ice-e info pack 1 refrigerant cycles
TRANSCRIPT
-
8/13/2019 ICE-E Info Pack 1 Refrigerant Cycles
1/4
Refrigerant cycles
In the e-learning section of theICE-E web site, the reader canachieve basic knowledge aboutthe refrigeration cycles. Thechoice of the most suitablecycle, in terms of energyconsumption reduction must besupported by severalconsiderations dealing bothwith thermodynamic andtechnological aspects. In thepresent Info Pack, fundamentalconsiderations aboutthermodynamics arepresented, aiming athighlighting the consequenceson cycle energetic efficiency.
Regarding technological aspects, the reader
may refer to Refrigerants, Operation and
choice of compressors, Heat exchangers,
Expansion device Info Packs.
Back to basicsThe purpose of a refrigeration system is to
transfer thermal energy from a low-
temperature source to a high-temperature
sink. From an energetic point of view, the goal
should be hit utilizing the least amount of
work, i.e. to maximize the Coefficient of
Performance (COP) for a given cooling
capacity and for fixed source and sink
temperatures. More thermodynamically
oriented reader could, alternatively, restate the
goal in terms of entropy: the purpose of a
refrigerating system is to transfer entropy from
a low-temperature source to a high-
temperature sink while generating the least
amount of entropy, or stated in another way
the goal is to generate the least amount of
entropy for a given cooling capacity for fixed
source and sink temperatures.
It is well known that the ideal cycle for
achieving this goal (when both the source and
the sink are isothermal) is the Carnot
Fundamental
considerations
about the
thermodynamics
of inverse cycles
can help ineconomic and
technological
choices for
refrigeration
systems
ICE-EINFORMATIONPACK
Figure 1 - Carnot cycle and ideal vapor compressionrefrigeration cycle
-
8/13/2019 ICE-E Info Pack 1 Refrigerant Cycles
2/4
refrigeration cycle, whose work is depicted by
the area a-b-c-d in figure 1 and whose
cooling capacity is given by the area 1-4-f-g
for figure 1 (taken from Cavallini et al, 2010) .
It is also well known that increasing TLand/or
decreasing T0increases the cycle efficiency.
The Carnot refrigeration cycle, however,
cannot be realized via practical hardware.
Therefore, the widely used reference cycle in
practice is based on the so-called ideal vapor
compression refrigeration cycle. The cycle
shown in figure 1 contains two irreversibilities:
(1) isenthalpic expansion ( exp) and
(2) superheating of the compressor discharge
vapor ( sup) to realize a constant-pressureheat rejection process in the condenser.
In practice, real vapor compression
refrigeration cycles include other
irreversibilities, principally among them are:
(3) non-isentropic adiabatic compression,
(4) non-isobaric heat rejection and
(5) non-isobaric heat addition.
Though not shown in the figure, two other
common modifications to the cycles are
superheating of the refrigerant at theevaporator outlet and subcooling of the
refrigerant at the condenser outlet. Finally,
external to the cycle itself, there are large
irreversibilities associated with the heat
transfers to and from the source and sink due
to the finite temperature differences between
the refrigerant and the external heat transfer
media.
All the design strategies of a refrigeration
system (included two-stage
compression/throttling, as depicted in figures2, 3) are intended for reducing the above
mentioned (1) and (2) irreversibilities.
Accordingly, a detailed analysis of the ideal
vapor compression refrigeration cycle, as
depicted in figure 1, gives cue on how to
reduce energy consumption for any kind of
vapour compression refrigeration cycle.
Evaluating cycle performanceThe most common method for evaluating the
overall thermodynamic performance of thesecycles is based on a First Law of
Thermodynamics approach, namely,
comparing the Coefficient of Performance
Figure 2. Two stage compression withintercooler, single throttling vapourcompression cycle (and related T,sdiagram, below).
Figure 3. Two stage compression withOFT, double throttling vapour compressioncycle (and related T,s diagram, below).
All the design
strategies of a
vapourcompression
refrigeration
system, are
intended for
reducing the
irreversibilities
linked to
throttling,compression and
heat transfer.
ICE-E INFO PACK
-
8/13/2019 ICE-E Info Pack 1 Refrigerant Cycles
3/4
(COP) and the Volumetric Cooling Capacity
(VCC). For a given cooling capacity, VCC
gives an indication about the compressor size
to achieve the specified cooling capacity.
The COP is the ratio of the energy
(refrigeration effect) extracted from the low
temperature source (if h is the specific
enthalpy of the refrigerant, qL=h1h4is the
energy extracted or the so called refrigeration
effect, referring to figure 1) and the input work
(wcomp=h2-h1). The volumetric cooling capacity
VCC is the energy extracted from the low
temperature source per unit of refrigerant
volume processed by the compressor.
One limitation to this approach is that the COP
is a function of the operating conditions (thehigh-side and low-side temperatures). For
example, is a COP of 5 better than a COP of
10? The short answer is: it depends.
