ice-e info pack 9 heat reclaim-recovery

Upload: lethanhvan186

Post on 04-Jun-2018

212 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/13/2019 ICE-E Info Pack 9 Heat Reclaim-recovery

    1/4

    Heat recovery and reclaim

    All the heat extractedfrom the cols store is

    lost to the ambient ifnot recovered: It canbe a very competitiveheat source.

    In cold stores a refrigeration system is lifting

    the heat load from the room temperature to a

    temperature high enough to reject it to

    ambient and hereby losing it. Also

    compressed air systems produce waste heat

    but the mail focus of this Info Pack in on therefrigeration system.

    In theory all the heat can be

    recovered but unfortunately some

    constraints exists the temperature levels being

    the largest.

    Amount of heat

    The heat rejected from the refrigeration

    system is the sum of the heat load (the cooling

    load) and the power supplied to therefrigeration compressor as illustrated in the

    figure.

    The efficiency of the heat recovery can be

    expressed as

    Refrigeration

    system

    Heat load

    on room

    Rejected

    heat

    Electrical

    power

    COPHP relate the COP of refrigeration (COPR)

    as

    If the heat is recovered without changing the

    running condition (the condensing pressure) of

    the refrigeration system one could argue that

    the heat is for free as the electrical power

    supplied to the compressor with or without the

    heat recovery.

    Heat sources

    As described in the Info Pack Compressors

    the most used compressor types in cold storesare reciprocating and oil injected screw

    compressors.

    On oil injected screw compressors quite a

    considerable part of the heat (up to 15%) is

    rejected through the oil cooler at quite high

    temperature (up to 90C) whereas the other

    compressor type only the heat rejected in the

    condenser is in question.

    The heat recovery is normally done by installing

    an extra heat exchanger in series and upstreamthe condenser / oil cooler. This makes it

    possible to operate the refrigeration system

    when no heat recovery is done.

    Constraints from themedia to be heated

    Just looking at the heat available for recovery is

    unfortunately not enough. The major constraints

    are

    1. Inlet temperature of media to beheated

    The only reason forrecover heat is toreduce the cost ofheating based onanother source

    ICE-EINFORMATIONPACK

  • 8/13/2019 ICE-E Info Pack 9 Heat Reclaim-recovery

    2/4

    2. Flow of media to be heated

    3. Required outlet temperature of

    media to be heated

    4. Simultaneity between waste heat

    production and requirement for

    heating

    Of 1: This is the lowest possible temperature

    for the condensation temperature if all heat is

    to be recovered (not taking into account

    possible sub cooling of the refrigerant).

    Of 2 and 3: This is to some extend given by

    the amount of heat required or the outlet

    temperature of the media to be heated.

    Of 4: A storage tank is often needed in orderto level out the difference in the time of

    production and the consumption of the waste

    heat.

    Temperature levels

    As mentioned the heat recovery can be

    considered as for free if the running condition

    of the refrigeration system is not changed.

    When considering haet recovery the systems

    have to be divided into

    Traditional refrigeration cycles

    Transcritical CO2cycles

    Traditional refrigeration cycles

    Considering the traditional refrigeration

    cycles (R404A, R717 etc.) the condensing

    temperature has a direct impact on the

    running cost and therefor minimized and this

    normally limits the temperature of the

    recovered heat too much. The temperature

    can depending on the refrigerant be raised a

    little by installing an extra heat exchanger

    before the condenser (a desuperheater) in

    which the quite warm discharge gas is

    cooled before entering the condenser.

    In figure 1 the heat recovery is shown for a

    R717 system operating at 75C condensing

    temperature cooled by a media being

    heated from 40 to 80C. The heat

    production is 100kW. In this example the

    condensing temperature is raised compared

    to normal refrigeration system.

    The process is limited at the lowest possible

    temperature difference which is found at the

    pinch point. In figure 1 this is found at the

    point where the condensation starts (at

    80kW).

    Figure 2 shows the same process but now

    the water is heated to 95C. This process is

    not possible as the refrigerant (red line)

    always has to have a higher temperature

    than the media to be heated. In this case

    the condensing pressure has to be raised to

    approx. 85C to have the pinch point at

    80kW above the green line.

    Transcritical CO2cycle

    The CO2cycle has some advantages when

    it comes to heat recovery and as the

    process is not that well known there is avery short introduction in the following:

    As CO2has a so-called critical point at 31C

    the heat rejection will often be a supercritical

    process: Above the critical point it is not

    possible to condense the refrigerant. The

    CO2 is to be considered as a more and

    more heavy gas as the heat rejection is

    progressing. This also means that the

    temperature is falling during the heat

    rejection: It has a glide.

