Los Angeles Unified School District Belmont Learning Complex Request for Proposal IOR Deficiency Report by Specification Number ID Spec. Section <1> Location Trade Description Drawing # Image # <2> 2427 Academy Houses Doors, Frames and Finish Hardware Incorrect door installed in bathrooms, window panels in doors. AB2-1.01 P0001636.jpg 890 Academy Houses Drywall/EIFS/SOFP Top of wall above door has not been fire proofed. P0001053.jpg 3287 Academy Houses Drywall/EIFS/SOFP Gypsum board openning for electrical receptical exceeds 1/8 max gap on South wall next entrance to room. AB P0001412.jpg 5124 Academy Houses Drywall/EIFS/SOFP Insulation not installed at exterior walls. AB1-1.03 P0001676.jpg 5007 Academy Houses Drywall/EIFS/SOFP From elevation 376.33 to top of parapet EIFS not installed, wall has Hip wrap installed. AB1-2.01 P0002476.jpg 2380 Academy Houses Drywall/EIFS/SOFP Plaster stuck to interior floors creating irregular concrete surface, total of 7 locations. Size varies. AB2-1.03 3174 Academy Houses Drywall/EIFS/SOFP 4 Holes in fire rated wall require patching or fire stop. East wall at North end. AB3-1.02 P0001454.jpg 899 Academy Houses Drywall/EIFS/SOFP Top of walls have not been fire proofed at N line corridor. AB4-1.01 P0001078.jpg 2401 Academy Houses Electrical (School) 8 Conduits thru rated wall are not fire stopped. AB2-1.01 P0001652.jpg 2437 Academy Houses Electrical (School) Conductors missing in boxes. AB2-1.01 P0001604.jpg 2218 Academy Houses Electrical (School) Boxes and conduit have been supported from light gage at roof deck. AB2-1.03 P0001785.jpg 2008 Academy Houses Electrical (School) Fire alarm conduit not identified. AB2-1.03 P0000973.jpg 2091 Academy Houses Electrical (School) Min. power packs not connected to power in rooms noted. AB2-1.03 P0001044.jpg 3087 Academy Houses Electrical (School) Conduit not properly supported. AB3-1.0 P0001520.jpg 3084 Academy Houses Electrical (School) Tele data boxes are not identified in the ceiling and the 1" conduit at the 8 x 8 box is not properly supported. AB3-1.0 P0001522.jpg 3307 Academy Houses Electrical (School) Fire rated plywood has not been installed in all electrical rooms as required by plans. AB3-1.01 3274 Academy Houses Electrical (School) 3-4S boxes conductors not pulled, 2-4S boxes conductor pulled, not landed, cover plates not provided. AB3-1.01 P0001268.jpg 3225 Academy Houses Electrical (School) 8 Gray tel-com boxes do not have cables and have not been identified. AB3-1.01 P0000972.jpg 878 Academy Houses Electrical (School) Conduit run in contact with rigid duct. Felt pads are required at points of contact. AB4-1.01 P0001031.jpg 732 Academy Houses Electrical (School) 3 Gray telcom boxes A) 1 wire pulled no cover no ID B) Cable pull not landed no ID on box C) Box with no cable pulled no ID. AB4-1.03 P0000971.jpg 806 Academy Houses Electrical (School) 2-4S boxes over door 302, conductor not pulled and coax cable pulled, no cover plates provided. AB4-1.03 P0001334.jpg 2217 Academy Houses Fire Protection Fire sprinkler main for roof monitor runs through the electrical room in violation of electrical code. AB2-1.03 P0001761.jpg 323 Academy Houses Flashing and Sheet Metal Incomplete roof area. Photo taken after temporary roof cover installed. Area of A.H. #2 Cooling tower area. AB 2-1.04 P0000999.jpg 795 Academy Houses HVAC and Temperature Control Systems 6 by 6 exhaust air register not installed. AB4-1.03 P0001336.jpg 907 Academy Houses Plumbing Clamps are loose on acid waste line and felt has not been used at clamps. Also identify acid waste line. P0000994.jpg 884 Academy Houses Plumbing 8 Vent 5 gas lines are in contact with duct. Felt pads required at point of contact. AB4-1.01 P0001059.jpg 612 Academy Houses Plumbing All control valves and pipe to be ID'ed. AB4-1.02 P0001196.jpg 847 Academy Houses Plumbing Lower access panel door not installed. Gas and water shut off valves inaccessible. AB4-1.02 P0001196.jpg 629 Academy Houses Plumbing Gas line installed on trapeze for electrical conduit in violation of code. Gas pipe must have its own hangers. AB4-1.02 P0001277.jpg 734 Academy Houses Plumbing Access door for water hammer arrestor not installed. AB4-1.03 P0001272.jpg 9019 Administration Drywall/EIFS/SOFP Parapet walls North and West elevation have not been installed. Ref. drawings 1 -2-AE- 3.01, 3-AE-3.02, 1-AE-2.01 AE-1.03 P0002206.jpg DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INF COMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE. <1> Specification Section as determined by the Inspector of Record (IOR). <2> Corresponds to the image numbers on the "Index of Deficiency Photographs". Print Date: 7/3/01 Page 1 of 154

