1 FACULTY OF ENGINEERING AND APPLIED SCIENCE ENGR3930U-HEAT TRANSFER DESIGN PROJECT REPORT Improving Home Insulation and Reducing Energy Consumption Instructors: Prof. Dr. Ibrahim Dincer TA: Rami El-Emam LAB GROUP No. Date performed Date Submitted Date received No. of pages Grade LAB GROUP MEMBERS Surname Name Signature ID 1 Tuan Nguyen 100344743 2 Daniel Bondarenko 100363648 Remarks: If one in group cheats, the entire group will be responsible for it. Plagiarism and dishonesty will not be tolerated. The group member(s), who don’t sign the report, will be considered “not contributed” and given “zero” for the report. This cover sheet should be fully completed. All reports should be submitted in two weeks time to the TAs during the lab session. 2

Upload: daniel-bondarenko

Post on 13-Apr-2017

36 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Heat Transfer Project

1

FACULTY OF ENGINEERING AND APPLIED SCIENCE

ENGR3930U-HEAT TRANSFER DESIGN PROJECT REPORT

Improving Home Insulation and Reducing Energy Consumption

Instructors: Prof. Dr. Ibrahim Dincer

TA: Rami El-Emam LAB GROUP No.

Date performed

Date Submitted

Date received

No. of pages

Grade

LAB GROUP MEMBERS

Surname Name Signature ID

1 Tuan Nguyen 100344743

2 Daniel Bondarenko 100363648

Remarks: • If one in group cheats, the entire group will be responsible for it. • Plagiarism and dishonesty will not be tolerated. • The group member(s), who don’t sign the report, will be considered “not contributed” and given “zero” for the report. • This cover sheet should be fully completed. • All reports should be submitted in two weeks time to the TAs during the lab session.

2

Page 2: Heat Transfer Project

2

Table of Contents

Page # Summary…………………………………………………………………………………………………………………………………………… 3

Introduction……………………………………………………………………………………………………………………………………… 3

Theory………………………………………………………………………………………………………………………………………………… 4

Energy Saving Tips and Government Subsidy Information………………………………………………………4

Weather Information For Oshawa…………………………………………………………………………………………………5

Air Properties For Weather Data………………………………………………………………………………………………… 6

Basement Floor Plan and Analysis……………………………………………………………………………………………………7

Basement Floor Optimization…………………………………………………………………………………………………………12

1st Floor Plan and Analysis……………………………………………………………………………………………………………… 16

1st Floor Optimization………………………………………………………………………………………………………………………34

2nd Floor Plan and Analysis…………………………………………………………………………………………………………… 38

2nd Floor Optimization…………………………………………………………………………………………………………………… 48

Conclusion………………………………………………………………………………………………………………………………………… 50

References……………………………………………………………………………………………………………………………………… 50

Page 3: Heat Transfer Project

3

SUMMARY

Essentially, this lab report contains our attempts and results in reducing the total energy losses within a house by at least 25 percent. Initially, we decided to map out a floor plan for a 2 storey approximately 3000 square foot house. Afterwards, we decided to calculate the energy and heat losses for the house in its initial state without any improvements. Afterwards, we decided to redesign the windows and insulation and recalculate the energy losses to see if the minimum improvement objective of 25 percent was accomplished. Once that was completed, we decided to look for various government subsidies that were provided by the Canadian Government, if one choose to make improvements towards their house based on our design and specifications. INTRODUCTION

The purpose of our Heat Transfer design project was to reduce the average energy

consumption of an average house by at least 25 percent. This was done by redesigning various sections of the house so that there could be less heat transfer losses, which in turn would reduce the amount of energy needed to cool/heat the house. According to Natural Resources Canada, it was shown statistically that Ontarians living in a single detached house consume roughly 118.7 PJ (peta joule) and 252.5 PJ of electricity and gas in a year, respectively. Therefore, it was important for us to accomplish the objective of the project because not only would it save money, but it would also improve the environment by lowering the carbon footprint and green house gases of the average Canadian. Also, by using the recycled materials such as mineral fiber insulation and environmentally friendly plastics like PLA, the carbon footprint would be reduced not only in energy consumption but also by the damage caused by unused or disposed building materials.

Figure 1: Table from Natural Resources Canada showing the annual energy consumption of single detached houses within Ontario.

Page 4: Heat Transfer Project

4

THEORY

In regards to the theory of our design project, it can be said that it was mostly based on thermal conductivity. This is because since we were designing the house to minimize heat loss, it can be said that selection of material to insulate the house was of utter most importance. Therefore thermal conductivity played a majored role in our design because it is one of the most important properties of a material that determines how much heat the material is able to conduct/insulate. As such, it can be said that materials with a high thermal conductivity are good heat conductors and materials of low thermal conductivity are good insulators. However, in regards to our project, we mostly selected material of low thermal conductivity because we were looking for good insulators that minimized heat loss.

We also used the theory of thermal resistance network for the walls and insulations of the house. This is because the walls of our house consists of many layers being the brick and motor, then the wood and insulation, then the plywood, and lastly the dry wall. Therefore, the theory of thermal resistance network was vital towards our project because it was mainly used to see the heat transfer losses that occur through the layers of the wall for our house.

In order to choose the proper temperature for the analysis the gas and energy bills were found highest during the month of January for winter period, with a gas bill valuing at $235.75 per month. It was further found what date had the lowest temperature and how low was it. ENERGY SAVING TIPS AND GOVERNMENT SUBSIDY INFORMATION If one decided that the improvements to reduce energy use and heat transfer losses by our method and design were too expensive or not practical, then here are some energy saving tips that are more cost effective and practical that can be used as an alternative. Try setting the thermostat at 20 degrees Celsius during the day and 17 degrees Celsius

during the night. Lowering a house’s temperature regularly during the night for 8 hours a day can reduce gas usage by 6%.

Install your thermostat in an air neutral zone. This will inhibit your furnace from running too often due to drafts or etc.

During cold months, windows will lose a significant amount of heat. Therefore, try to seal cracks and drafts with caulking or any alternative method to reduce the loss

Check your attic, make sure there is enough insulation and that the attic is well vented towards the outdoors.

If one were to redesign their homes based on our design and specification, then there are some subsidies provided by the Ontarian Government that will help financially. There is a list below of various rebates and incentives provided by the Ontario Government.

- Ontario home owners can get rebates for various insulations improvement from the following:

• Attic or roof insulation rebate of up to $750.00 • Exterior Wall Insulation of up to $1875.00 • Windows and Doors rebate of $40.00 dollars for each replacement unit

Page 5: Heat Transfer Project

5

- Ontario home owners can get a Eco Energy Home Retrofit Grant of up to $5000.00 if they do the following:

I. Have an accredited energy advisor do an energy evaluation on your home II. Do your home improvements

III. Have your advisor do another energy evaluation to see how much more energy efficient your house is

IV. The advisor will send your final evaluation to Natural Resources Canada, who will then send you a rebate check

Weather Data for the Coldest Day in January for Oshawa, Ontario [1]

Page 6: Heat Transfer Project

6

Minimum Temperature of the Day Data (Considering the wind speed effects on the heat transfer coefficient) Tout= -24.0 [oC] Dew Point Temperature = -26.5 [oC] Relative Humidity = 80% Wind direction 20 degrees from North Wind Speed =11[km/h]=3.056[m/s] Pressure = 101[kPa] Air Properties (Found in Table A-15): Coldest Day: T = -24[oC] Vwind=11[km/h]=3.056[m/s] ρ=[1.451+(1.394-1.451)*(-24+30)/(-20+30)][kg/m3]=1.4168[kg/m3] k=[0.02134+(0.02211-0.02134)*(-24+30)/(-20+30)][W/mK]=0.021802[W/mK] α=[1.465/105+(1.578-1.465)/105*(-24+30)/(-20+30)][m2/s2]=1.5328/105 [m2/s2] μ=[1.579/105+(1.630-1.579)/105*(-24+30)/(-20+30)][kg/ms]=1.6096/105[kg/ms] ν=[1.087/105+(1.169-1.087)/105*(-24+30)/(-20+30)][m2/s]=1.1362/105[m2/s] Pr=[0.7425+(0.7408-0.7425)*(-24+30)/(-20+30)]=0.74148 Hottest Day: T = 34[oC] Vwind=21[km/h]=7.222[m/s] ρ=[1.164+(1.145-1.164)*(34-30)/(35-30)][kg/m3]=1.1488[kg/m3] k=[0.02588+(0.02625-0.02588)*(34-30)/(35-30)][W/mK]=0.026176[W/mK] α=[2.208/105+(2.277-2.208)/105*(34-30)/(35-30)][m2/s2]=2,2632/105 [m2/s2] μ=[1.872/105+(1.895-1.872)/105*(34-30)/(35-30)][kg/ms]=1.8904/105[kg/ms] ν=[1.608/105+(1.655-1.608)/105*(34-30)/(35-30)][m2/s]=1.6456/105[m2/s] Pr=[0.7282+(0.7268-0.7282)* (34-30)/(35-30)]=0.72708

Page 7: Heat Transfer Project

7

Basement Floor Plan

Basement Window Sill-Box Dimensions Width [m] Height [m] Length [m]

Window 1 0.79 0.36 0.46 Window 2 0.79 0.26 0.52

Window Parameters: Double-Pane, Double Glazing, one side Low-e Coated Windows, air filled, tightly sealed, vinyl framed, with metal spacer type. Thickness of space inside the window Δxair=0.010[m]; Thickness of the acrylic of the window Δxw=0.0025[m]; kacrylic= kacr=0.19[W/(mK)] (From the ending article of chapter 9) Frame thickness Δxw=0.041[m] The basement wall is solidly composed of bricks and rocks, the approximate coefficient of conduction for this composite is chosen from Table A5 to be equivalent to the coefficient of conduction of dense fired clay bricks or kbasement wall= kbw= 1.34[W/(mK)]. The basement floor is concrete and from Table A5 can be approximated by the value kconcrete= kconc= 1.1[W/(mK)]

Page 8: Heat Transfer Project

8

Basement Heat Loss Analysis Frost Penetration depth is about 1.2[m] deep in the area of Oshawa, that is at the depth of 1.2[m] the soil temperature is 0[oC]. [2]

Note: The basement outer wall temperature is in contact with soil. The basement does not have air conditioning nor is it heated. Basement windows are blocked from wind interaction by a concrete barrier and a non-insulating transparency. Assumptions: Steady state conditions are applicable under extreme conditions (i.e. the coldest and the hottest temperatures) in order for the optimization process to yield stable results regardless of transient effects spanning over a year. That is the analysis of heat conduction of a given house considers peace time conditions and no immediate threat, such as local power station anomaly, or extreme weather such as hurricane. Assume ideal and incompressible gas conditions. The soil is dry and compact in the vicinity of the basement which allows for soil heat conduction coefficient to be ksoil=0.5[W/(Km)]. The surface temperature of soil is the same as the air temperature on either the hottest or the coldest day due to applied steady state conditions. Take a 100X100[m2] patch of land to approximate for heat losses from the ground to the atmosphere at a given penetration depth The average temperature of outer basement wall: For winter: Tsoil surface= Tss = -24[oC], Tfrost penetration depth= Tfpd = 0[oC] dx=1.2[m], ksoil = 0.5[W/(Km)], A=104[m] Q’soil = - ksoil*A*[Tss – Tfpd ]/dx = - 0.5*104*(-24-0)/1.2 [W] = 105[W] At a depth of around 2 meters the soil temperature given the above conditions would be: (105*2)/(0.5*10’000)-24[oC]=16[oC] For analysis purposes let the outer wall and the basement floor be at an average temperature of 5[oC] in order to compensate for any extreme weather conditions and be within a reasonable temperature range.

Page 9: Heat Transfer Project

9

Heat losses in the basement during winter: Heat Losses by Walls 1 & 3: Wall dimensions: L=4.30[m]; H=2.14[m]; A=4.30*2.14[m2]= 9.202 [m2]; Δx=0.60[m] kbw=1.34[W/(mK)] Heat lost from one wall: Qcond= -kbw*A*(ΔT /Δx) = -1.34[W/(mK)]* 9.202 [m2]*((5-15)[K] /0.60[m])= 205.51[W] Heat lost from both walls: Q1&3 = 2*Qcond = 2*205.51[W]= 411.02[W] Convective heat coefficient computation: 205.51/(9.202*(17-15))[W/(m2K)]=11.167[W/(m2K)] This coefficient is within a reasonable range compared to the value given in the book (8.29[W/(m2K)]). The calculated value is higher for the reasons that the warm air moves from the basement to the upper floors. The amount of heat lost by the two walls is 411.02[W]. Heat Losses by Wall 2: Wall dimensions: L=9.44[m]; H=2.14[m]; A=(9.44*2.14)-(window area)[m2]= (9.44*2.14-0.79*0.26) [m2] = 19.996[m2]; Δx=0.60[m]; kbw=1.34[W/(mK)] Heat lost from the wall: Q2= -kbw *A*(ΔT /Δx) = -1.34[W/(mK)]* 19.996 [m2]*((5-15)[K] /0.60[m])=446.577[W] Convective heat coefficient computation: 446.577/(19.996*(17-15))[W/(m2K)]=11.167[W/(m2K)] This coefficient is within a reasonable range compared to the value given in the book (8.29[W/(m2K)]). The calculated value is higher for the reasons that the warm air moves from the basement to the upper floors. It is also the same as the value calculated previously. The amount of heat lost by the wall is 446.577 [W]. Heat Losses by Wall 4: Wall dimensions: L=9.44[m]; H=2.14[m]; A=(9.44*2.14)-(window area)[m2]= (9.44*2.14-0.79*0.36) [m2] = 19.917[m2]; Δx=0.60[m]; kbw=1.34[W/(mK)] Heat lost from the wall: Q4= -kbw *A*(ΔT /Δx) = -1.34[W/(mK)]* 19.917 [m2]*((5-15)[K] /0.60[m])= 444.813[W] Convective heat coefficient computation: 444.813/(19.712*(17-15))[W/(m2K)]=11.283[W/(m2K)]

Page 10: Heat Transfer Project

10

This coefficient is within a reasonable range compared to the value given in the book (8.29[W/(m2K)]). The calculated value is higher for the reasons that the warm air moves from the basement to the upper floors. It is also the same as the value calculated previously. The amount of heat lost by the wall is 444.813[W]. Heat Losses by Window 1: Window Parameters: Double-Pane, Double Glazing, one side Low-e Coated Windows, air filled, tightly sealed, vinyl framed, with metal spacer type. L=0.79[m]; H=0.26[m]; A= 0.79*0.26 [m2] = 0.2054[m2]; Thickness of space inside the window Δxair=0.010[m]; Thickness of the acrylic of the window Δxw=0.0025[m]; kacrylic= kacr=0.19[W/(mK)] Frame thickness Δxw=0.041[m] From table 9-3: At Tavg=0[oC], ΔT=30[oC] for single glazed window h=2.6[W/(m2K)] In complement to the ending article of chapter 9, the convective heat transfer coefficient can be neglected if the air space thickness inside the windows is less than 0.013[m] and the conductive coefficient for air can be used instead. For such scenario the conductive coefficient is taken from Table A-15 to be 0.02364[W/(mK)] at 0 oC. The two cases will be analyzed during the calculations and a suitable one will be chosen for further analysis. According to Table 9-6, the given basement window can have a U-factor of about: 2.59+(2.06-2.59)*(10-6.4)/(12.7-6.4)[W/(m2K)]= 2.287[W/(m2K)] The analysis of the window will be performed based on the overall U-factor and on the thermal resistances of full window pane with and without convective heat transfer coefficients. The most relevant method will be chosen for further analysis for other windows. Note: The areas near the basement windows are isolated from the interaction with the wind and the wind speeds during the coldest day are not 24[km/h]. However, the convective heat transfer coefficient for the window is taken from Table 3-9 to approximate the possible conditions at the outer surface of the window. The conditions are taken to be that the heat flows away from the vertical window in a horizontal direction and the surface emittance of the window is 0.9, hence the convective heat transfer coefficient is at around 8.29[W/(m2K)]. However, according to the book this value is equivalent to the value of convective heat transfer coefficient inside the house. Since the calculated heat transfer coefficient inside the house is 11.167[W/(m2K)], assume that in the still air near the basement window this coefficient also applies. hbasement= hout =11.167[W/(m2K)] ; Tbasement air= Tba = 17[oC]; Tout = -24[oC] Heat lost from the window: Rin=1/(11.167[W/(m2K)]*0.2054[m2])=0.436[K/W]=Rout (By the conditions given above) Racr=0.0025[m]/(0.19[W/(mK)]*0.2054[m2])=0.064[K/W] Window with convective heat transfer coefficient Rah=1/(2.6[W/(m2K)]*0.2054[m2])=1.8725[K/W] Qw1= (ΔT /∑R) = (17-(-24))[K] /(0.436*2+0.064*2+1.8725)[K/W])=14.273[W] Window with conductive heat transfer coefficient Rak=0.01[m]/(0.02364[W/(mK)]*0.2054[m2])=2.059[K/W] Qw1= (ΔT /∑R) = (17-(-24))[K] /(0.436*2+0.064*2+2.059)[K/W])=13.403[W]

Page 11: Heat Transfer Project

11

Window with an overall U-factor coefficient RU=1/(2.287[W/(m2K)]*0.2054[m2])= 2.1288[K/W] Qw1= (ΔT /∑R) = (17-(-24))[K] /(0.436*2+0.064*2+2.1288)[K/W])=13.104[W] It is apparent that the values for heat losses are approximately in the same ball-park. For the reasons mentioned in the Cengel’s book, the convective heat transfer coefficient for the air spaces thinner than 13 millimeters can be avoided. Hence, the case of window with convective heat transfer coefficient can be neglected. Also, as it can be seen for the case of a full pane window with conductive heat transfer coefficient and the window with an overall U-factor coefficient the heat losses are nearly the same. Therefore, for the convenience of further analysis the tabulated values will be used to compute the heat losses from the windows with frames and the conductive heat transfer coefficient method will be used for full pane windows. The average temperature of the indoors window 1 surface is: 17[oC]-13.104[W]*0.436[K/W] =11.287[oC] To conclude for the amount of heat lost by this window the value of 13.104[W] is taken. Heat Losses by Window 2: Window Parameters: Similar to Window 1 L=0.79[m]; H=0.36[m]; A= 0.79*0.36 [m2] = 0.2844[m2]; Thickness of space inside the window Δxair=0.010[m]; Thickness of the acrylic of the window Δxw=0.0025[m]; kacrylic= kacr=0.19[W/(mK)] Frame thickness Δxw=0.041[m] Conditions are the same as in the case of window 1, except the area of the window is different. According to Table 9-6, the given basement window can have a U-factor of about: 2.59+(2.06-2.59)*(10-6.4)/(12.7-6.4)[W/(m2K)]= 2.287[W/(m2K)] hbasement= hout =11.167[W/(m2K)] ;Tbasement air= Tba = 17[oC]; Tout = -24[oC] Heat lost from the window: Rin=1/(11.167[W/(m2K)]*0.2844[m2])=0.3149[K/W]=Rout (By the conditions given above) Racr=0.0025[m]/(0.19[W/(mK)]*0.2844[m2])=0.0463[K/W] RU=1/(2.287[W/(m2K)]*0.2844[m2])=1.537[K/W] Qw2= (ΔT /∑R) = (17-(-24))[K] /(0.3149*2+0.0463*2+2.1288)[K/W])=14.380[W] The average temperature of the indoors window 2 surface is: 17[oC]-14.380[W]*0.3149[K/W] =12.472[oC] The amount of heat lost by this window is 14.380[W].

Page 12: Heat Transfer Project

12

Heat Losses by Basement Floor: Floor dimensions: L=9.44[m]; W=4.30[m]; A=(9.44*4.30)[m2] = 40.592[m2]; Δx=0.20[m]; kconcrete= kconc=1.1[W/(mK)] The convective heat transfer coefficient is calculated above and is taken to be h=11.167[W/(m2K)] Heat lost to the floor: Rair near floor= Ranf= 1/(11.167[W/(m2K)]* 40.592[m2])=0.00221[K/W] Rconduction floor= Rcf= 0.2[m]/(1.1[W/(mK)]* 40.592[m2])=0.00448[K/W] Qfloor= -(ΔT /∑R) = -((5-17)[K] /(0.00221+0.00448)[K/W])=1’793.722[W] Qfloor =1.793722[kW] The temperature of the floor is 17[oC]-1’793.722[W]*0.00221[K/W]=13.04[oC] The amount of heat lost by the floor is 1’793.722[W]. The total heat loss from the basement is the sum of all the losses: Qtotal=Qfloor+ Q1&3 + Q2 + Q4 + Qw1 +Qw2 =(1’793.722+411.02+446.577+444.813+13.104+14.380)[W] Qtotal=3’123.616[W] Minimizing Basement Heat Losses: The heat losses by the walls can be minimized by covering them with mineral fiber blanket (From Table A-5 for a 50[mm] thick blanket R=1.23[(m2K)/W]) and a plaster board (From Table A-5 for a 13[mm] thick board R=0.055[(m2K)/W]). Suppose that the surface and air temperatures of the basement remained the same as in the case without minimization. Heat Losses by Walls 1 & 3: Wall dimensions: L=4.30[m]; H=2.14[m]; A=4.30*2.14[m2]= 9.202 [m2]; Δx=0.60[m] kbw=1.34[W/(mK)] Heat lost from one wall: Rtotal=[0.6[m]/(1.34[W/(mK)]* 9.202 [m2])+1/(1.23[W/(m2K)]* 9.202 [m2]) +1/(0.055[W/(m2K)]* 9.202 [m2])] Rtotal= 2.113[K/W] Qcond= - ΔT /Rtotal = -((5-15)[K] /2.113[K/W])=4.733[W] Heat lost from both walls: Q1&3 = 2*Qcond = 2*4.733 [W]= 9.466[W] The amount of heat lost by the two walls is 9.466[W] which is 43 times less than the original value 411.02[W].

Page 13: Heat Transfer Project

13

Heat Losses by Wall 2: Wall dimensions: L=9.44[m]; H=2.14[m]; A=(9.44*2.14)-(window area)[m2]= (9.44*2.14-0.79*0.26) [m2] = 19.996[m2]; Δx=0.60[m]; kbw=1.34[W/(mK)] Heat lost from the wall: Rtotal=[0.6[m]/(1.34[W/(mK)]* 19.996[m2])+1/(1.23[W/(m2K)]* 19.996 [m2]) +1/(0.055[W/(m2K)]* 19.996 [m2])] Rtotal= 0.9723[K/W] Q2 = - ΔT /Rtotal = -((5-15)[K] /0.9723[K/W])=10.285[W] The amount of heat lost by the wall is 10.285[W] which is about 45 times less than the original value of 446.577 [W]. Heat Losses by Wall 4: Wall dimensions: L=9.44[m]; H=2.14[m]; A=(9.44*2.14)-(window area)[m2]= (9.44*2.14-0.79*0.36) [m2] = 19.917[m2]; Δx=0.60[m]; kbw=1.34[W/(mK)] Heat lost from the wall: Rtotal=[0.6[m]/(1.34[W/(mK)]* 19.917[m2])+1/(1.23[W/(m2K)]* 19.917 [m2]) +1/(0.055[W/(m2K)]* 19.917 [m2])] Rtotal= 0.976[K/W] Q4 = - ΔT /Rtotal = -((5-15)[K] /0.976[K/W])=10.244[W] The amount of heat lost by the wall is 10.244[W] which is again about 45 times greater than the original value of 444.813[W]. The heat losses by the windows can be minimized by covering the window sill boxes with a transparent PLA film (Poly-Lactic Acid is biodegradable and is made from corn starch [3]) (From Table A-5 an approximate value can be found similar to the R-value of vapor-permeable felt, that is RPLA=0.011[(m2K)/W]) and an isolated space of air. Assume that the PLA film is at the same temperature as the basement air or 17[oC]. The gravitational acceleration is approximately g=9.81[m/s2]. Take the average temperature of the air inside the isolated sill space. Since in the previous calculations the average indoor window surface temperature was about 12[oC], the average temperature would most likely be around (17+12)/2[oC] or approximately 15[oC] Tavg=15[oC] Therefore from Table A-15: ρ=1.225[kg/m3] k=0.02476[W/mK]

Page 14: Heat Transfer Project

14

α=2.009/105 [m2/s2] μ=1.802/105[kg/ms] ν=1.470/105[m2/s] Pr=0.7323 β=1/(273+15)[1/K]=0.00347[1/K] Heat Losses by Window 1: Window Parameters: Double-Pane, Double Glazing, one side Low-e Coated Windows, air filled, tightly sealed, vinyl framed, with metal spacer type. L=0.79[m]; H=0.26[m]; A= 0.79*0.26 [m2] = 0.2054[m2]; Thickness of space inside the window Δxair=0.010[m]; Thickness of the acrylic of the window Δxw=0.0025[m]; kacrylic= kacr=0.19[W/(mK)] Frame thickness Δxw=0.041[m] The characteristic length is the length of the isolated air space or Lc=0.46[m] Tbasement air= Tba = TPLA= 17[oC]; Tout = -24[oC], Tindoor window surface= Tiws=12[oC] Rayleigh value for the isolated window sill space: RaL=(g*β*(TPLA-Tiws)* Lc

3*Pr)/(ν)= (9.81*0.00347*(17-12)*(0.46)3*0.7323)/(1.470/105)=825.303 The aspect ratio geometry is H/Lc =0.26/0.46=0.565 which is crudely close to around 1 The Nusselt number can be found by Catton-Berkovsky-Polevikov equation (equation 9-52 in the reference book) Nu=0.18((Pr* RaL)/(0.2+Pr))0.29=1.177 (a very crude approximation) Q’=k*Nu*A*(TPLA-Tiws)/Lc =0.02476[W/(mK)]*1.177*0.2054[m2]*(17-12)[oC]/0.46[m]=0.065[W] h=Q’/( A*(TPLA-Tiws))=0.065[W]/(0.2054[m2]*(17-12)[oC])= 0.063[W/(m2 oC)] Because the approximation is fairly crude take a loss of 0.1[W] as a more compatible value. The amount of heat lost by sill isolated window is about 0.1[W] which is much less than the value of 13.104[W] that was calculated without the thin PLA membrane. Heat Losses by Window 2: Window Parameters: Similar to Window 1 L=0.79[m]; H=0.36[m]; A= 0.79*0.36 [m2] = 0.2844[m2]; Thickness of space inside the window Δxair=0.010[m]; Thickness of the acrylic of the window Δxw=0.0025[m]; kacrylic= kacr=0.19[W/(mK)] Frame thickness Δxw=0.041[m] The characteristic length is the length of the isolated air space or Lc=0.52[m] Tbasement air= Tba = TPLA= 17[oC]; Tout = -24[oC], Tindoor window surface= Tiws=12[oC] Rayleigh value for the isolated window sill space: RaL=(g*β*(TPLA-Tiws)* Lc

3*Pr)/(ν)= (9.81*0.00347*(17-12)*(0.52)3*0.7323)/(1.470/105)=1192.203 The aspect ratio geometry is H/Lc =0.36/0.46=0.7826 which is crudely close to around 1 The Nusselt number can be found by Catton-Berkovsky-Polevikov equation (equation 9-52 in the reference book)

Page 15: Heat Transfer Project

15

Nu=0.18((Pr* RaL)/(0.2+Pr))0.29=1.309 (a very crude approximation) Q’=k*Nu*A*(TPLA-Tiws)/Lc =0.02476[W/(mK)]*1.309*0.2844[m2]*(17-12)[oC]/0.52[m]=0.0886[W] h=Q’/( A*(TPLA-Tiws))= 0.0886[W]/(0.2844[m2]*(17-12)[oC])= 0.062[W/(m2 oC)] Because the approximation is fairly crude take a loss of 0.1[W] as a more compatible value. The amount of heat lost by sill isolated window is about 0.1[W] which is much less than the value of 14.380[W] that was calculated without the thin PLA membrane. To prevent the heat losses through the basement floor a carpet and fibrous pad can be applied (nothing else would be suitable enough because a tall person may begin to hit the ceiling and feel uncomfortable to enter the basement), from Table A-15 Rcarpet=0.367[(m2K)/W] Heat Losses by Basement Floor: Floor dimensions: L=9.44[m]; W=4.30[m]; A=(9.44*4.30)[m2] = 40.592[m2]; Δx=0.20[m]; kconcrete= kconc=1.1[W/(mK)] The convective heat transfer coefficient is assumed to be a conventional value given in the book h=8.29[W/(m2K)] Heat lost to the floor: Rair near floor= Ranf= 1/(8.29[W/(m2K)]*40.592[m2])=0.00297[K/W] Rconduction floor= Rcf= 0.2[m]/(1.1[W/(mK)]* 40.592[m2])=0.00448[K/W] Rcarpet=0.367[(m2K)/W]* 40.592[m2]=14.897[K/W] Qfloor= -(ΔT /∑R) = -((5-17)[K] /(0.00297+0.00448+14.897)[K/W])=0.8051[W] The temperature of the floor is 17[oC]-0.8051[W]*0.00297[K/W]=16.998[oC] Simply by putting a carpet on the floor the amount of heat lost by the floor is 0.8051[W], which is almost two thousand times less than the original value 1’793.722[W]! The minimized total heat loss from the basement is the sum of all the losses: Qtotal=Qfloor+ Q1&3 + Q2 + Q4 + Qw1 +Qw2 =(0.8051+9.466+10.285+10.244+0.1+0.1)[W] Qtotal=31[W] As a conclusion the minimized heat losses for the basement (31[W]) is a small fraction of un-insulated basement (3’123.616[W]) in fact it is approximately only 1% of that value!

