ice-e info pack 5 pipe work and system layout
TRANSCRIPT
Pipe work and system layout
There are several factors that
influence the design of piping:
Overall type of refrigeration system
Pressure loss in general
Pressure loss in vertical piping
Oil drainage and return
Circulation rates
Controls
Refrigerant
Many decisions and compromises are made
when designing and dimensioning the pipe
system for a cold store. This information pack
describes some important issues that
influence the energy bill.
In general terms at same load larger pipe
diameters have a lower pressure drop but
higher installation cost (incl. insulation). For
some piping the service dictates the
dimensioning.
Overall type of
distribution system
There are three overall common types of
distributions systems:
- Pump circulated systems: A low
pressure liquid distribution systems
which normally requires a refrigerant
pump to pump the cold refrigerant
from the central refrigeration unit to
the evaporators. This type is typically
utilizing R717 (NH3) as refrigerant
and used in large capacity systems.
- High pressure liquid distribution
systems, where the liquid is led to
the evaporators directly from the
condenser or high pressure receiver.
These are normally direct expansion
systems (DX) and are most
commonly used in smaller cold
stores not utilizing R717.
- Secondary refrigerant systems
where the distribution system is
designed for a media normally based
on water. These systems are
described in a different information
pack.
Generally pump circulated systems are used
when the capacity is high and the pipe work is
large and where many different evaporators
are served by a central refrigeration unit.
Further a separate pipe system for defrosting
can be present based on
Hot gas at discharge pressure
Warm liquid, typically in secondary
systems
Designing pipe
systems for cold stores is a trade between investment and running cost.
ICE-E
INFORMATION PACK
The diagrams show the increase in
energy consumption versus
pressure loss and temperature
change. Further description in the
right column.
0,0%
0,5%
1,0%
1,5%
2,0%
2,5%
3,0%
3,5%
4,0%
-50 -40 -30 -20 -10 0
[kW
h/k
Pa]
Evaporation temperature [° C]
Extra energy consumption caused by pressure loss in suction line
R717
R134a
Motor efficiency : 0,9Isentropic efficiency: 0,7Condensing temperature: 35° CConstant cooling load
0,0%
0,5%
1,0%
1,5%
2,0%
2,5%
3,0%
3,5%
4,0%
-50 -40 -30 -20 -10 0
[kW
h/k
]
Evaporation temperature [° C]
Extra energy consumption caused by decreased evaporation temperature
R717
R134aMotor efficiency : 0,9Isentropic efficiency: 0,7Condensing temperature: 35° CConstant cooling load
0
1.000
2.000
3.000
4.000
5.000
6.000
7.000
8.000
9.000
-50 -40 -30 -20 -10 0
[kW
h/k
/Ye
ar]
Evaporation temperature [° C]
Extra energy consumption caused by decreased evaporation temperature
R717
R134a
Motor efficiency : 0,9Isentropic efficiency: 0,7Condensing temperature: 35° CConstant cooling load of 100 kWOperation period: 5000 h/Year
0,0%
0,5%
1,0%
1,5%
2,0%
2,5%
3,0%
3,5%
4,0%
10 15 20 25 30 35 40 45
[kW
h/k
Pa]
Condensing temperature [° C]
Energy consumption caused by pressure loss on the high pressure side
R717
R134a
Motor efficiency : 0,9Isentropic efficiency: 0,7Evaporation temperature: -20° C
0,0%
0,5%
1,0%
1,5%
2,0%
2,5%
3,0%
3,5%
4,0%
10 15 20 25 30 35 40 45
[kW
h/k
]
Condensing temperature [° C]
Energy consumption caused by increased condensing temperature
R717
R134aMotor efficiency : 0,9Isentropic efficiency: 0,7Evaporation temperature: -20° C
Pressure loss in
general
Transporting a primary or secondary
refrigerant from the refrigeration unit to the
evaporator and back to the unit involves a
pressure loss which can be calculated as:
id
L)(c 0.5 p 2
From the equation it is clear that the pressure
loss is depending on the flow velocity squared,
and proportional to the density, friction losses
and pipe lengths.
The pressure loss has direct and indirect
influence on the energy consumption.
Direct energy consumption.
