icon en instrumentation cables
TRANSCRIPT
-
8/20/2019 Icon en Instrumentation Cables
1/76
The Quality Connection
ICON® Instrumentation Cable
PLTC/ITC and TC Types
-
8/20/2019 Icon en Instrumentation Cables
2/76
www.leoni-industrial-projects.com2
The product program “Instrumentation Cable ICON®“ covers products
which are based on the European standard EN 50288-7 and the US-
American standards UL 13, UL 2250 and UL 1277. This product program
gives extensive coverage to the requirements of the different Installation
and Safety Regulations which are applied for measurement, control andmonitoring systems in industrial plants. As a result the user has a product
program at his disposal for applications world wide.
On the solid basis of many years of experience in international
business (either project-oriented or geared to the site requirements
of the customers), we have defined a very wide produc t range
designed to meet all your field-driven product requirements.
We have selected and elaborated a product program designed to
cover all usual applications. The diversity of the environmental,
electrical, mechanical, installation and safet y requirements produces
a need for an extensive range of products.
In this catalog you will find a product guide showing the complete
UL instrumentation product range of LEONI Industrial Projects and
data sheets of the most common types.
The Quality Connection
■ Telecommunication cables
■ Data- and Bus cables (copper and fiber optic)
■ Mining cables
■ Cables for special applications
■ Instrumentation- and control cables
■ Thermocouple extension and compensating cables
■ Power cables (low and medium voltage)
Product range
Content Page
Introduction 5
Produc t Guide UL 13, UL 2250 and UL 1277 6
Instrumentation Cable PLTC / ITC 300 V 6Instrumentation Cable TC 600 V 10
DATASHEETS
Instrumentation Cable 300 V
PVC jacket unshielded
RE-YwYw-fl
Single-pair 22
Single-triple 23
PVC-jacket, shielded
RE-Yw(St)Yw-fl
Single- & multi-pair, collective shield 24
Multi-pair, individual & collective shield (PiMF) 26
Single- & multi-triple, collective shield 28
Multi-triple, individual & collective shield (TiMF) 30
Armor, PVC jacket
RE-Yw(St)YwSWAYw-fl
Single- & multi-pair, collective shield 32
Multi-pair, individual & collective shield (PiMF) 34Single- & multi-triple, collective shield 36
Multi-triple, individual & collective shield (TiMF) 38
-
8/20/2019 Icon en Instrumentation Cables
3/76
www.leoni-industrial-projects.com 3
AL-laminated jacket
RE-Yw(St)Yw(L)Yw-fl
Single- & multi-pair, collective shield 40
Multi-pair, individual & collective shield (PiMF) 42
Single- & multi-triple, collective shield 44Multi-triple, individual & collec tive shield (TiMF) 4 6
AL-laminated jacket, armor, PVC-jacket
RE-Yw(St)Yw(L)YwSWAYw-fl
Single- & multi-pair, collective shield 48
Multi-pair, individual & collective shield (PiMF) 50
Single- & multi-triple, collective shield 52
Multi-triple, individual & collective shield (TiMF) 54
Instrumentation Cables 600 V
PVC jacket, shielded
RE-Yw(St)Yw-fl
Single- & multi-pair, collective shield 56
Multi-pair, individual & collective shield (PiMF) 58
Single- & multi-triple, collective shield 60
Multi-triple, individual & collective shield (TiMF) 62
Instrumentation & Control Cables 300 V
PVC jacket, shielded
RE-Yw(St)Yw-flMulti-cores, collective shield, PVC jacket 64
Armor, PVC jacket
RE-Yw(St)YwSWAYw-fl
Multi-cores, collective shield, armor, PVC jacket 66
Instrumentation & Control Cables 600 V
PVC jacket, shielded
RE-Yw(St)Yw-fl
Multi-cores, collective shield, PVC jacket 68
Content
LEONI Kerpen GmbH can not be held responsible in any form whatsover for any
information provided by this publication. Printing errors excepted. Subject to altera-
tions. Issue 20110208 - replaces issue 20081022
General
General units 71
Conductors AWG and metric values by comparison 72
Color codes 73
Type designatio n 74
Abbreviation code 75
-
8/20/2019 Icon en Instrumentation Cables
4/76
www.leoni-industrial-projects.com4
Please visit our website
www.leoni-industrial-projects.com
Table of Contents
LEONI is one of the leading suppliers of standardized and
customer-specific special cables and pre-assembled cable
systems worldwide.
The Business Unit Industrial Projects allows us to give our custom-
ers access to the entire competence of a worldwide corporation,
focused to meet the needs of industrial applications. We supply
our products and solutions wherever everything depends on
maximum reliability, quality and durability, such as in oil and gas
extract ion and processing as well as in the petrochemical and
energy production industries. LEONI products are to be found in
many other applications such as the pulp and pap er, cement and
pharmaceutical industries and in waste management, in which
processes have to run in a controlled way via sensors and actua -
tors.
For us reliability doesn’t just mean keeping the right product avail-
able for you as a standard produc t or developing a project solution
for you – it also means supplying it precisely at the agreed time.
Safety, availability and reliability are vital in industrial
plant engineering and energy provision. This is b ecause these are
fields in which unexpec ted breakdowns are very expensive and have
critical effects on the environment.
Companies are asking for solutions which are perfectly tailored to
meet the application in question as well as the plant its elf. 70 %
of the cables leaving our company are developed, manufactured
and assembled according to customer specifications. We produce
quantities depending on the requirements of the projects and sup-
ply according to cable drumming schedules. We are also equipped
to provide project quantities in a considerable two-digit million euro
range. We take into account company-specific standards as well as
all important industrial and environmental standards on the national
and international level.
LEONI
Industrial Projects –
your expert for a market that
requires maximum reliability
-
8/20/2019 Icon en Instrumentation Cables
5/76
www.leoni-industrial-projects.com 5Table of Contents
The product range of
instrumentation cables acc. to UL
ICON®
UL Program
UL 13, UL 2250 and UL 1277
Instrumentation, Control and Thermocouple extension cables according
to above standards have to be applied in those systems, where “Installa-
tion and Safety regulations“ are based on the “National Electrical Code“
(NEC).
The NEC Handbook is published by the “National Fire Protection
Association“ a leading US standardization for safety, particularly for fire
protection. As installation guide it is mandatory in the USA, however, it
is also practiced in some other countries.
Instrumentation, Control and Thermocouple extension cables
will thereby meet the following standards and types:
■ e300 V “Power Limited Tray Cable” (PLTC) acc. to UL 13
“Instrumentation Tray Cable”(ITC) acc. to UL 2250
■ 600 V “Tray Cable” (TC) acc. to UL 1277 ib
-
8/20/2019 Icon en Instrumentation Cables
6/76
www.leoni-industrial-projects.com6 The Standard Types Instrumentation Cable
Instrumentation Cable
Common types
armoredunarmored(L) shieldarmored(L) shield
PLTC / ITC (UL 13 / UL 2250)
300 V
plain stranded copper conductors,pairs or triples,
individual and/or overall static shield
PVCw-insulation or XLPE-insulation
PVCw-jacket
ICON® Instrumentation Cable
TC (UL 1277)
600 V
plain stranded copper conductors,pairs or triples,
individual and/or overall static shield
PVCwNC-insulation, PVCw-insulation or XLPE-insulation,
PVCw-jacket
unarmored
-
8/20/2019 Icon en Instrumentation Cables
7/76
www.leoni-industrial-projects.com 7The Standard Types Instrumentation Cable
Technical data
Type of insulation/jacket PVCw/PVCw XLPE/PVCw
Type of cabling elements Pair, Triple, PiMF, TiMF
No. of cabling elements 1, 2, 4, 6, 8, 10, 12, 16, 24, 36
Conductor sizes AWG 20/7, AWG 18/7, AWG 16/7, AWG 14/7
1. Unarmored types RE-Yw(St)Yw-fl RE-2X(St)Yw-fl
Laying Recommended for outdoor installation, on racks, trays, in conduits, in dry and wet locations, for direct burial 2)
Bending radius 7.5 x cable diameter
2. Armored types RE-Yw(St)YwSWAYw-fl RE-2X(St)YwSWAYw-fl
Laying Recommended for outdoor installation, on racks, trays, in conduits, in dry and wet locations, for direct burial 2)
Bending radius 10 x cable diameter
3. (L) shielded type RE-Yw(St)Yw(L)Yw-fl RE-2X(St)Yw(L)Yw-fl
Laying Recommended for outdoor installation, on racks, trays, in conduits, in dry and wet locations, for direct burial
Bending radius 15 x cable diameter
4. (L) shielded type, armored RE-Yw(St)Yw(L)YwSWAYw-fl RE-2X(St)Yw(L)YwSWAYw-fl
Laying Recommended for outdoor installation, on racks, trays, in conduits, in dry and wet locations, for direct burial
Bending radius 15 x cable diameter
Reaction to fire
Flame propagation
a) Test on single cable
b) Test on bunched cables
UL 13 VW-1 test, IEC 60332-1
UL 1685, IEC 60332-3 part 24 (Cat.C)
Temperature range during operation
during installat ion
–40 °C up to 105 °C
–5 °C up to 50 °C
–40 °C up to 90 °C
–5 °C up to 50 °C
Sunlight resistance UL 1581 Section 1200
Oil resistance ICEA S-72-532
Application For transmission of analogue and digital signals in instrument and control systems in complianc with NEC article
725.154; allowed for use in hazardous classified locations class I and class II division 2 acc. to NEC 501.10(B) and NEC
502.10(B), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply
1) Color code of cabling elements see general. 2)
if applicable.
ICON® Instrumentation Cable according to UL 13 / 2250
Common types
Single & multi pair and single & multi triple, individual and/or overall shield, PVC-jacket■ unarmored
■ armored
■ (L) shielded
■ (L) shielded, armored
300 V
-
8/20/2019 Icon en Instrumentation Cables
8/76
www.leoni-industrial-projects.com8 The Standard Types Instrumentation Cable
Construction
Product types Unarmored types Armored types (L) shielded types L() shielded types, armored
Conductor Plain annealed copper; 7 stranded according to UL 13
size AWG
Conductor design mm
AWG 20/7
7 x 0.320
AWG 18/7
7 x 0.404
AWG 16/7
7 x 0.490
AWG 14/7
7 x 0.620
Insulation materialsCross linked polyethylene XLPE or
Polyvinyl chloride heat resistant PVCw
Cabling element 1)
without individual shield Pair, Triple
with individual shield PiMF, TiMF
Individual shield Aluminum/plastic-tape over solid tinned copper drain wire, plastic-tape under and above shield
Wrapping at least one plastic tape above cable core
Overall shield Aluminum/plastic-tape over stranded tinned copper drain wire
Inner jackets — PVCw, black
L() shield — — Laminated aluminium tape
Armoring —
Galvanized steel wire armor;
wire diameter depending on
cable diameter under armoring,
at least 0.9 mm
—
Galvanized steel wire armor;
wire diameter depending on
cable diameter under armoring,
at least 0.9 mm
Outer jacket PVCw
Color black or blue for intrinsically safe systems
Marking LEONI KERPEN ICON PLTC/ITC SIZE MATERIAL TYPE OF SHIELD UL
TEMPERATURE RATING SUN RES DIR BUR PRODUCTION LOT CODE LENGTH MARKING IN FEET
1) Color code of cabling elements see general. 2) if applicable.
