HOME INSPECTION REPORT LOCATED AT: 12065 New St Downey, California 90242 PREPARED EXCLUSIVELY FOR: Peter INSPECTED ON: Friday, February 9, 2018 Inspector, Joseph Tittelfitz Buena Vista Inspection Group

Upload: others

Post on 23-Mar-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

HOME INSPECTION REPORT

LOCATED AT:12065 New St

Downey, California 90242

PREPARED EXCLUSIVELY FOR:Peter

INSPECTED ON:Friday, February 9, 2018

Inspector, Joseph Tittelfitz Buena Vista Inspection Group

Page 2: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 2 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

Executive Summary

This is a summary review of the inspectors' findings during this inspection. However, it does not contain every detailed observation. This is provided as an additional service to our client, and is presented in the form of a listing of the items which, in the opinion of your inspector, merit further attention, investigation, or improvement. Some of these conditions are of such a nature as to require repair or modification by a skilled craftsman, technician, or specialist. Others can be easily handled by a homeowner such as yourself.

Often, following the inspector's advice will result in improved performance and/or extended life of the component(s) in question. In listing these items, your inspector is not offering any opinion as to who, among the parties to this transaction, should take responsibility for addressing any of these concerns. As with most of the facets of your transaction, we recommend consultation with your Real Estate Professional for further advice with regards to the following items:

Interior

WALLS & CEILINGS

1: - The sprayed-on acoustic ceilings may contain asbestos. Actual asbestos content can only be determined by laboratory testing. Further information on asbestos can be obtained from a licensed asbestos consultant or abatement contractor.

Roofing

Composition Shingle

SURFACE

2: - The roofing surface appears to have been properly installed and is in serviceable condition, with exceptions noted below. Attention to the items listed, together with routine maintenance, will keep it functional and maximize its useful life.1) one small crack shingle2) ask seller why roof is white

Exterior/Site/Ground

STUCCO

3: - The stucco exterior is in good condition, with a few minor cracks. These hairline cracks are typical and no action is indicated. They can be patched and sealed in the course of routine maintenance.

GATES

4: - The gate(s) is/are locked and/or were inaccessible for inspection. We recommend further review.

Page 3: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 3 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

Garage

GARAGE DOOR OPENER

5: - The garage door opener(s) operated properly to raise and lower the doors, including the auto-reverse mechanisms, which stopped and reversed the direction of the doors when they struck objects in their path.

Unit should have its own receptacle not an extension cord

Note- button only operates to close when held- should be one touch operation- thus could not check sensors

GARAGE DOORS

6: - The garage door is a single roll up design.

PASSAGE DOOR

7: - The door between the garage and the living space is of fire resistive construction, however, the self-closing mechanism has been disabled and the door is no longer a fire-rated assembly. We recommend the self-closing feature be restored.

Living Room

CEILING

8: - There are minor ceiling cracks. This type of cracking in this material is common and does not indicate a structural deficiency. These can be patched, prepared and finished in the course of routine maintenance.

Page 4: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 4 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

Friday, February 9, 2018Peter

12065 New StDowney, California 90242

Dear Peter,

We have enclosed the report for the property inspection we conducted for you on Friday, February 9, 2018 at:

12065 New StDowney, California 90242

Our report is designed to be clear, easy to understand, and helpful. Please take the time to review it carefully. If there is anything you would like us to explain, or if there is other information you would like, please feel free to call us. We would be happy to answer any questions you may have.

Throughout the report, you'll find special symbols at the front of certain comments. Below are the symbols and their meanings:

= Improve

= Monitor

= Repair

We thank you for the opportunity to be of service to you.

Sincerely,

Inspector, Joseph TittelfitzBuena Vista Inspection Group

Page 5: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

Table of Contents

Executive Summary.......................................................................................................................................2

Introduction....................................................................................................................................................6

Introductory Notes.........................................................................................................................................6

Air Conditioning.............................................................................................................................................7

Heat...............................................................................................................................................................8

Electrical System...........................................................................................................................................9

Interior.........................................................................................................................................................11

Insulation/Energy.........................................................................................................................................12

Plumbing......................................................................................................................................................12

Roofing........................................................................................................................................................13

Water Heater...............................................................................................................................................16

Exterior/Site/Ground....................................................................................................................................19

Attic..............................................................................................................................................................23

Bathroom.....................................................................................................................................................24

Bedroom......................................................................................................................................................28

Dining Room/Area.......................................................................................................................................30

Garage.........................................................................................................................................................30

Kitchen.........................................................................................................................................................33

Laundry Area...............................................................................................................................................35

Living Room.................................................................................................................................................37

Locations of Emergency Controls................................................................................................................38

Environmental Concerns.............................................................................................................................39

Conclusion...................................................................................................................................................39

Page 6: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 6 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

Introduction

We have inspected the major structural components and mechanical systems for signs of significant non- performance, excessive or unusual wear and general state of repair. The following report is an overview of the conditions observed.

