howto “change fg2-logger with gprs/umts/lte into live-data
Embed Size (px)
TRANSCRIPT

Change FG2-Logger with GPRS/UMTS/LTE into Live-Data Collector V2.0 / 02.09.2019
Flexgate2/HowToLiveCollector.docx/pdf
HowTo “Change FG2-Logger with GPRS/UMTS/LTE into Live-Data Collector”
Preconditions:
You need one (or more) miniloggers (below 1 string logger) and one Logger (of our FG2-series, grey
box) with GPRS or UMTS or LTE modem.
The collector has our (internally type nr. 134). The minilogger does not need any modifications
(except Step 1). Whereas the GPRS/UMTS/LTE logger requires new/changed firmware and some
setip.
Below is a FG2-Logger with directly connected string:
In the following instructions, a FG2-logger of this type is changed to a (FG2-) Live-Data-Collector.

Change FG2-Logger with GPRS/UMTS/LTE into Live-Data Collector V2.0 / 02.09.2019
Flexgate2/HowToLiveCollector.docx/pdf
Files: You wil need 3 files:
- param_134_livecollector.bin
- livecollector_1v2_type134.bin
- livecollector_parameter_default.txt
All files can be downloaded from our company server
ftp://130.180.108.25 -> firmware\Flexgate2\134_b_LiveCollector\EU_433MHz
If you have any questions: we will be happy to help you!
www.geo-precision.com
Step1: Check the Minilogger(s):
Check or note (Radio) Net and ensure Life-data is et to „Always“:

Change FG2-Logger with GPRS/UMTS/LTE into Live-Data Collector V2.0 / 02.09.2019
Flexgate2/HowToLiveCollector.docx/pdf
Step 2: Check the Setup of the GPRS/UMTS/LTE Logger that will become the Collector:
Check or note (Radio) Net and Internet Setup (especially IP, scripts, server and APN, you’ll
need/verify it in Step 7)
Step 3: Update Parameters and Firmware on the Collector (maybe if the Net is changed in the
parameters, close the Setup, select the logger again and repeat Step 3, as shown in Step 4):

Change FG2-Logger with GPRS/UMTS/LTE into Live-Data Collector V2.0 / 02.09.2019
Flexgate2/HowToLiveCollector.docx/pdf
(optionally) Step 4: If the Net is changed, the logger must be re-selected:
(here the Net remained unchanged, so the Step 4 could be omitted…)
Step 5: Import a predefined mask for collecting temperature data:
Enter the Serial Number(s) of the remote minilogger (only for the first channel, all other channels are
“cached” and the values may be taken from the cache, else it really would need VERY long… All live
data are sent in one “Live Frame”). The mask contains 1 minilogger (Type “Digital String, Standard
accuracy)” with up to 20 sensor.

Change FG2-Logger with GPRS/UMTS/LTE into Live-Data Collector V2.0 / 02.09.2019
Flexgate2/HowToLiveCollector.docx/pdf
ONLY DS-Temp:
The “Index” of Digital String Values starts at Index 192 (= Channel #1 on the
remote logger (Because the Digital String Minilogger stores Standard accuracy
the value represents 1/100 °C per Count (eg. The value -1700 represents -
17,00°C, hence the “Multiplier” is set to 0.01 (this is already done in the mask
for max. 20 channels)).
Index 255 is special: it represents the Signal strength the collector can see for this live data. This
value is often helpful to find good signal quality and a good position for the collector. Ideal is 120-
200, see Step 8.
Step 6: Enter your offset to GMT here. The FG2-Shell may vary it +/- 60 secs max. to balance the load
of the server (only if the value is exactly a multiple of 1 minute):

Change FG2-Logger with GPRS/UMTS/LTE into Live-Data Collector V2.0 / 02.09.2019
Flexgate2/HowToLiveCollector.docx/pdf
Step 7: Check / adjust the Mobile Internet Settings (as before seen in Step 2):

Change FG2-Logger with GPRS/UMTS/LTE into Live-Data Collector V2.0 / 02.09.2019
Flexgate2/HowToLiveCollector.docx/pdf
Step 8: Now you can check, if the “new” collector can receive the latest measurement values of the
minilogger and the signal quality. Check if you have selected all channels that you want to send to
the server (the measurements are still stored on the minilogger, just as normal).
Note: Signals in the range 80-100 may work “sometimes”, but not reliable. In this case: find a better
position for the collector. Below 80 the signal is too weak…
(Optionally Step 9: ) Do an Internet Transmission either by entering the command “cm” in the
Terminal (or “cm1” for MORE verbose output) or press the internal button on the logger until the
LEDs are on (button only available for NON-SDI12-loggers with supply voltage <= 9Volt).
***