harmonic analysis of transformer excitation currents

83
UNLV Retrospective Theses & Dissertations 1-1-1993 Harmonic analysis of transformer excitation currents Harmonic analysis of transformer excitation currents Xiaoqiang Gong University of Nevada, Las Vegas Follow this and additional works at: https://digitalscholarship.unlv.edu/rtds Repository Citation Repository Citation Gong, Xiaoqiang, "Harmonic analysis of transformer excitation currents" (1993). UNLV Retrospective Theses & Dissertations. 290. http://dx.doi.org/10.25669/q005-xcic This Thesis is protected by copyright and/or related rights. It has been brought to you by Digital Scholarship@UNLV with permission from the rights-holder(s). You are free to use this Thesis in any way that is permitted by the copyright and related rights legislation that applies to your use. For other uses you need to obtain permission from the rights-holder(s) directly, unless additional rights are indicated by a Creative Commons license in the record and/ or on the work itself. This Thesis has been accepted for inclusion in UNLV Retrospective Theses & Dissertations by an authorized administrator of Digital Scholarship@UNLV. For more information, please contact [email protected].

Upload: others

Post on 16-Nov-2021

13 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Harmonic analysis of transformer excitation currents

UNLV Retrospective Theses & Dissertations

1-1-1993

Harmonic analysis of transformer excitation currents Harmonic analysis of transformer excitation currents

Xiaoqiang Gong University of Nevada, Las Vegas

Follow this and additional works at: https://digitalscholarship.unlv.edu/rtds

Repository Citation Repository Citation Gong, Xiaoqiang, "Harmonic analysis of transformer excitation currents" (1993). UNLV Retrospective Theses & Dissertations. 290. http://dx.doi.org/10.25669/q005-xcic

This Thesis is protected by copyright and/or related rights. It has been brought to you by Digital Scholarship@UNLV with permission from the rights-holder(s). You are free to use this Thesis in any way that is permitted by the copyright and related rights legislation that applies to your use. For other uses you need to obtain permission from the rights-holder(s) directly, unless additional rights are indicated by a Creative Commons license in the record and/or on the work itself. This Thesis has been accepted for inclusion in UNLV Retrospective Theses & Dissertations by an authorized administrator of Digital Scholarship@UNLV. For more information, please contact [email protected].

Page 2: Harmonic analysis of transformer excitation currents

INFORMATION TO USERS

This manuscript has been reproduced from the microfilm master. UMI films the text directly from the original or copy submitted. Thus, some thesis and dissertation copies are in typewriter face, while others may be from any type of computer printer.

The quality of this reproduction is dependent upon the quality of the copy submitted. Broken or indistinct print, colored or poor quality illustrations and photographs, print bleedthrough, substandard margins, and improper alignment can adversely affect reproduction.

In the unlikely event that the author did not send UMI a complete manuscript and there are missing pages, these will be noted. Also, if unauthorized copyright material had to be removed, a note will indicate the deletion.

Oversize materials (e.g., maps, drawings, charts) are reproduced by sectioning the original, beginning at the upper left-hand corner and continuing from left to right in equal sections with small overlaps. Each original is also photographed in one exposure and is included in reduced form at the back of the book.

Photographs included in the original manuscript have been reproduced xerographically in this copy. Higher quality 6" x 9" black and white photographic prints are available for any photographs or illustrations appearing in this copy for an additional charge. Contact UMI directly to order.

University Microfilms International A Bell & Howell Inform ation C o m p an y

3 0 0 North Z e e b R oad . Ann Arbor. Ml 48106-1346 USA 313 /7 6 1 -4 7 0 0 800 /5 2 1 -0 6 0 0

Page 3: Harmonic analysis of transformer excitation currents
Page 4: Harmonic analysis of transformer excitation currents

Order N um ber 1352617

Harmonic analysis of transformer excitation currents

Gong, Xiaoqiang, M.S.University of Nevada, Las Vegas, 1993

U M I300 N. ZeebRd.Ann Arbor, MI 48106

Page 5: Harmonic analysis of transformer excitation currents
Page 6: Harmonic analysis of transformer excitation currents

HARMONIC ANALYSIS OF TRANSFORMER

EXCITATION CURRENTS

by

Xiaoqiang Gong

A thesis submitted in partial fulfillment

of the requirements for the degree of

Master of Science in

Electrical Engineering

Department of Electrical and Computer Engineering

University of Nevada, Las Vegas

May, 1993

Page 7: Harmonic analysis of transformer excitation currents

©1993 Xiaoqiang Gong

All Rights Reserved

Page 8: Harmonic analysis of transformer excitation currents

The thesis of Xiaoqiang Gong for the degree of Master of Science in Electrical

Engineering is approved.

Chairperson, Yahia Baughzouz, Ph.D.

Examining Committee Member, Sahjendra Singh, Ph.D.

V ^ y

Examining Committee Member, Ashok Iyer, Ph.D.

Graduate Faculty Representative, Ching-Shyang Chen, Ph.D.

Graduate Dean, Ronald W. Smith, Ph.D.

University of Nevada, Las Vegas

May 1993

ii

Page 9: Harmonic analysis of transformer excitation currents

ABSTRACT

Transformer core nonlinearity '1 has been a subject of research in electrical power

engineering for many decades. An accurate and simple transformer model that tabes

into account its iron saturation appears to be lacking. The objective of this thesis is

to propose a voltage-dependent model of transformer core nonlinearity that predicts

the exciting current waveforms at various supply voltages. The model is composed

of the core loss resistance and magnetizing reactance as seen by the fundamental

frequency component and a series of parallel-connected harmonic current phasors.

The single-phase transformer model is extended to represent three-phase transform­

ers under various connections, including Y/Y, Y /A , A /Y , and A /A both with and

without grounded neutral. Laboratory experiments have been conducted to verify

the accuracy of the proposed model.

Page 10: Harmonic analysis of transformer excitation currents

Contents

ABSTRACT ................... iii

LIST OF FIGURES ............. vi

LIST OF TABLES .............. ix

ACKNOWLEDGMENTS .............................................................................. x

1 INTRODUCTION 1

2 1$ TRANSFORMER NO-LOAD MODEL 5

2 . 1 Basic Definitions ................. 5

2.2 . Modeling Transformer Core N onlinearity .............................................. 7

3 3$ TRANSFORMER NO-LOAD MODEL 12

3.1 Y-grounded/Y Connection ......................................................... 15

3.2 Y/Y Connection ......................................................................................... 17

3.3 Y-grounded/A C onnection......................................................................... 19

3.4 Y /A Connection ......................................................................................... 20

iv

Page 11: Harmonic analysis of transformer excitation currents

3.5 A /Y Connection ......................................................................................... 21

3.6 A /A C o n n ec tio n ......................................................................................... 22

4 EXPERIMENTAL RESULTS 24

4.1 Experimental Circuit Set-Up . . . . ' ......................................................... 24

4.2 1$ T ransform er............................................................................................. 27

4.3 3$ T ransform er............................... 37

4.3.1 Y-grounded/Y C onnection............................................................ 37

4.3.2 Y /Y Connection ............................................................................ 39

4.3.3 Y-grounded/A C onnection.................................. 42

4.3.4 Y /A C o n n ec tio n ............................................................................ 48

4.3.5 A /Y C o n n ec tio n ............................................................................ 50

4.3.6 A /A C o n n ec tio n ............................................................................ 53

5 CONCLUSIONS 57

BIBLIOGRAPHY ............................................................................................ 59

APPENDIX 63

V

Page 12: Harmonic analysis of transformer excitation currents

List of Figures

1.1 Equivalent Circuit of Transformer Shunt Branch Showing Nonlinearity 3

2.1 (a) Preliminary and (b) Final Transformer shunt Branch Model . . . 8

2.2 Other Possible Model for Transformer Core N o n lin ea rity ...................... 10

3.1 Harmonic Model of Y-grounded/Y C onnection ...................................... 16

3.2 Harmonic Model of Y /Y C o n n ec tio n ...................................................... 17

3.3 Harmonic Model of Y-grounded/A Connection...................................... 19

3.4 Harmonic Model of Y /A C o n n ec tio n ...................................................... 21

3.5 Harmonic Model of A /Y C o n n ec tio n ...................................................... 22

3.6 Harmonic Model of A /A C onnection ...................................................... 23

4.1 (a) 1 <j> Transformer Test Circuit, (b) 3</> Transformer Test Circuit . . 25

4.2 Experiment Bench S e t - U p .......................................................................... 26

4.3 Distortion Examination Result of Laboratory Supply Voltages . . . . 27

4.4 (a) Excitation Current and Supply Voltage (b) Hysteresis Loop . . . 28

4.5 Variation of (a) Excitation Current and (b) Hysteresis Loop with Sup­

ply Voltage ................................................................................................... 30

vi

Page 13: Harmonic analysis of transformer excitation currents

4.6 Variation of (a) Core Loss Current, (b) Magnetizing C u rre n t .... 31

4.7 Variation of Distortion Current with Supply Voltage................... 32

4.8 Variation of (a) v / ic and (b) \ / i m Curves with Supply Voltage . . . . 33

4.9 Variation of R c and X m with Supply V oltage................................ 34

4.10 Variation of Harmonic Current (a) Magnitudes and (b) Phase Angles

with Supply V o lta g e .................................................................................... 35