ICON® Instrumentation Cable according to UL 13 / 2250
Common types
Single & multi pair and single & multi triple, individual and/or overall shield, PVC-jacket■ unarmored
■ armored
■ (L) shielded
■ (L) shielded, armored
300 V
-
8/20/2019 Icon en Instrumentation Cables
9/76
www.leoni-industrial-projects.com 9The Standard Types Instrumentation Cable
Electrical Data at 20 °C 300 V
Conductor sizes nom. AWG AWG 20/7 AWG 18/7 AWG 16/7 AWG 14/7
Conductor resistance max. Ω/km 35.8 22.8 14.3 9.0
Insulation resistance at 15.6 °C PVCw-insulation min. MΩxkm 30.5
XLPE-insulation min. MΩxkm 30.5
Inductance max. mH/km 1 (0.75 for (L) shielded types)
Mutual capacitance
PVCw-insulation Pair, Triple 1) 2)
PiMF, TiMFmax. nF/km
200
200
XLPE-insulation Pair, Triple 1) 2)
PiMF, TiMFmax. nF/km
125
125
Test voltage Core/core (Urms
)
Core/shield (Urms
) V
1500
1500
Operating voltage (Urms
) max. V 300
1) Values for cables with 1 element correspond to those for PiMF and TiMF resp. 2) Values for cables with >1 element -30 %.
ICON® Instrumentation Cable according to UL 13 / 2250
Common types
Single & multi pair and single & multi triple, individual and/or overall shield, PVC-jacket■ unarmored
■ armored
■ (L) shielded
■ (L) shielded, armored
300 V
-
8/20/2019 Icon en Instrumentation Cables
10/76
www.leoni-industrial-projects.com10 The Standard Types Instrumentation Cable
Instrumentation Cable
Common types
PLTC / ITC (UL 13 / UL 2250)
300 V
plain stranded copper conductors,
pairs or triples,
individual and/or overall static shield
PVCw-insulation or XLPE-insulation
PVCw-jacket
ICON® Instrumentation Cable
armored
TC (UL 1277)
600 V
plain stranded copper conductors,
pairs or triples,
individual and/or overall static shield
PVCwNC-insulation, PVCw-insulation or XLPE-insulation,
PVCw-jacket
unarmoredunarmored (L) shieldarmored(L) shield
-
8/20/2019 Icon en Instrumentation Cables
11/76
www.leoni-industrial-projects.com 11The Standard Types Instrumentation Cable
ICON® Instrumentation Cable according to UL 13 / 2250
Common types
Single & Multi pair and Multi triple, individual and/or overall shield, PVC-jacket
■ unarmored
■ armored
300 V
ICON® Instrumentation Cable according to UL 1277
Common types
Single & Multi pair and Single & Multi triple, indiv idual and/or overall shield, PVC-jacket
■ unarmored
600 V
Technical data
Type of insulation/jacket PVCw/PVCw PVCwNC/PVCw XLPE/PVCw
Type of cabling elements Pair, Triple, PiMF, TiMF
No. of cabling elements 1, 2, 4, 6, 8, 10,12, 16, 24, 36
Conductor sizes AWG 18/7, AWG 16/7, AWG 14/7
1. Unarmored types RE-Yw(St)Yw-fl RE-Yw4Y(St)Yw-fl RE-2X(St)Yw-fl
Laying Recommended for indoor and outdoor installation,
on racks, trays, in conduits, in dry and wet locations,
for direct burial
Bending radius 7.5 x cable diameter 10 x cable diameter 7.5 x cable diameter
Reaction to fire
Flame propagation
a) Test on single cable
b) Test on bunched cables
UL 13 VW-1 test, IEC 60332-1
UL 1685, IEC 60332-3 part 24 (Cat.C)
Temperature range during operation
during installation
–40 °C up to 90 °C
–5 °C up to 50 °C
Sunlight resistance UL 1581 Section 1200
Oil resistance ICEA S-73-532
Application For transmission of analogue and digital signals in instrument and control systems; UL listed tray cable in compliance
with NEC article 336, for use in hazardous classified locations class I and class II division 2 acc. to NEC 501.10(B) and
NEC 502.10(B), not allowed for direct connection to l ow impedance sources, e.g. public mains electrici ty supply
-
8/20/2019 Icon en Instrumentation Cables
12/76
www.leoni-industrial-projects.com12 The Standard Types Instrumentation Cable
Construction
Product types Unarmored types
Conductor Plain annealed copper; 7 stranded
size AWG
Conductor design mm
AWG 18/7
7 x 0.404
AWG 16/7
7 x 0.490
AWG 14/7
7 x 0.620
Insulation materials Polyvinylchloride PVC heat resistant PVCw or
Polyvinylchloride PVC heat resistant PVCw with nylon coating NC or
Cross linked polyethylene XLPE
Cabling element 1)
without individual shield Pair, Triple
with individual shield PiMF, TiMF
Individual shield Aluminum/plastic-tape over stranded tinned copper drain wire, plastic-tape under and above shield
Wrapping at least one plastic tape above cable core
Overall shield Aluminum/plastic-tape over stranded tinned copper drain wire
Outer jacket PVCw
Color black or blue for intrinsically safe systems
Marking LEONI KERPEN ICON TC SIZE MATERIAL T YPE OF SHIELD UL RATED VOLTAGE
TEMPERATURE RATING SUN RES DIR BUR PRODUCTION LOT CODE LENGTH MARKING IN FEET
1) Color code of cabling elements see general .
ICON® Instrumentation Cable according to UL 13 / 2250
Common types
Single & Multi pair and Multi triple, individual and/or overall shield, PVC-jacket
■ unarmored
■ armored
300 VICON® Instrumentation Cable according to UL 1277
Common types
Single & Multi pair and Multi triple, individual and/or overall shield, PVC-jacket
■ unarmored
600 V
-
8/20/2019 Icon en Instrumentation Cables
13/76
www.leoni-industrial-projects.com 13The Standard Types Instrumentation Cable
Electrical Data at 20 °C 600 V
Conductor sizes nom. AWG AWG 18/7 AWG 16/7 AWG 14/7
Conductor resistance max. Ω/km 22.8 14.3 9.0
Insulation resistance at 15°C PVCw-insulation min. MΩxkm 175
XLPE-insulation min. MΩxkm 810
Inductance max. mH/km 0.7
Mutual capacitance
PVCw-insulation Pair, Triple 1) 2)
PiMF, TiMFmax. nF/km
170
170
XLPE-insulation Pair, Triple 1) 2)
PiMF, TiMFmax. nF/km
120
120
Test voltage Core/core (Urms
)
Core/shield (Urms
) V
2000, PVCw insulation / 3000, XLPE insulation
2000, PVCw insulation / 3000, XLPE insulation
Operating voltage (Urms) max. V 600
1) Values for cables with 1 element correspond to those for PiMF and TiMF resp. 2) Values for cables with > 1 element -30 %.
ICON® Instrumentation Cable according to UL 13 / 2250
Common types
Single & Multi pair and Multi triple, individual and/or overall shield, PVC-jacket
■ unarmored
■ armored
300 VICON® Instrumentation Cable according to UL 1277
Common types
Single & Multi pair and Single & Multi triple, individual and/or overall shield, PVC-jacket
■ unarmored
600 V
-
8/20/2019 Icon en Instrumentation Cables
14/76
www.leoni-industrial-projects.com14 The Standard Types Instrumentation Cable
Instrumentation Control Cable
Common types
ICON® Instrumentation Control Cable
TC (UL 1277)
600 V
plain stranded copper conductors,
cores,
overall static shield
PLTC / ITC (UL 13 / UL 2250)
300 V
plain stranded copper conductors,
cores,
overall static shield
PVCw-insulation or XLPE-insulation
PVCw-jacket
armoredunarmored (L) shieldarmored(L) shield
PVCwNC-insulation, PVCw-insulation,or XLPE-insulation,
PVCw-jacket
unarmored
-
8/20/2019 Icon en Instrumentation Cables
15/76
www.leoni-industrial-projects.com 15The Standard Types Instrumentation Cable
Technical data
Type of insulation/jacket PVCw/PVCw XLPE/PVCw
Type of cabling elements Cores
No. of cabling elements 2, 4, 6, 8, 10, 12, 16, 24, 36
Conductor sizes AWG 20/7, AWG 18/7, AWG 16/7, AWG 14/7
1. Unarmored types RE-Yw(St)Yw-fl RE-2X(St)Yw-fl
Laying Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations, or direct
burial 2)
Bending radius 7.5 x cable diameter
2. Armored types RE-Yw(St)YwSWAYw-fl RE-2X(St)YwSWAYw-fl
Laying Recommended for outdoor installation, on racks, trays, in conduits, in dry and wet locations, or direct burial1)
Bending radius 7.5 x cable diameter
Reaction to fire
Flame propagation
a) Test on single cable
b) Test on bunched cables
UL 13 VW-1 test, IEC 60332-1
UL 1685, IEC 60332-3 part 24 (Cat.C)
Temperature range during operation
during installat ion
–40 °C up to 105 °C
–5 °C up to 50 °C
–40 °C up to 90 °C
–5 °C up to 50 °C
Sunlight resistance UL 1581 Section 1200
Oil resistance ICEA S-72-532
Application For transmission of analogue and digital signals in instrument and control systems in complianc with NEC article
725.154; allowed for use in hazardous classified locations class I and class II division 2 acc. to NEC 501.10(B) and NEC
502.10(B), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply
1) if applicable
ICON® Instrumentation Control Cable according to UL 13 / 2250
Common types
Multi core, overall shield, PVC-jacket
■ unarmored
■ armored
300 V
-
8/20/2019 Icon en Instrumentation Cables
16/76
www.leoni-industrial-projects.com16 The Standard Types Instrumentation Cable
Construction
Product types Unarmored types Armored types
Conductor Plain annealed copper; 7 stranded according to UL 13
size AWG
Conductor design mm
AWG 20/7
7 x 0.320
AWG 18/7
7 x 0.404
AWG 16/7
7 x 0.490
AWG 14/7
7 x 0.620
Insulation materialsCross linked polyethylene XLPE or
Polyvinyl chloride heat resistant PVCw
Cabling element 1)
without individual shield Core
Wrapping at least one plastic tape above cable core
Overall shield Aluminum/plastic-tape over stranded tinned copper drain wire
Inner jacket — PVCw, black
Armoring
Galvanized steel wire a rmor; wire diameter depending on
cable diameter under armoring, at least 0.9 mm
Outer jacket PVCw
Color black or blue for intrinsically safe systems
Marking LEONI KERPEN ICON PLTC/ITC SIZE MATERIAL T YPE OF SHIELD UL
TEMPERATURE RATING SUN RES DIR BUR 2) PRODUCTION LOT CODE LENGTH MARKING IN FEET
1) Color code of cabling elements see general . 2) if applicable
ICON® Instrumentation Control Cable according to UL 13 / 2250
Common types
Multi core, overall shield, PVC-jacket
■ unarmored
■ armored
300 V
-
8/20/2019 Icon en Instrumentation Cables
17/76
www.leoni-industrial-projects.com 17The Standard Types Instrumentation Cable
Electrical Data at 20 °C 300 V
Conductor sizes nom. AWG AWG 20/7 AWG 18/7 AWG 16/7 AWG 14/7
Conductor resistance max. Ω/km 35.8 22.8 14.3 9.0
Insulation resistance at 15.6 °C PVCw-insulation min. MΩxkm 30.5
XLPE-insulation min. MΩxkm 30.5
Inductance max. mH/km 1
Mutual capacitance
PVCw-insulation CORE max. nF/km 200
XLPE-insulation CORE max. nF/km 125
Test voltage Core/core (Urms
)
Core/shield (Urms
) V
1500
1500
Operating voltage (Urms
) max. V 300
ICON® Instrumentation Control Cable according to UL 13 /2250
Common types
Multi core, overall shield, PVC-jacket
■ unarmored
■ armored
300 V300 V
-
8/20/2019 Icon en Instrumentation Cables
18/76
www.leoni-industrial-projects.com18 The Standard Types Instrumentation Cable
Instrumentation Control Cable to UL 1277
Common types
ICON® Instrumentation Control Cable
TC (to UL 1277)
600 V
plain stranded copper conductors,
cores,
overall static shield
PLTC / ITC (UL 13 / UL 2250)
300 V
plain stranded copper conductors,
cores,
overall static shield
PVCw-insulation or, XLPE-insulation
PVCw-jacket
armoredunarmored (L) shieldarmored(L) shield
PVCwNC-insulation, PVCw-insulation, XLPE-insulation,
PVCw-jacket
unarmored
-
8/20/2019 Icon en Instrumentation Cables
19/76
www.leoni-industrial-projects.com 19The Standard Types Instrumentation Cable
ICON® Instrumentation Cable according to UL 13 / 2250
Common types
Single & Multi pair and Multi triple, individual and/or overall shield, PVC-jacket
■ unarmored
■ armored
300 VICON® Instrumentation Control Cable according to UL 1277
Common types
Multi Core, overall shield, PVC-jacket
■ unarmored
600 V
Technical data
Type of insulation/jacket PVCw/PVCw PVCwNC/PVCw XLPE/PVCw
Type of cabling elements Core
No. of cabling elements 2, 4, 6, 8, 10, 12, 16, 24, 36
Conductor sizes AWG 18/7, AWG 16/7, AWG 14/7
1. Unarmored types RE-Yw(St)Yw-fl RE-Yw4Y(St)Yw-fl RE-2X(St)Yw-fl
Laying Recommended for indoor and outdoor installation,
on racks, trays, in conduits, in dry and wet locations,
for direct burial
Bending radius 7.5 x cable diameter 10 x cable diameter 7.5 x cable diameter
Reaction to fire
Flame propagation
a) Test on single cable
b) Test on bunched cables
UL 13 VW-1 test, IEC 60332-1
UL 1685, IEC 60332-3 part 24 (Cat.C)
Temperature range during operation
during installation
–40 °C up to 90 °C
–5 °C up to 50 °C
Sunlight resistance UL 1581 Section 1200
Oil resistance ICEA S-73-532
Application For transmission of analogue and digital signals in instrument and control systems; UL listed tray cable in compliance
with NEC article 336, for use in hazardous classified locations class I and class II division 2 acc. to NEC 501.10(B) and
NEC 502.10(B), not allowed for direct connection to l ow impedance sources, e.g. public mains electrici ty supply
-
8/20/2019 Icon en Instrumentation Cables
20/76
www.leoni-industrial-projects.com20 The Standard Types Instrumentation Cable
ICON® Instrumentation Cable according to UL 13 / 2250
Common types
Single & Multi pair and Multi triple, individual and/or overall shield, PVC-jacket
■ unarmored
■ armored
300 VICON® Instrumentation Control Cable according to UL 1277
Common types
Multi core, overall shield, PVC-jacket
■ unarmored
Construction
Product types Unarmored types
Conductor Plain annealed copper; 7 stranded
size
Conductor design mm
AWG 18/7
7 x 0.320
AWG 16/7
7 x 0.404
AWG 14/7
7 x 0.620
Insulation materials Polyvinylchloride PVC heat resistant PVCw or
Polyvinylchloride PVC heat resistant PVCw with nylon jacket NC or
Cross linked polyethylene XLPE
Cabling element 1) Core
Wrapping at least one plastic tape above cable core
Overall shield Aluminum/plastic-tape over stranded tinned copper drain wire
Outer jacket PVCw
Color black or blue for intrinsically safe systems
Marking LEONI KERPEN ICON PLTC/ITC SIZE MATERIAL TYPE OF SHIELD UL RATED VOLTAGE
TEMPERATURE RATING SUN RES DIR BUR PRODUCTION LOT CODE LENGTH MARKING IN FEET
1) Color code of cabling elements see page 71 .
600 V
-
8/20/2019 Icon en Instrumentation Cables
21/76
www.leoni-industrial-projects.com 21The Standard Types Instrumentation Cable
ICON® Instrumentation Cable according to UL 13 / 2250
Common types
Single & Multi pair and Multi triple, individual and/or overall shield, PVC-jacket
■ unarmored
■ armored
300 V
ICON® Instrumentation Control Cable according to UL 1277
Common types
Multi core, overall shield, PVC-jacket
■ unarmored
600 V
Electrical Data at 20 °C 600 V
Conductor sizes nom. mm² AWG 18/7 AWG 16/7 AWG 14/7
Conductor resistance max. Ω/km 35.8 22.8 14.3
Insulation resistance at 15 °C PVCw-insulation min. MΩxkm 175
XLPE-insulation min. MΩxkm 810
Inductance max. mH/km 1
Mutual capacitance
PVCw-insulation Core max. nF/km 187
XLPE-insulation Core max. nF/km 120
Test voltage Core/core (Urms
)
Core/shield (Urms
) V
2000, PVCw insulation / 3000, XLPE insulation
2000, PVCw insulation / 3000, XLPE insulation
Operating voltage (Urms
) max. V 600
600 V
-
8/20/2019 Icon en Instrumentation Cables
22/76
www.leoni-industrial-projects.com22 The Standard Types Instrumentation Cable
Instrumentation Cable UL 13 / UL 2250
Flame Retardant, Sunlight Resistant
PLTC/ITC
105 °C / 300 V
Single-Pair, PVC-Insulation, PVC Jacket
RE-YwYw-flApplication
Power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to NEC
501.10(B) and NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct burial.
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG
18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 °C)
Color code................................ black, white, continuously numbered on white core (1, 2, 3..) for multi-
element
Wrapping.................................. at least 1 layer of plastic tape
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 °C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG PVC/PVC 105 °C SUN
RES PRODUCTION LOT CODE LENGTH MARKING IN FEET
Technical data Abbreviations
Flame propagation
- Test on single cable UL13 (VW-1)
- Test on bunched cables UL 1685 (vertical tray)
Gas/vapor tightness outer
jacket
NEC 501.15 (D) and (E)
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 °C)
Oil resistance ICEA S-73-532
Sunlight resistance UL 1581 section 1200
Temperature range
-40°C up to +105°C
(during operation)
-5°C up to +50°C
(during installation)
Min. bending radius - repeated
bending7.5 x cable diameter
RE- Instrumentation Cable
Yw PVC insulation, heat resistant
Yw PVC outer jacket, heat resistant
-fl reduced flame propagation
Electrical Properties at 20 °C
Conductor cross-section (AWG) AWG 14 AWG 16 AWG 18 AWG 20
Conductor resistance max. Ω/km / Ω/1000ft 8.9 / 2.72 14.3 / 4.36 22.8 / 6.93 35.8 / 10.92
Insulation resistance min. MΩ x km /
MΩ x 1000ft
30.5 / 100 (at 15.6 °C)
Inductance max. mH/km 1
L/R ratio max. max. µH/Ω 60 40 25
Test voltage Urms (core : core) V 1500
Test voltage Urms (core : shield) V 1500
Operating voltage V 300
Geometrical data
No. of elements RT of insulation RT outer jacket Outer dia. Weight Part number
nom. nom. approx. approx. Color
(mm / mils) (mm / mils) (mm / in) (kg/km / lbs/1000ft) black
AWG 14 /7
1 0.51 / 20 1.02 / 40 8.0 / 0.32 88 / 60 79030013
AWG 16 /7
1 0.38 / 15 0.89 / 35 6.5 / 0.26 66 / 50 79030012
AWG 18 /7
1 0.38 / 15 0.89 / 35 6.0 / 0.24 55 / 40 79030011
AWG 20 /7
1 0.30 / 12 0.89 / 35 5.2 / 0.20 40 / 30 79030010
RT = Radial Thickness
-
8/20/2019 Icon en Instrumentation Cables
23/76
www.leoni-industrial-projects.com 23The Standard Types Instrumentation Cable
Instrumentation Cable UL 13 / UL 2250
Flame Retardant, Sunlight Resistant
PLTC/ITC
105 °C / 300 V
Single-Triple, PVC-Insulation, PVC Jacket
RE-YwYw-flApplication
Power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to NEC
501.10(B) and NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct burial.
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 16 , AWG 18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 °C)
Color code................................ black, white, red, continuously numbered on white core (1, 2, 3..) for multi-
element
Wrapping.................................. at least 1 layer of plastic tape
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 °C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG PVC/PVC 105 °C SUN
RES PRODUCTION LOT CODE LENGTH MARKING IN FEET
Technical data Abbreviations
Flame propagation
- Test on single cable UL13 (VW-1)
- Test on bunched cables UL 1685 (vertical tray)
Gas/vapor tightness outer
jacket
NEC 501.15 (D) and (E)
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 °C)
Oil resistance ICEA S-73-532
Sunlight resistance UL 1581 section 1200
Temperature range
-40°C up to +105°C
(during operation)
-5°C up to +50°C
(during installation)
Min. bending radius - repeated
bending7.5 x cable diameter
RE- Instrumentation Cable
Yw PVC insulation, heat resistant
Yw PVC outer jacket, heat resistant
-fl reduced flame propagation
Electrical Properties at 20 °C
Conductor cross-section (AWG) AWG 16 AWG 18 AWG 20
Conductor resistance max. Ω/km / Ω/1000ft 14.3 / 4.36 22.8 / 6.93 35.8 / 10.92
Insulation resistance min. MΩ x km /
MΩ x 1000ft
30.5 / 100 (at 15.6 °C)
Mutual capacitance
single element:
2 to 4 elements:
above 4 elements:
nom. nF/km /
nF/1000ft
187 / 57
187 / 57
187 / 57
Inductance max. mH/km 1
L/R ratio max. max. µH/Ω 40 25
Test voltage Urms (core : core) V 1500
Test voltage Urms (core : shield) V 1500
Operating voltage V 300
Geometrical data
No. of elements RT of insulation RT outer jacket Outer dia. Weight Part number
nom. nom. approx. approx. Color
(mm / mils) (mm / mils) (mm / in) (kg/km / lbs/1000ft) black
AWG 16 /7
1 0.38 / 15 0.89 / 35 6.8 / 0.27 80 / 55 79030016
AWG 18 /7
1 0.38 / 15 0.89 / 35 6.3 / 0.25 65 / 45 79030015
AWG 20 /7
1 0.30 / 12 0.89 / 35 5.4 / 0.21 45 / 35 79030014
RT = Radial Thickness
-
8/20/2019 Icon en Instrumentation Cables
24/76
www.leoni-industrial-projects.com24 The Standard Types Instrumentation Cable
Instrumentation Cable UL 13 / UL 2250
Flame Retardant, Sunlight Resistant
PLTC/ITC
105 °C / 300 V
Single & Multi-Pair, PVC-Insulation, Collective Shield, PVC Jacket
RE-Yw(St)Yw-flApplication
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct burial.
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG
18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 °C)
Color code................................ black, white, continuously numbered on white core (1, 2, 3..) for multi-
element
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wireCommunication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 °C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/
PVC*) OS (UL) 105 °C SUN RES PRODUCTION LOT CODE LENGTH
MARKING IN FEET*) single element design without com wire
Technical data Abbreviations
Flame propagation
- Test on single cable UL13 (VW-1)
- Test on bunched cables UL 1685 (vertical tray)Gas/vapor tightness outer
jacket
NEC 501.15 (D) and (E)
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 °C)
Oil resistance ICEA S-73-532
Sunlight resistance UL 1581 section 1200
Temperature range
-40°C up to +105°C
(during operation)-5°C up to +50°C(during installation)
Min. bending radius - repeated
bending
7.5 x cable diameter
RE- Instrumentation Cable
Yw PVC insulation, heat resistant
(St)collective shield
Yw PVC outer jacket, heat resistant
-fl reduced flame propagation
Electrical Properties at 20 °C
Conductor cross-section (AWG) AWG 14 AWG 16 AWG 18 AWG 20
Conductor resistance max. Ω/km / Ω/1000ft 8.9 / 2.72 14.3 / 4.36 22.8 / 6.93 35.8 / 10.92
Insulation resistance min. MΩ x km /
MΩ x 1000ft
30.5 / 100 (at 15.6 °C)
Mutual capacitance
single element:
2 to 4 elements:
above 4 elements:
nom. nF/km /
nF/1000ft
200 / 61
190 / 58
150 / 46
200 / 61
190 / 58
150 / 46
200 / 61
180 / 55
150 / 46
200 / 61
180 / 55
150 / 46
Inductance max. mH/km 1
L/R ratio max. max. µH/Ω 60 40 25
Test voltage Urms (core : core) V 1500
Test voltage Urms (core : shield) V 1500
Operating voltage V 300
-
8/20/2019 Icon en Instrumentation Cables
25/76
www.leoni-industrial-projects.com 25The Standard Types Instrumentation Cable
Instrumentation Cable UL 13 / UL 2250
Flame Retardant, Sunlight Resistant
PLTC/ITC
105 °C / 300 V
Single & Multi-Pair, PVC-Insulation, Collective Shield, PVC Jacket
RE-Yw(St)Yw-flGeometrical data
No. of elements RT of insulation RT outer jacket Outer dia. Weight Part number
nom. nom. approx. approx. Color
(mm / mils) (mm / mils) (mm / in) (kg/km / lbs/1000ft) black
AWG 14 /7
1 0.51 / 20 1.02 / 40 8.2 / 0.32 109 / 75 79960628
2 0.51 / 20 1.27 / 50 12.6 / 0.50 207 / 140 79960629
4 0.51 / 20 1.27 / 50 14.6 / 0.57 318 / 215 79960630
6 0.51 / 20 1.52 / 60 18.0 / 0.71 492 / 325 79960631
8 0.51 / 20 1.52 / 60 19.1 / 0.75 578 / 390 79960632
10 0.51 / 20 1.52 / 60 21.7 / 0.85 705 / 475 79960633
12 0.51 / 20 1.78 / 70 23.3 / 0.92 851 / 575 79960634
16 0.51 / 20 1.78 / 70 26.4 / 1.04 1095 / 740 79960635
24 0.51 / 20 1.78 / 70 31.4 / 1.24 1548 / 1040 79960636
36 0.51 / 20 2.03 / 80 38.6 / 1.52 2299 / 1545 79960637
AWG 16 /7
1 0.38 / 15 0.89 / 35 6.7 / 0.26 69 / 55 79960000
2 0.38 / 15 1.27 / 50 10.8 / 0.43 146 / 95 79960001
4 0.38 / 15 1.27 / 50 12.5 / 0.50 217 / 145 79960002
6 0.38 / 15 1.27 / 50 14.8 / 0.58 297 / 195 79960254
8 0.38 / 15 1.52 / 60 16.1 / 0.64 384 / 260 79960003
10 0.38 / 15 1.52 / 60 18.2 / 0.72 460 / 310 79960255
12 0.38 / 15 1.52 / 60 18.8 / 0.74 533 / 355 79960004
16 0.38 / 15 1.52 / 60 21.1 / 0.83 680 / 455 79960005
24 0.38 / 15 1.78 / 70 25.4 / 1.01 1002 / 670 79960006
36 0.38 / 15 1.78 / 70 30.3 / 1.20 1433 / 955 79960007
AWG 18 /7
1 0.38 / 15 0.89 / 35 6.2 / 0.24 54 / 45 79960008
2 0.38 / 15 1.02 / 40 9.3 / 0.37 105 / 75 79960009
4 0.38 / 15 1.27 / 50 11.4 / 0.45 171 / 115 79960010
6 0.38 / 15 1.27 / 50 13.5 / 0.53 230 / 155 79960252
8 0.38 / 15 1.27 / 50 14.1 / 0.56 280 / 185 79960011
10 0.38 / 15 1.52 / 60 16.5 / 0.65 350 / 240 79960253
12 0.38 / 15 1.52 / 60 17.0 / 0.67 409 / 275 79960012
16 0.38 / 15 1.52 / 60 19.0 / 0.75 518 / 350 7996001324 0.38 / 15 1.78 / 70 23.1 / 0.91 776 / 505 79960014
36 0.38 / 15 1.78 / 70 28.6 / 1.07 1086 / 720 79960015
AWG 20 /7
1 0.30 / 12 0.89 / 35 5.3 / 0.21 39 / 35 79960016
2 0.30 / 12 1.02 / 40 8.0 / 0.31 76 / 55 79960017
4 0.30 / 12 1.02 / 40 8.8 / 0.36 109 / 75 79960018
6 0.30 / 12 1.27 / 50 11.3 / 0.44 160 / 110 79960250
8 0.30 / 12 1.27 / 50 11.8 / 0.47 194 / 130 79960019
10 0.30 / 12 1.27 / 50 13.3 / 0.52 225 / 155 79960251
12 0.30 / 12 1.27 / 50 13.7 / 0.54 263 / 175 79960020
16 0.30 / 12 1.52 / 60 15.8 / 0.63 355 / 240 79960021
24 0.30 / 12 1.52 / 60 18.6 / 0.73 488 / 325 79960022
36 0.30 / 12 1.52 / 60 21.8 / 0.86 693 / 460 79960023
RT = Radial Thickness
-
8/20/2019 Icon en Instrumentation Cables
26/76
www.leoni-industrial-projects.com26 The Standard Types Instrumentation Cable
Instrumentation Cable UL 13 / UL 2250
Flame Retardant, Sunlight Resistant
PLTC/ITC
105 °C / 300 V
Multi-Pair, PVC-Insulation, Individual & Collective Shield, PVC Jacket
RE-Yw(St)Yw-fl PiMFApplication
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct burial.