In the report, there may be specific references to areas and items that were inaccessible. We can make no representations regarding conditions that may be present but were concealed or inaccessible for review. With access and an opportunity for inspection, reportable conditions may be discovered. Inspection of the inaccessible areas will be performed upon arrangement and at additional cost after access is provided.

We do not review plans, permits, recall lists, and/or government or local municipality documents. Information regarding recalled appliances, fixtures and any other items in this property can be found on the Consumer Product Safety website. These items may be present but are not reviewed.

Our recommendations are not intended as criticisms of the building, but as professional opinions regarding conditions present. As a courtesy, the inspector may list items that they feel have priority in the Executive Summary portion of the report. Although the items listed in this section may be of higher priority in the opinion of the inspector, it is ultimately the client's responsibility to review the entire report. If the client has questions regarding any of the items listed, please contact the inspector for further consultation.

Lower priority conditions contained in the body of the report that are neglected may become higher priority conditions. Do not equate low cost with low priority. Cost should not be the primary motivation for performing repairs. All repair and upgrade recommendations are important and need attention.

This report is a "snapshot" of the property on the date of the inspection. The structure and all related components will continue to deteriorate/wear out with time and may not be in the same condition at the close of escrow.

Anywhere in the report that the inspector recommends further review, it is strongly recommended that this be done PRIOR TO THE CLOSE OF ESCROW. This report is not intended for use by anyone other than the client named herein. No other persons should rely upon the information in this report. Client agrees to indemnify, defend and hold inspector harmless from any third party claims arising out of client's unauthorized distribution of the inspection report.

By accepting this inspection report, you acknowledge that you have reviewed and are in agreement with all of the terms contained in the standard contract provided by the inspector who prepared this report.

Introductory Notes

NOTESOver the course of this inspection the temperature was estimated to be between 70 and 80 degrees.

The weather was sunny at the time of our inspection.

The scope of this inspection is limited to reasonably accessible areas. We make no attempt to move furnishings, stored personal property, and/or vegetation. Although no problems are anticipated, removal of these items may reveal reportable items.

Page 7: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 7 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

Air Conditioning

An air conditioning system consists of the cooling equipment operating and safety controls and a means of distribution. These items are visually examined for proper function, excessive or unusual wear, and general state of repair. Air conditioning systems are not tested if the outside temperature is too cold for proper operation. Detailed testing of the components of the cooling equipment or predicting their life expectancy requires special equipment and training and is beyond the scope of this inspection. This is a non-evasive, basic function review only. We do not dismantle, uncover or calculate efficiency of any system. Regular servicing and inspection of air conditioning equipment is encouraged.

BASIC INFORMATIONMethod of cooling: Gas compressionType of system: Gas heat with air conditioningNumber of units: 1Location of equipment: Split or remote systemCondenser location: Exterior

DUCT INSULATIONThe ducts are insulated with fiberglass. The insulation appears to be properly installed and in good condition.

Page 8: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 8 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

Heat

A heating system consists of the heating equipment, operating and safety controls, venting and the means of distribution. These items are visually examined for proper function, excessive or unusual wear and general state of repair. This is a non-evasive, basic function review only. We do not dismantle, uncover or calculate efficiency of any system. Regular servicing and inspection of heating systems is encouraged.

Forced Hot Air

BASIC INFORMATIONFurnace location: Garage

SYSTEM NOTESForced air furnaces operate by heating a stream of air moved by a blower through a system of ducts. Important elements of the system include the heat exchanger, exhaust venting, blower, controls, ducting, and combustion air supply.

GAS SUPPLYThe gas piping includes a 90 degree shutoff valve for emergency use. The valve was not tested at the time of inspection. This age and style of valve is normally found to be operable by hand and generally trouble free.

The gas connector is an approved flexible type in good condition.

Page 9: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 9 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

PLENUMThe plenum is the 'box', or portion of the ductwork, attached directly to the furnace acting as the termination or collector for all the individual supply or return ducts attached to it.

