HC900 Hybrid Controller
Industrial Measurement and Contro l
Trainin
Control ler, OI & HC Designer
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary 1
HC900 Control ler
Controller
Module
I/O Status LEDsI/O Modules
Size: Height 5.5
Power
Supply
.
Width10.5
266.7 mm
Depth 5.9
149.9 mm
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary 2
Ethernet Supervisory
Peer-to-peer
1 port on C30 & C50
Remote I/O port
(not on C30) Field
Wiring
Terminals
Termination
Cover &
Label
Serial Ports (RS232/485 Configuration
Modbus Master/Slave
. Honeywell OI
-
8/10/2019 HC900 ControllerOIandHCD
2/13
CPU Communications Ports
Serial Port Connections (1.2- 57.6KB)S1 Port is factory configured as RS232 (modem accessible)
with ELN Protocol for use with HC Designer
S2 Port is factory configured as RS485
with ELN Protocol for use with OI
Both serial ports can be software configured as
Modbus RTU Master or Slave (only 1 Master) using HC Designer
Ethernet Connections (Host & Peer-to-peer)E1 & E2 are 10/100BaseT ports
IP Addresses factory configured as:
E1 = 192.168.1.254
E2 = 192.168.2.254 C70 & C70R
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary 3
Must be on different Sub-nets
Both ports operate in parallel (not redundant)
Up to 10 Sockets (5 in C30)
Remote I/OEthernet Private, 100Base-T (RJ-45) (not on C30)
Serial Port (S1 & S2) Hardware Setup
Either por t can be configured as RS232 or RS485
Factory set as: S1=RS232, S2=RS485
Lead and Reserve CPU in redundant
configuration must match
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary 4
-
8/10/2019 HC900 ControllerOIandHCD
3/13
-
8/10/2019 HC900 ControllerOIandHCD
4/13
Analog Output
12
Out 1 +
Out 1 -1
21
2Out 1 +
Out 1 -
4
56
78
910
1112
1314
1516
17
Out 2 +
Out 2 -
Out 3+
Out 3 -
4
56
78
910
1112
1314
1516
17
4
56
78
910
1112
1314
1516
17
Out 2 +
Out 2 -
Out 3+
Out 3 -
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary
18
1920
Out 4+
Out 4 -
18
1920
18
1920
Out 4+
Out 4 -
Digital Input
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary
-
8/10/2019 HC900 ControllerOIandHCD
5/13
Digital Outputs
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary
Operator Interface
Honeywell Operator Interface Connections
Only Lead CPU Communicates
No Fail-over detection on loss of li nk
OI maintains communication to new Lead
RS 485
ELN
Protocol
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary 10
following Fail-overOnly one OI per CPU pair
-
8/10/2019 HC900 ControllerOIandHCD
6/13
Save Time Using HC900s One-Stop Tool
Control Strategy configu ration
Drag and drop and soft-wire function blocks Multiple worksheets for process segmentation
Operator Interface Configuration
OI Data Storage Configuration
Configure data groups, storage rates, continuous or batch selection
Create files for data storage setup
Alarms and Events, p lus E-mailed Alarm/Event Setup Select tags for alarms/events, set priorities for e-mail of occurrence
Set up alarm groups, remote acknowledge plus common alarm output
Communications Setup
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary 11
- -
Serial Modbus Master/Slave
Documentation - Preview, Print Out, and Export Function block configurations, Tag List / Modbus addresses, I/O list, OI Display
setup
Recipes, profiles, schedules, sequences
RUN Mode editing, with limited process disturbanceAdd, delete, modify analog and logic blocks, add tags, change soft-wiring
Significant Features
On-line monitoring for debug and setupUse watch windows, view multiple function blocks, change internal block values,
force block outputs including I/O, view live logic power flow , signal trace back & find
Operate Control Loops, SP programmers, SequencersOn-line operation for testing, or override (includes auto-tune)
Controller / Network Diagnostics
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary 12
ec , on ro er, e wor os onnec ons, eer on ro er s a us
-
8/10/2019 HC900 ControllerOIandHCD
7/13
Use Ethernet 100Base-T, RS232 direct, or RS232 modem connectionfor access including monito ring, run-mode configuration edits
Access mult ip le cont rollers connected via Ethernet or over Internet
Architecture
se concurrent y w t , so tware over t ernet
Ethernet 10Base-T LAN or Internet / Intranet
Direct RS-232, RS-485
OrSwitch
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary 13
. .
Modem
9.6 - 38.4 KB
Or
See Quick Start Guide
GraphicConfiguration Page
Main Toolbar
Main menu
Worksheet
Toolbar
HC Designer Layout
File Browser
Worksheet
Toolbox
Fast, Normal
Scan
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary 14
Function
Block
Worksheets Worksheet Category Tabs
Configuration
Function Block
Lists
-
8/10/2019 HC900 ControllerOIandHCD
8/13
Listing of Controller
Hybrid Control Designer Organizes Your Conf iguration and Setup Tasks
with Separate Tools Related to Each Function
Functional Tabs
Controller Utility Functions
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary 15
Operator Interface Display Key AssignmentsFunction Block Diagram Worksheet Pages
Simply Drag and Drop Function Blocks and Soft-Wire
Over 100
Function Block Types!
Click on desired item
Graphic Function Block Configuration
and drag to diagram
Click on output
pin and connect to input
pin of another block
or to a Signal Tag
Click on block to
view dialog box for
block entries
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary 16
Analog Input Dialog box - sim ple address, i npu t type and range assig nmen t
-
8/10/2019 HC900 ControllerOIandHCD
9/13
What are Function Blocks?
HC900 Function Blocks
-
functions or
algorithms for user
configuration of
control strategies
through soft-wire
connection
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary 17
Function Block Number
assigned by the sequence
of programming.
AI = mnemonic
267 = block #267
Block Order number, or sequence
of execution during On-line
operation.
11 = the 11th block to be executed.
The order may be changed from
the Confi ure menu
Function Block Attributes
Inputs
Digital Pin
I/O BlockPhysical address:
010201 = Rack #1,
Module #2, Channel #1
=
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary 18
Principal Blocks such as
PID Blocks and Setpoint
programmer blocks have
tag names.
Outputs
(Rising Edge) Trigger
-
8/10/2019 HC900 ControllerOIandHCD
10/13
Function Block Attributes
Digital
Variable fordisabling
analog input
Analog Input Function Block
Signal Tags for reference and
use by OI & Host devices
Analo g
Variable
for RSP
Softwire connections
Double-click on output pin
& single-click on input pin
Analog Output
PID Function
Block
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary 19
Function Block
Page Connectorto connect function block pins
on same page, different pages or different
worksheets. Does not use Modbus address
Segment Your Configuration Logically for Convenient Access Use Signal Tags and Connectors for r eference within / between worksheets orto substitute for soft-wiring
Signal Tag
HC Designer Worksheets
Connector
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary 20
-
8/10/2019 HC900 ControllerOIandHCD
11/13
Convenient Tool Bars are Provided for Configuration Selections
Main Tool bar
Upload, Download Configuration
Monitor ModeSignalTraceback
Show / HideTool Box Browser
Help topics
Print Report
HC Designer Tool Bars
For Function Block programming:
Add Wo rksh eet Cut, Copy &
Paste
Zoom In, Out
Set up Alarms, Events
Readjust
Block Order Unlock protected
Worksheet
For 1042 OI Display conf iguration
,
Configure
DisplaysConfigure
Data Storage
Configure
OI security
Configure
Help Displays
Find GridPropertiesPrint
Worksheet
Print
Display
ListUnlock Display
File
Names
StartupDisplay
Re-arrange sheets
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary 21
Controller Operations
Configure e-mail
alarms, eventsSet Controller name
Print I/O list
Configure alarms, events
Unlock Controller
Operations Worksheet
Operator Interface Configuration
Select Tags for Display Group,
Apply to Display Fo rmatSelect OI Display Button (1- 8)
App ly Disp lay Format to a Display Pos it ion
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary 22
-
8/10/2019 HC900 ControllerOIandHCD
12/13
Convenient Access for:
Controller, I/O,
Remote Rack
Diagnostic
Status
Upload/
Utility Functions
Backup active
Configuration
plus port settings
PID Tuning
Constants, PPO
Calibrations &
Setup, Test,
Selection of
PC Ports for
Controller
Setup of
Controller
Serial Ports
Network Address,
Name &Mail Server
address setup
OI Data Storage
Setup
Calibration
of Analog I/O
ownoa Recipe changes
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary 23
Access
HC Designer Network Settings
Device Name for controller + IP AddressTwo IP addresses must be on di fferent Sub-Net
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary 24
-
8/10/2019 HC900 ControllerOIandHCD
13/13
Configuration Editing in Run Mode
Add/delete function blocks, variables, s ignal tags and w orksheets
Change / add profiles, sequences, schedules, recipes & OI displays
Provides approximate time
outputs will be held.
Outputs are held during
Hot-start restart.
HC900 Training Part 1 Version 4.2 5/14//07Honeywell Proprietary 25
Users choice to do
Hot-start or Cold-start.