To overcome the mentioned limitation one
should compare the COP and the Carnots
cycle COPC(and this can be considered a
Second law of Thermodynamics approach):
= COP/COPC
Another way to consider and quantify the
irreversibilities is to choose an external
reference temperature T0(e.g., as the
temperature of the ambient) which can be
used to calculate the exergy losses. For the
example of figure 1, the external reference
temperature has to be chosen as the
temperature of the external cooling medium
(e.g., air) for the condenser. Once this is done,
the specific exergy losses can be calculated
for the four basic processes for the vapor
compression refrigeration cycle. They are
represented by the hatched areas in figure 1
(ideal reference cycle.
It is worth noting that for the ideal vapor
compression refrigeration cycle in figure 1 the
condenser exergy loss reduces to the
superheating loss ( sup), defined by the area e-
b-2, while compression and evaporation are
no-loss processes.
The magnitudes of the exergy losses for non-
isobaric, non-ideal heat transfer processes
and non-isoentropic compression (i.e.
irreversibilities (3), (4), (5), mentioned above)
described above are determined by
component and system designs, and by the
refrigerant. For example, the refrigerant
circuitry in the heat exchangers, the type of
compressor used and its design, and the
system configuration all will influence several
of the exergy losses.
Performance potential: ammonia
as an example
In the following, we consider a largely used
(old) refrigerant in refrigeration applications:
ammonia. We consider an evaporation
temperature TL= -40C, while the
condensation is T0= 40. With reference to the
set temperatures, the Carnot cycle COPCis
2.91.
We consider no condenser subcooling or
compressor superheat, and a compressorisentropic efficiency of 1. When the single
stage compressionsingle throttling is
considered, = 0.703.
Keeping fixed TLand T0, we want now to
consider the possibility of installing a two-
stage compressor, again ideally with
isoentropic behavior (figure 2). Furthermore,
an ideal intercooler is installed: i.e. it is
possible to lower the temperature of the
ammonia, after the low stage compressor
discharge (point 5, in figure 2) down to the
sink temperature (40 C), that is a limit
situation achievable theoretically only in an
heat exchanger with infinite heat transfer area
and in perfect counter-current configuration.
The intermediate pressure (i.e. the
intercooling pressure) is set equal to the
square root of the product of condenser an
evaporator saturation pressures.
Single throttling is considered (no condensate
subcooling, no vapour superheating).
In this case superheating losses (see hatchedarea indicating supin figure 1) are reduced,
while throttling losses are the same (see
hatched area indicating exp).
According to previous considerations, we
expect an increase in (or in system COP,
since Carnot cycle COPC, is fixed at 2.91).
It is possible to calculate = 0.730. That is an
increase of less than 4 %, in comparison to
the single stage compression arrangement.
Lets now evaluate the possibility to implement
the system configuration in figure 3, again with
fixed TLand T0and with no condensate
subcooling, no vapour superheating.
ICE-E INFO PACK
Is a COP of 5
better than a
COP of 10? Theshort answer is:
it depends.
-
8/13/2019 ICE-E Info Pack 1 Refrigerant Cycles
4/4
For more information, please contact: Claudio Zilio ([email protected])
Always compare
Carnot cycle
performance andthe performance
of the system
you are going to
evaluate.
You will have
quickly and
easily the first,objective, clear,
indubitable
number for
starting your
following
technological
and economic
evaluation.
In this case, point 5 temperature can be lower
than ambient temperature, since it is not any
more linked to the external heat sink
temperature, as in the case of the intercooler
in figure 2. This should bring about a reductionof ( sup). Furthermore, using two-stage
throttling, reduces the relevant hatched area in
figure 1 ( exp).
Accordingly, increases of about 40 % ( =
0.985). Being lower the refrigerant enthalpy at
the evaporator inlet (h4, in figure 3), also VCC
increases.
Which is the practical outcome of the
proposed thermodynamic consideration?
(Note: as mentioned before, in this info pack
we are not considering technological aspectslike, for example, limitations in compressor
discharge temperature because of
compatibility with lubricants etc. Please
consider the relevant info packs in ICE-E web
site).
From an economicalpoint of view, installing
a two-stage compressor is by far more heavy,
from an investment point of view, than using
two throttling valves or installing an
accumulator (open flash tank).
References
Cavallini A., Zilio C., Brown J.S. (2010).
Sustainability with prospective refrigerants. In:
Proc. of Sustainable Refrigeration and Heat
Pump Technology Conference. Stockholm,
June, 13-16, ISBN: 978-2-913149-81-6
ICE-E INFO PACK
Given this economical consideration, the
thermodynamic results clearly indicate that
using the system schematic in figure 2 will
offer poor chances of recovering the higher
investment funds in short time (indeed, it is arelatively rare system schematic, with
ammonia).
The further limited investment costs because
of one more throttling valve and one tank,
looks more promising in terms of shortening
the pay-back period.
As a concluding remark: the rather simplified
thermodynamic approach here proposed can
be considered a starting point if you are
looking for a new refrigeration system.:
If you are not a specialist in thermodynamics,
please remember of Carnot and ask to your
advisor to compare (it is rather simple, for
him), the coefficient of performance of the
system he is proposing to you (even
considering ideal processes of the refrigerant)
with the efficiency of the Carnots cycle.
You will have the first, objective, clear,
indubitable number for starting your following
technological and economic evaluation.