M-1
DRAWING NO.
MECHANICAL NOTES,LEGEND AND DRAWING INDEX
DRAWING TITLE
ISSUE
ISSUE FOR BID
10
/11/19
RENOVATIONS TO THE TREDYFFRINTOWNSHIP BUILDING
MEP - DRAWING INDEX
MD-1 MECHANICAL DEMOLITION FLOOR PLAN
M-1.1 MECHANICAL FLOOR PLAN - PHASE 1
P-1.2 PLUMBING FLOOR PLAN - PHASE 2
P-1.3
GENERAL SPECIFICATIONS
1. DRAWINGS ARE DIAGRAMMATIC. COORDINATE AND DETERMINE FINAL LOCATIONS OF SYSTEMS ANDCOMPONENTS IN FIELD. COORDINATE WITH ARCHITECTURAL DRAWINGS AND OTHER TRADES.
2. THE INTENTION IS FOR INSTALLATION OF COMPLETE AND OPERATING SYSTEMS. NOT EVERYCOMPONENT REQUIRED IS SHOWN. THE CONTRACTOR SHALL INCLUDE ALL COMPONENTS NORMALLYASSOCIATED WITH THE PARTICULAR SYSTEM. THE SYSTEM SHALL BE FULLY COMMISSIONED ANDSIGNED OFF BY AN OFFICER OF THE RESPECTIVE CONTRACTOR PRIOR TO FINAL OWNER ACCEPTANCETESTING. PROVIDE PERSONNEL TO ASSIST WITH OWNER ACCEPTANCE TESTING.
3. GIVE NOTICES, FILE PLANS, OBTAIN PERMITS AND LICENSES, PAY FEES AND BACK CHARGES, ANDOBTAIN NECESSARY APPROVALS FROM AUTHORITIES THAT HAVE JURISDICTION AS REQUIRED TOPERFORM WORK IN ACCORDANCE WITH ALL LEGAL REQUIREMENTS AND WITH THE DESIGN DOCUMENTS.
4. MATERIALS AND EQUIPMENT SHALL BE LISTED BY UNDERWRITERS LABORATORIES (UL) AND APPROVEDBY ASME AND AGA, AS APPLICABLE, FOR INTENDED SERVICE.
5. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS,TECHNIQUES, SEQUENCES AND PROCEDURES REQUIRED FOR SAFE EXECUTION AND COMPLETION OFTHE WORK AND FOR INITIATING, MAINTAINING AND SUPERVISING ALL SAFETY PRECAUTIONS ANDPROGRAMS IN CONNECTION WITH THE WORK.
6. ALL MATERIALS, EQUIPMENT AND METHOD OF INSTALLATION SHALL BE ACCORDANCE WITH THESTANDARDS, REGULATIONS, CODES, ORDINANCES AND LAW OF LOCAL, STATE AND FEDERALGOVERNMENTS AND OTHER AUTHORITIES THAT HAVE LAWFUL JURISDICTION.
7. IT SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO COORDINATE THE WORK UNDER THISCONTRACT WITH THAT OF ALL OTHER TRADES, INCLUDING, BUT NOT LIMITED TO, ELECTRICAL, HVAC,SPRINKLER, PLUMBING, STRUCTURAL AND GENERAL CONSTRUCTION. OFFSETS IN DUCTWORK,PIPINGAND CONDUITS AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THEOWNER.
8. EACH CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING REQUIRED FOR THE INSTALLATION OFNEW WORK UNDER THIS CONTRACT. CUTTING AND PATCHING SHALL BE COMPLETED IN A NEAT ANDWORKMANLIKE MANNER. PATCHING MATERIALS SHALL MATCH EXISTING MATERIALS TO THE GREATESTEXTENT POSSIBLE. PROVIDE TOUCH-UP TO MATCH EXISTING SURROUNDING AREAS OF CUTTING ANDPATCHING WORK.
9. INTERRUPTIONS TO EXISTING SERVICES AND SYSTEMS SHALL BE AS SHORT AS POSSIBLE AND AT ATIME AND DURATION APPROVED BY THE OWNER. INCLUDE ALL PREMIUM TIME ASSOCIATED WITHINTERRUPTIONS IN BID PROPOSAL. INTERRUPTIONS SHALL BE SCHEDULED WITH OWNER AT LEAST 48HOURS IN ADVANCE.
10. CONTRACTOR SHALL COORDINATE ITS RESPECTIVE CEILING MOUNTED EQUIPMENT AND DEVICES WITHOTHER TRADE CONTRACTORS PRIOR TO INSTALLATION TO AVOID CONFLICTS.
11. ALL DEBRIS SHALL BE CLEANED AND REMOVED FROM THE SITE BY END OF EACH WORK DAY. PRIOR TODISPOSAL OF EQUIPMENT AND MATERIALS, TURN OVER TO THE OWNER ANY REMOVED EQUIPMENT ANDMATERIALS REQUESTED BY THE OWNER.
12. WORK SHALL BE EXECUTED IN A WORKMANLIKE MANNER AND SHALL PRESENT A NEAT, RECTILINEARAPPEARANCE WHEN COMPLETED.
13. MAINTAIN MAXIMUM HEAD ROOM AT ALL TIMES. DO NOT RUN PIPES, DUCTS AND CONDUIT EXPOSEDUNLESS SHOWN AND NOTED TO BE EXPOSED ON DRAWINGS.
14. MATERIALS AND EQUIPMENT SHALL BE NEW, UNLESS NOTED OTHERWISE, AND INSTALLED ACCORDINGTO MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS SO THAT COMPLETED INSTALLATIONSHALL OPERATE SAFELY AND EFFICIENTLY.
15. EACH RESPECTIVE CONTRACTOR SHALL FIRE STOP ALL NEW AND EXISTING OPENINGS THROUGH FIRERATED FLOORS, WALLS AND CEILINGS WITH UL ASSEMBLIES OF EQUAL RATING. FIELD VERIFY EXISTINGCONDITIONS BEFORE SUBMITTING BID PROPOSAL.
16. COORDINATE ALL ROOF PENETRATIONS WITH WORK OF OTHER TRADES. ALL PENETRATIONS SHALL BESEALED WATERTIGHT. COORDINATE FLASHING REQUIREMENTS TO MAINTAIN ROOF WARRANTY.
17. MANUFACTURERS' MODEL NUMBERS ARE SPECIFIED SOLELY TO ESTABLISH STANDARDS OF QUALITYFOR PERFORMANCE AND MATERIALS.
18. SUBSTITUTED PRODUCTS SUBMITTED AND APPROVED FOR USE THAT NECESSITATE CHANGES TO THEWORK OF OTHER TRADES OF CONTRACT SHALL BE COORDINATED AND ARRANGED BY THE CONTRACTORWHO SUBMITTED THE SUBSTITUTION WITHOUT ADDITIONAL COST TO THE OWNER.
19. PRODUCT INSTALLATION SHALL ADHERE TO MANUFACTURER'S RECOMMENDATIONS AND INSTRUCTION.20. EACH RESPECTIVE CONTRACTOR SHALL PROVIDE PROPER ACCESS TO EQUIPMENT AND COMPONENTS
THAT REQUIRE INSPECTION, MAINTENANCE AND POSSIBLE REPAIR. ACCESS PANELS SHALL BE MINIMUM12"X12" OR AS NEEDED FOR PROPER ACCESS. ACCESS PANELS SHALL BE FURNISHED BY THISCONTRACTOR AND TURNED OVER TO GENERAL CONTRACTOR FOR INSTALLATION.
21. CONTRACTOR SHALL COORDINATE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS OF ALLAPPLICABLE EQUIPMENT WITH THE ELECTRICAL CONTRACTOR.
22. AS WORK PROGRESSES AND FOR DURATION OF CONSTRUCTION, MAINTAIN A COMPLETE SET OFCONTRACT DRAWINGS AT THE JOBSITE. RECORD WORK COMPLETED AND ALL CHANGES FROM ORIGINALCONTRACT DRAWINGS CLEARLY AND ACCURATELY INCLUDING WORK INSTALLED AS A MODIFICATIONOR ADDITION TO THE ORIGINAL DESIGN TURN OVER ALL OPERATING MANUALS, MAINTENANCEMANUALS, AND "AS BUILT" DRAWINGS TO OWNER AT CONCLUSION OF CONSTRUCTION.
23. DO NOT SUPPORT EQUIPMENT, DUCTWORK, PIPING, CONDUIT OR DEVICES FROM SUSPENDED CEILINGS.SUPPORT ALL EQUIPMENT, DUCTWORK, PIPING, CONDUIT AND DEVICES FROM BUILDING STRUCTURE TOPROVIDE A VIBRATION FREE INSTALLATION. NOTIFY ARCHITECT AND STRUCTURAL ENGINEER OF ALLWEIGHTS AND METHODS OF SUPPORT.
24. ANY REFERENCE TO MECHANICAL, PLUMBING, FIRE PROTECTION OR ELECTRICAL CONTRACTORS NOTEDON THE DRAWINGS SHALL NOT BE INTERPRETED AS AN INTENTION TO DEFINE SEPARATE CONTRACTORSFOR THE RESPECTIVE WORK. THE GENERAL CONTRACTOR SHALL COORDINATE AND PROVIDE ACOMPLETE INSTALLATION WITH COMPLETE MECHANICAL, PLUMBING, FIRE PROTECTION ANDELECTRICAL SYSTEMS, REGARDLESS OF ANY REFERENCES TO OTHER TRADE CONTRACTORS.
25. GUARANTEE WORK OF THIS CONTRACTOR IN WRITING FOR A PERIOD OF ONE YEAR FROM THE DATE OFOWNER'S ACCEPTANCE OR CERTIFICATE OF SUBSTANTIAL COMPLETION. PROMPTLY REPAIR OR REPLACEDEFECTIVE MATERIALS, EQUIPMENT, WORKMANSHIP AND INSTALLATIONS THAT DEVELOP DEFECTSWITHIN THIS PERIOD. PROMPTLY AND TO OWNERS SATISFACTION, CORRECT DAMAGE CAUSED INMAKING NECESSARY REPAIRS AND REPLACEMENTS UNDER THIS GUARANTEE AT NO ADDITIONAL COSTTO OWNER. SUBMIT GUARANTEE TO ARCHITECT BEFORE FINAL PAYMENT IS MADE. STATEMENT OFGUARANTEE REQUIREMENTS SHALL NOT BE INTERRUPTED TO LIMIT OWNER'S RIGHTS UNDER LAW ANDTHIS CONTRACT.
MECHANICAL DUCTWORK/EQUIPMENT NOTES
REGULATION OF VOLUME DAMPER SHALL BE ACCESSIBLETHROUGH THE FACE OF DIFFUSER.
COIL WITH FLANGED CONNECTION ALL AROUND.
FD MOUNTING TYPE DEPENDS ON AIR VELOCITIES AND DUCTSIZE - SEE SPECIFICATIONS.
HEATINGCOIL
DIRECTIONOF FLOW
REMOVE
NEW WORK
EXISTING
ACCESS DOOR IN DUCT
X DIMENSIONS SHALL BE 4" (10 CM) MINIMUM. IF A OR B IS GREATERTHAN 24" X 6" MINIMUM VOLUME DAMPER SHALL BE IN SHORTERBRANCH.
CONNECTION TO LINEAR DIFFUSER PLENUM
FIRERATEDWALL
FD
HEATING COIL
FIRERATEDWALL
FIRE DAMPER
PLENUMOVERLINEARDIFFUSER
ACCESS DOOR IN DUCT
CONICAL FITTING
PLENUM OVER DIFFUSER
OFFSET IN HORIZONTAL PLANE SHALL BEMADE WITH SMOOTH FITTINGS.
SUPPLY
HORIZONTAL OFFSET
RISE OR DROP
TRANSITION
TAP TAKE-OFF
ELEVATION - OFFSET IS VERTICAL PLANESHALL BE MADE WITH SMOOTHFITTINGS.
MAXIMUM INCLUDED ANGLE OF TRANSITION SIDES IS 15 o
ALL TERMINALDEVICES
DAMPERVOLUME
ALL TERMINALDEVICES
RETURN
VOLUME DAMPER
DUCTWORK SYMBOLOGY
SPLIT OR TAKE-0FF
SINGLE THICKNESS TURNING VANES - IN SQUARE ELBOWS,RADIUS ELBOWS PREFERED - SUBJECT TO SPACE CONDITIONS.
SINGLE LINE
ELBOW
DAMPERVOLUME
B
CONSTANT VOLUMESYSTEM
A
XTO VAVTERMINALUNIT
VARIABLE VOLUMESYSTEM
ACTUAL CONSTRUCTION
FLEX DUCT
FLEX DUCT
HANDDAMPER
FLEX DUCT
HANDDAMPER
SF-- SUPPLY FAN
EF-- EXHAUST FAN
FAN COIL UNIT
UNIT HEATER
--
--UH
FC
CO2 CARBON DIOXIDE SENSOR
SMOKE DETECTOR ON AC UNITS
MOTION SENSOR
DIFFERENTIAL PRESSURE SENSOR
SD
MS
DP
LOUVERED DOOR
AIR FLOW
EXHAUST FAN
SUPPLY AIR FLOW
RETURN OR EXHAUST
NEW CONNECTION TO EXISTING
TEMINATION OF DEMOLITION
LVDR
T OR THERMOSTAT
VARIABLE SPEED
AIR HANDLING UNITAHU--
FAN SWITCH
PUMP--P
S
CALL OUT SYMBOLS
TEMPERATURE SENSOR
REVISION NUMBER/INDICATESA REVISED FEATURE1
FD SELF-CLOSING FIRE DAMPERW/ ACCESS DOOR
SUPPLY DIFFUSER
SUPPLY DIFFUSER
SMOKE DAMPER WITH ACCESS DOOR
BLANKED FOR 3-WAY BLOW
BLANKED FOR 2-WAY BLOW
1-WAY BLOW SUPPLY DIFFUSER
UNDERCUT DOORUC 1"
OR
SD
MOTOR OPERATED DAMPER/ ZONE DAMPER
HVAC LEGEND
HAND DAMPER
MOD/ZD
HD
VARIABLE FREQUENCY DRIVE
WET BULB TEMPERATURE
WELD-WIRE MESH SCREEN (1/4")
W
CHILLED WATER SUPPLY
CHILLED WATER RETURN
DRY BULB TEMPERATURE
DIRECT DIGITAL CONTROL
DIRECT EXPANSION
CUBIC FEET PER MINUTE
ENTERING AIR TEMPERATURE
EXHAUST GRILLE
EXHAUST REGISTER
EXTERNAL STATIC PRESSURE
ENTERING WATER TEMPERATURE
FIRE DAMPER (W/ ACCESS DOOR)
FEET PER MINUTE
DX
EXHAUSTEXH
FURN
FLRDR
FPM
FT
FURNISHED
FLOOR DRAIN
FEET
FA
FD
FLEX
EXP
(F)
FREE AREA
FLEXIBLE
EXPANSION
FUTURE
EFFICIENCYEFF
ER
ESP
EWT
EG
ELEC ELECTRICAL
EA
EAT
DL
(E)
EACH
DOOR LOUVER
EXISTING
DN
DIA
DIM
DIFF
DOWN
DIAMETER
DIMENSION
DIFFUSER
DDC
CHWR
DB
COLUMN
CHWS
CW
CONN
CONTR
COLD WATER
CONNECTION
CONTRACTOR
CO
COL
CLG
CL
CFM
CLEAN-OUT
CEILING
CENTERLINE
POUNDS PER SQ INCH GAUGE
REVOLUTIONS PER MINUTE
SOUND ATTENUATOR
RELATIVE HUMIDITY
POUNDS PER SQ INCH ABSOLUTE
SA
SPECIFICATIONSSPECS
SCHEDULE
SMOKE DAMPER
SQUARE FOOT
SCREEN
SD
SF
SCH
SCR
RET RETURN
REQUIRED
ROOM
RELOCATE(RL)
RM
RPM
REQ'D
RH
PLUMBING
REMOVE
REGISTER
(R)
REG
PLBG
PSIA
PSIG
LEAVING AIR TEMPERATURE
LOW PRESSURE COND. RETURN
LOW PRESSURE STEAM
LEAVING WATER TEMPERATURE
MOTOR OPERATED DAMPER
NORMALLY CLOSED
MOUNTED
NTS NOT TO SCALE
OUTSIDE DIAMETER
PRESSURE DROP
OUTSIDE AIR
PD
OD
OA
NOT APPLICABLE
NUMBER
NOT IN CONTRACT
MANUAL AIR VENT
NC
NO
NIC
MTD
N/A
MAV
MECHANICAL
MANUFACTURER
MINIMUM
MF'R
MIN
MOD
LWT
MECH
KILOWATT
INCHES
LPS
LPR
KW
LAT
IN
Ø DIAMETER
WATER GAUGE
WITHOUT
WITH
WWMS
W/O
WB
WG
W/
AIR CONDITIONING
AUTOMATIC CONTROL VALVE
ABOVE FINISHED FLOOR
AIR HANDLING UNIT
BRAKE HORSEPOWER
BOTTOM OF DUCT
BOTTOM OF PIPE
CEILING DIFFUSER
BHP
CD
BOD
BOP
ARCH
AP
AFF
AHU
ARCHITECT
ACCESS PANEL
ADD'L
AD
ACV
AC
ADDITIONAL
ACCESS DOOR
GENERAL ABBREVIATIONS
GENERAL CONTRACTOR
GALLONS PER MINUTE
HOSE BIBB CONN W/ CHAINED CAP
HOT WATER SUPPLY
HOT WATER RETURN
HOUR
HERTZ
HORSEPOWER
HWS
HZ
HWR
HR
HP
GRILLE
RETURN GRILLE
HAND DAMPER
HEIGHT
HD
HGT
GR
HB
GR
GAUGE
GALLONS
GALVANIZEDGALV
GC
GPM
GA
GAL
VENT
UNDERCUT DOOR
WIDTH
VOLUME DAMPER
TYPICAL
VD
VFD
V
TYP
UC
TRANSFER GRILLE
TRANSFER
TEMPERATURE
SUPPLY
TG
TR
TEMP
SUP
SUPPLY REGISTER
STEEL
STEAM
STEAM TRAP
SR
ST
STL
STM
MAXIMUMMAX
AC-- AIR CONDITIONING UNIT
CH-- CHILLER UNIT
BUTTERFLY VALVE
BALL VALVE
B-- BOILER
HEAT PUMP LOOP RETURN
HEAT PUMP LOOP SUPPLY
HPR
HPS
CONDENSER WATER SUPPLY
CONDENSER WATER RETURNCWR
CWS
THERMOMETER
P PRESSURE GAUGE
FMFLOW METER
FSD COMBINATION FIRE SMOKE DAMPER
CONDENSING UNITCU--
HEAT PUMPHP--
ELECTRIC HEATEREH--
CO CARBON MONOXIDE SENSOR
COMBINATION FIRE/SMOKE DAMPERFSD
RETURN GRILLERG
SF-- SUPPLY FAN
AVGT
OR THERMOSTATAVERAGING TEMPERATURE SENSOR
1. PROJECT CONDITIONS1.1. THE CONTRACTOR SHALL BECOME COMPLETELY FAMILIAR WITH ALL EXISTING BUILDING AND SITE
CONDITIONS AND LIMITATIONS WHICH MAY HAVE A BEARING ON THE OPERATIONS HEREIN SPECIFIEDAND SHALL INCLUDE ALL WORK REQUIRED TO COMPLETE THE PROJECT AS SHOWN ON THE DRAWINGS.NO EXTRA COMPENSATION WILL BE ALLOWED FOR UNFORESEEN CONDITIONS THAT CAN BEDETERMINED FROM A CAREFUL EXAMINATION OF THE SITE, BUILDING AND DRAWINGS.
1.2. ITEMS OF VALUE WHICH ARE NOT INDICATED TO BE RETURNED TO THE OWNER SHALL BECOME THEPROPERTY OF THE CONTRACTOR. STORAGE OR SALE OF ITEMS ON THE PROJECT SITE IS PROHIBITED.
1.3. PROTECTION: ENSURE THE SAFE PASSAGE OF PERSONS IN AND AROUND THE BUILDING DURINGDEMOLITION. PREVENT INJURY TO PERSONS AND DAMAGE TO PROPERTY. PROVIDE ADEQUATESHORING AND BRACING TO PREVENT COLLAPSE. IMMEDIATELY REPAIR DAMAGED PROPERTY TO THECONDITION BEFORE BEING DAMAGED. TAKE EFFECTIVE MEASURES TO PREVENT WINDBLOWN DUST.
1.4. UTILITIES: MAINTAIN ALL UTILITIES EXCEPT THOSE THAT REQUIRE REMOVAL OR RELOCATION. KEEPUTILITIES IN SERVICE AND PROTECT FROM DAMAGE. DO NOT INTERRUPT UTILITIES SERVING OCCUPIEDAREAS OF THE SITE OR BUILDING WITHOUT FIRST OBTAINING PERMISSION FROM OWNER.
2. REGULATION REQUIREMENTS2.1. STRICTLY COMPLY WITH APPLICABLE CODES, REGULATIONS AND REQUIREMENTS OR AUTHORITY
HAVING JURISDICTION.3. HANDLING OF MATERIALS
3.1. REMOVE DEBRIS FROM THE SITE AS IT ACCUMULATES. DO NOT STORE, SELL, BURN OR OTHERWISEDISPOSE OF DEBRIS ON SITE. REMOVE ALL MATERIAL IN SUCH MANNER AS TO PREVENT SPILLAGE.
4. TRANSFER OF RESPONSIBILITY AND DISPOSITION OF MATERIALS4.1. UPON RECEIPT OF NOTICE TO PROCEED WITH THE WORK, THE TITLE TO ALL MATERIALS FOR
DEMOLITION SHALL BE VESTED. THE CONTRACTOR WHEREUPON THE OWNER WILL NOT BERESPONSIBLE FOR THE CONDITION, LOSS OR DAMAGE TO SAID PROPERTY. ALL SUCH ITEMS SHALL BEREMOVED FROM THE OWNER'S PROPERTY.
5. DISPOSAL OF DEMOLISHED MATERIALS5.1. REMOVE UNUSED EQUIPMENT AND FIXTURES AND ALL ASSOCIATED DUCTWORK AND PIPING SERVICING
EQUIPMENT AND FIXTURES INCLUDING ANY ABANDONED DUCTWORK AND PIPING NOT ASSOCIATEDWITH SAID EQUIPMENT AND FIXTURES AND NOT REQUIRED FOR NEW WORK. REMOVE DUCTWORK ANDPIPING BACK TO THE NEXT LIVE BRANCH WHICH WILL NOT OBSTRUCT THE NEW WORK AND CAP AIR ORWATER TIGHT. TRANSPORT AND LEGALLY DISPOSE OF MATERIALS OFF SITE.
5.2. ALL DEMOLITION SHALL BE COORDINATED WITH OWNER, ARCHITECT, ENGINEER AND GENERALCONTRACTOR. ALL DEBRIS SHALL BE CLEANED UP AND REMOVED FROM THE SITE BY THE END OF EACHWORK DAY. PRIOR TO DISPOSAL OF EQUIPMENT AND MATERIALS, TURN OVER TO OWNER ANYREMOVED EQUIPMENT AND MATERIALS PER OWNER'S REQUEST.
6. CLEAN UP AND REPAIR6.1. UPON COMPLETION OF DEMOLITION WORK, REMOVAL TOOLS, EQUIPMENT AND DEMOLISHED
MATERIALS FROM SITE. REMOVE PROTECTION AND LEAVE INTERIOR AREAS BROOM CLEAN.6.2. REPAIR DEMOLITION PERFORMED IN EXCESS OF THAT REQUIRED. RETURN STRUCTURES AND
SURFACES TO REMAIN IN CONDITION EXISTING PRIOR TO COMMENCEMENT OF SELECTIVE DEMOLITIONWORK. REPAIR ADJACENT CONSTRUCTION OR SURFACES SOILED OR DAMAGED BY SELECTIVEDEMOLITION WORK.
DEMOLITION NOTES:
M-2 MECHANICAL DETAILS
P-1 PLUMBING NOTES, LEGEND, AND SCHEDULES
P-1.1 PLUMBING FLOOR PLAN - PHASE 1
PLUMBING FLOOR PLAN - PHASE 3
HVAC GENERAL NOTES:
1. THERMOSTATS SHALL BE HONEYWELL COMMERCIAL VISION PRO 8000 OR OWNER APPROVED, 7-DAYPROGRAMMABLE WITH OVER-RIDE BUTTON FOR OCCUPANT AFTER HOURS CONTROL AND PASSWORDPROTECTION. INSTALL THERMOSTATS 48" ABOVE FINISHED FLOOR OR AS DIRECTED OTHERWISE BY ARCHITECT.COORDINATE FINAL LOCATION FOR EACH THERMOSTAT WITH ARCHITECT IN FIELD.
2. ALL CONDENSATE DRAIN LINES SHALL BE PIPED FULL SIZE OF UNIT DRAIN OUTLET AND PROVIDED WITH 'P' TRAP.TERMINATE CONDENSATE DRAIN PIPING AT NEAREST DRAIN.
3. EACH ROOFTOP UNIT OVER 2000 CFM SHALL HAVE A DUCT SMOKE DETECTOR LOCATED IN THE RETURN AIRSTREAM. DUCT SMOKE DETECTOR SHALL DE-ENERGIZE RESPECTIVE UNIT UPON ACTIVATION. DUCT SMOKEDETECTOR SHALL BE PROVIDED AND INSTALLED BY HE MECHANICAL CONTRACTOR. DUCT SMOKE DETECTORSHALL BE WIRED TO THE FIRE ALARM SYSTEM BY THE ELECTRICAL CONTRACTOR UNDER THE MECHANICALCONTRACTOR'S SCOPE OF WORK. MECHANICAL CONTRACTOR SHALL COORDINATE ALL WORK WITH THEELECTRICAL CONTRACTOR.
4. ALL CONTROL AND INTERLOCK WIRING FOR HVAC EQUIPMENT, WHETHER IT BE LINE OR LOW VOLTAGE, SHALL BETHE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR.
5. ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH NEC.6. EACH SYSTEM, EACH PIECE OF EQUIPMENT AND EACH AIR DEVICE SHALL BE FULLY TESTED AND BALANCED
UPON COMPLETION OF THE INSTALLATION WORK.7. TESTING AND BALANCING SHALL BE PROVIDED BY A COMPANY SPECIALIZING IN THE TESTING AND BALANCING OF
HVAC SYSTEMS. THE TEST AND BALANCE COMPANY SHALL BE A MEMBER OF AABC OR NEBB. BALANCEAIRFLOWS WITHIN 10% OF SCHEDULED AIR FLOWS TO ALL AIR DEVICES. IF AIR FLOW CANNOT BE BALANCED TOWITHIN 10%, PERFORM UP TO TWO PITOT TUBE TRAVERSES, AS DIRECTED BY OWNERS' REPRESENTATIVE, TODETERMINE THE CAUSE OF THE DEFICIENCY. SUBMIT SIX COPIES OF THE BALANCING REPORT FOR REVIEW PRIORTO FINAL INSPECTIONS.
8. DESIGN CONDITIONS ARE AS FOLLOWS:OUTDOOR SUMMER: 91 DEG DB, 75 DEG WB (ASHRAE 1%)INDOOR SUMMER: 74 DEG DB, 55% RHOUTDOOR WINTER: 11.6 DEG DB (ASHRAE 99.6%)INDOOR WINTER: 70 DEB DB
1. ALL DUCTWORK SHALL BE IN ACCORDANCE WITH SMACNA (SHEET METAL AND AIR CONDITIONING CONTRACTORSNATIONAL ASSOCIATION) STANDARDS.
2. PRIOR TO COMMENCING WORK, SHEET METAL SHOP DRAWINGS MUST BE PREPARED AND SUBMITTED FOR REVIEWAND APPROVAL TO THE ARCHITECT/ENGINEER. SHEETMETAL SHOP DRAWINGS SHALL INCLUDE ALL ELEMENTS OFTHE EQUIPMENT, DUCTWORK, AIR DEVICES, AND REFLECTED CEILING PLAN FOR COORDINATION OF CRITICALDIMENSIONS OF ARCHITECTURAL/ STRUCTURAL COMPONENTS.
3. SHEET-METAL FITTINGS SHOWN ARE TO BE PROVIDED. NO SUBSTITUTIONS ALLOWED WITHOUT PRIOR CONSENTFROM ENGINEER AND WILL BE REQUIRED TO BE REPLACED IF INSTALLED.
4. ALL WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN PIPING AND DUCTS (INCLUDINGDIVIDED DUCTS) AND TRANSITIONS AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THEOWNER.
5. VERIFY ALL EQUIPMENT CONNECTIONS WITH MANUFACTURER'S CERTIFIED DRAWINGS. VERIFY AND PROVIDE DUCTTRANSITIONS TO EQUIPMENT. FIELD VERIFY AND COORDINATE ALL DIMENSIONS BEFORE FABRICATING.
6. SUPPORT ALL EQUIPMENT AND DUCTWORK FROM BUILDING STRUCTURE TO PROVIDE A VIBRATION FREEINSTALLATION. NOTIFY STRUCTURAL ENGINEER OF ALL WEIGHTS AND METHODS OF SUPPORT.
7. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF AIR TERMINAL DEVICES.8. PROVIDE FLEXIBLE CONNECTIONS ON ALL DUCTS CONNECTING TO AIR HANDLING UNITS AN FANS.9. THE INSIDE OF ALL UNLINED DUCTWORK VISIBLE THROUGH A GRILLE SHALL BE PAINTED FLAT BLACK.10. PROVIDE FIRE DAMPERS WHERE SHOWN ON DRAWINGS AND/OR WHERE REQUIRED BY NFPA (NATIONAL FIRE
PROTECTION ASSOCIATION) 90A. FOR DUCTS THAT PENETRATE FIRE WALLS, FLOORS AND PARTITIONS, PROVIDESLEEVES WHERE PENETRATIONS ARE NOT PERPENDICULAR TO SURFACE PENETRATION. ENCLOSE DAMPERS IN 10GAUGE STEEL SLEEVE.
11. INSULATE ALL SUPPLY AIR AND RETURN AIR DUCTWORK WITH R-6 (INSTALLED) FIBROUS GLASS DUCT-WRAP WITHFOIL-DRAFT FLAME RESISTANT VAPOR BARRIER. INSULATION SHALL BE FIRE RATED IN ACCORDANCE WITH ASHRAE(AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR CONDITIONING ENGINEERS) 90A, 50/25 SMOKEDEVELOPMENT AND FLAME SPREAD REQUIREMENTS.
12. FLEXIBLE DUCT LENGTH SHALL NOT EXCEED 10 FEET. FLEXIBLE DUCT SHALL BE FABRIC COVERED GALVANIZEDSTEEL HELIX MECHANICALLY LOCKED TO THE FABRIC. THE FABRIC SHALL BE A LAMINATE OF ALUMINUM FOILFIBERGLASS AND ALUMINIZED POLYESTER WITH VAPOR BARRIER JACKET RATED AT 5500 RPM WITH FLEX-MASTERUSA TYPE 3 OR EQUAL. INSULATION R-VALUE SHALL MATCH SPECIFIED R-VALUE FOR AIR SYSTEM SERVED.
13. THOROUGHLY CLEAN ALL NEW DUCTWORK AFTER INSTALLATION.14. VOLUME DAMPERS SHALL BE PROVIDED AT THE BRANCH TAKE-OFF OF THE MAIN AND FOR EACH AIR DEVICE.15. DUCTWORK SCHEDULE
A. MEDIUM PRESSURE - SUPPLY DUCTWORK FROM AIR HANDLING UNIT TO VAV BOX SHALL BE 4-INCH W.G.CONSTRUCTION, LEAKAGE CLASS A, SEAL CLASS 12. MATERIAL SHALL BE GALVANIZED STEEL UNLESS NOTEDOTHERWISE.
B. LOW PRESSURE - ALL OTHER SUPPLY AIR, RETURN AIR AND EXHAUST AIR DUCTWORK SHALL BE 2-INCH W.G.CONSTRUCTION, LEAKAGE CLASS B, SEAL CLASS 12. MATERIAL SHALL BE GALVANIZED STEEL UNLESS NOTEDOTHERWISE.
ELECTRICAL COVER SHEET
ELECTRICAL DETAILS
E-1
E-2
ELECTRICAL FLOOR PLAN - LIGHTING - PHASE 1
ELECTRICAL FLOOR PLAN - LIGHTING - PHASE 2
ELECTRICAL FLOOR PLAN - POWER - PHASE 1
E-1.1
E-1.2
E-2.1
M-3 MECHANICAL SCHEDULES
FP-1.1 FIRE PROTECTION FLOOR PLAN - PHASE 1
FIRE PROTECTION FLOOR PLAN - PHASE 2FP-1.2
FP-1 FIRE PROTECTION LEGEND, GENERAL NOTES AND DETAILS
PD-1 PLUMBING DEMOLITION FLOOR PLAN
FIRE PROTECTION FLOOR PLAN - PHASE 3FP-1.3
M-1.2 MECHANICAL FLOOR PLAN - PHASE 2
M-1.3 MECHANICAL FLOOR PLAN - PHASE 3
ELECTRICAL FLOOR PLAN - POWER - PHASE 2E-2.2
ELECTRICAL FLOOR PLAN - LIGHTING - PHASE 3E-2.3
AS
N
OT
ED
AC
DF
T
T
T STT
RTU7
1
2
1
13
EXISTING LOCKED BOX WHICHCONTAINS CONTROL STATS FORRTU UNITS, RTU- 4,5,6 & 7.
(E) 34X14
(E) 14X5
(E) 1
2X6
(R) 8"Ø (R) 8"Ø
(R) 8"Ø(R) 8"Ø
(E) 1
4X5
(E) 1
4X8
(E) 1
2X10
(E)12X12RR
(E)12X12RR
(E)12X12CD
(E)12X12CD
(E)12X12CD
(E)12X12CD
AHU-5
13
(R) 8"Ø
RTU5
13
(E)12X12CD
(E)12X12CD
(E)12X12CD
(E)12X12CD
(E)8X4
(E)8X6
S
(E) 26X10
(E) 2
8X12
(E) 2
0X12
(R) 8"Ø (R) 8"Ø
(R) 8"Ø (R) 8"Ø
(E) 24X10 (R) 10"Ø
(R)VAV-STAT
S
T
(R) 5"Ø
(R)15X7(LINED)
T(R)VAV-STAT
VAV5
(R)VAV-STAT
OFF TOP OFDUCT- 8"Ø
(E) 16X6
(E) 20X8(E) 16X6
(E) 3
0X8
(E) 1
2X8
(E) 1
2X6
(E) 8
X4(E
) 8X4
(E) 10X4
(E) 10X4(E) 10X4
(E) 1
0X10
(E) 8X4
RTU8
3
(E)12X12RR
(E) 56X12
(E) 60X14
(E) 5
6X12
(E) 20X12
DSD
(E) 38X16
DSD
(E) 6
"Ø
(E) 1
0X5
(E) 1
2X6
(E) 10X5
(E) 3
0X12
(E) 3
0X8
(E) 2
6X8
(E) 12X5
(E) 15X6
(E) 8X4
VAV5(E)12X12
(LINED)
(R) 5"Ø
(E) 1
8X12
(E) 1
8X12
(E) 16X10
(E) 18X12(E) 15X6
(E) 10"Ø(R)12X12CD
(E) 1
4X8
(LIN
ED)
(E) 8"Ø
(E) 1
4X10
(LIN
ED)
(E) 8"Ø
(E) 8"Ø
(E) 1
8X10
(LIN
ED)
(E) 22X10(LINED)
VAV5
(R) 10"Ø(E) 30X12
(E) 1
8X12
(E) 3
4X14
(E) 22X14(LINED)(R) 10"Ø
(R) 8"Ø
(E) 1
0X8(E) 2
0X10
(E) 8
X4
(R) 8"Ø
(E) 8X4
(E) 28X10
(E) 2
4X10
(E) 4
4X10
(E) 2
2X10
VAV5
(E) 12X6
(E) 20X8
(E) 2
0X8
(E) 10X10
EFM-1
(R)
6
(E) 1
0X10
(E) 16X5
(E) 1
6X5
(E) 14X6
(E) 8
X4
(E) 1
6X8
(E) 8X4 (E) 14X6 (E) 14X5
(E) 14X5
(E) 2
4X14
(E) 10X4
(E) 1
8X6
(E) 20X8
(E) 18X6
(E)18X9(LINED)
(R) 10"Ø
VV5
(R) 10"Ø
(R) 10"Ø
(E)18X10
(R) 10"Ø
(E)16X8(LINED)
VV5
VV5
(E) 2
4X14
(R)VAV-STAT
(R)VAV-STAT
(R)VAV-STAT &TEMP. DIAL
(R) 10"Ø
(E)16X8(LINED)
(E)20X12
(E) 14X5
(E) 2
0X12
(R) 10"Ø
(E) 1
6X6
(LIN
ED)
VV5
(E) 15X6
(E) 15X6
(E) 8"Ø
(R) 8"Ø
(R) 8"Ø
(E) 2
0X12
(LIN
ED)
8
(E) 8X4
(E) 10X8
(E) 8X6
7
7(R)VAV-STAT
S
7
T
(R)VAV-STAT
RTU6
13
RTU4
13
RTU3
3
RTU2
3
RTU1
3
T
T
T
T
T
T
(E) 16X5(E) 16X8(E) 10X6
(E) 10X6
(E) 1
0X4
(E) 1
0X4
(E) 12X6
VAV5
VAV5 (R) CD
(R) CD
(E) 1
4X5
(R) RR
(R)VAV-STAT
(R) RR
(R) CD
(E) 1
6X8
(R) 5"Ø
(R) 5
"Ø
(E) 20X7
(E) 18X10
(E) 1
2X6
(R) CD
(R) CD
(R) CD
(R) CD
(R) CD
(R) RR
VAV5
(R) 7
"Ø
(E) 16X10(E) 16X10
(E) 1
0X8 (R) CD
(R) CD
(R) CD
VAV5
(R) 10"Ø
(E) 1
6X8
(E) 14X4
(R)VAV-STAT
(E) 18X16
(E) 2
4X16
(R) RR
(E) 14X4(E) 14X6
(E) 14X4
(E) 1
4X6
(E) 14X8
(E) 14X4
(R)12X12RR
(R)VAV-STAT
(E) 1
4X10
(R) 10"Ø
(E) 2
4X12
(E) 14X6(R) RR
(E) 18X10
(E) 8X4
(E) 8X6
(R) RR(R) RR
(R) CD
(E) 16X6
(E) 22X6
(E) 16X10
(E) 14X6
(E) 10X4
(E) 2
2X10
(E) 2
8X10
(E) 2
0X8
(E) 2
2X8(E) 8X4
(E) 1
0X4 (R) CD
(R) CD(E) 8X4
(E)8
X4
(E) 8
X6
(R) RR
(E) 2
8X16
(E) 3
2X16
(E) 1
6X6
(R) RR
(R) RR
(E) 8X4
(E) 14X6
(E) 14X6
VAV5
(R) 10"Ø
(R)VAV-STAT
(R)VAV-STAT
(R) CD
(R) CD
(E) 1
6X10
(E) 3
0X12
(E) 3
2X16
(E) 12X4
(E) 8
X4
(R) RR
(E) 1
2X4
(R) CD
(E) 18X6 (E) 12X6(E) 12X4
(E) 1
6X10
(E) 1
6X10
(E) 1
8X12
(E) 14X8(R) CD
(E) 8
X4
(R) CD
(R) CD
(E) 14X6
(E) 12X4
(R) CD
(E) 40X16(E) 40X16
(E) 3
0X12
(E) 2
0X8
(E) 40X16
(E) 40X16
(E) 3
2X16
(E) 2
0X14
(E) 2
0X14
(E) 40X16
VAV5
VAV5
VAV5
(R) 5"Ø
(R) 10"Ø
(E) 10X4
(R) CD
(R) RR
(R) CD
(E) 12X6
(E) 3
0X12
(R)VAV-STAT
(R) CD
(R) RR
(R) 10"Ø
(E) 1
6X10
(E) 1
4X8
(E) 14X8
(E) 2
0X12
(R) CD (R) CD
(R) RR
(R) RR
EFP-1
(R)
(R) RR
(R) CD
(E) 8
X4
(R) RR(E) 8X4
10
11
12
(R) ER
(E) 1
6X16
(R) CD
(E) 22X16
(E)16X8
(R) CD
(E) 8X4
(E) 1
8X12
(E) 2
0X16
(E)1
6X10
(R) RR
(R) RR
(R) CD (R) CD
(E) 14X5
(E)14X5
(E)16X10
(E)12X4(E)12X4
(E)12X4 (E)12X4
(E)16X8
(E)1
4X6
(E)4
0X16
(E)1
0X6
(E) 22X16(E) 22X16
(R) CD
(E)10X10(E)14X8
(E) 1
2X4
(E) 1
4X6
(E)2
6X12
(E)30X16(E)16X8
(E)12X10
(E)10X4
(E)10X10
(E)10X4
(E) 1
6X12
(R) ER
(R) ER
(R) CD
(R) CD (R) RR
(R) CD
(E)16X8
DSD 8
DSD 8
(E)10X6
(E)1
8X12
(E) 10X8
(E) 8
X4
(R) RR
(R) RR
(R) CD
(R) CD
(R) RR
(E) 1
4X6
(E) 1
6X6
(E) 1
6X6
(E) 2
0X10
(E) 10X4
(R) CD
(E) 10X4
(E)1
0X6
(E) 10X4(R) CD
14
EH-
(E)
EH-
(E)
EFM-2
(R)
T (R)VAV-STAT
S
(R) CD(R) RR
(R) RR
(R)VAV-STATT
S
7
(R) CD
S
7
(R) RR
(R) CD
(R) RR
(R) RR
1
1
1
(R) CD14
14
EXISTING LOCKED BOX WHICHCONTAINS CONTROL STATS FORRTU UNITS, RTU- 1,2 & 3.REMOVE RTU-1 & 3 STATS &RTU-2 STAT IF ADD-ALT ISACCEPTED.
(E) HOOD
(R) CD
(R) ER
(R) RR
(R) RR
T
(R)VAV-STAT
(E) 10X4(R) CD
(R) RR
(R) RR
(R) CD
(R) CD
(R) RR
(R) ER-SIDEWALL
(R) ER
(R) CD
(R) CD
(R) CD(R) CD
T(R)RTU-3
(R) CD
(R) CD
(R) CD
(R) CD
(R) CD (R) CD
(R) CD (R) CD
(R) CD
(R) CD(R) CD
(R) CD
(R) CD (R) CD
(R) CD(R) CD
(R) CD (R) CD
(R) CD
(R) CD(R) CD
(R) CD
(R) CD
(R) CD
(R) CD
(R) ER(R) CD
(R) CD
(E) 8X4
(R) CD
(R) RR
(R) RR
(R) RR
(R) RR(R) RR
(R) ER
(R) RR
(R) RR
(R) RR
(R) RR
(R) RR
(R) RR(R) RR(R) RR
(R) RR
(R) RR
(R) ER
(R) ER
(R) RR
(R) CD
(R) CD
(R) CD (R) CD
(R) CD
(R) CD
(R) CD
(R) CD
(R) CD
(R) CD
(R) CD
(R) CD
(R) CD
(R) CD
(R) CD
(R) CD
(R) CD
(R) CD(R) CD
(R) CD
(R) CD
SAHU-4
13(R) RR
(R) RR
(R) CD
(R) CD(R) CD
(R) CD
(R) RR (R) RR
T (E) EH STAT
EH-
(E)
(R) RR
(R) RR
EH-
(E)
(R) CD (R) CD (R) CD (R) CD
(R) CD
(R) RR
(R) SR HIGHIN SLOPEDCLG.
T(E) EH STAT
ON ROOF
EFP-2
(R)
15
15
15
16
MOD/ZD
T
4
VAV
CONFERENCE RM.
TO HAVE A COMPLETE RTU & ASSOCIATED VAV BOXES ANDCONTROLS REMOVE NOTED VAV BOXES AND ASSOCIATEDCONTROLS IN AREAS NOT IN SCOPE
LOCK-UP AREALOCK-UP AREA
(R) RR
VAV
(E)1
0X4LD-1
4'-0" L, 4- SLOT, 1" SLOT285 CFM
EH-
(E)
VAV
LOCK-UP AREA
EXTERIOR OFFICE
(E)14X6
5
5
5
(ADD -ALT)
(R) TEMPERATURE SENSOR &ASSOCIATED CONTROL WIRING BACKTO THERMOSTAT LOCATIONS . SEETHIS DRAWING.
MECHANICAL NOTES:
EXISTING HIGH WALL HEAT PUMP UNIT , ASSOCIATED PIPING ,CONTROLS AND ROOFTOP CONDENSING UNIT TO REMAIN.
EXISTING 2 1 /2 TON ROOFTOP CONDENSING UNIT SERVING HIGHWALL INDOOR HEAT PUMPS TO REMAIN.
REMOVE EXISTING RTU (ON ROOF) AND ASSOCIATED CONTROLS.REPLACEMENT RTU SHALL HAVE ROOF CURB ADAPTER, SEESCHEDULE AND CONSTRUCTION PLANS.
REMOVE EXISTING RTU SENSOR.
REMOVE EXISTING VAV BOX AND ASSOCIATED CONTROL STAT.
EXISTING 12X12 EXHAUST DUCT UP TO EXHAUST GOOSENECK ONROOF.
EXISTING TO REMAIN TEMPERATURE SENSOR AND ASSOCIATEDCONTROL WIRING TO RTU CONTROL STATS. IF ADD-ALT TO REPLACERTU-2 IS ACCEPTED, REMOVE TEMPERATURE SENSORS & ALLASSOCIATED WIRING ETC BACK TO THE RTU THERMOSTATSLOCATION IN THE POLICE SIDE OF BUILDING.
REMOVE EXISTING SMOKE DETECTOR FROM SUPPLY DUCTWORK.PATCH AIRTIGHT.
REMOVE EXISTING ROOFTOP EXHAUST FAN AND ROOF CURB.
(E) EXHAUST DUCT DN TO HOOD.
(E) EXHAUST DUCT UP TO WEATHER CAP ON ROOF.
(E)16X16 EXHAUST DUCT UP TO WEATHER CAP ON ROOF.
EXISTING RTU AND ASSOCIATED CONTROLS TO REMAIN.
CAP DUCT AIR TIGHT SEAL
ADD-ALT -REMOVE EXISTING EXHAUST FAN, HANGERS ETC.EXISTING CONTROL DEVICE TO REMAIN FOR CONNECTION TO NEWFAN.
ADD-ALT-REMOVE EXISTING ROOFTOP EXHAUST FAN. REMOVE ROOFCURB IF NEW FAN CANNOT BE INSTALLED ON CURB OR WITH ANADAPTER CURB.
1
2
3
4
5
7
8
6
9
10
11
12
13
14
GENERAL MECHANICAL DEMOLITION NOTES:
1. PRIOR TO COMMENCEMENT OF DEMOLITION, CONTRACTOR SHALLMEASURE AIRFLOW AT EACH HVAC UNIT AND AIR DEVICE AND PROVIDEA REPORT OF THE FINDINGS TO OWNER, ARCHITECT AND ENGINEERFOR REVIEW.
2. INTENT IS TO DISCONNECT AND REMOVE ALL EXISTING AIR DEVICESAND ANY ASSOCIATED FLEX DUCTWORK BACK TO THE NEAREST SHEETMETAL MAIN. PATCH AIRTIGHT SEAL OR CONNECTION FOR NEWDUCTWORK. REFER TO NEW WORK PLANS FOR NEW WORK.
15
16
KEY PLAN
PHASE 1 PHASE 2
MD-1
1
SCALE - 1/8" = 1'-0"
MECHANICAL DEMOLITION FLOOR PLAN
AS
N
OT
ED
JM
F
DF
N
0' 4' 16'8'
BRANCH/ FLEX DUCT SIZING SCHEDULE
DUCT SIZE CFM RANGE REMARK
6"Ø
8"Ø
10"Ø
12"Ø
0-100
101-260
261-400
401-600
MAX 10' LENGTH. FLEX DUCTWORK APPROVED ON SUPPLY SYSTEMSONLY.RETURN AND EXHAUST TO BE HARD DUCTED.
RTU6
RTU4RTU
3
RTU2
RTU1
(E) 16X5(E) 16X8
(E) 12X6
(E) 1
4X5
(E) 1
6X8
6"Ø
8"Ø
(E) 20X7
(E) 18X10
(E) 1
2X6
12X12 RR245 CFM 6
"Ø
(E) 16X10(E) 16X10
(E) 1
0X8
8"Ø
(E) 1
6X8
(E) 14X4(E) 18X16
(E) 2
4X16
(E) 14X4
(E) 14X6
(E) 1
4X6
(E) 14X8
(E) 14X4
(E) 1
4X10
10"Ø
(E) 2
4X12
(E) 14X6
(E) 18X10
(E) 8X4
(E) 8X6
(E)22X6
(E) 2
8X10
(E) 2
0X8
(E) 2
2X8
(E) 1
0X4
(E) 8X4
(E)8
X4
(E) 8
X6
(E) 28X16
(E) 3
2X16
(E) 1
6X6
(E) 8X4
12"Ø
(E) 1
6X10
(E) 3
0X12
(E) 3
2X16
(E) 12X4
(E) 8
X4
(E) 1
2X4
(E) 18X6 (E) 12X6(E) 12X4
(E) 1
6X10
(E) 1
6X10
(E) 1
8X12
(E) 14X8
(E) 8
X4
(E) 14X6
(E) 12X4
(E) 40X16(E) 40X16
(E) 3
0X12
(E) 2
0X8
(E) 40X16
(E) 40X16
(E) 3
2X16
(E) 20X14
(E) 2
0X14
(E) 40X16
VAVF
4"Ø
8"Ø
(E) 10X4
(E) 12X6
(E) 3
0X12
(E) 1
2X6
12"Ø
(E) 1
6X10
(E) 1
4X8
(E) 14X8
(E) 2
0X12
EFP-1
(ON ROOF)
(E) 8
X4
(E) 8X4
(E) 1
6X16
(E) 22X16
(E)16X8
(E) 8X4
(E) 1
8X12
(E) 2
0X16
(E)1
6X10
(E) 14X5
(E)14X5
(E)16X10
(E)12X4(E)12X4
(E)12X4 (E)12X4
(E)16X8
(E)1
4X6
(E)4
0X16
(E)1
0X6
(E) 22X16(E) 22X16
(E)14X8
(E) 1
2X4
(E) 1
4X6
(E)2
6X12
(E)30X16(E)16X8
(E)12X10 (E)10X10
(E)10X4
(E) 1
6X12
(E)16X8
DSD
DSD
(E)10X6
(E)1
8X12
(E) 10X8
(E) 8
X4
12X12 RR380 CFM
(E) 1
4X6
(E) 1
6X6
(E) 1
6X6
(E) 2
0X10
(E) 10X4
(E) 10X4
(E)1
0X6
VVD
VVC
VVC
VVE
VVF
VVA
VVD
T
TVV-C
T VV-C
T
VV-D
T
VV-E
TVV-F
T
VV-D
VVD
5
5
8
66
6
10
11
11
24X24 CD150 CFM
24X24 CD340 CFM
12X12 RRXXCFM
12X12 RR300 CFM12X12 RR
175 CFM
12X12 RR270 CFM
12X12 RR270 CFM
12X12 RR175 CFM
8X8 RR110CFM
24X24 RR490 CFM
12X12 CD100 CFM
12X12 RR100 CFM
TVV-A
12X12 RR170 CFM
12X12 RR160 CFM
TVV-F
6X6 CD80 CFM
6"Ø
14X14 RR370CFM
12X12 RR285 CFM
9X9 CD145 CFM
8X12 RR145 CFM
VAVA
12X12 CD120 CFM
(E)1
0X4
12X12 RR115 CFM
12X12 ER150 CFM
6X6 CD80 CFM
6X6 CD80 CFM
6X6 CD120 CFM
12X12 ER340 CFM
24X24 CD90 CFM
12X12 RR170 CFM
12X12 CD155 CFM
6X6 RR110 CFM
6X6 RR50 CFM
12X12 RR120 CFM
6X6 CD75 CFM
12X12 CD130 CFM
12X12 CD120 CFM
6X6 CD110 CFM
12X12 RR220 CFM
6X6 CD75 CFM
6X6 CD140 CFM
6X6 RR75CFM
6X6 RR140 CFM
12X12 CD95 CFM
12X12 RR95 CFM
6X6 CD120 CFM
6X6 CD55 CFM
12X12 CD190 CFM
6X6 RR55 CFM
12X12 ER340 CFM
12X12 ER335 CFM
6X6 CD110 CFM
6X6 CD110 CFM
12X12 CD170 CFM
12X12 CD170 CFM
6X6 CD150 CFM
(E)12X8
(E)14X4
(E)14X10
(E)14X10
12X12 RR250 CFM
12X12 RR345 CFM
12X12 RR345 CFM
(E)8X4
(E)1
0X6(E
)14X
10
(E)1
0X4 (E)30X20
12X12 CD130 CFM
12X12 CD280 CFM
12X12 CD280 CFM
6X6 CD100 CFM
12X12 CD190 CFM
12X12 CD190 CFM
12X12 CD190 CFM
12X12 CD190 CFM
12X12 RR380 CFM12X12 RR
380 CFM
LD-14'-0" L, 4- SLOT, 1" SLOT245 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT200 CFM
LD-14'-0" L, 2- SLOT, 3 /4" SLOT 150 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT200 CFM
LD-14'-0" L, 2- SLOT, 1 /2"SLOT110CFM
LD-14'-0" L, 2- SLOT,3 /4" SLOT 150 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT200 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT200 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT200 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT200 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT170 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT160 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT185 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT185 CFM
LD-14'-0" L, 4- SLOT, 1" SLOT285 CFM
EH-
(E)
EH-
(E)
12
12
EFM-2
7
EFP-2
7
300
200
245
350
540
1090
735
330
130
750
230
VAVE
VAVC
LOCK-UP AREA
100
EXTERIOR OFFICE
CONFERENCE RM.
VV-D
24X24 RR490 CFM
24X24 CD190 CFM
24X24 CD190 CFM
8"Ø
8"Ø
8"Ø
8"Ø
8"Ø
14X8
16X6
14X6
TO HAVE A COMPLETE RTU & ASSOCIATED VAV BOXES ANDCONTROLS PROVIDE NOTED VAV BOXES IN AREAS NOT IN SCOPE .PROVIDE ALL NECESSARY DUCTWORK ETC TO INSTALL BOXES INEXISTING DUCTWORK. ALSO PROVIDE THERMOSTATS FOR VAVCONTROL TO RTU.
8"Ø
4"Ø
8"Ø
8"Ø
SRTU-3SENSOR
(E) 1
4X6
(E)10X4
6X6 ER75 CFM
6X6 CD80 CFM
6X6 ER60 CFM
12X12 ER125 CFM
6X6 CD45 CFM
12X12 RR170 CFM
(E) 8X4
6X6 CD105 CFM
MOD/ZD
(E) CONTROLS TO REMAIN. BALANCE AIRFLOW WITHHOOD OPERATION
8X4
12X12 CD155 CFM
12X12 ER400 CFM
24X24 CD90 CFM
6X6 CD75 CFM
6X6 RR50 CFM
6X6 RR50 CFM
(E) 2
2X8(E) 8X4
(R) CD
(E) 10X4
(E) 10X4
12X12 CD190 CFM
12X12 RR120 CFM
6X6 RR60 CFM
S
RTU-2 SENSORADD-ALT
EXISTING LOCKED BOX WHICHCONTAINS CONTROL STATS FORRTU UNITS, RTU- 1,2 & 3.
14
ADD-ALT100 CFM
ADD-ALT100 CFM
ADD-ALT110 CFM
ADD-ALT110 CFM
ADD-ALT130 CFM
ADD-ALT130 CFM
ADD-ALT75 CFM
ADD-ALT75 CFM
ADD-ALT45 CFM
ADD-ALT45 CFM
ADD-ALT160 CFM
ADD-ALT160 CFM
ADD-ALT320 CFM
ADD-ALT100 CFM
ADD-ALT100 CFM
ADD-ALT120 CFM
ADD-ALT120 CFM
ADD-ALT100 CFM
ADD-ALT125 CFM
ADD-ALT70 CFM
ADD-ALT210 CFM
ADD-ALT70 CFM
ADD-ALT30 CFM
ADD-ALT70 CFM
(E)CD & RR120 CFMADD-ALT100 CFM
(E)12X12 RR180 CFMADD-ALT150 CFM
(E)12X12 CD180 CFMADD-ALT150 CFM
ADD-ALT50 CFM
ADD-ALT100 CFM
ADD-ALT80 CFM
ADD-ALT80 CFM
ADD-ALT65 CFM
ADD-ALT65 CFM
ADD-ALT120 CFM
ADD-ALT120 CFM
ADD-ALT180 CFM
ADD-ALT90 CFM
(E) HIGH WALL AC UNITS (TYP OF 3)
(ADD-ALT)
6X6 CD105 CFM
TRTU-4
S
S
1 (TYP)
14
15
(TYP)
1 (TYP)
3(TYP)
GENERAL MECHANICAL CONSTRUCTION NOTES
1. INTEGRAL OPPOSED BLADE DAMPERS SHALL BE PROVIDEDAT ALL AIR DEVICES. FINAL SUPPLY AIR DEVICE BALANCINGSHALL BE PERFORMED VIA INTEGRAL AIR DEVICE
2. ALL PENETRATIONS THRU RATED ASSEMBLIES SHALL BEPROVIDED WITH RADIANT DAMPERS.
3. FLEX DUCT WORK LENGTHS SHALL BE LIMITED TO WHAT ISALL INDICATED ON M-100.
4. ALL DIFFUSERS AND REGISTERS LOCATED IN TOILET ROOMSSHALL BE ALUMINUM CONSTRUCTION.
5. ALL RETURN/EXHAUST REGISTERS SHALL HAVE 45˚ FIXEDBLADES.
6. ALL SUPPLY MAINS SHALL BE LINED WITH 1" INTERNAL LINING. ALL BRANCH DUCTWORK SHALL BE EXTERNALLYWRAPPED.
7. REFER TO RTU DETAIL FOR INSTALLATION REQUIREMENTS.
8. ALL DUCT SIZES ARE INSIDE DUCT DIMENSIONS.9. REFER TO ARCHITECTURAL PLANS FOR FINAL AIR DEVICE
LOCATIONS.10. CONNECT NEW AIR DEVICES TO EXISTING DUCTWORK WITH
FLEX DUCTWORK OR SHEET METAL DUCTWORK AS REQUIRED.
SPECIAL MECHANICAL CONSTRUCTION NOTES
1. ADDITIONAL DUCTWORK IS SHOWN TO ACCOMMODATE NEWROOMS OR CHANGES TO THE AREA USAGE. THIS IS BECAUSE OFEXISTING DUCTWORK FROM THE ASSOCIATED RTU IS NOT PRESENTOR INADEQUATE SIZE. ROUTE NEW DUCTWORK AS REQUIRED,PROVIDE ALL OFFSETS, FITTINGS ETC FOR A COMPLETEINSTALLATION.2. PROVIDE ALL NECESSARY FLEX DUCT, DUCTWORK, FITTINGSETC. FOR CONNECTIONS FROM NEW AIR DEVICES TO EXISTINGDUCTWORK
MECHANICAL NOTES (ALL PHASES):
CAP DUCT AIR TIGHT SEAL.
DUCTWORK FROM RTU-5 TO REMAIN. BALANCE AIRDEVICES TO CFM INDICATED.
CONNECT AS REQUIRED WITH 'HARD DUCT' THE RETURNREGISTER TO EXISTING RETURN MAIN.
CONNECT MAIN LOBBY AIR DEVICES IN NEW CEILINGGRID TO EXISTING DUCTWORK AS REQUIRED.
EXISTING RTU TO REMAIN.
NEW RTU- SEE SCHEDULE.
NEW INLINE EXHAUST FAN, SEE SCHEDULE FOR FURTHERINFORMATION. ADD-ALT
NEW ROOFTOP EXHAUST FAN, SEE SCHEDULE FORFURTHER INFORMATION. ADD-ALT
EXISTING EXHAUST DUCT UP TO GOOSENECK ON ROOF.
EXISTING EXHAUST DUCT DN TO HOOD.
EXISTING EXHAUST DUCT UP TO ROOFTOP WEATHER CAP
INSTALL DUCT MOUNTED SMOKE DETECTOR IN RETURNDUCT MAIN.
BALANCE AIR DEVICE TO EXISTING AIRFLOW.
TYPICAL FOR ALL CONNECTIONS BETWEEN NEW ANDEXISTING WORK.
CONNECT NEW FLEX DUCTWORK SERVING VAV BOXES TOEXISTING DUCTWORK AS REQUIRED. (TYP)
15
14
13
12
2
1
3
4
5
6
7
8
9
10
11
RTU-2 ADD ALT NOTES:1.ADD - ALT IS FOR RTU-2 (17.5 TONS) TO BE REPLACED.PER EXISTING DRAWINGS THE TOTAL AIRFLOW OF THE UNIT IS 4955CFM. THE CFM NOTED FOR AIR DEVICES SERVED BY RTU-2 ARE FORTHE EXISTING UNIT NOT BEING REPLACED AND AN ADD- ALT CFM ISFOR THE UNIT BEING REPLACED.2. IF ADD-ALT IS ACCEPTED REMOVE TEMPERATURE SENSORS ANDALL ASSOCIATED WIRING ETC BACK TO THERMOSTATS LOCATION INTHE POLICE SIDE OF BUILDING.
KEY PLAN
PHASE 1
M-1-1
1
SCALE - 1/8" = 1'-0"
MECHANICAL FLOOR PLAN - PHASE 1
AS
N
OT
ED
JM
F
DF
N
0' 4' 16'8'
Project:
Description: Date: Scale:
Sketch #
.\AEI Title Block.jpg
BRANCH/ FLEX DUCT SIZING SCHEDULE
DUCT SIZE CFM RANGE REMARK
6"Ø
8"Ø
10"Ø
12"Ø
0-100
101-260
261-400
401-600
MAX 10' LENGTH. FLEX DUCTWORK APPROVED ON SUPPLY SYSTEMSONLY.RETURN AND EXHAUST TO BE HARD DUCTED. T
EXISTING LOCKED BOX WHICHCONTAINS CONTROL STATS FORRTU UNITS, RTU- 4,5,6 & 7.
(E) 34X14
(E) 14X5
(E) 1
2X6
(E) 8"Ø (E) 8"Ø
(E) 8"Ø(E) 8"Ø
(E) 1
4X5
(E) 1
4X8
(E) 1
2X10
(E)12X12 RR340 CFM
(E)12X12 CD195 CFM
(E)12X12 CD195 CFM
22X22 RR1100 CFM
24X24 CD100 CFM
RTU5
(E)12X12 CD110 CFM
(E)8X4
(E)8X6
(E) 26X10
(E) 2
8X12
(E) 2
0X12
8"Ø 8"Ø
(E) 24X10
OFF TOP OFDUCT- 8"Ø
(E) 3
0X8
(E) 1
2X8
(E) 1
2X6
(E) 8
X4
(E) 10X4
24X24 CD60 CFM 24X24 CD
200 CFM
(E) 10X4(E) 10X4
16X16 RR560 CFM
(E) 1
0X10
(E) 8X4
RTU8
(E)12X12 RR440 CFM 12X12 CD
225 CFM
(E) 56X12
(E) 60X14
(E) 5
6X12
(E) 20X12
DSD
(E) 38X16
DSD
(E) 1
0X5
(E) 1
2X6
(E) 10X5
12X12 CD105 CFM
12X12 CD105 CFM
(E) 3
0X12
(E) 3
0X8
(E) 15X6
(E)12X12(LINED)
(E) 1
8X12
(E) 1
8X12
(E) 16X10
(E) 18X12(E) 15X6
(E) 1
8X10
(LIN
ED)
(E) 22X10(LINED)
(E) 30X12
(E) 1
8X12
(E) 3
4X14
(E) 22X14 (LINED)10"Ø
8X12 ER300 CFM
(E) 1
0X8(E) 2
0X10
(E) 8
X4
6"Ø
(E) 8X46X6 ER75 CFM
6X6 CD75 CFM
(E) 28X10
6X6 CD75 CFM
12X12 RR270 CFM(OFF BOTTOMOF RTN DUCT)
24X24 CD270 CFM
(E) 2
4X10
(E) 4
4X10
(E) 2
2X10
(E) 12X6
(E) 20X8
(E) 2
0X8
(E) 10X10
EFM-1
(E) 1
0X10
(E) 16X5
(E) 1
6X5
(E) 14X6
(E) 8
X4
6X6 CD40 CFM
(E) 1
6X8
(E) 2
4X14
8"Ø 18X18
RR410 CFM
12X12RR270 CFM
(E) 1
8X6
(E) 20X8
(E) 18X6
(E)18X9(LINED)
VVE
(E)18X10
6"Ø
VVC
(E) 2
4X14
(E)20X12
30X8
(E) 2
0X12
(E) 15X6
(E) 2
0X12
(LIN
ED)
(E) 8X4
(E) 10X8
(E) 8X6
18X18RR400 CFM
22X22RR900 CFM
(E)12X12 CD110 CFM
(E)12X12 CD110 CFM
(E)12X12 CD110 CFM
(E)12X12 CD190 CFM
(E)12X12 CD190 CFM
(E)12X12 RR340 CFM
CO2
CO2
T
VVD
TVV-E VV-C VV-D
T VV-F
T VV-E
12X12RR130 CFM
12X12RR160 CFM
12X12RR
VVF
VVE
22X22RR800 CFM
VVE
TVV-E
12X12RR-1200 CFM
VVD
TVV-D
12X12RR-300 CFM
22X22RR1125 CFM
VVF
TVV-F
BUILDING FACILITY AREA HVAC TO REMAINAS-IS.RE-BALANCE AIR DEVICES TO CFMINDICATED.
12X12 CD140 CFM
12X12 CD140 CFM
12X12 CD140 CFM
12X12 CD140 CFM
12X12 RR210 CFM
22X22RR260 CFM
8"Ø
8"Ø
8X12 ER300 CFM
12X12 CD225 CFM
12X12 CD100 CFM
24X24 CD130 CFM
(E) 56X12
12X8
12X8
24X24 CD210 CFM
24X24 CD100 CFM
22X22RR865 CFM
12X12 RR290 CFM 14X6
24X24 CD145 CFM
24X24 CD145 CFM
24X24 CD400CFM
24X24 CD300 CFM
24X24 CD350 CFM
24X24 CD350 CFM
(E) 1
6X8
16x14
16X1
2
14X1
0
7
2
3
1
3
3
5
9
6
LD-14'-0" L, 2- SLOT, 1" SLOT180 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT220 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT180 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT180 CFM
LD-14'-0" L, 2- SLOT, 3/4" SLOT150 CFM
24X24 CD185 CFM
24X24 CD180 CFM
LD-14'-0" L, 2- SLOT, 3/4" SLOT150 CFM
LD-14'-0" L, 2- SLOT, 1 /2" SLOT100 CFM
LD-14'-0" L, 2- SLOT, 1/2" SLOT100 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT220 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT180 CFM
LD-14'-0" L, 2- SLOT,1" SLOT180 CFM
LD-14'-0" L, 2- SLOT, 3 /4" SLOT125 CFM
LD-14'-0" L, 2- SLOT, 3 /4" SLOT160 CFM
LD-14'-0" L, 2- SLOT, 3 /4" SLOT130 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT220 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT180 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT220 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT200 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT200 CFM
LD-14'-0" L, 2- SLOT, 3 /4" SLOT135 CFM
LD-14'-0" L, 2- SLOT,3 /4" SLOT135 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT210 CFM
LD-14'-0" L, 2- SLOT, 1" SLOT210 CFM
LD-14'-0" L, 1- SLOT, 3 /4" SLOT85 CFM
LD-14'-0" L, 1- SLOT, 3 /4" SLOT80CFM
RTU7
5
12
1
8"Ø 1125
8"Ø 8"Ø
8"Ø
300
615
24X24 CD220 CFM
800
12
10X8
8" Ø
7" Ø
900
400 270
585
24X24 CD280 CFM1
1
1
1
1
1
10"Ø
8"Ø
6"Ø
6"Ø
14
14
15
10X10
20X6
10"Ø
12X1
212
X14
1
24X8
12X14 12"Ø
14
10"Ø
1
1
1
1
14X6
14X6
14X628X8
12"Ø
8"Ø
14
8"Ø
6"Ø
8X10
14X6
AHU-5SENSOR
T
24X8
S
S
S
(E) SENSOR FOR RTU-7
(E) SENSOR FOR RTU-7
(TYP)
MECHANICAL NOTES (ALL PHASES):
CAP DUCT AIR TIGHT SEAL.
DUCTWORK FROM RTU-5 TO REMAIN. BALANCE AIRDEVICES TO CFM INDICATED.
CONNECT AS REQUIRED WITH 'HARD DUCT' THE RETURNREGISTER TO EXISTING RETURN MAIN.
CONNECT MAIN LOBBY AIR DEVICES IN NEW CEILINGGRID TO EXISTING DUCTWORK AS REQUIRED.
EXISTING RTU TO REMAIN.
NEW RTU- SEE SCHEDULE.
NEW INLINE EXHAUST FAN, SEE SCHEDULE FOR FURTHERINFORMATION. ADD-ALT
NEW ROOFTOP EXHAUST FAN, SEE SCHEDULE FORFURTHER INFORMATION. ADD-ALT
EXISTING EXHAUST DUCT UP TO GOOSENECK ON ROOF.
EXISTING EXHAUST DUCT DN TO HOOD.
EXISTING EXHAUST DUCT UP TO ROOFTOP WEATHER CAP
INSTALL DUCT MOUNTED SMOKE DETECTOR IN RETURNDUCT MAIN.
BALANCE AIR DEVICE TO EXISTING AIRFLOW.
TYPICAL FOR ALL CONNECTIONS BETWEEN NEW ANDEXISTING WORK.
CONNECT NEW FLEX DUCTWORK SERVING VAV BOXES TOEXISTING DUCTWORK AS REQUIRED. (TYP)
11
10
9
8
7
6
5
4
3
1
2
SPECIAL MECHANICAL CONSTRUCTION NOTES
1. ADDITIONAL DUCTWORK IS SHOWN TO ACCOMMODATE NEWROOMS OR CHANGES TO THE AREA USAGE. THIS IS BECAUSE OFEXISTING DUCTWORK FROM THE ASSOCIATED RTU IS NOT PRESENTOR INADEQUATE SIZE. ROUTE NEW DUCTWORK AS REQUIRED,PROVIDE ALL OFFSETS, FITTINGS ETC FOR A COMPLETEINSTALLATION.2. PROVIDE ALL NECESSARY FLEX DUCT, DUCTWORK, FITTINGSETC. FOR CONNECTIONS FROM NEW AIR DEVICES TO EXISTINGDUCTWORK
12
13
GENERAL MECHANICAL CONSTRUCTION NOTES
1. INTEGRAL OPPOSED BLADE DAMPERS SHALL BE PROVIDEDAT ALL AIR DEVICES. FINAL SUPPLY AIR DEVICE BALANCINGSHALL BE PERFORMED VIA INTEGRAL AIR DEVICE
2. ALL PENETRATIONS THRU RATED ASSEMBLIES SHALL BEPROVIDED WITH RADIANT DAMPERS.
3. FLEX DUCT WORK LENGTHS SHALL BE LIMITED TO WHAT ISALL INDICATED ON M-100.
4. ALL DIFFUSERS AND REGISTERS LOCATED IN TOILET ROOMSSHALL BE ALUMINUM CONSTRUCTION.
5. ALL RETURN/EXHAUST REGISTERS SHALL HAVE 45˚ FIXEDBLADES.
6. ALL SUPPLY MAINS SHALL BE LINED WITH 1" INTERNAL LINING. ALL BRANCH DUCTWORK SHALL BE EXTERNALLYWRAPPED.
7. REFER TO RTU DETAIL FOR INSTALLATION REQUIREMENTS.
8. ALL DUCT SIZES ARE INSIDE DUCT DIMENSIONS.9. REFER TO ARCHITECTURAL PLANS FOR FINAL AIR DEVICE
LOCATIONS.10. CONNECT NEW AIR DEVICES TO EXISTING DUCTWORK WITH
FLEX DUCTWORK OR SHEET METAL DUCTWORK AS REQUIRED.
14
15
KEY PLAN
PHASE 2
M-1.2
1
SCALE - 1/8" = 1'-0"
MECHANICAL FLOOR PLAN - PHASE 2
AS
N
OT
ED
JM
F
DF
N
0' 4' 16'8'
BRANCH/ FLEX DUCT SIZING SCHEDULE
DUCT SIZE CFM RANGE REMARK
6"Ø
8"Ø
10"Ø
12"Ø
0-100
101-260
261-400
401-600
MAX 10' LENGTH. FLEX DUCTWORK APPROVED ON SUPPLY SYSTEMSONLY.RETURN AND EXHAUST TO BE HARD DUCTED.
12X12 CD450 CFM
12X12 CD450 CFM
12X12CD450 CFM
6X6 CD110 CFM
(E) 16X6
(E) 22X6
(E) 16X10
(E) 14X6
(E) 10X4
(E)22X6
(E) 2
2X10
24X24 RR730 CFM
(E) 2
0X8
(E) 2
2X8
4
44
4
4
(E) 26X10
24X24 RR1300 CFM
(E) 16X6
(E) 20X8(E) 16X6
12X12 CD440 CFM
12X12 CD420 CFM
12X12 CD440 CFM
4
4
4
4
T (E) EH STAT
EH-
(E)EH-
(E)
PROVIDE SR HIGHIN SLOPEDCLG.
T(E) EH STAT
12X12 RR
12X12 RR
13
13
24X24 RR730 CFM
4
ADD-ALT100 CFM
ADD-ALT550 CFM
ADD-ALT240 CFM
ADD-ALT380 CFM
ADD-ALT380 CFM
ADD-ALT550 CFM
SPECIAL MECHANICAL CONSTRUCTION NOTES
1. ADDITIONAL DUCTWORK IS SHOWN TO ACCOMMODATE NEWROOMS OR CHANGES TO THE AREA USAGE. THIS IS BECAUSE OFEXISTING DUCTWORK FROM THE ASSOCIATED RTU IS NOT PRESENTOR INADEQUATE SIZE. ROUTE NEW DUCTWORK AS REQUIRED,PROVIDE ALL OFFSETS, FITTINGS ETC FOR A COMPLETEINSTALLATION.2. PROVIDE ALL NECESSARY FLEX DUCT, DUCTWORK, FITTINGSETC. FOR CONNECTIONS FROM NEW AIR DEVICES TO EXISTINGDUCTWORK
GENERAL MECHANICAL CONSTRUCTION NOTES
1. INTEGRAL OPPOSED BLADE DAMPERS SHALL BE PROVIDEDAT ALL AIR DEVICES. FINAL SUPPLY AIR DEVICE BALANCINGSHALL BE PERFORMED VIA INTEGRAL AIR DEVICE
2. ALL PENETRATIONS THRU RATED ASSEMBLIES SHALL BEPROVIDED WITH RADIANT DAMPERS.
3. FLEX DUCT WORK LENGTHS SHALL BE LIMITED TO WHAT ISALL INDICATED ON M-100.
4. ALL DIFFUSERS AND REGISTERS LOCATED IN TOILET ROOMSSHALL BE ALUMINUM CONSTRUCTION.
5. ALL RETURN/EXHAUST REGISTERS SHALL HAVE 45˚ FIXEDBLADES.
6. ALL SUPPLY MAINS SHALL BE LINED WITH 1" INTERNAL LINING. ALL BRANCH DUCTWORK SHALL BE EXTERNALLYWRAPPED.
7. REFER TO RTU DETAIL FOR INSTALLATION REQUIREMENTS.
8. ALL DUCT SIZES ARE INSIDE DUCT DIMENSIONS.9. REFER TO ARCHITECTURAL PLANS FOR FINAL AIR DEVICE
LOCATIONS.10. CONNECT NEW AIR DEVICES TO EXISTING DUCTWORK WITH
FLEX DUCTWORK OR SHEET METAL DUCTWORK AS REQUIRED.
MECHANICAL NOTES (ALL PHASES):
CAP DUCT AIR TIGHT SEAL.
DUCTWORK FROM RTU-5 TO REMAIN. BALANCE AIRDEVICES TO CFM INDICATED.
CONNECT AS REQUIRED WITH 'HARD DUCT' THE RETURNREGISTER TO EXISTING RETURN MAIN.
CONNECT MAIN LOBBY AIR DEVICES IN NEW CEILINGGRID TO EXISTING DUCTWORK AS REQUIRED.
EXISTING RTU TO REMAIN.
NEW RTU- SEE SCHEDULE.
NEW INLINE EXHAUST FAN, SEE SCHEDULE FOR FURTHERINFORMATION.
NEW ROOFTOP EXHAUST FAN, SEE SCHEDULE FORFURTHER INFORMATION.
EXISTING EXHAUST DUCT UP TO GOOSENECK ON ROOF.
EXISTING EXHAUST DUCT DN TO HOOD.
EXISTING EXHAUST DUCT UP TO ROOFTOP WEATHER CAP
INSTALL DUCT MOUNTED SMOKE DETECTOR IN RETURNDUCT MAIN.
BALANCE AIR DEVICE TO EXISTING AIRFLOW.
TYPICAL FOR ALL CONNECTIONS BETWEEN NEW ANDEXISTING WORK.
CONNECT NEW FLEX DUCTWORK SERVING VAV BOXES TOEXISTING DUCTWORK AS REQUIRED. (TYP)
11
10
9
8
7
6
5
4
3
1
2
12
13
14
15
NOTE:ADD - ALT IS FOR RTU-2 (17.5 TONS) TO BE REPLACED.PER EXISTING DRAWINGS THE TOTAL AIRFLOW OF THE UNIT IS 4955CFM. THE CFM NOTED FOR AIR DEVICES SERVED BY RTU-2 ARE FORTHE EXISTING UNIT NOT BEING REPLACED AND AN ADD- ALT CFM ISFOR THE UNIT BEING REPLACED.
KEY PLAN
PHASE 3M-1.3
1
SCALE - 1/8" = 1'-0"
MECHANICAL FLOOR PLAN - PHASE 3
AS
N
OT
ED
JM
F
DF
N
0' 4' 16'8'
CD
CEILING
TRAPROOF
FLASH WATERTIGHT
SUPPLY AIR
FLEXIBLECONNECTION (TYP.)
PROVIDE 45° TAPEREDCONNECTION AT RISER(TYP.)
FACTORY ROOF CURB
CONDENSATE DRAIN,DISCHARGE AT ROOF DRAIN
ACOUSTICALLY LINED DUCTWORKFIRST 10' OF SUPPLY AND RETURN,ALL OTHER DUCTWORK SHALL HAVEWRAP INSULATION
---RTU
RETURN AIR
M-2
1
SCALE: NONE
ROOFTOP UNIT DETAIL
PLUG
EXTEND AND SPILLTO ROOF DRAIN
TYPE "L" COPPEROR SCH 40 PVC
1 1/2" FOR DRAWTHRU UNITS
PLUG
M-2
2
SCALE: NONE
CONDENSATE TRAP DETAIL
ROOFTOPUNIT
MATERIAL:
S
SMOKE DETECTOR, UNITS OVER 2000 CFM, WIRED FORUNIT SHUTDOWN AND CONNECTED TO BLDG.FIRE ALARM SYSTEM AS REQUIRED
NEOPRENE GASKET
12" HIGH INSULATEDROOF CURB
ROOF
PENETRATION BOX
INSULATED REMOVABLECOVER
BASIS: PATE MODEL: CPBA-2 ORSHOP FABRIBATED
PROVIDE NEOPRENEPENETRATION SEAL AT ALLREFRIGERANT PIPES
3" Ø PVC FROM HOT WATER HEATER
2" RIGID FIBERGLASS INSULATIONINSTALL WITH WELDED PINS
BRAZED 90° ELBOW FITTING (TYPALL REFRIGERANT LINES)
SIDE VENT TERMINAL
SUPPLY AIR
MAIN DUCT
TAPERED CONNECTION 45º ANGLE(IF MAIN DUCT IS RECTANGULAR) ORCONICAL CONNECTION (IF MAIN DUCTIS ROUND) L = 1/4 W; 4" MIN
W
LBRANCH DUCT
(SEE PLANS FOR SIZE)UNLESS INDICATED OTHERWISEROUND DUCT TO DIFFUSER
VOLUME DAMPER
MAIN DUCT
FLEX DUCT10'-0" LONG
MAX
PLAN VIEW
ROOF DECK
CONDUIT FOR POWER TO FAN TOCLEAR DAMPER OPERATION
ROOFING OVER CURB BYROOFING CONTRACTOR
INSECT SCREEN
SECURE FAN BASE TO CURB
MOTOR
SETTING OF CURB BYMECH. CONTRACTOR
ANCHOR BACKDRAFTDAMPER TO ROOF DECK
GRAVITY BACKDRAFT DAMPER WITHADJUSTABLE COUNTER BALANCE
INSULATED ROOF CURB
M-2
5
SCALE: NONE
ROOF MOUNTED EXHAUST FAN DETAIL
M-2
6
SCALE: NONE
ROOF - PENETRATION BOX DETAIL
M-2
3
SCALE: NONE
FLEXIBLE DUCT DETAIL
M-2
4
SCALE: NONE
BRANCH TAKE-OFFS
ADD-ALT
AS
N
OT
ED
JM
F
DF
UNIT NO.
675
CFMMODELMFGR
ELECTRICALCHARACTERISTICS
STANDARD OFDESIGN
MUNICIPAL OFFICE BATHROOMS INLINE 0.5
ESP HP RPM WEIGHT
1
2
1
FLA
PROVIDE: SPEED CONTROLLER, GRAVITY BACKDRAFT DAMPER,DISCONNECT SWITCH,ROOF CURB AND OR ROOF CURB ADAPTER,BIRD SCREEN.
3 PROVIDE: SPEED CONTROLLER, DISCONNECT SWITCH, INTEGRALGRAVITY BACKDRAFT DAMPER, VIBRATION ISOLATION AND HANGERKIT.
GREENHECK
SONE
EF-M-1 120-V - 1Ø - 60 Hz
REMARKSTYPEAREA SERVED
EXHAUST FAN SCHEDULE
VERIFY THAT NEW EXHAUST FAN MATCHES EXISTING FAN TYPE, CFM, SP & VOLTAGE OF EXISTINGFAN. CONNECT NEW EXHAUST FAN INTO EXISTING CONTROL DEVICES.
SEQUENCE OF OPERATIONS:GENERAL1. UNIT SHALL HAVE A 7-DAY PROGRAMMABLE THERMOSTAT WITH THE FOLLOWING SCHEDULING MODES. a. OCCUPIED b. UNOCCUPIED2. IF ROOFTOP UNIT AIRFLOW IS 2000 CFM OR GREATER, A SMOKE DETECTOR SHALL BE PROVIDED IN THE AIRSTREAM AND INTEGRATED WITH THE FIRE ALARM SYSTEM TO DE-ENERGIZE THE FAN IN THE EVENT OF A FIRE ALARM EVENT.OCCUPIED MODE1. WHEN SYSTEM IS INDEXED TO THE OCCUPIED MODE THE FOLLOWING SHALL OCCUR. a. FAN TO BE INDEXED TO "ON" b. OUTSIDE AIR DAMPER TO BE OPENED TO THE MINIMUM POSITION. c. RETURN AIR DAMPER TO BE INDEXED TO THE APPROPRIATE POSITION RELATIVE TO THE OA DAMPER. (I.E. OA = 10%, RA = 90%) d. MODES OF OPERATION COOLING: WHEN SPACE TEMPERATURE RISES ABOVE THE THERMOSTATS COOLING SETPOINT AND THE OUTSIDE AIR ENTHALPY IS ABOVE THE ECONOMIZER
SETPOINT, THE FAN & 1ST STAGE OF REFRIGERATION CIRCUIT SHALL BE ENERGIZED TO PROVIDE COOLING TO THE SPACE. ON A CONTINUED RISE INSPACE TEMPERATURE, THE SECOND STAGE OF COOLING SHALL BE ENERGIZED (WHERE APPLICABLE). ON A DROP IN SPACE TEMPERATURE THEREVERSE SHALL OCCUR.
HEATING: WHEN SPACE TEMPERATURE DROPS BELOW THE THERMOSTATS HEATING SETPOINT THE FAN & 1ST STAGE OF HEATING CIRCUIT SHALL BEENERGIZED TO PROVIDE HEATING TO THE SPACE. ON A CONTINUED FALL IN SPACE TEMPERATURE THE SECOND STAGE OF HEATING SHALL BEENERGIZED (WHERE APPLICABLE). ON A RISE IN SPACE TEMPERATURE THE REVERSE SHALL OCCUR.
ECONOMIZING: WHEN SPACE TEMPERATURE RISES ABOVE THE THERMOSTAT'S COOLING SETPOINT AND THE OUTSIDE AIR ENTHALPY IS AT OR BELOW THEECONOMIZER SETPOINT, THE FAN SHALL ENERGIZE AND THE OUTSIDE AIR DAMPER AND RELIEF DAMPER SHALL MODULATE OPEN AND THERETURN AIR DAMPER SHALL MODULATE CLOSED TO MAINTAIN A 53°F MIXED AIR TEMPERATURE. THE POWERED EXHAUST FAN SHALL ENERGIZE TOMAINTAIN BUILDING PRESSURIZATION (WHERE APPLICABLE). IF MIXED AIR EXCEEDS SETPOINT AND THE SPACE TEMPERATURE CONTINUES TORISE, THE REFRIGERATION CIRCUIT SHALL BE ENERGIZED. ON A FALL IN SPACE TEMPERATURE THE REVERSE SHALL OCCUR.
UNOCCUPIED MODE1. WHEN THE SYSTEM IS INDEXED TO THE UNOCCUPIED MODE THE FOLLOWING SHALL OCCUR. a. FAN SHALL BE INDEXED TO "AUTO" b. OUTSIDE AIR DAMPER SHALL REMAIN CLOSED c. RETURN AIR DAMPER SHALL BE INDEXED TO THE OPEN POSITION (100%) d. THE HEATING & COOLING CIRCUITS SHALL CYCLE TO MAINTAIN SET BACK TEMPERATURES.
NO SCALE
PACKAGED ROOFTOP HEATING / COOLING
HONEYWELLCOMMERCIALTHERMOSTAT
ROOF TOP AIRCONDITIONING UNIT
S
INPUT
COOLING-DX
OUTPUT FILTER
INDIRECT FIRED GAS HEAT
SMBHTMBH
95 DEG OAT1
PACKAGED ROOFTOP AIR CONDITIONING UNIT SCHEDULE
REMARKSMOCP VOLT/PHASE/HZMCA
ELECTRICAL CHARACTERISTICSWEIGHT
LBS MODELMFGR.
STANDARD OF DESIGN
TRAN-EXSITING
NOMINALTONS
SUPPLYAIR CFM HP
ESP(IN. W.G.)
INDOOR SUPPLY FANOUTSIDEAIR CFM
TYPEUNIT NO.
TRANERTU-1 VAV UNIT W/ DX COOLING & GAS HEAT MERV 8
AIR DEVICE SCHEDULE
CD SUPPLY
SYMBOL TYPE MOUNTINGSERVICE ACCESSORIES REMARKSSIZE MATERIAL
STEEL
FINISH
WHITE
MAX.NC
25LOUVER
MODELMFGR.