Page 16: Heat Transfer Project

16

1st floor Plan

Page 17: Heat Transfer Project

17

1st Floor Window Sill-Box Dimensions Width [m] Height [m] Length [m]

Window 1 0.87 1.7 0.22 Window 2 0.47 1.8 0.25 Window 3 0.88 1.71 0.24 Window 4 0.72 1.8 0.19 Window 5 0.72 1.8 0.16 Window 6 0.72 1.8 0.17 Window 7 0.88 1.7 0.17 Window 8 0.88 1.7 0.22

Window Parameters (Door windows included): Double-Pane, Double Glazing, one side Low-e Coated Windows, air filled, tightly sealed, vinyl framed, with metal spacer type. Thickness of space inside the window Δxair=0.010[m]; All windows are glass, therefore from Table 1-1 kglass= kg= 0.78[W/(mK)] Thickness of the glass of the window Δxw=0.0025[m]; All the windows on the first floor have full pane windows, that is, they do not have frame. The first floor wall is composed of bricks, the approximate coefficient of conduction for bricks is chosen from Table A5 to be equivalent to the coefficient of conduction of dense fired clay bricks or kwall= kw= 1.34[W/(mK)]. The total thickness of the wall is 0.44[m]. The bricks are 0.12[m] thick and there is an air gap of 0.10[m] in the inter-space of the masonry. There is also a 0.087[m] air space between the bricks and the inside 0.013[mm] blaster board The floor of the first floor is 0.03[m] thick and is made of hard wood. From Table A-5 kwood = 0.159 [W/(mK)]

1st floor Door Data Door Length

[m] Height

[m] Windows? Door Window

Dimensions Length

[m] Height

[m] 1 0.87 2.07 Yes 0.55 0.93 2 1.80 2.07 Yes 1.80 2.07 3 0.87 2.07 Yes 0.55 0.93

Page 18: Heat Transfer Project

18

1st Floor Heat Loss Analysis Assumptions: Steady state conditions are applicable under extreme conditions (i.e. the coldest and the hottest temperatures) in order for the optimization process to yield stable results regardless of transient effects spanning over a year. That is the analysis of heat conduction of a given house considers peace time conditions and no immediate threat, such as local power station anomaly, or extreme weather such as hurricane. Assume ideal and incompressible gas conditions. The convective heat transfer coefficient inside the house is taken to be the conventional value given in the book or hin= 8.29 [W/(m2K)]. Winter Conditions: Tout= -24.0 [oC] Wind direction 20 degrees from North, but assume that the wind blows in the direction parallel to the all the walls for the maximum heat transfer. Wind Speed =11[km/h]=3.056[m/s] The space between the bricks inside the wall is assumed to be at around 0[oC]. For the air space between the bricks: Tavg=0[oC] Therefore from Table A-15: ρ=1.292[kg/m3] kinterspace= kinter=0.02364[W/mK] α=1.818/105 [m2/s2] μ=1.729/105[kg/ms] ν=1.338/105[m2/s] Pr=0.7362 β=1/(273)[1/K]=0.00366[1/K] Also assume that due to the low temperature of the air between the bricks its conductive heat transfer coefficient prevails over the convective heat transfer coefficient. The space between the bricks and the plaster board is assumed to be at around 15[oC]. For the air space between the bricks and the plaster board: Tavg=15[oC] Therefore from Table A-15: ρ=1.225[kg/m3] kinterspace2= kinter2=0.02476[W/mK] α=2.009/105 [m2/s2] μ=1.802/105[kg/ms] ν=1.470/105[m2/s] Pr=0.7323 β=1/(273+15)[1/K]=0.0035[1/K]

Page 19: Heat Transfer Project

19

Also assume that due to the steady state conditions of the air between the bricks and the plaster board, its conductive heat transfer coefficient prevails over the convective heat transfer coefficient. Heat losses on the 1st floor during winter: Heat Loss by Wall 1: Wall dimensions: Lc=10[m]; H=2.85[m]; A=(10*2.85-(areas of the windows))[m2]= (28.5-(0.87*1.7+0.88*1.7))[m2] A= 25.525[m2]; Δx=0.44[m]; kbw=1.34[W/(mK)] From Table A-5 Rplaster=0.055[W/(m2 K)] Re=(V*L)/ν=(3.056*10)/(1.1362/105)=2’689’667.31>105 Hence the flow is turbulent Nu=0.0296*Re0.8Pr1/3=0.0296*(2’689’667.31)0.8(0.74148)1/3=3’730.3568 Nu=(h[W/(m2K)]*10[m])/0.021802[W/(mK)] hout= (3’730.3568*0.021802)/10 [W/(m2K)]= 8.1329[W/(m2K)] hin= 8.29 [W/(m2K)] Heat lost from one wall: Rout=1/(8.1329 [W/(m2K)]*25.525 [m2])=0.00482[K/W] Rin=1/( 8.29[W/(m2K)]* 25.525 [m2])=0.00473[K/W] Rbrick=0.12[m]/(1.34[W/(mK)]* 25.525 [m2])= 0.0035[K/W] Rinter=0.10[m]/(0.02364[W/mK]* 25.525 [m2])= 0.1657[K/W] Rinter2=0.087[m]/( 0.02476 [W/mK]* 25.525 [m2])=0.1377[K/W] Rplaster=1/( 0.055[W/(m2 K)]* 25.525 [m2])=0.7123[K/W] Qw1= (ΔT /∑R) = (19-(-24))[K] /(0.00482+0.00473+0.0035*2+0.1657+0.1377+0.7123)[K/W]) Qw1= 41.6566[W] The amount of heat lost by the wall is 41.6566[W]. Heat Loss by Wall 2: Wall dimensions: Lc=4.5[m]; H=2.85[m]; A=(4.5*2.85)[m2]= 12.825[m2] A= 12.825 [m2]; Δx=0.44[m]; kbw=1.34[W/(mK)] Re=(V*L)/ν=(3.056*4.5)/(1.1362/105)=1’210’350.29>105 Hence the flow is turbulent Nu=0.0296*Re0.8Pr1/3=0.0296*(1’210’350.29)0.8(0.74148)1/3=1’969.339 Nu=(h[W/(m2K)]*4.5[m])/0.021802[W/(mK)] hout= (1’969.339*0.021802)/4.5 [W/(m2K)]= 9.5412[W/(m2K)] hin= 8.29 [W/(m2K)]

Page 20: Heat Transfer Project

20

Heat lost from one wall: Rout=1/(9.5412 [W/(m2K)]*12.825 [m2])=0.00817[K/W] Rin=1/( 8.29[W/(m2K)]*12.825 [m2])=0.00941[K/W] Rbrick=0.12[m]/(1.34[W/(mK)]* 12.825[m2])= 0.007[K/W] Rinter=0.1[m]/(0.02364[W/mK]*12.825[m2])= 0.3298[K/W] Rinter2=0.087[m]/( 0.02476[W/mK]* 12.825[m2])=0.274 [K/W] Rplaster=1/( 0.055[W/(m2 K)]* 12.825[m2])=1.4177[K/W] Qw2= (ΔT /∑R) = (19-(-24))[K] /(0.00817+0.00941+0.007*2+0.3298+0.274+1.4177)[K/W]) Qw2=20.9441[W] The amount of heat lost by the wall is 20.9441[W]. Heat Loss by Wall 3: Wall dimensions: Lc=4.5[m]; H=2.85[m]; A=(4.5*2.85-(areas of the windows))[m2]= (12.825-(0.47*1.8))[m2] A= 11.979[m2]; Δx=0.44[m]; kbw=1.34[W/(mK)] Re=(V*L)/ν=(3.056*4.5)/(1.1362/105)=1’210’350.29>105 Hence the flow is turbulent Nu=0.0296*Re0.8Pr1/3=0.0296*(1’210’350.29)0.8(0.74148)1/3=1’969.339 Nu=(h[W/(m2K)]*4.5[m])/0.021802[W/(mK)] hout= (1’969.339*0.021802)/4.5 [W/(m2K)]= 9.5412 [W/(m2K)] hin= 8.29 [W/(m2K)] Heat lost from one wall: Rout=1/(9.5412 [W/(m2K)]*11.979[m2])=0.00875[K/W] Rin=1/( 8.29[W/(m2K)]* 11.979[m2])=0.01[K/W] Rbrick=0.12[m]/(1.34[W/(mK)]* 11.979[m2])=0.0075[K/W] Rinter=0.1[m]/(0.02364[W/mK]* 11.979[m2])= 0.3531[K/W] Rinter2=0.087[m]/(0.02476 [W/mK]* 11.979 [m2])= 0.2933[K/W] Rplaster=1/( 0.055[W/(m2 K)]* 11.979[m2])=1.5178[K/W] Qw3= (ΔT /∑R) = (19-(-24))[K] /(0.00875+0.01+0.0075*2+0.3531+0.2933+1.5178)[K/W]) Qw3= 19.5637[W] The amount of heat lost by the wall is 19.5637[W]. Heat Loss by Wall 4: Wall dimensions: Lc=4.22[m]; H=2.85[m]; A=(4.22*2.85-(areas of the windows))[m2] A= (12.027-(1.8*2.07))[m2] = 8.301[m2]; Δx=0.44[m]; kbw=1.34[W/(mK)] Re=(V*L)/ν=(3.056*4.22)/(1.1362/105)=1’135’039.61>105 Hence the flow is turbulent

Page 21: Heat Transfer Project

21

Nu=0.0296*Re0.8Pr1/3=0.0296*(1’135’039.61)0.8(0.74148)1/3=1’870.684 Nu=(h[W/(m2K)]*4.22[m])/0.021802[W/(mK)] hout= (1’870.684*0.021802)/4.22 [W/(m2K)]= 9.665[W/(m2K)] hin= 8.29 [W/(m2K)] Heat lost from one wall: Rout=1/(9.665[W/(m2K)]* 8.301[m2])=0.01246[K/W] Rin=1/( 8.29[W/(m2K)]* 8.301[m2])=0.0145[K/W] Rbrick=0.12[m]/(1.34[W/(mK)]*8.301[m2])= 0.0108[K/W] Rinter=0.1[m]/(0.02364[W/mK]* 8.301[m2])= 0.5096[K/W] Rinter2=0.087[m]/(0.02476 [W/mK]* 8.301 [m2])=0.4233[K/W] Rplaster=1/( 0.055[W/(m2 K)]* 8.301 [m2])=2.1903[K/W] Qw4= (ΔT /∑R) = (19-(-24))[K] /(0.01246+0.0145+0.0108*2+0.5096+0.4233+2.1903)[K/W]) Qw4= 13.5571[W] The amount of heat lost by the wall is 13.5571[W]. Heat Loss by Wall 5: Wall dimensions: Lc=7.05[m]; H=2.85[m]; A=(7.05*2.85-(areas of the windows))[m2]= (20.0925-(0.88*1.7))[m2] A= 18.5965[m2]; Δx=0.44[m]; kbw=1.34[W/(mK)] Re=(V*L)/ν=(3.056*7.05)/(1.1362/105)=1’896’215.455>105 Hence the flow is turbulent Nu=0.0296*Re0.8Pr1/3=0.0296*(1’896’215.455)0.8(0.74148)1/3=2’820.341 Nu=(h[W/(m2K)]*7.05[m])/0.021802[W/(mK)] hout= (2’820.341*0.021802)/7.05 [W/(m2K)]= 8.722[W/(m2K)] hin= 8.29 [W/(m2K)] Heat lost from one wall: Rout=1/(8.722[W/(m2K)]* 18.5965 [m2])= 0.00617[K/W] Rin=1/( 8.29[W/(m2K)]*18.5965 [m2])=0.00649[K/W] Rbrick=0.12[m]/(1.34[W/(mK)]* 18.5965 [m2])= 0.0048[K/W] Rinter=0.1[m]/(0.02364[W/mK]*18.5965 [m2])= 0.2275[K/W] Rinter2=0.087[m]/(0.02476[W/mK]* 18.5965[m2])=0.1889[K/W] Rplaster=1/( 0.055[W/(m2 K)]* 18.5965[m2])=0.9777[K/W] Qw5= (ΔT /∑R) = (19-(-24))[K] /(0.00617+0.00649+0.0048*2+0.2275+0.1889+0.9777)[K/W]) Qw5= 30.3595[W] The amount of heat lost by the wall is 30.3595[W].

