HELLER COOLING SYSTEM

CONDENSER COOLING

Page 2: Heller System PPT 3 Cooling Systems

Heller System: “Indirect dry cooling”

•Air is used as a secondary cooling medium. •Water is still needed as primary coolant, however the cooling water flows in a closed cycle and is never in contact with the cooling air•The heat transfer between air and cooling water is achieved by convection and not by evaporation like in a wet cooling tower. 

Page 3: Heller System PPT 3 Cooling Systems

The Main Components of HELLER SYSTEM

1. Direct contact (DC) jet condenser/Surface condenser

2. Hydro machine group ( a cooling water circulation extraction pump, a recovery hydraulic turbine and a driving electric motor; mounted on a common shaft.)

3. Air coolers ( Cooling Tower)

Page 4: Heller System PPT 3 Cooling Systems
Page 5: Heller System PPT 3 Cooling Systems

1. Condenser

1. Direct contact (DC) jet condenser.• Mostly used; Low TTD (terminal temperature

difference ) of 0.3-0.6°K against usual 3-5 ° K for a given cooling tower rating,

• Better vacuum can be achieved

2. Surface condenser.• Used in special cases such as nuclear power stations

or various power units serving district heating networks

Page 6: Heller System PPT 3 Cooling Systems

Jet Condenser

• the cooling water is sprayed into the steam•steam by mixing directly with cold water gets condensed•part of the condensate equal to the turbine exhaust flow is sent back to the plant as feedwater•the remainder is cooled in a dry cooling tower and then sprayed on the turbine exhaust

Page 7: Heller System PPT 3 Cooling Systems

Jet Condenser( contd..)

for the spray condenser, a mass balance and an energy balance give the following equations:

w2=w4, w3=w2+w5 w2h2+w5h5=w3h3 from which w5/w2 = (h2-h3)/(h3-

h5) Since h2-h3 is much greater than

h3-h5, the circulating water flow (w5) is much larger than the steam flow (w2).

Page 8: Heller System PPT 3 Cooling Systems

Jet Condenser in a Heller System

Page 9: Heller System PPT 3 Cooling Systems

 2. Hydro-machine groups

For CW systems with surface condenser, regular CW circulating pumps are used

For DC condensers two or three (for units larger than 600 MWe) identical hydraulic machine groups connected in parallel are used.

Each group consists: a cooling water circulation & extraction pump, a recovery hydraulic turbine and a driving electric motor; mounted on a common shaft.

Page 10: Heller System PPT 3 Cooling Systems

3. Cooling Towers

 Draft options for air moving equipment. Allows the use of either natural or mechanical draft (unlike the direct ACC, where only mechanical draft can be applied). For medium and large capacity power units, natural draft results

in significantly better economics. The natural draft tower shell can either be of the usual

reinforced concrete type, or a structural steel tower with aluminum clad .

Flue gases can be exhausted through the natural draft tower – using a stack of approx. 40-50 m high instead of a tall chimney

Results in capital cost saving , reduces the ground level concentration of pollutants.

For mechanical draft cooling systems we prefer to supply induced draft fans instead of forced draft ones – to reduce warm air recirculation.

Page 11: Heller System PPT 3 Cooling Systems

Natural Draft

Natural draft towers use very large concrete chimneys to introduce air through the media .

Due to the large size of these towers, they are generally used for water flow rates above 45,000 m3/hr .

These types of towers are used only by utility power stations

Page 12: Heller System PPT 3 Cooling Systems

Mechanical Draft

Utilize large fans to force or suck air through circulated water .

The water falls downward over fill surfaces, which help increase the contact time between the water and the air - this helps maximise heat transfer between the two .

Cooling rates of Mechanical draft towers depend upon their fan diameter and speed of operation

Page 13: Heller System PPT 3 Cooling Systems

Air Flow Arrangement of Tower

Counter flows induced draft. Counter flow forced draft.Cross flow induced draft.

Page 14: Heller System PPT 3 Cooling Systems

Air coolers A great variety of water-to-air heat exchangers applicableFor power cooling tasks the best is the Forgó-type; a plate-fin-and-tube, surface treated, all aluminum water-

to-air heat exchanger; different geometries are available. For some special applications Forgó-type heat

exchangers are also supplied with carbon or stainless steel tubes and aluminum fins.

Heat exchanger bundles, arranged in a V shape, form the assembly units, so-called “cooling deltas”.

The cooling deltas are grouped in parallel sections.

Page 15: Heller System PPT 3 Cooling Systems

Factors Affecting Cooling Tower Performance

Range –Range is the difference between the cooling tower water inlet and outlet temperature.

The range at the exchanger is determined entirely by the heat load and the water circulation rate through the exchanger and on to the cooling water.

Range oC = Heat Load in kcals/hour / Water Circulation Rate in LPH

Approach -Approach is the difference between the cooling tower outlet cold water temperature and ambient wet bulb temperature.

Page 16: Heller System PPT 3 Cooling Systems

A fraction of the warm circuit water (equal to the condensate stream) is pumped forward to the thermal cycle while most of the warm circuit water is pumped via pipeline to a natural draft cooling tower where it cools down in Forgo-type water-to-air heat exchangers arranged vertically around the towers circumference.

Page 17: Heller System PPT 3 Cooling Systems

 A great variety of water-to-air heat exchangers applicable for HELLER System. For power cooling tasks the best is the so-called Forgó-type- a plate-fin-and-tube, surface treated, all aluminum water-to-air heat exchanger of which different geometries are available.

Heat exchanger bundles, arranged in a V shape, form the assembly units, so-called “cooling deltas”.The cooling deltas are grouped in parallel sections.

Page 18: Heller System PPT 3 Cooling Systems
Page 19: Heller System PPT 3 Cooling Systems

Forgo Type Heat Exchanger

Cooling delta washing equipmentenables efficient online cleaning.

A mono-metal all aluminum heat exchanger with protective surface treatment.The hard plate Al-fin and normal Al-tube bond provides enduring metallic contact due to “spring effect”. Minimum deposition and easy cleaning (cleaning once or twice a year).

Page 20: Heller System PPT 3 Cooling Systems

Dry/Wet HELLER System Options

GEA EGI has developed several cost effective dry/wet combinations derived from the all dry HELLER System

Aimed at improving:1. Environmental compatibility and 2. Water conservation issues relative to wet cooling3. Summertime heat rejection capabilities4. Turbine output 5. reducing investment costs relative to dry cooling.

HELLER System is well suited to dry/wet combinations, as at lower ambient temperatures it is capable to establish in dry operation mode the same vacuum than a wet cooling plant.

Page 21: Heller System PPT 3 Cooling Systems

Dry/Wet HELLER System Options

Dry HELLER System with Supplemental Spraying (1-3%)

Used for peak-shaving in the hottest summer hours ; improving plant availability at excessive conditions or in emergency cases

Spraying is applied only for limited time period with quality water needed.

Page 22: Heller System PPT 3 Cooling Systems

Dry/Wet HELLER System Options

HEAD (Delugable) Cooling System (1-20%)

A well-proven system The system operates fully dry for a significant part of

the year except during the summer hours coinciding with peak power demand.

An even water film (deluging) is applied on the special plate fins of the air cooled heat exchanger.

The applied quantity of water is significantly more than the evaporation; therefore the excess water is collected and re-circulated after the addition of the necessary make-up.

An interesting variant is when a large all-dry natural draft cooling tower is supplemented with mechanical draft dry/deluged HEAD cells to enhance summer capability.

These cells can be located either inside or outside of the tower.

In case of cells outside tower for plants operating in areas of severe winter climate, the same cells can be used as so-called pre-heaters during the start-up period, ensuring a freeze-proof start even under the most unfavorable winter conditions.

Page 23: Heller System PPT 3 Cooling Systems

Dry/Wet HELLER System Options

HELLER System with assisting wet cells (5-40%) A new brand of efficient dry/wet systems has been developed by

integrating the dry HELLER System with evaporative cooling cells.

The integration can be in parallel through a combined surface and DC condenser or through a surface condenser having separate sections assigned for the closed dry cooled circuit and the wet cooled one.