STANDARD OF DESIGN
PRICEOBD
RR OBDWHITERETURN ALUMINUM 25RETURN REGISTER PRICEREFER TO PLAN
REFER TO PLAN
REFER TO PLAN
REFER TO PLAN
ER-1 OBDWHITEEXHAUST ALUMINUM 30EXHAUSTREGISTER
PRICEREFER TO PLAN REFER TO PLAN
LD-1 OBDWHITESUPPLY ALUMINUM 25 BORDER TYPE 15 FOR T-BAR CEILING INSTALLATION. LINEAR SLOT DIFFUSER
PRICEREFER TO PLAN REFER TO PLAN SDS
TRANERTU-2 MERV 8
RTU-5
RTU-6
RTU-7
TRANE- EXISTING
TRAN-EXISTING
AIRFLOWAPPLICATION
AIRFLOWRPM
EATDB/WB
UNIT LATDB/WB STAGES
EATF
LATF MBH MBH STAGES
EER/IEER (SEER)
2 PROVIDE ROOF CURB ADAPTERS FOR UNIT INSTALLATION, VARIABLE SPEED COMPRESSORS- MODULATING 25% - 100%, MODULATING GAS HEAT- 2.5:1 TURNDOWN, CFS FFS & COND DP OVERFLOW SWITCH, DEMAND CONTROL VENTILATION (CO2), CO2 DUCTMOUNTED ZONE SENSOR, POWER EXHAUST, BAYSENS119 PROGRAMMABLE ZONE TEMPERATURE SENSOR CONFIGURED AS A CONSTANT VOLUME UNIT, SINGLE ZONE VARIABLE AIR VOLUME CONTROL SEQUENCE OF OPERATION, THROUGH THE BASEELECTRICAL WITH DISCONNECT SWITCH,ECONOMIZER,REFERENCED OR COMPARATIVE ENTHALPY, MICROPROCESSOR CONTROLS, HUMIDITY DUCT MOUNTED SENSOR, DIRTY FILTER SWITCH, POWERED WEATHERPROOF GFI OUTLET, CONNECT CONDENSATEDRAIN TO EXISTING HORIZONTAL DRAIN ON ROOF, MC SHALL INSTALL SMOKE DETECTOR IN RETURN DUCT MAIN, DISCONNECT GAS LINES FROM UNITS BEING REMOVED AND RECONNECT GAS LINES TO NEW INSTALLED UNITS..
SPD
635
635
SQUARE TO ROUND ADAPTER AS REQUIRED.
3 /4" SPACING 45 ° DEFLECTION
3 /4" SPACING 45 ° DEFLECTION
TRANERTU-3 MERV 8
TRANE- EXSITINGRTU-4
UNIT NO. INLET
VAV BOX SCHEDULE
BOXTYPE
BASIS OF DESIGN
MFGR MODEL NO.REMARKS
VAV - A OPEN/SHUT
CFM RANGEM
OPEN/SHUT
OPEN/SHUT
OPEN/SHUT
OPEN/SHUT
WITH ECONOMIZER (RTU-3, 2-ADD-ALT)
SEQUENCE OF OPERATIONS:GENERAL1. A CHANGEOVER VAV SYSTEM RESPONDS TO THE CHANGING COOLING OR HEATING DEMANDS BY VARYING THE QUANTITY OR VOLUME OF AIR DELIVERED TO EACH ZONE.EACH ZONE HAS A TEMPERATURE SENSOR FOR INDIVIDUAL COMFORT CONTROL. THE RTU'S CONTROL SYSTEM DETERMINES ZONE HEATING OR COOLING NEEDS BY USINGVOTING LOGIC, THEN REQUESTS HEATING OR COOLING FROM THE RTU.2. THE ROOFTOP UNIT'S RETURN DUCT MOUNTED SMOKE DETECTOR SHALL BE INTEGRATED WITH THE FIRE ALARM SYSTEM TO DE-ENERGIZE THE FAN IN THE EVENT OF A FIRE ALARM EVENT.
VAV VOTING FOR SYSTEM HEAT OR COOL1. EACH ZONE ATTACHED TO THE RTU'S CONTROL SYSTEM CAN 'VOTE' FOR HEATING OR COOLING. EACH ZONE GETS ONE VOTE AND IS ELIGIBLE TO VOTE IF:
a. THE ZONE IS IN COMMUNICATION WITH THE RTU'S CONTROLS. b. THE ZONE HAS A VALID ZONE TEMPERATURE READING. c. THE ZONE IS EDITED TO BE A VOTER IN THE RTU'S CONTROLS SETUP (THROUGH THE "INCLUDE IN CHANGEOVER" CHECKBOX). d. THE ZONE IS NOT TAGGED BY THE RTU'S CONTROLS (SEE VAV ZONE TAGGING BELOW).
VAV ZONE TAGGING FOR NO VOTE1. A VAV ZONE IS TAGGED AND EXCLUDED FROM THE VOTING DECISION IF ANY OF THE FOLLOWING ARE PRESENT: a. THE SYSTEM IS NOT IN MORNING WARM-UP OR PRE-COOL. b.THE ZONE IS RECEIVING ITS DESIRED SUPPLY AIR AND THE HEAT COOL MODE MATCHES THAT OF THE RTU MEMBER. c.THE ZONE TEMPERATURE IS FARTHEST AWAY FROM THE SETPOINT OF ALL VOTING ZONES RECEIVING THE DESIRED SUPPLY AIR. d. THE ZONE TEMPERATURE REMAINS THREE OR MORE DEGREES AWAY FROM THE SETPOINT FOR 60 MINUTES. e. THE TAGGED ZONE CONTINUES TO OPERATE AND COMMUNICATE NORMALLY BUT CANNOT VOTE FOR HEAT OR COOL. THIS PREVENTS ONE ZONE FROM DRIVING THE COMFORT OF ALL OTHER ZONES IF ITS SETPOINTS OR LOAD CANNOT BE SATISFIED. 2. THE ZONE BECOMES AN ELIGIBLE VOTER WHEN: a. IT RETURNS TO WITHIN 1 °F OF ITS ACTIVE SETPOINT. b. THE SYSTEM BECOMES UNOCCUPIED. c. VAV TAGGING IS DISABLED.
ZONE HEAT/COOL CALL STRENGTH1. AFTER THE HEAT/ COOL MODE OF THE ZONE IS DECIDED THE STRENGTH OF ITS HEATING OR COOLING CALL IS DETERMINED. a. COOL CALLER: A VAV BECOMES A "COOL CALLER" IF IT IS A VOTING VAV AND ITS ZONE TEMPERATURE IS MORE THAN 1° F ABOVE THE ACTIVE COOLING SETPOINT. A VAV LOSES ITS COOL CALL STATUS IF IT BECOMES A NON-VOTER OR IF ITS ZONE TEMPERATURE IS LESS THAN THE ACTIVE COOLING SETPOINT PLUS 0.5° F. b. STRONG COOL CALLER: A VAV BECOMES A "STONG COOL CALLER" IF IT IS A VOTING VAV AND ITS ZONE TEMPERATURE IS MORE THAN 2° F ABOVE THE ACTIVE COOLING SETPOINT. A VAV LOSES ITS STRONG COOL CALLER STATUS IF IT BECOMES A NON-VOTER OR IF ITS ZONE TEMPERATURE IS LESS THAN THE ACTIVE COOLING SETPOINT PLUS 1°F. c. HEAT CALLER: A VAV BECOMES A "HEAT CALLER" IF IT IS A VOTING VAV, AND ITS ZONE TEMPERATURE IS MORE THAN 2°F BELOW ACTIVE HEATING SETPOINT. A VAV LOSES ITS HEAT CALLER STATUS IF IT BECOMES A NON-VOTER OR IF ITS ZONE TEMPERATURE IS GREATER THAN THE ACTIVE HEATING SETPOINT MINUS 1.5°F. d. STRONG HEAT CALLER: A VAV BECOMES A "STRONG HEAT CALLER" IF IT IS A VOTING VAV AND ITS ZONE TEMPERATURE IS MORE THAN 3°F BELOW THE ACTIVE HEATING SETPOINT.A VAV LOSES ITS "STRONG HEAT CALLER" IF IT BECOMES A NON-VOTER OR IF ITS ZONE TEMPERATURE IS GREATER THAN THE ACTIVE HEATING SETPOINT MINUS 2° F
HEAT/COOL DECISION AND CONTROL OF THE RTU1. THE RTU CONTROLS PROGRAM DETERMINES THE QUANTITY AND THE STRENGTH OF ALL HEATING AND COOLING CALLS. AT POWER UP AND ON TRANSITION FROM UNOCCUPIED TO OCCUPIED, THE GREATER NUMBER OF HEAT OR COOL CALLS DETERMINES THE HEAT/COOL MODE OF THE AC SYSTEM. IF ALL THE SPACES ARE SATISFIED ( NO CALL) THE SYSTEM SHALL SEND A FAN ONLY REQUEST TO THE RTU.2. THE RTU CONTROLS SETS THE SUPPLY TEMPERATURE SETPOINT OF THE RTU, TAKING INTO CONSIDERATION THE VAV MEMBER'S DEVIATION FROM SETPOINT. IF ALL MEMBERS ARE SATISFIED ( NO VOTES), THE RTU SHALL BE IN "FAN ONLY. WHEN THE VAV'S NEED HEAT OR COOL, THE RTU'S CONTROLS SETS THE HEAT/COOL MODE ACCORDINGLY.
ECONOMIZING: WHEN SPACE TEMPERATURE RISES ABOVE THE THERMOSTAT'S COOLING SETPOINT AND THE OUTSIDE AIR ENTHALPY IS AT OR BELOW THEECONOMIZER SETPOINT, THE FAN SHALL ENERGIZE AND THE OUTSIDE AIR DAMPER AND RELIEF DAMPER SHALL MODULATE OPEN AND THERETURN AIR DAMPER SHALL MODULATE CLOSED TO MAINTAIN A 53°F MIXED AIR TEMPERATURE. THE POWERED EXHAUST FAN SHALL ENERGIZE TOMAINTAIN BUILDING PRESSURIZATION (WHERE APPLICABLE). IF MIXED AIR EXCEEDS SETPOINT AND THE SPACE TEMPERATURE CONTINUES TORISE, THE REFRIGERATION CIRCUIT SHALL BE ENERGIZED. ON A FALL IN SPACE TEMPERATURE THE REVERSE SHALL OCCUR.
UNOCCUPIED MODE1. WHEN THE SYSTEM IS INDEXED TO THE UNOCCUPIED MODE THE FOLLOWING SHALL OCCUR. a. FAN SHALL BE INDEXED TO "AUTO" b. OUTSIDE AIR DAMPER SHALL REMAIN CLOSED c. RETURN AIR DAMPER SHALL BE INDEXED TO THE OPEN POSITION (100%) d. THE HEATING & COOLING CIRCUITS SHALL CYCLE TO MAINTAIN SET BACK TEMPERATURES.
NO SCALE
PACKAGED ROOFTOP VAV HEATING / COOLING
HONEYWELLCOMMERCIALTHERMOSTAT
ROOF TOP AIRCONDITIONING UNIT
S
WITH ECONOMIZER (RTU-1 & 8)
VAV - B
VAV - C
VAV - D
VAV - E
TRANE
TRANE
TRANE
TRANE
TRANE
12.5
10
3
3
3
15
15
DOWNFLOW
DOWNFLOW
DOWNFLOW
1.75"
CONSTANT VOLUME UNIT W/ DX COOLING & GAS HEAT
CONSTANT VOLUME UNIT W/ DX COOLING & GAS HEAT
1.0"
0.75"
VARIABLE
2
0.5
0.5
0.5
675EF-M-2
750EF-P-1
400EF-P-2
MUNICIPAL PUBLIC BATHROOMS
POLICE LOCKERS AND BATHROOMS
POLICE LAB HOODRTC
4 RTC- ROOFTOP CENTRIFUGAL FAN.
3
1 3
2 4
1 3SQ-090-VG1 /6 1495 7.6 3.4 41 LBS
SQ-100-VG
SQ-100-VG
1 /4
1 /4 120-V - 1Ø - 60 Hz
120-V - 1Ø - 60 Hz
120-V - 1Ø - 60 Hz
56 LBS56 LBS GREENHECK
GREENHECK
GREENHECK
G-099-VG54 LBS1 /4
1263
12631384 9.1
6.4
6.4 3.73.7
2.85INLINE
INLINE
5000
4000
1100
25-170 4"Ø VCCF
VCCF
VCCF
VCCF
VCCF
5"Ø
6"Ø
8"Ø
10"Ø
50-260
60-380
105-680
165-1000
OPEN/SHUTVAV - F TRANE VCCF12"Ø240-1500
460-3-60
460-3-60
460-3-60
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
150940
5000
4000
1100
4539MODULATING250.0114.616380/678675750
PROVIDE ROOF CURB ADAPTERS FOR UNIT INSTALLATION, VAV OVERSIZED MOTOR W/ SHAFT GROUND RING,(3) VARIABLE SPEED COMPRESSORS- MODULATING 4% TO 100%,CF, FF AND CONDENSATE OVERFLOW SWITCH, DEMAND VENTILATION CONTROLS,MODULATING GAS HEAT 2.5:1, CO2 SENSOR DUCT MOUNTED,POWER EXHAUST, ECONOMIZER,THROUGH THE BASE ELECTRICAL WITH CIRCUIT BREAKER,THROUGH THE BASE ELECTRICAL WITH DISCONNECT SWITCH,REFERENCED OR COMPARATIVE ENTHALPY,COMPARATIVE ENTHALPY, VAV OPERATION, UNIT AND COMPONENTS SHALL BE ULTRA HIGH CONSTRUCTION, MICROPROCESSOR CONTROLS, HUMIDITY DUCT MOUNTED SENSOR, DIRTY FILTER SWITCH, POWERED WEATHERPROOF GFI OUTLET, CONNECTCONDENSATE DRAIN TO EXISTING HORIZONTAL DRAIN ON ROOF, BAROMETRIC RELIEF, MC SHALL INSTALL SMOKE DETECTOR IN RETURN DUCT MAIN, DISCONNECT GAS LINES FROM UNITS BEING REMOVED AND RECONNECT GAS LINES TO NEW INSTALLEDUNITS..
- - - -
3
3
YZC120F4RVA12.2/23.0 15404531188.0108.3561.25
80.0101.447.3 64.0
86.56107.3760.21/58.5480/67VARIABLE2.75
24.6734.0959.6/57.1380/670.75
600
165
VARIABLE - - - - MODULATING
CONSTANT VOLUME UNIT W/ DX COOLING & GAS HEAT
CONSTANT VOLUME UNIT W/ DX COOLING & GAS HEAT
CONSTANT VOLUME UNIT W/ DX COOLING & GAS HEAT
CONSTANT VOLUME UNIT W/ DX COOLING & GAS HEAT
1
1
1
1
1
1
1 PROVIDE CONTROL STATS FOR EACH VAV BOX.
2
YHC037E4RMA13.0/17.5 7671512
4 PROVIDE ROOF CURB ADAPTERS FOR UNIT INSTALLATION, ECON-COMP ENTHALPY 0-100%, CFS FFS & COND DP OVERFLOW SWITCH, DEMAND CONTROL VENTILATION (CO2), CO2 DUCT MOUNTED ZONE SENSOR, ECONOMIZER,POWER EXHAUST, BAYSENS119PROGRAMMABLE ZONE TEMPERATURE STAT, SINGLE ZONE CONSTANT VOLUME, THROUGH THE BASE ELECTRICAL WITH DISCONNECT SWITCH,ECONOMIZER,REFERENCED OR COMPARATIVE ENTHALPY, MICROPROCESSOR CONTROLS, HUMIDITY DUCT MOUNTEDSENSOR, DIRTY FILTER SWITCH, POWERED WEATHERPROOF GFI OUTLET, CONNECT CONDENSATE DRAIN TO EXISTING HORIZONTAL DRAIN ON ROOF, DISCONNECT GAS LINES FROM UNITS BEING REMOVED AND RECONNECT GAS LINES TO NEW INSTALLED UNITS..
1905
110.07142.1959.98/58.02 YZD150F4RVC12.4/19.60 2550
ADD-ALT
ADD-ALT
ADD-ALT
ADD-ALT
ADD-ALT
RTU-8 TRANEMERV 812.5 DOWNFLOWVAV UNIT W/ DX COOLING & GAS HEAT 5000 460-3-60 YZD150F4RVC12.4/19.60 25504539MODULATINGVARIABLE 250.0114.6163110.07142.1959.98/58.0280/671.75"5000 8675750 - - - - 3
RTU-2 17.5 DOWNFLOWCONSTANT VOLUME UNIT W/ DX COOLING & GAS HEAT 4955 4955 750 - - - - - - - -TRANE- EXSITING- - - - - - - - - - - -- - - -- - - -- - - -- - - -- - - -- - - -- - - -- - - -- - - -- - - -- - - -- - - -- - - -- - - -- - - -- - - -
DOWNFLOW
DOWNFLOW
DOWNFLOW
DOWNFLOW
780
5730
780
5730
120
600
4955 4955 750
940
4
SR SUPPLY STEEL WHITE 25LOUVER PRICEOBDREFER TO PLAN REFER TO PLAN 520 DOUBLE DEFLECTION BLADES.
AS
N
OT
ED
JM
F
DF
UNITNO.
1. ALL PLUMBING WORK SHALL BE IN ACCORDANCE WITH THE CURRENT PLUMBING CODE AND ALLAPPLICABLE LOCAL CODES AND DRAWINGS.
2. ALL MATERIALS AND EQUIPMENT SHALL BE NEW.3. MANUFACTURERS' MODEL NUMBERS ARE SPECIFIED SOLELY TO ESTABLISH STANDARDS OF QUALITY
FOR PERFORMANCE AND MATERIALS.4. PRODUCT INSTALLATION SHALL ADHERE TO MANUFACTURERS RECOMMENDATIONS.5. PROVIDE ACCESS PANELS FOR EQUIPMENT THAT REQUIRES PERIODIC SERVICE & TO ACCESS VALVES
AND ALL CONCEALED MECHANICAL EQUIPMENT.6. CONTRACTOR SHALL COORDINATE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS OF ALL
PLUMBING EQUIPMENT WITH THE ELECTRICAL DRAWINGS.7. ALL PLUMBING EQUIPMENT, PIPING, INSULATION, ETC., INSTALLED IN HVAC PLENUM SPACES SHALL
MEET CODE REQUIREMENTS FOR SMOKE AND COMBUSTIBILITY.8. PROVIDE SHUTOFF VALVES ON ALL BRANCH PIPING AND ON ALL SUPPLIES TO INDIVIDUAL FIXTURES
AND EQUIPMENT. PROVIDE BALL VALVES ON ALL WATER MAIN BRANCHES IN CORRIDORS AND WHEREINDICATED ON DRAWINGS. ALL VALVES SHALL BE ACCESSIBLE.
9. SUPPORT ALL EQUIPMENT PIPING FROM BLDG STRUCTURE TO PROVIDE A VIBRATION FREEINSTALLATION. NOTIFY STRUCTURAL ENGINEER OF ALL WEIGHTS AND METHODS OF SUPPORT.
10. RUN PIPING CONCEALED, UNLESS SPECIFIED OTHERWISE, AND CLEAR OF CEILING INSERTS.11. PROVIDE CLAMPS, OFFSETS, EXPANSION JOINTS, ANCHORS AND GUIDES AS NECESSARY TO PREVENT
STRESS ON PIPING.12. PROVIDE VENTS AT HIGH POINTS IN PIPING SYSTEMS AND DRAIN VALVES AT LOW POINTS.13. PROVIDE AT LEAST THREE-ELBOW SWING FOR PIPE TAKE-OFFS TO RISERS.14. HORIZONTAL SANITARY PIPING 2 1/2" AND SMALLER TO BE PITCHED A MINIMUM OF 1/4" PER FOOT IN
THE DIRECTION OF THE FLOW.15. HORIZONTAL SANITARY PIPING 3" AND UP TO AND INCLUDING 6" TO BE PITCHED AT A MINIMUM OF 1/8"
PER FOOT IN THE DIRECTION OF FLOW.16. HORIZONTAL SANITARY PIPING GREATER THAN 6" TO BE PITCHED A MINIMUM OF 1/16" PER FOOT IN
THE DIRECTION OF FLOW.17. CLEANOUTS SHALL BE PROVIDED AT THE BASE OF ALL SANITARY AND RAIN WATER VERTICAL STACKS.18. ANY REFERENCE TO ELECTRICAL, PLUMBING AND HVAC CONTRACTORS, NOTED ON THESE DRAWINGS
OR STATED IN THE SPECIFICATIONS SHALL NOT BE MISCONSTRUED AS AN INTENTION TO DEFINESEPARATE CONTRACTORS FOR THE RESPECTIVE WORK. THE GENERAL CONTRACTOR SHALLCO-ORDINATE AND PROVIDE A COMPLETE BUILDING WITH COMPLETE MECHANICAL AND ELECTRICALSYSTEMS, REGARDLESS OF ANY SPECIFICATION REFERENCES TO OTHER CONTRACTORS.
ACRYLIC SHOWER MODULECOMFORTDESIGNS
XSA4136BF.75 43 1/4"x36 1/4"x82 7/8" --- --- ---
SINGLE BOWL SINK ELKAY 20 GAUGE STAINLESS STEELHD320874LFR 15" x 15" x 6" DECK MOUNTED FAUCET, LEVER HANDLES ---
2" C.B. CAST BRASS
1 1/2" C.B. CAST BRASS W/CLEANOUT PLUG
Z5755-U SLOAN #8180-1.0BATTERY POWERED SENSOR OPERATED
FLUSHOMETERINTEGRALURINAL ZURN WALL HUNG 1.0 GPF ---
KOHLERUNDERMOUNT LAVATORY 20 GAUGE STAINLESS STEELK-2608-SU 19 7/8" x 16 11/16" SLOAN #ESD-2101-CPBATTERY POWERED SENSOR OPERATED
FAUCET & SOAP COMBOPROVIDE TRUEBRO #102W & 105W SUPPLY & WASTE PIPING INSULATION---
1 1/2" C.B. CAST BRASS W/CLEANOUT PLUG
---
DP, DN
VTR
WC
WH
UR
TYP
UP
V
TEE LOOKING UP
WALL HYDRANT
WATER CLOSET
TEE LOOKING DOWN
VENT THRU ROOF
TYPICAL
URINAL
VENT
140 HW
BLDG
ARCH
DWG
DP, DN
COND
MSB
140
SAN
NTS
RBF
SAN
RAF
RAC
LAV
IWR
MFR
G
HWR
G
HW
HB
CO
FLR
UP
FD
CD
ED ED
DN
CTE
CO
CW
AFF
AP
ELBOW DOWN OR DROP
ELBOW UP OR RISE
FLOOR CLEANOUT
HOT WATER
INDIRECT WASTE RECEPTOR
MANUFACTURER
NOT TO SCALE
RUN BELOW FLOOR
HOT WATER RETURN
MOP SERVICE BASIN
RUN ABOVE FLOOR
RUN ABOVE CEILING
FLOW IN DIRECTION OF ARROW
HOSE BIBB W/ VACUUM BREAKER
FLOOR DRAIN
140
P-TRAP
SANITARY
LAVATORY
GAS
FLOOR
EMERGENCY DRAIN
ACCESS PANEL
BALL VALVE
CHECK VALVE
CONDENSATE
COLD WATER
CONNECT TO EXISTING
DIRECTION OF SLOPE
ABOVE FINISHED FLOOR
DOWN
DRAWING
BUILDING
WALL CLEANOUT
ARCHITECT
RWC RAIN WATER CONDUCTOR
RCP REINFORCED CONCRETE PIPE
RWC
W/ PRESSURE BALANCING MIXING VALVE, HAND HELD SHOWER ASSEMBLYWITH SLIDE BAR, VACUUM BREAKER AND 60" HOSE.
WDP WASHING MACHINE DRAIN PAN
ELKAY #LK2477CR
2# HIGH PRESSURE 2 PSI GAS2#
DOUBLE BOWL SINK DAYTON 23 GAUGE STAINLESS STEELK233224DF 33 1/2"x22"x6 1/16" ELKAY #LK2478CR LEVER HANDLE ------1 1/2" W/ CLEANOUT PLUG
1. PIPE MATERIALSA. SERVICE: ABOVE GROUND WATER PIPING
PIPE MATERIAL: TYPE L COPPER TUBING ASTMB882 FACTORY.FITTING MATERIAL: WROUGHT COPPER AND BRONZE SOLDER JOINTS.PIPE JOINT: 95-5 LEAD FREE SOLDER
B. SERVICE: SANITARY WASTE & VENT (ABOVE GRADE)PIPE MATERIAL: SERVICE WEIGHT CAST IRON NO-HUB CONFORMING TO CS 301, TYPE ME COPPERTUBINGFITTING MATERIAL: CAST IRON DRAINAGE PATTERN, WROUGHT COPPER DRAINAGE PATTERN TOSUIT PIPE MATERIALPIPE JOINT: HEAVY DUTY CISPI APPROVED STAINLESS STEEL NO-HUB COUPLING W/ NEOPRENEGASKET, 95-5 SOLDER FOR COPPER.
2. VALVESA. BALL VALVES 2" AND SMALLER ON WATER SERVICES SHALL BE 2 PIECE ALL BRONZE WITH FULL
PORT STAINLESS STEEL BALL, TEFLON SEATS, SOLDER ENDS AND 600 PSI COLD WORKINGPRESSURE: JENKINS 902, APOLLO OR WATTS APPROVED EQUAL, UNLESS OTHERWISE NOTED.
3. INSULATIONA. INSULATION SHALL BE BY OWENS CORNING, CERTAIN-TEED OR MANVILLE.B. INSULATION, JACKETS AND ADHESIVES SHALL BE FLAME RETARDANT AND SHALL HAVE ASTM E-84
FIRE HAZARD RATINGS OF 25 FLAME SPREAD, 50 SMOKE DEVELOPED AND 50 FUEL CONTRIBUTED.C. DOMESTIC HOT WATER: NEW DOMESTIC HOT WATER PIPING SUPPLY AND RECIRCULATION PIPING
SHALL BE INSULATED WITH HEAVY DENSITY FIBERGLASS WITH SELF-SEALING LAP AND ALLSERVICE JACKET. FITTINGS AND VALVES SHALL BE INSULATED WITH TWO LAYERS BLANKETINSULATION WITH PVC COVERS. INSULATION SHALL BE RATED FOR MAXIMUM OPERATINGTEMPERATURE OF 450 DEGREES F. REFER TO PIPE INSULATION MATRIX ON THIS SHEET FORREQUIRED INSULATION THICKNESS.
D. DOMESTIC COLD WATER: NEW COLD WATER SUPPLY PIPING, VALVES AND FITTINGS SHALL BEINSULATED AS SPECIFIED FOR HOT WATER SUPPLY PIPING, IN ADDITION, CONTINUOUS VAPORBARRIER SHALL BE MAINTAINED. REFER TO PIPE INSULATION MATRIX ON THIS SHEET FORREQUIRED INSULATION THICKNESS.
E. RAIN WATER CONDUCTOR: HORIZONTAL RAIN WATER CONDUCTORS SHALL BE INSULATED WITHMINIMUM 1" THICK INSULATION.
4. HANGERS, ANCHORS, CLAMPS AND INSERTSA. PROVIDE CAST BRASS SPLIT RING HINGE HANGERS, SUPPORT PIPING FROM BUILDING STRUCTURE
TO MAINTAIN REQUIRED GRADE AND PITCH OF PIPE LINES, PREVENT VIBRATION, SECURE PIPINGIN PLACE. SECURE HANGERS TO INSERTS WHERE PRACTICAL. HANGER RODS SHALL HAVEMACHINE THREADS.
B. HANGER RODS SHALL BE CONNECTED TO BEAM CLAMP, UL APPROVED CONCRETE INSERTS ORPHILLIPS SHALL BE APPROVED EQUAL EXPANSION SHIELD. RAMSET OR POWER DRIVEN INSERTSWILL NOT BE ALLOWED.
C. HANGER SPACING SHALL MEET REQUIREMENTS OF STATE AND LOCAL CODES.5. SLEEVES AND PENETRATIONS
A. PIPE SLEEVES THROUGH FIRE RATED CONSTRUCTION SHALL BE SCHEDULE 40 STEEL. SLEEVESTHROUGH PARTITIONS AND NON FIRE RATED CONSTRUCTION SHALL BE 26 GAUGE GALVANIZEDSTEEL WITH LOCAL LONGITUDINAL SEAMS.
B. PACKING FOR SLEEVES THAT DO NOT REQUIRE MAINTENANCE OF FIRE RATINGSHALL BE OAKUM,SILICATE FOAM, CERAMIC FIBER WITH APPROVED SEALANT. PACK OR FOAM TO WITHIN ONE INCHOF BOTH WALL SURFACES. SEAL PENETRATION PACKING WITH APPROVED CAULKING ANDPAINTABLE WATERPROOF MASTIC SURFACE FINISH OR SILICONE CAULKING.
