iallai ii -- e sese - · pdf file1 - 4 iallai ii-- e sese solid base sump fibrelite double...

4
1 - 4 INSTALLATION INSTRUCTIONS EL-G-E500 Encore Dispenser SOLID BASE SUMP FIBRELITE DOUBLE SIDED ENTRY BOOT (SUPPLIED SEPARATELY) 40FC SEALANT (x4) CORBEL ANCHOR BOLTS (x4) DISPENSER SUMP SUPPORT FRAME CONCRETE TIE RODS x 6 SHEAR VALVE SUPPORT RAIL (SEE SHEAR VALVE ARRANGEMENT BELOW) DISPENSER SIDE RAILS (x2) SPREADER PLATE (x2) MPK10-KIT (SUPPLIED SEPARATELY) CHANNEL SPRING NUT (4 PER RAIL) 229 229 238 122 Shear Valve Arrangement in Plan WHERE 4 SHEAR VALVE RAILS ARE USED IT WILL BE NECESSARY TO USE 2 Nº EL/G/500/SVR/C SHEAR VALVE RAILS. STANDARD SHEAR VALVE RAIL Issue: 12/06/2016

Upload: hadung

Post on 06-Mar-2018

226 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: IALLAI II -- e sese - · PDF file1 - 4 iallai ii-- e sese solid base sump fibrelite double sided entry boot (supplied separately) 40fc sealant (x4) corbel anchor bolts (x4) dispenser

1 - 4

INSTALLATION INSTRUCTIONSEL-G-E500 Encore Dispenser

SOLID BASE SUMP

FIBRELITE DOUBLE SIDED ENTRY BOOT(SUPPLIED SEPARATELY)40FC SEALANT (x4)

CORBEL

ANCHOR BOLTS (x4)

DISPENSER SUMP SUPPORT FRAME

CONCRETE TIE RODS x 6

SHEAR VALVE SUPPORT RAIL(SEE SHEAR VALVE ARRANGEMENT BELOW)

DISPENSER SIDE RAILS (x2)

SPREADER PLATE(x2)

MPK10-KIT (SUPPLIED SEPARATELY)

CHANNEL SPRING NUT (4 PER RAIL)

229 229238122

Shear Valve Arrangement in Plan

WHERE 4 SHEAR VALVE RAILS ARE USED IT WILL BE NECESSARY TO USE 2 NºEL/G/500/SVR/C SHEAR VALVE RAILS.

STANDARDSHEAR VALVERAIL

Issue: 12/06/2016

Page 2: IALLAI II -- e sese - · PDF file1 - 4 iallai ii-- e sese solid base sump fibrelite double sided entry boot (supplied separately) 40fc sealant (x4) corbel anchor bolts (x4) dispenser

2 - 4

INSTALLATION INSTRUCTIONSEL-G-E500 Encore Dispenser

5

6

2

Dispenser top has been supplied preassembled with metalwork.

For PSB 50 to 110, PSBD 50 to 110 and PDBD pipe entry kit models a 150mm hole should be drilled.Mark up hole positions as illustrated.

If sump is trimmed to minimum height centre point of hole is 110mm from base internally.NB: Hole size drilled is Ø150mm. OD of flange is Ø190mm

Dry fit the corbel on top of the sump to check level and prepare a adequate support base.NB:- Sump should be embedded into the support base when installed.

Sump can be trimmed to reduce the height of the system by up to 255mm , if 150mm holes will be drilled for pipe entry kits.If larger holes will be drilled please contact Fibrelite for maximum trim point.

Mark trim point around the sump. Check position of pipe entry sealkits before trimming with a circular saw.Refer to 5 and 6 for pipework positions with and without trimming.

Island Level

HaunchingPermitted

525

INS

IDE

1300 x 1000

300

INS

IDE

825

MA

X.

110

OD Flange Ring 190mm

100

DETAIL OF DOUBLE SIDED ENTRY BOOT

OUTSIDE INSIDE

3

1

4

281

281

255

300

581 Min.

Page 3: IALLAI II -- e sese - · PDF file1 - 4 iallai ii-- e sese solid base sump fibrelite double sided entry boot (supplied separately) 40fc sealant (x4) corbel anchor bolts (x4) dispenser

3 - 4

INSTALLATION INSTRUCTIONSEL-G-E500 Encore Dispenser

ACETONE

8

Abrade internal groove of corbel and top edge of the sump (inside & outside) with sandpaper. Degrease with acetone.

9

Apply a bead of sealant to the top of the sump flange. If this has been removed during trimming, apply sealant inside the groove of the corbel. Position the corbel onto the sump and push down firmly.

Apply sealant to BOTH the internal and external joint between the sump and corbel. Smooth off and press into the joint with soapy water to remove trapped air.Allow 12hours for the sealant to set.

Optional vacuum water or hydrostatic test.Ensure pipework is capped off below the upward riser. Tighten clips on pipe entry sealkits against the pipe. Tighten nuts on upper support frame metalwork. Vacuum test at 0.6m depth setting only.

11

10

OPTIONAL HYDROSTATIC TEST

7

12

Complete pipework and secure to shear valve rails with the MPK-10 mounting kit. Refer to the shear valve arrangement plan detail on page 1.

Run pipework through side wall, connect to upward riser. Cap off pipework to allow vacuum testing in Stage 8.

Page 4: IALLAI II -- e sese - · PDF file1 - 4 iallai ii-- e sese solid base sump fibrelite double sided entry boot (supplied separately) 40fc sealant (x4) corbel anchor bolts (x4) dispenser

4 - 4

INSTALLATION INSTRUCTIONSEL-G-E500 Encore Dispenser

500“A”

5-10 300

Minimum200Maximum350

16

Remove upper nut & washer on the 4 anchor boltsInstall & connect the dispenser to the sump frame & anchor bolt. Fit & tighten nut & washer.

14

15

Backfill around the sump equally in levels to prevent uneven load against the sump wall.

Concrete island depth fixed as per architect drawing.Allow concrete to cure

VERY IMPORTANTOUTER EDGE “A” OF FRAME SET 5-10mm ABOVE GENERAL GRADE AREA WITH CONCRETE RAMPED AWAY OVER 300mm

x 4

NUT

DISPENSER

WASHER

SUMP FRAME

Run conduit through the locator holes in the dispenser top framework.

13