4.11 Actual and Predicted Excitation Current Waveshapes (V=130V) . . . 36

4.12 Photos of (a) ia with Respect to van (b) in with Respect to van for

Y-grounded/Y C onnection.......................................................................... 38

4.13 Spectrum of (a) Ia and van (b) in and van for Y-grounded/Y Connection 39

4.14 Photos of (a)?A and van (b)u^jv', van and ujvjv' for Y/Y Connection . 40

4.15 Spectrum of (a) Ia in Y /Y and Ia for Y-grounded/Y (b) van in Y /Y

and van in Y-grounded/Y Connection ................................................... 41

4.16 Photos of (a) iA and is (b) iA and ic for Y-grounded/A Connection . 43

4.17 Photo of (a) Ia and z/y (b) z^ and z'a for Y-grounded/A Connection . 44

4.18 Spectrum of (a) Ia , z’b and ic (b) in and za for Y-grounded/A Connection 46

4.19 (a) Photo of ua6 c with Respect to za (b) Spectrum of vabc for Y-

grounded/A C o n nec tion ............................................................................. 47

4.20 Photos of (a) ia and (b) za with Respect to van for Y /A Connection 49

4.21 Photo of Vabc with Respect to vab on Secondary Side for Y /A Connection 50

4.22 Spectrum of (a) i’a and z’a (b) vabc and z'a for Y /A Connection . . . . 51

4.23 Photos of (a) %ab and (b) ia with Respect to vab for A /Y Connection 52

4.24 Spectrum of Iab and Ia for A /Y C onnection.......................................... 53

Page 14: Harmonic analysis of transformer excitation currents

4.25 Photos of (a) iA and {ab for A /A Connection (b) before and after

the A Closed ................................................................................................ 54

4.26 Spectrum of Ia b , *a and z'a for A /A Connection................................... 55

4.27 (a) Photo and (b) Spectrum of vabc and Circular Current z’a for A /A

Connection ................. .’ ............................................................................... 56

viii

Page 15: Harmonic analysis of transformer excitation currents

List of Tables.

4.1 Model Parameter Values at Different Supply V oltages.......................... 32

4.2 Polynomial Coefficients of Model P aram eters .......................................... 34

4.3 The Harmonic RMS Values of %a and in for Y-grounded/Y Connection 37

ix

Page 16: Harmonic analysis of transformer excitation currents

ACKNOWLEDGMENTS

My greatest appreciation goes to my major advisor, Professor Yahia Baghzouz for

his enlightening guidance, his persuasive talent of turning the most difficult and subtle

problems into laconism and his inconceivable patience and endurance in clarifying

most of my ideas.

My sincerely thanks also go to Dr. Brogan and Dr. Iyer for their graceful rec­

ommendation of my assistantship extension so as to financially support me to finish

all the experiments required by the second part of my thesis. I cordially thank Dr.

Singh for serving in my thesis committee and I am also grateful to Dr. Chin-Shyang

Chen of the Department of Mathematics for his heuristic explanation and instruction

during the course I had with him and his serving in my thesis committee.

Finally, I wish to express my great appreciation to my wife for her considerate

love, patience, encouragement and understanding.

x

Page 17: Harmonic analysis of transformer excitation currents

C hapter 1

INTRO DUCTIO N

In the past, voltage and current waveforms in electric power systems were sinu­

soidal in nature. Electric loads were linear and transformer saturation generated very

little distortion due to overdesign. In the past few decades, however, there has been

an accelerated increase in nonlinear loads due to technology advancement in static

power switching devices. There also has been a change in design philosophy of power

transformers: transformers are being designed to operate deep in their saturation re­

gion [1 ], thereby making their shunt branch highly nonlinear. These electric loads and

transformer nonlinearity are producing significant waveform distortion. The higher

frequency components (odd-integer multiples of the fundamental frequency, i.e., har­

monics) are known to cause serious problems to electric power companies as well as

customers, such as maloperation of control and protection equipment, overloading of

power apparatus and systems, and degradation of computer operation and telephone

communications [2 ].

Transformers are often taught in simple terms with reference to efficiency, voltage

1

Page 18: Harmonic analysis of transformer excitation currents

regulation, and linear equivalent circuit. Under no-load conditions, however, the

linear circuit transformer model in which the shunt branch is modeled as a linear core

resistance and magnetizing reactance, is no longer applicable since the transformer

behaves as a highly nonlinear device.

Transformer nonlinearity is explained in electric machinery books [3, 4] by sepa­

rating the excitation current ie into two components: the magnetization current im

(required to produce the flux in the core) is nonsinusoidal due to the magnetic satura­

tion, and the core loss current ic (required to make up the hysteresis and eddy current

losses) is also nonsinusoidal because of the nonlinear effects of hysteresis. Therefore,

the total current is nonsinusoidal even when the supply voltage is purely sinusoidal.

Nonlinearity is often represented by a nonlinear core loss resistance in parallel with

a nonlinear magnetizing inductance (Figure 1 .1 (a)), or a block showing a hysteresis

loop (Figure 1.1(b)). These circuit diagrams merely show the existence of nonlinearity.

They do not provide any measure of strength of nonlinearity nor its high dependence

on the voltage supply. The development of a simple and accurate voltage-dependent

steady-state model that can be developed and verified in the laboratory will shed

some light on these nonlinearity concepts.

A considerable amount of work has been reported in the literature with regard

to the representation of transformer core nonlinearity. Some investigators concen­

trated on modeling the hysteresis loop using exponential functions [6 , 1 ], polynomial

functions [7], piecewise approximation techniques [8 , 9], and Fourier descriptors [10].

But most require large amounts of information or complex theoretical background.

In Reference [11], Ewart developed a digital computer simulation model which ac-

Page 19: Harmonic analysis of transformer excitation currents

3

(a )

m

Figure 1.1: Equivalent Circuit of Transformer Shunt Branch Showing Nonlinearity

curately represents transformer nonlinearity. This is also relatively complex since

it is a dynamic model involving differential equations and iterative numerical meth­

ods. Dommel et. al [12], developed a relatively simple iterative procedure to obtain

the magnetization current of transformers. While the method is accurate for mod­

ern transformers with grain-oriented steel core, it may not be suitable for laboratory

transformers where the magnetization curve does not have a sharply defined knee and

the core loss current component represents a significant part of the total excitation

current.

W ith regard to 3^ transformers, a complicated FFT algorithm for harmonic anal­

ysis was suggested [17]. Reference [18, 19, 20] also present some other methods to

include harmonic components in the determinations of magnetizing characteristics,

but none of them give us the idea of how the excitation currents and neutral currents

look like and how they are affected by different wire connections. The authors of [21]

Page 20: Harmonic analysis of transformer excitation currents

4

presented a distorted neutral current in Fig. [8 ] of their paper, but no explanation

has been given for it.

The purposes of this thesis are to investigate the harmonic behaviors of exci­

tation currents for single-phase transformers and three-phase transformers in terms

of magnetic saturation, modeling, voltage-dependency, nonlinearity, total harmonic

distortion(THD) and harmonic spectrum.

This thesis is composed in the following five chapters: Chapter 1 gives an intro­

duction to excitation current harmonic analysis of transformers; Chapter 2 presents

a voltage-dependent model for \<j) transformers with no-load, which is based on FFT,

quadratic interpolation and three sets of experimental data measured under three

different supply voltages, namely, Kwn, Vrated, Vmax• In Chapter 3, six harmonic

models of 3<f> transformers are introduced based on the 1 <j> transformer model for six

practical wire-connection situations. All of the experimental analyses and results for

both l(f> transformers and 3<f> transformers are presented in Chapter 4 to verify the

validity of the models. The conclusion coming up in Chapter 5 highlights the ac­

complishment in this thesis and the expectation of harmonic analysis of transformer

excitation currents.

Page 21: Harmonic analysis of transformer excitation currents

C hapter 2

1$ TRANSFORM ER NO-LOAD

MODEL

2.1 B asic D efin itions

The analysis of nonlinear devices such as transformer saturation requires defini­

tions and mathematical relationships beyond those of ordinary fundamental-frequency

network analysis. The definitions that follow are provided for the analysis of nonlinear

circuits.

It is known that the excitation current has half-wave odd symmetry (i.e., ie(t) =

—ie(t + T / 2 )); hence, it is made up of odd harmonics only. If an ideal AC voltage

supply v is described as a sine function of time, i.e.

v = V%V s in u t , (2 . 1)

Page 22: Harmonic analysis of transformer excitation currents

6

where V is the root-mean-square (rms) value of the supply voltage and u> is angular

frequency, then the excitation current (ze) of a l<j> transformer when fed by the voltage

v in 2 . 1 can be expressed by equation (2 .2 ) when fed by the voltage v in equation (2 .1 ):

N Nie - ^ 2 ieh - ' f i hhs in (hu t - 0 h), (2 .2 )

where Ieh is the rms value of the h-th harmonic currents of ie, Oh is the phase angle of

the h-th harmonic components with respect to the fundamental component of ie and

N is the highest harmonic order being concerned. The distortion current component

id is defined asN

id. = ie — ie i = V2 ^ 2 Ieh.sin{hut — Oh), (2.3)h=3,5,—

where iei is the fundamental component of ie. The rms values of ie and id are com­

puted by ______

h =\

NE it = 'Jn - n,- (2.4)/i=l,3 , -

The total Harmonic Distortion (T H D ) is a useful measure of the severity of which a

waveform is distorted. This quantity is defined by

T H D = 100-p-(%). (2.5)Ie 1

The active, reactive and apparent powers P , Q and S are calculated by

P = V IelcosOu Q = VIeisinOi, S = V Ie. (2 .6 )

Page 23: Harmonic analysis of transformer excitation currents

7

Unlike the case when both voltage and current are sinusoidal, the apparent power S

is different from y /P 2 -f- Q'2. This difference which is created by voltage and current

of unlike frequencies is called distortion power

D = V Id = y/S* - (P 2 + Q2). (2.7)

Finally the ratio of active and apparent powers yields the power factor

P F = j = I-f-cos01. (2.8)

Note that only the fundamental in-phase component of the excitation current accounts

for power absorbed by hysteresis and eddy current losses.