Electrical System

An electrical system consists of the service, distribution, wiring and convenience outlets (switches, lights, and receptacles). Our examination of the electrical system includes the exposed and accessible conductors, branch circuitry, panels, overcurrent protection devices, and a random sampling of convenience outlets. We look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature of the electrical wiring prevents inspection of every length of wire.

BASIC INFORMATIONService entry into building: Overhead service dropVoltage supplied by utility: 120 voltsCapacity (available amperage): 125 amperes

System grounding source: Water supply piping

Branch circuit protection: Circuit breakers

Page 10: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 10 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

Wiring material: Copper wiring where seen

METER & MAINThe meter and main electrical service panel are outside on the right side of the building.

CB MAIN PANELThe main service panel is in good condition with circuitry installed and fused correctly.

The circuits in the panel are labeled. We did not verify the accuracy of the labeling, but it appears to be typical. When the opportunity arises, we suggest checking the labeling by actually operating the breakers.

Page 11: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 11 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

Interior

Our review of the interior includes inspection of walls, ceilings, floors, doors, windows, steps, stairways, balconies and railings. These features are visually examined for proper function, excessive wear and general state of repair. Some of these components may not be visible/accessible because of furnishings and/or storage. In such cases these items are not inspected.

WALLS & CEILINGS

The sprayed-on acoustic ceilings may contain asbestos. Actual asbestos content can only be determined by laboratory testing. Further information on asbestos can be obtained from a licensed asbestos consultant or abatement contractor.

FLOORS: OVERALLThe floors have a good appearance and are in serviceable condition.

Page 12: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 12 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

DETECTORS: OVERALLThe smoke detectors were inspected for location only. For future reference, testing with only the built-in test button verifies proper battery and horn function, but does not test the smoke sensor. We advise testing with real or simulated smoke.

Insulation/Energy

Insulation, weatherstripping, dampers, double-glazed glass and set-back thermostats are features that help reduce heat loss and/or gain and increase system and appliance efficiency. Our visual inspection includes review to determine if these features are present in representative locations and we may offer suggestions for upgrading. Our review of insulation is based upon uniformly insulated or are insulated to current standards. It is our opinion that all homes could benefit from energy conservation upgrades, and we suggest that you consult professionals.

ATTIC INSULATIONThe attic has fiberglass batt insulation.

Plumbing

A plumbing system consists of the domestic water supply lines, drain, waste and vent lines and gas lines. Inspection of the plumbing system is limited to visible faucets, fixtures, valves, drains, traps, exposed pipes and fittings. These items are examined for proper function, excessive or unusual wear, leakage, and

Page 13: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 13 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

general state of repair. The hidden nature of piping prevents inspection of every pipe and joint. A sewer lateral test, necessary to determine the condition of the underground sewer lines, is beyond the scope of this inspection If desired, a qualified individual could be retained for such a test. Our review of the plumbing system does not include landscape watering, fire suppression systems, private water supply/waste disposal systems, or recalled plumbing supplies. Review of these systems requires a qualified and licensed specialist.

WATER PRESSUREThe system water pressure, as measured at the exterior hose bibs, is within the range of normal.

Roofing

A roof system consists of the surface materials, connections, penetrations and drainage (gutters and downspouts). We visually review these components for damage and deterioration and do not perform any destructive testing. If we find conditions suggesting damage, improper application, or limited remaining service life, these will be noted. We may also offer opinions concerning repair and replacement. Opinions stated herein concerning the roof are based on a limited visual inspection. These do not constitute a warranty that the roof is, or will remain, free of leaks.

Page 14: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 14 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

Composition Shingle

BASIC INFORMATIONLocation: Covers whole building

Page 15: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 15 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

Roof slope: MediumMaterial: Asphalt composition shingleLayers: Single layer

INSPECTION METHODOur inspection of this roof was conducted from the roof surface. The inspector walked upon the surface and visually examined the accessible roofing components.

SURFACE

The roofing surface appears to have been properly installed and is in serviceable condition, with exceptions noted below. Attention to the items listed, together with routine maintenance, will keep it functional and maximize its useful life.1) one small crack shingle2) ask seller why roof is white

Page 16: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 16 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

SERVICE DROPThe service drop appears to be properly installed and in good condition.

Water Heater

Our review of water heaters includes the tank, water and gas connections, electrical connections, venting and safety valves. These items are examined for proper function, excessive or unusual wear, leakage and general state of repair. We do not fully review tankless/on-demand systems and suggest you consult a specialist. The hidden nature of piping and venting prevents inspection of every pipe, joint, vent and connection.

