Page 1 of 18
PRIMARY CHILLED WATER PUMPS AT LOWER ROOF -HEAD LOSS CALCULATION
Project : WHITE SQUARE TOWER
Consultant : MZ&P
Main contractor : EZDAN
Chilled Water pump : Primary Pumps
Location : Lower Roof
Nos of pumps : 6 working & 1 stand by
SLNO NODE DESCRIPTION SIZE(MM)
SUPPLY SIDE
1 A-B PIPE 200 6.0 6.0 760.0
2 A-B ELBOWS 90 LR 200 1 13 13.0 760.0
3 A-B FC 200 1 8 8.0 760.0
4 A-B BFV 200 1 760.0
5 A-B STRAINER 200 1 760.0
QTY-PIPE (FT)
QTY-FITTINGS
(NO)
EQUIVALENT LENGTH FOR FITTINGS
( FT )
TOTAL EQUIVALENT LENGTH (FT)
FLOW RATE (GPM)
-
Page 2 of 18
PRIMARY CHILLED WATER PUMPS AT LOWER ROOF -HEAD LOSS CALCULATION
Project : WHITE SQUARE TOWER
Consultant : MZ&P
Main contractor : EZDAN
Chilled Water pump : Primary Pumps
Location : Lower Roof
Nos of pumps : 6 working & 1 stand by
SLNO NODE DESCRIPTION SIZE(MM)QTY-PIPE
(FT)
QTY-FITTINGS
(NO)
EQUIVALENT LENGTH FOR FITTINGS
( FT )
TOTAL EQUIVALENT LENGTH (FT)
FLOW RATE (GPM)
6 A-B ECCENTRIC REDUCER 200X150 1 8.5 8.5 760.0
7 B-C ENLARGER 200X150 1 8.5 8.5 760.0
8 B-C PIPE 200 6.0 6.0 760.0
9 B-C FC 200 1 8 8.0 760.0
10 B-C NRV 200 1 760.0
11 B-C DRV 200 1 0.0 760.0
12 B-C BFV 200 1 0.0 760.0
-
Page 3 of 18
PRIMARY CHILLED WATER PUMPS AT LOWER ROOF -HEAD LOSS CALCULATION
Project : WHITE SQUARE TOWER
Consultant : MZ&P
Main contractor : EZDAN
Chilled Water pump : Primary Pumps
Location : Lower Roof
Nos of pumps : 6 working & 1 stand by
SLNO NODE DESCRIPTION SIZE(MM)QTY-PIPE
(FT)
QTY-FITTINGS
(NO)
EQUIVALENT LENGTH FOR FITTINGS
( FT )
TOTAL EQUIVALENT LENGTH (FT)
FLOW RATE (GPM)
13 B-C TEE 450X200 1 29 29.0 760.0
14 C-D PIPE 450 36.0 36.0 5033.7
-
Page 4 of 18
PRIMARY CHILLED WATER PUMPS AT LOWER ROOF -HEAD LOSS CALCULATION
Project : WHITE SQUARE TOWER
Consultant : MZ&P
Main contractor : EZDAN
Chilled Water pump : Primary Pumps
Location : Lower Roof
Nos of pumps : 6 working & 1 stand by
SLNO NODE DESCRIPTION SIZE(MM)QTY-PIPE
(FT)
QTY-FITTINGS
(NO)
EQUIVALENT LENGTH FOR FITTINGS
( FT )
TOTAL EQUIVALENT LENGTH (FT)
FLOW RATE (GPM)
15 C-D TEE 450X450 1 29 29.0 5033.7
16 C-D PIPE 450 48.2 48.2 5033.7
17 C-D ELBOWS 90 LR 450 6 29 174.0 5033.7
18 C-D PIPE 450 11.3 11.3 5033.7
19 C-D TEE 450X450 1 29 29.0 5033.7
20 D-E PIPE 450 156.0 156.0 5033.7
21 D-E TEE 450X200 1 29 29.0 5033.7
-
Page 5 of 18
PRIMARY CHILLED WATER PUMPS AT LOWER ROOF -HEAD LOSS CALCULATION
Project : WHITE SQUARE TOWER
Consultant : MZ&P
Main contractor : EZDAN
Chilled Water pump : Primary Pumps
Location : Lower Roof
Nos of pumps : 6 working & 1 stand by
SLNO NODE DESCRIPTION SIZE(MM)QTY-PIPE
(FT)
QTY-FITTINGS
(NO)
EQUIVALENT LENGTH FOR FITTINGS
( FT )
TOTAL EQUIVALENT LENGTH (FT)
FLOW RATE (GPM)
22 E-F PIPE 200 19.7 6 19.7 760.0
23 E-F ELBOWS 90 LR 200 2 13 26.0 760.0
24 E-F BFV 200 1 0.0 760.0
25 E-F STRAINER 200 1 0.0 760.0
26 E-F FC 200 1 8 8.0 760.0
27 F-G CHILLER 760.0
28 G-H PIPE 200 19.7 19.7 760.0
-
Page 6 of 18
PRIMARY CHILLED WATER PUMPS AT LOWER ROOF -HEAD LOSS CALCULATION
Project : WHITE SQUARE TOWER
Consultant : MZ&P