2.2 M od eling Transform er Core N on lin earity

Under no-load condition, it is customary to neglect the voltage drop across the

series impedance (i.e., primary winding resistance and leakage reactance) of a trans­

former since it is much smaller in magnitude than the shunt branch [3, 4]. Further­

more, the excitation current represents only a small percentage of the transformer

rated current.

From Equations (2.2) and (2.3), the excitation current can be separated into two

components, ie = ie\ + id- The fundamental component can further decomposed into

the in-phase component ic\ and the quadrature component zmj. These components

should flow through the fundamental-frequency equivalent core loss resistance and

Page 24: Harmonic analysis of transformer excitation currents

8

lml W

R

(b)

Figure 2.1: (a) Preliminary and (b) Final Transformer shunt Branch Model

magnetizing reactance, which can be computed by

V VR c = — , = — , (2.9)

■*cl -*ml

where I ci and Imi represent the rms values of ic and imi , respectively. Figure 2.1(a)

illustrates the excitation current division above.

Figure 2.1(a) shows a possible representation of transformer saturation. However,

like the excitation current, the conventional phasor quantity of id can not be drawn.

The distortion current can best be described in terms of Fourier series components.

Consequently, the current source id is replaced by a number of parallel harmonic

current sources, each of which can be represented in phasor form I eiL6 i, i — 3,5, • • •, n.

The resulting circuit model is shown in Figure 2.1(b).

The circuit in Figure 2.1(b) perfectly models transformer saturation at a specific

voltage supply. However, the model is no longer valid if the voltage deviates from

Page 25: Harmonic analysis of transformer excitation currents

9

the specified value since the fundamental component iei and harmonics generated by

saturation effect critically depend on the peak magnitude of the supply voltage.

One way to develop a voltage-dependent model that is valid in the normal op­

erating range is to determine the values of the model parameters at three different

voltage levels, namely, minimum operating voltage I4un5 rated voltage V Tated and

maximum operating voltage V m a x . The model parameters can then be approximated

by quadratic functions of the supply voltage:

W = a + bV + c V \ W = R c,X m,I e3 , I 3 5 , - - - , 0 3 ,95,••• (2 .1 0 )

The coefficients a, b and c in equation (2.10) are simply found by

a 1 V m in v 2.m m

- 1

W o

b — 1 Vrated. V 2y rated Wi ( 2 .1 1 )

c 1 V n a x V2' m a x w2

where W o , W \ and W 2 axe the measured values of W corresponding to V m in , V Tated and

Vmax, respectively.

The equivalent circuit in Figure 2.1(b) along with Equations (2.10) and (2.11)

form the complete proposed voltage-dependent model for transformer nonlinearity.

What follows describes complications involved when attempting to split the excitation

current in ways other than the harmonic components.

An alternative approach for representing the shunt element of a transformer would

involve a transformation of the schematic in Figure 1.1(b) into two blocks as shown

Page 26: Harmonic analysis of transformer excitation currents

10

Figure 2.2: Other Possible Model for Transformer Core Nonlinearity

in Figure 2.2. In this case, the excitation current is separated into a core loss currents

ic and a magnetizing current im. A mathematical model for the v / i c curve of the

nonlinear resistor and the X/im curve of the nonlinear reactor is required. The core loss

and magnetizing current components may be written in terms of the instantaneous

voltage and flux linkage as follows [15]:

ic = axv + a3 v 3 + a5 v 5 d (2 .1 2 )

im = bx\ + 6 3 A3 + 6 5 A5 + • • • (2.13)

where

A = J vdt = —V 2 —cosut. (2-14)

In order to determine the coefficients, = 1,3, * * -, Equations (2.12) and

(2.13) can be expanded in terms of harmonic components by using mathematical ta ­

Page 27: Harmonic analysis of transformer excitation currents

11

bles for sine and cosine functions, e.g., (siniot ) 3 = (Zsinu>t — sm3wf)/4, (sinivt ) 5 =

lOsinut — bsinZwt + sm5u;f)/16, • • •, (see the APPENDIX for details). If the real

and imaginary parts of the fundamental and harmonic components are available from

measured data, then the coefficients can be found by simple algebra. To illustrate, if

equations (2.12) and (2.13) are terminated at the 9-th power, the following relation­

ships are found:

1 3 1 0 35 126 Vci Ielfl

0 ± 1 ±5 ± 2 1 ±84 | F 3 C3 lezfz

0 0 1 7 36 ^ 5 CS = lehfs

0 0 0 ± 1 ±9 I V 7 c7 lerfr

0 0 0 0 1

1

<a___

i

where {±,c,-,/,} correspond to { —,a,i,cos9i} and smf?,-} for ic and im, respec­

tively. Note that the matrix is an upper triangular and the unknowns are solved with

minimal effort.

Note that the model in Figure 2.2 described by Equations (2.12), (2.13) and (2.14)

requires significant additional computation effort when compared to the previous

model coefficients model. Furthermore, Equation (2.15) indicates that the coeffi­

cients a,- and 6 ,- are complex rational functions of the rms voltage, hence can not

be approximated by simple low-order polynomials. Consequently, this model is not

recommended for transformer nonlinearity.

Page 28: Harmonic analysis of transformer excitation currents

C hapter 3

3$ TRANSFORM ER NO-LOAD

MODEL

In ideal situations, a three-phase transformer bank is considered being symmetri­

cally magnetized by a balanced Z<f) voltage supply and only odd harmonic components

are present as mentioned in Section 2 .1 . Therefore, the rms values of the fundamen­

tal components of the three excitation currents, namely i^, and ic, are equal. So

are the harmonic components (3rd, 5th, 7th, 9th, • • •) of the three excitation cur­

rents. If 7el, / e3, Ies, Ie7 , 7e9, • • •, are denoted as the rms values of the fundamental

and harmonic components respectively, then the iq and ic , under Y-grounded/Y

connection, can be represented, according to equation (2.2), in a Fourier series as

follows:

iA = V 2{Ieisinu>t + Ie3 sin(Zu)t — 03) + I essin(5u>t — 05) +

Ie7 sin(7cot — 07) -f- Iegsin(9ujt — 09) -)- • • •}, (3-1)

12

Page 29: Harmonic analysis of transformer excitation currents

iB = V 2 {Ielsin(ujt - + / e3 sm[3(wf - - 0 3] + I e5 sin[b{ujt - ^ - ) - 6 5 ] +0 0 u

2 tt 27rI e7sin[7(ut - — ) - 07\ + I e9sin[9(u}t - — ) - 09] + • • •}, (3.2)

i c = \ /2 { Iexsin(u)t + ^ ) + I<Qsin[3(ut + ^ ) - 03] + 7e5sm[5(wf + ^ ) - 05] +

2 tt 27t/ e7 .sin[7 (wt -)——) — 6 7\ + / egszn[9(wi H——) — 6 g[ + •••}. (3-3)

0 0

The current in that flows in the neutral line is equal to the sum of iB and ic in

accordance with Kirchhoff’s current law. The sum of equations (3.1), (3.2) and (3.3)

Page 30: Harmonic analysis of transformer excitation currents

14

= sin(3u>t + #3 ) + sin(3ut — 2r — 8 3 ) + sin{3wt + 27r — O 3 )

= sin{Zu)t — 6 3 ) + sin{3u)t — 8 3 ) + sin(3ujt — 8 3 )

= 3sin(3u!t — 8 3 ) , ( 3 . 6 )

2 7T 27Tsin(5u>t — 85) + 5zn(5 (o;t — —) — 85) + sin(5 (u)t + — ) — 85)

O o2 ^ 27r

sin(bujt — 8 5) + sin(5u>t — 4 7 r + —-----05) + sin(5u)t + 4 7 T---- ----- 8 5 )O i)

27T 27Tsin(5u>t — 85) + s in((5u)t — 85) + — ) + sin((5u)t — 85)---- —)

o 0

0, (3.7)

2tt 27rs i n ( 7u t — 87 ) + s i n ( 7 (u>t — —) — 87) + s i n { 7(u>t + — ) — 87)

O u27r 2tt

s i n { 7uit — 6 7 ) + s i n ( 7ujt — Air — ----- 8 7 ) + s i n { 7u t + 47T + —----- 8 7 )o 02?r 27r

s i n { 7u)t — 87 ) + s i n { ( 7u)t — 87) — —) + s i n ( ( 7ujt — 8 7 ) + — )u O

0, (3.8)

sin(9ut — 8 9 ) + sin(9(u)t — —) — 8 9 ) + sin(9(wf + — ) — 8 9 )O o

= sin(9uit + 09) + sin(9ut — 6 ir — 8 9 ) + sin(9u>t + 6 7 7 — 8 9 )

= sin(9ujt — 8 9 ) + sin(9ujt — 8 9 ) + sin(9u>t — 8 9 )

= 3sin(9u>t — 8 9 ), (3.9)

Page 31: Harmonic analysis of transformer excitation currents

15

then

ipj = V2{3Ie3 sin(3u)t — 03 ) + 3Iegsin(9u}t — 0g) H }

= 3 \ / 2 {Ie3 sin( 3 ujt — 93) + I egsin(9u>t — 6 9 ) + ■ • •}. (3.10)

It is noted that (under balanced condition), i/y contains only triple harmonic compo-

nents(3rd, 9th, • • •). Furthermore, the rms values of the triple harmonic components

of iff are three times of the ones of the line currents.