6. TESTINGA. TEST AND ADJUST PLUMBING SYSTEMS AS REQUIRED BY ARCHITECT AND AUTHORITIES THAT HAVE
JURISDICTION. PERFORM TEST RECOMMENDED BY MANUFACTURERS OF MATERIAL ANDEQUIPMENT; THIS REQUIREMENT MAY BE WAIVED BY ARCHITECT. TEST PLUMBING SYSTEMSUNDER PRESSURE AND HEADS SPECIFIED IN PLUMBING CODES. CLEAN SYSTEMS THOROUGHLYBEFORE TESTING. FIXTURES, EQUIPMENT, PIPE, VALVES AND FITTINGS SHALL BE FREE OF GREASE,METAL CUTTINGS, DIRT AND OTHER FOREIGN MATERIAL. REPAIR STOPPAGE, DISCOLORATION ANDDAMAGE TO PARTS OF BUILDING, FINISHES AND FURNISHINGS DUE TO FAILURE TO PROPERLYCLEAN PIPING SYSTEM.
7. DISINFECTION OF WATER SYSTEMSA. WATER PIPING SYSTEMS SHALL BE THOROUGHLY DISINFECTED WITH A SOLUTION CONTAINING NO
LESS THAN 50 PARTS PER MILLION OF AVAILABLE CHLORINE. CHLORINATING MATERIALS SHALLBE EITHER LIQUID CHLORINE OR SODIUM HYPOCHLORITE SOLUTION, SHALL BE INTRODUCED INTOTHE SYSTEM AND DRAWN TO ALL POINTS IN THE SYSTEM. DISINFECTION SOLUTION SHALL BEALLOWED TO REMAIN IN SYSTEM FOR 24 HOURS, DURING THIS TIME, VALVES AND FAUCETSSHALL BE OPENED AND CLOSED SEVERAL TIMES. AFTER DISINFECTION, SOLUTION SHALL BEFLUSHED FROM THE SYSTEM WITH CLEAR WATER UNTIL RESIDUAL CHLORINE CONTENT IS NOGREATER THAN 2 PARTS PER MILLION.
8. IDENTIFICATION OF PLUMBING SYSTEMS:A. PROVIDE PIPING IDENTIFICATION LABELS AND DIRECTIONAL ARROWS ON ALL PLUMBING SYSTEMS.
INSTALL LABELS AT 10' INTERVALS & AT EACH SIDE OF FLOOR & WALL SEPARATIONS.B. PROVIDE VALVE TAGS AT EACH DOMESTIC WATER SHUTOFF VALVE. PROVIDE VALVE TAG INDEX
IDENTIFYING VALVE NUMBER, LOCATION AND SERVICE.9. MISCELLANEOUS
A. ALL PLUMBING WORK SHALL BE IN ACCORDANCE WITH THE CURRENT PLUMBING CODE AND ALLAPPLICABLE CODES AND STANDARDS
B. PROVIDE SHUTOFF VALVES ON ALL BRANCH PIPING AND ON ALL SUPPLIES TO INDIVIDUAL FIXTURESAND EQUIPMENT. PROVIDE BALL VALVES ON ALL WATER MAIN BRANCHES IN CORRIDORS ANDWHERE INDICATED ON DRAWINGS. ALL VALVES SHALL BE ACCESSIBLE.
C. PROVIDE VENTS AT HIGH POINTS IN PIPING SYSTEMS AND DRAIN VALVES AT LOW POINTS.D. PROVIDE AT LEAST THREE-ELBOW SWING FOR PIPE TAKE-OFFS TO RISERS.E. PITCH PIPING MINIMUM 1/8" PER 1'-0" TOWARDS DIRECTION OF FLOW TO ALLOW FOR DRAINING.F. FLOOR CLEANOUTS SHALL BE JR SMITH 4031 SERIES.G. WALL CLEANOUTS SHALL BE JR SMITH 4436 SERIES.H. PROVIDE TRAP GUARDS ON ALL FLOOR DRAINS.I. WHERE PIPING (DOMESTIC WATER, SANITARY, VENT, GAS, ETC.) IS LOCATED WITHIN WALLS,
PROVIDE NAILER PLATES WHERE PIPING IS LOCATED WITHIN 1 1/2" OF THE FRAMING MEMBER.
ELONGATED BOWL,VITREOUS CHINA
ADA WATER CLOSETFLUSH VALVE
1.6 GPF SLOAN #8111 --- SOLID PLASTIC, OPEN FRONT SEAT W/O COVER, COMFORT SEATS #C104C1301MANSFIELDBATTERY POWERED SENSOR OPERATED
FLUSHOMETER
REFRIGERATOR OUTLET BOXW/ 1/4 TURN VALVE. PROVIDE FIRE RATED MODEL WHEN LOCATED INA RATED WALL.
DESCRIPTIONSYMBOLMFGR MODEL
FIXTURE
TYPE SIZE
PLUMBING FIXTURE SCHEDULE
TYPE SUPPLYTRAP COLOR CARRIER REMARKS
WC-1
UR-1
LAV-1
SHO-1
SK-1
SK-2
MFGR
INTEGRAL
---
1" SUPPLY
3/4" SUPPLY
1/2" SUPPLIES, ANGLE STOP, C.B.ESCUTCHEON
1/2" SUPPLIES
1/2" SUPPLIES, ANGLE STOP, C.B.ESCUTCHEON
1/2" SUPPLIES, ANGLE STOP, C.B.ESCUTCHEON
WHITE
WHITE
LUSTER
WHITE
STAINLESS STEEL
STAINLESS STEEL
DESCRIPTION MFGR MODEL NO. REMARKS
PLUMBING SPECIALTIES
OATEYROB-1 ICE MAKER OUTLET BOX
PLUMBING GENERAL NOTES LEGEND
PLUMBING NOTES AND SPECIFICATIONS
ACRYLIC
GENERAL SPECIFICATIONS
1. DRAWINGS AND SPECIFICATIONS FORM COMPLIMENTARY REQUIREMENTS; PROVIDE WORK SPECIFIEDAND NOT SHOWN, AND WORK SHOWN BUT NOT SPECIFIED AS THOUGH EXPLICITLY REQUIRED BY BOTH.ALTHOUGH WORK IS NOT SPECIFICALLY SHOWN OR SPECIFIED, PROVIDE SUPPLEMENTARY ORMISCELLANEOUS ITEMS, APPURTENANCES, DEVICES AND MATERIALS OBVIOUSLY NECESSARY FOR ASOUND, SECURE AND COMPLETE INSTALLATION.
2. THE DRAWINGS AND SPECIFICATIONS INDICATE A PERFORMANCE SPECIFICATION FOR THE FIREPROTECTION AND FIRE ALARM SYSTEMS. AWARDED CONTRACTORS ARE RESPONSIBLE FOR DETAILEDDESIGN AND PREPARATION OF SIGNED AND SEALED ENGINEERING DOCUMENTS FOR REVIEW/APPROVALFROM OWNERS INSURANCE CARRIER AND LOCAL AUTHORITY HAVING JURISDICTION.
3. DRAWINGS ARE DIAGRAMMATIC: THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL COMPONENTSNECESSARY FOR A COMPLETE INSTALLATION. DETERMINE LOCATIONS OF SYSTEMS AND COMPONENTSIN FIELD. COORDINATE WITH ARCHITECTURAL DRAWINGS AND OTHER TRADES.
4. ADDRESS QUESTIONS REGARDING DRAWINGS TO ARCHITECT IN WRITING BEFORE AWARD OF CONTRACT.OTHERWISE, ARCHITECT'S INTERPRETATION OF MEANING AND INTENT OF DRAWINGS SHALL BE FINAL.
5. THE INTENTION IS FOR INSTALLATION OF COMPLETE AND OPERATING SYSTEMS INSTALLED INACCORDANCE WITH THE ASSOCIATED MANUFACTURER'S INSTRUCTIONS. NOT EVERY COMPONENTREQUIRED IS SHOWN. THE CONTRACTOR SHALL INCLUDE ALL COMPONENTS NORMALLY ASSOCIATEDWITH THE PARTICULAR SYSTEM AND/OR REQUIRED BY THE MANUFACTURER'S INSTALLATIONINSTRUCTIONS. THE SYSTEM SHALL BE FULLY COMMISSIONED AND SIGNED OFF BY AN OFFICER OF THERESPECTIVE CONTRACTOR. PRIOR TO FINAL OWNER ACCEPTANCE TESTING, PROVIDE PERSONNEL TOASSIST IN 24 HOURS OF ACCEPTANCE TESTING.
6. PRIOR TO COMMENCING WORK, COORDINATION DRAWINGS MUST BE PREPARED AND SUBMITTED FORREVIEW AND APPROVAL TO THE ARCHITECT/ENGINEER. EACH TRADE (HVAC, PLUMBING, ELECTRIC, ANDFIRE PROTECTION) IS RESPONSIBLE FOR DOCUMENTING THEIR WORK ON THE PLAN ORIGINALLYSUBMITTED AS THE SPRINKLER PIPE FABRICATION DRAWING. LOCATION AND ELEVATION OF THERESPECTIVE DISCIPLINE'S WORK MUST BE SHOWN ON THE COORDINATION DRAWINGS. SHEETMETALSHOP DRAWINGS SHALL INCLUDE ALL ELEMENTS OF THE EQUIPMENT, DUCTWORK, AIR DEVICES, ANDREFLECTED CEILING PLAN FOR COORDINATION OF CRITICAL DIMENSIONS OF ARCHITECTURAL/STRUCTURAL COMPONENTS.
7. GIVE NOTICES, FILE PLANS, OBTAIN PERMITS AND LICENSES, PAY FEES AND BACK CHARGES, ANDOBTAIN NECESSARY APPROVALS FROM AUTHORITIES THAT HAVE JURISDICTION AS REQUIRED TOPERFORM WORK IN ACCORDANCE WITH ALL LEGAL REQUIREMENTS AND WITH THE DESIGN DOCUMENTS
8. PRIOR TO COMMENCING WORK, CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND EQUIPMENT DATAFOR MATERIALS AND EQUIPMENT TO THE ARCHITECT FOR REVIEW AND APPROVAL. MATERIALS ANDEQUIPMENT SHALL NOT BE INSTALLED BEFORE SHOP DRAWINGS ARE REVIEWED AND APPROVED.SCHEDULE AT LEAST TEN WORKING DAYS, EXCLUSIVE OF TRANSMITTAL TIME, FOR SUBMITTAL REVIEWSHALL BE ALLOWED.
9. MATERIALS AND EQUIPMENT SHALL BE LISTED BY UNDERWRITERS LABORATORIES (UL) AND APPROVEDBY ASME AND AGA FOR INTENDED SERVICE.
10. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS,TECHNIQUES, SEQUENCES AND PROCEDURES REQUIRED FOR SAFE EXECUTION AND COMPLETION OFWORK, AND FOR INITIATING, MAINTAINING AND SUPERVISING ALL SAFETY PRECAUTIONS ANDPROGRAMS IN CONNECTION WITH THE WORK.
11. COORDINATE WORK OF THIS SECTION WITH THAT OF OTHER SECTIONS.12. ALL MATERIALS, EQUIPMENT AND METHOD OF INSTALLATION SHALL BE ACCORDANCE WITH THE
STANDARDS, REGULATIONS, CODES, ORDINANCES, AND LAW OF LOCAL, STATE, AND FEDERALGOVERNMENTS, AND OTHER AUTHORITIES THAT HAVE LAWFUL JURISDICTION.
13. IT SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO COORDINATE HIS WORK WITH THAT OF ALLOTHER TRADES, INCLUDING (BUT NOT LIMITED TO), ELECTRICAL, HVAC, SPRINKLER, PLUMBING,STRUCTURAL AND GENERAL ARCHITECTURE. OFFSETS IN PIPING AND OFFSETS AROUND OBSTRUCTIONSSHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
14. DEVIATION FROM CONTRACT DOCUMENTS, OR PROPOSED SUBSTITUTION OF MATERIALS OR EQUIPMENT FOR THOSE SPECIFIED, SHALL BE REQUESTED IN SEPARATE LETTER, WHETHER DEVIATIONS ARE DUE TO FIELD CONDITIONS, STANDARD SHOP PRACTICE OR OTHER CAUSE. THE CONTRACTOR IS RESPONSIBLE FOR ANY COSTS INCURRED AS A RESULT OF THE CHANGES NEEDED TOACCOMMODATE THE SUBSTITUTED EQUIPMENT INCLUDING THE WORK OF OTHER TRADES.
15. EACH CONTRACTOR IS RESPONSIBLE FOR ITS CUTTING AND PATCHING REQUIRED FOR THEINSTALLATION OF ITS NEW WORK. CUTTING AND PATCHING SHALL BE COMPLETED IN A NEAT ANDWORKMANLIKE MANNER. PATCHING MATERIALS SHALL MATCH EXISTING MATERIALS TO THEGREATEST EXTENT POSSIBLE. PROVIDE TOUCH-UP TO MATCH EXISTING SURROUNDING AREAS OFCUTTING AND PATCHING WORK
16. INTERRUPTIONS TO EXISTING SERVICES AND SYSTEMS SHALL BE AS SHORT AS POSSIBLE AND AT ATIME AND DURATION APPROVED BY THE OWNER. INCLUDE ALL PREMIUM TIME ASSOCIATED WITHINTERRUPTIONS. INTERRUPTIONS SHALL BE SCHEDULED WITH OWNER 48 HOURS IN ADVANCE.
17. PROVIDE CHASE COORDINATION DRAWINGS PRIOR TO CONSTRUCTION DOCUMENTING ALL UTILITIESTHROUGH CHASES FOR ALL TRADES. PROVIDE SUBMITTAL FOR ENGINEER'S REVIEW PRIOR TOCONSTRUCTION.
18. CONTRACTOR SHALL COORDINATE ITS RESPECTIVE CEILING MOUNTED EQUIPMENT WITH OTHER TRADECONTRACTORS PRIOR TO INSTALLATION TO AVOID CONFLICTS.
19. ANY DEMOLITION SHALL BE COORDINATED WITH OWNER, ARCHITECT, G.C. AND ENGINEER. ALL DEBRISSHALL BE CLEANED UP AND REMOVED FROM THE SITE BY THE END OF THE DAY. PRIOR TO DISPOSAL OFEQUIPMENT AND MATERIALS, TURN OVER TO THE OWNER ANY REMOVED EQUIPMENT AND MATERIALSPER OWNERS REQUEST.
20. WORK SHALL BE EXECUTED IN A WORKMANLIKE MANNER AND SHALL PRESENT NEAT, RECTILINEARAPPEARANCE WHEN COMPLETED. MAINTAIN MAXIMUM HEAD ROOM AT ALL TIMES. DO NOT RUN PIPES,DUCTS, AND CONDUIT EXPOSED UNLESS SHOWN AND NOTED TO BE EXPOSED ON DRAWINGS.MATERIALS AND EQUIPMENT SHALL BE NEW AND INSTALLED ACCORDING TO MANUFACTURER'SINSTRUCTIONS AND RECOMMENDATIONS, SO THAT COMPLETED INSTALLATION SHALL OPERATE SAFELYAND EFFICIENTLY.
21. EACH RESPECTIVE CONTRACTOR SHALL FIRE STOP ALL NEW AND EXISTING SLEEVES THROUGHCONCRETE FLOORS AND FIRE RATED WALLS OR PARTITIONS WITH UL RATED ASSEMBLIES WITH EQUALFIRE RATING. FIELD VERIFY EXISTING CONDITIONS BEFORE SUBMITTING PRICE.
22. COORDINATE ROOF PENETRATIONS WITH WORK OF OTHER SECTIONS AND WITH FLASHINGREQUIREMENTS.
23. ANY INTERFERENCE SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER'S REPRESENTATIVE, ANDSHALL BE RESOLVED PRIOR TO THE INSTALLATION OF THE WORK INVOLVED.
24. ALL MATERIALS AND EQUIPMENT SHALL BE NEW UNLESS NOTED OTHERWISE.25. MANUFACTURERS' MODEL NUMBERS ARE SPECIFIED SOLELY TO ESTABLISH STANDARDS OF QUALITY
FOR PERFORMANCE AND MATERIALS.25. SUBSTITUTED PRODUCTS SUBMITTED AND APPROVED FOR USE THAT NECESSITATE CHANGES TO THE
WORK OF THAT OR ANY OTHER TRADES OF CONTRACT SHALL BE COORDINATED AND ARRANGED BY THECONTRACTOR WHO SUBMITTED THE SUBSTITUTION WITHOUT ADDITIONAL COST TO THE OWNER.
26. PRODUCT INSTALLATION SHALL ADHERE TO MANUFACTURERS RECOMMENDATIONS.27. EACH RESPECTIVE CONTRACTOR SHALL PROVIDE PROPER ACCESS TO EQUIPMENT THAT REQUIRES
INSPECTION, REPLACEMENT OR REPAIR. ACCESS PANELS SHALL BE A MINIMUM OF 12" X 12" OR ASNEEDED FOR APPROPRIATE ACCESS. TO BE SUPPLIED TO GENERAL CONTRACTOR FOR INSTALLATION.ACCESS PANELS IN RATED ASSEMBLIES SHALL BE ACUDOR FW-5050. ACCESS PANELS IN NON-RATEDDRYWALL CEILINGS SHALL BE WIND-LOCK "STEALTH". ACCESS PANELS IN NON-RATED WALLS SHALL BEADUDOR UF-5000.
28. CONTRACTOR SHALL COORDINATE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS OF ALLAPPLICABLE EQUIPMENT WITH THE ELECTRICAL CONTRACTOR.
29. ALL EQUIPMENT, PIPING, INSULATION, ETC., INSTALLED IN HVAC PLENUM SPACES SHALL MEET CODEREQUIREMENTS FOR SMOKE AND COMBUSTIBILITY.
30. AS WORK PROGRESSES AND FOR DURATION OF CONTRACT, MAINTAIN COMPLETE SET OF PRINTS OFCONTRACT DRAWINGS AT JOB SITE AT ALL TIMES. RECORD WORK COMPLETED AND ALL CHANGESFROM ORIGINAL CONTRACT DRAWINGS CLEARLY AND ACCURATELY INCLUDING WORK INSTALLED AS AMODIFICATION OR ADDITION TO THE ORIGINAL DESIGN TURN OVER ALL OPERATING MANUALS,MAINTENANCE MANUALS, AND "AS BUILT" DRAWINGS TO OWNER AT CONCLUSION OF CONSTRUCTION.
31. DO NOT SUPPORT EQUIPMENT FROM SUSPENDED CEILINGS. SUPPORT ALL EQUIPMENT AND PIPINGFROM BUILDING. STRUCTURE TO PROVIDE A VIBRATION FREE INSTALLATION. NOTIFY ARCHITECT ANDSTRUCTURAL ENGINEER OF ALL WEIGHTS AND METHODS OF SUPPORT.
32. RUN PIPING/WIRING CONCEALED, UNLESS SPECIFIED OTHERWISE, AND CLEAR OF CEILING INSERTS.33. PROVIDE CLAMPS, OFFSETS, EXPANSION JOINTS, ANCHORS AND GUIDES AS NECESSARY TO PREVENT
STRESS ON PIPING/WIRING. .34. ANY REFERENCE TO ELECTRICAL, PLUMBING AND HVAC CONTRACTORS, NOTED ON THESE DRAWINGS
OR STATED IN THE SPECIFICATIONS SHALL NOT BE MISCONSTRUED AS AN INTENTION TO DEFINESEPARATE CONTRACTORS FOR THE RESPECTIVE WORK. THE GENERAL CONTRACTOR SHALL COORDINATEAND PROVIDE A COMPLETE BUILDING WITH COMPLETE MECHANICAL AND ELECTRICAL SYSTEMS,REGARDLESS OF ANY SPECIFICATION REFERENCES TO OTHER CONTRACTORS.
35. GUARANTEE WORK OF THIS CONTRACTOR IN WRITING FOR ONE YEAR FROM THE DATE OF OWNER'SACCEPTANCE OF CERTIFICATE OF SUBSTANTIAL COMPLETION. PROMPTLY, REPAIR OR REPLACEDEFECTIVE MATERIALS, EQUIPMENT, WORKMANSHIP AND INSTALLATIONS THAT DEVELOP DEFECTSWITHIN THIS PERIOD. PROMPTLY AND TO OWNERS SATISFACTION, CORRECT DAMAGE CAUSED INMAKING NECESSARY REPAIRS AND REPLACEMENTS UNDER GUARANTEED AT NO ADDITIONAL COST TOOWNER. SUBMIT GUARANTEE TO ARCHITECT BEFORE FINAL PAYMENT. STATEMENT OF GUARANTEEREQUIREMENTS SHALL NOT BE INTERRUPTED TO LIMIT OWNER'S RIGHTS UNDER LAW AND THISCONTRACT.
LAVATORY / SINK PIPING DETAILNO SCALE
CAST SETSCREWESCUTCHEON
FLOOR
McGUIRE NO. 8089P-TRAP
COUNTERTOP
ANGLE STOPS
McGUIRE NO 151DRAIN ASSEMBLY
COUNTERTOP
1/2"1/2"
PROVIDE TRUEBROPIPING INSTALLATION
REFRIGERATOR WATER FEED DETAILNO SCALE
CEILING
FLOOR
COORDINATE MOUNTING HEIGHTW/SPECIFIED REFRIGERATOR
CWREFRIGERATOR OUTLET BOX
1/2" CW DNIN WALL
ELECTRIC WATER COOLER W/BOTTLER FILLER
HALSEY TAYLOR STAINLESS STEELHTHB-
HACG8BLSS-WF--- --- PRESS BAR ------
1 1/2" C.B. CAST BRASS W/CLEANOUT PLUG
EWC-1 1/2" SUPPLIES, C.B. ESCUTCHEON STAINLESS STEEL
AS
N
OT
ED
JM
F
DF
(R) LAV
(R) SK (R) SHO
(R) SK
REMOVE EXISTING PLUMBING FIXTURES.EXISTING PIPING TO REMAIN FORINSTALLATION OF NEW FIXTURES.
REMOVE EXISTING PLUMBING FIXTURE.EXISTING PIPING TO REMAIN FORINSTALLATION OF NEW FIXTURE.
REMOVE EXISTING PLUMBING FIXTURES.EXISTING PIPING TO REMAIN FOR
INSTALLATION OF NEW FIXTURES.
REMOVE EXISTING PLUMBING FIXTURES.EXISTING PIPING TO REMAIN FOR
INSTALLATION OF NEW FIXTURES.
REMOVE EXISTING PLUMBING FIXTURE.EXISTING PIPING TO REMAIN FORINSTALLATION OF NEW FIXTURE.
REMOVE EXISTING PLUMBING FIXTURES.EXISTING PIPING TO REMAIN FORINSTALLATION OF NEW FIXTURES.
REMOVE EXISTING PLUMBING FIXTURE.EXISTING PIPING TO REMAIN FORINSTALLATION OF NEW FIXTURE.
(R) WC
(R) UR
(R) LAV (R) LAV(R) UR
(R) UR
(R) WC (R) WC (R) SHO (R) SHO
(R) WC(R) WC
(R) LAV (R) LAV (R) LAV
(R) WC
(R) WC (R) WC
(R) WC
(R) LAV
(R) LAV
(R) LAV
(R) LAV
(R) SK
(R) WC
(R) SK
(R) SK
(R) WC
(R) WC (R) WC (R) WC
(R) UR(R) LAV
(R) LAV
(R) LAV(R) LAV
TOILET ROOM FIXTURESEXISTING TO REMAIN
JANITOR CLOSET FIXTUREEXISTING TO REMAIN
(E) WC (E) LAV
(E) MSB
(R) EWC
KEY PLAN
PHASE 1 PHASE 2
PHASE 3PD-1
1
SCALE - 1/8" = 1'-0"
PLUMBING DEMOLITION FLOOR PLAN
AS
N
OT
ED
JM
F
DF
N
0' 4' 16'8'
LAV-1LAV-1LAV-1UR-1
UR-1
WC-1 WC-1 SHO-1SHO-1
WC-1 WC-1
LAV-1LAV-1LAV-1SK-1
SHO-1
SK-2 WC-1
WC-1
WC-1
LAV-1
LAV-1LAV-1
LAV-1
SK-1
INSTALL NEW FIXTURES.CONNECT TO EXISTING PIPING.MODIFY EXISTING PIPING ASREQUIRED FOR INSTALLATIONOF NEW FIXTURES.
INSTALL NEW FIXTURES.CONNECT TO EXISTING PIPING. MODIFY EXISTING PIPING AS
REQUIRED FOR INSTALLATION OF NEW FIXTURES.CONNECT TO EXISTING CW PIPING AND EXTEND 1/2" CW LINE
TO COFFEE MACHINE & ICE MAKER. TERMINATE CW FEEDSWITH ROB-1 (TYP. FOR 2). SEE ARCH PLANS FOR FINAL
EQUIPMENT LOCATION.
INSTALL NEW FIXTURES.CONNECT TO EXISTING PIPING.
MODIFY EXISTING PIPING ASREQUIRED FOR INSTALLATION
OF NEW FIXTURES.
WC-1
WC-1
UR-1
TOILET ROOM FIXTURESEXISTING TO REMAIN
JANITOR CLOSET FIXTUREEXISTING TO REMAIN
(E) WC (E) LAV
(E) MSB
INSTALL NEW FIXTURES.CONNECT TO EXISTING PIPING.
MODIFY EXISTING PIPING ASREQUIRED FOR INSTALLATION
OF NEW FIXTURES.
EWC
KEY PLAN
PHASE 1
P-1.1
1
SCALE - 1/8" = 1'-0"
PLUMBING FLOOR PLAN - PHASE 1
AS
N
OT
ED
JM
F
DF
0'4' 16'8'
LAV-1LAV-1
LAV-1LAV-1
SK-1
SK-1
WC-1 WC-1 WC-1
WC-1UR-1
WC-1
INSTALL NEW FIXTURES.CONNECT TO EXISTING PIPING.MODIFY EXISTING PIPING ASREQUIRED FOR INSTALLATIONOF NEW FIXTURES.
INSTALL NEW FIXTURE.CONNECT TO EXISTING PIPING. MODIFY EXISTING PIPING AS
REQUIRED FOR INSTALLATION OF NEW FIXTURE.CONNECT TO EXISTING CW PIPING AND EXTEND 1/2" CW LINE
TO COFFEE MACHINE & ICE MAKER. TERMINATE CW FEEDSWITH ROB-1 (TYP. FOR 2). SEE ARCH PLANS FOR FINAL
EQUIPMENT LOCATION.
JANITOR CLOSET FIXTUREEXISTING TO REMAIN
INSTALL NEW FIXTURE.CONNECT TO EXISTING PIPING. MODIFY EXISTING PIPING ASREQUIRED FOR INSTALLATION OF NEW FIXTURE.CONNECT TO EXISTING CW PIPING AND EXTEND 1/2" CW LINETO COFFEE MACHINE & ICE MAKER. TERMINATE CW FEEDSWITH ROB-1 (TYP. FOR 2). SEE ARCH PLANS FOR FINALEQUIPMENT LOCATION.
KEY PLAN
PHASE 2
P-1.2
1
SCALE - 1/8" = 1'-0"
PLUMBING FLOOR PLAN - PHASE 2
AS
N
OT
ED
JM
F
DF
0' 4' 16'8'
NOTE:NO PLUMBING SCOPE IN PHASE 3.
KEY PLAN
PHASE 3P-1.3
1
SCALE - 1/8" = 1'-0"
PLUMBING FLOOR PLAN - PHASE 3
AS
N
OT
ED
JM
F
DF
0' 4' 16'8'
SPRINKLER CRITERIA GPM /SQ.FT.
CONCEALED SPRINKLER2 1/4" MIN.2 3/4" MAX.
COVER PLATE
CEILING
1. THE DRAWINGS AND SPECIFICATIONS INDICATE A PERFORMANCE SPECIFICATION FOR THE FIRE PROTECTION SYSTEM.THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE AND OPERATING SYSTEM IN COMPLIANCE WITH THEAPPLICABLE NFPA CODES. AWARDED CONTRACTOR IS RESPONSIBLE FOR DETAILED DESIGN AND PREPARATION OFSIGNED AND SEALED ENGINEERING DOCUMENTS FOR REVIEW/APPROVAL FROM THE OWNER'S INSURANCE CARRIERAND LOCAL AUTHORITY HAVING JURISDICTION.
2. PRIOR TO COMMENCING WORK, CONTRACTOR SHALL SUBMIT SPRINKLER SHOP DRAWINGS, HYDRAULICCALCULATIONS AND EQUIPMENT DATA FOR MATERIALS AND EQUIPMENT TO THE ENGINEER FOR REVIEW ANDAPPROVAL. MATERIALS AND EQUIPMENT SHALL NOT BE INSTALLED BEFORE SHOP DRAWINGS ARE REVIEWED ANDAPPROVED. SCHEDULE AT LEAST TEN WORKING DAYS, EXCLUSIVE OF TRANSMITTAL TIME, FOR SUBMITTAL REVIEW.
3. GENERAL NOTES, SYMBOLS LIST AND DETAILS ARE APPLICABLE TO ALL DRAWINGS OF THIS SECTION.4. SPRINKLER PIPE SIZES ARE TO BE CALCULATED HYDRAULICALLY BY THE FIRE PROTECTION CONTRACTOR.5. THE CONTRACTOR SHALL COORDINATE SPRINKLER HEADS AND ASSOCIATED PIPING LOCATIONS WITH THE ARCHITECT
PRIOR TO COMMENCING WORK IN FINISHED AREAS.6. THE CONTRACTOR SHALL COORDINATE SPRINKLER HEAD LOCATIONS WITH LIGHTING LAYOUT, DUCTWORK AND PIPING
AND OTHER TRADES PRIOR TO ROUGH-IN.7. SEISMIC: WHERE REQUIRED SUBMIT WORKING PLANS, REVIEWED, SIGNED AND STAMPED BY A PROFESSIONAL
STRUCTURAL ENGINEER REGISTERED IN THE STATE IN WHICH THE PROJECT IS LOCATED, CERTIFYING THAT THE PLANSMEETS ALL SEISMIC REQUIREMENTS ESTABLISHED BY AUTHORITIES.
