages)D9080 = K3 (Mode 3)D9081 = K100 (displays lower four digits of D100)D100 = K1234
SW1-2 = ON (displays messages)D9080 = K4 (Mode 4)D9081 = K100 (displays lower two digits of D100 and lower two digits of D101)D100 = K56D101 = K12content value D101 content value D100
(3)
(4)
(5)
This mode can be applied to the timer display, the settings of the counter, and the current value.
11
Display Mode 5: Display of A One-digit Alphanumeric (0 - 9, A - Z or a - z) and A Three-digit Number (0 - 999)This mode assigns D9081 to be the indicator register. Its content value Kn directs the indicator to Register Dn. The lower three digits of Dn will be shown on the right side of the display, and an alphanumeric specified by b7 - b0 of Dn+1, on the left side of the display where the decimal point specified by b10 - b8 of Dn+1 flashes. Please refer to the following example for details.
This mode can be applied to a multi-data display where the data title is shown on the left side and the data content is shown on the right.
A Program Example of Ladder Chart:Simply adjust the PLC's VR1 to see the content value of D0 - D9 on the display and the data title, 0 - 9, while performing the following program.
(6)
ExampleContent Value of D100
SW1-2 = ON (displays messages)D9080 = K5 (Mode 5)D9081 = K100 displays lower three digits of D100 displays the alphanumeric specified by b7 - b0 of D101 in the position where the decimal point specified by b10 - b8 of Dn+1 flashesD100 = K256D101 = H10A
Contrast of Numbers and Displayed AlphanumericNumber Displayed
Character Number Displayed Character Number Displayed
Character Number Displayed Character
Set the display mode of the display
Set the indicator register of the display
Read the value of VR1
Convert the value of VR1 into a number of 0 - 9
Fill in the alphanumeric on the left side of the display
Read the content value of the register corresponding to D0 - D9 and display the value on the right side
12
Display Mode 6: Data Programmer ModeThis mode shows the same screen as displayed in Mode 5. Read the instructions on Mode 5 before reading the instructions in this section. This mode can set multiple sets of data with 4 push-button switches.The special register and the special relay used in this mode are explained as below: <1> D9080: Mode Designation (D9080 = K6)<2> D9081:
<3> D9082:
<4> D9083:
<5> D9084:
<6>The monitoring/programming functions of the data programmer's numbers are performed with 5 special relays (such 5 special relays only perform the corresponding functions in this mode). It's available to use external input signals to drive corresponding special relays to achieve external operations in practical application.M9084: Monitoring function. The display shows the table contents directed by D9084 while the contact turns ON.M9085: Setting function. The data setting function is accessed while the contact turns ON.M9086: Increasing function (+).M9087: Decreasing function (-).M9088: Output of error signals. When the data attribute is set to be readable only and the setting function is to be performed, M9088 will become ON for a scan time.
(7)
Indicator Register for the table of data titles. Its content value Kn directs the indicator to Dn, where Dn is the heading register for the table of data titles and the length of the table is determined by D9083(L). Each register in this table can designate a data title, the position of its decimal point, and the data attribute (R/RW).
Indicator Register for the table of data contents. Its content value Km directs the indicator to Dm, where Dm is the heading register for the table of data contents and the length of the table is determined by D9083(L). Each register in the table can accommodate three digits of numeric data (0 - 999).Register for the length of the table. Its content value KL designates the length for the table of data titles and the table of data contents.Register for task indicator. Its content value Kp (=K0~K[L-1]) designates the length for the table of data titles and the table of data contents, and displays its corresponding table content on the display.
Designate the position of the decimal point
Designate the data attribute as 0: readable and writeable ; 1: readable only
Table of Data Titles Table of Data Titles
13
Suppose M9084 - M9087 should be driven by the external push-button switch,
The operation process of the mode is shown as follows:
Press
the display shows relevant data designated by D9084.
Press or to change the content value of D9084; the display will change accordingly.
After pressing,
the first digit begins to flash. Press orto change the data of the first digit.
After pressing,
the second digit begins to flash. Press orto change the data of the second digit.
After pressing,
the third digit begins to flash. Press orto change the data of the third digit.
Press
to finish the data setting.
Press
to surrender the setting.