It is also noted tha t the harmonic behavior in a 3<f> transformer depends not only

on the core characteristic and supply voltage, but also on the way the transformer is

connected. The following discussion covers all practical wire connection situations,

namely, Y-grounded/Y, Y/Y, Y-grounded/A, A /Y and A /A .

3.1 Y -g ro u n d ed /Y C onnection

In this case, each transformer is supplied by a single-phase voltage from a 3</>

voltage supply source. Therefore, each of them behaves exactly like a l(/> transformer,

which means that the waveshape of each excitation current will be the same as of

a 1 ^ transformer. Since there is no secondary-side currents and all the harmonic

components of the excitation currents find their paths returning to the source through

the neutral line, thus, the harmonic model can be easily constructed as shown in

Figure 3.1.

From this model, it is easy to see that all the fundamental and harmonic compo­

nents (zei, ie3 , ie5 , • • •) of the three excitation currents sum up at node N according to

Page 32: Harmonic analysis of transformer excitation currents

16

Supply Voltages IdealTranslormeis

N1:N2120v

120v —O ■o—.

120v ■o—

o - 1

Figure 3.1: Harmonic Model of Y-grounded/Y Connection

Kirchhoff’s current law. As mentioned before, the fundamental and non-triple har­

monic components { i ei , i e5, i e7 , • • ■) add up to zero because of their 1 2 0 degree phase

displacement and triple harmonic components (ze3, i e9, • • •) sum up to three times the

value found in each phase current. Therefore, the current z/v in the neutral line is

*N — i-A + "b ic = 3ie3 + 3ze9 + 3zei5 + • • • (3-11)

Since the 3rd harmonic is significantly larger than 9th and higher triple harmonics,

the neutral current ipj is expected to be a near sinusoidal signal with a frequency

three times that of the supply voltage.

Page 33: Harmonic analysis of transformer excitation currents

17

Supply Voltages ldealTransformers

N1:N2

120v i i

‘H' O—lV«]

120v O -

— O O—1

Figure 3.2: Harmonic Model of Y/Y Connection

3.2 Y /Y C onnection

When the primary neutral is isolated, the path for the 3rd and other triple har­

monic components is cut off. To reflect this effect, the harmonic model is modified

as shown in Figure 3.2.

Without the return paths, the 3rd and other triple harmonic currents are forced to

zero. This fact is represented by opened switches serially connected with the 3rd and

other triple harmonic current sources in the model. This also means that all of the

three excitation currents iB and ic are composed of fundamental and non-triple

harmonic components, i.e.,

i e — f el + *e5 + *e7 + *ell + (3.12)

Page 34: Harmonic analysis of transformer excitation currents

18

Therefore, one could expect a completely different shape of ie. Since ie5, ie7 , iell

• • • are much smaller than i e 3 in magnitude, then the fundamental current ie 1 has

less distortion in waveshape after adding up with ie5 , ie7 ? Mi> • • •> i-e-> the excitation

current ie appears close to the fundamental current iel.

With a near sinusoidal excitation current, the phase voltage across the primary

winding for each transformer is no longer sinusoidal because of the nonlinear magne­

tization curve relating the flux linkage to the magnetizing current. A third harmonic

component is generated inside each phase voltage in each phase for this reason [24].

This third harmonic component is symbolized by a third-harmonic-frequency volt­

age source ves inserted in each phase of the model. Since the supply voltage van 1 is

sinusoidal and

van< = van + vpfpji, (3.13)

where uaw' is the voltage across nodes N and N’. This potential difference between

the neutrals of the source and that of the transformer is then determined by

vnn ' — van• — v a n • (3-14)

Equation (3.14) implies that vyvyv' is expected to be a voltage of third harmonic

frequency, which cancels the third harmonic component ue 3 of the phase voltages.

Page 35: Harmonic analysis of transformer excitation currents

19

Supply Voltages Ideal

TransfoimersN1:N2

J20v

•o—i

120v

120v

Figure 3.3: Harmonic Model of Y-grounded/A Connection

3.3 Y -g ro u n d ed /A C onnection

In this situation, like in Y-grounded/Y case, all the harmonic components of the

excitation currents find their returning paths through the neutral line. Therefore,

the excitation currents and the neutral current are expected to have the same wave­

shapes as the ones in the Y-grounded/Y case. Moreover, the secondary voltages are

anticipated to be equal in amplitude and have 120-degree phase relationship among

them under the ideal situation (identical transformers and balanced 3<j> voltage sup­

ply). Hence, it is not possible for a circulating current to exist inside the A loop, i.e.

*'a = 0, because the secondary voltages sum up to zero. The harmonic model for this

connection is shown in Figure 3.3.

Page 36: Harmonic analysis of transformer excitation currents

2 0

What is worthy to be mentioned here is that if the secondary voltages are out of

balance, will exist inside the A loop. This circulating current, in return, will affect

the excitation currents on the primary sides.

3.4 Y /A C onnection ,

This case is much similar to Y /Y connection situation, where there is no path for

the third and triple harmonic current components. As mentioned in the Y /Y case,

the phase voltages across each primary winding contain third harmonic voltages,

which induce third harmonic voltages on the secondary sides. Since the 3rd harmonic

voltages on the secondary side are in phase[24], they add up to produce a third-

harmonic current flowing in the A loop.

By mutual coupling, this secondary current induces third harmonic voltage source

in each primary side, which is opposite to the original third-harmonic voltage source.

As a result of cancellation of the two third harmonic voltages, the terminal voltages

recover to sinusoidal shapes.

Based on the facts mentioned above, the harmonic model for this case has been

derived from the model of Y /Y connection. Figure 3.4 shows the modified model.

On the secondary side, the circular current is represented by a current source i&. Its

induced third-harmonic voltage sources on the primary sides are symbolized by three

opposite-connected voltage sources. For the third and triple harmonic components of

the excitation currents, they are still sketched by the current sources connected with

opened switches.

Page 37: Harmonic analysis of transformer excitation currents

21

Supply Voltages Ideal

Transformers

N1:N2120v

120v —O-

120v —O

t—o

Figure 3.4: Harmonic Model of Y/A Connection

3.5 A /Y C onnection

In this situation, the excitation currents behave exactly as same as in Y-grounded/Y

connection, because all the harmonic components also have returning paths to the

supply. The transformer bank is fed by line voltages that are adjusted to 120V.

Therefore, the same harmonic model redrawn in Figure 3.5 applies here as well.

The only difference between this model and the previous one is that the line

currents and phase differ from one another. According to Kirchhoff’s current law,

each of the line currents is equal to the difference of two corresponding excitation

currents. Since the third and triple harmonic components of the excitation currents

are in phase and in same amplitude, it can be expected that the line currents will

Page 38: Harmonic analysis of transformer excitation currents

2 2

Supply Voltages jdealTransfoimeis

N1:N2

120v

■o—i- 0-

120v

O—-0

■O—

Figure 3.5: Harmonic Model of A/Y Connection

not contain the third and triple components, but the fundamental, fifth and other

harmonic components still exist.

3.6 A /A C onnection

With balanced line voltages in this case, it can be expected that there will be three

balanced secondary voltages of same amplitude and 120 degree phase displacement on

the secondary side. Obviously, such secondary voltages will sum up to zero when the A

loop is closed. In other terms, there will not be any circulating current flowing within

the secondary loop. The excitation currents and the line currents on the primary side

will be exactly identical to the ones in the A /Y connection situation discussed above.

Page 39: Harmonic analysis of transformer excitation currents

23

Supply Voltages IdealTransformers

N1:N2

120v

120v

Figure 3.6: Harmonic Model of A/A Connection

Consequently, the harmonic model is the same as shown in Figure 3.6.

If the phase voltages on the secondary sides deviate from balanced condition, the

circular current will exist in the A loop. As mentioned in Y-grounded/A case, all of

the excitation currents will be impacted in appearance.

Page 40: Harmonic analysis of transformer excitation currents

C hapter 4

EXPERIM ENTAL RESULTS

4.1 E xp erim en ta l C ircuit S et-U p

To verify the proposed harmonic models for the 1 (f> and 3<f> transformers, a number

of laboratory experiments have been conducted. The laboratory experiments consist

of the following: (a) examining the excitation current waveshapes and corresponding

hysteresis loops for various voltages on a scope, (b) recording line current, neutral

current and loop current in 3<j> connections. The Fourier series components of the

excitation current are derived to determine the model parameters in Eqn. (2.10).