Upload: others

Post on 26-Jul-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

2427 Academy Houses Doors, Frames and Finish Hardware Incorrect door installed in bathrooms, window panels in doors. AB2-1.01 P0001636.jpg890 Academy Houses Drywall/EIFS/SOFP Top of wall above door has not been fire proofed. P0001053.jpg

3287 Academy Houses Drywall/EIFS/SOFP Gypsum board openning for electrical receptical exceeds 1/8 max gap on South wall next entrance to room.

AB P0001412.jpg

5124 Academy Houses Drywall/EIFS/SOFP Insulation not installed at exterior walls. AB1-1.03 P0001676.jpg5007 Academy Houses Drywall/EIFS/SOFP From elevation 376.33 to top of parapet EIFS not installed, wall has Hip wrap installed. AB1-2.01 P0002476.jpg

2380 Academy Houses Drywall/EIFS/SOFP Plaster stuck to interior floors creating irregular concrete surface, total of 7 locations. Size varies.

AB2-1.03

3174 Academy Houses Drywall/EIFS/SOFP 4 Holes in fire rated wall require patching or fire stop. East wall at North end. AB3-1.02 P0001454.jpg899 Academy Houses Drywall/EIFS/SOFP Top of walls have not been fire proofed at N line corridor. AB4-1.01 P0001078.jpg

2401 Academy Houses Electrical (School) 8 Conduits thru rated wall are not fire stopped. AB2-1.01 P0001652.jpg2437 Academy Houses Electrical (School) Conductors missing in boxes. AB2-1.01 P0001604.jpg2218 Academy Houses Electrical (School) Boxes and conduit have been supported from light gage at roof deck. AB2-1.03 P0001785.jpg2008 Academy Houses Electrical (School) Fire alarm conduit not identified. AB2-1.03 P0000973.jpg2091 Academy Houses Electrical (School) Min. power packs not connected to power in rooms noted. AB2-1.03 P0001044.jpg3087 Academy Houses Electrical (School) Conduit not properly supported. AB3-1.0 P0001520.jpg3084 Academy Houses Electrical (School) Tele data boxes are not identified in the ceiling and the 1" conduit at the 8 x 8 box is not

properly supported.AB3-1.0 P0001522.jpg

3307 Academy Houses Electrical (School) Fire rated plywood has not been installed in all electrical rooms as required by plans. AB3-1.013274 Academy Houses Electrical (School) 3-4S boxes conductors not pulled, 2-4S boxes conductor pulled, not landed, cover plates

not provided.AB3-1.01 P0001268.jpg

3225 Academy Houses Electrical (School) 8 Gray tel-com boxes do not have cables and have not been identified. AB3-1.01 P0000972.jpg878 Academy Houses Electrical (School) Conduit run in contact with rigid duct. Felt pads are required at points of contact. AB4-1.01 P0001031.jpg732 Academy Houses Electrical (School) 3 Gray telcom boxes A) 1 wire pulled no cover no ID B) Cable pull not landed no ID on

box C) Box with no cable pulled no ID.AB4-1.03 P0000971.jpg

806 Academy Houses Electrical (School) 2-4S boxes over door 302, conductor not pulled and coax cable pulled, no cover plates provided.

