hvac duct user manual software.pdf

Upload: garciajoya

Post on 06-Jan-2016

130 views

Category:

Documents


9 download

TRANSCRIPT

  • 1

  • 2

    Copyright 2007 Mc4 Software, LLC

    All Rights Reserved. Patents Pending. This publication, or parts thereof, may not be reproduced in any form, by any method, or for any purpose. Mc4 Software, LLC reserves the right to revise and improve the software described in this publication, from time to time, without notice to users. Trademark Acknowledgments AutoCAD is a registered trademark of Autodesk, Inc. All brand names, product names or trademarks belong to their respective holders. GOVERNMENT USE Use, duplication, or disclosure by the U.S. Government is subject to restrictions as set forth in FAR 52.227-19 (Commercial Computer Software - Restricted Rights) and DFAR 252.227-7013(c) (1) (ii) (Rights in technical data and computer software), as applicable.

    Mc4 SOFTWARE LICENSE AGREEMENT

    IMPORTANT: THIS SOFTWARE END USER LICENSE AGREEMENT ("EULA") IS A LEGAL AGREEMENT BETWEEN

    YOU AND MC4. READ IT CAREFULLY BEFORE COMPLETING THE INSTALLATION PROCESS AND USING THE

    SOFTWARE. IT PROVIDES A LICENSE TO USE THE SOFTWARE AND CONTAINS WARRANTY INFORMATION AND

    LIABILITY DISCLAIMERS. BY INSTALLING AND USING THE SOFTWARE, YOU ARE CONFIRMING YOUR

    ACCEPTANCE OF THE SOFTWARE AND AGREEING TO BECOME BOUND BY THE TERMS OF THIS AGREEMENT. IF

    YOU DO NOT AGREE TO BE BOUND BY THESE TERMS, THEN SELECT THE "CANCEL" BUTTON, DO NOT INSTALL

    THE SOFTWARE AND RETURN THE SOFTWARE TO YOUR PLACE OF PURCHASE FOR A FULL REFUND.

    THIS EULA SHALL APPLY ONLY TO THE SOFTWARE SUPPLIED BY MC4 HEREWITH REGARDLESS OF WHETHER

    OTHER SOFTWARE IS REFERRED TO OR DESCRIBED HEREIN.

    1. Definitions

    (a) "Education Version" means a version of the Software, so identified, for use by students and faculty of

    educational institutions, only. (b) "Mc4" means Mc4 Software, LLC. and its licensors, if any. (c) "Software"

    means only the Mc4 software program(s) and third party software programs, in each case, supplied by Mc4

    herewith, and corresponding documentation, associated media, printed materials, and online or electronic

    documentation. (d) "Trial version" means a version of the Software, so identified, to be used only to

    review, demonstrate and evaluate the Software for a limited-time period. The trial version may have

    limited features, may lack the ability for the end-user to save the end product, and will cease operating

    after a pre-determined amount of time due to an internal mechanism within the trial version.

    2. License Grants

  • 3

    (a) You may install and use the Software on a single computer; OR, install and store the Software on a

    storage device, such as a network server, used only to install the Software on your other computers over

    an internal network, provided you have a license for each separate computer on which the Software is

    installed and run. A license for the Software may not be shared, installed or used concurrently on

    different computers. If Mc4 identifies the Software as a Network Version, you may install, access and

    use one (1) copy of the Software on your computer file server, for your own internal business needs, with

    the Mc4 license manager tool. The Software may be Installed on or accessed by other computers, or on an

    individual computer, as a multiple-user installation, so long as the maximum number of concurrent users

    does not to exceed the permitted number. (b) In the event the Software is distributed along with other

    Mc4 software products as part of a suite of products (collectively, the "Mc4 Suite"), the license of the Mc4

    Suite is licensed as a single product and none of the products in the Mc4 Suite, including the Software,

    may be separated for installation or use on more than one computer. (c) You may make one copy of the

    Software in machine-readable form solely for backup purposes. You must reproduce on any such copy all

    copyright notices and any other proprietary legends on the original copy of the Software. (d) Education

    versions may not be used for, or distributed to any party for, any commercial purpose. (e) You agree that

    Mc4 may audit your use of the Software for compliance with these terms at any time, upon reasonable

    notice.

    3. License Restrictions

    (a) Other than as set forth in Section 2, you may not make or distribute copies of the Software, or

    electronically transfer the Software from one computer to another or over a network. (b) You may not

    alter, merge, modify, adapt or translate the Software, or decompile, reverse engineer, disassemble, or

    otherwise reduce the Software to a human-perceivable form. (c) Unless otherwise provided herein, you

    may not rent, lease, or sublicense the Software. (d) Other than with respect to a trial version of the

    Software, you may permanently transfer all of your rights under this EULA only as part of a sale or

    transfer, provided you retain no copies, you transfer all of the Software (including all component parts,

    the media and printed materials, any upgrades, this EULA, and the serial numbers), and the recipient

    agrees to the terms of this EULA. If the Software is an upgrade, any transfer must include all prior versions

    of the Software from which you are upgrading. You may retain no copies of the Software. You may not sell

    or transfer any Software purchased under a volume discount. You may not sell or transfer any trial version

    of the Software. If the copy of the Software is licensed as part of the Mc4 Suite (as defined above), the

    Software shall be transferred only with and as part of the sale or transfer of the whole Mc4 Suite and not

    separately. (e) Unless otherwise provided herein, you may not modify the Software or create derivative

    works based upon the Software. (f) Unless otherwise provided herein, you shall not (A) in the aggregate,

    install or use more than one copy of the trial version of the Software, (B) download the trial version of the

    Software under more than one username, (C) alter the contents of a hard drive or computer system to

    enable the use of the trial version of the Software for an aggregate period in excess of the trial period for

    one license to such trial version, and (D) use the trial version of the Software for a purpose other than the

    sole purpose of determining whether to purchase a license to a commercial or education version of the

    Software; provided, however, notwithstanding the foregoing, you are strictly prohibited from installing or

    using the trial version of the Software for any commercial training purpose. (g) You may not export the

    Software into any country prohibited by the United States Export Administration Act and the regulations

    thereunder. (h) You may receive the Software in more than one medium but you shall only install or use

    one medium. Regardless of the number of media you receive, you may use only the medium that is

    appropriate for the server or computer on which the Software is to be installed. (i) In the event that you

  • 4

    fail to comply with this EULA, Mc4 may terminate the license and you must destroy all copies of the

    Software (with all other rights of both parties and all other provisions of this EULA surviving any such

    termination).

    4. Upgrades

    If this copy of the Software is an upgrade from an earlier version of the Software, it is provided to you on

    a license exchange basis. You agree by your installation and use of such copy of the Software to

    voluntarily terminate your earlier EULA and that you will not continue to use the earlier version of the

    Software or transfer it to another person or entity unless such transfer is pursuant to Section 3.

    5. Prior Same Version License

    If this copy of the Software is licensed as part of the Mc4 Suite (as defined above), and you have a prior

    license to the same version, and the Mc4 Suite was licensed to you with a discount based, in whole or in

    part, on your prior license to the same version, the Software is provided to you on a license exchange

    basis. You agree by your installation and use of this copy of the Software to voluntarily terminate your

    EULA with respect to such prior license and that you will not continue to install or use such prior license of

    the Software or transfer it to another person or entity.

    6. Ownership

    The foregoing license gives you limited license to use the Software. Mc4 and its suppliers retain all right,

    title and interest, including all copyright and intellectual property rights, in and to, the Software (as an

    independent work and as an underlying work serving as a basis for any application you may develop), and

    all copies thereof. All rights not specifically granted in this EULA, including Federal and International

    Copyrights, are reserved by Mc4 and its suppliers.

    7. LIMITED WARRANTY AND DISCLAIMER

    (a) Except with respect to the trial version of the Software, Mc4 warrants that, for a period of ninety (90)

    days from the date of delivery (as evidenced by a copy of your receipt): (i) when used with a

    recommended hardware configuration, the Software will perform in substantial conformance with the

    documentation supplied with the Software; and, (ii) the physical media on which the Software is furnished

    will be free from defects in materials and workmanship under normal use. (b) MC4 PROVIDES NO

    REMEDIES OR WARRANTIES, WHETHER EXPRESS OR IMPLIED, FOR THE TRIAL VERSION

    OF THE SOFTWARE. THE TRIAL VERSION OF THE SOFTWARE IS PROVIDED "AS IS". (c)

    EXCEPT AS SET FORTH IN THE FOREGOING LIMITED WARRANTY WITH RESPECT TO

    SOFTWARE OTHER THAN THE TRIAL VERSION, MC4 AND ITS SUPPLIERS DISCLAIM ALL

    OTHER WARRANTIES AND REPRESENTATIONS, WHETHER EXPRESS, IMPLIED, OR

    OTHERWISE, INCLUDING THE WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A

    PARTICULAR PURPOSE. ALSO, THERE IS NO WARRANTY OF NON-INFRINGEMENT AND

    TITLE OR QUIET ENJOYMENT. MC4 DOES NOT WARRANT THAT THE SOFTWARE IS

    ERROR-FREE OR WILL OPERATE WITHOUT INTERRUPTION. NO RIGHTS OR REMEDIES

    REFERRED TO IN ARTICLE 2A OF THE UCC WILL BE CONFERRED ON YOU UNLESS

  • 5

    EXPRESSLY GRANTED HEREIN. THE SOFTWARE IS NOT DESIGNED, INTENDED OR

    LICENSED FOR USE IN HAZARDOUS ENVIRONMENTS REQUIRING FAIL-SAFE CONTROLS,

    INCLUDING WITHOUT LIMITATION, THE DESIGN, CONSTRUCTION, MAINTENANCE OR

    OPERATION OF NUCLEAR FACILITIES, AIRCRAFT NAVIGATION OR COMMUNICATION

    SYSTEMS, AIR TRAFFIC CONTROL, AND LIFE SUPPORT OR WEAPONS SYSTEMS. MC4

    SPECIFICALLY DISCLAIMS ANY EXPRESS OR IMPLIED WARRANTY OF FITNESS FOR SUCH

    PURPOSES. (d) IF APPLICABLE, LAW REQUIRES ANY WARRANTIES WITH RESPECT TO

    THE SOFTWARE, AND ALL SUCH WARRANTIES ARE LIMITED IN DURATION TO NINETY

    (90) DAYS FROM THE DATE OF DELIVERY. (e) NO ORAL OR WRITTEN INFORMATION OR

    ADVICE GIVEN BY Mc4, ITS DEALERS, DISTRIBUTORS, AGENTS OR EMPLOYEES SHALL

    CREATE A WARRANTY OR IN ANY WAY INCREASE THE SCOPE OF ANY WARRANTY

    PROVIDED HEREIN. (f) (USA only) SOME STATES DO NOT ALLOW THE EXCLUSION OF

    IMPLIED WARRANTIES, SO THE ABOVE EXCLUSION MAY NOT APPLY TO YOU. THIS

    WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND YOU MAY ALSO HAVE OTHER

    LEGAL RIGHTS THAT VARY FROM STATE TO STATE.

    8. Exclusive Remedy

    Your exclusive remedy under the preceding is to return the Software to the place you acquired it, with a

    copy of your receipt and a description of the problem. Provided that any non-compliance with the above

    warranty is reported in writing to Mc4 no more than ninety (90) days following delivery to you, Mc4 will

    use reasonable commercial efforts to supply you with a replacement copy of the Software that

    substantially conforms to the documentation, provide a replacement for defective media, or refund to you

    your purchase price for the Software, at its option. Mc4 shall have no responsibility if the Software has

    been altered in any way, if the media has been damaged by misuse, accident, abuse, modification or

    misapplication, or if the failure arises out of use of the Software with other than a recommended

    hardware configuration. Any such misuse, accident, abuse, modification or misapplication of the Software

    will void the warranty above. THIS REMEDY IS THE SOLE AND EXCLUSIVE REMEDY AVAILABLE TO YOU FOR

    BREACH OF EXPRESS OR IMPLIED WARRANTIES WITH RESPECT TO THE SOFTWARE AND RELATED

    DOCUMENTATION.

    9. LIMITATION OF LIABILITY

    (a) NEITHER Mc4 NOR ITS SUPPLIERS SHALL BE LIABLE TO YOU OR ANY THIRD PARTY FOR ANY INDIRECT, SPECIAL, INCIDENTAL, PUNITIVE, COVER OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, DAMAGES FOR THE INABILITY TO USE EQUIPMENT OR ACCESS DATA, LOSS OF BUSINESS, LOSS OF PROFITS, BUSINESS INTERRUPTION OR THE LIKE), ARISING OUT OF THE USE OF, OR INABILITY TO USE, THE SOFTWARE AND BASED ON ANY THEORY OF LIABILITY INCLUDING BREACH OF CONTRACT, BREACH OF WARRANTY, TORT (INCLUDING NEGLIGENCE), PRODUCT LIABILITY OR OTHERWISE, EVEN IF Mc4 OR ITS REPRESENTATIVES HAVE BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES AND EVEN IF A REMEDY SET FORTH HEREIN IS FOUND TO HAVE FAILED OF ITS ESSENTIAL PURPOSE.(b) Mc4'S TOTAL LIABILITY TO

  • 6

    YOU FOR ACTUAL DAMAGES FOR ANY CAUSE WHATSOEVER WILL BE LIMITED TO THE GREATER OF $500 OR THE AMOUNT PAID BY YOU FOR THE SOFTWARE THAT CAUSED SUCH DAMAGE.(c) (USA only) SOME STATES DO NOT ALLOW THE LIMITATION OR EXCLUSION OF LIABILITY FOR INCIDENTAL OF CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY TO YOU AND YOU MAY ALSO HAVE OTHER LEGAL RIGHTS THAT VARY FROM STATE TO STATE.(d) THE FOREGOING LIMITATIONS ON LIABILITY ARE INTENDED TO APPLY TO THE WARRANTIES AND DISCLAIMERS ABOVE AND ALL OTHER ASPECTS OF THIS EULA.

    10. Basis of Bargain

    The limited warranty and disclaimer, exclusive remedies and limited liability set forth above are

    fundamental elements of the basis of the agreement between Mc4 and you. Mc4 would not be able to

    provide the Software on an economic basis without such limitations. Such limited warranty and disclaimer,

    exclusive remedies and limited liability inure to the benefit of Mc4's licensors.

    11. U.S. GOVERNMENT RESTRICTED RIGHTS LEGEND

    This Software and the documentation are provided with "RESTRICTED RIGHTS" applicable to private and

    public licenses alike. Without limiting the foregoing, use, duplication, or disclosure by the U.S.

    Government is subject to restrictions as set forth in this EULA and as provided in DFARS 227.7202-1(a) and

    227.7202-3(a) (1995), DFARS 252.227-7013 (c)(1)(ii)(OCT 1988), FAR 12.212(a)(1995), FAR 52.227-19, or

    FAR 52.227-14, as applicable. Manufacturer: Mc4 software, LLC, 1501 Edwards Ferry Road Leesburg -

    VA 20176.

    12. (Outside of the USA) Consumer End Users Only

    The limitations or exclusions of warranties and liability contained in this EULA do not affect or prejudice

    the statutory rights of a consumer, i.e., a person acquiring goods otherwise than in the course of a

    business.

    The limitations or exclusions of warranties, remedies or liability contained in this EULA shall apply to you

    only to the extent such limitations or exclusions are permitted under the laws of the jurisdiction where

    you are located. 13. Third Party Software

    The Software may contain third party software which requires notices and/or additional terms and

    conditions. Such required third party software notices and/or additional terms and conditions are located

    at www.mc4software.com and are made a part of and incorporated by reference into this EULA.

    14. General

    This EULA shall be governed by the internal laws of the Commonwealth of Virginia, without giving effect

    to principles of conflict of laws. You hereby consent to the exclusive jurisdiction and venue of the state

    courts sitting in Loudoun County, Virginia, if in state courts, or Alexandria, Virginia if in federal courts to

    resolve any disputes arising under this EULA. In each case this EULA shall be construed and enforced

    without regard to the United Nations Convention on the International Sale of Goods.

  • 7

    This EULA contains the complete agreement between the parties with respect to the subject matter

    hereof, and supersedes all prior or contemporaneous agreements or understandings, whether oral or

    written. You agree that any varying or additional terms contained in any purchase order or other written

    notification or document issued by you in relation to the Software licensed hereunder shall be of no

    effect. The failure or delay of Mc4 to exercise any of its rights under this EULA or upon any breach of this

    EULA shall not be deemed a waiver of those rights or of the breach.

    No Mc4 dealer, agent or employee is authorized to make any amendment to this EULA.

    If any provision of this agreement shall be held by a court of competent jurisdiction to be contrary to law

    that provision will be enforced to the maximum extent permissible and the remaining provisions of this

    Agreement will remain in full force and effect.

    All questions concerning this EULA shall be directed to: Mc4 software, LLC, 1501 Edwards Ferry Road

    Leesburg - VA 20176.

    Mc4 and other trademarks contained in the Software are trademarks or registered trademarks of Mc4 Software, LLC in the United States and/or other countries. Third party trademarks, trade names, product names and logos may be the trademarks or registered trademarks of their respective owners. You may not remove or alter any trademark, trade names, product names, logo, copyright or other proprietary notices, legends, symbols or labels in the Software. This EULA does not authorize you to use Mc4's or its licensors' names or any of their respective trademarks.

  • 8

    TABLE OF CONTENTS

    1 GETTING STARDED..............................................................11

    1.1 Overview................................................................................... 11

    1.2 Installing and Launching Mc4Suite Duct Module ..................................... 12

    2 INTRODUCTION..................................................................13

    3 SEQUENCE OF OPERATIONS...................................................15

    4 ARCHIVES.........................................................................16

    4.1 Duct Project Archives.................................................................... 16

    4.2 Air Outlet Archive ........................................................................ 18

    4.2.1 Manufacturer Archive .......................................................................22

    4.3 Standard Sizes Archive................................................................... 22

    4.4 Fittings Archive ........................................................................... 24

    5 Air Duct Drawing................................................................26

    5.1 AHU Placement ........................................................................... 26

    5.2 DUCT Drawing............................................................................. 28

    5.3 Diffusers drawing ......................................................................... 33

    5.3.1 Diffusers multiple drawing (array) ........................................................38

    5.4 Diffuser-Duct connection................................................................ 39

    5.5 Legend drawing ........................................................................... 40

    6 EDITING...........................................................................41

    6.1 Duct Details ............................................................................... 41

    6.2 FITTINGS DETAILS......................................................................... 43

    6.2.1 Transition.....................................................................................43

    6.2.2 Elbow..........................................................................................44

    6.2.3 Tee ............................................................................................45

  • 9

    6.2.4 Tee Branch..................................................................................46

    6.2.5 Tee Cross....................................................................................47

    6.3 Diffusers Details .......................................................................... 47

    7 CALCULATION ...................................................................49

    7.1 Supply Air Duct Calculation ............................................................. 50

    7.1.1 Equal Friction Sizing Method...............................................................50

    7.1.2 Sizing and Balancing with dampers .......................................................52

    7.1.3 Sizing and Balancing without dampers ...................................................52

    7.1.4 Static Regain Sizing and Balancing without dampers...................................53

    7.1.5 Static Regain Sizing and Balancing with dampers.......................................53

    7.1.6 Verification of existing duct system ......................................................54

    8 REPORTS .........................................................................55

    8.1 Sizing Report Printout ................................................................... 55

    8.2 Bill of Material Report ................................................................... 57

  • 10

    PREFACE This manual will introduce you to all aspects regarding Duct network drawing and sizing calculation with Mc4Suite Duct Module.

    The program allows the user to draw the air duct network (supply and/or exhaust) using rectangular, circular and flexible ducts, and place the diffusers in each ventilated space. The user draws lines only (axis of duct or one of face axis) and the program will create the 3D model automatically. Plus, the program is able to create also the 3D model for each type of fittings (Tee, Elbow, Cross, etc.) allowing the user to customize them (dimensions, radius, type of junction).

    Once a duct network has been drawn, it is possible to size it according to two different calculation methods:

    Equal Friction Method

    Static Regain Method

    After calculation it will be possible to balance the air duct distribution with or without regulation damper.

    Finally, it is possible to obtain any plant view, for every floor inserted in the project, any cross section and isometric view. Plus, the program produces the reports for calculation and material list.

  • 11

    1 GETTING STARDED

    1.1 Overview

    The users manual is designed to help you get familiar with McSuite 2006 Duct Module. Simply follow the manual and perform all of the steps in the same order as described here. This will guide you in a duct project drawing.

    It is possible to find additional information in the Mc4Software documentation:

    o Mc4 Software Tutorials;

    o On-line Help;

    o Sample movies and technical newsletters;

    o On-line technical support;

    o Internet website www.mc4software.com;

    o Mc4 Software trainings and meetings

    Warning! Please note that User manual has been developed in I-P system only. If you are unfamiliar with I-P system units, we recommend you to use the Tutorial as a learning tool and simply input the numbers as shown here. You will easily transition to Metric system on your real-life project. Unit measurement system can be switched fro IP to SI mode in each moment by using the specific command.

    Mc4 Suite requires AutoCAD 2006 or later installed in your computer. If AutoCAD works on your PC, so does Hvac Cad. If you have not AutoCAD 2006, Mc4 Software provides full software packages including AutoCAD 2006 OEM.

    Mc4Suite hardware and software requirements are following:

    o Windows 2000 Professional - Windows XP (Professional, Home Edition, Tablet PC Edition)

    o CPU Pentium III 800 MHz

    o RAM 256 Mb (recommended 512 Mb )

    o 500 MB free disk space for installation

    o VGA video or higher

    o Monitor resolution 1024x768 with True Colour (16.8 million colours)

    o Internet Explorer 6.0

    o CD-Rom Drive

    To apply Mc4Suite successfully, you need some AutoCAD knowledge. Basically, needs to know how to:

    open and save drawings;

    use zoom command;

    pick a single entity;

  • 12

    select entities using select objects options;

    pick a point on the screen;

    Input a numeric and alphanumeric value in the dialogs and in the command prompt area;

    Optionally, you may use AutoCAD move command to improve the presentation of the final drawing, and layer and plot commands to produce a hard copy of the drawing.

    1.2 Installing and Launching Mc4Suite Duct Module

    In case of problems installing the software, contact Mc4Software Technical Support at www.mc4software.com/Technical support.

    Insert the Mc4Suite 2006 CD into your computers CD drive.

    In a few seconds, the installation program will run automatically. If it does not run, the auto run feature may be turned off on your system. You can still run the install program manually.

    Go to operative system Start button and select option.

    Type [D]:\setup.exe (where D is your CD drive) and press .

    While the install program is running, just follow the instructions that appear.

    After computing the space requirements click the 'Next' button.

    Read and Accept the Mc4Software EULA then click the 'Next' button.

    Select installation type and click the Next button.

    If you want to change either the Program installing folder or Working Directory, specify the new location at this step by clicking on the input box and typing the correct path (include the drive letter if appropriate). You may also click 'Browse' to choose a directory. When the drive and directory are set, click on the 'Next' button.

    Continue by following the instructions on the screen and clicking the 'Next' button to proceed. You can go back to a previous screen by clicking the 'Back' button. At the end of the installation process, a pop-up window will appear to let you know you are done. Click OK.

    Double click on the shortcut that was placed on your desktop or click on the Windows Start button then select Programs, Mc4Software, and Mc4 Suite 2006 from the menu to run Mc4 Suite 2006.

  • 13

    2 INTRODUCTION

    It is possible to use duct module with or without building input (stand alone). In this case we suggest the user to fill out the level form and insert the architectural plan, if available, in order to use the objects filter by level. This feature is really important to better understand what being drawn and at which level.

    Following two figures show a duct net distribution through two levels and how the automatic filter by level works. In the first figure a cross section is shown. In the second figure are show first and second floor only, and the program filters automatically the part of air duct net has to be displayed.

    Cross section view

    Floor 2 Plant view

    Floor 2

    Floor 1

  • 14

    Floor 1 plant view: the program shows just the air duct have been drawn in this floor

  • 15

    3 SEQUENCE OF OPERATIONS

    Figure below shows a typical approach to the duct design.

    Figure 3.1 - Duct drawing: Typical approach flow chart

  • 16

    4 ARCHIVES

    4.1 Duct Project Archives

    Duct Project Archive appears when Project Data Duct System.. command is running, or when the user select Add to project option in the side bar Duct section (see figure below).

    Figure 4.1 - Duct Project side bar

    It is necessary to define a duct project record for each AHU. The program allows the user to draw supply and return duct net for each AHU/Duct project.

    Duct Project Archive mask is displayed in the figure below.

    Figure 4.2 - Duct Project Archive - Design Data Form In this mask three buttons and two tabs are present. Three buttons are helpful to create a new project button, a delete one already present, button, and a create a new one by copying . When a new project is being inserted, the program shows the box message mask where enter a description.

    In the project mask, two tabs are present: Design Data and Curvature Radius.

    In the first one, all general information is present. The program fills up the form using default data; the user can change it at any time.

  • 17

    DESIGN DATA TAB

    For reference see fig.4.2.

    Followings input data field are present:

    Unit: Select an AHU if present or create a new one. AHU list will be not empty if an AHU has been sized with the program (heating and/or cooling load calculation with air ventilation system). If empty, create a new one by selecting Add to project option.

    Designer: select a designer from the list, if desired;

    Name: Enter a description for the project;

    Supply\Return color: Select the default color for supply and return duct net from drop down menu;

    Air temperature and R.H.: Thermo-Hygrometric Moist Air conditions. The program uses these parameters to calculate air density and air viscosity used for the head loss calculation;

    Internal Coating: This data is a detail printed in the report. It is not used for calculation;

    Duct Roughness: Enter a average value of duct roughness. It is involved in the head loss calculation;

    Height/Width Ratio: this is ratio between height and wide of rectangular duct used by the program in the automatic sizing;

    Maximum Width and Maximum Height: These values represent the dimensions limits for duct sizing;

    Circular Duct Approximation [n]: this the quantity of lines used for circular drawing resolution;

    Thickness: Enter the total thickness of duct. In case of insulated duct, the insulation thickness has to be included;

    Converging/Diverging Angle: Angle value is shown in the figure 4.3. Default value is set in the Duct Project mask and the user can modify it;

    Figure 4.3 - Converging/Diverging Angle

  • 18

    Flange Height: enter the height of the flange in order to obtain a realistic duct drawing;

    Duct Section Length: it represents the length of the duct. This is the distance between two flanges;

    ELBOW RADIUS DEFAULT VALUES

    Figure 4.4 - Elbow Radius Default Values

    In this mask the user sets the radius of elbow based on the width of the duct. In this case, as shown in the figure, the program will use a 4 inches radius if the width of duct is less or equal to 10 inches.

    4.2 Air Outlet Archive

    Run Data Base - Air Outlet command in the main drop down menu. The program will display the mask of the archive that contains two tabs: Project and Database.

    Copy the diffusers which will be inserted in the project from Database tab to the Project tab; to do so, select the diffuser and click on button.

    If it is necessary to insert a new article in the archive, it needs to insert it in the Project tab and then it will be possible to store it in the Database tab using button.

    The mask contains three areas:

    List of articles stored in the archives

    Image of diffuser

    List of dimensions for each type of diffuser

  • 19

    Figure 4.5 - Diffusers Database

    To insert a new diffuser select the Project tab and click on button. If the user did not use a template file, the list is empty at first access to this mask.

    While this command running, the program shows the message box where enter the description of diffuser (see figure below).

  • 20

    Figure 4.6 - New Article in the diffusers Archive

    After description entering, click on to register the new record. The program will copy the description in the relative field on the right side of the mask. Once the description has been entered it is necessary to select the type of diffuser from the apposite drop down menu (see figure 4.7) between available options. According to selection the program will display the image of diffuser in order to better understand all the required dimensions helpful for drawing.

    In our example, Round type of diffuser has been selected.

    At this point it needs to insert all different sizes for this diffuser. To do so, use control buttons present in that section of the mask and shown in the figure 4.8.

  • 21

    Figure 4.7 - Diffuser Type Selection

    Press and the program will insert a new row.

    Figure 4.8 - Sizes of diffusers

    Insert an identification code for each size. Plus, it needs to enter the maximum air flow rate and the relative head loss in order to allow the program to calculate the Kv coefficient based on following formula:

    PQKv

    =

    where Q is the air flow rate and P represents the head losses. Kv value is almost constant for different flow rate values. Therefore, the program can use it to calculate the head losses with a different air flow rate.

    The program is also able to select automatically the size of diffuser according to the flow rate of the room, or the flow rate typed manually from the user.

  • 22

    For instance, if in the database there are two diffusers like displayed in the figure 4.8, the program will select one of them based on following criteria:

    if Q 100 cfm, the diffuser selected automatically will be Diff-1;

    if 100 < Q 200 cfm, the diffuser selected automatically will be Diff-2;

    if Q > 200 cfm, the diffuser selected automatically will be Diff-2 because it is the last one of the list.

    In order to draw the diffuser with the real scale factor, it is necessary to specify all dimensions in the apposite fields (connection diameter, exits diameter, etc.). Of course, the quantity and the type of fields where enter the dimensions, depend on the type of diffuser.

    button orders the diffusers based on the maximum flow rate, from the smallest to biggest one.

    4.2.1 Manufacturer Archive

    By selecting option in Manufacturer drop down menu, it is possible to activate the Manufacturers managing mask (see figure below).

    Figure 4.9 - Manufacturers Archive form

    For each record it is possible to enter all information available. Like all databases present in the program, click for saving the record into the database in order to use it again in a different project.

    4.3 Standard Sizes Archive

    The archive already contains a list of commercial sizes used by the program for sizing (see figure 4.11).

    While duct sizing calculation is running, the program displays the mask shown in the figure 4.10. By enabling the check button No Standard Dimensions the program will not use the dimensions

  • 23

    present in the Archive but it will find the right size of duct increasing step by step the minimum value specified in the apposite field.

    Figure 4.10 - Sizing Form

    If that check control has been not enabled, the program will use the dimensions registered in the Archive.

    Figure 4.11 - Duct Commercial Sizes

  • 24

    If we do not to use a particular size, it is sufficient to cancel it from database or modify the value inserted.

    To add dimensions click on button. The program will insert a new record and the cursor is focused on the new cell: type the value in the unit of measure shown on the top of the columns.

    4.4 Fittings Archive

    All fittings inserted in the program are grouped by type and each one of them is linked to an explaining picture where it is possible to find also the ASHRAE referring in order to evaluate the local loss coefficient C0.

    For every fitting the program contains a form where set its own properties. Run the command Database Duct Fittings in the main drop down menu and the following mask will appear:

    Figure 4.12 Fittings Form

    In this mask it is possible to distinguish three areas:

    Area #1: (left side of mask) it contains the list of available fittings. On the top we can find a drop down menu helpful for filter (it contains all categorizes: Elbows, Tees, Wyes, etc.). The user cannot add a new fitting.

    Area #2: (middle of the mask) the picture of the fitting is displayed;

    Area #3: (right side of mask) all technical information and all alternative fittings useable with the focused one, are displayed. Fields contained in this area are following:

    Code: code of fitting;

    Type: description of fitting. The same description is displayed on the list of fitting but the user can modify it in this field only;

    Category: category of fitting. It is helpful when a filter is active;

  • 25

    Section Type: it is a code to specify the type of sections for each fitting

    N of exits: relative to the main duct, the number of exits.

    ASHRAE reference: code referred to the ASHRAE Handbook helpful to evaluate the local loss coefficient C0;

    Alternative fittings: code of fittings used automatically by the program when it has to redraw the net after modification.

  • 26

    5 AIR DUCT DRAWING

    5.1 AHU Placement

    Run Mc4Suite Duct Air Handling Unit command from drop down menu (or click on in the tool bar) and the side bar shows all necessary information for drawing (the type of AHU, Z coordinate).

    The side bar is shown below.

    Figure 5.1 - AHU Drawing: side bar

    Here, the user has to select the AHU from drop down menu and enable the check control to place the object up on the ceiling of the current level (the program will calculate the Z value automatically).

    If the list of AHU is empty it is necessary to select Add to project option in the drop down menu to display the mask which allows the user to define the AHU graphical data correctly. The mask which will appear is shown in the figure 5.2.

    In this mask it is possible to find five sections containing general and graphical data:

    General data: it contains four fields where enter the description of the AHU (Type), the Abacus Code which will be used in the label and in the Bill of Material form, the Manufacturer and the Net Air Flow Rate (this value is just a data for the AHU, it will be not used for calculation);

    Dimensions: here needs to specify the dimensions of the body referred to the figure shown in the middle of the form;

    Supply connections: enter the dimensions of the supply attachment and its position (Lateral or Top). First supply duct net attached to the AHU will have these dimensions;

    Exhaust connections: same thing as supply connections, but for return duct net;

    Primary Air connections: AHU drawing includes also an attachment for renewal air (for instance, when the air system includes also an air changing). Enter the dimensions of the attachment in order to obtain a realistic drawing and a correctly occupied spaces evaluation.

  • 27

    Figure 5.2 - AHU graphical data form

    The graphical object drawn by the program is shown in the figure below, where it is possible to better understand the dimensions of the body and attachments.

    Figure 5.3 - AHU details

  • 28

    5.2 DUCT Drawing

    To draw the ducts needs to run following command Mc4Suite>Ducts>Duct from drop down menu or straight from tool bar:

    Figure 5.4 - Duct drawing commands

    While the command is running, the side bar shows the property of the duct which has being drawn.

    Figure 5.5 - Duct drawing - Side Bar

    In the duct project mask it is possible to create more than one project so, before starting drawing make sure the current project is that one desired. Current projects are shown in the side bare represented in the figure 5.6. In the list of projects is always available Add to project option in order to open the relative manager mask.

    Figure 5.6 - Current Projects Bar

  • 29

    Distribution Line: in the same duct project it is possible to draw both supply and return (exhaust) duct distribution, so here it is necessary to specify if the duct has being drawn belongs to the supply or return duct net;

    Air Direction: two options are available: Downstream and Upstream. It is necessary to select Downstream when the user is drawing a duct starting from AHU to Diffuser or from a main duct to a branch. Upstream has to be select if the drawing direction is the opposite. It is necessary to meet this requirement because the air flow direction has to be from fan to diffuser in the supply duct net, and it has to be the opposite in the exhaust duct distribution. In case of error, during the sizing calculation the program will display a warning text message;

    Figure 5.7 - Air Direction Setting

    Figure above should make clear the criteria used for duct drawing. Both of ducts shown in the figure have been drawn from right to left (see starting and ending point). Arrow indicates the air flow direction.

    Fixed Z coordinate: in the pull down menu three options are available:

    Nothing: Z coordinate of the duct has being drawn is free. That means if the user use an OSNAP to an object, the Z coordinate of the duct will be the same as the object. Therefore it is necessary to select this option when the starting point of the duct has to be the AHU attachment or another duct;

    Absolute Coordinate: to draw a duct at certain height from the ground (from Zero) it is necessary to select this option and type the value of the height in the next field (Z field).

    Relative to ceiling: in this case the user has to select the correct level and digit in the Z field just the distance between the interior part of the ceiling and the axis of the duct.

    Z[ft]: the value entered in this field depends on the previous selection (previous field).

  • 30

    Figure 5.8 - Duct Z coordinates example drawing

    To make clear the interaction between the two fields just above described, we can do an example referring to the figure above shown. To draw the ducts both in the basement and main floor it is possible to set the parameters as follow:

    Fixed Z coordinate = Absolute coordinate Z [ft] = 7.25 (duct in the basement) Z = 17.25 (to draw the duct in the main floor)

    Fixed Z coordinate = Relative to ceiling Z [ft] = - 1.00 (for both basement and main floor), but it is necessary to select the current level correctly.

    Section type: select the type of the duct between rectangular, round, flexible;

    Rotated: if this check is enabled the program rotates the duct so the program switches width and height dimensions. Of curse, this option makes sense with rectangular duct only;

    Dimensions: dimensions of the duct have being drawn. This section contains two fields where typing Base/Diameter and Height. Use Base/Diameter field to enter a diameter of the round/flexible duct. If the user does not fix the value here entered, the program is free to modify them after sizing calculation in order to meet the fluid-dynamic conditions specified in

    the calculation mask (max P/ft and max air velocity in the main and branch ducts).

    Thickness: thickness of duct. It may include the thickness of the insulation.

    Line: specify the horizontal and vertical relative position of the line being drawn. The user will draw just lines as ducts; the program will create automatically the 3D model based on the dimensions and the line position. See the figure below to better understand how to use this feature.

  • 31

    Figure 5.9 - 2D - 3D Lines Position Correspondence

    In the figure below is shown difference between right and left horizontal line in a plan view.

    Figure 5.10 - Horizontal duct line settings Plan View

    Instead, in the following figure is displayed the difference between Top, Center and Bottom vertical duct line.

  • 32

    Figure 5.11 - Vertical duct line settings

    Fittings: For every type of fitting (Elbow, Tee, Wye, Cross) it is possible to select which one the program has to use while drawing. Available choices for every type of fitting are Dynamic, Semi-Static and Static. Dynamic fittings have a lower local loss coefficient; the Static ones have a higher value of C0.

    Duct Layout can be executed by launching duct command and using the mouse tracking to draw lines. It is possible to draw horizontal, vertical and sloped ducts.

    While the command is running, in the prompt line following options will be displayed:

    From point: place the cursor in the starting position and click the mouse. This option is available at every first access to the command;

    Specify next point [up/down/rx/ry]: all these options will be available after first click. Select the second point with a mouse left click or select:

    o Up: to draw a vertical duct from starting point to a higher point. Enter the length of the duct;

    o Down: to draw a vertical duct from starting point to lower point. Enter the length of the duct;

    o Rx,Ry: helpful to rotate the AutoCAD axis in order to allow the user drawing with an isometric view. Axis rotation is necessary because AutoCAD allows the user to draw in XY Plan only.

    If an AHU has been inserted, the first duct connected to it will have the same dimensions as the AHU attachments. Duct dimensions will be locked until the first node. The program creates a node where the direction of the duct changes or where the user clicks with the mouse. Therefore, we suggest user to draw a little duct in order to allow the program to insert the

  • 33

    transition fitting immediately after AHU, also because this is the most common type of installation.

    To start correctly from the AHU it is necessary to activate the AutoCAD OSNAP tool. To do so, it needs to open the manager mask by right click on the Osnap button placed at bottom of the screen and by selecting Settings option in the menu which will appear. We suggest you the configuration shown in the figure 5.12.

    Figure 5.12 - Suggested OSNAP settings

    Plus, it is necessary to do not lock the Z coordinate so, in the side bar it needs to select Nothing in the Fixed Z coordinate field. The program will fill out the Z field automatically showing the Z value of the attachment.

    Plus it is possible to check out the Z-values at bottom of the screen where AutoCAD shows X,Yand Z coordinate. The unit of measure of those numbers is Drawing Unit, instead, in Z field it is possible to see straight the value expressed in feet [ft] (it is calculated as drawing unit x scale factor).

    Figure 5.13 - AHU - Duct connection sample

    5.3 Diffusers drawing

    The command which allow the user to insert diffusers in the project plan is Mc4 suite - Duct Diffuser from drop down menu, or through the apposite icon in the tool bar.

  • 34

    Side bar is shown here below.

    Figure 5.14 - Diffuser drawing: side bar

    Distribution line: Select the type of the duct distribution between Supply and Return;

    Pre-code + Progressive: to associate a numerical code to the terminal. It could be helpful for the calculation report checking.

    Type: Select in the pop up menu the type of diffuser. The program will show, in the article type field the terminals belong to that category only.

    Article Type: Select desired diffusers producer. Of course, these terminals have to be inserted in the database;

    Flow Rate [cfm]: air flow rate through the terminal. The program will accept the value here entered and it will size the terminal based on this flow rate only if the terminal will be inserted outside building, or if in the room is not present a ventilation calculation. If the flow rate value is fixed (fixed check box enabled) the program will use it even a ventilation calculation has been executed.

    In order to make clear how the program works, please, follow the example. Consider a room where the ventilation flow rate is 150 cfm. In the figure below, two diffusers have been inserted on the room and the program divided the air rate automatically (75 cfm per each).

  • 35

    Figure 5.15 - Duct Sharing data - Diffuser's flow rate

    It is also possible to fix just one or both diffusers flow rate. For instance, in the same sample, if the user fixes the rate of the first diffuser at 90 cfm; the second one will be sized for 60 cfm automatically (see figure 5.16). Of course, it is possible to fix both of flow rates, regardless of calculation.

    Figure 5.16 - Fixed flow rates

    A/D B: Dimensions of selected diffuser. In case of round diffuser, field A/D will show its diameter;

  • 36

    Pressure drop: Head loss thorough the diffuser.

    Junction section:

    Diffusers can be inserted on the duct at any position (along or at the end of the duct) by using the apposite OSNAP (nearest, endpoint). To do so it is necessary to enable following check field:

    Connected to duct: If this check is enabled the user has to select a duct for diffuser drawing (by using OSNAP tool). In this case the program will create automatically the connection branch between selected duct and diffuser. To place the diffuser whenever, but not connected to the duct (it is possible to create a connection after duct drawing), needs to do not activate this control.

    Connected to duct = Enabled

    Figure below shows the result of drawing based on the side bar settings. If the Distance from duct is null, the program will place the diffuser at the end of the duct; in this case the field Angle is not involved in the drawing.

    Figure 5.17 Diffuser drawing: side bar settings

    Distance from duct: referred to the value of the angle entered in the next field, the program will draw a duct using this value as a length;

    Angle: this field can be used in two different ways depending on the Distance from duct is null or not:

    Distance from duct null: two values are available: 90 - 270 referred to the duct direction;

  • 37

    Figure 5.18 - Angle value meaning with Dist0

    Distance from duct = null: angle value is involved if the diffuser along the duct (not at ending point). It is referred to the horizontal axis of the section view of the duct (see figure below). This feature is particularly helpful to place the grid diffuser straight on the duct (no connection duct is required).

    Figure 5.19 - Angle meaning with Dist=0

    Distance from duct/ceiling: enter the vertical distance between duct/ceiling and diffusers, depending on Connect to duct option is enable/disable

    Connected to duct = Not Enabled

    The diffuser can be placed wherever. The user has to connect them to the duct at another time. In this case fields Distance from duct and Angle are not involved in the drawing procedure. The user can set the distance from ceiling of the current level in the field Delta Z from the roof.

  • 38

    Figure 5.20 - Not connected diffusers drawing

    5.3.1 Diffusers multiple drawing (array)

    The program allows the user to cover a large area with diffusers by using just one command. Run Mc4 Suite Ducts Outlet/Inlet Array from drop down menu (see figure below).

    Figure 5.21 - Diffusers Array Command

    While this command is running, in the side bar it is possible to set all parameters helpful for drawing.

  • 39

    Figure 5.22 - Array diffusers command

    The user has to specify the distance between diffusers perpendicularly and parallel to the selected wall (Parallel Dist/Perpendicular Dist). Plus, it needs to specify the height of installation of diffusers (distance from ceiling, from floor, absolute Z coordinate) in the Position field and the Delta Z value.

    To place the diffusers, it is necessary to click the mouse twice: first click to indicate the area (click wherever in the room space), second click on a wall line to indicate the direction of displacement.

    5.4 Diffuser-Duct connection

    As before explained, if some diffuser has been inserted by using the free way, it means it is not connected to any duct, it is necessary to link them to the duct for sizing calculation. To do so, two commands are available: the first one allows the connection terminal by terminal; the second one allows connecting more than one diffuser to the same duct, simultaneously.

    To use the first command, run Mc4 Suite>Ducts>Join Outlet/Inlet command from drop down menu, or from tool bar.

  • 40

    While the command is running, it needs to select the diffuser and then the duct has to be connected. The type of duct will be brawn automatically by the program for connection will be the same as the last one used during the drawing, with the same type of fittings.

    The connection between duct and grid terminal or linear diffuser will be drawn only if they have been placed at same height from the ground. Instead, for round and/or square terminal, the connection will be drawn only if they are not at the same level; in this case the program will draw also the vertical branch.

    5.5 Legend drawing

    Run the command Mc4Suite>Legend.

    The program displays a form where it needs to select, in the drop-down menu, the Type of the legend (Duct-Diffusers).

    Once the type of the object has been choice, it is necessary to select the Layout of the legend and then the name of the duct project (if the project will be selected is not the current one, the legend will be placed in the drawing but it could be not displayed if the project is off).

    The field project has a different means according to the selected object. That means that a floor will be a project when the room is the selected object. For Air and Hydronic System the project is the same as the pipe or duct project.

    Once the selection form has been filled out, it is possible to draw the legend. To do so, it is necessary to click in the working area to pick the point where the legend has to be placed.

    Note: the details printed in the legend are not dynamics. So, if something in the project will change once the legend has been drawn, it is necessary to redraw it for updating.

  • 41

    6 EDITING

    All object information can be displayed and modified, if required, in the details mask. To open this form it needs to follow these simple steps:

    Select the object (multiple selection is allowed)

    Right click on mouse to show the quick drop-down menu

    In this menu it is necessary to select Extended Data option

    The program will adapt the mask according to the selected object. When more than one object has been selected, common field (property) will be filled up with a blank space. If the user changes those properties, they will be assigned to all objects.

    Please, close the mask by clicking button for confirmation.

    6.1 Duct Details

    The mask containing all details will appear by selecting the line and running Extended Data command, as explained in the previous section. Instead, to edit the property of the fittings it needs to select the fittings in the 3D model view.

    Duct Extended Data mask contains four tabs: Technical Data, Axis Data, Calculation and Label.

    TECHNICAL DATA

    Details shown in this mask are following:

    Figure 6.1 - Technical Data tab

    Width, Height: dimensions of selected duct. If a calculation has not been executed, these dimensions are those one used during the drawing. After calculation the program will adapt them, if necessary, according to the total flow rate and the maximum air velocity allowed. When the check fixed has been marked, the dimensions will be kept also after the calculation, the program will not modify them. It is possible to fix just one of them; that means that the program will adapt the remaining one.