Page 22: Heat Transfer Project

22

Heat Losses by Wall 6 and Wall 12: Wall dimensions: Lc=0.8605[m]; H=2.85[m]; A=(0.8605*2.85 [m2]= 2.452[m2]; Δx=0.44[m]; kbw=1.34[W/(mK)] Re=(V*L)/ν=(3.056*0.8605)/(1.1362/105)=231’445.872>105 Hence the flow is turbulent Nu=0.0296*Re0.8Pr1/3=0.0296*(231’445.872)0.8(0.74148)1/3=524.265 Nu=(h[W/(m2K)]* 0.8605 [m])/0.021802[W/(mK)] hout= (524.265*0.021802)/ 0.8605 [W/(m2K)]= 13.283[W/(m2K)] hin= 8.29 [W/(m2K)] Heat lost from one wall: Rout=1/(13.283[W/(m2K)]* 2.452[m2])= 0.0307[K/W] Rin=1/( 8.29[W/(m2K)]* 2.452[m2])=0.0492[K/W] Rbrick=0.12[m]/(1.34[W/(mK)]* 2.452[m2])=0.0365[K/W] Rinter=0.1[m]/(0.02364[W/mK]* 2.452[m2])=1.7252[K/W] Rinter2=0.087[m]/(0.02476[W/mK]* 2.452[m2])=1.433[K/W] Rplaster=1/( 0.055[W/(m2 K)]* 2.452[m2])=7.4151[K/W] Qw6= (ΔT /∑R) = (19-(-24))[K] /(0.0307+0.0492+0.0365*2+1.7252+1.433+7.4151)[K/W]) Qw6= 4.0089[W] Qw6 &w12=2* Qw6= 2*4.0089 [W]=8.0178[W] The amount of heat lost by two walls is 8.0178[W]. Heat Loss by Wall 7: Wall dimensions: Lc=0.55[m]; H=2.85[m]; A=(0.55*2.85 =1.5675[m2]; Δx=0.44[m]; kbw=1.34[W/(mK)] Re=(V*L)/ν=(3.056*0.55)/(1.1362/105)=147’931.702>105 Hence the flow is turbulent Nu=0.0296*Re0.8Pr1/3=0.0296*(147’931.702)0.8(0.74148)1/3=366.472 Nu=(h[W/(m2K)]* 0.55[m])/0.021802[W/(mK)] hout= (366.472*0.021802)/ 0.55[W/(m2K)]=14.527[W/(m2K)] hin= 8.29 [W/(m2K)] Heat lost from one wall: Rout=1/(14.527[W/(m2K)]* 1.5675[m2])=0.0439[K/W] Rin=1/( 8.29[W/(m2K)]* 1.5675[m2])=0.077[K/W] Rbrick=0.12[m]/(1.34[W/(mK)]* 1.5675[m2])= 0.0571[K/W] Rinter=0.1[m]/(0.02364[W/mK]* 1.5675[m2])=2.6986[K/W]

Page 23: Heat Transfer Project

23

Rinter2=0.087[m]/(0.02476[W/mK]* 1.5675[m2])=2.2416[K/W] Rplaster=1/( 0.055[W/(m2 K)]* 1.5675[m2])=11.5992 [K/W] Qw7= (ΔT /∑R) = (19-(-24))[K] /(0.0439+0.077+0.0571*2+2.6986+2.2416+11.5992)[K/W])=2.563[W] The amount of heat lost by the wall is 2.563[W]. Heat Loss by Wall 8: Wall dimensions: Lc=1.06[m]; H=2.85[m]; A=(1.06*2.85-(areas of the windows))[m2]= (3.021-(0.72*1.8))[m2] A =1.725[m2]; Δx=0.44[m]; kbw=1.34[W/(mK)] Re=(V*L)/ν=(3.056*1.06)/(1.1362/105)=285’104.735>105 Hence the flow is turbulent Nu=0.0296*Re0.8Pr1/3=0.0296*(285’104.735)0.8(0.74148)1/3=619.434 Nu=(h[W/(m2K)]*1.06 [m])/0.021802[W/(mK)] hout= (619.434*0.021802)/ 1.06[W/(m2K)]= 12.741[W/(m2K)] hin= 8.29 [W/(m2K)] Heat lost from one wall: Rout=1/(12.741[W/(m2K)]* 1.725[m2])=0.0455[K/W] Rin=1/( 8.29[W/(m2K)]* 1.725[m2])=0.07[K/W] Rbrick=0.12[m]/(1.34[W/(mK)]* 1.725[m2])=0.0519[K/W] Rinter=0.1[m]/(0.02364[W/mK]*1.725[m2])= 2.4522[K/W] Rinter2=0.087[m]/(0.02476 [W/mK]* 1.725[m2])= 2.0369[K/W] Rplaster=1/( 0.055[W/(m2 K)]* 1.725[m2])= 10.5402[K/W] Qw8= (ΔT /∑R) = (19-(-24))[K] /(0.0455+0.07+0.0519*2+2.4522+2.0369+10.5402)[K/W]) Qw8= 2.8199[W] The amount of heat lost by the wall is 2.8199[W]. Heat Loss by Wall 9: Wall dimensions: Lc=1.00[m]; H=2.85[m]; A=(1.00*2.85-(areas of the windows))[m2]= (2.85-(0.72*1.8))[m2] A= 1.554[m2]; Δx=0.44[m]; kbw=1.34[W/(mK)] Re=(V*L)/ν=(3.056*1.00)/(1.1362/105)=268’966.731>105 Hence the flow is turbulent Nu=0.0296*Re0.8Pr1/3=0.0296*(268’966.731)0.8(0.74148)1/3=591.222 Nu=(h[W/(m2K)]* 1.00 [m])/0.021802[W/(mK)] hout= (591.222*0.021802)/ 1.00[W/(m2K)]= 12.890[W/(m2K)] hin= 8.29 [W/(m2K)]

Page 24: Heat Transfer Project

24

Heat lost from one wall: Rout=1/(12.890 [W/(m2K)]* 1.554 [m2])=0.0499[K/W] Rin=1/( 8.29[W/(m2K)]* 1.554[m2])=0.0776[K/W] Rbrick=0.12[m]/(1.34[W/(mK)]* 1.554[m2])=0.0576[K/W] Rinter=0.1[m]/(0.02364[W/mK]*1.554[m2])=2.7221[K/W] Rinter2=0.087[m]/(0.02476[W/mK]* 1.554[m2])=2.2611[K/W] Rplaster=1/( 0.055[W/(m2 K)]* 1.554[m2])=11.7 [K/W] Qw9= (ΔT /∑R) = (19-(-24))[K] /(0.0499+0.0776+0.0576*2+2.7221+2.2611+11.7)[K/W]) Qw9= 2.5405[W] The amount of heat lost by the wall is 2.5405[W]. Heat Loss by Wall 10: Wall dimensions: Lc=1.06[m]; H=2.85[m]; A=(1.06*2.85-(areas of the windows))[m2]= (3.021-(0.72*1.8))[m2] A= 1.725[m2]; Δx=0.44[m]; kbw=1.34[W/(mK)] Re=(V*L)/ν=(3.056*1.06)/(1.1362/105)=285’104.735>105 Hence the flow is turbulent Nu=0.0296*Re0.8Pr1/3=0.0296*(285’104.735)0.8(0.74148)1/3=619.434 Nu=(h[W/(m2K)]* 1.06 [m])/0.021802[W/(mK)] hout= (619.434*0.021802)/1.06 [W/(m2K)]= 12.741[W/(m2K)] hin= 8.29 [W/(m2K)] Heat lost from one wall: Rout=1/(12.741[W/(m2K)]*1.725[m2])=0.0455[K/W] Rin=1/( 8.29[W/(m2K)]* 1.725[m2])=0.0699K/W] Rbrick=0.12[m]/(1.34[W/(mK)]*1.725[m2])=0.0519[K/W] Rinter=0.10[m]/(0.02364[W/mK]*1.725[m2])=2.4522[K/W] Rinter2=0.087[m]/(0.02476[W/mK]* 1.725[m2])=2.0369[K/W] Rplaster=1/( 0.055[W/(m2 K)]* 1.725[m2])= 10.5402[K/W] Qw10= (ΔT /∑R) = (19-(-24))[K] /(0.0455+0.0699+0.0519*2+2.4522+2.0369 +10.5402)[K/W]) Qw10=2.8199[W] The amount of heat lost by the wall is 2.8199[W]. Heat Loss by Wall 11: Wall dimensions: Lc=0.55[m]; H=2.85[m]; A=(0.55*2.85)[m2]=1.5675 [m2]; Δx=0.44[m]; kbw=1.34[W/(mK)] Re=(V*L)/ν=(3.056*0.55)/(1.1362/105)=147’931.702>105 Hence the flow is turbulent Nu=0.0296*Re0.8Pr1/3=0.0296*(147’931.702)0.8(0.74148)1/3=366.472

Page 25: Heat Transfer Project

25

Nu=(h[W/(m2K)]* 0.55 [m])/0.021802[W/(mK)] hout= (366.472*0.021802)/ 0.55 [W/(m2K)]= 14.527[W/(m2K)] hin= 8.29 [W/(m2K)] Heat lost from one wall: Rout=1/(14.527[W/(m2K)]*1.5675[m2])=0.0439[K/W] Rin=1/( 8.29[W/(m2K)]* 1.5675[m2])=0.07696[K/W] Rbrick=0.12[m]/(1.34[W/(mK)]* 1.5675[m2])=0.0571[K/W] Rinter=0.10[m]/(0.02364[W/mK]* 1.5675[m2])=2.6986[K/W] Rinter2=0.087[m]/(0.02476[W/mK]* 1.5675 [m2])=2.2416[K/W] Rplaster=1/( 0.055[W/(m2 K)]* 1.5675 [m2])=11.5992 [K/W] Qw11= (ΔT /∑R) = (19-(-24))[K] /(0.0439+0.07696+0.0571*2+2.6986+2.2416+11.5992)[K/W]) Qw11= 2.5634[W] The amount of heat lost by the wall is 2.5634[W]. Heat Loss by Wall 13: Wall dimensions: Lc=1.55[m]; H=2.85[m]; A=(1.55*2.85)[m2] =4.4175[m2]; Δx=0.44[m]; kbw=1.34[W/(mK)] Re=(V*L)/ν=(3.056*1.55)/(1.1362/105)=416’898.433>105 Hence the flow is turbulent Nu=0.0296*Re0.8Pr1/3=0.0296*(416’898.433)0.8(0.74148)1/3=839.490 Nu=(h[W/(m2K)]* 1.55 [m])/0.021802[W/(mK)] hout= (839.490*0.021802)/ 1.55[W/(m2K)]= 11.808[W/(m2K)] hin= 8.29 [W/(m2K)] Heat lost from one wall: Rout=1/(11.808[W/(m2K)]* 4.4175[m2])=0.0192[K/W] Rin=1/( 8.29[W/(m2K)]* 4.4175[m2])=0.0273[K/W] Rbrick=0.12[m]/(1.34[W/(mK)]* 4.4175[m2])=0.0203[K/W] Rinter=0.10[m]/(0.02364[W/mK]* 4.4175[m2])=0.9576[K/W] Rinter2=0.087[m]/(0.02476[W/mK]* 4.4175 [m2])=0.7954[K/W] Rplaster=1/( 0.055[W/(m2 K)]* 4.4175 [m2])=4.1159[K/W] Qw13= (ΔT /∑R) = (19-(-24))[K] /(0.0192+0.0273+0.0203*2+0.9576+0.7954+4.1159)[K/W]) Qw13=7.2196[W] The amount of heat lost by the wall is 7.2196[W].

Page 26: Heat Transfer Project

26

Heat Loss by Wall 14: Wall dimensions: Lc=4.5[m]; H=2.85[m]; A=( 4.5*2.85-(areas of the windows+ areas of the doors))[m2] A= (12.825-(0.88*1.7+0.87*2.07))[m2]=9.5281 [m2]; Δx=0.44[m]; kbw=1.34[W/(mK)] Re=(V*L)/ν=(3.056*4.5)/(1.1362/105)=1’210’350.29>105 Hence the flow is turbulent Nu=0.0296*Re0.8Pr1/3=0.0296*(1’210’350.29)0.8(0.74148)1/3=1’969.339 Nu=(h[W/(m2K)]* 4.5[m])/0.021802[W/(mK)] hout= (1’969.339*0.021802)/ 4.5[W/(m2K)]= 9.541[W/(m2K)] hin= 8.29 [W/(m2K)] Heat lost from one wall: Rout=1/(9.541[W/(m2K)]* 9.5281[m2])=0.011[K/W] Rin=1/( 8.29[W/(m2K)]* 9.5281[m2])=0.0127 [K/W] Rbrick=0.12[m]/(1.34[W/(mK)]* 9.5281[m2])=0.0094[K/W] Rinter=0.10[m]/(0.02364[W/mK]* 9.5281[m2])=0.444[K/W] Rinter2=0.087[m]/(0.02476[W/mK]* 9.5281[m2])=0.3688[K/W] Rplaster=1/( 0.055[W/(m2 K)]* 9.5281[m2])=1.9082[K/W] Qw14= (ΔT /∑R) = (19-(-24))[K] /(0.011+0.0127+0.0094*2+0.444+0.3688+1.9082)[K/W])=15.56[W] The amount of heat lost by the wall is 15.56[W]. The net heat loss by the walls of the 1st floor is about 170.185[W] Heat Losses by Window 1: Window Parameters: Double-Pane, Double Glazing, one side Low-e Coated Windows, air filled, tightly sealed, vinyl framed, with metal spacer type. L=0.87[m]; H=1.70[m]; A= 0.87*1.70 [m2] = 1.479[m2]; Thickness of space inside the window Δxair=0.010[m]; Thickness of the glass of the window Δxw=0.0025[m]; kglass= kg=0.78 [W/(mK)] In complement to the ending article of chapter 9, the convective heat transfer coefficient can be neglected if the air space thickness inside the windows is less than 0.013[m] and the conductive coefficient for air can be used instead. For such scenario the conductive coefficient is taken from Table A-15 to be 0.02364[W/(mK)] at 0 oC. The convective heat transfer coefficient inside the house is taken to be the conventional value given in the book or hin= 8.29 [W/(m2K)]. The outside convective heat transfer coefficient is assumed to be the same as the one calculated for the wall where window 1 is positioned (wall 1) hout = 8.1329[W/(m2K)] ; Tinside air= Tia = 19[oC]; Tout = -24[oC]