AB4-1.03 P0001334.jpg

2217 Academy Houses Fire Protection Fire sprinkler main for roof monitor runs through the electrical room in violation of electrical code.

AB2-1.03 P0001761.jpg

323 Academy Houses Flashing and Sheet Metal Incomplete roof area. Photo taken after temporary roof cover installed. Area of A.H. #2 Cooling tower area.

AB 2-1.04 P0000999.jpg

795 Academy Houses HVAC and Temperature Control Systems 6 by 6 exhaust air register not installed. AB4-1.03 P0001336.jpg

907 Academy Houses Plumbing Clamps are loose on acid waste line and felt has not been used at clamps. Also identify acid waste line.

P0000994.jpg

884 Academy Houses Plumbing 8 Vent 5 gas lines are in contact with duct. Felt pads required at point of contact. AB4-1.01 P0001059.jpg612 Academy Houses Plumbing All control valves and pipe to be ID'ed. AB4-1.02 P0001196.jpg847 Academy Houses Plumbing Lower access panel door not installed. Gas and water shut off valves inaccessible. AB4-1.02 P0001196.jpg629 Academy Houses Plumbing Gas line installed on trapeze for electrical conduit in violation of code. Gas pipe must

have its own hangers.AB4-1.02 P0001277.jpg

734 Academy Houses Plumbing Access door for water hammer arrestor not installed. AB4-1.03 P0001272.jpg9019 Administration Drywall/EIFS/SOFP Parapet walls North and West elevation have not been installed. Ref. drawings 1 -2-AE-

3.01, 3-AE-3.02, 1-AE-2.01AE-1.03 P0002206.jpg

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 1 of 154

Page 2: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

9020 Administration Drywall/EIFS/SOFP Refer to drawings AE-3.02 detail 2. Parapet walls on east elevation at the radius have not been installed.

AE-1.03 P0002218.jpg

9075 Administration Electrical (School) Electrical sub panel with no conductors, no pull strings, no internal hardware. Column line 4-A.5.

AE-1.03 P0002216.jpg

6018 Administration Flashing and Sheet Metal Screws on sheet metal coping not sealed correctly. (Not caulked or no-neoprene washers used).

AE-1.03 P0002332.jpg

9110 Administration General Contracting Cap flashing galvanized tube steel, plywood, roofing material, left on roof. AE-1.03 P0002231.jpg233 Parking Garage Drywall/EIFS/SOFP At South gypsum fire rated wall - Two holes 1 @ 4" and 1 @ 7'8" from deck slab

correction required.AA 1.03 P0000718.jpg

335 Parking Garage Drywall/EIFS/SOFP At South gypsum fire rated wall - Two holes 1 @ 4" and 1 @ 7'8" from deck slab correction required.

AA 1.03 P0000718.jpg

366 Parking Garage Drywall/EIFS/SOFP South wall not completed at EastWest corner. AA 1.09 P0000678.jpg18 Parking Garage Drywall/EIFS/SOFP Wrong size drilled anchors in wall. Correct size not installed. AA-1.0214 Parking Garage Drywall/EIFS/SOFP Shot pins spaced further apart that allowed per detail above. AA-1.03 P0000587.jpg

