how to determine correct number of earthing electrodes strips plates and pipes part 1

Upload: robert-galarza

Post on 14-Jan-2016

44 views

Category:

Documents


5 download

DESCRIPTION

art

TRANSCRIPT

  • electrical-engineering-portal.comhttp://electrical-engineering-portal.com/how-to-determine-correct-number-of-earthing-electrodes-strips-plates-and-pipes-part-1?utm_source=Technical+Articles&utm_campaign=e0b983c2ea-RSS_EMAIL_CAMPAIGN&utm_medium=email

    How to Determine Correct Number of Earthing Electrodes (Strips,Plates and Pipes) part 1

    How to Determine Correct Number of Earthing Electrodes (Strips, Plates and Pipes) - part 1

    IntroductionNumber of Earthing Electrode and Earthing Resistance depends on the resistivity of soil and time for fault current topass through (1 sec or 3 sec). If we divide the area for earthing required by the area of one earth plate gives thenumber of earth pits required.

    There is no general rule to calculate the exact number of earth pits and size of earthing strip, but discharging ofleakage current is certainly dependent on the cross section area of the material so for any equipment the earth stripsize is calculated on the current to be carried by that strip.

    First the leakage current to be carried is calculated and then size of the strip is determined.

    For most of the electrical equipment like transformer, diesel generator set etc., the general concept is to have 4number of earth pits. 2 nos for body earthing with 2 separate strips with the pits shorted and 2 nos for Neutral with 2separate strips with the pits shorted.

  • The Size of Neutral Earthing Strip should be capable to carry neutral current of that equipment.The Size of Body Earthing should be capable to carry half of neutral Current .

    For example for 100kVA transformer , the full load current is around 140A.

    The strip connected should be capable to carry at least 70A ( neutral current) which means a strip of GI 25x3mmshould be enough to carry the current and for body a strip of 253 will do the needful. Normally we consider the stripsize that is generally used as standards.

    However a strip with lesser size which can carry a current of 35A can be used for body earthing. The reason for using2 earth pits for each body and neutral and then shorting them is to serve as back up. If one strip gets corroded andcuts the continuity is broken and the other leakage current flows through the other run thery by completing the circuit.

    Similarly for panels the no of pits should be 2 nos. The size can be decided on the main incomer circuit breaker.

    For example if main incomer to breaker is 400A, then body earthing for panel can have a strip size of 256 mm whichcan easily carry 100A.

    Number of earth pits is decided by considering the total fault current to be dissipated to the ground in case of fault andthe current that can be dissipated by each earth pit. Normally the density of current for GI strip can be roughly 200amps per square cam. Based on the length and dia of the pipe used the number of earthing pits can be finalized.

    1. Calculate numbers of pipe earthingA. Earthing resistance and number of rods for isolated earth pit(without buried earthing strip)The earth resistance of single rod or pipe electrode is calculated as per BS 7430:

    R=/23.14xL (loge (8xL/d)-1)

    Where:

    = Resistivity of soil ( meter),L = Length of electrode (meter),D = Diameter of electrode (meter)

    Example:

    Calculate isolated earthing rod resistance. The earthing rod is 4 meter long and having 12.2mm diameter, soilresistivity 500 meter.

    R=500/ (23.144) x (Loge (84/0.0125)-1) =156.19 .

    The earth resistance of single rod or pipe electrode is calculated as per IS 3040:

    R=100x/23.14xL (loge(4xL/d))

    Where:

    = Resistivity of soil ( meter),

  • L = Length of electrode (cm),D = Diameter of electrode (cm)

    Example:

    Calculate number of CI earthing pipe of 100mm diameter, 3 meter length. System has fault current 50KA for 1 sec andsoil resistivity is 72.44 -Meters.

    Current Density At The Surface of Earth Electrode (As per IS 3043):

    Max. allowable current density I = 7.571000/(xt) A/m2Max. allowable current density = 7.571000/(72.44X1) = 889.419 A/m2Surface area of one 100mm dia. 3 meter Pipe = 2 x 3.14 x r x L = 2 x 3.14 x 0.05 x3 = 0.942 m2Max. current dissipated by one Earthing Pipe = Current Density x Surface area of electrodeMax. current dissipated by one earthing pipe = 889.419x 0.942 = 837.83 A say 838 AmpsNumber of earthing pipe required = Fault Current / Max.current dissipated by one earthing pipe.Number of earthing pipe required = 50000/838 = 59.66 Say 60 Nos.Total number of earthing pipe required = 60 Nos.Resistance of earthing pipe (isolated) R = 100x/23.14xLx(loge (4XL/d))Resistance of earthing pipe (isolated) R = 10072.44 /23.14x300x(loge (4X300/10)) = 7.99 /PipeOverall resistance of 60 no of earthing pipe = 7.99/60 = 0.133 .