Page 27: Heat Transfer Project

27

Heat lost from the window: Rin=1/(8.29 [W/(m2K)]* 1.479[m2])= 0.08156[K/W] Rout=1/(8.1329 [W/(m2K)]* 1.479[m2])= 0.0831[K/W] Rg=0.0025[m]/(0.78[W/(mK)]* 1.479[m2])=0.00217[K/W] Rak=0.01[m]/(0.02364[W/(mK)]* 1.479[m2])=0.286[K/W] Qw1= (ΔT /∑R) = (19-(-24))[K] /(0.08156+0.0831+2*0.00217+0.286)[K/W])= 94.506[W] The amount of heat lost by this window is 94.506[W]. The average temperature of the indoors window 1 surface is: 19[oC]- 94.506 [W]*0.08156[K/W] = 11.2911[oC] Heat Losses by Window 2: Window Parameters: Double-Pane, Double Glazing, one side Low-e Coated Windows, air filled, tightly sealed, vinyl framed, with metal spacer type. L=0.47[m]; H=1.80[m]; A= 0.47*1.80[m2] =0.846[m2]; Thickness of space inside the window Δxair=0.010[m]; Thickness of the glass of the window Δxw=0.0025[m]; kglass= kg=0.78 [W/(mK)] In complement to the ending article of chapter 9, the convective heat transfer coefficient can be neglected if the air space thickness inside the windows is less than 0.013[m] and the conductive coefficient for air can be used instead. For such scenario the conductive coefficient is taken from Table A-15 to be 0.02364[W/(mK)] at 0 oC. The convective heat transfer coefficient inside the house is taken to be the conventional value given in the book or hin= 8.29 [W/(m2K)]. The outside convective heat transfer coefficient is assumed to be the same as the one calculated for the wall where window 2 is positioned (wall 3) hout = 9.665[W/(m2K)] ; Tinside air= Tia = 19[oC]; Tout = -24[oC] Heat lost from the window: Rin=1/(8.29 [W/(m2K)]* 0.846 [m2])= 0.143[K/W] Rout=1/(9.665[W/(m2K)]* 0.846 [m2])=0.122[K/W] Rg=0.0025[m]/(0.78[W/(mK)]*0.846 [m2])= 0.00379[K/W] Rak=0.01[m]/(0.02364[W/(mK)]* 0.846 [m2])= 0.5[K/W] Qw2= (ΔT /∑R) = (19-(-24))[K] /(0.143+0.122+2*0.00379+0.5)[K/W])= 55.658[W] The amount of heat lost by this window is 55.658[W]. The average temperature of the indoors window 2 surface is: 19[oC]- 97.36 [W]*0.143 [K/W] = 5.0775[oC]

Page 28: Heat Transfer Project

28

Heat Losses by Window 3: Window Parameters: Double-Pane, Double Glazing, one side Low-e Coated Windows, air filled, tightly sealed, vinyl framed, with metal spacer type. L=0.88[m]; H=1.71[m]; A= 0.88*1.71[m2] = 1.505[m2]; Thickness of space inside the window Δxair=0.010[m]; Thickness of the glass of the window Δxw=0.0025[m]; kglass= kg=0.78 [W/(mK)] In complement to the ending article of chapter 9, the convective heat transfer coefficient can be neglected if the air space thickness inside the windows is less than 0.013[m] and the conductive coefficient for air can be used instead. For such scenario the conductive coefficient is taken from Table A-15 to be 0.02364[W/(mK)] at 0 oC. The convective heat transfer coefficient inside the house is taken to be the conventional value given in the book or hin= 8.29 [W/(m2K)]. The outside convective heat transfer coefficient is assumed to be the same as the one calculated for the wall where window 3 is positioned (wall 5) hout = 8.722[W/(m2K)] ; Tinside air= Tia = 19[oC]; Tout = -24[oC] Heat lost from the window: Rin=1/(8.29 [W/(m2K)]* 1.505[m2])= 0.0802[K/W] Rout=1/(8.722 [W/(m2K)]* 1.505[m2])= 0.0762[K/W] Rg=0.0025[m]/(0.78[W/(mK)]* 1.505[m2])= 0.00213[K/W] Rak=0.01[m]/(0.02364[W/(mK)]* 1.505[m2])= 0.281[K/W] Qw3= (ΔT /∑R) = (19-(-24))[K] /(0.0802+0.0762+2*0.00213+0.281)[K/W])= 97.36[W] The amount of heat lost by this window is 97.36[W]. The average temperature of the indoors window 3 surface is: 19[oC]- 97.36 [W]*0.0802 [K/W] = 11.1917[oC] Heat Losses by Window 4: Window Parameters: Double-Pane, Double Glazing, one side Low-e Coated Windows, air filled, tightly sealed, vinyl framed, with metal spacer type. L=0.72[m]; H=1.80[m]; A= 0.72*1.80[m2] = 1.296[m2]; Thickness of space inside the window Δxair=0.010[m]; Thickness of the glass of the window Δxw=0.0025[m]; kglass= kg=0.78 [W/(mK)] In complement to the ending article of chapter 9, the convective heat transfer coefficient can be neglected if the air space thickness inside the windows is less than 0.013[m] and the conductive coefficient for air can be used instead. For such scenario the conductive coefficient is taken from Table A-15 to be 0.02364[W/(mK)] at 0 oC. The convective heat transfer coefficient inside the house is taken to be the conventional value given in the book or hin= 8.29 [W/(m2K)].

Page 29: Heat Transfer Project

29

The outside convective heat transfer coefficient is assumed to be the same as the one calculated for the wall where window 4 is positioned (wall 8) hout = 12.741[W/(m2K)] ; Tinside air= Tia = 19[oC]; Tout = -24[oC] Heat lost from the window: Rin=1/(8.29 [W/(m2K)]* 1.296[m2])= 0.0931[K/W] Rout=1/(12.741 [W/(m2K)]* 1.296[m2])=0.0606[K/W] Rg=0.0025[m]/(0.78[W/(mK)]* 1.296[m2])= 0.00247 [K/W] Rak=0.01[m]/(0.02364[W/(mK)]* 1.296 [m2])= 0.326[K/W] Qw5= (ΔT /∑R) = (19-(-24))[K] /(0.0931+0.0606+2*0.00247+0.326)[K/W])=88.726[W] The amount of heat lost by this window is 88.726[W]. The average temperature of the indoors window 4 surface is: 19[oC]- 88.726 [W]*0.0931 [K/W] = 10.7396[oC] Heat Losses by Window 5: Window Parameters: Double-Pane, Double Glazing, one side Low-e Coated Windows, air filled, tightly sealed, vinyl framed, with metal spacer type. L=0.72[m]; H=1.80[m]; A= 0.72*1.80[m2] = 1.296[m2]; Thickness of space inside the window Δxair=0.010[m]; Thickness of the glass of the window Δxw=0.0025[m]; kglass= kg=0.78 [W/(mK)] In complement to the ending article of chapter 9, the convective heat transfer coefficient can be neglected if the air space thickness inside the windows is less than 0.013[m] and the conductive coefficient for air can be used instead. For such scenario the conductive coefficient is taken from Table A-15 to be 0.02364[W/(mK)] at 0 oC. The convective heat transfer coefficient inside the house is taken to be the conventional value given in the book or hin= 8.29 [W/(m2K)]. The outside convective heat transfer coefficient is assumed to be the same as the one calculated for the wall where window 5 is positioned (wall 9) hout = 12.890[W/(m2K)] ; Tinside air= Tia = 19[oC]; Tout = -24[oC] Heat lost from the window: Rin=1/(8.29 [W/(m2K)]* 1.296 [m2])= 0.0931[K/W] Rout=1/(12.89 [W/(m2K)]* 1.296 [m2])= 0.0599[K/W] Rg=0.0025[m]/(0.78[W/(mK)]* 1.296 [m2])=0.00247 [K/W] Rak=0.01[m]/(0.02364[W/(mK)]* 1.296 [m2])= 0.326[K/W] Qw5= (ΔT /∑R) = (19-(-24))[K] /(0.0931+0.0599+2*0.00247+0.326)[K/W])=88.854[W] The amount of heat lost by this window is 88.854[W]. The average temperature of the indoors window 5 surface is: 19[oC]- 88.854 [W]*0.0931 [K/W] = 10.7277[oC]

Page 30: Heat Transfer Project

30

Heat Losses by Window 6: Window Parameters: Double-Pane, Double Glazing, one side Low-e Coated Windows, air filled, tightly sealed, vinyl framed, with metal spacer type. L=0.72[m]; H=1.80[m]; A= 0.72*1.80[m2] = 1.296[m2]; Thickness of space inside the window Δxair=0.010[m]; Thickness of the glass of the window Δxw=0.0025[m]; kglass= kg=0.78 [W/(mK)] In complement to the ending article of chapter 9, the convective heat transfer coefficient can be neglected if the air space thickness inside the windows is less than 0.013[m] and the conductive coefficient for air can be used instead. For such scenario the conductive coefficient is taken from Table A-15 to be 0.02364[W/(mK)] at 0 oC. The convective heat transfer coefficient inside the house is taken to be the conventional value given in the book or hin= 8.29 [W/(m2K)]. The outside convective heat transfer coefficient is assumed to be the same as the one calculated for the wall where window 6 is positioned (wall 10) hout = 12.741[W/(m2K)] ; Tinside air= Tia = 19[oC]; Tout = -24[oC] Heat lost from the window: Rin=1/(8.29 [W/(m2K)]* 1.296[m2])= 0.0931[K/W] Rout=1/(12.741 [W/(m2K)]* 1.296[m2])= 0.0606[K/W] Rg=0.0025[m]/(0.78[W/(mK)]* 1.296[m2])= 0.00247[K/W] Rak=0.01[m]/(0.02364[W/(mK)]* 1.296[m2])= 0.326[K/W] Qw6= (ΔT /∑R) = (19-(-24))[K] /(0.0931+0.0606+2*0.00247+0.326)[K/W])= 88.726[W] The amount of heat lost by this window is 88.726[W]. The average temperature of the indoors window 6 surface is: 19[oC]- 88.726 [W]*0.0931 [K/W] = 10.7396 [oC] Heat Losses by Window 7: Window Parameters: Double-Pane, Double Glazing, one side Low-e Coated Windows, air filled, tightly sealed, vinyl framed, with metal spacer type. L=0.88[m]; H=1.70[m]; A= 0.88*1.70 [m2] =1.496[m2]; Thickness of space inside the window Δxair=0.010[m]; Thickness of the glass of the window Δxw=0.0025[m]; kglass= kg=0.78 [W/(mK)] In complement to the ending article of chapter 9, the convective heat transfer coefficient can be neglected if the air space thickness inside the windows is less than 0.013[m] and the conductive coefficient for air can be used instead. For such scenario the conductive coefficient is taken from Table A-15 to be 0.02364[W/(mK)] at 0 oC. The convective heat transfer coefficient inside the house is taken to be the conventional value given in the book or hin= 8.29 [W/(m2K)].

Page 31: Heat Transfer Project

31

The outside convective heat transfer coefficient is assumed to be the same as the one calculated for the wall where window 7 is positioned (wall 14) hout = 9.541[W/(m2K)] ; Tinside air= Tia = 19[oC]; Tout = -24[oC] Heat lost from the window: Rin=1/(8.29 [W/(m2K)]*1.496 [m2])= 0.0806[K/W] Rout=1/(9.541 [W/(m2K)]*1.496 [m2])=0.07[K/W] Rg=0.0025[m]/(0.78[W/(mK)]* 1.496[m2])= 0.00214[K/W] Rak=0.01[m]/(0.02364[W/(mK)]*1.496[m2])= 0.283[K/W] Qw7= (ΔT /∑R) = (19-(-24))[K] /(0.0806+0.07+2*0.00214+0.283)[K/W])= 98.2[W] The amount of heat lost by this window is 98.2[W]. The average temperature of the indoors window 7 surface is: 19[oC]- 98.2[W]*0.0806 [K/W] = 11.0851[oC] Heat Losses by Window 8: Window Parameters: Double-Pane, Double Glazing, one side Low-e Coated Windows, air filled, tightly sealed, vinyl framed, with metal spacer type. L=0.88[m]; H=1.70[m]; A= 0.88*1.70 [m2] =1.496[m2]; Thickness of space inside the window Δxair=0.010[m]; Thickness of the glass of the window Δxw=0.0025[m]; kglass= kg=0.78 [W/(mK)] In complement to the ending article of chapter 9, the convective heat transfer coefficient can be neglected if the air space thickness inside the windows is less than 0.013[m] and the conductive coefficient for air can be used instead. For such scenario the conductive coefficient is taken from Table A-15 to be 0.02364[W/(mK)] at 0 oC. The convective heat transfer coefficient inside the house is taken to be the conventional value given in the book or hin= 8.29 [W/(m2K)]. The outside convective heat transfer coefficient is assumed to be the same as the one calculated for the wall where window 8 is positioned (wall 1) hout = 8.1329[W/(m2K)] ; Tinside air= Tia = 19[oC]; Tout = -24[oC] Heat lost from the window: Rin=1/(8.29 [W/(m2K)]*1.496[m2])= 0.0806[K/W] Rout=1/(8.1329 [W/(m2K)]*1.496[m2])= 0.0822[K/W] Rg=0.0025[m]/(0.78[W/(mK)]* 1.496 [m2])= 0.00214[K/W] Rak=0.01[m]/(0.02364[W/(mK)]* 1.496 [m2])= 0.283[K/W] Qw8= (ΔT /∑R) = (19-(-24))[K] /(0.0806+0.0822+2*0.00214+0.283)[K/W])=95.539[W] The amount of heat lost by this window is 95.539[W]. The average temperature of the indoors window 8 surface is: 19[oC]- 95.539 [W]*0.0806 [K/W] = 11.2996[oC]