  • 42

    Length: length of the duct coming form the drawing. The user cannot edit or modify the length in any way. For all transition fittings, instead, it is possible to edit and fix this value manually in this mask. Default value of the angle is contained in the duct project mask. The program uses that value while the user is drawing.

    Joint Type: program show the type of the joint for the inlet and outlet section of selected duct. Flanged, Welded and No Joint are the three available options.

    Code: Code of the duct. We have 310R for rectangular duct, 310C for circular and 310F for flexible duct.

    AXIS DATA Tab

    All Details Data shown in this tab are following:

    Figure 6.2 - Single-Line Data tab.

    Line: explain the position of the line relative to the duct. It is helpful to place the duct in the right position.

    Rotated: when marked it rotates the duct by switching the width and height dimensions values.

    Label Visibility: default option is If required. Additional two options are available: Never and Always. In the first case the program will show the label just if required, because if the duct is connected to another one having the same dimensions, probably is not necessary to show twice the same information. Instead, if Never/Always has been selected, the program hides/shows the label regardless.

    CALCULATION DATA Tab

    Program fills up this tab just after calculation. All data cannot be modified by the user, it is just a control mask.

  • 43

    Figure 6.3 - Calculation Data tab

    Program displays the head loss through the duct and its rate and air velocity (important for noise).

    LABEL

    In this mask it is possible to set the type of label (user can customize it by let it showing all information desired) and lock his position even the program will redraw it for updating (use this feature after layout setting).

    Figure 6.4 - Label Tab

    6.2 FITTINGS DETAILS

    In the next section all detail data mask regarding the fittings will be shown. All masks will be almost the same as the duct one. Technical data mask will change because it has been adapted to the specific fitting (transition has different parameters than Tee, for instance).

    So that, in the next section just the technical data tab will be treated, the rest of the tabs are not different than the duct one.

    6.2.1 Transition

    The program will use it automatically when the dimensions of duct change or when there is transition from rectangular/square to round ducts or vice versa.

    This type of fitting can be symmetric or asymmetric. Figure below shows the two different scenarios.

  • 44

    Figure 6.5 - Symmetric and Asymmetric Transitions Fittings

    Figure above shows the two situations mentioned before. The user can select the type of fitting by setting the property of the duct Axis.

    Details tab shows following information about this type of fitting:

    Figure 6.6 - Transition Fitting: Technical data Tab

    Dimensions for inlet and outlet section can be managed through the relative duct sizes (because they will be the same as the duct), so they cannot be modified in this mask.

    The user can set the type of joint and the angle of the converging/diverging fitting. The default value of this angle is set in the duct project mask and it can be modified at any time.

    The code of the fitting is 273R.

    6.2.2 Elbow

    The user can decide the type of fitting (dynamic, dynamic with vanes or static) at drawing time in the side bar (see figure below).

  • 45

    Figure 6.7 - Elbow Fittings

    Any way, it is possible to change the type also after drawing through the details data mask where it needs to select another fitting code.

    Figure below shows the detail mask for an elbow.

    Figure 6.8 - Elbow Detail Mask - Technical Data Tab

    The user can set the dimensions (width and height) of the inlet section because the outlet section will have the dimensions of the duct connected with the elbow.

    Besides, it is possible to change the internal radius by typing the value and by enabling the fixed check.

    To change the type of fitting (elbow or with tap) please select a different type from the relative drop-down menu and by selecting the relative code.

    6.2.3 Tee

    As well as the elbows, for the TEE fitting it is possible to have three different types of fittings: Dynamic, Semi-Static and Static. Figure below shows the difference between them.

  • 46

    Figure 6.9 Diverging TEE fittings

    Figure below, instead, shows the details it is possible to check through the details manager mask. It is possible to change all accessible properties, the rest are just for checking.

    Figure 6.10 - TEE Data Mask

    All information have been highlighted in red are changeable: inlet section dimensions, type and relative height of joint, code of fitting. By changing the code the type of fitting will change (to static or semi static type).

    6.2.4 Tee Branch

    Three types of tee branch are available, as shown in the figure below. Select it while a duct is being drawn or after in the detail manager mask.

  • 47

    Figure 6.11 Diverging TEE Branch

    6.2.5 Tee Cross

    Figure below shows all available types of fittings.

    Figure 6.12 - Diverging TEE Cross

    6.3 Diffusers Details

    As well as every detail mask contained in the software, to open the diffuser information mask it needs to select it and then to select Extended Data option from the short cut menu that appears when right-click.

    The mask contains two tabs, all diffuser information is shown in the Outlet tab, and instead the label mask permits the selection of the label.

    The Outlet tab is displayed in the figure below.

  • 48

    Figure 6.13 - Diffuser Extended Data - Outlet Tab

    Here it is possible to modify some diffusers data that are already inserted in the project:

    Article Type: this is the description of the diffuser (manufacturer) has been selected from the database.

    Model: each type of diffuser more than one model might be available (size). The program selects it according to the rate but the user can select a different one in this mask (once it has been drawn) or while it is being drawn.

    Code: this code will be used in the bill of material stage.

    Flow Rate: this field shows the flow rate through the diffuser. This value can be calculated automatically by the program if the building has been drawn and the ventilation calculation has been run. If not the designer has to specify it manually. However, it is possible to set this value differently than the calculated one; to do so it needs to mark the fixed check placed near the field.

    Loss: Head Loss through the diffuser.

    Label Visibility: if marked, the label of the diffuser, with all information the designer wants to show, will be displayed.

    Duct Alignment: if the axis of the duct will be changed, the diffuser could not be aligned with the duct self. If this control is marked, the position of the diffuser will be adapted to the new situation automatically (automatic alignment).

    In the second tab it is possible to select a different type of label from the label database, showing different information, and fix its position by marking the relative check present in the second row.

    Figure below shows how the tab looks like.

    Figure 6.14 - Diffuser Extended Data mask - Label Tab

  • 49

    7 CALCULATION

    Calculation options depend on the type of the duct net is being sized (supply or exhausting).

    Following figures (calculation masks) summarizes all available calculation for both systems (supplying exhausting):

    Supplying:

    Figure 7.1 - Calculation Mask - Supplying

    Exhausting:

    Figure 7.2 - Calculation Mask - Exhausting

  • 50

    To run the calculation command it needs to execute the Calculation>Duct System command from the main drop-down menu, or click on the relative icon on the duct tool bar.

    Figure 7.3 - Duct Tool Bar

    Once the command is running two different options are available to the user:

    1. Select a duct in the drawing area by clicking on it

    2. Select Supply between all available options present in the command line.

    In the first case the program will size all ducts are included between the selected one and the rest of the distribution system (toward diffusers).

    The second option, instead, is available if the duct system has been connected to the AHU only. In this case the software will size the entire duct distribution.

    In the next sections will go through every mask has to be filled out in order to provide the software all information needed for the calculation.

    7.1 Supply Air Duct Calculation

    7.1.1 Equal Friction Sizing Method

    The first available option in the calculation mask allows the user sizing the system with the equal friction method. Using this method, ducts are sized for a constant pressure loss per unit of length.

    Figure 7.4 - Friction Chart for Round Duct - Font: ASHRAE

  • 51

    The shaded area is the suggested range of friction rate and air velocity. The choice of the value depends on the cost of the energy and the cost of installation and material. Lower is the energy cost then higher can be the friction loss. Instead, if the installation cost is economical, the friction loss can be low (larger ducts will be required).

    In the program, once selected the first available option (sizing), it needs to click on button in the right lower corner of the mask.

    At this time, the mask shown in the figure below will be displayed.

    Figure 7.5 - Sizing Calculation Mask

    In this mask it is possible to distinguish two different sections.

    All information about sizing calculation have to be specified in the Input General Data where it needs to specify the friction loss (ft of water/100 feet) and the air velocity limits (ft/s) the program has to meet, for the main ducts and the branches. Ducts will be sized according to these limits.

