LYNTONVALE AVENUE GATLEY Snagging Report Thursday, 9 January 2020 Prepared For Mr N Jones 142 Issues Identified I Lively CEnv FCIOB MCABE Lively Professional Services Ltd

Upload: others

Post on 06-Aug-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LYNTONVALE AVENUE GATLEY

Snagging Report

Thursday, 9 January 2020

Prepared For Mr N Jones

142 Issues Identified

I Lively CEnv FCIOB MCABELively Professional Services Ltd

Page 2: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 1 16 LYNTONVALE AVENUEAssigned To Identification.Summary

The house was in need of a full clean and the heatingfiring up as the house was extremely cold, this willcause the house to deteriorate during the cold weather.

There is a large amount of shrinkage that needs to beaddressed throughout the house.

All the fire doors throughout the house do not complywith building regulations and need adjusting.

LOCATION 2 FRONT DRIVEAssigned To LandscaperThe left hand garden area needs the rubble removingand the soil lowering to the drive edging.

LOCATION 3 FRONT DRIVEAssigned To LandscaperThe soil needs lowering on the left hand side and thehardcore removing.

09:19 09/01/202009:19 09/01/2020

09:20 09/01/202009:20 09/01/2020

09:21 09/01/202009:21 09/01/2020

Page 2 of 37

Page 3: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 4 FRONT GARDENAssigned To LandscaperThe front garden raised bed needs the hardcoreremoving.

LOCATION 5 FRONT FLAGGED AREAAssigned To GroundworkerThere are several cracked flags that needs replacing.

LOCATION 6 FRONT ELEVATIONAssigned To RendererThe left hand corner render bead needs filling abovethe gully.

LOCATION 7 FRONT ELEVATIONAssigned To BuilderPlease confirm the the ground level is not breaching thedamp proof course where you have not maintained150mm below dpc.

09:22 09/01/202009:22 09/01/2020

09:24 09/01/202009:24 09/01/2020

09:26 09/01/202009:26 09/01/2020

09:27 09/01/202009:27 09/01/2020

Page 3 of 37

Page 4: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 8 FRONT ELEVATIONAssigned To RendererThe nail needs removing from the top of the render.

LOCATION 9 FRONT ELEVATIONAssigned To MasticThe front door threshold needs sealing to prevent wateringress.

LOCATION 10 FRONT ELEVATIONAssigned To Window FitterThe front door side panel cill needs extending to therender, this is due to the door frame being smaller thanthe opening size. The cill also needs an end cap fitting.

LOCATION 11 FRONT ELEVATIONAssigned To MasticThe waste pipe needs sealing properly.

09:29 09/01/202009:29 09/01/2020

09:30 09/01/202009:30 09/01/2020

09:31 09/01/202009:31 09/01/2020

09:34 09/01/202009:34 09/01/2020

Page 4 of 37

Page 5: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 12 FRONT ELEVATIONAssigned To RendererThe render has cracked and needs attention to the leftof the waste pipe.

LOCATION 13 FRONT ELEVATIONAssigned To MasticThe utility door cill needs sealing underneath to preventwater ingress.

LOCATION 14 FRONT ELEVATIONAssigned To RendererThe head over the utility door is not level.

LOCATION 15 FRONT ELEVATIONAssigned To RendererThe wall to the right of the utility door needs patching.

09:34 09/01/202009:34 09/01/2020

09:35 09/01/202009:35 09/01/2020

09:38 09/01/202009:38 09/01/2020

09:38 09/01/202009:38 09/01/2020

Page 5 of 37

Page 6: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 16 RIGHT HAND ELEVATIONAssigned To PlumberThe downspout needs returning to the top of the gull toensure the water goes down it, please check all otherdownspouts as most are like this.

LOCATION 17 RIGHT HAND ELEVATIONAssigned To RendererThe soil pipe needs patching.

LOCATION 18 RIGHT HAND ELEVATIONAssigned To RendererThe wall needs patching to the right of the electric box.

LOCATION 19 RIGHT HAND ELEVATIONAssigned To MasticThe soil pipe needs sealing better.

09:39 09/01/202009:39 09/01/2020

09:41 09/01/202009:41 09/01/2020

09:43 09/01/202009:43 09/01/2020

09:44 09/01/202009:44 09/01/2020

Page 6 of 37

Page 7: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 20 RIGHT HAND ELEVATIONAssigned To MasticThe conduit needs sealing.