Page 32: Heat Transfer Project

32

Heat Losses by Doors 1 & 3: Door Dimensions Ld1=0.87[m]; Hd1=2.07[m]; A d1= (0.87*2.07)-(area of the window) [m2] =1.801-0.5115=1.2895[m2]; Δxd=0.045[m] The door is made from hardwood, therefore, from table A-15 kdoor=0.159[W/(mK)] Heat lost from the door: Rin=1/(8.29 [W/(m2K)]* 1.2895[m2])=0.0935 [K/W] Rout=1/(9.665 [W/(m2K)]* 1.2895[m2])= 0.0802[K/W] Rd=0.045[m]/(0.78[W/(mK)]* 1.2895[m2])= 0.00361[K/W] Qd1= (ΔT /∑R) = (19-(-24))[K] /(0.0935+0.0802+0.00361)[K/W])=242.513[W] Door Window Parameters: Double-Pane, Double Glazing, one side Low-e Coated Windows, air filled, tightly sealed, vinyl framed, with metal spacer type. Lwd1=0.55[m]; Hwd1=0.93[m]; A wd1= 0.55*0.93[m2] = 0.5115[m2]; Thickness of space inside the window Δxair=0.010[m]; Thickness of the glass of the window Δxw=0.0025[m]; kglass= kg=0.78 [W/(mK)] In complement to the ending article of chapter 9, the convective heat transfer coefficient can be neglected if the air space thickness inside the windows is less than 0.013[m] and the conductive coefficient for air can be used instead. For such scenario the conductive coefficient is taken from Table A-15 to be 0.02364[W/(mK)] at 0 oC. The convective heat transfer coefficient inside the house is taken to be the conventional value given in the book or hin= 8.29 [W/(m2K)]. The outside convective heat transfer coefficient is assumed to be the same as the one calculated for the wall where door 1 is positioned (wall 3) and it can also be assumed to approximate the convective heat transfer coefficient of wall 14 (the value is fairly close to 9.541[W/(m2K)] ) hout = 9.665[W/(m2K)] ; Tinside air= Tia = 19[oC]; Tout = -24[oC] Heat lost from the door’s window: Rin=1/(8.29 [W/(m2K)]* 0.5115 [m2])=0.236[K/W] Rout=1/(9.665 [W/(m2K)]* 0.5115 [m2])= 0.202[K/W] Rg=0.0025[m]/(0.78[W/(mK)]* 0.5115 [m2])= 0.00627[K/W] Rak=0.01[m]/(0.02364[W/(mK)]* 0.5115[m2])= 0.827[K/W] Qwd1= (ΔT /∑R) = (19-(-24))[K] /(0.236+ 0.202+2*0.00627+0.827)[K/W])= 33.658[W] Qnetdoor1= Qwd1+ Qd1=(242.513+33.658)[W]=276.171[W] Qtotaldoors= 2*Q netdoor1=2*276.171[W]=552.343[W] The net amount of heat lost by these doors is 552.343[W].

Page 33: Heat Transfer Project

33

Heat Losses by Door 2: Door Dimensions The door is a sliding glass type door (or French-door) or a Double Door. This door has Double Glazing, one side Low-e Coated Windows, air filled, tightly sealed, vinyl framed, frame width is 0.088[m], with metal spacer type. Lwd1=1.80[m]; Hwd1=2.07[m]; A wd1= 1.80*2.07[m2] =3.726[m2]; Thickness of space inside the window Δxair=0.0064[m]; From Table 9-6: The U-factor for such configuration is given as U=2.59[W/(mK)] The convective heat transfer coefficient inside the house is taken to be the conventional value given in the book or hin= 8.29 [W/(m2K)]. The outside convective heat transfer coefficient is assumed to be the same as the one calculated for the wall where door 2 is positioned (wall 4) hout = 9.665[W/(m2K)] ; Tinside air= Tia = 19[oC]; Tout = -24[oC] Heat lost from the door: Rin=1/(8.29 [W/(m2K)]* 3.726[m2])=0.0324[K/W] Rout=1/(9.665 [W/(m2K)]* 3.726[m2])= 0.0278[K/W] RU=1/(2.59[W/(m2K)]* 3.726[m2])= 0.1036[K/W] Qwd2= (ΔT /∑R) = (19-(-24))[K] /(0.0324+0.0278+0.1036)[K/W])= 262.515[W] The net amount of heat lost by this door is 262.515[W]. Heat Losses by the Floor of the 1st floor: Floor dimensions: L=10 and 7.05 and 2.499 and 1.7495[m]; W=4.5 and 4.22 and 0.55 and 0.7495 [m]; A=(10*4.5+7.05*4.22+2.499*0.55+1.7495*0.7495)[m2] = 77.312[m2]; Δx=0.03[m]; From Table A-5 khardwood=0.159[W/(mK)] The convective heat transfer coefficient inside the house is taken to be the conventional value given in the book or hin= 8.29 [W/(m2K)]. Heat lost to the floor: Rair near floor= Ranf= 1/(8.29[W/(m2K)]*77.312[m2])= 0.00156[K/W] Rconduction floor= Rcf= 0.03[m]/(0.159[W/(mK)]*77.312 [m2])= 0.00244[K/W] Rbasement air = Rba= 1/(11.167 [W/(m2K)]*77.312[m2])= 0.00116[K/W] Qfloor= -(ΔT /∑R) = ((19-17)[K] /( 0.00156+0.00244+0.00116)[K/W])= 387.599[W] The amount of heat lost by the floor is 387.599[W].

Page 34: Heat Transfer Project

34

Heat Losses by the Floor of the 1st floor: Floor dimensions: L=10 and 7.05 and 2.499 and 1.7495[m]; W=4.5 and 4.22 and 0.55 and 0.7495 [m]; A=(10*4.5+7.05*4.22+2.499*0.55+1.7495*0.7495)[m2] = 77.312[m2]; Δx=0.03[m]; From Table A-5 khardwood=0.159[W/(mK)] The convective heat transfer coefficient inside the house is taken to be the conventional value given in the book or hin= 8.29 [W/(m2K)]. Heat lost to the floor: Rair near floor= Ranf= 1/(8.29[W/(m2K)]*77.312[m2])= 0.00156[K/W] Rconduction floor= Rcf= 0.03[m]/(0.159[W/(mK)]*77.312 [m2])= 0.00244[K/W] Rbasement air = Rba= 1/(11.167 [W/(m2K)]*77.312[m2])= 0.00116[K/W] Qfloor= -(ΔT /∑R) = ((19-17)[K] /( 0.00156+0.00244+0.00116)[K/W])= 387.599[W] The total heat loss from the 1st floor is the sum of all the losses: Qtotal= (170.185+94.506+55.658+97.36+88.726+88.854+88.726+98.2+95.539+552.343 +262.515 +387.599)[W]=2080.2[W] Minimizing 1st Floor Heat Losses: The heat losses by the walls are fairly small and any further implementing of insulation may create an uncanny look of the house, and if the air spaces are filled the house may actually loose heat more than without fillings. Hence, the losses through the windows, the floor and the ceiling can be altered to reduce the heat losses. The heat losses by the windows can be minimized by covering the window sill boxes with a transparent PLA film (Poly-Lactic Acid is biodegradable and is made from corn starch [3]) (From Table A-5 an approximate value can be found similar to the R-value of vapor-permeable felt, that is RPLA=0.011[(m2K)/W]) and an isolated space of air. Assume that the PLA film is at the same temperature as the 1st floor air or 19[oC]. The gravitational acceleration is approximately g=9.81[m/s2]. Take the average temperature of the air inside the isolated sill space. Since in the previous calculations for the first floor window yielded a result at around 10[oC] for most of the windows (except for window 2 in its case the inside surface temperature was closer to 5[oC]). The average temperature for most windows would most likely be around (19+11)/2[oC] or 15[oC] and for window 2 the average temperature is around (19+5)/2[oC] or closer to 10[oC].

Page 35: Heat Transfer Project

35

For most windows: Tavg=15[oC] Therefore from Table A-15: ρ=1.225[kg/m3] k=0.02476[W/mK] α=2.009/105 [m2/s2] μ=1.802/105[kg/ms] ν=1.470/105[m2/s] Pr=0.7323 β=1/(273+15)[1/K]=0.00347[1/K] Heat Losses by Window 1: The characteristic length is the length of the isolated air space or Lc=0.22[m] T1stair= T1s1 = TPLA= 19[oC]; Tout = -24[oC], Tindoor window surface= Tiws=11[oC] Rayleigh value for the isolated window sill space: RaL=(g*β*(TPLA-Tiws)* Lc

3*Pr)/(ν)= (9.81*0.00347*(19-11)*(0.22)3*0.7323)/(1.470/105)=144.4535 The aspect ratio geometry is H/Lc =1.7/0.22= 7.727 The Nusselt number can be found by Catton-Berkovsky-Polevikov equation (equation 9-53 in the reference book) Nu=0.22((Pr* RaL)/(0.2+Pr))0.28*(H/L)-1/4=0.22((0.7323*144.4535)/(0.2+0.7323))0.28*(7.727)-1/4 Nu=0.4963 Q’=k*Nu*A*(TPLA-Tiws)/Lc =0.02476[W/(mK)]* 0.4963*1.479[m2]*(19-11)[oC]/0.22[m]=0.661[W] Because the approximation is fairly crude take a loss of 1[W] as a more compatible value. The amount of heat lost by sill isolated window is about 1[W] which is much less than the value of 94.506 [W] that was calculated without the thin PLA membrane. In fact if the dimensions and parameters for the windows 3 through 8 are compared with window 1 then it will be noticed that in most cases the heat lost as a result of installing a PLA film over the window sill would be around 1[W].

Width [m] Height [m] Length [m] Window 1 0.87 1.7 0.22 Window 3 0.88 1.71 0.24 Window 4 0.72 1.8 0.19 Window 5 0.72 1.8 0.16 Window 6 0.72 1.8 0.17 Window 7 0.88 1.7 0.17 Window 8 0.88 1.7 0.22

Hence, take a rough value of 1[W] of heat lost through all the listed windows as a result of PLA use.

Page 36: Heat Transfer Project

36

For window 2: Tavg=10[oC] Therefore from Table A-15: ρ=1.246[kg/m3] k=0.02439[W/mK] α=1.944/105 [m2/s2] μ=1.778/105[kg/ms] ν=1.426/105[m2/s] Pr=0.7336 β=1/(273+10)[1/K]=0.0035[1/K] Heat Losses by Window 2: The characteristic length is the length of the isolated air space or Lc=0.25[m] Tbasement air= Tba = TPLA= 19[oC]; Tout = -24[oC], Tindoor window surface= Tiws= 5[oC] Rayleigh value for the isolated window sill space: RaL=(g*β*(TPLA-Tiws)* Lc

3*Pr)/(ν)= (9.81*0.0035*(19-5)*(0.25)3*0.7336)/(1.426/105)=386.3891 The aspect ratio geometry is H/Lc =1.8/0.25=7.2 The Nusselt number can be found by Catton-Berkovsky-Polevikov equation (equation 9-53 in the reference book) Nu=0.22((Pr* RaL)/(0.2+Pr))0.28*(H/L)-1/4=0.22((0.7336*386.3891)/(0.2+0.7336))0.28*(7.2)-1/4 Nu=0.6655 Q’=k*Nu*A*(TPLA-Tiws)/Lc =0.02439[W/(mK)]* 0.6655*0.846[m2]*(19-5)[oC]/0.25[m]=0.7690[W] Because the approximation is fairly crude take a loss of 1[W] as a more compatible value. The amount of heat lost by sill isolated window is about 1[W] which is much less than the value of 55.658 [W] that was calculated without the thin PLA membrane. To prevent the heat losses through the floor a carpet and fibrous pad can be applied, from Table A-15 Rcarpet=0.367[(m2K)/W] Heat Losses by the Floor of the 1st floor: Floor dimensions: L=10 and 7.05 and 2.499 and 1.7495[m]; W=4.5 and 4.22 and 0.55 and 0.7495 [m]; A=(10*4.5+7.05*4.22+2.499*0.55+1.7495*0.7495)[m2] = 77.312[m2]; Δx=0.03[m]; From Table A-5 khardwood=0.159[W/(mK)] The convective heat transfer coefficient inside the house is taken to be the conventional value given in the book or hin= 8.29 [W/(m2K)]. Heat lost to the floor: Rair near floor= Ranf= 1/(8.29[W/(m2K)]*77.312[m2])= 0.00156[K/W] Rconduction floor= Rcf= 0.03[m]/(0.159[W/(mK)]*77.312 [m2])= 0.00244[K/W]

Page 37: Heat Transfer Project

37

Rbasement air = Rba= 1/(11.167 [W/(m2K)]*77.312[m2])= 0.00116[K/W] Rcarpet=0.367[(m2K)/W]*77.312 [m2]= 28.3735[K/W] Qfloor= -(ΔT /∑R) = ((19-17)[K] /( 0.00156+0.00244+0.00116+28.3735)[K/W])= 0.0705 [W] Simply by putting a full carpet over the floor the amount of heat lost by the floor is now 0.0705[W]. The minimized total heat loss from the basement is the sum of all the losses: The total heat loss from the 1st floor is the sum of all the losses: Qtotal= (170.185+1+1+1+1+1+1+1+1+552.343 +262.515 +0.0705)[W]=993.1135[W] Qtotal= (170.185+94.506+55.658+97.36+88.726+88.854+88.726+98.2+95.539+552.343 +262.515 +387.599)[W]=2080.2[W] As a conclusion the minimized heat losses for the first floor (993.1135 [W]) almost a half less than the original value (2080.2 [W]) in fact it is only about 47.7% of that value!

