ice-e info pack 9 heat reclaim-recovery
TRANSCRIPT
-
8/13/2019 ICE-E Info Pack 9 Heat Reclaim-recovery
1/4
Heat recovery and reclaim
All the heat extractedfrom the cols store is
lost to the ambient ifnot recovered: It canbe a very competitiveheat source.
In cold stores a refrigeration system is lifting
the heat load from the room temperature to a
temperature high enough to reject it to
ambient and hereby losing it. Also
compressed air systems produce waste heat
but the mail focus of this Info Pack in on therefrigeration system.
In theory all the heat can be
recovered but unfortunately some
constraints exists the temperature levels being
the largest.
Amount of heat
The heat rejected from the refrigeration
system is the sum of the heat load (the cooling
load) and the power supplied to therefrigeration compressor as illustrated in the
figure.
The efficiency of the heat recovery can be
expressed as
Refrigeration
system
Heat load
on room
Rejected
heat
Electrical
power
COPHP relate the COP of refrigeration (COPR)
as
If the heat is recovered without changing the
running condition (the condensing pressure) of
the refrigeration system one could argue that
the heat is for free as the electrical power
supplied to the compressor with or without the
heat recovery.
Heat sources
As described in the Info Pack Compressors
the most used compressor types in cold storesare reciprocating and oil injected screw
compressors.
On oil injected screw compressors quite a
considerable part of the heat (up to 15%) is
rejected through the oil cooler at quite high
temperature (up to 90C) whereas the other
compressor type only the heat rejected in the
condenser is in question.
The heat recovery is normally done by installing
an extra heat exchanger in series and upstreamthe condenser / oil cooler. This makes it
possible to operate the refrigeration system
when no heat recovery is done.
Constraints from themedia to be heated
Just looking at the heat available for recovery is
unfortunately not enough. The major constraints
are
1. Inlet temperature of media to beheated
The only reason forrecover heat is toreduce the cost ofheating based onanother source
ICE-EINFORMATIONPACK
-
8/13/2019 ICE-E Info Pack 9 Heat Reclaim-recovery
2/4
2. Flow of media to be heated
3. Required outlet temperature of
media to be heated
4. Simultaneity between waste heat
production and requirement for
heating
Of 1: This is the lowest possible temperature
for the condensation temperature if all heat is
to be recovered (not taking into account
possible sub cooling of the refrigerant).
Of 2 and 3: This is to some extend given by
the amount of heat required or the outlet
temperature of the media to be heated.
Of 4: A storage tank is often needed in orderto level out the difference in the time of
production and the consumption of the waste
heat.
Temperature levels
As mentioned the heat recovery can be
considered as for free if the running condition
of the refrigeration system is not changed.
When considering haet recovery the systems
have to be divided into
Traditional refrigeration cycles
Transcritical CO2cycles
Traditional refrigeration cycles
Considering the traditional refrigeration
cycles (R404A, R717 etc.) the condensing
temperature has a direct impact on the
running cost and therefor minimized and this
normally limits the temperature of the
recovered heat too much. The temperature
can depending on the refrigerant be raised a
little by installing an extra heat exchanger
before the condenser (a desuperheater) in
which the quite warm discharge gas is
cooled before entering the condenser.
In figure 1 the heat recovery is shown for a
R717 system operating at 75C condensing
temperature cooled by a media being
heated from 40 to 80C. The heat
production is 100kW. In this example the
condensing temperature is raised compared
to normal refrigeration system.
The process is limited at the lowest possible
temperature difference which is found at the
pinch point. In figure 1 this is found at the
point where the condensation starts (at
80kW).
Figure 2 shows the same process but now
the water is heated to 95C. This process is
not possible as the refrigerant (red line)
always has to have a higher temperature
than the media to be heated. In this case
the condensing pressure has to be raised to
approx. 85C to have the pinch point at
80kW above the green line.
Transcritical CO2cycle
The CO2cycle has some advantages when
it comes to heat recovery and as the
process is not that well known there is avery short introduction in the following:
As CO2has a so-called critical point at 31C
the heat rejection will often be a supercritical
process: Above the critical point it is not
possible to condense the refrigerant. The
CO2 is to be considered as a more and
more heavy gas as the heat rejection is
progressing. This also means that the
temperature is falling during the heat
rejection: It has a glide.