If the primary or secondary refrigerant is
pumped through the pipes to the evaporator
and back the pump itself require energy which
is often neglected when calculating the energy
consumption of the entire refrigeration system
and COP. The required pump power is
calculated as:
pump
totpump
pqP
The direct pump power can easily make up 10
% of the total energy consumption of the entire
refrigeration system in commercial type
systems.
Indirect energy consumption.
The piping pressure drop courses an indirect
energy consumption in two ways:
Heating by the pump
Lowering the suction pressure of the
compressor
The direct energy consumption of the pump
ends up as heat in the refrigerant which the
refrigeration unit must cool.The shaft power
for open type pumps) and total electrical
consumption for semi hermetic pumps
Depending on the efficiency and the operation
conditions of the refrigeration unit the direct
pump power influence the power consumption
of the refrigeration unit in the following relation:
COP
pumpPrefP
Pressure loss suction side
The refrigeration unit is controlled so that it
can maintain a preset temperature in the cold
store. In practice this is done by controlling the
evaporation pressure in the evaporator(s) or
by activating additional evaporators. For small
variations in working pressures the power
consumption of the refrigeration unit is
approximately proportional with the pressure
ratio between the discharge pressure and the
suction pressure:
suctp
dischpref
ref
ref
refq
refP
So if a certain pressure is required in the
evaporator in order to maintain a preset
temperature in the cold room the suction
pressure at the compressure have to be lower
as a consequence of the pressure loss in the
pipe system:
esuctionlinpevapp suctp
In the world of refrigeration there is a tendency
to express pressures as the corresponding
saturated temperature of the refrigerant. This
is also the case for pressure drops and as a
rough rule of thumb 1°C pressure drop
on the suction or discharge side
results in 2-4% higher power
consumption for the compressor.
An example is shown in the left column for two
systems for 100kW cooling load and the same
service conditions utilizing R717 and R134a
respectively.
Pressure loss suction side
The first two diagrams show the percentage
increase in energy consumption for the
refrigeration systems at 35°C condensing
pressure only caused by the suction line
pressure loss at different evaporating
temperatures.
Both diagrams show the percentage change,
but the actual increase in kWh is higher at low
temperatures. This is illustrated in the third
diagram.
Similar curves can be made for other relevant
refrigerants.
ICE-E INFO PACK
Pressure loss discharge side
The hot gas leaving the compressor is led to
a desuperheater (for heat recovery) or
directly to the condenser. The pressure loss
on this side of the compressor also causes
some extra energy. The fourth and fifth
diagram shows the relation similar to the
diagram above.
Summary
Generally the largest impacts on energy
consumption are the actual evaporation and
condensing temperatures where the focus
should be. Secondly the pressure loss on the
low pressure side is more important than the
pressure loss on the high temperature side.
Comparing the two diagrams it is clear that
the pressure loss (in Pa) on the suction side
is more important than the discharge
pressure loss.
Pressure loss
determined by the
service of the piping
In some parts of a refrigeration installation the
service of the piping is dictating the sizing
and thereby the pressure drop:
Vertical piping for two-phase
refrigerant flow (riser)
Vapor lines (suction lines) for
transportation of lubricant oil back to
the compressor
Often the refrigerant distribution system
(pipes) is placed outside on the roof of the
cold store or along the ceiling in order to
optimize the logistics in cold store and in
large systems to make easy access the
valves. In pump circulated systems more
liquid refrigerant is fed to the evaporator that
evaporated (circulation rate > 1) and more or
less liquid has to flow along the vapor against
gravity in a vertical pipe, a riser. The liquid
refrigerant (or oil) is to be pulled by the vapor
flow: If the pipe diameter is small the vapor
velocity is high and the liquid is drawn up, but
the frictional pressure drop is high. If the flow
velocity is too low (too large pipe diameter) oil
and liquid refrigerant will not be carried
along. In that case a liquid column with
vapor bubbles will build up creating a
static pressure loss. In other words the
riser has to be designed for the specific
cooling load (vapor amount) in order to
minimize the pressure drop. This also
implies that for a given load a specific
pipe size is optimal. This again means
that the design has to be carefully
examined by experienced personnel
when operating evaporators at part load.
In the case it is possible to install double
risers, but the design is out of the scope
of this info pack.