136 Parking Garage Electrical (Parking) Link seals not installed at exterior walls. EA107 P0000421.jpg11 Parking Garage Electrical (School) Box penetration on opposite sides of wall 3" apart need fire safeing. Closer than 24"

apart.AA-1.02 P0000282.jpg

665 Parking Garage Fire Protection Sprinkler line drops under HVAC duct not properly supported. AA 1.01 AA 1.02

P0000739.jpg

375 Parking Garage Fire Protection 5 Sprinkler 11' drops: Requires support at sprinkler head. AA 1.03 P0000711.jpg262 Parking Garage Fire Protection Fire sprinkler wall penetration not sleeved or fire stop caulked. AA 1.05 P0002521.jpg

9 Parking Garage HVAC and Temperature Control Systems Anchor bolts at bracing straps need torque testing. SA-1.3

274 Parking Garage Hydraulic Elevators All drilled anchors shall be tension or torque tested. AA-1.04 P0002527.jpg2506 Site-Wide Concrete/Masonry/Reinforcing Steel (Site

Retaining Walls)From station 3+34.47 to station 2+00.00 concrete starter wall snap-tie holes have not been purged.

C-1.12 P0002436.jpg

2507 Site-Wide Roofing and Waterproofing From station 3+34.47 to station 2+00.00 concrete starter wall and masonry retaining wall has not been water proofed.

C-1.12 P0002439.jpg

562 Triple Gym General Contracting Remove combustible debris between AH # 4 and TGYM at line T&T1 from 1.9 to 7. AC-1.02 P0000944.jpg468 Triple Gym HVAC and Temperature Control Systems Open conduit sleeves in CMU walls required to be firestopped. See note on G-1. AC 1.02 P0000805.jpg

1435 Triple Gym Miscellaneous Iron and Steel Stairs Tube steel header for doors 108-108.4 not anchored at masonry. AC1.01 P0002145.jpg430 Triple Gym Plumbing Protection shields required at clevis hangers on foam insulated condensate line. AC 1.02 P0000869.jpg576 Triple Gym Plumbing Patch pipe hanger at beams with fire proofing. AC-1.02 P0000823.jpg300 01045 Parking Garage Plumbing A 6" hole has been core drilled thru the ramp slab for a 4" vent line. The cored hole has

cut thru 2 #9 rebar. One looking east and west and one looking north and south. Patometer testing was not asked for.

PA-1.02

2342 01400 Academy Houses Electrical (School) Drilled anchors have not been tested. AB2-1.01 P0001723.jpg2475 01400 Academy Houses Electrical (School) Drilled anchors have not been tested in room. AB2-1.01-

1.02-1.03P0001033.jpg

2332 01400 Academy Houses Electrical (School) Drilled anchors have not been tested in all rooms noted. AB2-1.01-1.02-1.03

P0001033.jpg

3158 01400 Academy Houses Electrical (School) Anchorage for hanger rod for light fixtures and conduit and conduit rack support have not been tested.

AB3-1.02 P0001033.jpg

3167 01400 Academy Houses Electrical (School) Anchorage for main breaker, AC4MDL, panels and distributor transformer have not been tested.

AB3-1.02 P0001293.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 2 of 154

Page 3: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

3098 01400 Academy Houses Electrical (School) Drilled anchors for anchoring main gear have not been tested. AB3-1.03 P0001293.jpg5083 01400 Academy Houses General Contracting Misc. construction materials stored throughout level 1. AB1-1.01 P0002040.jpg2062 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.01 P0001799.jpg2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02 P0001799.jpg2063 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.03 P0001799.jpg

55 01400 Parking Garage Electrical (School) All anchor bolts shall be tension or torque tested per above code. AA-1.0130 01400 Parking Garage HVAC and Temperature Control Systems All drilled anchors shall be tension or torque tested. AA-1.02 P0000003.jpg

190 01400 Parking Garage Hydraulic Elevators Drilled anchors for fan not torque tested. AA-1.07 P0000385.jpg374 01400 Parking Garage Miscellaneous Iron and Steel Stairs 3/4 Wedge anchors for stair & stair landings supports. AA 1.03-1.06-

1.09P0000704.jpg

57 01400 Parking Garage Plumbing All drilled anchors shall be tension or torque tested per code above. PA-1.011432 01400 Triple Gym General Contracting Misc. trash inc. lumber and pallets. AC1.01 P0002158.jpg1462 01400 Triple Gym General Contracting Top of footing needs to be cleaned, typical. AC1.01 P0002140.jpg

551 01400 Triple Gym Plumbing Anchorage for plumbing lines supported to North and South CMU walls require testing for shear

AC-1.02 P0000775.jpg

637 01900 Academy Houses Electrical (School) No seismic sway bracing provided for busway supports, conduit runs and unistrut supports in electrical room.

