i-nx-q air cooled, 4 pipe chillers - low noise version
TRANSCRIPT
i-NX-Q Air Cooled, 4 Pipe Chillers - Low Noise version(45-139kW) Heat Pump - Three Phase
Climaveneta’s range of small to medium sized i-NX-Q chillers are designed to produce chilled and hot water simultaneously and efficiently using variable frequency drive compressors. The super low noise variant offers up to a 7dB(A) reduction against the baseline model.
Key Features:Simultaneous production of chilled water and hot water
Two inverter scroll compressors
Wide operating range
ErP 2021 compliant
Available with EC fans
Available with factory installed pumps
les.mitsubishielectric.co.uk
The unit combines two variable speed scroll compressorsin two separate refrigerant circuits. The full inverter solutionapplied on two separate refrigerant circuits ensures maximumreliability and total versatility, matching the thermal load requestconstantly and with maximum precision, while minimising energy consumption.
Effective as of September 2019015015
UNITED KINGDOM Mitsubishi Electric Europe Living Environmental Systems Division, Travellers Lane, Hatfield, Hertfordshire, AL10 8XB, England. Telephone: 01707 282880 Fax: 01707 278881IRELAND Mitsubishi Electric Europe, Westgate Business Park, Ballymount, Dublin 24, Ireland. Telephone: (01) 419 8800 Fax: (01) 419 8890 International code: (003531)
Country of origin: United Kingdom - Japan - Thailand - Malaysia. ©Mitsubishi Electric Europe 2019. Mitsubishi and Mitsubishi Electric are trademarks of Mitsubishi Electric Europe B.V. The company reserves the right to make any variation in technical specification to the equipment described, or to withdraw or replace products without prior notification or public announcement. Mitsubishi Electric is constantly developing and improving its products. All descriptions, illustrations, drawings and specifications in this publication present only general particulars and shall not form part of any contract. All goods are supplied subject to the Company’s General Conditions of Sale, a copy of which is available on request. Third-party product and brand names may be trademarks or registered trademarks of their respective owners.
Note: The fuse rating is for guidance only. Please refer to the relevant databook for detailed specification. It is the responsibility of a qualified electrician/electrical engineer to select the correct cable size and fuse rating based on current regulation and site specific conditions. Mitsubishi Electric’s air conditioning equipment and heat pump systems contain a fluorinated greenhouse gas, R410A (GWP:2088), R32 (GWP:675), R407C (GWP:1774) or R134a (GWP:1430). *These GWP values are based on Regulation (EU) No 517/2014 from IPCC 4th edition. In case of Regulation (EU) No.626/2011 from IPCC 3rd edition, these are as follows. R410A (GWP:1975), R32 (GWP:550), R407C (GWP:1650) or R134a (GWP:1300).
@meuk_les Mitsubishi Electric LivingEnvironmental Systems UK mitsubishielectric2 thehub.mitsubishielectric.co.uk@green_gateway greengateway.mitsubishielectric.co.uk
Telephone: 01707 282880email: [email protected]: les.mitsubishielectric.co.uk / microsite: mechillers.co.uk
MODEL
V/ph/Hz
kWkWkW/kW
kWkWkW/kW
kWkWkWkW/kW
kW-%
Kw-%-
l/skPa
l/skPa
N°N°kgkg
dB(A)dB(A)
mmmmmmkg
i-NX-Q SL 0402Pi-NX-Q SL 0352Pi-NX-Q SL 0302Pi-NX-Q SL 0262P i-NX-Q SL 0552Pi-NX-Q SL 0502Pi-NX-Q SL 0252Pi-NX-Q SL 0202Pi-NX-Q SL 0182Pi-NX-Q SL 0152P
i-NX-Q SL Air Cooled, 4 Pipe Chiller - Low Noise Version (45-139kW) Heat Pump - Three Phase