The impact by the riser pressure drop is
the same as already explained: In order
to maintain the right evaporator
performance and cold store temperature
the refrigeration compressor will operate
at a lower suction pressure which cost
extra energy.
An example: For too large riser the
potential static pressure is depending on
the refrigerant density. For R717 the
static pressure loss of pure liquid is 6,4
KPa/m which cost approximately 6400
kWh/year (@ -30° C, 5000 h/year, P_e =
100 kW).
Oil management
Depending on the compressor type and
the efficiency of the oil separation more
or less lubricating oil which will as
already mentioned be carried into the
piping systems.
The oil can be soluble or non-soluble and
the management of the oil in the system
has to be handled by the design of the
pipe system.
Soluble oils are used in DX type systems
in which the oil dissolved in the liquid
refrigerant has to be dragged back to the
compressor by the gas flow and
inclination of piping.
For refrigerant systems based on
ammonia (R717) as refrigerant non
soluble oil is used to lubricate the
compressor.
ICE-E INFO PACK
Mixture of liquid and
gas flow in a riser
Valve station in
R717 system
ICE-E INFO PACK
ICE-E INFO PACK The oil management in these systems is
based on the fact that the oil is heavier than
the ammonia. The systems must therefore be
equipped with oil tapping valves spread
around the entire system at the points where
the oil concentrates.
If the pipe system is not properly designed or
serviced on a regular basis oil presence will
eventually increase the pressure drop and
reduce the evaporator performance, which
the refrigeration unit will compensate for by
decreasing the suction pressure
correspondingly.
Insulation
Piping in refrigeration systems are often
insulated in order to
Minimize parasitic heat entering the
system
Eliminate moisture condensation on
the outside and ice build up
Eliminate condensation of
refrigerant inside vapor lines
Concerning the parasitic heat the choice of
insulation thickness is like the pipe size a
trade-off between installation cost (thickness)
and running cost (extra power consumption
for the compressor and condensator).
Recommendations can be found in [1]
Outside the cold store itself the refrigeration
piping is often colder than the dew point of
the air which has to be taken into account
when choosing the type of insulation. Some
type has a very low permeability for water
vapor and others need to have a vapor
retarder at the outside in order to avoid water
vapor to penetrate and condensate inside the
insulation.
In both cases it is evident to keep the
insulation / vapor retarder undamaged in
order to keep the moisture out.
On subzero piping the moisture will build up
as ice inside the insulation which will further
damage the insulation. At warmer pipes
the moisture will vet the insulation.
In both cases the efficiency of the
insulation will be lowered resulting in
higher parasitic heat.
Corrosion
Water (and oxygen) has to be present in
order to corrode a metal surface. Even
though work in being done to keep the
insulation/vapor retarder intact it is nearly
impossible to keep moisture out of the
insulation and thereby the pipe surface.
Due to this carbon steel piping is normally
coted before insulation. More information
is to be found in [1].
References
[1] AHSRAE HANDBOOK, Refrigeration, 2010
ISBN 978-1-933742-82-3
Nomenclature
p = pressure difference [Pa]
ptot = total pressure difference [Pa]
density [kg/m3]
c = flow velocity [m/s]
friction factor [-]
L = pipe length [m]
di = internal pipe diameter [m]
sum of friction coefficients for bends,
contractions, expansions etc. [-]
Ppump = pump effect [W]
q = liquid flow [kg/s]
pump efficiency of pump [-]
Pref = compressor effect [W]
COP = Coefficient Of Performance [-]
ref = pressure ratio compressor
pdisch = outlet pressure compressor [Pa a]
psuct = suction pressure compressor [Pa a]
The work associated with this information pack has been carried out in accordance with the highest academic standards and reasonable endeavours have been made to achieve the degree of reliability and accuracy appropriate to work of this kind. However, the ICE-E project does not have control over the use to which the results of this work may be put by the Company and the Company will therefore be deemed
to have satisfied itself in every respect as to the suitability and fitness of the work for any par ticular purpose or application. In no circumstances will the ICE-E project, its servants or agents accept liability however caused arising from any error or inaccuracy in any operation, advice or report arising from this work, nor from any resulting damage, loss, expenses or claim. © ICE-E 2012
For more information, please contact: Lars Reinholdt ([email protected])