ice-e info pack 12 free cooling

Upload: lethanhvan186

Post on 04-Jun-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/13/2019 ICE-E Info Pack 12 Free Cooling

    1/3

    Free cooling

    Introduction

    Free cooling can save energy and operating

    expenses in cold stores, where the application of

    traditional cooling systems has resulted in very

    high energy costs. By using free cooling, the

    overall thermal management running

    expenditure is expected to be reduced by about

    20 to 40 % in a number of cases.

    Description

    One solution for free cooling is to create an

    overpressure in the cold store by venting

    ambient air into the cold store. Motorized

    dampers can be used to ensure optimum airflow

    in the cold store and to prevent unwanted

    ambient air from entering the enclosure.

    The free cooling can replace the mechanical

    cooling at times when the source temperature is

    sufficient low.

    Application of the

    technology

    Free cooling can be used in climates where the

    ambient temperature in long periods is lower

    than the requested indoor temperature of the

    cold store or enclosure. Typically free cooling is

    used in produce cold stores.

    Capacity

    The capacity of the system is primarily

    dependent on the air flow and the temperature

    difference between the source (tsource) and the

    Free cooling canprovidesignificantreduction of

    energy forcooling

    There are manymethods toprovide the free

    cooling source

    ICE-EINFORMATIONPACK

    Potato store showing louvers used to draw ambient air intothe store

  • 8/13/2019 ICE-E Info Pack 12 Free Cooling

    2/3

    ICE-E INFO PACK

    requested indoor temperature (tindoor). There

    has to be sufficient temperature difference

    between the two temperatures, else the

    energy used for transportation of the air will beto large compared with the supplied cooling

    energy.

    The cooling capacity of 1000 m3/h air entering

    at 5C and 90% RH is 730 W per degree

    heating.

    The number of hours per month that are below

    5 C and 0 C are show below for a Danish

    climate (labeled with blue colour in the

    figures). In these hours it will be possible touse ambient air for cooling of e.g. vegetables

    which typically are cooled to a temperature

    between 2C and 7C. It can be seen from the

    graphs that the potential is reduced if

    temperatures below 0C are required.

    The different sources can be ambient air, from

    the ground or from water (sea, lake or bore

    hole). Humidity in the air supplied to the cold

    store will generally not be a large problem

    since the air is heated when entering the cold

    store and thereby the relative humidity

    decreases - leaving little risk for condensation.

    Control

    The temperature of the cold store is controlled

    by a sensor inside the cold store. This system

    decides how much the store has to be cooled.

    An outside temperature sensor control

    decides if the free cooling, the refrigeration or

    a mix has to be applied.

    A system using outside air mixed with

    recirculated air can be controlled by the use of

    modulating dampers. Dampers can be used at

    the ductwork both on the outside air intake,

    exhaust air and the recirculated air. In case of

    cool outside air the quantity of outside air is

    increased and the amount of recirculated air is

    reduced to provide the required supply air

    temperature. This results in at certain times of

    the year, and often at night time, that cooling

    by the refrigeration system is avoided.

    An outside temperature sensor is used to

    determine when the outside air is sufficient

    cold and the proportion of the outside air that

    should be supplied. In summer, with high

    outside temperatures, the ventilation should

    be at a minimum to reduce the refrigeration

    load. Therefore the dampers should be as

    airtight as possible to avoid air entering the

    cold store during warm periods.

    The enthalpy, often used for regulation in

    comfort cooling systems, would in principle be

    better to regulate by than the temperatures,

    but in practice this is normally not relevant for

    free cooling of stores.

    Alternatives:

    Alternative sources to

    free cooling with

    ambient air are bore

    hole and ground, sea,

    river or lake water

    Design:

    Estimate the

    annually number of

    hours below the

    design temperatureof the cold store

  • 8/13/2019 ICE-E Info Pack 12 Free Cooling

    3/3

    ICE-E INFO PAC

    The work associated with this information pack has been carried out in accordance with the highest academic standards and reasonable endeavours have been made to achieve the degree of reliability andaccuracy appropriate to work of this kind. However, the ICE-E project does not have control over the use to which the results of this work may be put by the Company and the Company will therefore be deemedto have satisfied itself in every respect as to the suitability and fitness of the work for any particular purpose or application. In no circumstances will the ICE-E project, its servants or agents accept liability however

    caused arisin from an error or inaccurac in an o eration, advice or re ort arisin from this work, nor from an resultin dama e, loss, ex enses or claim. ICE-E 2012

    Installation

    In cases where ambient air is used as the

    source, many systems use a combination ofmechanical and free cooling, where the free

    cooling takes over when the ambient

    temperature is sufficiently low.

    The inlet to the enclosure should be placed in

    a position where there is no obstruction for the

    air flow in the enclosure. It will be a little more

    efficient to place the inlet from the ambient at

    the facade of the building which are

    overshadowed or facing north rather than

    exposed to solar irradiation. The outlet

    (damper) should be placed at a high position

    preferably opposite to the inlet due to better

    temperature efficiency. The temperature

    sensor used for regulating the free cooling

    should be placed at the warmest position in

    the enclosure.

    Alternatives

    As mentioned a number of alternatives to

    traditional free cooling with ambient air exist.

    The source can be cold from the ground

    where the energy is extracted from buried

    pipes, bore holes or from sea or lake water.

    In very cold climates heat from the ground

    might also be used for heating of the cold

    stores to avoid low temperatures in the store.

    If some temperature variation is allowed it may

    be possible to reduce store temperatures

    overnight and to use the thermal capacity of

    the store to maintain temperatures during theday. This is unusual as usually free cooling is

    used for produce stores and tight temperature

    control is required. One option to overcome

    this would be to use a thermal store or phase

    change material to act as a battery for the

    store and to discharge the cooling from the

    store during the day.

    The storage room or enclosure should be

    placed and constructed to minimize heat gains

    from the ambient by use of appropriate

    amount of insulation, reduction of solar gains

    by shading or by use of surfaces with low

    solar absorbance. Use of shading might be

    difficult (expensive) but can be done by having

    shading of e.g. lamellas above a dark roof that

    due to shading will have lower surface

    temperatures and a lower maximum cooling

    need.

    If the ambient temperature is lower than the

    cold storage temperature for long periods

    consideration should be made to construct the

    building envelope with heat pipes or thermo

    siphon which could transport cold from theambient to the enclosure. The heat pipes

    might be integrated in the traditional

    refrigeration system.

    Limitations of system

    The largest limitation will in most cases be the

    climatic conditions which in a number of cases

    will limit the possible application of free

    cooling to short periods.

    In this connection there will often be

    coincidence between low cooling needs and

    low ambient temperatures but in some cases

    there is a cooling need for cooling down of

    warm goods place in the cold store.

    Consideration should also be taken to the

    allowable air velocity. If the system is

    designed with a high air velocity this might

    influence the thermal comfort of workers and

    might have some influence on sensitive goods

    as vegetables or plants.Another restrain might be the temperature

    variation. If the temperature of inlet air is to

    low some goods might be affected. This could

    be solved by mixing and regulation of the

    incoming air to achieve a suitable inlet

    temperature. It could also be solved by

    arrangements and manifolds which distributes

    the inlet air equally.

    For more information, please contact: Lars Reinholdt ([email protected])