Main contractor : EZDAN
Chilled Water pump : Primary Pumps
Location : Lower Roof
Nos of pumps : 6 working & 1 stand by
SLNO NODE DESCRIPTION SIZE(MM)QTY-PIPE
(FT)
QTY-FITTINGS
(NO)
EQUIVALENT LENGTH FOR FITTINGS
( FT )
TOTAL EQUIVALENT LENGTH (FT)
FLOW RATE (GPM)
29 G-H ELBOWS 90 LR 200 2 13 26.0 760.0
30 G-H FC 200 1 8 8.0 760.0
-
Page 7 of 18
PRIMARY CHILLED WATER PUMPS AT LOWER ROOF -HEAD LOSS CALCULATION
Project : WHITE SQUARE TOWER
Consultant : MZ&P
Main contractor : EZDAN
Chilled Water pump : Primary Pumps
Location : Lower Roof
Nos of pumps : 6 working & 1 stand by
SLNO NODE DESCRIPTION SIZE(MM)QTY-PIPE
(FT)
QTY-FITTINGS
(NO)
EQUIVALENT LENGTH FOR FITTINGS
( FT )
TOTAL EQUIVALENT LENGTH (FT)
FLOW RATE (GPM)
31 G-H DRV 200 1 0.0 760.0
32 G-H BFV 200 0.0 760.0
33 G-H MBFV 200 1 0.0 760.0
34 G-H TEE 450X200 1 29 42.0 760.0
35 H-I PIPE 450 156.0 156.0 5033.7
36 H-I TEE 450 1 29 29.0 5033.7
37 I-J PIPE 450 44.0 44.0 5033.7
-
Page 8 of 18
PRIMARY CHILLED WATER PUMPS AT LOWER ROOF -HEAD LOSS CALCULATION
Project : WHITE SQUARE TOWER
Consultant : MZ&P
Main contractor : EZDAN
Chilled Water pump : Primary Pumps
Location : Lower Roof
Nos of pumps : 6 working & 1 stand by
SLNO NODE DESCRIPTION SIZE(MM)QTY-PIPE
(FT)
QTY-FITTINGS
(NO)
EQUIVALENT LENGTH FOR FITTINGS
( FT )
TOTAL EQUIVALENT LENGTH (FT)
FLOW RATE (GPM)
38 I-J ELBOWS 90 LR 450 4 29 116.0 5033.7
39 J-A PIPE 450 5.0 5.0 5033.7
TOTAL PRESSURE DROP (FT)
15% SAFETY FACTOR
TOTAL FRICTION HEAD
Primary pump head as per Calculation
-
Page 9 of 18
PRIMARY CHILLED WATER PUMPS AT LOWER ROOF -HEAD LOSS CALCULATION
Project : WHITE SQUARE TOWER
Consultant : MZ&P
Main contractor : EZDAN
Chilled Water pump : Primary Pumps
Location : Lower Roof
Nos of pumps : 6 working & 1 stand by
SLNO NODE DESCRIPTION SIZE(MM)QTY-PIPE
(FT)
QTY-FITTINGS
(NO)
EQUIVALENT LENGTH FOR FITTINGS
( FT )
TOTAL EQUIVALENT LENGTH (FT)
FLOW RATE (GPM)
Primary pump head as per Design
-
Page 10 of 18
PRIMARY CHILLED WATER PUMPS AT LOWER ROOF -HEAD LOSS CALCULATION
Project : WHITE SQUARE TOWER
Consultant : MZ&P
Main contractor : EZDAN
Chilled Water pump : Primary Pumps
Location : Lower Roof
Nos of pumps : 6 working & 1 stand by
REMARKS
SUPPLY SIDE
0.01 0.06 Carrier Hand Book
0.01 0.13 Carrier Hand Book
0.01 0.08 Carrier Hand Book
0.01 0.08
0.01 1.08
FRICTION LOSS FT/FT
FRICTION HEAD (FT.OF
WATER COLUMN)
Crane Valves Tech. Data
Crane Valves Tech. Data
-
Page 11 of 18
PRIMARY CHILLED WATER PUMPS AT LOWER ROOF -HEAD LOSS CALCULATION
Project : WHITE SQUARE TOWER
Consultant : MZ&P
Main contractor : EZDAN
Chilled Water pump : Primary Pumps
Location : Lower Roof
Nos of pumps : 6 working & 1 stand by
REMARKSFRICTION
LOSS FT/FT
FRICTION HEAD (FT.OF
WATER COLUMN)
0.01 0.09 Carrier Hand Book
0.01 0.09 Carrier Hand Book
0.01 0.06 Carrier Hand Book
0.01 0.08 Carrier Hand Book
0.26
2.71
0.08
Crane Valves Tech. Data
Crane Valves Tech. Data
Crane Valves Tech. Data
-
Page 12 of 18
PRIMARY CHILLED WATER PUMPS AT LOWER ROOF -HEAD LOSS CALCULATION