Example SW1-2 =ON (displays messages)D9080 = K6 (Mode 6)D9081 = K7000; the heading register for the table of data titles is D7000 (providing the latched function)D9082 = K7010; the heading register for the table of data contents is D7010 (providing the latched function)D9083 = K3; the length of the table is "3", indicating there are 3 sets of dataD9084 = K0; as the content value of the current task indicator is "0", the first set of data in the table will be exhibited in the display
Data Title Numeric Display Data AttributeReadable & WriteableReadable onlyReadable & Writeable
Data AttributeCRH
34.91281.00
A Program Example of Ladder Chart
is the button
is the button
is the button
is the button
X0 - X3 constitute the setting keyboard.
Set the display mode for the display
Designate the heading register for the table of data titles
Designate the heading register for the table of data contents
Set the length of the table
Initialize the table indicator
Set the title, format and attribute of each set of data
14
Display Mode 7: Display of A Five-digit (0 - 32767) NumberThis mode assigns D9081 to be the indicator register. Its content value Kn directs the indicator to Register Dn. The content value of Dn will be shown on the display. Please refer to the following example for details.
(8)
Example
SW1-2 = ON (displays messages)D9080 = K7 (Mode 7)D9081 = K100 (displays the content value of D100)D100 = K12345
15
4. Number, Specification and Routing of Input/Output4-1 Input/Output Number and Precautions for Expansion
All models of VB Series Main unit (VB0-14M....VB2-32M) occupy the I/O address of X0 - X17/Y0 -
Y17; the I/O address of the first expansion module will be aligned from X20/Y20.
Special modules do not occupy the I/O address while VB-8XY will occupy 8 points of input and 8
points of output.
Instructions on the condition related to I/O expansion
VB Series PLC's Main unit and expansion units themselves are provided with power supply for
circuits which is also the power supply that expansion modules and special modules depend on. The
number of modules can be expanded from the Main unit and the expansion unit is specified as
below:
The following two requirements should be met when modules are expanded from the Main unit
(1)
(2)
The following two requirements should be met when modules are expanded from the expansion unit
(1)
(2)
The maximum number of input/output points: 128: X0 - X77 and Y0 - Y22 (VB0)
256: X0 - X177 and Y0 - Y177 (VB2)
The number of special modules which can be connected: 2 special modules max. (VB0)
8 special modules max. (VB2)
The number of expansion modules) + (The number of special modules × 2) ≦ 4
Output points of the Main unit and output points connected behind the Main unit
(The number of relays which are ON × 6) + (The number of transistors which are ON) ≦192
The number of expansion modules) + (The number of special modules × 2) ≦ 12
Output points of the expansion unit and output points connected behind the expansion unit
(The number of relays which are ON × 6) + (The number of transistors which are ON) ≦ 192
DC 24V Output Limit (Micro) SwitchNPN/PNP Proximity (Photoelectric) Switch Selector SwitchChange-over Switch PLC Main Unit Push-button Switch Expansion Unit
4-2 Input Specification and Routing
(1) Input Specification
Item SpecificationExternal Power Supply
Input Signal Circuit
Input ON Circuit
Input OFF Circuit
Input Resistance
Input Reaction Time
Input Signal Type
Isolation Approach
DC24V±10%
7mA/DC 24V
Above 3.5mA
Under 1.7mA
3.3 KΩ approximately
10 mS approximately
No voltage contact or NPN/PNP open-collector transistor
Photocoupler
The input responding time at X0 ~ X7 can be set 0 ~ 60mS.