The model is then verified for some voltage within the normal operating range.

Figure 4.1(a) shows the 1 <f> transformer test circuit: a variable AC supply is con­

nected across the primary side of the transformer under test. A 120V/60V, 0.5A/1A,

shell-type transformer is used in the experiment. Signals proportional to the supply

voltage, excitation current and flux linkage are obtained by using a potential trans­

former, current probe (or current transformer) and an RC integrator. These signals

24

Page 41: Harmonic analysis of transformer excitation currents

25

C T TransformerUnder Test

P T 1MQ

4jjF

P C

S C O P E

Supply VoltagesTransformer Under Test

N1:N2

O—1HARMONICSANALYZER

SCOPE

F ig u re 4 .1 : (a ) 1(f) T ra n sfo rm er T e st C ircu it , (b ) 3 (f> T ran sform er T est C ircu it

Page 42: Harmonic analysis of transformer excitation currents

26

Figure 4.2: Experiment Bench Set-Up

are fed into an oscilloscope for display. The microcomputer houses a Fortran package

to determine the harmonic content of the excitation current.

Figure 4.1(b) shows the 3(j> transformer test circuit: a 120V/60V, 0.5A/1A, 3<f>

transformer bank is fed by a three-phase, four-wire AC voltage supply. The signals

are picked up by a number of current probe for waveform display. The harmonic

spectrum for all the currents and voltages are measured by using a harmonic analyzer.

The photo in Figure 4.2 shows the bench set-up for both test circuits.

Before the experiment had been started, the supply voltages have been examined

for distortion. The result is shown in Figure 4.3. It is found that the supply voltages

in the power laboratory have very little distortion (T H D < 2%).

Page 43: Harmonic analysis of transformer excitation currents

27

1000Va -0— Vb -4-— Vc -&-»

THE)

100Va 1.4864%

Vb 1.2216%

Vc 1.3931 %

10

0.1

0.013 5 7 9 11

Harmonic Order131 15 17 19

Figure 4.3: Distortion Examination Result of Laboratory Supply Voltages

4.2 1<1> Transform er

Figure 4.4 displays photos of excitation current and corresponding hysteresis loop

at rated supply voltage. Note that the rms value of excitation current is about 6%

of full load current. It is important to point out that the relative magnitude of I e

is smaller and the hysteresis loop is much narrower (i.e., less core loss) in practical

transformers intended for industrial use.

Additional knowledge on transformer nonlinearity is achieved by examining the

variation of hysteresis loop and excitation current for voltages below and above nom­

inal value. Due to lack of storage capability of the scope being used, the waveforms

are stored in the microprocessor for simultaneous printing. Figure 4.5 shows the mea-

Page 44: Harmonic analysis of transformer excitation currents

28

(a)

(b)

F ig u re 4 .4 : (a ) E x c ita t io n C u rren t and S u p p ly V o lta g e (b ) H y s te r e s is L oop

Page 45: Harmonic analysis of transformer excitation currents

29

sured current waveforms and hysteresis loops for supply voltages of 100V, 120V, and

140V. Note the significant changes in the peak value of ie and tail of the loop.

The personal computer also provides a means of separating the core loss, magne­

tizing, and distortion current components from the total excitation current. These

current components are isolated and displayed individually as shown in Figure 4.6.

The separation of im and ic can be obtained by external circuitry (i.e., potentiometers

and information windings) [13]. However, the separation of i j (see in Figure 4.7) may

never be achieved without microcomputer applications.

Figure 4.8 shows the corresponding v / i c and X/im curves on the first quadrant

(curves on the third quadrant are simply determined by odd-symmetry). Note that

both curves do not simply extend as the supply voltage increases, but rather change

shape.

The fundamental-frequency R c and Lm as well as the magnitudes and phase an­

gles of the harmonic current components are calculated for each of the three supply

voltages, and the results are shown in Table 4.1. It is found that harmonics higher

than the 9-th order are negligible. The second-order polynomial coefficient according

to (11) are listed in Table 4.2.

The resulting polynomial functions representing all model parameters are plotted

in Figure 4.9 for voltages ranging form 100V to 140V. Note that R c increases slightly,

while X m decreases with an increase in voltage. These results agree with those found

in [11], With regard to harmonic currents, Figure 4.10 indicates that the magnitude of

the lower harmonics (3rd and 5th) varies significantly while their phase angles change

slowly with voltage. On the other hand, it is the phase angles of the higher harmonics

Page 46: Harmonic analysis of transformer excitation currents

Flux

(Wb-t)

Excit

ation

Cu

rren

ts (m

A)

30

120.00V - 1 0 0 VV - 1 2 0 VV - 1 4 0 V100.00

80.00

60.00

40.00

20.00

0.00

0.00 1.00 2.00 3.00 4.00 5.00 6.00A n g le (rad)

0.40

V - 1 0 0 VV - 1 2 0 VV - 1 4 0 V0.30

0.20

0.10

0.00

0?)

0.00 50.00 100.00Excitation Current (mA)

F igu re 4 .5 : V aria tion o f (a ) E x c ita t io n C u rren t a n d (b ) H y stere s is L oop w ith S u p p ly V o ltage

Page 47: Harmonic analysis of transformer excitation currents

Mag

netiz

ing

Curren

t (m

A)

Copp

er L

oss

Curren

t (m

A)

4 0 . 0 0

V-100V V—120V V-140V

30.00

20.00

10.00

0.00

0.00 1.00 2.00 3.00 4.00 5.00 6.00Angle (rad)

120.00

V-100V V—120 V V—140 V100.00

80.00

60.00

40.00

20.00

0.00

-40.00

-60.00

-80.00

- 100.00

0.00 1.00 2.00 3.00 4.00 5.00 6.00Angle(rad)

F ig u re 4 .6 : V a r ia tio n o f (a ) C ore L oss C u rren t, (b ) M a g n e tiz in g C u rren t

Page 48: Harmonic analysis of transformer excitation currents

Mag

netiz

ing

Cune

nt (m

A)

32

40.00V-100V V-120V V—140 V

30.00

20.00

10.00

0.00

- 10.00

- 20.00

-30.00

-40.006.000.00 1.00 2.00 4.00 5.003.00

Anglc(rad)

Figure 4.7: Variation of Distortion Current with Supply Voltage

w V=100V

>o<Mt*H11> >o-3*iHII>

Rc(ku>) 4.51 4.66 4.76X m(ku,) 4.61 3.96 2.75Ie3 (mA) 5.46 9.96 19.1293 (deg) -84.55 -80.73 -79.82

Ies(mA) 1.70 3.02 6.516 s(deg) -119.76 -100.73 -90.74

Ie7 (mA) 0.66 1.10 1.5097 {deg) -152.93 -99.42 -106.13

Ie9 (mA) 0.24 0.58 0.1899 (deg) -184.00 -123.29 -189.40

Table 4.1: Model Parameter Values at Different Supply Voltages

Page 49: Harmonic analysis of transformer excitation currents

Flux

Link

age

(Wb-t)

Volta

ge (V

)

33

200.00

V-100VV-120VV-140V

180.00

160.00

140.00

120.00

100.00

80.00

60.00

40.00

20.00

(a)0.00

0.00 5.00 10.00 15.00 20.00 25.00 30.00 35.00Copper Loss Current (mA)

0.40

0.35

0.30

0.25

0.20

0.15

0.10

V-100V V-120V V—140 V0.05

(b)

0.00

0.00 20.00 40.00 60.00 80.00 « 100.00Magnetizing Current (mA)

F ig u re 4 .8 : V a r ia tio n o f (a ) v / i c and (b ) \ / i m C u rv es w ith S u p p ly V o lta g e

Page 50: Harmonic analysis of transformer excitation currents

Copp

er Lo

ss Re

sistan

ce and

Mag

netiz

ing I

nduc

tance

(Ohm

)

34

w a b c

Rc 3.19 0.018 -0.001X m -0.36 0.118 -0.0007l a 52.84 -1.056 0.005803 -157.26 0.990 -0.0036

l a 27.83 -0.534 0.002705 -374.93 3.856 -0.0130

Ie 7 -2.16 0.033 -0.000107 -1323.51 19.23 -0.0752

Ie 9 -12.52 0.220 -0.000909 -2388.39 37.885 -0.1584

Table 4.2: Polynomial Coefficients of Model Parameters

4800.00

4600.00

Rc — Xm —4400.00

4200.00

4000.00

3800.00

3600.00

3400.00

3200.00

3000.00

2800.00

100.00 110.00 120.00 130.00 140.00Supply Voltage (V)

Figure 4.9: Variation of Rc and X m with Supply Voltage

Page 51: Harmonic analysis of transformer excitation currents

35

<s

20.00

18.00 Ic3Ic5Ie7Ie916.00

14.00

12.00

10.00

8.00

6.00

4.00

2.00

0.00

100.00 110.00 120.00 130.00 140.00Supply Voltage (V)

1?3*i3cg<3

<3

-80.00

-90.00

- 100.00

- 110.00

- 120.00

-130.00

-140.00

-150.00

-160.00 Ie3Ie5Ie7Ie9-170.00

-180.00

(b)-190.00

100.00 110.00 120.00 130.00 140.00Supply Voltage (V)

F ig u re 4 .1 0 : V aria tion o f H arm on ic C u rren t (a ) M a g n itu d e s an d (b ) P h a se A n g le s w ithS u p p ly V o lta g e

i

Page 52: Harmonic analysis of transformer excitation currents

36

Measured Ie Predicted Ie80.00

70.00

60.00

50.00

40.00

30.00

20.00

10.00

0.00

- 10.00

- 20.00

-30.00

-40.00

-50.00

-60.00

-70.00 -

-80.00

0.00 1.00 2.00 3.00 4.00 5.00 6.00Angle (rad)

Figure 4.11: Actual and Predicted Excitation Current Waveshapes (V=130V)

(7th and 9th) that are more sensitive to voltage rather than their magnitudes.