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG
18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 °C)
Color code................................ black, white, continuously numbered on white core (1, 2, 3..) for multi-
element
Individual shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Wrapping.................................. at least 1 layer of plastic tapeCollective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 °C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/PVC
SPOS (UL) 105 °C SUN RES PRODUCTION LOT CODE LENGTH
MARKING IN FEET
Technical data Abbreviations
Flame propagation
- Test on single cable UL13 (VW-1)
- Test on bunched cables UL 1685 (vertical tray)Gas/vapor tightness outer
jacket
NEC 501.15 (D) and (E)
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 °C)
Oil resistance ICEA S-73-532
Sunlight resistance UL 1581 section 1200
Temperature range
-40°C up to +105°C
(during operation)
-5°C up to +50°C
(during installation)
Min. bending radius - repeated
bending
7.5 x cable diameter
RE- Instrumentation Cable
Yw PVC insulation, heat resistant
(St) collective shield
Yw PVC outer jacket, heat resistant
-fl reduced flame propagation
PiMF pair in metal foil
Electrical Properties at 20 °C
Conductor cross-section (AWG) AWG 14 AWG 16 AWG 18 AWG 20
Conductor resistance max. Ω/km / Ω/1000ft 8.9 / 2.72 14.3 / 4.36 22.8 / 6.93 35.8 / 10.92
Insulation resistance min. MΩ x km /
MΩ x 1000ft
30.5 / 100 (at 15.6 °C)
Mutual capacitance nom. nF/km /
nF/1000ft
200 / 61 200 / 61 200 / 61 200 / 61
Inductance max. mH/km 1
L/R ratio max. max. µH/Ω 60 40 25
Test voltage Urms (core : core) V 1500
Test voltage Urms (core : shield) V 1500
Operating voltage V 300
-
8/20/2019 Icon en Instrumentation Cables
27/76
www.leoni-industrial-projects.com 27The Standard Types Instrumentation Cable
Instrumentation Cable UL 13 / UL 2250
Flame Retardant, Sunlight Resistant
PLTC/ITC
105 °C / 300 V
Multi-Pair, PVC-Insulation, Individual & Collective Shield, PVC Jacket
RE-Yw(St)Yw-fl PiMFGeometrical data
No. of elements RT of insulation RT outer jacket Outer dia. Weight Part number
nom. nom. approx. approx. Color
(mm / mils) (mm / mils) (mm / in) (kg/km / lbs/1000ft) black
AWG 14 /7
2 0.51 / 20 1.27 / 50 13.9 / 0.55 238 / 160 79960638
4 0.51 / 20 1.52 / 60 16.7 / 0.66 387 / 260 79960639
6 0.51 / 20 1.52 / 60 20.0 / 0.79 552 / 375 79960640
8 0.51 / 20 1.52 / 60 21.3 / 0.84 687 / 465 79960641
10 0.51 / 20 1.78 / 70 24.7 / 0.97 857 / 580 79960642
12 0.51 / 20 1.78 / 70 26.4 / 1.04 987 / 665 79960643
16 0.51 / 20 1.78 / 70 29.7 / 1.17 1271 / 855 79960644
24 0.51 / 20 2.03 / 80 36.0 / 1.42 1871 / 1285 79960645
36 0.51 / 20 2.29 / 90 43.4 / 1.71 2911 / 1960 79960646
AWG 16 /7
2 0.38 / 15 1.27 / 50 12.1 / 0.48 170 / 115 79960024
4 0.38 / 15 1.27 / 50 14.2 / 0.56 259 / 170 79960025
6 0.38 / 15 1.52 / 60 17.3 / 0.69 388 / 255 79960260
8 0.38 / 15 1.52 / 60 18.4 / 0.72 470 / 310 79960026
10 0.38 / 15 1.52 / 60 20.8 / 0.82 570 / 370 79960261
12 0.38 / 15 1.52 / 60 21.6 / 0.85 641 / 420 79960027
16 0.38 / 15 1.78 / 70 24.8 / 0.98 861 / 565 79960028
24 0.38 / 15 1.78 / 70 29.4 / 1.16 1208 / 800 79960029
36 0.38 / 15 2.03 / 80 35.4 / 1.40 1792 / 1175 79960030
AWG 18 /7
2 0.38 / 15 1.27 / 50 11.4 / 0.44 144 / 100 79960031
4 0.38 / 15 1.27 / 50 13.1 / 0.52 210 / 145 79960032
6 0.38 / 15 1.52 / 60 16.0 / 0.63 305 / 205 79960258
8 0.38 / 15 1.52 / 60 17.0 / 0.67 381 / 250 79960033
10 0.38 / 15 1.52 / 60 19.1 / 0.75 450 / 305 79960259
12 0.38 / 15 1.52 / 60 19.8 / 0.78 514 / 340 79960034
16 0.38 / 15 1.78 / 70 22.7 / 0.90 687 / 455 79960035
24 0.38 / 15 1.78 / 70 26.9 / 1.06 968 / 640 79960036
36 0.38 / 15 2.03 / 80 32.4 / 1.28 1411 / 935 79960037
AWG 20 /72 0.30 / 12 1.02 / 40 8.9 / 0.36 94 / 65 79960038
4 0.30 / 12 1.27 / 50 11.2 / 0.44 152 / 345 79960039
6 0.30 / 12 1.27 / 50 13.1 / 0.52 209 / 135 79960256
8 0.30 / 12 1.27 / 50 13.7 / 0.54 253 / 165 79960040
10 0.30 / 12 1.52 / 60 16.0 / 0.63 310 / 210 79960257
12 0.30 / 12 1.52 / 60 16.6 / 0.65 357 / 240 79960041
16 0.30 / 12 1.52 / 60 18.5 / 0.73 455 / 300 79960042
24 0.30 / 12 1.52 / 60 21.8 / 0.86 662 / 415 79960043
36 0.30 / 12 1.78 / 70 26.4 / 1.04 936 / 615 79960044
RT = Radial Thickness
-
8/20/2019 Icon en Instrumentation Cables
28/76
www.leoni-industrial-projects.com28 The Standard Types Instrumentation Cable
Instrumentation Cable UL 13 / UL 2250
Flame Retardant, Sunlight Resistant
PLTC/ITC
105 °C / 300 V
Single & Multi-Triple, PVC-Insulation, Collective Shield, PVC Jacket
RE-Yw(St)Yw-flApplication
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct burial.
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG
18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 °C)
Color code................................ black, white, red, continuously numbered on white core (1, 2, 3..) for multi-
element
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wireCommunication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 °C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/
PVC*) OS (UL) 105 °C SUN RES PRODUCTION LOT CODE LENGTH
MARKING IN FEET*) single element design without com wire
Technical data Abbreviations
Flame propagation
- Test on single cable UL13 (VW-1)
- Test on bunched cables UL 1685 (vertical tray)Gas/vapor tightness outer
jacket
NEC 501.15 (D) and (E)
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 °C)
Oil resistance ICEA S-73-532
Sunlight resistance UL 1581 section 1200
Temperature range
-40°C up to +105°C
(during operation)
-5°C up to +50°C
(during installation)
Min. bending radius - repeated
bending
7.5 x cable diameter
RE- Instrumentation Cable
Yw PVC insulation, heat resistant
(St) collective shield
Yw PVC outer jacket, heat resistant
-fl reduced flame propagation
Electrical Properties at 20 °C
Conductor cross-section (AWG) AWG 14 AWG 16 AWG 18 AWG 20
Conductor resistance max. Ω/km / Ω/1000ft 8.9 / 2.72 14.3 / 4.36 22.8 / 6.93 35.8 / 10.92
Insulation resistance min. MΩ x km /
MΩ x 1000ft
30.5 / 100 (at 15.6 °C)
Mutual capacitance
single element:
2 to 4 elements:
above 4 elements:
nom. nF/km /
nF/1000ft
200 / 61
190 / 58
150 / 46
200 / 61
190 / 58
150 / 46
200 / 61
180 / 55
150 / 46
200 / 61
180 / 55
150 / 46
Inductance max. mH/km 1
L/R ratio max. max. µH/Ω 60 40 25
Test voltage Urms (core : core) V 1500
Test voltage Urms (core : shield) V 1500
Operating voltage V 300
-
8/20/2019 Icon en Instrumentation Cables
29/76
www.leoni-industrial-projects.com 29The Standard Types Instrumentation Cable
Instrumentation Cable UL 13 / UL 2250
Flame Retardant, Sunlight Resistant
PLTC/ITC
105 °C / 300 V
Single & Multi-Triple, PVC-Insulation, Collective Shield, PVC Jacket
RE-Yw(St)Yw-flGeometrical data
No. of elements RT of insulation RT outer jacket Outer dia. Weight Part number
nom. nom. approx. approx. Color
(mm / mils) (mm / mils) (mm / in) (kg/km / lbs/1000ft) black
AWG 14 /7
1 0.51 / 20 1.02 / 40 8.6 / 0.35 134 / 90 79960647
2 0.51 / 20 1.27 / 50 14.0 / 0.55 275 / 185 79960648
4 0.51 / 20 1.52 / 60 16.5 / 0.65 454 / 305 79960649
6 0.51 / 20 1.52 / 60 21.2 / 0.84 663 / 450 79960650
8 0.51 / 20 1.78 / 70 23.2 / 0.91 848 / 570 79960651
10 0.51 / 20 1.78 / 70 24.1 / 0.95 1010 / 680 79960652
12 0.51 / 20 1.78 / 70 26.8 / 1.05 1191 / 805 7996065316 0.51 / 20 1.78 / 70 30.2 / 1.19 1546 / 1040 79960654
24 0.51 / 20 2.03 / 80 36.5 / 1.44 2274 / 1530 79960655
36 0.51 / 20 2.29 / 90 44.0 / 1.73 3349 / 2250 79960656
AWG 16 /7
1 0.38 / 15 1.02 / 40 7.2 / 0.28 90 / 65 79960045
2 0.38 / 15 1.27 / 50 11.9 / 0.47 180 / 125 79960046
4 0.38 / 15 1.27 / 50 13.7 / 0.54 288 / 195 79960047
6 0.38 / 15 1.52 / 60 17.3 / 0.68 420 / 285 79960266
8 0.38 / 15 1.52 / 60 18.4 / 0.72 525 / 355 79960048
10 0.38 / 15 1.52 / 60 20.6 / 0.81 647 / 430 79960267
12 0.38 / 15 1.52 / 60 21.2 / 0.83 749 / 495 79960049
16 0.38 / 15 1.78 / 70 24.3 / 0.96 995 / 660 79960050
24 0.38 / 15 1.78 / 70 28.9 / 1.14 1400 / 945 79960051
36 0.38 / 15 2.03 / 80 34.9 / 1.37 2060 / 1385 79960052
AWG 18 /7
1 0.38 / 15 0.89 / 35 6.5 / 0.26 66 / 50 79960053
2 0.38 / 15 1.27 / 50 10.8 / 0.43 170 / 115 79960054
4 0.38 / 15 1.27 / 50 12.4 / 0.49 223 / 150 79960055
6 0.38 / 15 1.27 / 50 15.2 / 0.60 315 / 215 79960264
8 0.38 / 15 1.52 / 60 16.7 / 0.66 413 / 270 79960056
10 0.38 / 15 1.52 / 60 18.6 / 0.74 492 / 330 79960265
12 0.38 / 15 1.52 / 60 19.2 / 0.76 564 / 380 79960057
16 0.38 / 15 1.52 / 60 21.5 / 0.85 722 / 485 7996005824 0.38 / 15 1.78 / 70 26.1 / 1.03 1055 / 710 79960059
36 0.38 / 15 1.78 / 70 30.8 / 1.22 1518 / 1015 79960060
-
8/20/2019 Icon en Instrumentation Cables
30/76
www.leoni-industrial-projects.com30 The Standard Types Instrumentation Cable
Instrumentation Cable UL 13 / UL 2250
Flame Retardant, Sunlight Resistant
PLTC/ITC
105 °C / 300 V
Multi-Triple, PVC-Insulation, Individual & Collective Shield, PVC Jacket
RE-Yw(St)Yw-fl TiMFApplication
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct burial.