BASIC INFORMATIONLocation: In the garage

Page 17: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 17 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

T/P RELEASE VALVEThe water heater is equipped with a temperature and pressure relief valve. This device is an important safety device and should not be altered or tampered with. We observed no adverse conditions.

GAS SUPPLYThe gas piping for the appliance includes a local 90 degree shut-off valve for use in an emergency or in case of repair. The valve was not tested at the time of inspection, but is of a type usually found to be serviceable.

Page 18: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 18 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

VENTINGThe water heater vent is properly installed and appears in serviceable condition.

WATER CONNECTORSThe cold water inlet and hot water outlet connections appear properly installed and in serviceable condition.

Page 19: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 19 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

SEISMIC RESTRAINTThe water heater tank has been secured. This feature will help prevent water heater movement and possible gas leakage, limit damage and provide a source of usable domestic water in the event of a major earthquake.

Exterior/Site/Ground

BASIC INFORMATIONGeneral lot topography: Flat lot

Page 20: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 20 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

Driveway: Concrete on grade

Walkways: Concrete

Walkways: Pavers set on a compacted gravel and/or sand bed

Page 21: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 21 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

Patio: Concrete

Primary exterior wall covering: Stucco

Page 22: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 22 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

WATER SHUT-OFF LOCATIONThe domestic water supply main shut-off valve is outside at the front of the building.

GAS METER LOCATIONThe gas meter is outside on the left side of the building. The main gas supply shutoff valve is located on the riser pipe between the ground and the meter. This valve should be turned 90 degrees (either way) in order to shut off the gas.

Page 23: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 23 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

STUCCO

The stucco exterior is in good condition, with a few minor cracks. These hairline cracks are typical and no action is indicated. They can be patched and sealed in the course of routine maintenance.

GATES

The gate(s) is/are locked and/or were inaccessible for inspection. We recommend further review.

Attic

The attic contains the roof framing and serves as a raceway for components of the mechanical systems. There are often heating ducts, electrical wiring and appliance vents in the attic. We visually examine the attic components for proper function, excessive or unusual wear, general state of repair, leakage, venting and misguided improvements. Where walking in an unfinished attic can result in damage to the ceiling, inspection is from the access opening only.

ACCESS/ENTRYThe attic access is located in the hall.

RAFTERSRafters are boards that support the roof sheathing, which in turn, supports the roof covering.

Page 24: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 24 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

The roof structure appears to be constructed in a manner typical of houses of this type and age. The rafters are generally in good condition, where seen, and have performed adequately since their installation.

Bathroom

Bathrooms are visually inspected for proper function of components, active leakage, excessive or unusual wear and general state of repair. Fixtures are tested using normal operating features and controls. Due to finished surfaces such as drywall/plaster, tile, and flooring, much of the bathroom is considered inaccessible. We do not test or confirm proper application of secondary equipment including but not limited to steam units, spa tubs, heated towel bars, etc.

Page 25: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 25 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

First Floor Hallway

DRAIN TRAPThe drain trap and associated piping are PVC plastic.

WATER BASINThe wash basin appears to be properly installed. When operated, it was observed to be fully functional and in serviceable condition.

Page 26: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 26 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

BATHTUBThe bathtub appears to be properly installed and in serviceable condition.

SHOWERThe shower was operated for the inspection and appeared to be in serviceable condition.

RECEPTACLESGFCI (ground fault circuit interrupter) protection has been installed providing an increased margin of safety. We recommend testing the device on a monthly basis.

Page 27: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 27 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

First Floor Master

WATER BASINThe wash basin appears to be properly installed. When operated, it was observed to be fully functional and in serviceable condition.

SHOWERThe shower was operated for the inspection and appeared to be in serviceable condition.

Page 28: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 28 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

RECEPTACLESGFCI (ground fault circuit interrupter) protection has been installed providing an increased margin of safety. We recommend testing the device on a monthly basis.

Bedroom

First Floor Master

RECEPTACLESThe receptacles were found to be properly installed and in serviceable condition. The number of receptacles is considered adequate for the size of the room.

Page 29: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 29 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

First Floor Right Rear

RECEPTACLESThe receptacles were found to be properly installed and in serviceable condition. The number of receptacles is considered adequate for the size of the room.

First Floor Right Front

RECEPTACLESThe receptacles were found to be properly installed and in serviceable condition. The number of receptacles is considered adequate for the size of the room.

Page 30: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 30 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

Dining Room/Area

RECEPTACLESThe receptacles were found to be properly installed and in serviceable condition. The number of receptacles is considered adequate for the size of the room.