    The process is shown in Figure 3. Three

    Figure 1 Temperature slope in heatrecovery condenserred line: refrigerant

    blue line: water, heated 40 > 80C

    Superheat

    Subcooling

    Condensing

    Figure 3 Trans critical CO2refrigeration cyclesEvaporating temperature -5C, gas cooler outlet temperature 40CGas cooler pressure: Green: 90 bar a, red: 100 bar a and blue: 120 bar a(Source: Danfoss)

    Figure 2 Identical to Figure 1

    green line: water, heated 40 > 95C

    ICE-E INFO PACK

  • 8/13/2019 ICE-E Info Pack 9 Heat Reclaim-recovery

    3/4

    ICE-E INFO PACK

    identical cycles are shown, all rejecting heat

    down to 40C. The three COPs shows that in

    contrast to traditional cycles the COP can

    raise at raising compressor discharge

    pressure. The critical parameter for the cycle

    is the temperature out of the gas cooler, if allheat is to be recovered the media to be

    heated has to have a low inlet temperature.

    As the super critical CO2 has a temperature

    glide it better fits the slope of for instance

    water as media to be heated. This is shown in

    Figure 4 where water is heated from 15 to

    75C. Even though water is quite cold at the

    inlet it is not possible to utilize this to cool the

    CO2 all the way down and the gas cooler is

    rejecting the last part of the heat to ambient

    (and losing it).

    If a traditional refrigeration cycle was used for

    making 75C water, the condensing

    temperature had to be raised to 78C. The

    CO2 cycle was not changed!

    The energetic cost ofrecovering heat

    As stated the recovered heat is from an

    energetic point of view for free (excluding

    extra pumps etc.) as long as the conditions for

    the refrigeration system are not changed.

    But often raising the condensing temperature

    is needed which will cause the electrical

    power consumption to go up: The recovered

    heat is no longer for free.

    Instead of using the COPHR as the measure

    for the efficiency of the recovery the cost of

    recovery can be compared to the extrapower

    consumption due to the altered running

    condition. This can be expressed as the

    Efficiency of Heat Recovery, EHRdefined as

    EHRis sometime called marginal COP or COP

    of heat recovery.

    EHR can be very high even when the no

    change is done to the running condition.

    Actual it can turn negative implying that

    energy is produced! This is due to the fact that

    in the case of 100% recovery the ambient

    condition does not affect the running condition

    any longer. In the case of on heat recovery

    a further raise in ambient temperature could

    have caused an increase in running

    condition compared to the situation of 100%

    recovery. This situation is possible ontranscritical CO2systems.

    EHR can also be very low: In the case of

    only a minor part of the heat is recovered

    and the condensing pressure is raised also

    the heat rejected to ambient is done at the

    elevated pressure. In other words the COP

    for the whole refrigeration capacity is

    affected negatively in order to recover only a

    little part of the heat.

    Heat pumpsThe conditions shown in Figure 1 and 2 is

    not possible to achieve in ordinary NH3

    refrigeration systems as the condensing

    pressure (> 40 bar a) will be too high for a

    standard compressor. In this case a heat

    pump compressor can be (or a complete

    heat pump system) installed turning the

    system into a kind of two stage system (see

    the Info Pack on Refrigerant cycles).

    Doing this will decouple the running of therefrigeration system and the heat recovery

    and the before mentioned situation of very

    low EHRwill be eliminated. Or more precise

    it will be eliminated in some case:

    When installing a heat pump the

    refrigeration system (and cold store) has to

    be thoroughly analyzed and optimized: The

    installation of a heat pump can look very

    promising when the condensing pressure is

    high but it can turn out to be bad in the case

    the condensing pressure is optimized and

    lowered.

    Strategy of heatrecovery

    If the heat is recovered to a storage tank

    which is often the case in facilities where the

    recovered heat is used for cleaning

    purposes two strategies exists:

    1. Build up a stratified layer in the

    tank having cold water in the

    Figure 3 Heat recovery on transcritical CO2

    refrigeration cycles.Water heated form 15 to 75C.Pinch point inside the HRHX (Heat RecoveryHeat eXchanger)CO2further cooled in an air cooled gas cooler

    Figure 5 Heat recovery heat exchanger for oil

    system on screw compressor

  • 8/13/2019 ICE-E Info Pack 9 Heat Reclaim-recovery

    4/4

    ICE-E INFO PACK

    bottom part and recovering the heat

    to the required temperature (e.g.

    60C) in the top.

    2. Charging the tank being fully mixed

    The last strategy is the best from an energeticpoint of view: The EHR will be high in the

    beginning and decline throughout the

    charging the tank. In strategy 1 the EHR will

    have the low value throughout the charging.

    And the amount of energy in the tank will be

    the nearly the same: Strategy 1 will charge a

    little bit more resulting from the lower EHR. In

    other words an electrical heating element in

    the tank would have given the same.

    Investment and paybackThe only reason for recover heat isto reduce the cost of heating basedon another source.

    One has to keep this in mind when making

    the cost benefit analysis of heat recovery. The

    sensibility to future change in price of the

    competing heat source, future change in the

    operation of the cold store etc. must be taken

    into account. Into this picture has to be taken

    the possibility of selling the recovered heat.

    ICE-E INFO PAC

    ICE-E INFO PACK

    ICE-E INFO PACK

    ICE-E INFO PACK

    For more information, please contact: Lars Reinholdt ([email protected])

    Figure 5 Heat recovery heat exchanger fordesuperheating on screw compressor system