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG
18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 °C)
Color code................................ black, white, red, continuously numbered on white core (1, 2, 3..) for multi-
element
Individual shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Wrapping.................................. at least 1 layer of plastic tapeCollective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 °C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/PVC
STOS (UL) 105 °C SUN RES PRODUCTION LOT CODE LENGTH
MARKING IN FEET
Technical data Abbreviations
Flame propagation
- Test on single cable UL13 (VW-1)
- Test on bunched cables UL 1685 (vertical tray)Gas/vapor tightness outer
jacket
NEC 501.15 (D) and (E)
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 °C)
Oil resistance ICEA S-73-532
Sunlight resistance UL 1581 section 1200
Temperature range
-40°C up to +105°C
(during operation)
-5°C up to +50°C
(during installation)
Min. bending radius - repeated
bending
7.5 x cable diameter
RE- Instrumentation Cable
Yw PVC insulation, heat resistant
(St) collective shield
Yw PVC outer jacket, heat resistant
-fl reduced flame propagation
TiMF triple in metal foil
Electrical Properties at 20 °C
Conductor cross-section (AWG) AWG 14 AWG 16 AWG 18 AWG 20
Conductor resistance max. Ω/km / Ω/1000ft 8.9 / 2.72 14.3 / 4.36 22.8 / 6.93 35.8 / 10.92
Insulation resistance min. MΩ x km /
MΩ x 1000ft
30.5 / 100 (at 15.6 °C)
Mutual capacitance nom. nF/km /
nF/1000ft
200 / 61 200 / 61 200 / 61 200 / 61
Inductance max. mH/km 1
L/R ratio max. max. µH/Ω 60 40 25
Test voltage Urms (core : core) V 1500
Test voltage Urms (core : shield) V 1500
Operating voltage V 300
-
8/20/2019 Icon en Instrumentation Cables
31/76
www.leoni-industrial-projects.com 31The Standard Types Instrumentation Cable
Instrumentation Cable UL 13 / UL 2250
Flame Retardant, Sunlight Resistant
PLTC/ITC
105 °C / 300 V
Multi-Triple, PVC-Insulation, Individual & Collective Shield, PVC Jacket
RE-Yw(St)Yw-fl TiMFGeometrical data
No. of elements RT of insulation RT outer jacket Outer dia. Weight Part number
nom. nom. approx. approx. Color
(mm / mils) (mm / mils) (mm / in) (kg/km / lbs/1000ft) black
AWG 14 /7
2 0.51 / 20 1.52 / 60 16.5 / 0.65 324 / 220 79960657
4 0.51 / 20 1.52 / 60 18.9 / 0.75 513 / 345 79960658
6 0.51 / 20 1.78 / 70 24.0 / 0.94 773 / 520 79960659
8 0.51 / 20 1.78 / 70 25.0 / 0.98 959 / 645 79960660
10 0.51 / 20 1.78 / 70 28.2 / 1.11 1162 / 785 79960661
12 0.51 / 20 1.78 / 70 29.2 / 1.15 1327 / 895 79960662
16 0.51 / 20 2.03 / 80 33.6 / 1.32 1766 / 1190 79960663
24 0.51 / 20 2.03 / 80 40.1 / 1.58 2550 / 1715 79960664
36 0.51 / 20 2.29 / 90 48.7 / 1.96 3756 / 2525 79960665
AWG 16 /7
2 0.38 / 15 1.27 / 50 13.3 / 0.52 215 / 145 79960069
4 0.38 / 15 1.52 / 60 15.9 / 0.63 350 / 230 79960070
6 0.38 / 15 1.52 / 60 19.6 / 0.77 490 / 330 79960272
8 0.38 / 15 1.52 / 60 20.9 / 0.82 610 / 410 79960071
10 0.38 / 15 1.78 / 70 24.1 / 0.95 791 / 520 79960273
12 0.38 / 15 1.78 / 70 24.7 / 0.97 891 / 585 79960072
16 0.38 / 15 1.78 / 70 27.7 / 1.09 1145 / 755 79960073
24 0.38 / 15 2.03 / 80 33.5 / 1.32 1650 / 1110 79960074
36 0.38 / 15 2.03 / 80 39.8 / 1.57 2365 / 1590 79960075
AWG 18 /7
2 0.38 / 15 1.27 / 50 12.3 / 0.48 172 / 115 79960076
4 0.38 / 15 1.27 / 50 14.2 / 0.56 260 / 175 79960077
6 0.38 / 15 1.52 / 60 18.0 / 0.71 395 / 270 79960270
8 0.38 / 15 1.52 / 60 19.1 / 0.75 491 / 325 79960078
10 0.38 / 15 1.52 / 60 21.5 / 0.85 585 / 395 79960271
12 0.38 / 15 1.78 / 70 22.7 / 0.89 702 / 465 79960079
16 0.38 / 15 1.78 / 70 25.3 / 1.00 898 / 595 79960080
24 0.38 / 15 1.78 / 70 30.1 / 1.19 1268 / 845 79960081
36 0.38 / 15 2.03 / 80 36.3 / 1.43 1840 / 1240 79960082
AWG 20 /72 0.30 / 12 1.27 / 50 10.4 / 0.41 120 / 85 79960083
4 0.30 / 12 1.27 / 50 12.0 / 0.47 180 / 125 79960084
6 0.30 / 12 1.27 / 50 14.6 / 0.57 250 / 170 79960268
8 0.30 / 12 1.52 / 60 16.1 / 0.63 335 / 230 79960085
10 0.30 / 12 1.52 / 60 17.9 / 0.70 400 / 270 79960269
12 0.30 / 12 1.52 / 60 18.4 / 0.72 450 / 305 79960086
16 0.30 / 12 1.52 / 60 20.6 / 0.81 628 / 385 79960087
24 0.30 / 12 1.78 / 70 25.0 / 0.98 835 / 565 79960088
36 0.30 / 12 1.78 / 70 29.6 / 1.17 1190 / 800 79960089
RT = Radial Thickness
-
8/20/2019 Icon en Instrumentation Cables
32/76
www.leoni-industrial-projects.com32 The Standard Types Instrumentation & Control Cable
Instrumentation Cable UL 13 / UL 2250
Flame Retardant, Sunlight Resistant
PLTC/ITC
105 °C / 300 V
Single & Multi-Pair, PVC-Insulation, Collective Shield, Armor, PVC Jacket
RE-Yw(St)YwSWAYw-flApplication
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
For indoor and outdoor installation in cable trays or in raceways. Not recommended for direct burial.
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG
18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 °C)
Color code................................ black, white, continuously numbered on white core (1, 2, 3..) for multi-
element
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wireInner jacket 1........................... heat resistant polyvinyl chloride PVC (105 °C), black
Armor....................................... galvanized round steel wires
Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 °C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/
PVC*) OS (UL) 105 °C SUN RES PRODUCTION LOT CODE LENGTH
MARKING IN FEET*) single element design without com wire
Technical data Abbreviations
Flame propagation- Test on single cable UL13 (VW-1)
- Test on bunched cables UL 1685 (vertical tray)
Gas/vapor tightness outer jacket
NEC 501.15 (D) and (E)
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 °C)
Oil resistance ICEA S-73-532
Sunlight resistance UL 1581 section 1200
Temperature range-40°C up to +105°C(during operation)
-5°C up to +50°C
(during installation)
Min. bending radius - repeated
bending
10 x cable diameter
RE-Instrumentation Cable
Yw PVC insulation, heat resistant
(St) collective shield
Yw PVC inner jacket, heat resistant
SWA steel wire armor
Yw PVC outer jacket, heat resistant
-fl reduced flame propagation
Electrical Properties at 20 °C
Conductor cross-section (AWG) AWG 14 AWG 16 AWG 18 AWG 20
Conductor resistance max. Ω/km / Ω/1000ft 8.9 / 2.72 14.3 / 4.36 22.8 / 6.93 35.8 / 10.92Insulation resistance min. MΩ x km /
MΩ x 1000ft
30.5 / 100 (at 15.6 °C)
Mutual capacitance
single element:2 to 4 elements:
above 4 elements:
nom. nF/km /
nF/1000ft
200 / 61190 / 58
160 / 49
200 / 61190 / 58
160 / 49
200 / 61180 / 55
150 / 46
200 / 61180 / 55
150 / 46
Inductance max. mH/km 1
L/R ratio max. max. µH/Ω 60 40 25
Test voltage Urms (core : core) V 1500
Test voltage Urms (core : shield) V 1500
O eratin volta e V 300
-
8/20/2019 Icon en Instrumentation Cables
33/76
www.leoni-industrial-projects.com 33The Standard Types Instrumentation & Control Cable
Instrumentation Cable UL 13 / UL 2250
Flame Retardant, Sunlight Resistant
PLTC/ITC
105 °C / 300 V
Single & Multi-Pair, PVC-Insulation, Collective Shield, Armor, PVC Jacket
RE-Yw(St)YwSWAYw-flGeometrical data
No. of
elements
RT of
insulation
RT of inner
jacket 1
Dia. over
inner jacket 1
Dia. of
armor wire
RT outer jacket Outer dia. Weight Part number
nom. nom. nom. nom. nom. approx. approx. Color
(mm / mils) (mm / mils) (mm / in) (mm) (mm / mils) (mm / in) (kg/km /
lbs/1000ft)
black
AWG 14 /7
1 0.51 / 20 1.02 / 40 8.1 / 0.32 0.9 1.27 / 50 12.5 / 0.49 319 / 215 79840471
2 0.51 / 20 1.27 / 50 12.6 / 0.50 0.9 1.52 / 60 17.5 / 0.69 540 / 365 79840472
4 0.51 / 20 1.27 / 50 14.6 / 0.58 0.9 1.52 / 60 19.5 / 0.77 700 / 475 79840473
6 0.51 / 20 1.52 / 60 18.0 / 0.71 1.25 1.78 / 70 24.1 / 0.95 1097 / 740 79840474
8 0.51 / 20 1.52 / 60 19.1 / 0.75 1.25 1.78 / 70 25.2 / 0.99 1234 / 830 7984047510 0.51 / 20 1.52 / 60 21.7 / 0.86 1.25 1.78 / 70 27.8 / 1.09 1440 / 970 79840476
12 0.51 / 20 1.78 / 70 23.3 / 0.92 1.25 1.78 / 70 29.3 / 1.15 1649 / 1100 79840477
16 0.51 / 20 1.78 / 70 26.4 / 1.04 1.6 2.03 / 80 33.6 / 1.32 2213 / 1490 79840478
24 0.51 / 20 1.78 / 70 31.4 / 1.23 1.6 2.03 / 80 38.6 / 1.52 2845 / 1915 79840479
36 0.51 / 20 2.03 / 80 38.6 / 1.52 2 2.29 / 90 47.1 / 1.85 4256 / 2860 79840480
AWG 16 /7
1 0.38 / 15 0.89 / 35 6.7 / 0.26 0.9 1.27 / 50 11.0 / 0.43 248 / 175 79840000
2 0.38 / 15 1.27 / 50 10.6 / 0.43 0.9 1.27 / 50 15.0 / 0.59 414 / 285 79840001
4 0.38 / 15 1.27 / 50 12.6 / 0.50 0.9 1.52 / 60 17.4 / 0.69 555 / 375 79840002
6 0.38 / 15 1.27 / 50 14.8 / 0.58 0.9 1.52 / 60 19.7 / 0.77 694 / 470 79840254
8 0.38 / 15 1.52 / 60 16.2 / 0.64 1.25 1.52 / 60 21.8 / 0.85 924 / 620 79840003
10 0.38 / 15 1.52 / 60 18.2 / 0.72 1.25 1.78 / 70 24.3 / 0.96 1097 / 740 79840255