The process is shown in Figure 3. Three
Figure 1 Temperature slope in heatrecovery condenserred line: refrigerant
blue line: water, heated 40 > 80C
Superheat
Subcooling
Condensing
Figure 3 Trans critical CO2refrigeration cyclesEvaporating temperature -5C, gas cooler outlet temperature 40CGas cooler pressure: Green: 90 bar a, red: 100 bar a and blue: 120 bar a(Source: Danfoss)
Figure 2 Identical to Figure 1
green line: water, heated 40 > 95C
ICE-E INFO PACK
-
8/13/2019 ICE-E Info Pack 9 Heat Reclaim-recovery
3/4
ICE-E INFO PACK
identical cycles are shown, all rejecting heat
down to 40C. The three COPs shows that in
contrast to traditional cycles the COP can
raise at raising compressor discharge
pressure. The critical parameter for the cycle
is the temperature out of the gas cooler, if allheat is to be recovered the media to be
heated has to have a low inlet temperature.
As the super critical CO2 has a temperature
glide it better fits the slope of for instance
water as media to be heated. This is shown in
Figure 4 where water is heated from 15 to
75C. Even though water is quite cold at the
inlet it is not possible to utilize this to cool the
CO2 all the way down and the gas cooler is
rejecting the last part of the heat to ambient
(and losing it).
If a traditional refrigeration cycle was used for
making 75C water, the condensing
temperature had to be raised to 78C. The
CO2 cycle was not changed!
The energetic cost ofrecovering heat
As stated the recovered heat is from an
energetic point of view for free (excluding
extra pumps etc.) as long as the conditions for
the refrigeration system are not changed.
But often raising the condensing temperature
is needed which will cause the electrical
power consumption to go up: The recovered
heat is no longer for free.
Instead of using the COPHR as the measure
for the efficiency of the recovery the cost of
recovery can be compared to the extrapower
consumption due to the altered running
condition. This can be expressed as the
Efficiency of Heat Recovery, EHRdefined as
EHRis sometime called marginal COP or COP
of heat recovery.
EHR can be very high even when the no
change is done to the running condition.
Actual it can turn negative implying that
energy is produced! This is due to the fact that
in the case of 100% recovery the ambient
condition does not affect the running condition
any longer. In the case of on heat recovery
a further raise in ambient temperature could
have caused an increase in running
condition compared to the situation of 100%
recovery. This situation is possible ontranscritical CO2systems.
EHR can also be very low: In the case of
only a minor part of the heat is recovered
and the condensing pressure is raised also
the heat rejected to ambient is done at the
elevated pressure. In other words the COP
for the whole refrigeration capacity is
affected negatively in order to recover only a
little part of the heat.
Heat pumpsThe conditions shown in Figure 1 and 2 is
not possible to achieve in ordinary NH3
refrigeration systems as the condensing
pressure (> 40 bar a) will be too high for a
standard compressor. In this case a heat
pump compressor can be (or a complete
heat pump system) installed turning the
system into a kind of two stage system (see
the Info Pack on Refrigerant cycles).
Doing this will decouple the running of therefrigeration system and the heat recovery
and the before mentioned situation of very
low EHRwill be eliminated. Or more precise
it will be eliminated in some case:
When installing a heat pump the
refrigeration system (and cold store) has to
be thoroughly analyzed and optimized: The
installation of a heat pump can look very
promising when the condensing pressure is
high but it can turn out to be bad in the case
the condensing pressure is optimized and
lowered.
Strategy of heatrecovery
If the heat is recovered to a storage tank
which is often the case in facilities where the
recovered heat is used for cleaning
purposes two strategies exists:
1. Build up a stratified layer in the
tank having cold water in the
Figure 3 Heat recovery on transcritical CO2
refrigeration cycles.Water heated form 15 to 75C.Pinch point inside the HRHX (Heat RecoveryHeat eXchanger)CO2further cooled in an air cooled gas cooler
Figure 5 Heat recovery heat exchanger for oil
system on screw compressor
-
8/13/2019 ICE-E Info Pack 9 Heat Reclaim-recovery
4/4
ICE-E INFO PACK
bottom part and recovering the heat
to the required temperature (e.g.
60C) in the top.
2. Charging the tank being fully mixed
The last strategy is the best from an energeticpoint of view: The EHR will be high in the
beginning and decline throughout the
charging the tank. In strategy 1 the EHR will
have the low value throughout the charging.
And the amount of energy in the tank will be
the nearly the same: Strategy 1 will charge a
little bit more resulting from the lower EHR. In
other words an electrical heating element in
the tank would have given the same.
Investment and paybackThe only reason for recover heat isto reduce the cost of heating basedon another source.
One has to keep this in mind when making
the cost benefit analysis of heat recovery. The
sensibility to future change in price of the
competing heat source, future change in the
operation of the cold store etc. must be taken
into account. Into this picture has to be taken
the possibility of selling the recovered heat.
ICE-E INFO PAC
ICE-E INFO PACK
ICE-E INFO PACK
ICE-E INFO PACK
For more information, please contact: Lars Reinholdt ([email protected])
Figure 5 Heat recovery heat exchanger fordesuperheating on screw compressor system