8. BEFORE STARTING WORK IN A PARTICULAR AREA OF THE PROJECT, VISIT SITE AND EXAMINE CONDITIONS UNDERWHICH WORK MUST BE PERFORMED INCLUDING PREPARATORY WORK DONE UNDER OTHER SECTIONS OR CONTRACTSBY OWNER. REPORT CONDITIONS THAT MIGHT AFFECT WORK ADVERSELY IN WRITING THROUGH THE CONTRACTOR TOTHE ARCHITECT/ENGINEER. DO NOT PROCEED WITH WORK UNTIL DEFECTS HAVE BEEN CORRECTED AND THECONDITIONS ARE SATISFACTORY. COMMENCEMENT OF WORK SHALL INDICATE ACCEPTANCE OF EXISTING CONDITIONS.
9. ALL SPRINKLER HEADS IN ACOUSTICAL DROP CEILINGS SHALL BE CENTERED IN TILE.
EXISTING(E)
90° ELBOW
SP WET PIPE SPRINKLER SYSTEM
SQ.FT.
SPKR
O/G-1
PSI
WF
TS
FS
GPM
GV
MIN
(N)
FD
NTS
ORDINARY HAZARD - GROUP 1
POUNDS PER SQUARE INCH
SQUARE FOOT
SPRINKLER
WATER FLOW DETECTOR
TAMPER SWITCH
NOT TO SCALE
FLOOR DRAIN
GATE VALVE
MINIMUM
NEW
FLOW SWITCH
GALLONS PER MINUTE
DR
DN
DSS
DWG
COMP
CV
DIPS DOUBLE INTERLOCKED PREACTION SPRINKLER SYSTEM
DRY PIPE SPRINKLER SYSTEM
DRAIN RISER
DOWN
DRAWING
COMPRESSOR
CHECK VALVE
OFFICES
NFPA HAZARDCLASSIFICATION
LIGHT
CEILING3" - 5" BELOW
UPRIGHT SPRINKLER
UPRIGHT DEFLECTOR
SPRINKLERTEMPERATURE
SP
DIRECTION OF FLOW
WET SPRINKLER SYSTEM
POINT OF CONNECTION BETWEEN EXISTING
3-WAY ALARM TEST
DE
DSP
SHUT OFF VALVE
POINT OF CONNECTION BETWEEN
DELUGE SPRINKLER SYSTEM
AND TO BE REMOVED WORK
DRYPIPE SPRINKLER SYSTEM
NEW AND EXISTING WORK
CHECK VALVE
PRESSURE GUAGE
SOLENOID RELEASE VALVE
SYSTEM CONTROL VALVE
PREACTION ALARM HORN WITH FLASHING
DRY PIPE VALVE
PREACTION CONTROL PANEL
BACKFLOW PREVENTER
PREACTION DELUGE VALVE
WATERFLOW DETECTOR
SYMBOL DESCRIPTION
TYCO SERIES TY-B
BASIS OF DESIGN MANUFACTURER& MODEL #
VICTAULIC, VIKING, RELIABLE
ACCEPTABLEMFGR.
PSIG POUNDS PER SQUARE INCH (GAUGE)
QUICK RESPONSE, THERMO-SENSITIVE GLASS BULB SPRAY SPRINKLER, WHITEFINISH. TO BE USED IN ALL AREAS WITH FINISHED CEILINGS
QUICK RESPONSE, THERMO-SENSITIVE GLASS BULB SPRAY SPRINKLER. TO BE USEDIN ALL AREAS WITHOUT FINISHED CEILINGS
TYCO TY-FRBUPRIGHT VICTAULIC, VIKING, RELIABLE
PENDANT
1. PIPE AND FITTINGSA. PIPE SHALL MEET APPLICABLE ANSI OR ASTM STANDARDS AND SHALL HAVE MANUFACTURER'S NAME AND STANDARD
MARKED ON EACH LENGTH. JOINTS SHALL MEET APPLICABLE ANSI OR ASTM STANDARDS. WHERE ANSI OR ASTMSTANDARD DOES NOT EXIST, JOINTS AND FITTINGS SHALL BEAR UL LISTED SYMBOL.
B. SERVICE: LIGHT HAZARD ABOVE GROUND WET-PIPE SPRINKLER (2 1/2" AND BELOW).PIPE MATERIAL: CPVC (CHLORINATED POLYVINYL CHLORIDE), ASTM D1784FITTING MATERIAL: CPVC, ASTM F437 & ASTM F438.PIPE JOINT: SOLVENT CEMENT, ASTM F656 & ASTM F493
C. SERVICE: ORDINARY HAZARD ABOVE GROUND WET-PIPE SPRINKLER (2 1/2" AND BELOW).PIPE MATERIAL: WELDED AND SEAMLESS STEEL PIPE, SCHEDULE 40, ASTM A53.FITTING MATERIAL: MALLEABLE IRON, CLASS 150, ANSI B 16.3PIPE JOINT: THREADED OR VICTAULIC
D. SERVICE: ABOVE GROUND WET-PIPE SPRINKLER (3" AND LARGER".PIPE MATERIAL: WELDED AND SEAMLESS STEEL PIPE, SCHEDULE 40, ASTM A53FITTING MATERIAL: MALLEABLE IRON, CLASS 150, ANSI B16.3.PIPE JOINT: THREADED OR VICTAULIC
2. HANGERS, ANCHORS, CLAMPS, AND INSERTSA. HANGERS SHALL MEET NFPA STANDARDS. PROVIDE ADJUSTABLE SWIVEL RIGHTS FOR PIPING 3" AND SMALLER.
SUPPORT PIPING FROM BUILDING STRUCTURE TO MAINTAIN REQUIRED GRADE AND PITCH OF PIPE LINES, PREVENTVIBRATIONS, SECURE PIPING IN PLACE. SECURE HANGERS TO INSERTS WHERE PRACTICAL. HANGER TODS SHALL HAVEMACHINE THREADS.
B. HANGER RODS SHALL BE CONNECTED TO BEAM CLAMP, UL-APPROVED CONCRETE INSERTS OR PHILIPS OR APPROVEDEQUAL EXPANSION SHIELDS. RAMSET OR POWER DRIVEN INSETS WILL NOT BE ALLOWED.
C. HANGER SPACING SHALL MEET REQUIREMENT OF STATE AND LOCAL CODES. PIPE SUPPORTS, VERTICAL ANDHORIZONTAL, SHALL NOT BEAR ON SLEEVES.
3. SPRINKLER HEADSA. PROVIDE UL-LISTED AND FM APPROVED FUSIBLE LINK SPRAY SPRINKLER HEADSB. HEADS SHALL HAVE ORDINARY DEGREE TEMPERATURE RATINGS.C. SPRINKLER HEADS SHALL BE RELOCATED OR ADDED TO PROVIDE ADEQUATE COVERAGE THROUGHOUT ALL AREAS IN
ACCORDANCE WITH THE REQUIREMENTS OF NFPA 13.D. WHERE SPRINKLER HEADS ARE SUBJECT TO PHYSICAL DAMAGE PROVIDE PROTECTIVE WIRE GUARD.
4. SPRINKLER SYSTEM INSTALLATIONA. WORK SHALL BE NEAT AND RECTILINEAR. PIPING SHALL RUN CONCEALED. WORK SHALL BE PROPERLY AND
EFFECTIVELY PROTECTED AND PIPE OPENING SHALL BE TEMPORARILY CLOSED TO PREVENT CONSTRUCTION ANDDAMAGE BEFORE COMPLETION.
5. CONTINUITY OF SERVICESA. NOTIFY THE "AUTHORITY HAVING JURISDICTION" WHEN SHUTDOWNS OF EXISTING SYSTEMS ARE NECESSARY.
6. TESTSA. TEST SPRINKLER SYSTEM AS REQUIRED IN NFPA CODE, OWNERS INSURANCE CARRIER, AND AGENCIES THAT HAVE
JURISDICTION.B. NOTIFY ARCHITECT AND AGENCIES THAT HAVE JURISDICTION TESTS ARE TO BE MADE. TEST SPRINKLER PIPING AND
MAKE WATERTIGHT BEFORE CONCEALMENT. TEST SHALL BE WITNESSED BY THE INSURANCE UNDERWATERSREPRESENTATIVE, THE MUNICIPAL INSPECTOR AND A REPRESENTATIVE OF THE ARCHITECT.
C. SPRINKLER SYSTEM SHALL BE TESTED TO HYDROSTATIC TEST OF 200 PSI IN ACCORDANCE WITH NFPA REQUIREMENTSD. IF INSPECTION OR TEST SHOWS DEFECTS, SUCH DEFECTIVE WORK OR MATERIAL, SHALL BE REPLACED AND
INSPECTED AND TESTS SHALL BE REPEATED UNTIL WORK IS ACCEPTED. REPAIRS TO PIPING SHALL BE MADE WITHNEW MATERIAL
7. CLEANINGA. CLEAN INSTALLATION THOROUGHLY UPON COMPLETION TO REMOVE GREASE, CUTTINGS, DIRT AND OTHER FOREIGN
MATERIALS. REPAIR STOPPAGES, DISCOLORATION AND DAMAGE THAT RESULT FROM FAILURE TO CLEAN PIPINGPROPERLY WITHIN CONTRACT PRICE.
GENERAL NOTES - FIRE PROTECTION
FIRE PROTECTION NOTES
FIRE PROTECTION ABBREVIATIONS(NOT ALL ABBREVIATIONS ARE NECESSARILY USED ON THIS PROJECT)
FIRE PROTECTION SYMBOLS(NOT ALL SYMBOLS ARE NECESSARILY USED ON THIS PROJECT)
SPRINKLER SYSTEM DESIGN DATA
SPRINKLER SCHEDULE
REMARKSFINISHORIFICEDIAMETER
TEMPERATURERATING
TYPESYMBOL
WHITE
WHITE
1/2"
1/2"
155° F
155° F
155° F0.10 GPM/ 1500 SQ. FT.NFPA 13 LIGHT HAZARD
OCCUPANCY
NO SCALE
CONCEALED SPRINKLER HEADINSTALLATION DETAIL
NO SCALE
UPRIGHT SPRINKLER HEADINSTALLATION DETAIL
1. THE DRAWINGS AND SPECIFICATIONS INDICATE A PERFORMANCE SPECIFICATION FOR THE FIRE PROTECTION AND FIRE ALARM SYSTEMS. AWARDEDCONTRACTORS ARE RESPONSIBLE FOR DETAILED DESIGN AND PREPARATION OF SIGNED AND SEALED ENGINEERING DOCUMENTS FORREVIEW/APPROVAL FROM OWNERS INSURANCE CARRIER AND LOCAL AUTHORITY HAVING JURISDICTION.
2. DRAWINGS ARE DIAGRAMMATIC: THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL COMPONENTS NECESSARY FOR A COMPLETEINSTALLATION. DETERMINE LOCATIONS OF SYSTEMS AND COMPONENTS IN FIELD. COORDINATE WITH ARCHITECTURAL DRAWINGS AND OTHERTRADES.
3. ADDRESS QUESTIONS REGARDING DRAWINGS TO ARCHITECT IN WRITING BEFORE AWARD OF CONTRACT. OTHERWISE, ARCHITECT'SINTERPRETATION OF MEANING AND INTENT OF DRAWINGS SHALL BE FINAL.
4. THE INTENTION IS FOR INSTALLATION OF COMPLETE AND OPERATING SYSTEMS INSTALLED IN ACCORDANCE WITH THE ASSOCIATEDMANUFACTURER'S INSTRUCTIONS. NOT EVERY COMPONENT REQUIRED IS SHOWN. THE CONTRACTOR SHALL INCLUDE ALL COMPONENTS NORMALLYASSOCIATED WITH THE PARTICULAR SYSTEM AND/OR REQUIRED BY THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE SYSTEM SHALL BEFULLY COMMISSIONED AND SIGNED OFF BY AN OFFICER OF THE RESPECTIVE CONTRACTOR. PRIOR TO FINAL OWNER ACCEPTANCE TESTING, PROVIDEPERSONNEL TO ASSIST IN 24 HOURS OF ACCEPTANCE TESTING.
5. GIVE NOTICES, FILE PLANS, OBTAIN PERMITS AND LICENSES, PAY FEES AND BACK CHARGES, AND OBTAIN NECESSARY APPROVALS FROMAUTHORITIES THAT HAVE JURISDICTION AS REQUIRED TO PERFORM WORK IN ACCORDANCE WITH ALL LEGAL REQUIREMENTS AND WITH THE DESIGNDOCUMENTS
6. PRIOR TO COMMENCING WORK, CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND EQUIPMENT DATA FOR MATERIALS AND EQUIPMENT TO THEARCHITECT FOR REVIEW AND APPROVAL. MATERIALS AND EQUIPMENT SHALL NOT BE INSTALLED BEFORE SHOP DRAWINGS ARE REVIEWED ANDAPPROVED. SCHEDULE AT LEAST TEN WORKING DAYS, EXCLUSIVE OF TRANSMITTAL TIME, FOR SUBMITTAL REVIEW SHALL BE ALLOWED.
7. MATERIALS AND EQUIPMENT SHALL BE LISTED BY UNDERWRITERS LABORATORIES (UL) AND APPROVED BY ASME AND AGA FOR INTENDED SERVICE.8. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES
REQUIRED FOR SAFE EXECUTION AND COMPLETION OF WORK, AND FOR INITIATING, MAINTAINING AND SUPERVISING ALL SAFETY PRECAUTIONS ANDPROGRAMS IN CONNECTION WITH THE WORK.
9. COORDINATE WORK OF THIS SECTION WITH THAT OF OTHER SECTIONS.10. ALL MATERIALS, EQUIPMENT AND METHOD OF INSTALLATION SHALL BE ACCORDANCE WITH THE STANDARDS, REGULATIONS, CODES, ORDINANCES,
AND LAW OF LOCAL, STATE, AND FEDERAL GOVERNMENTS, AND OTHER AUTHORITIES THAT HAVE LAWFUL JURISDICTION.11. IT SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO COORDINATE HIS WORK WITH THAT OF ALL OTHER TRADES, INCLUDING (BUT NOT
LIMITED TO), ELECTRICAL, HVAC, SPRINKLER, PLUMBING, STRUCTURAL AND GENERAL ARCHITECTURE. OFFSETS IN PIPING AND OFFSETS AROUNDOBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
12. DEVIATION FROM CONTRACT DOCUMENTS, OR PROPOSED SUBSTITUTION OF MATERIALS OR EQUIPMENT FOR THOSE SPECIFIED, SHALL BEREQUESTED IN SEPARATE LETTER, WHETHER DEVIATIONS ARE DUE TO FIELD CONDITIONS, STANDARD SHOP PRACTICE OR OTHER CAUSE.
13. EACH CONTRACTOR IS RESPONSIBLE FOR ITS CUTTING AND PATCHING REQUIRED FOR THE INSTALLATION OF ITS NEW WORK. CUTTING ANDPATCHING SHALL BE COMPLETED IN A NEAT AND WORKMANLIKE MANNER. PATCHING MATERIALS SHALL MATCH EXISTING MATERIALS TO THEGREATEST EXTENT POSSIBLE. PROVIDE TOUCH-UP TO MATCH EXISTING SURROUNDING AREAS OF CUTTING AND PATCHING WORK
14. INTERRUPTIONS TO EXISTING SERVICES AND SYSTEMS SHALL BE AS SHORT AS POSSIBLE AND AT A TIME AND DURATION APPROVED BY THE OWNER.INCLUDE ALL PREMIUM TIME ASSOCIATED WITH INTERRUPTIONS. INTERRUPTIONS SHALL BE SCHEDULED WITH OWNER 48 HOURS IN ADVANCE.
15. CONTRACTOR SHALL COORDINATE ITS RESPECTIVE CEILING MOUNTED EQUIPMENT WITH OTHER TRADE CONTRACTORS PRIOR TO INSTALLATION TOAVOID CONFLICTS.
16. ANY DEMOLITION SHALL BE COORDINATED WITH OWNER, ARCHITECT, G.C. AND ENGINEER. ALL DEBRIS SHALL BE CLEANED UP AND REMOVED FROMTHE SITE BY THE END OF THE DAY. PRIOR TO DISPOSAL OF EQUIPMENT AND MATERIALS, TURN OVER TO THE OWNER ANY REMOVED EQUIPMENT ANDMATERIALS PER OWNERS REQUEST.
17. WORK SHALL BE EXECUTED IN A WORKMANLIKE MANNER AND SHALL PRESENT NEAT, RECTILINEAR APPEARANCE WHEN COMPLETED. MAINTAINMAXIMUM HEAD ROOM AT ALL TIMES. DO NOT RUN PIPES, DUCTS, AND CONDUIT EXPOSED UNLESS SHOWN AND NOTED TO BE EXPOSED ONDRAWINGS. MATERIALS AND EQUIPMENT SHALL BE NEW AND INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS ANDRECOMMENDATIONS, SO THAT COMPLETED INSTALLATION SHALL OPERATE SAFELY AND EFFICIENTLY.
18. EACH RESPECTIVE CONTRACTOR SHALL FIRE STOP ALL NEW AND EXISTING SLEEVES THROUGH CONCRETE FLOORS AND FIRE RATED WALLS ORPARTITIONS WITH UL RATED ASSEMBLIES WITH EQUAL FIRE RATING. FIELD VERIFY EXISTING CONDITIONS BEFORE SUBMITTING PRICE.
19. COORDINATE ROOF PENETRATIONS WITH WORK OF OTHER SECTIONS AND WITH FLASHING REQUIREMENTS.20. ANY INTERFERENCE SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER'S REPRESENTATIVE, AND SHALL BE RESOLVED PRIOR TO THE
INSTALLATION OF THE WORK INVOLVED.21. ALL MATERIALS AND EQUIPMENT SHALL BE NEW UNLESS NOTED OTHERWISE.22. MANUFACTURERS' MODEL NUMBERS ARE SPECIFIED SOLELY TO ESTABLISH STANDARDS OF QUALITY FOR PERFORMANCE AND MATERIALS.23. SUBSTITUTED PRODUCTS SUBMITTED AND APPROVED FOR USE THAT NECESSITATE CHANGES TO THE SAID CONTRACTOR'S WORK OR THE WORK OF
OTHER TRADES OF CONTRACT SHALL BE COORDINATED AND ARRANGED BY THE CONTRACTOR WHO SUBMITTED THE SUBSTITUTION WITHOUTADDITIONAL COST TO THE OWNER.
24. PRODUCT INSTALLATION SHALL ADHERE TO MANUFACTURERS RECOMMENDATIONS25. EACH RESPECTIVE CONTRACTOR SHALL PROVIDE PROPER ACCESS TO EQUIPMENT THAT REQUIRES INSPECTION, REPLACEMENT OR REPAIR. ACCESS
PANELS SHALL BE A MINIMUM OF 12" X 12" OR AS NEEDED FOR APPROPRIATE ACCESS. TO BE SUPPLIED TO GENERAL CONTRACTOR FORINSTALLATION. ACCESS PANELS IN RATED ASSEMBLIES SHALL BE ACUDOR FW-5050. ACCESS PANELS IN NON-RATED DRYWALL CEILINGS SHALL BEWIND-LOCK "STEALTH". ACCESS PANELS IN NON-RATED WALLS SHALL BE ADUDOR UF-5000.
26. CONTRACTOR SHALL COORDINATE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS OF ALL APPLICABLE EQUIPMENT WITH THE ELECTRICALCONTRACTOR.
27. ALL EQUIPMENT, PIPING, INSULATION, ETC., INSTALLED IN HVAC PLENUM SPACES SHALL MEET CODE REQUIREMENTS FOR SMOKE ANDCOMBUSTIBILITY.
28. AS WORK PROGRESSES AND FOR DURATION OF CONTRACT, MAINTAIN COMPLETE SET OF PRINTS OF CONTRACT DRAWINGS AT JOB SITE AT ALLTIMES. RECORD WORK COMPLETED AND ALL CHANGES FROM ORIGINAL CONTRACT DRAWINGS CLEARLY AND ACCURATELY INCLUDING WORKINSTALLED AS A MODIFICATION OR ADDITION TO THE ORIGINAL DESIGN TURN OVER ALL OPERATING MANUALS, MAINTENANCE MANUALS, AND "ASBUILT" DRAWINGS TO OWNER AT CONCLUSION OF CONSTRUCTION.
29. DO NOT SUPPORT EQUIPMENT FROM SUSPENDED CEILINGS. SUPPORT ALL EQUIPMENT AND PIPING FROM BUILDING. STRUCTURE TO PROVIDE AVIBRATION FREE INSTALLATION. NOTIFY ARCHITECT AND STRUCTURAL ENGINEER OF ALL WEIGHTS AND METHODS OF SUPPORT.
30. RUN PIPING/WIRING CONCEALED, UNLESS SPECIFIED OTHERWISE, AND CLEAR OF CEILING INSERTS.31. PROVIDE CLAMPS, OFFSETS, EXPANSION JOINTS, ANCHORS AND GUIDES AS NECESSARY TO PREVENT STRESS ON PIPING/WIRING. .32. ANY REFERENCE TO ELECTRICAL, PLUMBING AND HVAC CONTRACTORS, NOTED ON THESE DRAWINGS OR STATED IN THE SPECIFICATIONS SHALL NOT
BE MISCONSTRUED AS AN INTENTION TO DEFINE SEPARATE CONTRACTORS FOR THE RESPECTIVE WORK. THE GENERAL CONTRACTOR SHALLCOORDINATE AND PROVIDE A COMPLETE BUILDING WITH COMPLETE MECHANICAL AND ELECTRICAL SYSTEMS, REGARDLESS OF ANY SPECIFICATIONREFERENCES TO OTHER CONTRACTORS.
33. GUARANTEE WORK OF THIS CONTRACTOR IN WRITING FOR ONE YEAR FROM THE DATE OF OWNER'S ACCEPTANCE OF CERTIFICATE OF SUBSTANTIALCOMPLETION. PROMPTLY, REPAIR OR REPLACE DEFECTIVE MATERIALS, EQUIPMENT, WORKMANSHIP AND INSTALLATIONS THAT DEVELOP DEFECTSWITHIN THIS PERIOD. PROMPTLY AND TO OWNERS SATISFACTION, CORRECT DAMAGE CAUSED IN MAKING NECESSARY REPAIRS ANDREPLACEMENTS UNDER GUARANTEED AT NO ADDITIONAL COST TO OWNER. SUBMIT GUARANTEE TO ARCHITECT BEFORE FINAL PAYMENT.STATEMENT OF GUARANTEE REQUIREMENTS SHALL NOT BE INTERRUPTED TO LIMIT OWNER'S RIGHTS UNDER LAW AND THIS CONTRACT.
BUILDING CODE: 2015 INTERNATIONAL BUILDING CODEMECHANICAL CODE: 2015 INTERNATIONAL MECHANICAL CODEPLUMBING CODE: 2015 INTERNATIONAL PLUMBING CODEFUEL GAS CODE: 2015 INTERNATIONAL FUEL GAS CODEELECTRICAL CODE: 2014 NATIONAL ELECTRICAL CODEFIRE CODE: 2015 INTERNATIONAL FIRE CODEENERGY CODE: 2015 INTERNATIONAL ENERGY CONSERVATION CODE
MUNICIPALITY
USE AND OCC. CLASSIFICATION
APPLICABLE CODES
BUSINESS GROUP B
TREDYFFRIN TOWNSHIP, PA
CODE SUMMARY
GENERAL SPECIFICATIONS
EXISTING SPRINKLER SYSTEM.NFPA 13 LIGHT HAZARD CLASSIFICATION.
0.10 GPM/ 1500 SQ.FT.CONNECTED TO EXISTING SPRINKLER SERVICE.
INTERFACE WITH BUILDING FIRE ALARM SYSTEM.TURN DOWN/ REWORK SPRINKLER HEADS ASREQUIRED TO SATISFY SPACE CONDITIONS &
CEILING MODIFICATIONS.
KEY PLAN
PHASE 1
FP-1.1
1
SCALE - 1/8" = 1'-0"
FIRE PROTECTION FLOOR PLAN - PHASE 1
AS
N
OT
ED
JM
F
DF
0'4' 16'8'
EXISTING SPRINKLER SYSTEM.NFPA 13 LIGHT HAZARD CLASSIFICATION.
0.10 GPM/ 1500 SQ.FT.CONNECTED TO EXISTING SPRINKLER SERVICE.
INTERFACE WITH BUILDING FIRE ALARM SYSTEM.TURN DOWN/ REWORK SPRINKLER HEADS ASREQUIRED TO SATISFY SPACE CONDITIONS &
CEILING MODIFICATIONS.
KEY PLAN
PHASE 2
FP-1.2
1
SCALE - 1/8" = 1'-0"
FIRE PROTECTION FLOOR PLAN - PHASE 2
AS
N
OT
ED
JM
F
DF
0'4' 16'8'
NOTE:NO FIRE PROTECTION SCOPE INPHASE 3.EXISTING FIRE PROTECTIONSYSTEM TO REMAIN.
KEY PLAN
PHASE 3FP-1.3
1
SCALE - 1/8" = 1'-0"
FIRE PROTECTION FLOOR PLAN - PHASE 3
AS
N
OT
ED
JM
F
DF
0' 4' 16'8'
VOICE COMMUNICATION OUTLET
CEILING MOUNTED JUNCTION BOX
MOTOR OR MOTORIZED EQUIPMENT. NUMBER INDICATESHORSEPOWER (HP)
DISCONNECT SWITCH, SIZE AS INDICATED ON PLAN
JB
A
FUSED DISCONNECT SWITCH, SIZE AS INDICATED ON PLAN
LOCKING OR NONLOCKING NEMA RECEPTACLE ASNOTED
MS
TV CABLE TV OUTLET
RECESSED DOWNLIGHT, "A" INDICATES TYPE, "2"INDICATES CIRCUIT BREAKER POSITION, "a" INDICATESSWITCHING
2 a
WALL MOUNTED LIGHT FIXTURE, "A" INDICATES TYPE, "2"INDICATES CIRCUIT BREAKER POSITION, "a" INDICATESSWITCH CONTROL
A
2 a
A
2 aCEILING OR WALL MOUNTED LINEAR LED LIGHT FIXTURE,"A" INDICATES TYPE, "2" INDICATES CIRCUIT BREAKERPOSITION, "a" INDICATES SWITCH CONTROL
CEILING OR WALL MOUNTED INDUSTRIAL LED STRIPLIGHT FIXTURE, "A" INDICATES TYPE, "2" INDICATESCIRCUIT BREAKER POSITION, "a" INDICATES SWITCHCONTROL
A
2 a
CEILING OR WALL MOUNTED SINGLE FACE EXIT SIGN, "X"INDICATES TYPE, ARROWS AS INDICATED ON PLANS.CONNECT TO LOCAL LIGHTING BRANCH CIRCUIT AHEADOF ALL SWITCHING UNLESS OTHERWISE NOTED
X X
WALL MOUNTED EMERGENCY BATTERY PACK WITH(2)-LIGHT HEADS, "EM" INDICATES TYPE. CONNECT TOLOCAL LIGHTING BRANCH CIRCUIT AHEAD OF ALLSWITCHING UNLESS OTHERWISE NOTED
2#12 & 1#12GND. IN 3/4" CONDUIT CONCEALED INWALL OR CEILING UNLESS OTHERWISE NOTED
125V., 20A SIMPLEX RECEPTACLE MOUNTED AT 18" AFFUNLESS OTHERWISE NOTED
125V., 20A DUPLEX RECEPTACLE MOUNTED AT 18" AFFUNLESS OTHERWISE NOTED. ALL DWELLING UNITRECEPTACLES SHALL BE TAMPER RESISTANT INACCORDANCE WITH NEC ART.406.11."+" INDICATESMOUNTED AT 42" AFF OR 6" ABOVE COUNTER ORBACKSPLASH
WP
+
125V., 20A DUPLEX GFCI RECEPTACLE MOUNTED AT 18"AFF UNLESS OTHERWISE NOTED. "+" INDICATESMOUNTED AT 42" AFF OR 6" ABOVE COUNTER ORBACKSPLASH. "WP" INDICATES WEATHERPROOFENCLOSURE
+
125V., 20A DOUBLE DUPLEX RECEPTACLE MOUNTED AT18" AFF UNLESS OTHERWISE NOTED.
125V., 20A DUPLEX RECEPTACLE WITH BOTTOMRECEPTACLE CONNECTED TO WALL SWITCH, MOUNTEDAT 18" AFF UNLESS OTHERWISE NOTED. "+" INDICATESMOUNTED AT 42" AFF OR 6" ABOVE COUNTER ORBACKSPLASH
JB
125V., 20A TOGGLE SWITCH MOUNTED AT 42" AFFUNLESS OTHERWISE NOTED.
125V., 20A DOOR JAMB SWITCH MOUNTED AT 42" AFFUNLESS OTHERWISE NOTED.