LOCATION 21 LEFT HAND ELEVATIONAssigned To RendererSeveral areas along the render bead needs filling.

LOCATION 22 LEFT HAND ELEVATIONAssigned To RendererThe dent in the render needs patching.

LOCATION 23 REAR GARDENAssigned To LandscaperThe excess soil and spoil needs removing to provide aflat garden area.

09:45 09/01/202009:45 09/01/2020

09:47 09/01/202009:47 09/01/2020

09:47 09/01/202009:47 09/01/2020

09:48 09/01/202009:48 09/01/2020

Page 7 of 37

Page 8: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 24 REAR ELEVATIONAssigned To RendererThe right hand corner bead needs filling at the bottom.

LOCATION 25 REAR ELEVATIONAssigned To Window FitterThe rear patio door cill has been cut short and needsreplacing.

LOCATION 26 REAR ELEVATIONAssigned To MasticThe patio door cill needs sealing underneath to preventwater ingress.

LOCATION 27 REAR ELEVATIONAssigned To MasticThe patio door cill needs sealing on the left hand side.

09:49 09/01/202009:49 09/01/2020

09:50 09/01/202009:50 09/01/2020

09:51 09/01/202009:51 09/01/2020

09:52 09/01/202009:52 09/01/2020

Page 8 of 37

Page 9: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 28 REAR ELEVATIONAssigned To RooferThere is water staining from the soffit which wouldsuggest a leak from the roof which needs investigating.

LOCATION 29 REAR ELEVATIONAssigned To RendererThe right hand elevation and rear elevation renderbeads are at different heights and the corner needsfilling with render.

LOCATION 30 HALLAssigned To Door FitterThe cover bead is short and needs replacing to coverthe expanding foam at the bottom of the front doorframe.

LOCATION 31 HALLAssigned To DecoratorThe left hand corner needs caulking to the skirtingboards.

09:53 09/01/202009:53 09/01/2020

09:55 09/01/202009:55 09/01/2020

10:00 09/01/202010:00 09/01/2020

10:02 09/01/202010:02 09/01/2020

Page 9 of 37

Page 10: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 32 HALLAssigned To DecoratorThe wall needs sanding and filling and the skirtingboard needs caulking to the left of the radiator.

LOCATION 33 HALLAssigned To DecoratorThe window cill needs caulking the plaster removingfrom below it and redecorating were it is scratched.

LOCATION 34 HALLAssigned To JoinerThe skirting board to the left of the door is out ofsquare.

LOCATION 35 HALLAssigned To DecoratorThe lounge / kitchen casing needs the plug or fillersanding where the fixings are.

10:03 09/01/202010:03 09/01/2020

10:04 09/01/202010:04 09/01/2020

10:08 09/01/202010:08 09/01/2020

10:09 09/01/202010:09 09/01/2020

Page 10 of 37

Page 11: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 36 HALLAssigned To JoinerThe lounge door handle needs the cover fixing, the oneon it is a privacy lock..

LOCATION 37 HALLAssigned To JoinerThe holes in the door edges throughout the house needfilling were the joiner has fixed his jig.

LOCATION 38 HALLAssigned To DecoratorThe wall needs filling to the right of the lounge door.

LOCATION 39 HALLAssigned To DecoratorThe corner needs caulking above the radiator.

10:10 09/01/202010:10 09/01/2020

10:11 09/01/202010:11 09/01/2020

10:12 09/01/202010:12 09/01/2020

10:13 09/01/202010:13 09/01/2020

Page 11 of 37

Page 12: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 40 HALLAssigned To DecoratorThe radiator pipes need patching and painting.

LOCATION 41 HALLAssigned To DecoratorThe wall behind the radiator needs painting.

LOCATION 42 HALLAssigned To DecoratorThe nail holes need filling in the architrave around thelounge door.

LOCATION 43 HALLAssigned To DecoratorThe study casing needs sanding and the architravesneed filling

10:14 09/01/202010:14 09/01/2020

10:14 09/01/202010:14 09/01/2020

10:16 09/01/202010:16 09/01/2020

10:17 09/01/202010:17 09/01/2020

Page 12 of 37

Page 13: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 44 HALLAssigned To JoinerThe architrave is lipping to the study.