Page 38: Heat Transfer Project

38

2nd floor Plan

2nd Floor Window Sill-Box Dimensions Width [m] Height [m] Length [m]

Window 1 0.82 1.57 0.29 Window 2 0.82 1.57 0.22 Window 3 0.47 1.40 0.24 Window 4 0.47 1.40 0.24 Window 5 0.82 1.44 0.26 Window 6 0.47 1.40 0.23 Window 7 0.47 1.40 0.22

Page 39: Heat Transfer Project

39

Window Parameters: Double-Pane, Double Glazing, one side Low-e Coated Windows, air filled, tightly sealed, vinyl framed, with metal spacer type. Thickness of space inside the window Δxair=0.010[m]; All windows are glass, therefore from Table 1-1 kglass= kg= 0.78[W/(mK)] Thickness of the glass of the window Δxw=0.0025[m]; All the windows on the second floor have a 0.041[m] thick frame. The window overall U-factoe is therefore: 3.26+(2.88-3.26)*(10-6.4)/(12.7-6.4)[W/(m2K)]= 3.043[W/(m2K)]

The floor of the second floor is 0.343[m] thick. 0.03[m] is made of hard wood, 0.013[m] is plaster board and there is an air gap of 0.3[m] between them. The wood and the plaster board are separated by a 0.04[m] by 0.2[m] hardwood board. From Table A-5 kwood = 0.159 [W/(mK)], Rplaster board= Rpb=0.055[(m2K)/W] The air inside the floor is taken to be at a temperature of about 20[oC] The ceiling and the roof of the second floor is 0.313[m] thick. 0.3[m] is made of mostly mineral fiber, 0.013[m]. From Table A-5 Rplaster board= Rpb=0.055[(m2K)/W], Rmineralfiber =3.32[W/(m2K)] The convective heat transfer coefficient inside the house is taken to be the conventional value given in the book or hin= 8.29 [W/(m2K)].The convective heat transfer coefficient outside the house and near the ventilated roof is taken to be the conventional value given in the book for winter conditions or hout= 34 [W/(m2K)]. The temperature of the roof is assumed to be close to -20[oC] on that day. 2nd Floor Heat Loss Analysis Assumptions: Steady state conditions are applicable under extreme conditions (i.e. the coldest and the hottest temperatures) in order for the optimization process to yield stable results regardless of transient effects spanning over a year. That is the analysis of heat conduction of a given house considers peace time conditions and no immediate threat, such as local power station anomaly, or extreme weather such as hurricane. Assume ideal and incompressible gas conditions. The convective heat transfer coefficient inside the house is taken to be the conventional value given in the book or hin= 8.29 [W/(m2K)]. Winter Conditions: Tout= -24.0 [oC] Wind direction 20 degrees from North, but assume that the wind blows in the direction parallel to the all the walls for the maximum heat transfer. Wind Speed =11[km/h]=3.056[m/s] The space between the bricks inside the wall is assumed to be at around 0[oC].

Page 40: Heat Transfer Project

40

For the air space between the bricks: Tavg=0[oC] Therefore from Table A-15: ρ=1.292[kg/m3] kinterspace= kinter=0.02364[W/mK] α=1.818/105 [m2/s2] μ=1.729/105[kg/ms] ν=1.338/105[m2/s] Pr=0.7362 β=1/(273)[1/K]=0.00366[1/K] Also assume that due to the low temperature of the air between the bricks its conductive heat transfer coefficient prevails over the convective heat transfer coefficient. The space between the bricks and the plaster board is assumed to be at around 15[oC]. For the air space between the bricks and the plaster board: Tavg=15[oC] Therefore from Table A-15: ρ=1.225[kg/m3] kinterspace2= kinter2=0.02476[W/mK] α=2.009/105 [m2/s2] μ=1.802/105[kg/ms] ν=1.470/105[m2/s] Pr=0.7323 β=1/(273+15)[1/K]=0.0035[1/K] Also assume that due to the steady state conditions of the air between the bricks and the plaster board, its conductive heat transfer coefficient prevails over the convective heat transfer coefficient. Heat losses on the 2nd floor during winter: Heat Loss by Wall 1: Wall dimensions: Lc=10[m]; H=2.85[m]; A=(10*2.85-(areas of the windows))[m2]= (28.5-(0.47*1.4*2))[m2] A= 27.184[m2]; Δx=0.44[m]; kbw=1.34[W/(mK)] From Table A-5 Rplaster=0.055[W/(m2 K)] Re=(V*L)/ν=(3.056*10)/(1.1362/105)=2’689’667.31>105 Hence the flow is turbulent Nu=0.0296*Re0.8Pr1/3=0.0296*(2’689’667.31)0.8(0.74148)1/3=3’730.3568 Nu=(h[W/(m2K)]*10[m])/0.021802[W/(mK)] hout= (3’730.3568*0.021802)/10 [W/(m2K)]= 8.1329[W/(m2K)] hin= 8.29 [W/(m2K)]

Page 41: Heat Transfer Project

41

Heat lost from one wall: Rout=1/(8.1329 [W/(m2K)]*27.184[m2])=0.0045[K/W] Rin=1/( 8.29[W/(m2K)]* 27.184[m2])=0.0044[K/W] Rbrick=0.12[m]/(1.34[W/(mK)]* 27.184[m2])=0.0033[K/W] Rinter=0.10[m]/(0.02364[W/mK]* 27.184[m2])=0.1556[K/W] Rinter2=0.087[m]/( 0.02476 [W/mK]* 27.184[m2])=0.1293[K/W] Rplaster=1/( 0.055[W/(m2 K)]* 27.184[m2])=0.6688[K/W] Qw1= (ΔT /∑R) = (21-(-24))[K] /(0.0045+0.0044+0.0033*2+0.1556+0.1293+0.6688)[K/W]) Qw1= 46.43[W] The amount of heat lost by the wall is 46.43[W]. Heat Loss by Wall 2: Wall dimensions: Lc=4.5[m]; H=2.85[m]; A=(4.5*2.85)-(0.82*1.57)[m2]= 11.5376[m2] Δx=0.44[m]; kbw=1.34[W/(mK)] Re=(V*L)/ν=(3.056*4.5)/(1.1362/105)=1’210’350.29>105 Hence the flow is turbulent Nu=0.0296*Re0.8Pr1/3=0.0296*(1’210’350.29)0.8(0.74148)1/3=1’969.339 Nu=(h[W/(m2K)]*4.5[m])/0.021802[W/(mK)] hout= (1’969.339*0.021802)/4.5 [W/(m2K)]= 9.5412[W/(m2K)] hin= 8.29 [W/(m2K)] Heat lost from one wall: Rout=1/(9.5412 [W/(m2K)]* 11.5376[m2])=0.0091[K/W] Rin=1/( 8.29[W/(m2K)]* 11.5376[m2])=0.105[K/W] Rbrick=0.12[m]/(1.34[W/(mK)]* 11.5376[m2])=0.0078[K/W] Rinter=0.1[m]/(0.02364[W/mK]* 11.5376[m2])=0.3666[K/W] Rinter2=0.087[m]/( 0.02476[W/mK]* 11.5376[m2])=0.3045[K/W] Rplaster=1/( 0.055[W/(m2 K)]* 11.5376[m2])=1.5759[K/W] Qw2= (ΔT /∑R) = (21-(-24))[K] /(0.0091+0.105+0.0078*2+0.3666+0.3045+1.5759)[K/W]) Qw2=18.934[W] The amount of heat lost by the wall is 18.934[W].

Page 42: Heat Transfer Project

42

Heat Loss by Wall 3: Wall dimensions: Lc=4.5[m]; H=2.85[m]; A=(4.5*2.85) [m2]= 12.825[m2] Δx=0.44[m]; kbw=1.34[W/(mK)] Re=(V*L)/ν=(3.056*4.5)/(1.1362/105)=1’210’350.29>105 Hence the flow is turbulent Nu=0.0296*Re0.8Pr1/3=0.0296*(1’210’350.29)0.8(0.74148)1/3=1’969.339 Nu=(h[W/(m2K)]*4.5[m])/0.021802[W/(mK)] hout= (1’969.339*0.021802)/4.5 [W/(m2K)]= 9.5412 [W/(m2K)] hin= 8.29 [W/(m2K)] Heat lost from one wall: Rout=1/(9.5412 [W/(m2K)]* 12.825[m2])=0.0082[K/W] Rin=1/( 8.29[W/(m2K)]* 12.825[m2])=0.0094[K/W] Rbrick=0.12[m]/(1.34[W/(mK)]* 12.825[m2])=0.007[K/W] Rinter=0.1[m]/(0.02364[W/mK]* 12.825[m2])=0.3298[K/W] Rinter2=0.087[m]/(0.02476 [W/mK]* 12.825[m2])=0.274[K/W] Rplaster=1/( 0.055[W/(m2 K)]* 12.825[m2])=1.4177 [K/W] Qw3= (ΔT /∑R) = (21-(-24))[K] /(0.0082+0.0094+0.007*2+0.3298+0.274+1.4177)[K/W]) Qw3= 21.9181[W] The amount of heat lost by the wall is 21.9181[W]. Heat Loss by Wall 4: Wall dimensions: Lc=4.22[m]; H=2.85[m]; A=(4.22*2.85-(areas of the windows))[m2] A= (12.027-(1.57*0.82))[m2] = 10.7396[m2]; Δx=0.44[m]; kbw=1.34[W/(mK)] Re=(V*L)/ν=(3.056*4.22)/(1.1362/105)=1’135’039.61>105 Hence the flow is turbulent Nu=0.0296*Re0.8Pr1/3=0.0296*(1’135’039.61)0.8(0.74148)1/3=1’870.684 Nu=(h[W/(m2K)]*4.22[m])/0.021802[W/(mK)] hout= (1’870.684*0.021802)/4.22 [W/(m2K)]= 9.665[W/(m2K)] hin= 8.29 [W/(m2K)] Heat lost from one wall: Rout=1/(9.665[W/(m2K)]* 10.7396[m2])=0.0096[K/W] Rin=1/( 8.29[W/(m2K)]* 10.7396[m2])=0.0112[K/W]

Page 43: Heat Transfer Project

43

Rbrick=0.12[m]/(1.34[W/(mK)]* 10.7396[m2])=0.0083[K/W] Rinter=0.1[m]/(0.02364[W/mK]* 10.7396[m2])=0.3939[K/W] Rinter2=0.087[m]/(0.02476 [W/mK]* 10.7396[m2])=0.3272[K/W] Rplaster=1/( 0.055[W/(m2 K)]* 10.7396[m2])=1.693[K/W] Qw4= (ΔT /∑R) = (21-(-24))[K] /(0.0096+0.0112+0.0083*2+0.3939+0.3272+1.693)[K/W]) Qw4= 18.3561[W] The amount of heat lost by the wall is 18.3561[W]. Heat Loss by Wall 5: Wall dimensions: Lc=7.05[m]; H=2.85[m]; A=(7.05*2.85)[m2]= 20.0925 [m2] Δx=0.44[m]; kbw=1.34[W/(mK)] Re=(V*L)/ν=(3.056*7.05)/(1.1362/105)=1’896’215.455>105 Hence the flow is turbulent Nu=0.0296*Re0.8Pr1/3=0.0296*(1’896’215.455)0.8(0.74148)1/3=2’820.341 Nu=(h[W/(m2K)]*7.05[m])/0.021802[W/(mK)] hout= (2’820.341*0.021802)/7.05 [W/(m2K)]= 8.722[W/(m2K)] hin= 8.29 [W/(m2K)] Heat lost from one wall: Rout=1/(8.722[W/(m2K)]* 20.0925[m2])= 0.0057[K/W] Rin=1/( 8.29[W/(m2K)]* 20.0925[m2])=0.006[K/W] Rbrick=0.12[m]/(1.34[W/(mK)]* 20.0925[m2])=0.0045 [K/W] Rinter=0.1[m]/(0.02364[W/mK]* 20.0925[m2])=0.2105 [K/W] Rinter2=0.087[m]/(0.02476[W/mK]* 20.0925[m2])=0.1749 [K/W] Rplaster=1/( 0.055[W/(m2 K)]* 20.0925[m2])=0.9049[K/W] Qw5= (ΔT /∑R) = (21-(-24))[K] /( 0.0057+0.006+0.0045*2+0.2105+0.1749+0.9049)[K/W]) Qw5= 34.3249[W] The amount of heat lost by the wall is 34.3249[W]. Heat Losses by Wall 6: Wall dimensions: Lc=4.22[m]; H=2.85[m]; A=(4.22*2.85)-(window areas) [m2]= 12.027-2*(0.47*1.4) [m2]= 10.711[m2]; Δx=0.44[m]; kbw=1.34[W/(mK)] Re=(V*L)/ν=(3.056*4.22)/(1.1362/105)=1’135’039.61>105 Hence the flow is turbulent Nu=0.0296*Re0.8Pr1/3=0.0296*(1’135’039.61)0.8(0.74148)1/3=1’870.684 Nu=(h[W/(m2K)]*4.22[m])/0.021802[W/(mK)] hout= (1’870.684*0.021802)/4.22 [W/(m2K)]= 9.665[W/(m2K)]

Page 44: Heat Transfer Project

44

hin= 8.29 [W/(m2K)] Heat lost from one wall: Rout=1/(9.665[W/(m2K)]* 10.711[m2])=0.0097[K/W] Rin=1/( 8.29[W/(m2K)]* 10.711[m2])=0.0113[K/W] Rbrick=0.12[m]/(1.34[W/(mK)]* 10.711[m2])=0.0084[K/W] Rinter=0.1[m]/(0.02364[W/mK]* 10.711[m2])=0.3949[K/W] Rinter2=0.087[m]/(0.02476 [W/mK]* 10.711[m2])=0.328[K/W] Rplaster=1/( 0.055[W/(m2 K)]* 10.711[m2])=1.6975[K/W] Qw4= (ΔT /∑R) = (21-(-24))[K] /(0.0097+0.0113+0.0084*2+0.3949+0.328+1.6975)[K/W]) Qw4= 18.306[W] The amount of heat lost by the wall is 18.306[W]. Heat Loss by Wall 7: Wall dimensions: Lc=1.55[m]; H=2.85[m]; A=(1.55*2.85)[m2] =4.4175[m2]; Δx=0.44[m]; kbw=1.34[W/(mK)] Re=(V*L)/ν=(3.056*1.55)/(1.1362/105)=416’898.433>105 Hence the flow is turbulent Nu=0.0296*Re0.8Pr1/3=0.0296*(416’898.433)0.8(0.74148)1/3=839.490 Nu=(h[W/(m2K)]* 1.55 [m])/0.021802[W/(mK)] hout= (839.490*0.021802)/ 1.55[W/(m2K)]= 11.808[W/(m2K)] hin= 8.29 [W/(m2K)] Heat lost from one wall: Rout=1/(11.808[W/(m2K)]* 4.4175[m2])=0.0192[K/W] Rin=1/( 8.29[W/(m2K)]* 4.4175[m2])=0.0273[K/W] Rbrick=0.12[m]/(1.34[W/(mK)]* 4.4175[m2])=0.0203[K/W] Rinter=0.10[m]/(0.02364[W/mK]* 4.4175[m2])=0.9576[K/W] Rinter2=0.087[m]/(0.02476[W/mK]* 4.4175 [m2])=0.7954[K/W] Rplaster=1/( 0.055[W/(m2 K)]* 4.4175 [m2])=4.1159[K/W] Qw13= (ΔT /∑R) = (21-(-24))[K] /(0.0192+0.0273+0.0203*2+0.9576+0.7954+4.1159)[K/W]) Qw13=7.5554[W] The amount of heat lost by the wall is 7.5554[W].