Garage

Garages and/or vehicle storage areas are visually inspected for general state of repair. Due to the presence of the storage and personal property, our review of these areas is limited.

WALL FRAMINGIn the areas where the wall framing is visible, all components appear to be properly installed and generally in good condition.

Page 31: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 31 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

GARAGE DOOR OPENER

The garage door opener(s) operated properly to raise and lower the doors, including the auto-reverse mechanisms, which stopped and reversed the direction of the doors when they struck objects in their path.

Unit should have its own receptacle not an extension cord

Note- button only operates to close when held- should be one touch operation- thus could not check sensors

Page 32: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 32 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

FLOORThe floor is a concrete slab.

DOORS

The rear screen door is damaged. We recommend it be repaired or replaced.

GARAGE DOORS

The garage door is a single roll up design.

Page 33: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 33 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

PASSAGE DOOR

The door between the garage and the living space is of fire resistive construction, however, the self-closing mechanism has been disabled and the door is no longer a fire-rated assembly. We recommend the self-closing feature be restored.

Kitchen

The kitchen is visually inspected for proper function of components, active leakage, excessive or unusual wear, and general state of repair. We inspect built-in appliances to the extent possible using normal operating controls. Freestanding stoves are operated, but refrigerators, small appliances, portable dishwashers, and microwave ovens are not tested.

DRAIN TRAPSThe drain trap and associated piping are PVC plastic.

SINKThe sink is metal.

There is a double sink.

Page 34: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 34 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

The sink appears to be properly installed. When operated, it was observed to be fully functional and in serviceable condition.

RECEPTACLESGFCI (ground fault circuit interrupter) protection has been installed providing an increased margin of safety. We recommend testing the device on a monthly basis.

VENTILATIONKitchen ventilation is provided by a range hood over the burners, venting to the exterior. The fan appears to be properly installed and in serviceable condition.

Page 35: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 35 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

STOVEThe stove was turned on with the normal operating controls and found to be in satisfactory working condition.

OVENThe oven was turned on with the normal operating controls and found to be in satisfactory working condition.

DISPOSALThe disposal was turned on with normal user controls and observed to be in satisfactory working condition.

DISHWASHERThe dishwasher responded to normal user controls and was found in good condition.

Laundry Area

Laundry areas and/or laundry rooms are visually inspected for general state of repair. Due to their hidden nature, we do not review appliances, connections, hookups, or venting.

Page 36: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 36 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

GAS SUPPLYThe gas piping for the appliance includes a local 90 degree shut-off valve for use in an emergency or in case of repair. The valve was not tested at the time of inspection, but is of a type usually found to be serviceable.

DRYER VENTThe dryer vent appears properly installed and in serviceable condition.

Page 37: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 37 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

WASHER/DRYERThe hookups for the washer are properly installed and in serviceable condition. The washer itself was not tested.

Living Room

RECEPTACLESThe receptacles were found to be properly installed and in serviceable condition. The number of receptacles is considered adequate for the size of the room.

Page 38: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 38 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

CEILING

There are minor ceiling cracks. This type of cracking in this material is common and does not indicate a structural deficiency. These can be patched, prepared and finished in the course of routine maintenance.

Locations of Emergency Controls

In an emergency, you may need to know where to shut off the gas, the water and/or the electrical system. We have listed below these controls and their location for your convenience. We urge that you familiarize yourself with their location and operation.

METER & MAINELECTRICAL SYSTEMThe meter and main electrical service panel are outside on the right side of the building.

Page 39: HOME INSPECTION REPORT · 2018-05-08 · running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature

Page 39 of 39Copyright© 2010-2018, SPECTACULAR, Buena Vista Inspection Group, Joseph Tittelfitz 174567653

GAS METER LOCATIONEXTERIOR/SITE/GROUNDThe gas meter is outside on the left side of the building. The main gas supply shutoff valve is located on the riser pipe between the ground and the meter. This valve should be turned 90 degrees (either way) in order to shut off the gas.

Environmental Concerns

Environmental issues include but are not limited to radon, fungi/mold, asbestos, lead paint, lead contamination, toxic waste, formaldehyde, electromagnetic radiation, buried fuel oil tanks, ground water contamination and soil contamination. We are not trained or licensed to recognize or discuss any of these materials. We may make reference to one of more of these materials in this report when we recognize one of the common forms of these substances. If further study or analysis seems prudent, the advice and services of the appropriate specialists are advised.

Conclusion

COMMENTSThis structure appears to be very well built utilizing quality materials and professional workmanship. It is in need of only typical maintenance and upgrading.