Project : WHITE SQUARE TOWER
Consultant : MZ&P
Main contractor : EZDAN
Chilled Water pump : Primary Pumps
Location : Lower Roof
Nos of pumps : 6 working & 1 stand by
REMARKSFRICTION
LOSS FT/FT
FRICTION HEAD (FT.OF
WATER COLUMN)
0.01 0.29 Carrier Hand Book
0.008 0.29 Carrier Hand Book
-
Page 13 of 18
PRIMARY CHILLED WATER PUMPS AT LOWER ROOF -HEAD LOSS CALCULATION
Project : WHITE SQUARE TOWER
Consultant : MZ&P
Main contractor : EZDAN
Chilled Water pump : Primary Pumps
Location : Lower Roof
Nos of pumps : 6 working & 1 stand by
REMARKSFRICTION
LOSS FT/FT
FRICTION HEAD (FT.OF
WATER COLUMN)
0.008 0.23 Carrier Hand Book
0.008 0.39 Carrier Hand Book
0.008 1.39 Carrier Hand Book
0.008 0.09 Carrier Hand Book
0.008 0.23 Carrier Hand Book
0.008 1.25 Carrier Hand Book
0.008 0.23 Carrier Hand Book
-
Page 14 of 18
PRIMARY CHILLED WATER PUMPS AT LOWER ROOF -HEAD LOSS CALCULATION
Project : WHITE SQUARE TOWER
Consultant : MZ&P
Main contractor : EZDAN
Chilled Water pump : Primary Pumps
Location : Lower Roof
Nos of pumps : 6 working & 1 stand by
REMARKSFRICTION
LOSS FT/FT
FRICTION HEAD (FT.OF
WATER COLUMN)
0.01 0.20 Carrier Hand Book
0.01 0.26 Carrier Hand Book
0.08
1.08
0.01 0.08 Carrier Hand Book
10.80 MCQUAY Selection
0.01 0.20 Carrier Hand Book
Crane Valves Tech. Data
Crane Valves Tech. Data
-
Page 15 of 18
PRIMARY CHILLED WATER PUMPS AT LOWER ROOF -HEAD LOSS CALCULATION
Project : WHITE SQUARE TOWER
Consultant : MZ&P
Main contractor : EZDAN
Chilled Water pump : Primary Pumps
Location : Lower Roof
Nos of pumps : 6 working & 1 stand by
REMARKSFRICTION
LOSS FT/FT
FRICTION HEAD (FT.OF
WATER COLUMN)
0.01 0.26 Carrier Hand Book
0.01 0.08 Carrier Hand Book
-
Page 16 of 18
PRIMARY CHILLED WATER PUMPS AT LOWER ROOF -HEAD LOSS CALCULATION
Project : WHITE SQUARE TOWER
Consultant : MZ&P
Main contractor : EZDAN
Chilled Water pump : Primary Pumps
Location : Lower Roof
Nos of pumps : 6 working & 1 stand by
REMARKSFRICTION
LOSS FT/FT
FRICTION HEAD (FT.OF
WATER COLUMN)
3.60
0.30
0.50
0.01 0.42 Carrier Hand Book
0.006 0.94 Carrier Hand Book
0.006 0.17 Carrier Hand Book
0.006 0.26 Carrier Hand Book
Crane Valves Tech. Data
Crane Valves Tech. Data
Crane Valves Tech. Data
-
Page 17 of 18
PRIMARY CHILLED WATER PUMPS AT LOWER ROOF -HEAD LOSS CALCULATION
Project : WHITE SQUARE TOWER
Consultant : MZ&P
Main contractor : EZDAN
Chilled Water pump : Primary Pumps
Location : Lower Roof
Nos of pumps : 6 working & 1 stand by
REMARKSFRICTION
LOSS FT/FT
FRICTION HEAD (FT.OF
WATER COLUMN)
0.006 0.70 Carrier Hand Book
0.006 0.03 Carrier Hand Book
TOTAL PRESSURE DROP (FT) 29.13
15% SAFETY FACTOR 4.37
ft of water 33.50
Kpa 100.18
ft of water 33.50
-
Page 18 of 18
PRIMARY CHILLED WATER PUMPS AT LOWER ROOF -HEAD LOSS CALCULATION
Project : WHITE SQUARE TOWER
Consultant : MZ&P
Main contractor : EZDAN
Chilled Water pump : Primary Pumps
Location : Lower Roof
Nos of pumps : 6 working & 1 stand by
REMARKSFRICTION
LOSS FT/FT
FRICTION HEAD (FT.OF
WATER COLUMN)
ft of water 30.00
PRIMARY at chiller yard