Page 45: Heat Transfer Project

45

Heat Loss by Wall 8: Wall dimensions: Lc=4.5[m]; H=2.85[m]; A=( 4.5*2.85-(areas of the windows))[m2] A= (12.825-(0.82*1.44))[m2]=11.6442 [m2]; Δx=0.44[m]; kbw=1.34[W/(mK)] Re=(V*L)/ν=(3.056*4.5)/(1.1362/105)=1’210’350.29>105 Hence the flow is turbulent Nu=0.0296*Re0.8Pr1/3=0.0296*(1’210’350.29)0.8(0.74148)1/3=1’969.339 Nu=(h[W/(m2K)]* 4.5[m])/0.021802[W/(mK)] hout= (1’969.339*0.021802)/ 4.5[W/(m2K)]= 9.541[W/(m2K)] hin= 8.29 [W/(m2K)] Heat lost from one wall: Rout=1/(9.541[W/(m2K)]*11.6442 [m2])=0.009[K/W] Rin=1/( 8.29[W/(m2K)]* 11.6442[m2])= 0.0104[K/W] Rbrick=0.12[m]/(1.34[W/(mK)]* 11.6442[m2])=0.0077 [K/W] Rinter=0.10[m]/(0.02364[W/mK]* 11.6442[m2])=0.3633 [K/W] Rinter2=0.087[m]/(0.02476[W/mK]* 11.6442[m2])=0.3018 [K/W] Rplaster=1/( 0.055[W/(m2 K)]* 11.6442[m2])=1.5614[K/W] Qw14= (ΔT /∑R) = (21-(-24))[K] /(0.009+0.0104+0.0077*2+0.3633+0.3018+1.5614)[K/W])=19.9[W] The amount of heat lost by the wall is 19.9[W]. The net heat loss by the walls of the 2nd floor is about 185.725[W] Heat Losses by Window 1 & 2: Window Parameters: Double-Pane, Double Glazing, one side Low-e Coated Windows, air filled, tightly sealed, vinyl framed, with metal spacer type. L=0.82[m]; H=1.57[m]; A= 0.82*1.57 [m2] = 1.2874[m2]; Frame thickness Δxw=0.041[m] The convective heat transfer coefficient inside the house is taken to be the conventional value given in the book or hin= 8.29 [W/(m2K)]. The outside convective heat transfer coefficient is assumed to be the same as the one calculated for the wall where window 1 is positioned (wall 2) hout = 11.808 [W/(m2K)] ; Tinside air= Tia =21[oC]; Tout = -24[oC] Heat lost from the window: Rin=1/(8.29 [W/(m2K)]* 1.2874 [m2])=0.0937[K/W]

Page 46: Heat Transfer Project

46

Rout=1/(11.808[W/(m2K)]* 1.2874[m2])=0.0658[K/W] RU=1/(3.04[W/(m2K)]* 1.2874[m2])=0.2555[K/W] Qw1= (ΔT /∑R) = (21-(-24))[K] /(0.0937+0.0658+0.2555)[K/W])=108.4337[W] The amount of heat lost by this window is 108.4337[W] and by two windows it is 216.8674[W]. The average temperature of the indoors window 1 surface is: 21[oC]- 108.4337[W]*0.0658 [K/W] = 13.865[oC] Heat Losses by Window 3, 4,6 &7: Window Parameters: Double-Pane, Double Glazing, one side Low-e Coated Windows, air filled, tightly sealed, vinyl framed, with metal spacer type. L=0.47[m]; H=1.4[m]; A= 0.87*1.4 [m2] = 1.218[m2]; Frame thickness Δxw=0.041[m] The convective heat transfer coefficient inside the house is taken to be the conventional value given in the book or hin= 8.29 [W/(m2K)]. The outside convective heat transfer coefficient is assumed to be the highest calculated for the wall of the house hout = 11.808 [W/(m2K)] ; Tinside air= Tia =21[oC]; Tout = -24[oC] Heat lost from the window: Rin=1/(8.29 [W/(m2K)]* 1.218 [m2])=0.099[K/W] Rout=1/(11.808[W/(m2K)]* 1.218[m2])=0.0695[K/W] RU=1/(3.04[W/(m2K)]* 1.218[m2])=0.2701 [K/W] Qw1= (ΔT /∑R) = (21-(-24))[K] /(0.099+0.0695+0.2701)[K/W])=102.5992[W] The amount of heat lost by this window is 102.5992[W] and by four such windows it is 410.3968[W]. The average temperature of the indoors window 1 surface is: 21[oC]-102.5992[W]*0.0695[K/W] [K/W] = 13.869[oC] Heat Losses by Window 5: Window Parameters: Double-Pane, Double Glazing, one side Low-e Coated Windows, air filled, tightly sealed, vinyl framed, with metal spacer type. L=0.82[m]; H=1.44[m]; A= 0.82*1.44 [m2] = 1.1808[m2]; Frame thickness Δxw=0.041[m] The convective heat transfer coefficient inside the house is taken to be the conventional value given in the book or hin= 8.29 [W/(m2K)]. The outside convective heat transfer coefficient is assumed to be the highest calculated for the wall of the house hout = 11.808[W/(m2K)] ; Tinside air= Tia =21[oC]; Tout = -24[oC]

Page 47: Heat Transfer Project

47

Heat lost from the window: Rin=1/(8.29 [W/(m2K)]* 1.1808 [m2])=0.1022[K/W] Rout=1/(11.808[W/(m2K)]* 1.1808[m2])=0.0717[K/W] RU=1/(3.04[W/(m2K)]* 1.1808[m2])= 0.2786[K/W] Qw1= (ΔT /∑R) = (21-(-24))[K] /(0.1022+0.0717+0.2786)[K/W])= 99.448[W] The amount of heat lost by this window is 99.448[W]. The average temperature of the indoors window 1 surface is: 21[oC]- 99.448 [W]*0.0717 [K/W] = 13.87[oC] Heat Losses by the Roof of the 2nd floor: Roof dimensions: L=10 and 7.05 and 2.499 and 1.7495[m]; W=4.5 and 4.22 and 0.55 and 0.7495 [m]; A=(10*4.5+7.05*4.22+2.499*0.55+1.7495*0.7495)[m2] = 77.312[m2]; Δx=0.313[m]; Insulated with plaster and mineral fiber. From Table A-5 and A-6 Rplaster =0.055[W/(m2K)] Rmineralfiber =3.32[W/(m2K)] The convective heat transfer coefficient inside the house is taken to be the conventional value given in the book or hin= 8.29 [W/(m2K)]. The convective heat transfer coefficient outside the house is taken to be the conventional value given in the book for winter conditions or hout= 34 [W/(m2K)]. Heat lost to the ceiling: Rout=1/(34[W/(m2K)]* 77.312 [m2])= 0.0038[K/W] Rin=1/( 8.29[W/(m2K)]* 77.312[m2])=0.0016 [K/W] Rplaster =1/(0.055 [W/(m2K)]*77.312 [m2])=0.2352[K/W] Rmineralfiber =1/(3.32[W/(m2K)]* 77.312[m2])= 0.0039[K/W] Qceileing= -(ΔT /∑R) = ((19-(-24))[K] /(0.0038+0.0016+0.2352+0.0039)[K/W])= 175.869 [W] The amount of heat lost by the ceiling is 175.869[W].

Page 48: Heat Transfer Project

48

Heat Losses by the Floor of the 2nd floor: The floor of the second floor is 0.343[m] thick. 0.03[m] is made of hard wood, 0.013[m] is plaster board and there is an air gap of 0.3[m] between them. The wood and the plaster board are separated by a 0.04[m] by 0.2[m] hardwood board. From Table A-5 kwood = 0.159 [W/(mK)], Rplaster board= Rpb=0.055[(m2K)/W] The air inside the floor is taken to be at a temperature of about 20[oC] For the air space between the floors: Tavg=20[oC] Therefore from Table A-15: ρ=1.204[kg/m3] kinterspace= kinter=0.02514[W/mK] α=2.074/105 [m2/s2] μ=1.825/105[kg/ms] ν=1.516/105[m2/s] Pr=0.7309 Assume that the conduction by air prevails over convection and conduction by the wood studs. Floor dimensions: L=10 and 7.05 and 2.499 and 1.7495[m]; W=4.5 and 4.22 and 0.55 and 0.7495 [m]; A=(10*4.5+7.05*4.22+2.499*0.55+1.7495*0.7495)[m2] = 77.312[m2]; Δx=0.03[m]; From Table A-5 khardwood=0.159[W/(mK)] The convective heat transfer coefficient inside the house is taken to be the conventional value given in the book or hin= 8.29 [W/(m2K)]. Heat lost to the floor: Rair near floor= Ranf= 1/(8.29[W/(m2K)]*77.312[m2])= 0.0016[K/W]= Rair 1st floor Rfloor=0.03[m]/( 0.159[W/mK]*77.312[m2])=0.0024[K/W] Rinter=0.3[m]/(0.02476[W/mK]* 77.312[m2])=0.1567[K/W] Rplaster=1/( 0.055[W/(m2 K)]*77.312[m2])=0.2352[K/W] Qfloor= -(ΔT /∑R) = ((21-19)[K] /( 0.0024+0.1567+0.2352)[K/W])= 5.0723[W] The total heat loss from the 2nd floor is the sum of all the losses: Qtotal= (185.725+216.8674+410.3968+99.448+175.869+5.0723)[W]=1093.4[W] Minimizing 2nd Floor Heat Losses: The heat losses by the walls, the floor and ceiling are fairly small comparing to the losses through the windows and any further implementing of insulation may create an uncanny look of the house. Hence, the losses through the windows can be altered to reduce the heat losses. The heat losses by the windows can be minimized by covering the window sill boxes with a transparent PLA film (Poly-Lactic Acid is biodegradable and is made from corn starch [3]) (From Table A-5 an approximate value can be found similar to the R-value of vapor-permeable felt, that is RPLA=0.011[(m2K)/W]) and an isolated space of air. Assume that the PLA film is at the same temperature as the 1st floor air or 19[oC]. As was estimated in the case for the 1st floor the approximate

Page 49: Heat Transfer Project

49

heat loss for the PLA covered sills is about 1[W]. Therefore, simply by covering the windows with the PLA covering the total heat loss becomes approximately: Qtotal= (185.725+2+4+1+175.869+5.0723)[W]=373.6663[W] This alternation in heat transfer parameter is only 34.17% of the original heat loss value and it saves nearly 65.83% of energy. CONCLUSION As a result of optimization procedures performed above the give house could save up above 70% of its original energy consumption. Technically this type of saving should mean that for this particular house the savings would be in a range of $165 to $170 dollars. That is if the insulating materials were bought for $750 the return on investment would be fulfilled within about three and a bit winter periods costing $235 of un-insulated energy waste. REFERENCES HomePerformance, Choosing A. "Ontario Home Energy Savings Program - Ontario Home Energy Rebate." Home Energy Audit - Government Grants Rebates - Ontario BC Canada. Web. 28 Mar. 2011. <http://www.homeperformance.com/ontario-rebate-grants-ontario-government-energy-rebates>. "Residential Sector Ontario Table 34: Single Detached Secondary Energy Use and GHG Emissions by Energy Source." Office of Energy Efficiency | L'Office De L'efficacité énergétique. Web. 028 Mar. 2011. <http://oee.nrcan.gc.ca/corporate/statistics/neud/dpa/tablestrends2/res_on_34_e_4.cfm?attr=0>. The Reference Book and Tables: Y.A. Cengel, Heat Transfer, a Practical Approach, 3rd edition, McGraw-Hill, New York (2007) [1] Weather Data: http://www.climate.weatheroffice.gc.ca/climateData/hourlydata_e.html?Prov=XX&timeframe=1&StationID=48649&Month=1&Day=17&Year=2011&cmdB1=Go [2] Frost Penetration File http://www.raqsa.mto.gov.on.ca/techpubs/ops.nsf/fee5d2d0c518bc6c85257172004af2c6/a48e402f1bf0b57c852570c9006cfae6/$FILE/OPSD3090.101%20Rev%231%20Nov2010.pdf [3] PLA and environmentally friendly plastics http://www.fpintl.com/resources/wp_biodegradable_plastics.htm

Page 50: Heat Transfer Project