    If not otherwise specified, the standard dimensions of the duct will be used (the ones present in the database). Instead, if the check highlighted in the figure above the program will not use the standard dimension. In this case, it will find the best solution starting from the value specified in the Minimum Dimension, and increasing that value at any repetition (iterative calculation) in the amount has been specified in the Dimensional Spacing field; in any case the dimension will not go over the limit specified in the Maximum Dimension field.

    Once everything have been set, click on arrow button; the next mask that appears will show the result of the calculation (see figure below).

    Total pressure value is the head pressure has to be provided by the fan, with the total flow rate.

    Results mask shows also the code of the most demanding diffuser and the total unbalancing between this diffuser the less demanding one. Based on this value, the designer has to decide if a balancing is required or not because higher is this value and higher will be the difference between the theoretical and real flow rate to the diffusers (this affects the real temperature/RH in the diffuser surrounding zone).

  • 52

    Figure 7.6 - Results Mask

    7.1.2 Sizing and Balancing with dampers

    Through this type of calculation the program will insert a damper where it is needed and calculate the drop pressure it has to provide. The calculation mask looks like the one displayed in the figure 7.5, just the section dedicated to the balancing calculation is also active (see figure below).

    Figure 7.7 - Balancing Data

    The first field contains the minimum allowable unbalancing value; that means that if the unbalancing is higher than this value the program has to find the best dimensions of the duct to reduce this gap (smaller duct dimensions).

    Instead, if the unbalancing is higher than the value typed in the second field, the program has to insert the dampers where needed. Therefore, if the two values are the same, the program does not change the duct dimension but it adds just dampers.

    7.1.3 Sizing and Balancing without dampers

    Same thing as described above, but in this case the first field only is active (just one parameter has to be specified). The program does not add any damper but it tries to find the best dimensions for not included in the most demanding path.

    Figure 7.8 - Balancing Data - No Dampers

  • 53

    7.1.4 Static Regain Sizing and Balancing without dampers

    The objective of this method is to obtain the same static pressure at diverging flow junctions by changing downstream duct sizes.

    The calculation parameter mask is shown in the figure below.

    Figure 7.9 - Static Regain Sizing Mask

    The user has to specify the desired air velocity in the first duct downstream the fan (root section) in the Calculation Option section and the program will fill out the Test S1 section. In this section following field are present:

    D/De: it is the diameter D of the round duct or the Equivalent Diameter De of a rectangular duct

    B: it is the height of the first rectangular duct (connected to the fan)

    L: it is the width of the duct

    V: Calculated air velocity

    For this type of calculation the parameter Increment/Decrement is important because it is the maximum increment/decrement that the duct size has to have for the static pressure recovering. If this value is not typed, the program tries to recover the maximum allowable pressure; that means that the dimensions of the duct might be really large.

    If a standard dimensions have not to be used, it needs to mark the relative check and specify the range of the duct dimensions and increasing step use for the iterative calculation.

    Finally, in the balancing section, it needs to specify the air velocity at the end of the net system and the minimum allowed unbalance.

    Once finished, it needs to click on arrow button to run the calculation.

    At the end, the mask already displayed in the figure 7.6 will show up with all results.

    7.1.5 Static Regain Sizing and Balancing with dampers

    Calculation detail mask is the same as the 7.9 figures. In this mask the user has to set the minimum unbalancing allowed value. The program calculates the dampers and inserts them in the correct position.

  • 54

    7.1.6 Verification of existing duct system

    The last option is useful when the dimensions of the ducts have not to be changed (just head loss calculation). In this case, the fixing of the dimensions is not required.

    Plus, this option allows the balancing of the system. If the balancing check has been marked, it is necessary to specify the values for the minimum admitted unbalancing; when this value will be exceeded the program reduces the dimensions and inserts the dampers.

    Figure 7.10 - Verification Calculation Mask

    When all data have been set it needs to click on Next arrow button and the program calculates the head loss through the system and shows the results in the mask that looks like the 7.6 figures.

    Settaggi per le derivazioni 3722D e 3736

    I due rapporti indicati nei campi rbi/acb e ls/ac vengono utilizzati per il calcolo delle perdite localizzate nelle derivazioni con invito 3722D e 3736. In particolare si assume che le perdite che si hanno nelle derivazioni 3722D e 3736 siano essenzialmente dovute sul main a variazioni di sezione (allargamento o restringimento fittizio) e sul branch ad una o due curve a 90.

  • 55

    8 REPORTS

    In the File drop-down menu are available two options, for calculation and bill of material report creation.

    8.1 Sizing Report Printout

    Run File>Reports Output>Duct System command. While this command is running following mask will appear.

    Figure 8.1 - Reports Selection Mask

    The caption of the mask indicates the system information is being printed (Supply / Exhausting) and the current duct project name (Duct Sys in the sample displayed in the figure 8.1).

    The program shows the Supply System first and then the Exhausting one, regardless the supply duct net is present or not. If it is not present (the designer did not draw it), click on button to skip this step.

    Once the type on system has been choice, please select the type of information have to be printed: Dimensioning or Bill of Material; in this case select the first one. Select the language if necessary or leave English and then click on three dots button to set the path and file name the program will create. RTF is the file format; it is editable with MSWord or any type of word editor programs.

    Click button once finished and the program creates the report file and opens automatically this file by using MSWord. If this software program is not installed on the users computer, the file just created will be not edited; the user can edit it by using a different word editor program.

    The first part of the report contains all information about the designer and the project. The program will fill that form in automatically if the user filled up the relative form present in the program. However, it is possible to edit the file; that means that it is possible to add, change and delete all required data.

    In the second section, instead, all details regarding the design data and the calculation method has been used for dimensioning.

    At the end of this section, the numbering of the most request duct path is displayed.

  • 56

    Figure 8.2 - Design Data and Result Summary

    The designer can set the duct label in order to show the number of themselves (this is useful to find the most demanding path and to check the system out because there is a correspondence between report and drawing).

    To do so, run Database>Label command from the main drop-down menu to open the label manager mask. Here, it needs to select the duct label type in the upper section of the mask, and mark the check corresponding to Duct # label (see figure below) in the lower section.

    Figure 8.3 - Label Manager Mask - Duct Properties

    At any time the user can manage this information and show/plot everything has to be plotted or displayed. To speed up the modifying process it is also possible to create a New Label type and assign it to the ducts have been drawn.

    Warning: the number of the duct will be displayed after sizing report creation only.

  • 57

    Figure 8.4 -Duct Label Sample

    The second section of the report shows all fluid-dynamic information about the calculation for every single duct portion of the net (from node to node). Figure below displays a typical duct analysis printed in the report.

    Figure 8.5 - Duct Fluid-Dynamic Analysis

    The table shown in the figure above is replicated for each duct present in the project.

    8.2 Bill of Material Report

    Run the same command described in the previous section: File>Reports Output>Duct System. In the mask that appears select the second available option, Bill of Material, as shown in the figure below.

  • 58

    Figure 8.6 - Bill of Material Report

    Select the language and the folder where the file has to be created and type the name; click on button to confirm.

    At this stage the program shows a settings mask where the user can specify the thickness of the duct according to the shape (round, rectangular) and to the dimensions. Based on the thickness and on the type of material, the designer has to specify the weight of the duct, as well as the maximum length of them. The settings Mask look like the one shown in the following figure.

    Figure 8.7 - Bill of Material Settings Mask

    The details shown in this mask are following:

    Cross Section: Shape of the duct: Round or Rectangular.

    A: it represents the largest dimension of the rectangular and the diameter of it in case of round duct.

    L: Maximum allowable length for each duct trunk (between two joints).

    S. Thickness

  • 59

    Weight: Weight of the duct per unit of surface (footage).

    Glong: Type of longitudinal joint (along the axis of the duct);

    Gtrasv: Type of Joint between two duct trunk

    Click on button to create the file.