LOCATION 45 HALLAssigned To Decorator/ MasticThe newel needs filling and the flooring needs sealing.

LOCATION 46 LOUNGEAssigned To JoinerThe gap in the fire doors is in excess of 4mm andneeds adjusting to comply with building regulations.

LOCATION 47 LOUNGEAssigned To JoinerThe skirting board has a deflection of over 20mm andneeds rectifying on the left hand wall below the window.

10:18 09/01/202010:18 09/01/2020

10:18 09/01/202010:18 09/01/2020

10:20 09/01/202010:20 09/01/2020

10:23 09/01/202010:23 09/01/2020

Page 13 of 37

Page 14: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 48 LOUNGEAssigned To DecoratorThe plaster needs cleaning of the underside of thewindow cill.

LOCATION 49 LOUNGEAssigned To Window FitterThe left hand window handle is damaged and needsreplacing.

LOCATION 50 LOUNGEAssigned To DecoratorThe filler is cracked and needs replacing to the righthand side of the window cill.

LOCATION 51 LOUNGEAssigned To DecoratorThe radiator pipes need patching and painting.

10:24 09/01/202010:24 09/01/2020

10:25 09/01/202010:25 09/01/2020

10:26 09/01/202010:26 09/01/2020

10:28 09/01/202010:28 09/01/2020

Page 14 of 37

Page 15: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 52 LOUNGEAssigned To MasticThe skirting board and flooring junction needs sealing.

LOCATION 53 LOUNGEAssigned To DecoratorThe top of the skirting board needs caulking behind theradiator..

LOCATION 54 LOUNGEAssigned To JoinerThe skirting board needs replacing were it has beeninfilled.

LOCATION 55 DINING AREAAssigned To Window FitterThe right hand patio door glass needs adjusting in theframe.

10:29 09/01/202010:29 09/01/2020

10:30 09/01/202010:30 09/01/2020

10:31 09/01/202010:31 09/01/2020

10:33 09/01/202010:33 09/01/2020

Page 15 of 37

Page 16: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 56 DINING AREAAssigned To DecoratorThe radiator pipes need patching and painting.

LOCATION 57 DINING AREAAssigned To Floor LayerThe flooring cuts around the study casing are poor andneed attention.

LOCATION 58 DINING AREAAssigned To DecoratorThe casing needs sanding where the fixings are.

LOCATION 59 DINING AREA/ KITCHENAssigned To BuilderThere is a deflection in the floor finish, this is in front ofthe radiator and between the breakfast bar.

10:35 09/01/202010:35 09/01/2020

10:36 09/01/202010:36 09/01/2020

10:37 09/01/202010:37 09/01/2020

10:39 09/01/202010:39 09/01/2020

Page 16 of 37

Page 17: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 60 KITCHENAssigned To Kitchen FitterThe sink base unit needs a shelf fitting.

LOCATION 61 KITCHENAssigned To MasticThe granit worktop needs sealing against the ovenhousing.

LOCATION 62 KITCHENAssigned To DecoratorThe wall needs filling above the switch.

LOCATION 63 KITCHENAssigned To Floor LayerThe laminate is poor cut around the utility door casingand the cover strip is short.

10:43 09/01/202010:43 09/01/2020

10:46 09/01/202010:46 09/01/2020

10:47 09/01/202010:47 09/01/2020

10:48 09/01/202010:48 09/01/2020

Page 17 of 37

Page 18: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 64 KITCHENAssigned To JoinerThe skirting board to the left of the utility door is out ofsquare.

LOCATION 65 UTILITYAssigned To DecoratorThe door casing is rough and needs sanding.

LOCATION 66 UTILITYAssigned To JoinerThe fire door margins are in excess of 4mm and needsadjusting to comply with building regulations.

LOCATION 67 UTILITYAssigned To JoinerThe architrave mitre is lipping.

10:51 09/01/202010:51 09/01/2020

10:52 09/01/202010:52 09/01/2020

10:52 09/01/202010:52 09/01/2020

10:53 09/01/202010:53 09/01/2020

Page 18 of 37

Page 19: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 68 UTILITYAssigned To DecoratorThe water pipe needs patching underneath theworktop.

LOCATION 69 UTILITYAssigned To Kitchen FitterPlinths need fitting to both sides of the base unit.