    Top

    B. Earthing resistance and number of rods for isolated earth pit(with buried earthing strip)Resistance of earth strip (R) As per IS 3043:

    R=/23.14xLx (loge (2xLxL/wt))

    Example:

    Calculate GI strip having width of 12mm , length of 2200 meter buried in ground at depth of 200mm, soil resistivity is72.44 -meter.

    Resistance of earth strip(Re) = 72.44/23.14x2200x(loge (2x2200x2200/.2x.012)) = 0.050 From above calculation overall resistance of 60 no of earthing pipes (Rp) = 0.133 .And it connected to bury earthing strip. Here net earthing resistance = (RpxRe)/(Rp+Re)Net eatrthing resistance = (0.1330.05)/(0.133+0.05) = 0.036

    Top

  • C. Total earthing resistance and number of electrode for group(parallel)In cases where a single electrode is not sufficient to provide the desired earth resistance, more than one electrodeshall be used. The separation of the electrodes shall be about 4 m. The combined resistance of parallel electrodes isa complex function of several factors, such as the number and configuration of electrode the array.

    The total resistance of group of electrodes in different configurations as per BS 7430:

    Ra=R (1+a/n) where a=/2X3.14xRxS

    Where:

    S = Distance between adjustment rod (meter), = Factor given in table below,n = Number of electrodes, = Resistivity of soil ( meter),R = Resistance of single rod in isolation ()

    Factors for parallel electrodes in line (BS 7430)Number of electrodes (n) Factor ()2 1.03 1.664 2.155 2.546 2.877 3.15

    8 3.399 3.6110 3.8

    For electrodes equally spaced around a hollow square, e.g. around the perimeter of a building, the equations givenabove are used with a value of taken from following table.

    For three rods placed in an equilateral triangle, or in an L formation, a value of = 1.66 may be assumed.

    Factors for electrodes in a hollow square (BS 7430)Number of electrodes (n) Factor ()2 2.713 4.514 5.48

  • 5 6.136 6.637 7.038 7.369 7.6510 7.912 8.314 8.616 8.918 9.220 9.4

    For Hollow square total number of electrodes (N) = (4n-1).

    The rule of thumb is that rods in parallel should be spaced at least twice their length to utilize the full benefit of theadditional rods. If the separation of the electrodes is much larger than their lengths and only a few electrodes are inparallel, then the resultant earth resistance can be calculated using the ordinary equation for resistances in parallel.

    In practice, the effective earth resistance will usually be higher than calculation.

    Typically, a 4 spike array may provide an improvement 2.5 to 3 times. An 8 spike array will typically give animprovement of maybe 5 to 6 times.

    The Resistance of Original Earthing Rod will be lowered by Total of 40% for Second Rod, 60% for third Rod,66% forforth rod.

    Example:

    Calculate Total Earthing Rod Resistance of 200 Number arranges in Parallel having 4 Meter Space of each and if itconnects in Hollow Square arrangement. The Earthing Rod is 4 Meter Long and having 12.2mm Diameter, SoilResistivity 500 .

    First Calculate Single Earthing Rod Resistance:

    R = 500/ (23.144) x (Loge (84/0.0125)-1) =136.23 .

    Now calculate total resistance of earthing rod of 200 number in parallel condition:

    a = 500/(23.14x136x4) =0.146Ra (Parallel in Line) =136.23x (1+100.146/200) = 1.67 .

    If earthing rod is connected in Hollow square than rod in each side of square is 200 = (4n-1) so n = 49 No .

    Ra (in hollow square) =136.23x (1+9.40.146/200) = 1.61 .

  • Originally published at Electrical Notes - Calculate Numbers of Plate/Pipe/Strip Earthings (Part-1)

    How to Determine Correct Number of Earthing Electrodes (Strips, Plates and Pipes) part 1Introduction1. Calculate numbers of pipe earthingA. Earthing resistance and number of rods for isolated earth pit (without buried earthing strip)Example:Example:

    B. Earthing resistance and number of rods for isolated earth pit (with buried earthing strip)Example:

    C. Total earthing resistance and number of electrode for group (parallel)Example: