Page 1: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-1

Intelligent Control Panel SLC

Page 2: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-3

FACP

M M M

M M M

M M M

NFPA Style 4 SLC

Branch Line Resistor from End of Line to FACP

Shall Not Over 50 ohms per Branch

Twisted Unshielded Pair 12 to 18 AWG

SLC Distance

12 AWG 3810 M 16 AWG 1828 M

14 AWG 2895.6 M 18 AWG 1127 M

5000 ft ( 1500 M) for Shield Twisted Pair Cable (12 to 18 AWG)

Page 3: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-4

Isolator Application - Style 4 Riser

Max 25 standard devices between Isolators

Page 4: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-5

M M

M

M

MM

M

M

M

NFPA Style 6 SLC

Loop Resistor from End of Line to FACP Shall Not Over 50 ohms

5000 ft ( 1500 M) for Shield Twisted Pair Cable (12 to 18 AWG)

Twisted Unshielded Pair 12 to 18 AWG

SLC Distance

12 AWG 3810 M 16 AWG 1828 M

14 AWG 2895.6 M 18 AWG 1127 M

Page 5: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-6

Isolator Application - Style 6

Max 25 standard devices between Isolators

Page 6: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-7

M M

M

M

MM

M

M

M

Style 6 with Isolators

Page 7: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-10

(+) SLC Channel A

no connection

(-) SLC Channel A

NFS-320 / 640 / 3030 / NFS2-640 / NFS2-3030

Floating Shield

Page 8: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-11

FlashScan is an algorithm that greatly enhances the speed of communication between theAnalog intelligent devices. If one of the devices within a single group has new information,The panel CPU stops the group poll and concentrates on single points. The net effect is aresponse speed greater than five times that of earlier designs.

SLC Data Formats

Page 9: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-12

LED Operation

CLIP Mode FlashScan Mode

Control Panel

Device Standby Activated Standby Activated

Onyx Panels

Monitor Module Control Module Detector

Blink Red Blink Green Blink Red

Steady Red Steady Green Steady Red

Blink Green Blink Green Blink Green

Steady Red Steady Green Steady Red

FDM-1 Blink Red Steady Red Blink Red Steady Red

Page 10: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-13

SLC Loop Devices

A Signaling Line Circuit can contain a variety of devices, each with a specific function to perform.

Intelligent Detectors to identify a variety of threat conditions – various smoke levels, heat, etc.

Addressable Modules to interface the system to conventional input/output circuits and devices – notification appliances, smoke detectors, waterflow and supervisory devices, etc.

Addressable Pull Stations for manual alarm activation. These devices actually contain an Addressable Module inside.

Loop Isolators to prevent total loop failure from a SLC short.

Page 11: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-14

FlashScan Intelligent Detectors

FSP-851 Intelligent Photoelectric Detector. FSP-851T Intelligent Photo/Thermal Detector. FAPT-851 Acclimate™ Intelligent Photoelectric/Thermal Detector. FSI-851 Intelligent Ionization Detector. FST-851 Intelligent Thermal Detector. FST-851R Intelligent Rate-of-Rise Thermal Detector. FST-851H Intelligent High-Temperature Thermal Detector. FSD-751PL Intelligent Duct Photo Detector - Low-Flow FSD-751RPL Intelligent Duct Photo Detector with Relay - Low-Flow FSH-751 Intelligent HARSH (Hostile Area Smoke Head) Detector. FSL-751 Intelligent Laser Detector, low profile. Base Options:

B501 Intelligent Detector Base without flange. B501BP Intelligent Detector Bases, without flange – 10 pack. B710LP Intelligent Detector Base with flange. B710LPBP Intelligent Detector bases with flange – 10 pack. B501BH Intelligent Sounder Base/Assembly. B501BHT Intelligent Temporal Sounder/Base Assembly. B224BI Intelligent Isolator base. B224RB Intelligent Relay base. B710HD Intelligent Base for the HARSH Detector.

Page 12: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-15

FlashScan Monitor Modules

FMM-1 Addressable Monitor Module. Monitors normally-open contact type devices on either a Class A or Class B circuit.

FDM-1 Addressable Dual Monitor Module, 2 Class B circuits for normally-open contact type devices.

FZM-1 Addressable Monitor Module for compatible two-wire conventional smoke detectors.

FMM-101 Addressable Mini Module. Monitors a single normally-open contact type device on a Class B connection.

The FMM-101 can be mounted inside the enclosure of a single monitored device.

FMM-1

Page 13: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-16

FlashScan Control Modules

FCM-1 Addressable Control Module. Configured for one NFPA Style Y (Class B) or Style Z (Class A) circuit. 24 VDC power must be supplied. 3-amps max.

FRM-1 Addressable Relay Module. Provides two Form-C dry contacts that switch together (DPDT). Use for elevator recall, damper control, door holding, auxiliary control functions, etc.

FTM-1 Addressable Firephone Control Module.**Compatible with NFS-3030 and NFS-640 with FlashScan Software Ver. 2.0, Ver. 3.0 respectively.

FCM-1

Page 14: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-17

XP10-M - 10 Class B or Five Class-A Initiating Device Circuits for normally open alarm contact devices.

XP6-MA - Six Class B or Three Class A Initiating Device Circuit Module for Monitoring UL Listed two-wire smoke detectors (requires filtered, resettable 24 volts.)

Mounts in BB-XP backboxes – two modules, surface mount. Mount up to six modules on a CHS-6 chassis.

Addressable Multiple Input Modules

XP6-MA

Page 15: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-18

XP6-C Transponder Control Module. six Notification Appliance Circuits, Class A or B.

SYNC-1 Synchronization daughter module for XP6-C using System Sensor appliances.

XP6-R Transponder Relay Module. Six Form-C Dry Contact Relays.

Mounts in BB-XP backboxes – two modules, surface mount.

Addressable Multiple Output Modules

XP6-C

Page 16: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-19

NBG-12LX Addressable Pull Station

Key Resettable Dual Action. Can be opened without initiating an alarm condition! Addressable Mini-Module mounted inside station. Polling LED viewable through front handle.

Addressable FlashScan

Module

Page 17: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-20

Isolator Modules

ISO-X SLC Loop Isolator Module. Isolates against short circuits on the SLC.

Page 18: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-21

Break-off address stopfor panels with FlashScanMode.

FlashScan Modules

8

9 0

1

2

3

4

7

6

5ADDRESSLOOP

8 9

012

345

6 7

ONES

8 910

1112

13141501

2345

6 7

TENS

Page 19: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-22

Page 20: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-23

Page 21: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-24

Page 22: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-25

Page 23: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-26

Page 24: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-27

Page 25: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-28

Page 26: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-30

Page 27: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-31

Devices - Modules

Isolator Module (ISO-X) Supervises loop wiring for short

circuit conditions Allows critical component

functions Required for Style 7 operation Supported by FlashScan and

CLIP systems 1

2

3

4

Page 28: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-32

The circuit connected to terminals 6 & 7 are assigned the base address.The circuit connected to terminals 8 & 9 are assigned the base address plus 1. RED LED lights for either circuit 1 or circuit 2 alarm.

FDM-1 Wiring Class B Style B

8

9 0

1

2

3

4

7

6

5

ADDRESSLOOP

8

02

4

6

ONES

8 910

1112

13141501

2345

6 7

TENS

Page 29: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-35

+SLC -

+SLC-

Wiring an NBG-12LX Pull Station

Page 30: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-36

P

P

P

P

S

S

Building 2

Building 1

P = PrimaryS= Secondary

Wiring Surge Suppressor

Page 31: HONEYWELL BUILDING SOLUTIONS 04-0001-1 Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS04-0001-37