(2) NPN Input Routing
(3) PNP Input Routing
17
(4) Routing Approach to the Sensor Power Supply Provided by PLC
NPN Routing PNP Routing
NPN Routing PNP Routing
(5) Routing Approach to the Sensor Power Supply Provided from the External Source
AC Power Supply Contactor
Fuse Surge Arrest RC 0.1 μf + 100 ~ 120Ω
Inductive Load DC Power Supply
Incandescent Lamp LED
Neon Lamp Surge Arresting Diode
18
+
4-3 Output Specification and Routing
(1) Output Specification
Output Type NPN/PNP Transistor Output Relay Output
Loading Power Supply
Maximum Load
Open-circuit Electric Leakage
Output Reaction Time
Isolation Approach
DC5~30V
0.5A
Below 0.1mA
Below 0.2mS
Photocoupler
Below AC 250V/DC 30V
Resistance Load of 2A/PointInductive Load of 80VA/PointLamp Load of 100W/Point
10mS approximately
Mechanical Isolation
(2) Relay Output Routing
19
(3) NPN Output Routing
(4) PNP Output Routing
DC Power Supply
Fuse
Electrical Interlock
Inductive Load
LED
20
VB-8XY
VB-8XVB-8Y
VB-16XYVB-16X
VB0-32M-A/VB2-32M-A/VB-32E-A
VB0-28M-A
VB0-20M-A
VB0-14M-A
VB2-16M-A
5. Diagram of Input/Output for Every Model
21
22
6. Installation Method and Dimension Diagram6-1 Installation Method
(1) Installation of 35mm Aluminum Rail (DIN RAIL)
(2) Installation with Installation Hole
23
6-2 Dimension Diagram
(1) Various Main Unit and Expansion Unit
(2) I/O Expansion Module and Special Module
24
Appendix A-1Font Data Font Data Font Data Font Data
25
Appendix A-2Font Data Font Data Font Data Font
26
Appendix B-1
Instructions on Connection between VIGOR VB Series PLC and Fuji Human -Machine Interface
(1) COM Port (2nd
COM Port), VB-485
(2) COM Port (2nd
COM Port), VB-232
(3) Writer Slot (1st
COM Port)
(4) Writer Slot (1st
COM Port)
(5) Writer Auxiliary
Slot (1st COM Port)
5P European-Type
Terminal Block
D-Sub 25-Pin Male
Connector
D-Sub 9-Pin Female
Connector
D-Sub 25-Pin Male
Connector
COM Port, Fuji Human-
Machine Interface
COM Port, Fuji Human-
Machine Interface
Commercialized Connector
COM Port,
Fuji Human-
M a c h i n e
Interface
COM Port, Fuji Human-
Machine Interface
D-Sub 25-Pin Male
Connector
D-Sub 25-Pin Male
Connector
COM Port, Fuji Human-
Machine Interface
USB Type-A Connector
JST 2.0 Connector
Please set the communication port (2nd COM Port) of the communication expansion card as Computer Link protocol Station number "0" while the communication rate is 19200bps.
* The VBFDHMI-200 connection cable supplied by VIGOR can be used as the connection cable herein.
27
Appendix B-2
Instructions on Connection between VIGOR VB Series PLC and Digital Human-Machine Interface
(1) COM Port (2nd
COM Port), VB-485
(2) COM Port (2nd
COM Port), VB-232
(3) Writer Slot (1st
COM Port)
(4) Writer Auxiliary
Slot (1st COM Port)
5P European-Type
Terminal Block
D-Sub 25-Pin Male
Connector
D-Sub 9-Pin Female
Connector
D-Sub 25-Pin Male
Connector
D-Sub 25-Pin Male
Connector
D-Sub 25-Pin Male
Connector
USB Type-A Connector
JST 2.0 Connector
COM Port, Digital Human-
Machine Interface
Please set the communication port (2nd COM Port) of the communication expansion card as Computer Link protocol Station number "0" while the communication rate is 19200bps.
COM Port, Digital Human-
Machine Interface
COM Port, Digital Human-
Machine Interface
COM Port, Digital Human-
Machine Interface
* The VBFDHMI-200 connection cable supplied by VIGOR can be used as the connection cable herein.
28
Appendix B-3Instructions on Connection between VIGOR VB Series PLC and Hitech Human-Machine Interface
(1) COM Port (2nd COM Port), VB-485
(2) COM Port (2nd COM Port), VB-232
(3) Writer Slot (1st COM Port)
(4) Writer Auxiliary Slot (1st COM Port)
5P European-Type Terminal Block D-Sub 25-Pin
Male Connector
D-Sub 9-Pin Female Connector
D-Sub 25-Pin Male Connector
D-Sub 25-Pin Male Connector
USB Type-A Connector
JST 2.0 Connector
COM Port, Hitech Human- Machine Interface
COM Port, Hitech Human- Machine Interface
COM Port, Hitech Human- Machine Interface
COM Port, Hitech Human- Machine Interface
D-Sub 25-Pin Female Connector
* The MWPC25-200 connection cable supplied by VIGOR can be used as the connection cable herein.
* The VBPC25-200 connection cable supplied by VIGOR can be used as the connection cable herein.
Please set the communication port (2nd COM Port) of the communication expansion card as Computer Link protocol Station number "0" while the communication rate is 19200bps.
Taipei Head Office:No.42-12, Pidao Village, Danshuei Jen, Taipei 251, TaiwanTel:886-2-2620-4393Fax:886-2-2620-4976
Taichung Branch Office:5Fl., No. 98, Sec. 2, Dungshing Rd.,Nantuen Chiu, Taichung, 408 TaiwanTel:886-4-2471-9298Fax:886-4-2471-9508