12 0.38 / 15 1.52 / 60 18.9 / 0.74 1.25 1.78 / 70 25.0 / 0.98 1222 / 800 79840004
16 0.38 / 15 1.52 / 60 21.2 / 0.83 1.25 1.78 / 70 27.3 / 1.07 1402 / 945 79840005
24 0.38 / 15 1.78 / 70 25.6 / 1.01 1.6 2.03 / 80 32.8 / 1.30 2080 / 1400 79840006
36 0.38 / 15 1.78 / 70 30.4 / 1.20 1.6 2.03 / 80 37.6 / 1.48 2696 / 1815 79840007
AWG 18 /7
1 0.38 / 15 0.89 / 35 6.1 / 0.24 0.9 1.27 / 50 10.4 / 0.41 235 / 160 79840008
2 0.38 / 15 1.02 / 40 9.4 / 0.37 0.9 1.27 / 50 13.8 / 0.54 343 / 235 79840009
4 0.38 / 15 1.27 / 50 11.3 / 0.45 0.9 1.52 / 60 16.2 / 0.64 474 / 330 79840010
6 0.38 / 15 1.27 / 50 13.4 / 0.53 0.9 1.52 / 60 18.3 / 0.72 597 / 400 79840252
8 0.38 / 15 1.27 / 50 14.2 / 0.56 0.9 1.52 / 60 19.1 / 0.75 654 / 445 79840011
10 0.38 / 15 1.52 / 60 16.5 / 0.65 1.25 1.52 / 60 22.1 / 0.87 905 / 615 7984025312 0.38 / 15 1.52 / 60 17.1 / 0.67 1.25 1.78 / 70 23.2 / 0.91 1000 / 680 79840012
16 0.38 / 15 1.52 / 60 19.1 / 0.75 1.25 1.78 / 70 25.2 / 0.99 1174 / 790 79840013
24 0.38 / 15 1.78 / 70 23.1 / 0.91 1.25 1.78 / 70 29.1 / 1.15 1542 / 1040 79840014
36 0.38 / 15 1.78 / 70 27.3 / 1.07 1.6 2.03 / 80 34.5 / 1.36 2218 / 1520 79840015
AWG 20 /7
1 0.30 / 12 0.89 / 35 5.3 / 0.21 0.9 1.02 / 40 9.1 / 0.36 185 / 125 79840016
2 0.30 / 12 1.02 / 40 8.0 / 0.31 0.9 1.27 / 50 12.4 / 0.48 285 / 195 79840017
4 0.30 / 12 1.02 / 40 9.2 / 0.36 0.9 1.27 / 50 13.6 / 0.53 348 / 240 79840018
6 0.30 / 12 1.27 / 50 11.3 / 0.44 0.9 1.52 / 60 16.2 / 0.63 470 / 320 79840250
8 0.30 / 12 1.27 / 50 11.9 / 0.47 0.9 1.52 / 60 16.8 / 0.66 513 / 350 79840019
10 0.30 / 12 1.27 / 50 13.3 / 0.52 0.9 1.52 / 60 18.2 / 0.71 585 / 395 79840251
12 0.30 / 12 1.27 / 50 13.8 / 0.54 0.9 1.52 / 60 18.7 / 0.73 626 / 455 79840020
16 0.30 / 12 1.52 / 60 15.9 / 0.63 1.25 1.78 / 70 22.0 / 0.84 879 / 595 79840021
24 0.30 / 12 1.52 / 60 18.6 / 0.73 1.25 1.78 / 70 24.7 / 0.97 1130 / 760 79840022
36 0.30 / 12 1.52 / 60 21.9 / 0.86 1.25 1.78 / 70 28.0 / 1.10 1439 / 970 79840023
RT = Radial Thickness
-
8/20/2019 Icon en Instrumentation Cables
34/76
www.leoni-industrial-projects.com34 The Standard Types Instrumentation & Control Cable
Instrumentation Cable UL 13 / UL 2250
Flame Retardant, Sunlight Resistant
PLTC/ITC
105 °C / 300 V
Multi-Pair, PVC-Insulation, Individual & Collective Shield, Armor, PVC Jacket
RE-Yw(St)YwSWAYw-fl PiMFApplication
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
For indoor and outdoor installation in cable trays or in raceways. Not recommended for direct burial.
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG
18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 °C)
Color code................................ black, white, continuously numbered on white core (1, 2, 3..) for multi-
element
Individual shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Wrapping.................................. at least 1 layer of plastic tapeCollective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Inner jacket 1........................... heat resistant polyvinyl chloride PVC (105 °C), black
Armor....................................... galvanized round steel wires
Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 °C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/PVC
SPOS (UL) 105 °C SUN RES PRODUCTION LOT CODE LENGTH
MARKING IN FEET
Technical data Abbreviations
Flame propagation- Test on single cable UL13 (VW-1)
- Test on bunched cables UL 1685 (vertical tray)
Gas/vapor tightness outer
jacket
NEC 501.15 (D) and (E)
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 °C)
Oil resistance ICEA S-73-532
Sunlight resistance UL 1581 section 1200
Temperature range-40°C up to +105°C
(during operation)
-5°C up to +50°C
(during installation)
Min. bending radius - repeated
bending
10 x cable diameter
RE-
Instrumentation CableYw PVC insulation, heat resistant
(St) collective shield
Yw PVC inner jacket, heat resistant
SWA steel wire armor
Yw PVC outer jacket, heat resistant
-fl reduced flame propagation
PiMF pair in metal foil
Electrical Properties at 20 °C
Conductor cross-section (AWG) AWG 14 AWG 16 AWG 18 AWG 20
Conductor resistance max. Ω/km / Ω/1000ft 8.9 / 2.72 14.3 / 4.36 22.8 / 6.93 35.8 / 10.92Insulation resistance min. MΩ x km /
MΩ x 1000ft
30.5 / 100 (at 15.6 °C)
Mutual capacitance nom. nF/km /
nF/1000ft
200 / 61 200 / 61 200 / 61 200 / 61
Inductance max. mH/km 1
L/R ratio max. max. µH/Ω 60 40 25
Test voltage Urms (core : core) V 1500
Test voltage Urms (core : shield) V 1500
Operating voltage V 300
-
8/20/2019 Icon en Instrumentation Cables
35/76
www.leoni-industrial-projects.com 35The Standard Types Instrumentation & Control Cable
Instrumentation Cable UL 13 / UL 2250
Flame Retardant, Sunlight Resistant
PLTC/ITC
105 °C / 300 V
Multi-Pair, PVC-Insulation, Individual & Collective Shield, Armor, PVC Jacket
RE-Yw(St)YwSWAYw-fl PiMFGeometrical data
No. of
elements
RT of
insulation
RT of inner
jacket 1
Dia. over
inner jacket 1
Dia. of
armor wire
RT outer jacket Outer dia. Weight Part number
nom. nom. nom. nom. nom. approx. approx. Color
(mm / mils) (mm / mils) (mm / in) (mm) (mm / mils) (mm / in) (kg/km /
lbs/1000ft)
black
AWG 14 /7
2 0.51 / 20 1.27 / 50 14.1 / 0.56 0.9 1.52 / 60 19.0 / 0.75 605 / 410 79840124
4 0.51 / 20 1.52 / 60 16.7 / 0.66 1.25 1.78 / 70 22.8 / 0.90 965 / 650 79840482
6 0.51 / 20 1.52 / 60 20.0 / 0.79 1.25 1.78 / 70 26.1 / 1.03 1234 / 830 79840483
8 0.51 / 20 1.52 / 60 21.3 / 0.84 1.25 1.78 / 70 27.4 / 1.08 1417 / 955 79840484
10 0.51 / 20 1.78 / 70 24.7 / 0.97 1.25 1.78 / 70 30.7 / 1.21 1692 / 1140 7984048512 0.51 / 20 1.78 / 70 26.4 / 1.04 1.6 2.03 / 80 33.6 / 1.32 2106 / 1415 79840486
16 0.51 / 20 1.78 / 70 29.7 / 1.17 1.6 2.03 / 80 36.9 / 1.45 2518 / 1695 79840487
24 0.51 / 20 2.03 / 80 36.0 / 1.42 2 2.29 / 90 44.5 / 1.75 3763 / 2530 79840488
36 0.51 / 20 2.29 / 90 43.4 / 1.71 2 2.54 / 100 52.5 / 2.06 5166 / 3475 79840490
AWG 16 /7
2 0.38 / 15 1.27 / 50 12.2 / 0.48 0.9 1.52 / 60 17.0 / 0.67 495 / 335 79840024
4 0.38 / 15 1.27 / 50 14.3 / 0.56 0.9 1.52 / 60 19.2 / 0.75 633 / 430 79840025
6 0.38 / 15 1.52 / 60 17.3 / 0.69 1.25 1.78 / 70 23.4 / 0.93 1014 / 665 79840260
8 0.38 / 15 1.52 / 60 18.4 / 0.72 1.25 1.78 / 70 24.5 / 0.96 1097 / 740 79840026
10 0.38 / 15 1.52 / 60 20.8 / 0.82 1.25 1.78 / 70 26.9 / 1.06 1272 / 860 79840261
12 0.38 / 15 1.52 / 60 21.6 / 0.85 1.25 1.78 / 70 27.7 / 1.09 1375 / 930 79840027
16 0.38 / 15 1.78 / 70 24.9 / 0.98 1.25 1.78 / 70 30.9 / 1.22 1692 / 1140 79840028
24 0.38 / 15 1.78 / 70 29.4 / 1.16 1.6 2.03 / 80 36.6 / 1.44 2422 / 1630 79840029
36 0.38 / 15 2.03 / 80 36.5 / 1.40 2 2.29 / 90 45.0 / 1.74 3645 / 2450 79840030
AWG 18 /7
2 0.38 / 15 1.27 / 50 11.3 / 0.44 0.9 1.52 / 60 16.2 / 0.63 446 / 305 79840031
4 0.38 / 15 1.27 / 50 13.1 / 0.52 0.9 1.52 / 60 18.0 / 0.71 557 / 380 79840032
6 0.38 / 15 1.52 / 60 16.0 / 0.63 1.25 1.52 / 60 21.6 / 0.85 853 / 575 79840258
8 0.38 / 15 1.52 / 60 17.0 / 0.67 1.25 1.78 / 70 23.1 / 0.91 974 / 660 79840033
10 0.38 / 15 1.52 / 60 19.1 / 0.75 1.25 1.78 / 70 25.2 / 0.99 1117 / 755 79840259
12 0.38 / 15 1.52 / 60 19.8 / 0.78 1.25 1.78 / 70 25.9 / 1.02 1194 / 805 79840034
16 0.38 / 15 1.78 / 70 22.8 / 0.90 1.25 1.78 / 70 28.8 / 1.14 1454 / 980 79840035
24 0.38 / 15 1.78 / 70 26.9 / 1.06 1.6 2.03 / 80 34.1 / 1.35 2086 / 1405 7984003636 0.38 / 15 2.03 / 80 32.4 / 1.28 1.6 2.03 / 80 39.6 / 1.56 2749 / 1855 79840037
AWG 20 /7
2 0.30 / 12 1.02 / 40 9.2 / 0.36 0.9 1.27 / 50 13.6 / 0.53 332 / 230 79840038
4 0.30 / 12 1.27 / 50 11.2 / 0.44 0.9 1.52 / 60 16.1 / 0.63 455 / 310 79840039
6 0.30 / 12 1.27 / 50 13.1 / 0.52 0.9 1.52 / 60 18.0 / 0.70 556 / 380 79840256
8 0.30 / 12 1.27 / 50 13.8 / 0.54 0.9 1.52 / 60 18.7 / 0.73 615 / 415 79840040
10 0.30 / 12 1.52 / 60 16.0 / 0.63 1.25 1.52 / 60 21.6 / 0.85 854 / 575 79840257
12 0.30 / 12 1.52 / 60 16.6 / 0.65 1.25 1.78 / 70 22.7 / 0.89 934 / 630 79840041
16 0.30 / 12 1.52 / 60 18.6 / 0.73 1.25 1.78 / 70 24.7 / 0.97 1093 / 685 79840042
24 0.30 / 12 1.52 / 60 21.8 / 0.86 1.25 1.78 / 70 27.9 / 1.10 1383 / 935 79840043
36 0.30 / 12 1.78 / 70 26.8 / 1.04 1.6 2.03 / 80 34.0 / 1.33 2047 / 1380 79840044
RT = Radial Thickness
-
8/20/2019 Icon en Instrumentation Cables
36/76
www.leoni-industrial-projects.com36 The Standard Types Instrumentation & Control Cable
Instrumentation Cable UL 13 / UL 2250
Flame Retardant, Sunlight Resistant
PLTC/ITC
105 °C / 300 V
Single & Multi-Triple, PVC-Insulation, Collective Shield, Armor, PVC Jacket
RE-Yw(St)YwSWAYw-flApplication
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).For indoor and outdoor installation in cable trays or in raceways. Not recommended for direct burial.