Also they can be integrated either in parallel or in series via water-to-water heat exchangers for transforming the heat dissipation of the wet tower to the closed dry circuit.

Offer great operational flexibility, high availability and, much better environmental compatibility than the wet cooling tower

Offer remarkably lower investment cost and improved summertime heat rejection than all-dry cooling plants.

Page 24: Heller System PPT 3 Cooling Systems

Summary

 A completely closed and pressurized cooling circuit, where vacuum is limited to the small space of DC or surface condenser.

The intermediate cooling water circuit supports flexibility in tower when looking at distance and arrangement wise, without major cost or auxiliary power penalties.

A sectioned air cooler arrangement is used and easy & efficient online air cooler cleaning is ensured.

Air moving either by mechanical or natural draft as well as steam condensing by surface or DC condenser can be applied.

Natural draft allows the exhaust of flue gases via the cooling tower (stack-in-tower and FGD in tower slutions) resulting in capital cost saving and meanwhile dramatically reducing ground level concentration of pollutants.

The DC condenser and natural draft tower shell support high thermal efficiency and they are practically maintenance-free with 100% availability.

Page 25: Heller System PPT 3 Cooling Systems

Summary

A variety of air coolers (material and surface wise) are available. The preference is for applying the FORGO-type mono-metal, all-aluminum air coolers for 40+ years life-span, withstanding external and internal corrosion, no flow accelerated corrosion (FAC), adequate for OT water chemistry.

The conventional condensate extraction pumps can be substituted by simple booster pumps with an alternative connection to the return cold line allowing to remain within resin temperature limit of CPP (i.e. in the most common cases 60 °C) even at max. ambient temperatures.

The large volume of water in the dry cooling circuit provides buffering condensate capacity as well as adequate conditions for CPP; and by its high thermal inertia can efficiently counter the negative effects of wind gusts (stabilizing back-pressure, thus avoiding surprise turbine trip at excessively warm ambient conditions).

 The extra condensate volume in the DC condenser hot-well allows primary frequency control of supercritical cycles by condensate throttling.

Page 26: Heller System PPT 3 Cooling Systems

Case study was put together for investigating cooling systems serving a 900 MWe supercritical coal fired power

unit. Here the final results – presented in the form of a bar chart – show a massive reduction in costs of the all-dry natural draft HELLER System compared to a direct

ACC.

Page 27: Heller System PPT 3 Cooling Systems

Advantages of Heller System

Highest efficiency among dry cooling options Supporting power cycle operational flexibility Easing power cycle water chemistry Backing improvement in power cycle

reliability & availability and reduced maintenance

Lower condenser pressure in winterFlexibility in siting

Page 28: Heller System PPT 3 Cooling Systems

..contd

Low noiseLow parasitic power consumptionNo hot air recirculationEnvironment friendlyLesser noise emission, CO2 emissions;

greater opportunity to reduce ground level concentration of pollutants

Economical aspect: massive reduction of present value costs (comparable capital cost w.r.t. ACC)

Page 29: Heller System PPT 3 Cooling Systems

Environmental Impact: Comparison with ACC

Page 30: Heller System PPT 3 Cooling Systems

Economic viability: Comparison with ACC

Page 31: Heller System PPT 3 Cooling Systems

Disadvantages of Heller System

Added complexity with the introduction of a secondary loop to carry the rejected heat, and its necessary piping

Significant loss of temperature driving potential for the ACHX, which increases the heat exchanger surface area needed

Additional pumping power requirement for the fluid loop

Page 32: Heller System PPT 3 Cooling Systems

Typical performance of 800MW TPP

Page 33: Heller System PPT 3 Cooling Systems

Conclusions

The indirect dry cooling HELLER System and its dry/wet derivatives have successfully demonstrated their reliability and effectiveness.

Given the long lasting impact o a cooling method for a power plant and even on the surrounding area, iIs is important to compare the lifecycle v cost issue.

Evaluations show how the advanced HELLER System extends the economic viability of water conserving cooling. The natural draft HELLER System can be competitive on present value basis against wet cooling even at a medium cooling water make-up cost.