125V., 20A CEILING FAN SPEED SWITCH MOUNTED AT42" AFF UNLESS OTHERWISE NOTED.
125V., 20A 3-WAY TOGGLE SWITCH MOUNTED AT 42"AFF UNLESS OTHERWISE NOTED.
125V., 20A BATHROOM EXHAUST FAN TIMER SWITCHMOUNTED AT 42" AFF UNLESS OTHERWISE NOTED.
125V., 20A MOTOR RATED SWITCH MOUNTED AT 42"AFF UNLESS OTHERWISE NOTED.
IC
B
INTERCOM STATION
DOOR BELL/INTERCOM STATION
J
OS
DATA COMMUNICATION OUTLET
VOICE & DATA COMMUNICATION OUTLET
5
WALL MOUNTED JUNCTION BOX
MOTOR STARTER, SIZE AS INDICATED ON PLAN
2'X4' RECESSED LED FIXTURE, "A" INDICATES TYPE, "2"INDICATES CIRCUIT BREAKER POSITION, "a" INDICATESSWITCHING
2'X4' RECESSED LED FIXTURE CONNECTED TOEMERGENCY (EM) AND/OR NIGHT LIGHT (NL) CIRCUIT,"A" INDICATES TYPE, "2" INDICATES CIRCUIT BREAKERPOSITION, "a" INDICATES SWITCHING
A
2 a
A
2 a
2'X2' RECESSED LED FIXTURE, "A" INDICATES TYPE, "2"INDICATES CIRCUIT BREAKER POSITION, "a" INDICATESSWITCHING
2'X2' RECESSED LED FIXTURE CONNECTED TOEMERGENCY (EM) AND/OR NIGHT LIGHT (NL) CIRCUIT,"A" INDICATES TYPE, "2" INDICATES CIRCUIT BREAKERPOSITION, "a" INDICATES SWITCHING
A
2
A
2
a
a
CEILING OR WALL MOUNTED EXIT SIGN WITH INTEGRALEMERGENCY LIGHT HEADS, "X" INDICATES TYPE,ARROWS AS INDICATED ON PLANS. CONNECT TO LOCALLIGHTING BRANCH CIRCUIT AHEAD OF ALL SWITCHINGUNLESS OTHERWISE NOTED
EM
WALL OR CEILING MOUNTED TWIN REMOTE EMERGENCYLIGHT "EM" INDICATES TYPE, "WP" INDICATESWEATHERPROOF.
WALL MOUNTED DUAL TECHNOLOGY OCCUPANCYSENSOR
CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCYSENSOR
PENDANT MOUNTED LIGHT FIXTURE, "A" INDICATESTYPE, "2" INDICATES CIRCUIT BREAKER POSITION, "a"INDICATES SWITCHING
2#12 & 1#12GND. IN 3/4" CONDUIT, UNLESSOTHERWISE NOTED, HOME RUN TO PANEL, "P1"INDICATES PANEL NAME, "3" INDICATES CIRCUITBREAKER POSITION
P1-3
PLAN NOTE CALLOUT
A
2
M METER AND SOCKET
POWER OPERATED DOOR SYSTEM
NEW CONNECTION TO EXISTING
TERMINATION OF DEMOLITION
RECESSED WALLWASHER DOWNLIGHT, "A" INDICATESTYPE, "2" INDICATES CIRCUIT BREAKER POSITION, "a"INDICATES SWITCHING
A
2 a
CEILING MOUNTED PADDLE FAN, "A" INDICATES TYPE,"2" INDICATES CIRCUIT BREAKER POSITION
CEILING OR WALL MOUNTED DOUBLE FACE EXIT SIGN,"X" INDICATES TYPE, ARROWS AS INDICATED ON PLANS.CONNECT TO LOCAL LIGHTING BRANCH CIRCUIT AHEADOF ALL SWITCHING UNLESS OTHERWISE NOTED COMBINATION POWER/DATA FLOOR FLUSH MOUNTED
BOX OR POKE-THRU DEVICE, REFER TO PLANS FOR TYPEAND DEVICE CONFIGURATION
A
2 a
2#12 & 1#12GND. IN 3/4" CONDUIT RUN IN OR UNDERCONCRETE SLAB UNLESS OTHERWISE NOTED
2#12 & 1#12GND. IN 3/4" CONDUIT RUN EXPOSEDUNLESS OTHERWISE NOTED
DRAWOUT CIRCUIT BREAKER MEDIUM VOLTAGE
DRAWOUT CIRCUIT BREAKER
FUSE
GROUND CONNECTION
E ELECTRIC INTERLOCK SWITCH
MOLDED CASE CIRCUIT BREAKER
J JUNCTION OR PULL BOX. SIZE AS INDICATED ON PLAN
PANEL"P1"
FUSED SWITCH
COMBINATION MOTOR STARTER AND DISCONNECTSWITCH, SIZE AS INDICATED ON PLAN
PANELBOARD, SIZE, TYPE AND RATING AS INDICATED ONPLAN
PANELBOARD, SURFACE MOUNTED
PANELBOARD, FLUSH MOUNTED
T
COPPER GROUND BAR, SIZE AS INDICATED ON PLAN
TRANSFORMER, SIZE, TYPE AND RATING AS INDICATEDON PLAN
G COPPER GROUND CONDUCTOR, SIZE AS INDICATED ONPLAN
WARNING AND SIGNALING FIXTURES/SIGNS.
WALL-MOUNTED CLOCKS, PROGRAM BELLS,FIRE ALARM AUDIBLE AND VISUAL DEVICES(OR AS SHOWN ON ARCHITECTURAL DETAILS)
EXIT SIGNS, BATTERY UNITS ANDEMERGENCY REMOTE HEADS (OR 6" BELOWFINISHED CEILING TO TOP OF FIXTURE)
TOP OF FLUSH AND SURFACE MOUNTEDELECTRICAL PANELBOARDS, TELEPHONECABINETS, OR FIRE ALARM CABINETS.
TOP OF BACK-MOUNTED WALL EXITFIXTURES (NOT MOUNTED ABOVE DOORS)
TOP OF HIGHEST ELECTRICAL SAFETYDISCONNECT SWITCHES, MAGNETICSTARTERS, CONTACTORS.
WALL MOUNTED TELEPHONES AND PAYSTATIONS, THERMOSTATS (3'-6" ATHANDICAP LOCATIONS).
WALL MOUNTED ELECTRICAL LIGHT SWITCHES,MANUAL MOTOR STARTERS, FIRE ALARM PULLSTATIONS, AND WALL MOUNTED WIREMOLD. OBTAINMOUNTING HEIGHT APPROVAL FROM BUILDINGINSPECTOR PRIOR TO ROUGHING IN LIGHT SWITCHES.
ELECTRICAL RECEPTACLE WITHINELECTRICAL/MECHANICAL SPACES ANDELEVATOR ROOMS.
FINISHED FLOOR
NO SCALE
6'-6"
6'-3"
6'-0"
4'-6"
3'-6"
2'-0"
1'-6"
10'-0"
PER N.F.P.A. &A.D.A. CODE
REQUIREMENTS
CENTEREDABOVE DOOR OR
WINDOWOPENING
ELECTRICAL RECEPTACLES, TELEPHONEOUTLETS, COMPUTER OUTLETS UNLESS INWIREMOLD, OR OTHERWISE NOTED.
0'-8" BOTTOM OF EXIT SIGN ADJACENT TO DOOR(WHERE REQUIRED)
ADA UNIT INTERCOM. CENTEROF "CALL" BUTTON.
3'-0"
TYPICAL STANDARD MOUNTING HEIGHTSDETAIL
NOTES:1. MOUNTING HEIGHTS TO CENTER OF OUTLETS UNLESS OTHERWISE
NOTED. IN MASONRY WALL CONSTRUCTION THE ABOVE MOUNTINGHEIGHTS SHALL BE USED FOR REFERENCE TO NEAREST BLOCK ORBRICK COURSING.
2. THE ABOVE MOUNTING HEIGHTS SHALL BE ADHERED TO UNLESSSPECIFICALLY NOTED OR DETAILED OTHERWISE ON THE DRAWINGSOR SPECIFICATIONS.
1
SJ
SF
S3
ST
SOS
S
ELEVATOR CONTROLLER. REFER TO "ELEVATOR CONTROLSWITCH" NOTE ON THIS PLAN FOR ADDITIONALINFORMATION
EC
SWITCHES, COVERPLATES AND RECEPTACLES BASIS OF DESIGN:COMMERCIAL - DEVICES SHALL BE WHITE WITH A METAL STAINLESS STEEL COVERPLATERESIDENTIAL-DEVICE COLOR BY ARCHITECT WITH A MATCHING COVERPLATE
CEILING MOUNTED 125V., 20A DOUBLE DUPLEXRECEPTACLE.
CEILING MOUNTED 125V., 20A DUPLEX RECEPTACLE
ELECTRICAL SYMBOLS
MTD.
P.C.
P.S.
PLG
SLD
SP/ST
S/S
R.T.U.
N.L.
SW.
UH
T/C
VAV
XFMR.
WP
V
(E)
(RL)
(R)
MOD MOTOR OPERATED DOOR
ELECTRIC WATER COOLEREWC
ELECTRIC WALL HEATEREWH
ABOVE
AMPS
ABOVE FINISHED FLOOR
CABINET HEATER
CIRCUIT BREAKER
AIR HANDLER UNIT
CEILING
ABOVE FINISHED GRADE
DRAWING
DUAL ELEMENT (TIME DELAY)
EXHAUST FAN
ELECTRICAL CONTRACTOR
ELECTRIC BASEBOARD HEATER
ELECTRIC UNIT HEATER
EMERGENCY POWER-OFF
INDICATES LIGHT FIXTURE WIREDTO EMERGENCY CIRCUIT
A.H.U.
DWG
E.P.O.
EUH
EM
E.B.H.
E.C.
E.F.
D.E.
C.H.
CLG.
C/B
A.F.F.
A.F.G.
ABV.
A
J.B.
MECH.
MLO
MCB
M.C.
KW
KVA
HWH
IG
HVAC
GND.
HP
HTR.
G.F.I.
JUNCTION BOX
MECHANICAL CONTRACTOR
MAIN LUGS ONLY
MAIN CIRCUIT BREAKER
MECHANICAL
KILOVOLT-AMPERE
KILOWATT
HEATING, VENTILATING,
HOT WATER HEATER
ISOLATED GROUND
HEATER
HORSE POWER
GROUND FAULT INTERRUPT
GROUND
FU.
G.C.
FACP
EXIST.
FIRE ALARM CONTROL PANEL
GENERAL CONTRACTOR
FUSE (OR FUSED)
EXISTING
PLUMBING CONTRACTOR
UNIT HEATER
VARIABLE AIR VOLUME
REMOVE EXISTING
RELOCATED EXISTING
EXISTING TO REMAIN
WEATHERPROOF
TRANSFORMER
VOLTS
SINGLE POLE/SINGLE THROW
SINGLE LINE DIAGRAM
SAFETY SWITCH
TIME CLOCK
SWITCH
PAY STATION
ROOF TOP UNIT
PLUMBING
NIGHT LIGHTING
MOUNTED
UNLESS OTHERWISE NOTEDU.O.N.
FATB FIRE ALARM TERMINAL BOX
FSD FIRE SMOKE DAMPER
(DISCONNECT SWITCH)
PUSHBUTTON SWITCH
& AIR CONDITIONING
ABBREVIATIONS
CEILING MOUNTED 125V., COMBINATION SMOKEDETECTOR/HORN-STROBE
CARBON MONOXIDE DETECTOR,CEILING MOUNTED 125V
F
H
S FIRE ALARM SMOKE DETECTOR
FIRE ALARM DUCT SMOKE DETECTOR
FIRE ALARM HEAT DETECTOR
FIRE ALARM SPEAKER
FIRE ALARM PULL STATION
FIRE ALARM STROBE
FIRE ALARM HORN/STROBE
FIRE ALARM WATER FLOW SWITCH
FIRE ALARM TAMPER SWITCH
S
WF
TS
S
S
F
F
FIRE ALARM ADDRESSABLE INPUT MODULEAM
CM FIRE ALARM ADDRESSABLE CONTROL MODULE
CO
FIRE ALARM DOOR HOLD OPEN DEVICEDH
VOICE COMMUNICATION OUTLET
TV CABLE TV OUTLET
IC
DC
DOOR INTERCOM STATION
DOOR CONTROLLER
DATA COMMUNICATION OUTLET
VOICE & DATA COMMUNICATION OUTLET
MC
CR
FURNITURE FEED
CARD READER
WIRELESS RADIO LINK
WIRELESS RADIO LINK
JJ
DP FURNITURE WHIP AND FEED (COORDINATE REQUIREMENTS)
P = POWERD = DATA
GENERAL SPECIFICATIONS
1. DRAWINGS ARE DIAGRAMMATIC: THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL COMPONENTSNECESSARY FOR A COMPLETE AND OPERATIONAL SYSTEM. COORDINATE AND DETERMINE FINALLOCATIONS OF SYSTEMS AND COMPONENTS IN FIELD. COORDINATE WITH ARCHITECTURAL DRAWINGSAND OTHER TRADES.
2. ADDRESS ALL QUESTIONS REGARDING DRAWINGS TO ARCHITECT IN WRITING BEFORE SUBMITTING BIDPROPOSAL. OTHERWISE, ARCHITECT'S INTERPRETATION OF MEANING AND INTENT OF DRAWINGS SHALLBE FINAL.
3. THE INTENTION IS FOR INSTALLATION OF COMPLETE AND OPERATING SYSTEMS. NOT EVERYCOMPONENT REQUIRED IS SHOWN. THE CONTRACTOR SHALL INCLUDE ALL COMPONENTS NORMALLYASSOCIATED WITH THE PARTICULAR SYSTEM. THE SYSTEM SHALL BE FULLY COMMISSIONED ANDSIGNED OFF BY AN OFFICER OF THE RESPECTIVE CONTRACTOR PRIOR TO FINAL OWNER ACCEPTANCETESTING. PROVIDE PERSONNEL TO ASSIST WITH OWNER ACCEPTANCE TESTING.
4. GIVE NOTICES, FILE PLANS, OBTAIN PERMITS AND LICENSES, PAY FEES AND BACK CHARGES, ANDOBTAIN NECESSARY APPROVALS FROM AUTHORITIES THAT HAVE JURISDICTION AS REQUIRED TOPERFORM WORK IN ACCORDANCE WITH ALL LEGAL REQUIREMENTS AND WITH THE DESIGN DOCUMENTS.
5. PRIOR TO COMMENCING WORK, CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND EQUIPMENT DATAFOR MATERIALS AND EQUIPMENT TO THE ARCHITECT FOR REVIEW AND APPROVAL. MATERIALS ANDEQUIPMENT SHALL NOT BE INSTALLED BEFORE SHOP DRAWINGS ARE REVIEWED AND APPROVED. ATLEAST TEN (10) WORKING DAYS, EXCLUSIVE OF TRANSMITTAL TIME, SHALL BE ALLOWED FORSUBMITTAL REVIEW.
6. MATERIALS AND EQUIPMENT SHALL BE LISTED BY UNDERWRITERS LABORATORIES (UL) AND APPROVEDBY ASME AND AGA, AS APPLICABLE, FOR INTENDED SERVICE.
7. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS,TECHNIQUES, SEQUENCES AND PROCEDURES REQUIRED FOR SAFE EXECUTION AND COMPLETION OFTHE WORK AND FOR INITIATING, MAINTAINING AND SUPERVISING ALL SAFETY PRECAUTIONS ANDPROGRAMS IN CONNECTION WITH THE WORK.
8. ALL MATERIALS, EQUIPMENT AND METHOD OF INSTALLATION SHALL BE ACCORDANCE WITH THESTANDARDS, REGULATIONS, CODES, ORDINANCES AND LAW OF LOCAL, STATE AND FEDERALGOVERNMENTS AND OTHER AUTHORITIES THAT HAVE LAWFUL JURISDICTION.
9. IT SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO COORDINATE THE WORK UNDER THISCONTRACT WITH THAT OF ALL OTHER TRADES, INCLUDING, BUT NOT LIMITED TO, ELECTRICAL, HVAC,SPRINKLER, PLUMBING, STRUCTURAL AND GENERAL CONSTRUCTION. OFFSETS IN DUCTWORK,PIPINGAND CONDUITS AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THEOWNER.
10. DEVIATION FROM CONTRACT DOCUMENTS, OR PROPOSED SUBSTITUTION OF MATERIALS OR EQUIPMENTFOR THOSE SPECIFIED, SHALL BE REQUESTED IN SEPARATE LETTER, WHETHER DEVIATIONS ARE DUE TOFIELD CONDITIONS, STANDARD SHOP PRACTICE OR OTHER CAUSE. THE CONTRACTOR IS RESPONSIBLEFOR ANY COSTS INCURRED AS A RESULT OF THE CHANGES NEEDED TO ACCOMMODATE THESUBSTITUTED EQUIPMENT, INCLUDING THE WORK OF OTHER TRADES.
11. EACH CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING REQUIRED FOR THE INSTALLATION OFNEW WORK UNDER THIS CONTRACT. CUTTING AND PATCHING SHALL BE COMPLETED IN A NEAT ANDWORKMANLIKE MANNER. PATCHING MATERIALS SHALL MATCH EXISTING MATERIALS TO THE GREATESTEXTENT POSSIBLE. PROVIDE TOUCH-UP TO MATCH EXISTING SURROUNDING AREAS OF CUTTING ANDPATCHING WORK.
12. INTERRUPTIONS TO EXISTING SERVICES AND SYSTEMS SHALL BE AS SHORT AS POSSIBLE AND AT ATIME AND DURATION APPROVED BY THE OWNER. INCLUDE ALL PREMIUM TIME ASSOCIATED WITHINTERRUPTIONS IN BID PROPOSAL. INTERRUPTIONS SHALL BE SCHEDULED WITH OWNER AT LEAST 48HOURS IN ADVANCE.
13. CONTRACTOR SHALL COORDINATE ITS RESPECTIVE CEILING MOUNTED EQUIPMENT AND DEVICES WITHOTHER TRADE CONTRACTORS PRIOR TO INSTALLATION TO AVOID CONFLICTS.
14. ALL DEMOLITION WORK SHALL BE COORDINATED WITH OWNER'S REPRESENTATIVE, ARCHITECT,ENGINEER AND GENERAL CONTRACTOR. ALL DEBRIS SHALL BE CLEANED AND REMOVED FROM THE SITEBY END OF EACH WORK DAY. PRIOR TO DISPOSAL OF EQUIPMENT AND MATERIALS, TURN OVER TO THEOWNER ANY REMOVED EQUIPMENT AND MATERIALS REQUESTED BY THE OWNER.
15. WORK SHALL BE EXECUTED IN A WORKMANLIKE MANNER AND SHALL PRESENT A NEAT, RECTILINEARAPPEARANCE WHEN COMPLETED.
16. MAINTAIN MAXIMUM HEAD ROOM AT ALL TIMES. DO NOT RUN PIPES, DUCTS AND CONDUIT EXPOSEDUNLESS SHOWN AND NOTED TO BE EXPOSED ON DRAWINGS.
17. MATERIALS AND EQUIPMENT SHALL BE NEW, UNLESS NOTED OTHERWISE, AND INSTALLED ACCORDINGTO MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS SO THAT COMPLETED INSTALLATIONSHALL OPERATE SAFELY AND EFFICIENTLY.
18. EACH RESPECTIVE CONTRACTOR SHALL FIRE STOP ALL NEW AND EXISTING OPENINGS THROUGH FIRERATED FLOORS, WALLS AND CEILINGS WITH UL ASSEMBLIES OF EQUAL RATING. FIELD VERIFY EXISTINGCONDITIONS BEFORE SUBMITTING BID PROPOSAL.
19. COORDINATE ALL ROOF PENETRATIONS WITH WORK OF OTHER TRADES. ALL PENETRATIONS SHALL BESEALED WATERTIGHT. COORDINATE FLASHING REQUIREMENTS TO MAINTAIN ROOF WARRANTY.
20. ANY INTERFERENCE SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER'S REPRESENTATIVE ORARCHITECT AND SHALL BE RESOLVED PRIOR TO THE INSTALLATION OF THE WORK INVOLVED.
21. MANUFACTURERS' MODEL NUMBERS ARE SPECIFIED SOLELY TO ESTABLISH STANDARDS OF QUALITYFOR PERFORMANCE AND MATERIALS.
22. SUBSTITUTED PRODUCTS SUBMITTED AND APPROVED FOR USE THAT NECESSITATE CHANGES TO THEWORK OF OTHER TRADES OF CONTRACT SHALL BE COORDINATED AND ARRANGED BY THE CONTRACTORWHO SUBMITTED THE SUBSTITUTION WITHOUT ADDITIONAL COST TO THE OWNER.
23. PRODUCT INSTALLATION SHALL ADHERE TO MANUFACTURER'S RECOMMENDATIONS AND INSTRUCTION.24. EACH RESPECTIVE CONTRACTOR SHALL PROVIDE PROPER ACCESS TO EQUIPMENT AND COMPONENTS
THAT REQUIRE INSPECTION, MAINTENANCE AND POSSIBLE REPAIR. ACCESS PANELS SHALL BE MINIMUM12"X12" OR AS NEEDED FOR PROPER ACCESS. ACCESS PANELS SHALL BE FURNISHED BY THISCONTRACTOR AND TURNED OVER TO GENERAL CONTRACTOR FOR INSTALLATION.
25. CONTRACTOR SHALL COORDINATE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS OF ALLAPPLICABLE EQUIPMENT WITH THE ELECTRICAL CONTRACTOR.
26. AS WORK PROGRESSES AND FOR DURATION OF CONSTRUCTION, MAINTAIN A COMPLETE SET OFCONTRACT DRAWINGS AT THE JOBSITE. RECORD WORK COMPLETED AND ALL CHANGES FROM ORIGINALCONTRACT DRAWINGS CLEARLY AND ACCURATELY INCLUDING WORK INSTALLED AS A MODIFICATIONOR ADDITION TO THE ORIGINAL DESIGN TURN OVER ALL OPERATING MANUALS, MAINTENANCEMANUALS, AND "AS BUILT" DRAWINGS TO OWNER AT CONCLUSION OF CONSTRUCTION.
27. DO NOT SUPPORT EQUIPMENT, DUCTWORK, PIPING, CONDUIT OR DEVICES FROM SUSPENDED CEILINGS.SUPPORT ALL EQUIPMENT, DUCTWORK, PIPING, CONDUIT AND DEVICES FROM BUILDING STRUCTURE TOPROVIDE A VIBRATION FREE INSTALLATION. NOTIFY ARCHITECT AND STRUCTURAL ENGINEER OF ALLWEIGHTS AND METHODS OF SUPPORT.
28. ANY REFERENCE TO MECHANICAL, PLUMBING, FIRE PROTECTION OR ELECTRICAL CONTRACTORS NOTEDON THE DRAWINGS SHALL NOT BE INTERPRETED AS AN INTENTION TO DEFINE SEPARATE CONTRACTORSFOR THE RESPECTIVE WORK. THE GENERAL CONTRACTOR SHALL COORDINATE AND PROVIDE ACOMPLETE INSTALLATION WITH COMPLETE MECHANICAL, PLUMBING, FIRE PROTECTION ANDELECTRICAL SYSTEMS, REGARDLESS OF ANY REFERENCES TO OTHER TRADE CONTRACTORS.
29. GUARANTEE WORK OF THIS CONTRACTOR IN WRITING FOR A PERIOD OF ONE YEAR FROM THE DATE OFOWNER'S ACCEPTANCE OR CERTIFICATE OF SUBSTANTIAL COMPLETION. PROMPTLY REPAIR OR REPLACEDEFECTIVE MATERIALS, EQUIPMENT, WORKMANSHIP AND INSTALLATIONS THAT DEVELOP DEFECTSWITHIN THIS PERIOD. PROMPTLY AND TO OWNERS SATISFACTION, CORRECT DAMAGE CAUSED INMAKING NECESSARY REPAIRS AND REPLACEMENTS UNDER THIS GUARANTEE AT NO ADDITIONAL COSTTO OWNER. SUBMIT GUARANTEE TO ARCHITECT BEFORE FINAL PAYMENT IS MADE. STATEMENT OFGUARANTEE REQUIREMENTS SHALL NOT BE INTERRUPTED TO LIMIT OWNER'S RIGHTS UNDER LAW ANDTHIS CONTRACT.
1. PROJECT CONDITIONS1.1. THE CONTRACTOR SHALL BECOME COMPLETELY FAMILIAR WITH ALL EXISTING BUILDING AND SITE
CONDITIONS AND LIMITATIONS WHICH MAY HAVE A BEARING ON THE OPERATIONS HEREIN SPECIFIEDAND SHALL INCLUDE ALL WORK REQUIRED TO COMPLETE THE PROJECT AS SHOWN ON THE DRAWINGS.NO EXTRA COMPENSATION WILL BE ALLOWED FOR UNFORESEEN CONDITIONS THAT CAN BEDETERMINED FROM A CAREFUL EXAMINATION OF THE SITE, BUILDING AND DRAWINGS.
1.2. ITEMS OF VALUE WHICH ARE NOT INDICATED TO BE RETURNED TO THE OWNER SHALL BECOME THEPROPERTY OF THE CONTRACTOR. STORAGE OR SALE OF ITEMS ON THE PROJECT SITE IS PROHIBITED.
1.3. PROTECTION: ENSURE THE SAFE PASSAGE OF PERSONS IN AND AROUND THE BUILDING DURINGDEMOLITION. PREVENT INJURY TO PERSONS AND DAMAGE TO PROPERTY. PROVIDE ADEQUATESHORING AND BRACING TO PREVENT COLLAPSE. IMMEDIATELY REPAIR DAMAGED PROPERTY TO THECONDITION BEFORE BEING DAMAGED. TAKE EFFECTIVE MEASURES TO PREVENT WINDBLOWN DUST.
1.4. UTILITIES: MAINTAIN ALL UTILITIES EXCEPT THOSE THAT REQUIRE REMOVAL OR RELOCATION. KEEPUTILITIES IN SERVICE AND PROTECT FROM DAMAGE. DO NOT INTERRUPT UTILITIES SERVING OCCUPIEDAREAS OF THE SITE OR BUILDING WITHOUT FIRST OBTAINING PERMISSION FROM OWNER.
2. REGULATION REQUIREMENTS2.1. STRICTLY COMPLY WITH APPLICABLE CODES, REGULATIONS AND REQUIREMENTS OR AUTHORITY
HAVING JURISDICTION.3. HANDLING OF MATERIALS
3.1. REMOVE DEBRIS FROM THE SITE AS IT ACCUMULATES. DO NOT STORE, SELL, BURN OR OTHERWISEDISPOSE OF DEBRIS ON SITE. REMOVE ALL MATERIAL IN SUCH MANNER AS TO PREVENT SPILLAGE.
4. TRANSFER OF RESPONSIBILITY AND DISPOSITION OF MATERIALS4.1. UPON RECEIPT OF NOTICE TO PROCEED WITH THE WORK, THE TITLE TO ALL MATERIALS FOR
DEMOLITION SHALL BE VESTED. THE CONTRACTOR WHEREUPON THE OWNER WILL NOT BERESPONSIBLE FOR THE CONDITION, LOSS OR DAMAGE TO SAID PROPERTY. ALL SUCH ITEMS SHALL BEREMOVED FROM THE OWNER'S PROPERTY.
5. DISPOSAL OF DEMOLISHED MATERIALS5.1. REMOVE UNUSED EQUIPMENT AND FIXTURES AND ALL ASSOCIATED DUCTWORK AND PIPING SERVICING
EQUIPMENT AND FIXTURES INCLUDING ANY ABANDONED DUCTWORK AND PIPING NOT ASSOCIATEDWITH SAID EQUIPMENT AND FIXTURES AND NOT REQUIRED FOR NEW WORK. REMOVE DUCTWORK ANDPIPING BACK TO THE NEXT LIVE BRANCH WHICH WILL NOT OBSTRUCT THE NEW WORK AND CAP AIR ORWATER TIGHT. TRANSPORT AND LEGALLY DISPOSE OF MATERIALS OFF SITE.
5.2. ALL DEMOLITION SHALL BE COORDINATED WITH OWNER, ARCHITECT, ENGINEER AND GENERALCONTRACTOR. ALL DEBRIS SHALL BE CLEANED UP AND REMOVED FROM THE SITE BY THE END OF EACHWORK DAY. PRIOR TO DISPOSAL OF EQUIPMENT AND MATERIALS, TURN OVER TO OWNER ANYREMOVED EQUIPMENT AND MATERIALS PER OWNER'S REQUEST.
6. CLEAN UP AND REPAIR6.1. UPON COMPLETION OF DEMOLITION WORK, REMOVAL TOOLS, EQUIPMENT AND DEMOLISHED
MATERIALS FROM SITE. REMOVE PROTECTION AND LEAVE INTERIOR AREAS BROOM CLEAN.6.2. REPAIR DEMOLITION PERFORMED IN EXCESS OF THAT REQUIRED. RETURN STRUCTURES AND
SURFACES TO REMAIN IN CONDITION EXISTING PRIOR TO COMMENCEMENT OF SELECTIVE DEMOLITIONWORK. REPAIR ADJACENT CONSTRUCTION OR SURFACES SOILED OR DAMAGED BY SELECTIVEDEMOLITION WORK.