To verify the validity of the proposed model, it was decided to compare the

predicted excitation current waveshape with the measured one when the supply

voltage is set at 130V. The parameter values of model at this voltage are as fol­

lows: R c = 4.72 kCl,Xm = 3.42Hl,/e3 = 13.95Z-80°mA, Ie5 = 4.50Z-94°m,4, I e7 =

1.31Z—95°mA, and I e 9 = 0.47Z—140°mA The results are shown in Figure 4.11. The

model predicted the current waveshape with very good accuracy. The model was also

checked at other voltage values. It was found to perform very well in 100-140V range,

but resulted in noticeable current deviation at voltages below 90V and above 145V.

Page 53: Harmonic analysis of transformer excitation currents

37

Harmonic Order z 'A r(m A ) u ( m A )

1 3.6008 42.8603 27.113 9.25195 0.3570 2.50557 0.0909 0.77199 0.9957 0.319411 0.0257 0.194813 0.0116 0.091613 0.1070 0.033717 0.0122 0.065019 0.0078 0.0094

Table 4.3: The Harmonic RMS Values of and for Y-grounded/Y Connection

4.3 3 $ Transform er

4.3.1 Y-grounded/Y Connection

The excitation current in this Y-grounded/Y situation is similar to that of 1 </>

transformer case as shown in Figure 4.4. Figure 4.12 presents the waveforms of

excitation current ia and neutral current z'/v with respect to phase voltage v a n - Fig­

ure 4.13 sketches the harmonic analysis results of %a and ipj. Comparing both photos

in Figure 4.12(a) and Figure 4.4(a) will conclude that the excitation current is not

changed in a 3<j> transformer Y-grounded/Y situation.

Table 4.3 gives the measured rms values of all the harmonic components(up to

19th) for ia and i n - It is easy to see from Table 4.3 that each triple harmonic

component (3rd, 9th, 15th, • • •) of i ^ is approximately three times of the corresponding

harmonic component in Ia - This fact confirms that all the 3rd and triple harmonic

components of the three excitation currents are in phase and they sum up in the

neutral line. Another fact, which is also easy to see, is that the fundamental and

non-triple harmonic components of z’/v are nearly zero.

Page 54: Harmonic analysis of transformer excitation currents

38

Figure 4.12: P hotos o f (a ) i . \ with Respect to v _.\n (h) i n with Respect to u , \ n for Y g ro u n d e d /Y Connection

Page 55: Harmonic analysis of transformer excitation currents

39

2T3§

1l

100

In —1-----

10

0.1

0.01

0.0013 7 9

Harmonic Order11Order

191 5 13 15 17

Figure 4.13: Spectrum of (a) i , 4 and van (b) i-N and van for Y-grounded/Y Connection •

4.3.2 Y /Y C onnection

To find out how the isolated neutral line affect the excitation current and phase

voltage, the photographs and spectrum of %a and van have been taken and presented

in Figures 4.14 and 4.15.

From Figure 4.14(a), it is easy to see that both shapes of Ia and van have changed

significantly when compared with Figure 4.12(a). For z’x, a nearly sinusoidal wave­

form replaces the previous sharp-peaked shape. On the contrary, a sharp-peaked

waveform substitutes the approximately sinusoidal pattern for v an • The reason for

these changes can be found from the spectrum of Figure 4.15(a), which shows both

Ia in Y/Y and Y-grounded/Y connections.

Page 56: Harmonic analysis of transformer excitation currents

40

(b)

F ig u re 4 .1 4 : P h o to s o f ( a ) i ,4 an d v a n (b)i>>uv', v A n an d v n n < for Y / Y C o n n ec tio n

Page 57: Harmonic analysis of transformer excitation currents

Phase

Volta

ges

(V)

Excit

ation

Cu

nent

s (m

A)

41

1 0 0

la (Y/Y) la (Y-groundcd/Y)

10

0.1

0.01

(a)0.001 1 3 75 9 11 13 15 17 19

Harmonic Order

1000

Va (Y/Y) Va (Y-grounded/Y)

100

lO

0.1

(b)

0.0131 5 7 9 11 13 15 17 19

Harmonic Order

Figure 4.15: Spectru m o f (a) in Y / Y and for Y -g ro u n d ed /Y (b) v a n in Y / Y and v a n

in Y -g ro u n d ed /Y Connection

Page 58: Harmonic analysis of transformer excitation currents

42

Figure 4.15(a) clearly shows that the 3rd and triple harmonic components in the

excitation current decrease dramatically in magnitude. As a result of it, the fun­

damental component of the excitation current is only affected slightly by the 5th

and other non-triple harmonic components with much smaller rms values and the

excitation current appears in the near sinusoidal shape.

With regard to the voltage waveform, Figure 4.14(b) shows the source voltage van1,

phase voltage van and voltage between neutrals vnn>- These voltages are related by

Kirchhoff’s voltage law

v a n 1 = v a n + v n n >-

Figure 4.15(b) displays a quite large amount (almost 1/3 of fundamental component)

of 3rd harmonic component in the phase voltage van• It is this 3rd harmonic which

deviates van from a sinusoidal shape to a high-peaked pattern.

4.3.3 Y-grounded/A Connection

According to the theoretical prediction stated before, all the currents of iyi, is ,

ic and z'at are supposed to be the same as in Y-grounded/Y connection case. Also

there is no current on the secondary side. Surprisingly, however, severely distorted

waveforms of m, is , ic and ijv as well as z’a showed on the screen of the oscilloscope.

Figures 4.16 and 4.17 present all pictures of them.

In these pictures, Ia is used as a reference current for other currents. It is not diffi­

cult to see that the three excitation currents appear in different waveshapes, although

the corresponding phase voltages are still nearly sinusoidal in shape. Moreover, the

Page 59: Harmonic analysis of transformer excitation currents

43

(a)

im&i&i&Z

flUERAGC

F ig u re 4 .16: P h o to s o f (a ) z.4 and i s (b ) z.4 and i c for Y -g r o u n d e d /A C o n n ec tio n

Page 60: Harmonic analysis of transformer excitation currents

44

■'FWX.

n m

yum mm gpglg/f

(b)

F ig u re 4 .1 7 : P h o to o f (a ) and iyv (b ) i& an d for Y -g r o u n d e d /A C o n n ectio n

Page 61: Harmonic analysis of transformer excitation currents

45

neutral current i/v is no longer dominated by only the 3rd harmonic component,

but the combination of the fundamental, 3rd, 5th, 9th, and 15th. The spectrum in

Figure 4.18 clearly expresses this out.

To find out why these currents changed so significantly, the summation of the

phase voltages (va -f -f vc) on the secondary side has been examined by inspecting

this open-circuit voltage. Photograph and spectrum of it are shown in Figure 4.19

along with the photo of i&.

A surprising result comes out: instead of zero voltage summation, a severely

distorted voltage waveform has been captured. The harmonic analysis outcome of

the distorted voltage contains significant harmonic components on the 3rd, 5th, 7th,

9th, and 15th. It is easy to understand that when the A loop is closed, there must

be a circular current existing inside it and the i& must contain plenty of harmonic

components, since its driving voltage is composed of various harmonic components.

The cause of this voltage can be accounted for the imbalance of the supply voltages

and the inequality of the magnetic characteristics of the three transformers in the

bank.

Through the magnetic coupling effect, the circular current ia will definitely affect

the excitation currents i^ , ie and ic on the primary side. The influence of on

each of the excitation currents depends on their own saturation curves and respected

phase angle to each of them. For the 3rd and triple harmonic components of i&, they

have the same influence on all of i a , ib and ic , because they are in phase with the

3rd and triple harmonic components on the primary side. For the fundamental and

non-triple harmonic components of 2a, the influence is quiet different, since they are

Page 62: Harmonic analysis of transformer excitation currents

Neutr

al Cu

rrent

and S

econd

ary

Curre

nt (m

A)

Excit

ation

Curr

ents

(m A)

46

100

lb -4-- Ic -Q

10

(a)

0.1 1 3 75 11 13 15 17 19Harmonic Order

100

Id -H-

10

1

(b)

0.1 1 3 75 11 13 15 17Harmonic Order

F ig u r e 4 .1 8 : S p ec tru m o f (a ) i , i , i s a n d i c (b ) i/v and i & for Y -g r o u n d e d /A C o n n ectio n

Page 63: Harmonic analysis of transformer excitation currents

Summ

ation

ofV

a+Vh

+Vc

(mV)

1000Vabc

100

107I 5 9 13 15 171 1

Harmonic Order

Figure 4.19: (a) P h o to o f r,,f,c with Respect to i ± (b) Spectrum o f v a bc f°r Y -g r o u n d e d /A Connection

Page 64: Harmonic analysis of transformer excitation currents

48

not in the same phase difference to all of the fundamental and non-triple harmonic

components on the primary side at the same time. The different influences produce

different rms values for the fundamental and non-triple harmonic components among

the three excitation currents.

The neutral current in flowing .through the neutral line is the sum of the excitation

currents in phase A, B and C. Since the third and triple harmonic components of them

axe in phase, their algebraic sum consist of the third and triple harmonic components

of For the rest of harmonic components, their vector sum become the fundamental

and non-triple harmonic components of ipj. Because the different rms values and non-

120-degree phase displacement among them, their sums are no long equal to zero.

4.3.4 Y /A Connection

The experimental results in this case are very close to what are expected according

to the harmonic model mentioned for Y /A case. Figure 4.20 and 4.21 present the

waveforms of the excitation current and f a with respect to v a n , and the summation

voltage vabc on the secondary side with respect to vabc• Notice that van is sinusoidal

now instead of highly-peaked pattern as in Y /Y case, because of the cancellation

effect of the 3rd harmonic voltage induced by Ia- The shape of is determined by

Vabc, which contains only the 3rd harmonic component and a very small fundamental

component coming from the imbalance of the supply voltages and the magnetization

difference among the three transformers.

The shortage of the 3rd and triple harmonic components in the excitation currents

because of the isolated neutral line, makes the 5th harmonic take a major role in

Page 65: Harmonic analysis of transformer excitation currents

49

(b )

F igu re 4 .20 : P h o to s o f (a ) i A and (b ) i A w ith R esp ec t to v A N for Y / A C o n n e c tio n

Page 66: Harmonic analysis of transformer excitation currents

50

Figure 4.21: Photo of vaic with Respect to vab on Secondary Side for Y/A Connection

determining the shape of the excitation currents. Figure 4.22 shows the harmonic

contents of iA, and vabc.

4.3.5 A /Y C onnection

Figure 4.23 shows the waveforms of (a) the excitation current iAs and (b) the line

current i A with respect to phase voltage vAb -

It is not difficult to find out that the iAB matches the excitation current iA in

Y-grounded/Y situation exactly in shape except for their 30 degree phase difference.

The result for the phase difference is that iAB is generated by the line voltage vAig,

which is leading iA s driving voltage vA by 30 degree.

The spectrum of iA in Figure 4.24 shows that there are almost no 3rd harmonic

and triple harmonic components in the line currents. Because the three 3rd and triple

harmonics of the excitation currents are identical in amplitude and in phase, and a

Page 67: Harmonic analysis of transformer excitation currents

Seco

ndar

y Vo

ltage

(m

V) a

nd Se

cond

ary

Curren

t (m

A)

Excit

ation

Cu

rren

t and

Secon

dary

Cu

rren

t (m

A)

51

10 0

Id -+«

10

0.1

0.01

000.001 1 3 5 7 11 13 15 17

Harmonic Order

100

Vabc

10

0.1

0.01

0.001 1 3 5 7 11 13 1715Harmonic Order

F ig u re 4 .2 2 : S p ec tru m o f (a ) and z'a (b ) v abc a n d z‘a for Y / A C on n ectio n

Page 68: Harmonic analysis of transformer excitation currents

52

(b)

F ig u re 4 .23 : P h o to s o f (a ) i A B an d (b ) i A w ith R esp ec t to v A B for A / Y C o n n ec tio n

Page 69: Harmonic analysis of transformer excitation currents

5 3

I

100

lab - 0 — la

10

0.1

0.01

0.001 1 3 7 11Order

5 9Harmonic Order

13 17 1915

Figure 4.24: Spectrum of %ab and for A/Y Connection

line current is equal to the difference of two excitation currents, then the 3rd and triple

harmonic components in the phase currents cancel each other in a line current. This

leaves the line currents containing only non-triple harmonic components, in which the

5th component becomes predominant. The spectrum of also verifies this fact.

4.3.6 A /A Connection

In this case, the photos of the excitation current %a b and the line current %a

have been taken as shown in Figure 4.25(a). A close comparison with the excitation

current and line current in Figure 4.23 indicates that there are slight waveshape

changes between them. Figure 4.25(b) clearly depicts the difference by putting the

two excitation currents into one photo.

Page 70: Harmonic analysis of transformer excitation currents

54

l A B —c lo s e d

(b)

Figure 4.25: Photos of (a) and i^B for A /A Connection (b) i^B before and after the A Closed

Page 71: Harmonic analysis of transformer excitation currents

55

f§<55

a*3£

100

lab

10

0.1

0.01

0.0013 7 11 15 191 5 9

Harmonic Order13 17

Order

Figure 4.26: Spectrum of M and ?a for A/A Connection

To find out the cause of the small difference, the summation of secondary voltage

Vabc and secondary current have been examined. As shown in Figure 4.27, a third

harmonic voltage and a third harmonic current have been measured. It is this har­

monic voltage that causes the harmonic circular current z' a - By magnetic coupling

with the primary winding, this small z'a affects the 3rd harmonic and fundamental

components of the excitation currents.

The appearance of voltage vabc can be accounted for the result of the imbalanced

supply voltages and the unequal magnetizing characteristics of the three transformers.

Page 72: Harmonic analysis of transformer excitation currents

Seco

ndar

y Vo

ltage

(m

V) a

nd Se

cond

ary

Curren

t (m

A)

5 6

100V abc

Id -+—

10

0.1

0.01

(b)

0.0019 13 17 197 11 151 3 5

Harmonic Order

Figure 4.27: (a) Photo and (b) Spectrum of vabc and Circular Current for A /A Connec­tion

Page 73: Harmonic analysis of transformer excitation currents

C hapter 5

CONCLUSIONS

This thesis presents harmonic models for 1 <f> and 3(f> transformers at no load. The

proposed 1 (f> model is composed of a shunt connection of the core loss resistance and

magnetizing reactance (as seen by the fundamental-frequency current), and harmonic

current sources (representing the core nonlinearity). The model parameters are ob­

tained from the Fourier series components of excitation current with the aid of a

microcomputer that is integrated with the experimental setup. Voltage-dependence

is incorporated in the model by expressing its parameters as second-order polynomials

of voltage supply. The models for 3(f) transformers are based on the l<f> model, with

modification made according to the type of connections in primary and secondary

sides.

The models are verified through laboratory experiments. These models present

very clear qualitative explanation of harmonic problem of excitation currents, neutral

currents, line currents and phase voltages. With the help of the models, one can

easily understand the unique harmonic mechanism under no-load condition in 1 (f) and

57

Page 74: Harmonic analysis of transformer excitation currents

3(f) transformers.

Page 75: Harmonic analysis of transformer excitation currents

Bibliography .

[1] J. D. Greene and C. A. Gross, “Nonlinear Models of Transformers,” IEEE Trans,

on Industry Applications, Vol. 24, No. 3, 1988, pp. 434-8.

[2] V. E. Wagner, “Effects of Harmonics on Equipment,” IEEE/PES 1992 Winter

Meeting, New York, New York, 92 WM 035-6 PWRD.

[3] Stephen J. Chapman, “Electric Machinery Fundamentals,” McGraw-Hill Book

Company, Chapter II.

[4] A. E. Fitzgerald, C. Kingsley, Jr., A. Kusko, “Electric Machinery,” McGraw-Hill

Book Company, Chapter I.

[5] E. B. Makram and A. A. Girgis, “A New Method in Teaching Power System

Harmonics in the Undergraduate Power Curriculum,” IEEE Trans, on Power

Systems, Vol. 5, No. 4, 1990, pp. 1407-12.

[6] J. H. Huang and W. Lord, “Exponential Series of B/H Curve Modeling,” IEEE

Proceedings, Vol. 23, No. 6, 1976, pp. 559-60.

59

Page 76: Harmonic analysis of transformer excitation currents

6 0

[7] S. Prusty and M. V. S. Rao, “A Novel Approach for Predetermination of Magne­

tization Characteristics of Transformers Including Hysteresis,” IEEE Trans, on

Magnetics, Vol. 20, No. 4, 1984, pp. 607-12.

[8] M. 0 . Mahmoud and R. W. W h iteh ead “Piecewise Fitting Function for Magne-i ■

tization Characteristics,” IEEE Trans. Power Apparatus and Systems, Vol. 104,

No. 7, 1985, pp. 1822-4.

[9] C. E. Lin, J. B. Wei, C. L. Huang and C. J. Huang, “A New Method for Repre­

senting Hysteresis Loop,” IEEE Trans, on Power Delivery, Vol. 4, No. 1, 1989,

pp. 413-20.

[10] S. S. Udpa and W. lord, “A Fourier Descriptor Model of Hysteresis Loop Phe­

nomena,” IEEE Trans, on Magnetics, Vol. 21, No. 6, 1985, pp. 2370-3.

[11] D. N. Ewart, “Digital Computer Simulation Model for Steel-Core Transformer,”

IEEE Trans, on Power Delivery, Vol. 1, No. 3, 1986, pp. 174-83.

[12] H. W. Dommel, A. Yan and S. Wei, “Harmonics from Transformer Saturation,”

IEEE Trans, on Power Delivery, Vol. 1, No. 2, 1986, pp. 209-15.

[13] E. B. Makram, R. L. Thompson and A. A. Girgis, “A New Laboratory Exper­

iment for Transformer Modeling in the Presence of Harmonic Distortion Using

a Computer-Controlled Harnonic Generator,” IEEE Trans, on Power Systems,

Vol. 3, No. 4, 1988, pp. 1857-63.

Page 77: Harmonic analysis of transformer excitation currents

61

[14] B. Szabados and J. Lee, “Harmonic Impedance Measurements on Transformers,”

IEEE Trans, on Power Apparatus and Systems, Vol. PAS-100, No. 12, 1981, pp.

5020-6.

[15] A. E. Emanuel, “Contribution to an Improved Method for Measurement and

Modeling of Loads for Harmonic Power Flow Studies,” Proc. IEEE 4th Int. Conf.

on Harmonics in Power Systems, Budapest, Hungary, Oct. 4-6, 1990, pp. 114-20.

[16] C. M. Summers, “The Faraday Electrical Machines Laboratory,” Proc of the

IEEE, Vol. 64, No. 11, 1976, pp. 1556-82.

[17] J. C. Li and Y. P. Wu, “FFT Algorithms for the Harmonic Analysis of Three-

Phase Transformer Banks,” IEEE Transactions on Power Delivery, Vol. 6, No.

1, January 1991, pp. 158-165.

[18] M. A. S. Masoum and E. F. Fuchs, “Transformer Magnetizing Current and Iron-

Core Losses in Harmonic Power Flow,” IE EE/PE S 1992 summer meeting, Seat­

tle, Washington, 92 SM 496-0PWRS.

[19] C. G. A. Koreman, “Determination of the Magnetizing Characteristics of Three-

Phase Transformers in Field Tests,” IEEE Transactions on Power Delivery, Vol.

4, No. 3, July 1989, pp. 1779-1785.

[20] V. Brandwajn, FI. W. Dommel and I. I. Dommel, “Matrix Representation of

Three-Phase n-Winding Transformers for Steady-State and Transient Studies,”

IEEE Transactions on Power Apparatus and Systems, Vol. PAS-101, No. 6, June

1982, pp. 1369-1378.

Page 78: Harmonic analysis of transformer excitation currents

62

[21] P. T. Krein and P. W. Sauer, “An Integrated Laboratory for Electric Machines,

Power Systems, and Power Electronics,” IEEE/PES 1991 Summer Meeting, San

Diego, California, 91 SM 315-2 PWRS.

[22] T. M. Gruzs, “A Survey of Neutral Currents in Three-Phase Computer ̂•

Power Systems,” IEEE Transactions on Industry Applications, Vol. 26, No. 4,

July/August 1990, pp. 719-725.

[23] Y. Baghzouz and X. D. Gong, “Voltage-Dependent Model for Teaching Trans­

former Core Nonlinearity,” IEEE/PES 1992 Summer Meeting, Seattle, Washing­

ton, 92 SM 393-9 PWRS (will appear in IEEE Transaction on Power Systems).

[24] EE department of MIT, “Magnetic Circuits and Transformers,” John Wiley &

Sons, INC. 1958, Chapter XXIII.

Page 79: Harmonic analysis of transformer excitation currents

6 3

APPENDIX

EXPANSIONS OF HIGH-ORDER SINE AND CONSINE

FUNCTIONS

The expansion derivations of bigh-order sine and cosine functions into multi-angle

sine and cosine functions axe listed here:

s in2a = 1(1 — cos2a) (5.1)/i

s m a = s m a • s m a

= s in a ■ 1(1 — cos2a)

1 • 1 •= —s m a — —sin a • cosza 2 21 ■ 1 1 , . n= —s m a — — • — ( sm o a — sm a )Lt ^ Z

= (3smo: — sin3o:)/4 (5-2)

sin5a = sin2a ■ sin3a

1 3 1= -(1 — cos2 a )( -s in a — -sin3a )

2 4 4

= -(3szna — sin3a — 3sina ■ cos2a + sin3a • cos2a)81 3 1

= -[3-szno: — sin3a — -(szn3a — sina ) + -(sm 5 a -f sina)]8 2 2

Page 80: Harmonic analysis of transformer excitation currents

64

1 3 1 3 1= o [(3 + o + -z)sina. - (1 + -)sz'n3a + -sm 5a]

- L J - w j - i8 2 2

= (lOsma — 5sin3a + sin5ct)/16 (5.3)

s in 7a = sin 2 a. • sin5a

= —(1 — cos2a)(10sma — 5sm3a + sinba)/16 &

= ^-(lO sm a — 5sin3a -f sinha — lOsma • cos2a + 5sm 3a • cos2a o Z

—sin5a ■ cos2a)

1 5= — [lOsma — 5sin3a + sin5a — 5(sin3a — s in a ) + ~(sin5a -f sina)o Z Z

- \- { s in la + sm 3a)]C4

= oo[(10 + 5 + - ) s in a — (5 + 5 + -)s in 3 a + (1 + ;h.sm5a: — lsm 7a]02 2 2 2 21 , 35 • 21 • o 7 • . 1 • „ X= sina — —sm da *f -sznoa — - s m ia )

o Z 2 2 2 2

= (S5sina — 2 1 s in 3 a 7 s in 5 a — sin7a)/64 (5-4)

sin9a = sin2a ■ sin7a

= -(1 — cos2a)(35szna — 21sin3a + 7sin5a — sin7a)/64Ci

= —-(35szna — 21szn3a + 7sinba — sin7a — 35sm a • cos2a 128

+21szn3a • cos2a — 7sin5a ■ cos2a + sin7a ■ cos2a)

Page 81: Harmonic analysis of transformer excitation currents

65

1 35= -[35sma — 21sm3a + 7sin5a — s in la — — (sinZa — sina)

128 2

2 1 7 i~—(sin5a + sina) — -{ s in la + sinZa) + -(s in 9 a + sin5a)]

14 i t £i

1 r/or 35 21, . 35 7, . „ /w 21 1 .= ^2 8 1(35 + ~ 2 + y ) 3 ,na “ (21 + ~ 2 + 2 ^ + (7 + y + -j)sm ba

7 1—(1 + —)sin7a + -szn9a] z z

1 .126 . 84 , 36 . c 9 . 1 . „ ,= —— (—— sina — —stnZa + — sinba — —sm 7a + -szn9a)128 2 2 2 2 2

= (126szna — 84sm3a -f 36sm5a — 9sin7a + szrc9a)/256 (5.5)

cos2a — 1(1 + cos2 a) (5-6)z

cos3a = cosa • cos2a

= lc o sa ( l + co32q;) z1 1 1 /= -cosa + - • -[cosa + cosZa)

= {Zcosa + cosZa)/4 (5.7)

cos5a = cos2a ■ cos3a

= -(1 + cos2a)(3cosa -f cosZa)/4

= - (3 cosa + cosZa + 3cos2a • cosa + cos2a ■ cosZa)81 3 1

= -[3cosa -f cosZa + -(cos3a + cosa) + -(cos5a + cosa)]8 2 2

Page 82: Harmonic analysis of transformer excitation currents

6 6

cos7 a

cos9 a

1 3 1 3 1- o K3 + o + n )cosa + (1 + -z)cos3a + -cos5a]o L I L I

1 5 1= -(5cosa + —cos3a + -cos5a) 8 2 2

= (lOcosa + 5cos3a! + cos5or)/16 (5.8)

= cos2a • cos5a

= —(1 + cos2a)(10cosa + 5cos3a + cos5a)/16 z

= ^-(lOcosa + bcosZa + cos5a + 10cosa • cos2a + 5cos3a • cos2aOZ

+cos5a • cos2a)

1 5= — [lOcosa + 5cos3a + cos5a + 5(cos3o; + cosa) + — (cos5a -f cosa) oz 2

+^(cos7a: + cos3a;)] z

1 5 1 5 1= 3 2 ^ ^ + ^ + -)cosa + (5 + 5 + ^)cosZa + (1 + -)cosba -+- - cosla ]

1 / 35 21 o 7 r 1 „ X= ^{-prcosa + — cosZa + -cosba + -co sta )02 2 2 2 2

= (35cosa + 21cos3o: -f- 7cos5a + cosla)/QA (5-9)

= cos2a ■ cos7a

= ^(1 + cos2a)(35co5o; + 21co,s3a + Icosba + cos7a)/64 z

= —— (35co5a + 21cos3a + Icosba + cosla + 35cosa • cos2a lzo

+21c0s3a • cos2a -f 1 cosba ■ cos2a + cosla ■ cos2a)

Page 83: Harmonic analysis of transformer excitation currents

-[35coso! + 21co,s3a + 7cos5a + cos7a + — (cosZa + cosa) 128 2

21 7 1+ — (c0s5a + cosa) + -(co s la + cosZa) + -(cos9o; + cos5o:)]2 2 2

1 r/or 35 21 35 7. 0 21 1J2g [(35 + y + — )coso; + (21 + — + -)cosZa + (7 + — + -

7 1+ (! + 2 )cos7q: + 2C<w9q0]

1 .126 84 „ 36 B 9 1 „ ,—- ( ——cosa + — cosoa + — cos5a + —cosla + -cos9a)128 2 2 2 2 2

(126cosa + 84cos3a + Zbcosba + 9cos7a + cos9a)/256

) cos5a

(5.10)