POWER SUPPLY PERFORMANCE COOLING ONLY (EN14511 VALUE)COOLING CAPACITY *1 *2
TOTAL POWER INPUT *1 *2
EER *1 *2
HEATING ONLY (EN14511 VALUE)TOTAL HEATING CAPACITY *2 *3
TOTAL POWER INPUT *2 *3
COP *2 *3
COOLING WITH TOTAL HEAT RECOVERYCOOLING CAPACITY *4
TOTAL POWER INPUT *4
RECOVERY HEAT EXCHANGER CAPACITY *4
TER SEASONAL COOLING EFFICIENCYP RATED CAPACITY *5
SEER *5 *6
PERFORMANCE ŋs *5 *7
SEASONAL HEATING EFFICIENCY *8
RATED HEAT OUTPUT AT T DESIGN H *9 *10
SCOP *9 *10
SEASONAL SPACE HEATING ENERGY EFFICIENCY *9 *10
SEASONAL SPACE HEATING ENERGY EFFICIENCY CLASS *9 *10
HEAT EXCHANGERS HEAT EXCHANGER USER SIDE IN COOLINGWATER FLOW RATE *1
PRESSURE DROP *1
HEAT EXCHANGER USER SIDE IN HEATINGWATER FLOW RATE *3
PRESSURE DROP *3
REFRIGERANT CIRCUITCOMPRESSORSNO. CIRCUITSREFRIGERANT CHARGE R410AOIL CHARGE NOISE LEVELSOUND PRESSURE *11
SOUND POWER LEVEL *12 *13
SIZE AND WEIGHTWIDTH (A) *14
DEPTH (B) *14
HEIGHT (H) *14
OPERATING WEIGHT *14
400/3+N/50
45.614.123.23
51.215.193.37
46.1413.7859.17.62
45.64.41174
37.03.93154A++
2.1826.1
2.4733.2
2226.74.6
4779
262513502070960
400/3+N/50
52.317.263.03
59.017.823.31
53.0616.5268.67.37
52.34.43174
43.03.97156A++
2.5134.4
2.8444
2227.34.6
4779
262513502070960
400/3+N/50
56.318.73.01
62.518.383.4
57.7517.2574.07.61
56.34.5177
45.03.98156A++
2.722.4
3.0127.9
2227.84.6
4880
262513502070990
400/3+N/50
105.037.372.81
114.234.093.35
109.433.52140.97.47
105.04.34170
79.04.01158-
5.0334.8
5.541.6
2245.813.4
5183
3250135020701440
400/3+N/50
89.530.862.9
98.128.433.45
94.5927.75120.77.77
89.54.33170
74.04.09161-
4.2927.0
4.7232.7
2240.613.4
5082
3250135020701330
400/3+N/50
138.449.782.78
153.245.333.38
145.544.93187.77.42
138.44.45175
115.04.13162-
6.6335.0
7.3843.3
2260.013.4
5587
4500135020701660
400/3+N/50
119.944.082.72
132.439.43.36
126.439.5163.67.34 119.94.4173 97.04.11161-
5.7535.3
6.3843.4
2253.413.4
5385
3875135020701520
400/3+N/50
84.0 29.272.87
93.127.633.37
84.6526.96110.07.21
84.04.25167
70.04.04159A++
4.0333.2
4.4841.1
2243.87.2
5082
3250135020701210
400/3+N/50
70.925.972.73
78.523.223.38
75.0922.9596.77.47
70.94.22166
59.03.97156A++
3.423.7
3.7829.3
2231.27.2
4981
2625135020701080
400/3+N/50
62.922.712.77
70.721.493.29
65.2220.4284.47.33
62.94.39173
52.04.0157A++
3.0127.9
3.435.6
2229.24.6
4981
262513502070990
Eurovent Certified Data
*1 Plant (side) cooling heat exchanger water (in/out) 12.0°C/7.0°C; Source (side) heat exchanger air (in) 35.0°C. *2 Values in compliance with EN14511. *3 Plant (side) heating heat exchanger water (in/out) 40.0°C/45.0°C; Source (side) heat exchanger air (in) 7.0°C at 87% R.H. *4 Plant (side) cooling heat exchanger water (in/out) 12.0°C/7.0°C; Plant (side) heating heat exchanger water (in/out) 40.0°C/45.0°C. *5 Parameter calculated according to [Regulation (EU) N. 2016/2281]. *6 Seasonal energy efficiency ratio. *7 Seasonal space cooling energy efficiency. *8 Weather conditions average, bivalent temperature -7.0°C. *9 Seasonal space heating energy efficiency class LOW TEMPERATURE [REGULATION (EU) N. 813/2013]. *10 Calculated with variableflow rate and variable temperature. *11 Average sound pressure level at 10m distance, unit in a free field on a reflective surface; non-binding value calcuated from the sound power level. *12 Sound power on the basis of measurements madein compliance with ISO 9614. *13 Sound power level in cooling and heating, outdoors. *14 Unit in standard configuration/execution, without optional accessories.