DEMOLITION NOTES
DF
AS
N
OT
ED
JM
F
RP-1
SPECIFICATIONS FOR
ENGRAVED, LAMINATED ACRYLIC
OR MELAMINE LABEL. REFER TO
208Y/120V
ADDITIONAL INFORMATION
EQUIPMENT DESIGNATION
EQUIPMENT VOLTAGE
FIXTURE IN ROOM
TO NEXT LIGHTING
SENSOR
OCCUPANCY
TO NEXT OCCUPANCY
SENSOR IN ROOM
BLUE (CONTROL)
BLACK (COMMON)
RED (+24VDC)
L1
N
G
POWER SWITCH PACK
LIGHTING
FIXTURE
(MAXIMUM OF 5)
TOGGLE SWITCH
(TYPICAL)
6'-0" MAXIMUM LENGTH
MC CABLE
BRANCH CIRCUIT WIRE
AND CONDUIT (TYPICAL)
JUNCTION BOX
(TYPICAL)
J J
E-2
1
SCALE - NONE
DETAIL - NAMPLATE
E-2
2
SCALE - NONE
WIRING DIAGRAM - CEILING MOUNTED OCCUPANCY SENSOR
E-2
3
SCALE - NONE
DETAIL - LIGHTING FIXTURE WIRING
STEEL/UNISTRUT/CEILING/ETC.
SUSPENDED CEILING
FLOOR
18" FOR DATA/PHONE/VOICE OUTLETSUNLESS OTHERWISE SPECIFIED BYARCHITECT
4" SQ X 2 1/8" DEEP BOX WITHRAISED DEVICE COVER
DEPTH OF RAISED COVER =DEPTH OF DRYWALL (+)FINISH COAT
COMMUNICATION CABLERUN IN 1" EMT RACEWAY
PLENUM RATED CABLE(PROVIDE PULL WIRE WHENCABLE IS NOT PROVIDED)
INSTALL BUSHINGON CONDUIT END
E-2
4
SCALE - NONE
DETAIL - DEVICE INSTALLATION
HOT(H)
BLAC
KGROUND
(GND)
GREE
N
GROUND (GND)
HOT (H)BLACK
GREEN
WHITENEUTRAL (N)
NEUTRAL(N)
WHI
TE
120 VOLTSOURCE
E-2
5
SCALE - NONE
DETAIL - TYPICAL DUPLEX RECEPTACLE WIRING
1 CIRCUIT NO. ON PLAN
GROUND BAR GROUND BARNORMAL EQUIPMENT ISOLATED EQUIPMENT
NEAR WALL BOX
AL
UTR
EN
#12 HOT
D
GRD
GRD
20A
AØ BØ
POWER PANEL
20A
BOX
BASE
ON
CONTRACTOR
FLEXIBLE POWER WHIP FURNISHED BY OTHERS
3/4" FLEXIBLE METAL CONDUIT
JUNCTION BOX (FLOOR OR WALL MOUNTED)
FURNITURE NOTES:1. THE FURNITURE WIRING WAS DESIGNED BASED ON A 8 WIRE SYSTEM (3 HOTS, 1 OVERSIZED NEUTRAL, 1 HOT, 1
NEUTRAL AND 2 EQUIPMENT GROUNDS) AS SHOWN WITH 16 CUBICLES PER 8 WIRE CIRCUIT. THE CONTRACTORSHALL TAKE THE RESPONSIBILITY OF REDESIGNING THE LAYOUT IF THE FURNITURE IS DIFFERENT THEN ORIGINALDESIGN PARAMETERS.
208/120 VOLT, 3 PHASE, 4 WIRE
#12 HOT
#12 HOT
#12 HOT
#12 ISOLATED
#12 NEUT
#12 EQUIP GRD
#10 NEUT
RG
CØ
JUNCTION BOX ABOVE CEILING
1 CIRCUIT NO. ON PLAN
WIRE SHALL BE NO. 10 AWGTHE 3 PHASE SHARED NEUTRAL3/4" CONDUIT E.M.T.
CONNECTION
MODULARFURNITURE
AND INSTALLED BY
E-2
6
SCALE - NONE
WIRE MODULAR PARTITION WIRING DIAGRAM
DF
AS
N
OT
ED
JM
F
1. ALL LIGHTING FIXTURES ARE NEW UNLESS NOTED OTHERWISE. COORDINATEEXACT LOCATION OF ALL NEW LIGHTING FIXTURE WITH WITH ARCHITECTURALDRAWINGS. VERIFY ANY QUANTITY DISCREPANCY WITH ARCHITECT AND AEI.
2. ALL LIGHTING CONTROL SHALL BE REPLACED WITH NEW OCCUPANCY WALLSWITCH OR CEILING SENSOR, UNLESS NOTED OTHERWISE. WHERE CONTROLSWITCH IS SHOWN WITH CEILING OCCUPANCY SENSOR, THE SWITCH SHALLBE USED FOR OCCUPANCY SENSOR OVER-RIDE. REFER TO DETAIL 2/E-1.1.
3. COORDINATE PLACEMENT OF WALL SWITCH WITH ARCHITECT DRAWINGSPRIOR TO ROUGH-IN.
4. CONNECT NEW LIGHTING FIXTURES TO EXISTING LIGHTING CIRCUIT BREAKERSIN PANEL 'LP'. LIGHTING CIRCUITS NUMBERS SHOWN ARE FOR REFERENCEONLY.
GENERAL ELECTRICAL
30(E)T
15T
(E)PANELEP
(E)PANELEPB
(E)PANELEL
(E)PANELEO
7.5
(E)PANELPP
(E)TRANSFSWITCH
(E)FACP(E)MAINSWITCHBOARD FF
F
(E)TELE/COM
(E)(E)
(E)PULLBOX
(E)
(E)
(E)
SO
SS
OS
SO
S
SO
S
SO
SS
OS
SO
SS
OS
SO
S
SOS
SO
S
SOS
SOS
SOS
S
SOS
SO
S
SO
SS
OS
OS
OS
OS OS
OS
OS
OSOS
OS
OS
OS
OS
OS
OS
OS
OSOS
OS
SO
SS
OS
S
S
SO
S
SO
S
S
S
S
S
OS
OS
Sa
OS
S S
S
B1 B1A1
B1
B1 B1 B1B1 B1 B1
B1
B1
B1
B1
B1
B1
B1B1
B1
B1B1
B1
B1
B1
B1
B1
B1
B1 B1
B1
B1
B1
B1B1
A1 A1 A1 A1 A1
A1A1
A1 A1
A1A1
A1 A1
A1
A1
A1
A1A1
A1
A1
A1 A1 A1
A1A1
A1
A1A1
A1
A1A1
A1 A1 A1
A1A1
A1 A1 A1
A1
A1
A1
A1 A1 A1
A1 A1 A1 A1
A1
A1
A1 A1
A1
A1
A1
A1A1A1A1
A1 A1 A1
A1
A1
A1A1
A1 A1
A1
A1
A1 A1 A1
A1 A1 A1 A1
A1 A1
A1 A1
A1
A1 A1
A1
A1
A1 A1
A1
A1 A1
A1A1 A1
A1A1 A1
A1
A1
A1
A1
A1
A1
A1
A1A1A1
A1 A1 A1
B1
B1
B1
B1B1
B1
A1 A1
A1
X1X1
X1
X1
X1
X1
X1
X1
X1
X1
S
SOS
X1
X1
X1
X1
OS
OS
OS
OS
OS
OS
OS
OS
S
OS
S S
SSa
F1
F1 F1a a
a
E1
(E)PANELPAB
75
(E)XFMR (E)PANELPA-A
(E)PANELLA
(E)PANELDP
(E)MAINSWITCHBOARD
X1
X1X1
X1
X1
OS
S
S
2 2
2
2
2 2
2
2
2
2
2 2
2
2 2
2
22
2
1
11
1
1
1 1 1 1
1
4
4
4 4
4
1 1
1
1
4 1 1 1
4
4
4
4
4
4
4
4 4
6 6
66
6
6
6 6
6
6 6
6
6
1
3
3
3
3
3 3
3 3
3 3
3
3
3
33
3 3
5
5
5
5
5
5
5 5
5
5
5
5
5 5
5
5 5
55
5
8
8
8
8
8
8
8
8
8
8
88
8
8
8
8
8
8 8
ELECTRICAL PLAN NOTES:
CONNECT NEW SHOWER LIGHTING FIXTURES TO EXISTING 120V CIRCUIT FEEDING LIGHTS.
ALL NIGHTLIGHT/ EMERGENCY LIGHTING FIXTURES AND EXIT SIGNS SHALL BE UN-SWITCHEDAND CONNECTED TO NEAREST EMERGENCY PANEL SERVING AREA.
1
2
1
1
2
2
(TYP)
(TYP)
D1 D1
D1
D1
5
5
55
S S
OS
30(E)T
15T
(E)PANELEP
(E)PANELEPB
(E)PANELEL
(E)PANELEO
(E)PANELDP 7.5
(E)PANELPP
(E)TRANSFSWITCH
(E)FACP(E)MAINSWITCHBOARD FF
F
(E)TELE/COM
(E)(E)
(E)PULLBOX
(E)
(E)
(E)
ALL EXISTING TO REMAIN CEILING DEVICES SHALL BE PROTECTED DURING CONSTRUCTION.IF CEILING TILE IS REPLACED, RELOCATE DEVICE IN SAME LOCATION AFTER NEW WORK ISCOMPLETE.
DISCONNECT AND REMOVE ALL CEILING LIGHTING FIXTURES AND ASSOCIATED CONTROLSTHROUGHOUT SPACE. RETAIN WIRE AND CONDUIT FOR REUSE IN NEW WORK.
COORDINATE THE EXACT QUANTITY OF MECHANICAL EQUIPMENT TO BE DEMOLISHED ORRELOCATED WITH MECHANICAL DRAWINGS.
1.
GENERAL ELECTRICAL
2.
S(R)
S(R)
S(R) S(R
)S(R
) S(R)
(R)S (R
)
S(R) S(R
)S(R
) S(R)
S(R) S(R
)
S(R) S(R
)S(R
) S(R)
S(R) S(R
)
S(R) S(R
)S(R
) S(R)
(E)PANELPAB
75
(E)XFMR (E)PANELPA-A
(E)PANELLA
SS(R
)
(R)(
R)S
S(R
)(R)
SS
(R)S(R)S(R)S
(R)S
ELECTRICAL PLAN NOTES:
COORDINATE CEILING AND WALL DEVICE REMOVAL AND RELOCATION IN MEETING ROOM. AND ADJACENT CORRIDOR. WALL SWITCHESCONTROL VARIES SENSITIVE EQUIPMENT IN THIS ROOM. FIELD VERIFY ALL WORK IN THIS ROOM PRIOR TO BEGINNING CONSTRUCTION.
EXISTING EXHAUST HOOD CONTROL SWITCH TO REMAIN.
REMOVE WIRE TO EXISTING RTU (ON ROOF). REMOVE ALL ASSOCIATED FIRE ALARM AND CONTROLS BACK TO SOURCE.
REMOVE EXISTING WIRE AND CONDUIT TO VAV BOX FOR REMOVAL BY MECHANICAL CONTRACTOR..
ADD-ALT -DISCONNECT AND REMOVE WIRE AND CONDUIT TO EXISTING EXHAUST FAN, FOR REMOVAL BY OTHERS.
ADD-ALT-DISCONNECT AND REMOVE WIRE AND CONDUIT TO EXISTING ROOFTOP EXHAUST FAN.
1
1 1
S(R)
S(R)
S(R)
S(R)
S(R)
S(R)
S(R)
S(R)
S(R)
S(R)
S(R)
S(R) S(R
)
S(R) S(R
)
S (R)S (R
)
S(R
)S
(R)
(R)(
R)S
S
(R)S
(R)
S
(R)S
(R)
S
(R)S
(R)S
1
(R)S
(E)S2
2
4
3.
3
3
3
3
RTU3
RTU2
RTU1
4
4
4
4
4
4
4
4
4
4
4
4
5
5
6
5
6
(R)S
(R)(R)SS
(R)(R)SS
KEY PLAN
PHASE 1
E-1.1
2
SCALE - 1/8" = 1'-0"
ELECTRICAL FLOOR PLAN - LIGHTING - PHASE 1
AS
N
OT
ED
JM
F
DF
E-1.1
1
SCALE - 1/8" = 1'-0"
ELECTRICAL FLOOR PLAN - DEMOLITION LIGHTING - PHASE 1
0' 4' 16'8' 0' 4' 16'8'
B1 B1 B1 B1
B1
B1
B1
B1 B1 B1
B1
B1 B1
B1 B1
B1 B1 B1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1A1
A1A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1 A1
A1 A1
A1
A1A1A1A1
A1 A1
A1 A1
A1 A1 A1
A1
A1A1A1
A1A1A1
A1 A1
A1A1
A1
A1
A1A1A1A1
A1 A1 A1
A1 A1 A1
A1A1
A1
A1 A1A1
A1A1A1
A1 A1
A1 A1 A1
A1
A1
A1 A1
A1
A1
A1
A1 A1
A1
A1A1A1
B1 B1 B1
A1A1
X1 X1
X1
X1
X1
X1
X1
X1
X1
X1
X1
X1
D1 D1
D1 D1
D1 D1
D1 D1 D1 D1
D1 D1
OS OS
OS OS OS
OS
OS
OS
OS
OS OS
OS
OS
OS
OS
OS
OS
OS
OSOS
OS
OS
OS
OS
OS
OS
OS
SO
S
SO
S
SO
S
S
SOS
S
S
S
SOS
S S S
S
Sa
a
a
a
a
a
a
OS OS
OSOS
SOS
SOS
SX1
N.I.C.
S
S
S
S
S
1. ALL LIGHTING FIXTURES ARE NEW UNLESS NOTED OTHERWISE. COORDINATEEXACT LOCATION OF ALL NEW LIGHTING FIXTURE WITH WITH ARCHITECTURALDRAWINGS. VERIFY ANY QUANTITY DISCREPANCY WITH ARCHITECT AND AEI.
2. ALL LIGHTING CONTROL SHALL BE REPLACED WITH NEW OCCUPANCY WALLSWITCH OR CEILING SENSOR, UNLESS NOTED OTHERWISE. WHERE CONTROLSWITCH IS SHOWN WITH CEILING OCCUPANCY SENSOR, THE SWITCH SHALLBE USED FOR OCCUPANCY SENSOR OVER-RIDE. REFER TO DETAIL 2/E-1.1.FOR OFFICE FURNITURE SYSTEM LIGHTS SHALL BE CONTROLLED BY CEILINGSENSOR.
3. COORDINATE PLACEMENT OF WALL SWITCH WITH ARCHITECT DRAWINGSPRIOR TO ROUGH-IN.
4. CONNECT NEW LIGHTING FIXTURES TO EXISTING LIGHTING CIRCUIT BREAKERSIN PANEL 'LB'. LIGHTING CIRCUITS NUMBERS SHOWN ARE FOR REFERENCEONLY.
GENERAL ELECTRICAL
ELECTRICAL PLAN NOTES:
SKY LIGHT FIXTURE SHALL BE CONTROLLED BY PHOTO CELL WITH LOCAL SWITCH OVER RIDE.
ALL NIGHTLIGHT/ EMERGENCY LIGHTING FIXTURES AND EXIT SIGNS SHALL BE UN-SWITCHEDAND CONNECTED TO NEAREST EMERGENCY PANEL SERVING AREA.
1
2
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1 1
1
2
2 2
2 2
2
2
2
2
2
22
2
4
4
4
4
1 1 1 1
1 1
D1
D1
3
33
3
3
3
3
3 3 3 3
3
3 3
3
3
3
3 3 3
33
5 5
5 5
5 5
5 5
5
5
5
5
5 5
5 5
5 5
5
5 4
4
4 4
4
4
4
444
4 4 4
4 4
4 4
4
4 4 4
2 (TYP)
2 (TYP)
OS
OS
OS
+
+
++
J
JJ
112.5
(E)T
(E)PANEL SL
(E)PANELPB-B
(E)PANEL PB-A
(E)PANEL LB
S3
S
S
Sb
SDS
OS
OS
OSSSSS
SS
SSD
OSOS
OS
S
SOS SOS SOS
SOS
OS
OS
SOS
OS
OS
Sa
SOSS3
S3OS
S3OSS3OS
SOS
SOS
OS
S3
OS
Sa
OS
OS
OS
SOS SOS
SOS
SOS
OS
OS
Sa
2
TV TV
J
1
TV
SOSSOS
SOSSOS
TV
TV
TV
F
F F
F
FF
J
J
(E) (E)
(E)
(E)
(E)
(E)(E)
(E)
(E)
(E) (E) (E)
(E)
(E)(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)(E)
(E)
(E)(E)
(E)(E)
(E)
(E)
(R)
(E)
(R)
(R)
(R) (R)
(R)
(R)
(R)(R)
(R)
(R)(R)
(R)(R)
(R)
(R)
(R)
(R)
(R) (R)
(R)
(R)
(R)
(R)
(R)
(R)
(R)(R)
(R)
(R)
(R)
(E)
1
1
(R)
(R)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E) (E)
(E)
(E)
(E)(E)
(E)
(E)
(E)(E)
(R)
(R)
(E)
(E)
(E)
(E) (E)(E)
(E)
(E) (E)
(E)
(R)
(R)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(R)
RTU8
3
8
7
7
7
8
7
7
1
11
1
1 1
1
11
1
1
1
1
1
11
1
1
1
1
1
1
REMOVE ALL RECEPTACLES AT WALLS BE DEMOLISHED, COORDINATE DEMOLITION WORK WITH ARCHITECTURAL DRAWINGSAND GENERAL CONTRACTOR.
DISCONNECT AND REMOVE ALL CEILING LIGHTING FIXTURES AND ASSOCIATED CONTROLS THROUGHOUT OFFICE SPACE.RETAIN WIRE AND CONDUIT FOR REUSE IN NEW WORK.
RECEPTACLES AND TELECOMMUNICATION DEVICES SHALL REMAIN IN EXISTING TO REMAIN ROOMS AND WALLS.
FOR ALL EXISTING BLANK COVERS PLATES THROUGHOUT SPACE, PATCH AND PAINT WALL TO MATCH EXISTING CONDITIONS.
VERIFY ALL CEILING DEVICES PRIOR TO DEMOLITION WORK. SECURE DEVICES TO ABOVE CEILING DURING CONSTRUCTION. ALLFIRE ALARM, EMERGENCY, AND SECURITY DEVICES SHALL REMAIN OPERABLE DURING RENOVATION. RELOCATE TO SAMELOCATION WHEN NEW CEILING IS INSTALLED. NEW WIRE AND CONDUIT EXTENSION SHALL MATCH EXISTING.
COORDINATE THE EXACT QUANITIY OF MECHANICAL EQUIPMENT TO BE DEMOLISHED OR RELOCATED WITHMECHANICAL DRAWINGS
1.
GENERAL ELECTRICAL
2.
3.
4.
5.
ELECTRICAL PLAN NOTES:
COORDINATE CEILING AND WALL DEVICE REMOVAL AND RELOCATION IN MEETING ROOM. AND ADJACENT CORRIDOR.WALL SWITCHES CONTROL VARIES SENSITIVE EQUIPMENT IN THIS ROOM. FIELD VERIFY ALL WORK IN THIS ROOM PRIORTO BEGINNING CONSTRUCTION.
COORDINATE RELOCATION OR REMOVAL OF EXISTING SILENT ALARM SYSTEM TO POLICE STATION.
REMOVE WIRE AND CONDUIT TO EXISTING RTU (ON ROOF). REMOVE ALL ASSOCIATED FIRE ALARM AND CONTROLS BACKTO SOURCE.
REMOVE EXISTING WIRE AND CONDUIT TO VAV BOX FOR REMOVAL BY MECHANICAL CONTRACTOR..
ADD-ALT -DISCONNECT AND REMOVE WIRE AND CONDUIT TO EXISTING EXHAUST FAN, FOR REMOVAL BY OTHERS.
ADD-ALT-DISCONNECT AND REMOVE WIRE AND CONDUIT TO EXISTING ROOFTOP EXHAUST FAN.
DISCONNECT FURNITURE SYSTEM FEED TO FURNITURE SYSTEM FOR REMOVAL BY OTHERS. RETAIN FURNITURE SYSTEMWHIP, WIRE AND CONDUIT FOR REUSE IN NEW WORK.
DISCONNECT AND REMOVE FURNITURE POWER POLE. REMOVE ALL POWER AND TELE DATA WIRING AND CONDUIT BACKTO SOURCE.
1
2
3
4
5
6
6.
7
8
KEY PLAN
PHASE 2
AS
N
OT
ED
JM
F
DF
E-1.2
2
SCALE - 1/8" = 1'-0"
ELECTRICAL FLOOR PLAN - LIGHTING - PHASE 2
E-1.2
1
SCALE - 1/8" = 1'-0"
ELECTRICAL FLOOR PLAN - DEMOLITION LIGHTING - PHASE 2
0' 4' 16'8'
0'4' 16'8'
30(E)T
15T
(E)PANELEP
(E)PANELEPB
(E)PANELEL
(E)PANELEO
(E)PANELDP 7.5
(E)PANELPP
(E)TRANSFSWITCH
(E)FACP(E)MAINSWITCHBOARD FF
F
(E)TELE/COM
(E)(E)
(E)PULLBOX
(E)
(E)
(E)
SHEET NOTES:
1. ALL SINGLE PHASE BRANCH CIRCUITING SHALL BE 2#12 & 1#12GND - 3/4"C UON. ALL THREE
PHASE BRANCH CIRCUITING SHALL BE 3#12 & 1#12GND - 3/4"C UON. ROUTE ALL BRANCH
CIRCUITS TO PANEL INDICATED IN ROOM UON. REFER TO SINGLE LINE DIAGRAM FOR
ADDITIONAL WIRE SIZES.
2. REFER TO APPROPRIATE TRADE DRAWINGS FOR EXACT LOCATION OF HVAC, PLUMBING, AND
ARCHITECTURAL EQUIPMENT.
3. ALL EXISTING FIRE ALARM AND SECURITY SHALL REMAIN., RELOCATE ANY CEILING DEVICE
WHERE CEILING IS REPLACED. CONNECT NEW DEVICES TO EXISTING FIRE ALARM SYSTEM.
MODIFIY SYSTEM AS REQUIRED TO ACCOMMODATE NEW DEVICES.
F
F
F
(E)
(E)
F(E)
F(E)
F
(E)
F
(E)
F
(E)
F
(E)
(E)PANELPAB
75
(E)XFMR (E)PANELPA-A
(E)PANELLA
EFM-2
EFP-2
EFP-1
(E)
F(N)
F(N)
F(N)
F(N)
F(N)
F(N)
F(N)
F(N)
F(N)
F(N)
F(N)
RTU2
RTU1
(N)
ELECTRICAL PLAN NOTES:
CONNECT TO EXISTING PANEL FEEDING RTU(S) PROVIDE NEW 45A BREAKER AND 3#6, +GND IN EXISTING CONDUIT.NEW BREAKER SHALL MATCH EXISTING CONDITIONS.
PROVIDE NEW DUCT DETECTORS ON RETURN SIDE OF ALL RTU UNITS AS SHOWN ON MECHANICAL DRAWING. CONNECT TO FIREALARM SYSTEM.
CONNECT TO EXISTING PANEL DP IN MAIN ELECTRICAL ROOM PROVIDE NEW 20A BREAKER AND 3#12, +GND IN 3/4" CONDUIT.NEW BREAKER SHALL MATCH EXISTING CONDITIONS.
FOR ADD ALTERNATE EXHAUST FANS. IF EXISTING CIRCUIT IS NOT SUITABLE, PROVIDE 20/1 BREAKER IN EXISTING PANEL IF SPAREBREAKER IS NOT AVAILABLE. NEW BREAKER SHALL MATCH EXISTING BREAKERS.
1
1
1
2
2
2
RTU3
32
3
PANEL LACIRCUIT #34
PANEL LACIRCUIT #36
PANEL LACIRCUIT #38
4
4
4
4
RTU4
3F(N)
F(N)
KEY PLAN
PHASE 1
E-2-.1
1
SCALE - 1/8" = 1'-0"
ELECTRICAL FLOOR PLAN - POWER - PHASE 1
AS
N
OT
ED
JM
F
DF
0'4' 16'8'
J
JJ
J
(E)
(E)
(E) (E) (E)
(E)
(E)(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)(E)
++
112.5
(E)T
30(E)T
15T
(E)PANELEP
(E)PANELEPB
(E)PANELEL
(E)PANELEO
(E)PANELDP 7.5
(E)PANELPP
(E)TRANSFSWITCH
(E)FACP(E)MAINSWITCHBOARD FF
F
(E)TELE/COM
(E)PANEL SL
(E)PANELPB-B
(E)PANEL PB-A
(E)PANEL LB
(E)(E)
(E) (E)
(E)PULLBOX
(E)
(E)
(E)
(E)
ELECTRICAL PLAN NOTES:
CONNECT TO EXISTING PANEL FEEDING RTU(S) PROVIDE NEW 45A BREAKER AND 3#6, +GND IN EXISTING CONDUIT.NEW CIRCUIT BREAKER SHALL MATCH EXISTING CONDITIONS. COORDINATE CONDUIT ROUTING WITH MECH CONTRACTOR.
PROVIDE NEW DUCT DETECTORS ON RETURN SIDE AS SHOWN ON MECHANICAL DRAWING. CONNECT TO FIRE ALARM SYSTEM.
VERIFY ELECTRICAL REQUIREMENTS FOR NEW FURNITURE SYSTEM. MODIFY EXISTING FURNITURE FEED LOCATIONS OR PROVIDENEW FEEDS TO MEET REQUIREMENTS OF NEW SYSTEM. PROVIDE NEW CIRCUITS AS REQUIRED TO EXISTING PANELBOARDS.PROVIDE ALL NECESSARY MODIFICATIONS IN FIELD TO INSTALL SYSTEM, INCLUDING NEW BREAKERS AND WIRING AND CONDUIT.
ADD ALTERNATE; EXHAUST FAN. CONNECT TO EXISTING SPARE BREAKER ON PANEL PB-B.
1
2
3
3
3
3
3
RTU8
RTU7
1
2
2
(E)
2
(E)
RTU5
J(E) 3
CONNECT NEWRECEPTACLES TOEXISTING BRANCHCIRCUIT FEEDINGSIGN-IN AREA.
(E)
(E)
COORDINATE DATAAND SECURITYREQUIREMENTSWITH TREDYFFRIN
SHEET NOTES:
1. ALL SINGLE PHASE BRANCH CIRCUITING SHALL BE 2#12 & 1#12GND - 3/4"C UON. ALL THREE
PHASE BRANCH CIRCUITING SHALL BE 3#12 & 1#12GND - 3/4"C UON. ROUTE ALL BRANCH
CIRCUITS TO PANEL INDICATED IN ROOM UON. REFER TO SINGLE LINE DIAGRAM FOR
ADDITIONAL WIRE SIZES.
2. REFER TO APPROPRIATE TRADE DRAWINGS FOR EXACT LOCATION OF HVAC, PLUMBING, AND
ARCHITECTURAL EQUIPMENT.
3. ALL EXISTING FIRE ALARM AND SECURITY SHALL REMAIN., RELOCATE ANY CEILING DEVICE
WHERE CEILING IS REPLACED. CONNECT NEW DEVICES TO EXISTING FIRE ALARM SYSTEM.
MODIFIY SYSTEM AS REQUIRED TO ACCOMMODATE NEW DEVICES.
EFM-1
4
4
KEY PLAN
PHASE 2
E-2.2
1
SCALE - 1/8" = 1'-0"
ELECTRICAL FLOOR PLAN - POWER - PHASE 2
AS
N
OT
ED
JM
F
DF
0' 4' 16'8'
1. ALL LIGHTING FIXTURES ARE NEW UNLESS NOTED OTHERWISE. COORDINATEEXACT LOCATION OF ALL NEW LIGHTING FIXTURE WITH WITH ARCHITECTURALDRAWINGS. VERIFY ANY QUANTITY DISCREPANCY WITH ARCHITECT AND AEI.
2. COORDINATE PLACEMENT OF WALL SWITCH WITH ARCHITECT DRAWINGSPRIOR TO ROUGH-IN.
3. CONNECT NEW LIGHTING FIXTURES TO EXISTING LIGHTING CIRCUIT FEEDINGAREA.
GENERAL ELECTRICAL
ELECTRICAL PLAN NOTES:
(4)NEW DECORATIVE LED HIG BAY LIGHTING FIXTURES SHALL BE HUBBELL #SAV MH 35 8 22" U N WW. FIXTURESHALL BE MOUNTED AT 18' ABOVE FINISHED FLOOR. PROVIDE DIMMER FOR LIGHTING CONTROL.
NEW RECESSED DOWN LIGHTS SHALL CONNECTED TO EXISTING BRANCH CIRCUIT IN AREA.COORDINATE LOCATION FOR NEW DIMMER SWITCH CONTROLLING LOBBY LIGHTS.
1
2
2
1
1
1
1
a a
aa
aa
a a
2 2
2 2
2 2
2
SDa
E1
E1 E1
E1
E1
E1 E1
E1
KEY PLAN
PHASE 3
E-2.3
1
SCALE - 1/8" = 1'-0"
ELECTRICAL FLOOR PLAN - LIGHTING - PHASE 3
AS
N
OT
ED
JM
F
DF
0' 4' 16'8'