LOCATION 70 UTILITYAssigned To Decorator/ Floor TilerThe wall around the pipe needs patching and the floorgrouting below it.

LOCATION 71 UTILITYAssigned To DecoratorThe wall needs filling to the right of the door.

10:54 09/01/202010:54 09/01/2020

10:55 09/01/202010:55 09/01/2020

10:55 09/01/202010:55 09/01/2020

10:57 09/01/202010:57 09/01/2020

Page 19 of 37

Page 20: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 72 UTILITYAssigned To JoinerThe skirting board is short and needs replacing belowthe door hinges.

LOCATION 73 UTILITYAssigned To DecoratorThe wall around the switch needs filling.

LOCATION 74 DOWNSTAIRS CLOAKSAssigned To JoinerThe fire door margins are in excess of 4mm and needsadjusting to comply with building regulations.

LOCATION 75 DOWNSTAIRS CLOAKSAssigned To Floor TilerThe floor tiles need grouting.

10:58 09/01/202010:58 09/01/2020

10:59 09/01/202010:59 09/01/2020

10:59 09/01/202010:59 09/01/2020

11:00 09/01/202011:00 09/01/2020

Page 20 of 37

Page 21: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 76 DOWNSTAIRS CLOAKSAssigned To DecoratorThe casing needs sanding and redecorating.

LOCATION 77 CYLINDER CUPBOARDAssigned To PlumberThe pipe needs fire sealing.

LOCATION 78 CYLINDER CUPBOARDAssigned To PlumberThe hole for the pipes in the ceiling need fire sealing orcollars.

LOCATION 79 CYLINDER CUPBOARDAssigned To DecoratorThe wall needs filling around the pipe.

11:01 09/01/202011:01 09/01/2020

11:02 09/01/202011:02 09/01/2020

11:03 09/01/202011:03 09/01/2020

11:04 09/01/202011:04 09/01/2020

Page 21 of 37

Page 22: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 80 CYLINDER CUPBOARDAssigned To MasticThe ceiling needs sealing with intumescent sealantaround the edges.

LOCATION 81 DOWNSTAIRS CLOAKSAssigned To MasticThe edges of the sink need sealing.

LOCATION 82 DOWNSTAIRS CLOAKS/ UTILITYAssigned To MasticThe skirting boards and tiles need sealing.

LOCATION 83 DOWNSTAIRS CLOAKSAssigned To ElectricianThe blanks need fitting in the consumer unit as a matterof urgency.

11:04 09/01/202011:04 09/01/2020

11:05 09/01/202011:05 09/01/2020

11:07 09/01/202011:07 09/01/2020

11:08 09/01/202011:08 09/01/2020

Page 22 of 37

Page 23: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 84 DOWNSTAIRS CLOAKSAssigned To DecoratorThe architraves need caulking.

LOCATION 85 DOWNSTAIRS CLOAKSAssigned To DecoratorThe casing needs sanding and filling were the fixingsare.

LOCATION 86 STUDYAssigned To BuilderThe floor is out of level and shows on the bottom of thedoor.

LOCATION 87 STUDYAssigned To DecoratorThe kitchen door casing needs sanding and filling..

11:09 09/01/202011:09 09/01/2020

11:10 09/01/202011:10 09/01/2020

11:13 09/01/202011:13 09/01/2020

11:14 09/01/202011:14 09/01/2020

Page 23 of 37

Page 24: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 88 STUDYAssigned To JoinerThe fire door margins are in excess of 4mm and needsadjusting to comply with building regulations to bothdoors.

LOCATION 89 STUDYAssigned To DecoratorThe architrave is split and needs filling to the kitchendoor..

LOCATION 90 STUDYAssigned To DecoratorAll skirting board corners need caulking.

LOCATION 91 STUDYAssigned To DecoratorThe window board needs caulking and repaintingwhere it is scratched.

11:14 09/01/202011:14 09/01/2020

11:15 09/01/202011:15 09/01/2020

11:16 09/01/202011:16 09/01/2020

11:17 09/01/202011:17 09/01/2020

Page 24 of 37

Page 25: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 92 STUDYAssigned To Plastic SurgeonThe left hand sash frame is damaged where materialshave been brought in.

LOCATION 93 STUDYAssigned To DecoratorThe wall needs filling around the socket.

LOCATION 94 STUDYAssigned To DecoratorThe radiator pipes need patching and painting.