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 °C)
Color code................................ black, white, red, continuously numbered on white core (1, 2, 3..) for multi-
element
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wireInner jacket 1........................... heat resistant polyvinyl chloride PVC (105 °C), black
Armor....................................... galvanized round steel wires
Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 °C), black, blue for intrinsicallysafe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/
PVC*) OS (UL) 105 °C SUN RES PRODUCTION LOT CODE LENGTH
MARKING IN FEET*) single element design without com wire
Technical data Abbreviations
Flame propagation- Test on single cable UL13 (VW-1)
- Test on bunched cables UL 1685 (vertical tray)
Gas/vapor tightness outer
jacket
NEC 501.15 (D) and (E)
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 °C)
Oil resistance ICEA S-73-532
Sunlight resistance UL 1581 section 1200
Temperature range-40°C up to +105°C
(during operation)
-5°C up to +50°C(during installation)
Min. bending radius - repeated
bending
10 x cable diameter
RE- Instrumentation CableYw PVC insulation, heat resistant
(St) collective shield
Yw PVC inner jacket, heat resistant
SWA steel wire armor
Yw PVC outer jacket, heat resistant
-fl reduced flame propagation
Electrical Properties at 20 °C
Conductor cross-section (AWG) AWG 14 AWG 16 AWG 18 AWG 20
Conductor resistance max. Ω/km / Ω/1000ft 8.9 / 2.72 14.3 / 4.36 22.8 / 6.93 35.8 / 10.92Insulation resistance min. MΩ x km /
MΩ x 1000ft
30.5 / 100 (at 15.6 °C)
Mutual capacitance
single element:
2 to 4 elements:
above 4 elements:
nom. nF/km /
nF/1000ft
200 / 61
190 / 58
160 / 49
200 / 61
190 / 58
160 / 49
200 / 61
180 / 55
150 / 46
200 / 61
180 / 55
150 / 46
Inductance max. mH/km 1
L/R ratio max. max. µH/Ω 60 40 25
Test voltage Urms (core : core) V 1500
Test voltage Urms (core : shield) V 1500
O eratin volta e V 300
-
8/20/2019 Icon en Instrumentation Cables
37/76
www.leoni-industrial-projects.com 37The Standard Types Instrumentation & Control Cable
AWG 20 /7
1 0.30 / 12 0.89 / 35 5.6 / 0.22 0.9 1.02 / 40 9.4 / 0.37 194 / 135 79840061
2 0.30 / 12 1.02 / 40 8.8 / 0.34 0.9 1.27 / 50 13.2 / 0.51 319 / 215 79840062
4 0.30 / 12 1.27 / 50 10.4 / 0.41 0.9 1.27 / 50 14.8 / 0.58 421 / 290 79840063
6 0.30 / 12 1.27 / 50 12.6 / 0.50 0.9 1.52 / 60 17.5 / 0.69 560 / 380 79840262
8 0.30 / 12 1.27 / 50 13.4 / 0.53 0.9 1.52 / 60 18.3 / 0.72 616 / 415 79840064
10 0.30 / 12 1.27 / 50 14.9 / 0.59 0.9 1.52 / 60 19.8 / 0.78 706 / 475 79840263
12 0.30 / 12 1.52 / 60 15.9 / 0.63 1.25 1.52 / 60 21.4 / 0.84 910 / 615 7984006516 0.30 / 12 1.52 / 60 17.7 / 0.70 1.25 1.78 / 70 23.8 / 0.94 1099 / 740 79840066
24 0.30 / 12 1.52 / 60 20.8 / 0.82 1.25 1.78 / 70 26.9 / 1.06 1388 / 945 79840067
36 0.30 / 12 1.78 / 70 25.2 / 1.00 1.6 2.03 / 80 32.4 / 1.28 2070 / 1420 79840068
RT = Radial Thickness
Instrumentation Cable UL 13 / UL 2250
Flame Retardant, Sunlight Resistant
PLTC/ITC
105 °C / 300 V
Single & Multi-Triple, PVC-Insulation, Collective Shield, Armor, PVC Jacket
RE-Yw(St)YwSWAYw-flGeometrical data
No. of
elements
RT of
insulation
RT of inner
jacket 1
Dia. over
inner jacket 1
Dia. of
armor wire
RT outer jacket Outer dia. Weight Part number
nom. nom. nom. nom. nom. approx. approx. Color
(mm / mils) (mm / mils) (mm / in) (mm) (mm / mils) (mm / in) (kg/km /
lbs/1000ft)
black
AWG 14 /7
1 0.51 / 20 1.02 / 40 8.8 / 0.35 0.9 1.27 / 50 13.2 / 0.52 356 / 240 79840491
2 0.51 / 20 1.27 / 50 14.0 / 0.55 0.9 1.52 / 60 18.9 / 0.74 643 / 435 79840492
4 0.51 / 20 1.52 / 60 16.5 / 0.65 1.25 1.52 / 60 22.1 / 0.87 1000 / 675 79840493
6 0.51 / 20 1.52 / 60 21.2 / 0.84 1.25 1.78 / 70 27.3 / 1.07 1383 / 930 79840494
8 0.51 / 20 1.78 / 70 23.2 / 0.91 1.25 1.78 / 70 29.2 / 1.15 1632 / 1100 7984049510 0.51 / 20 1.78 / 70 24.1 / 0.95 1.25 1.78 / 70 30.1 / 1.18 1820 / 1225 79840496
12 0.51 / 20 1.78 / 70 26.8 / 1.05 1.6 2.03 / 80 34.0 / 1.34 2330 / 1570 79840497
16 0.51 / 20 1.78 / 70 30.2 / 1.19 1.6 2.03 / 80 37.4 / 1.47 2814 / 1895 79840498
24 0.51 / 20 2.03 / 80 36.5 / 1.44 2 2.29 / 90 45.0 / 1.77 4131 / 2780 79840499
36 0.51 / 20 2.29 / 90 44.0 / 1.73 2 2.54 / 100 53.1 / 2.09 7265 / 4885 79840500
AWG 16 /7
1 0.38 / 15 1.02 / 40 7.2 / 0.28 0.9 1.27 / 50 11.6 / 0.45 289 / 195 79840045
2 0.38 / 15 1.27 / 50 12.0 / 0.47 0.9 1.52 / 60 16.9 / 0.66 505 / 340 79840046
4 0.38 / 15 1.27 / 50 13.6 / 0.54 0.9 1.52 / 60 18.5 / 0.73 647 / 440 79840047
6 0.38 / 15 1.52 / 60 17.2 / 0.68 1.25 1.78 / 70 23.3 / 0.92 1043 / 705 79840266
8 0.38 / 15 1.52 / 60 18.4 / 0.72 1.25 1.78 / 70 24.5 / 0.96 1165 / 785 79840048
10 0.38 / 15 1.52 / 60 20.6 / 0.81 1.25 1.78 / 70 26.7 / 1.06 1354 / 915 79840267
12 0.38 / 15 1.52 / 60 21.1 / 0.83 1.25 1.78 / 70 27.2 / 1.07 1466 / 990 79840049
16 0.38 / 15 1.78 / 70 24.4 / 0.96 1.25 1.78 / 70 30.4 / 1.20 1823 / 1225 79840050
24 0.38 / 15 1.78 / 70 28.8 / 1.14 1.6 2.03 / 80 36.0 / 1.43 2626 / 1770 79840051
36 0.38 / 15 2.03 / 80 34.8 / 1.37 1.6 2.29 / 90 42.5 / 1.68 3569 / 2430 79840052
AWG 18 /7
1 0.38 / 15 0.89 / 35 6.5 / 0.26 0.9 1.27 / 50 10.9 / 0.43 248 / 170 79840053
2 0.38 / 15 1.27 / 50 10.9 / 0.43 0.9 1.27 / 50 15.3 / 0.59 425 / 285 79840054
4 0.38 / 15 1.27 / 50 12.4 / 0.49 0.9 1.52 / 60 17.3 / 0.68 554 / 380 79840055
6 0.38 / 15 1.27 / 50 15.1 / 0.60 1.25 1.52 / 60 20.7 / 0.81 820 / 565 79840264
8 0.38 / 15 1.52 / 60 16.6 / 0.66 1.25 1.78 / 70 22.7 / 0.90 984 / 670 79840056
10 0.38 / 15 1.52 / 60 18.7 / 0.74 1.25 1.78 / 70 24.8 / 0.98 1140 / 770 79840265
12 0.38 / 15 1.52 / 60 19.2 / 0.76 1.25 1.78 / 70 25.3 / 1.00 1225 / 825 79840057
16 0.38 / 15 1.52 / 60 21.4 / 0.85 1.25 1.78 / 70 27.5 / 1.09 1453 / 1005 79840058
24 0.38 / 15 1.78 / 70 26.0 / 1.03 1.6 2.03 / 80 33.2 / 1.31 2156 / 1455 79840059
36 0.38 / 15 1.78 / 70 30.8 / 1.22 1.6 2.03 / 80 38.0 / 1.50 2800 / 1925 79840060
-
8/20/2019 Icon en Instrumentation Cables
38/76
www.leoni-industrial-projects.com38 The Standard Types Instrumentation & Control Cable
Instrumentation Cable UL 13 / UL 2250
Flame Retardant, Sunlight Resistant
PLTC/ITC
105 °C / 300 V
Multi-Triple, PVC-Insulation, Individual & Collective Shield, Armor, PVC Jacket
RE-Yw(St)YwSWAYw-fl TiMFApplication
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
For indoor and outdoor installation in cable trays or in raceways. Not recommended for direct burial.
Construction
Conductor.........