LOCATION 95 STAIRS TO FIRST FLOORAssigned To DecoratorThe quadrant over the right hand string needs caulking.

11:18 09/01/202011:18 09/01/2020

11:19 09/01/202011:19 09/01/2020

11:20 09/01/202011:20 09/01/2020

11:21 09/01/202011:21 09/01/2020

Page 25 of 37

Page 26: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 96 STAIRS TO FIRST FLOORAssigned To DecoratorThe cover bead needs caulking on the string.

LOCATION 97 LANDINGAssigned To DecoratorThe half newel needs caulking.

LOCATION 98 LANDINGAssigned To DecoratorBedroom 3 architrave needs caulking.

LOCATION 99 LANDINGAssigned To DecoratorThe ceiling needs filling above bedroom 4 door andfurther along the wall.

11:23 09/01/202011:23 09/01/2020

11:24 09/01/202011:24 09/01/2020

11:25 09/01/202011:25 09/01/2020

11:26 09/01/202011:26 09/01/2020

Page 26 of 37

Page 27: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 100 LANDINGAssigned To JoinerThe handrail is poorly fitted to the top newel.

LOCATION 101 BEDROOM 2Assigned To DecoratorThe casing needs sanding and filling were the fixingsare.

LOCATION 102 BEDROOM 2Assigned To Window FitterThe left hand window handle is damaged.

LOCATION 103 BEDROOM 2Assigned To DecoratorThe window cill is damaged and needs filling.

11:28 09/01/202011:28 09/01/2020

11:29 09/01/202011:29 09/01/2020

11:30 09/01/202011:30 09/01/2020

11:31 09/01/202011:31 09/01/2020

Page 27 of 37

Page 28: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 104 BEDROOM 2Assigned To DecoratorThe radiator pipes need painting and the skirting boardneeds caulking behind the radiator.

LOCATION 105 BEDROOM 3Assigned To JoinerThe fire door margins are in excess of 4mm and needsadjusting to comply with building regulations.

LOCATION 106 BEDROOM 3Assigned To DecoratorThe radiator pipes need painting and the skirting boardneeds caulking behind the radiator.

LOCATION 107 BEDROOM 3Assigned To DecoratorThe window frame needs caulking.

11:32 09/01/202011:32 09/01/2020

11:34 09/01/202011:34 09/01/2020

11:34 09/01/202011:34 09/01/2020

11:36 09/01/202011:36 09/01/2020

Page 28 of 37

Page 29: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 108 BEDROOM 4Assigned To DecoratorThe casing needs filling were it is split and sandingwere the fixings are.

LOCATION 109 BEDROOM 4Assigned To DecoratorThe casing needs filling.

LOCATION 110 BEDROOM 4Assigned To JoinerThe fire door margins are in excess of 4mm and needsadjusting to comply with building regulations.

LOCATION 111 BEDROOM 4Assigned To DecoratorThe glue needs cleaning off the architrave and it needsfilling and caulking.

11:36 09/01/202011:36 09/01/2020

11:37 09/01/202011:37 09/01/2020

11:38 09/01/202011:38 09/01/2020

11:39 09/01/202011:39 09/01/2020

Page 29 of 37

Page 30: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 112 BEDROOM 4Assigned To DecoratorAll skirting board corners need caulking.

LOCATION 113 BEDROOM 4Assigned To DecoratorThe radiator pipes need painting.

LOCATION 114 BEDROOM 4Assigned To DecoratorThe window frame and cill needs caulking.

LOCATION 115 BEDROOM 4Assigned To DecoratorThe window cill needs the plaster removing fromunderneath and filling in several places.

11:40 09/01/202011:40 09/01/2020

11:41 09/01/202011:41 09/01/2020

11:42 09/01/202011:42 09/01/2020

11:43 09/01/202011:43 09/01/2020

Page 30 of 37

Page 31: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 116 BEDROOM 1Assigned To DecoratorThe casing needs sanding in several places and werethe fixings are.

LOCATION 117 BEDROOM 1Assigned To JoinerThe fire door margins are in excess of 4mm and needsadjusting to comply with building regulations.

LOCATION 118 BEDROOM 1Assigned To DecoratorThe radiator pipes need painting and the skirting boardneeds caulking behind the radiator.

LOCATION 119 BEDROOM 1Assigned To DecoratorThe window frame needs caulking.

11:44 09/01/202011:44 09/01/2020

11:46 09/01/202011:46 09/01/2020

11:46 09/01/202011:46 09/01/2020

11:47 09/01/202011:47 09/01/2020

Page 31 of 37

Page 32: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 120 BEDROOM 1Assigned To DecoratorAll skirting board corners need caulking.

LOCATION 121 EN SUITEAssigned To DecoratorThe casing needs filling were it is split and re fillingaround the keeper where it has been poorly filled.

LOCATION 122 EN SUITEAssigned To JoinerThe fire door margins are in excess of 4mm and needsadjusting to comply with building regulations.

LOCATION 123 EN SUITEAssigned To JoinerNo privacy lock has been fitted.

11:48 09/01/202011:48 09/01/2020

11:49 09/01/202011:49 09/01/2020

11:50 09/01/202011:50 09/01/2020

11:51 09/01/202011:51 09/01/2020

Page 32 of 37

Page 33: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 124 EN SUITEAssigned To Wall Tiler / MasticThere are a number of wall tiles that are lipping and thearchitrave needs sealing.

LOCATION 125 EN SUITEAssigned To Floor LayerThe tiles and carpet need a cover strip fitting.

LOCATION 126 EN SUITEAssigned To PlumberThe shower control needs sealing.

LOCATION 127 EN SUITEAssigned To MasticThe shower tray needs re sealing.

11:52 09/01/202011:52 09/01/2020

11:53 09/01/202011:53 09/01/2020

11:54 09/01/202011:54 09/01/2020

11:55 09/01/202011:55 09/01/2020

Page 33 of 37

Page 34: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 128 EN SUITEAssigned To Wall Tiller/ DecoratorThe wall needs grouting behind the radiator pipeshrouds and the pipes need painting.

LOCATION 129 EN SUITEAssigned To Wall TillerThe wall needs grouting around the pipe in the vanityunit.

LOCATION 130 EN SUITEAssigned To DecoratorThe ceiling needs touching up.

LOCATION 131 BEDROOM 1Assigned To DecoratorThe wall needs filling above the en suite door.

11:56 09/01/202011:56 09/01/2020

11:58 09/01/202011:58 09/01/2020

11:59 09/01/202011:59 09/01/2020

12:00 09/01/202012:00 09/01/2020

Page 34 of 37

Page 35: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 132 BEDROOM 1Assigned To DecoratorThe wall and ceiling need filling.

LOCATION 133 BATHROOMAssigned To Floor LayerThe tiles and carpet need a cover strip.

LOCATION 134 BATHROOMAssigned To JoinerThe fire door margins are in excess of 4mm and needsadjusting to comply with building regulations.

LOCATION 135 BATHROOMAssigned To Wall Tiller/ DecoratorThe tile needs grouting behind the shroud and theradiator pipes need painting.

12:01 09/01/202012:01 09/01/2020

12:01 09/01/202012:01 09/01/2020

12:02 09/01/202012:02 09/01/2020

12:03 09/01/202012:03 09/01/2020

Page 35 of 37

Page 36: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 136 BATHROOMAssigned To Wall Tiller/ MasticThe floor tile needs grouting and the floor to wall tilesand architraves needs sealing

LOCATION 137 BATHROOMAssigned To DecoratorThe ceiling line needs touching up.

LOCATION 138 BATHROOMAssigned To Wall TillerThe tiles and tile trim need grouting to the front of thebath.

LOCATION 139 BATHROOMAssigned To MasticThe end of the bath needs sealing.

12:04 09/01/202012:04 09/01/2020

12:05 09/01/202012:05 09/01/2020

12:06 09/01/202012:06 09/01/2020

12:07 09/01/202012:07 09/01/2020

Page 36 of 37

Page 37: I Lively CEnv FCIOB MCABE Lively Professional Services Ltd...The house was in need of a full clean and the heating firing up as the house was extremely cold, this will cause the house

LOCATION 140 BATHROOMAssigned To Wall TillerThe wall needs grouting around the pipe in the vanityunit.

LOCATION 141 BATHROOMAssigned To PlumberThe shower tray is holding water which suggest alevelling issue with the tray or the tray casting is faulty.

LOCATION 142 LOFTAssigned To ElectricianThe cover needs fitting to the batteries.