AB4-1.02 P0001282.jpg

2495 02830 Site-Wide Chain Link Fence and Gates From station 4+96 to 1+00.00 fence on top of masonry wall not installed and no cap block.

P0002450.jpg

2500 02830 Site-Wide Chain Link Fence and Gates From station 8+63.48 to 3+96.92 fencing on top of concrete wall not installed. C-1.13 P0002433.jpg411 03100-3300 Parking Garage Cast-in-Place Concrete (Parking) 1) Remove snap ties left at slab ceiling 2) Where concrete column abutts horizontal

beam cold joint / rock pocket exposed to surface. Correction required. 3) Patch West concrete wall.

AA 1.01 P0000740.jpg

2456 03200 Academy Houses Structural Steel - Detailing Rebar for floor slab and masonry wall rusty and damaged. AB2-.101 P0001612.jpg339 03200 Parking Garage Cast-in-Place Concrete (Parking) Exposed rebar at shear wall under landing across from Door 206. P0000713.jpg342 03200 Parking Garage Cast-in-Place Concrete (Parking) Rebar from shear on W line is exposed at landing. AA 109 P0000696.jpg139 03200 Parking Garage Reinforcing Steel (Parking) Reinforcing bars are badly bent, rusted and not per plan SA101 P0000426.jpg

2390 03300 Academy Houses Cast-in-Place Concrete (Parking) Hole chipped into slab to relocate conduits into frame wall area at South East corner of room at C.7-9.

AB2-1.01 P0001673.jpg

2120 03300 Academy Houses Cast-in-Place Concrete (Parking) Concrete surface out of tolerance, uneven concrete floor at doors 118.1-119.1-120-121. AB2-1.01 P0001929.jpg2112 03300 Academy Houses Cast-in-Place Concrete (Parking) Concrete surface out of tolerance, floor uneven, doors; 112-113-114-115, about 32'

lineal.AB2-1.01 P0001929.jpg

2121 03300 Academy Houses Cast-in-Place Concrete (Parking) Concrete surface out of tolerance, uneven concrete floor at doors; 116-116.1-117-117.1. AB2-1.01 P0001929.jpg2106 03300 Academy Houses Cast-in-Place Concrete (Parking) Hole in deck where conduit relocated into 3rd floor short wall and full height. Wall on

2nd floor.AB2-1.02-1.03

P0001994.jpg

2094 03300 Academy Houses Cast-in-Place Concrete (Parking) 1' x 1' square opening and 4" diameter hole in floor deck. AB2-1.03 P0001888.jpg3322 03300 Academy Houses Cast-in-Place Concrete (Parking) Concrete surface out of tolerance, concrete slab near doors 112-113-114-115 (column

line G) uneven.AB3-1.01 P0001929.jpg

3323 03300 Academy Houses Cast-in-Place Concrete (Parking) Concrete surface out of tolerance, concrete slab near drinking fountain uneven. AB3-1.01 P0001929.jpg3325 03300 Academy Houses Cast-in-Place Concrete (Parking) Concrete surface out of tolerance, concrete joint going East-West near column line F.4,

floor uneven.AB3-1.01 P0001931.jpg

3166 03300 Academy Houses Cast-in-Place Concrete (Parking) 3 Holes in slab used for safety post require repair. AB3-1.02 P0001445.jpg3128 03300 Academy Houses Cast-in-Place Concrete (Parking) Holes in slab used for safety hand rail post require patching. Total of 3 in rooms noted. AB3-1.03 P0001182.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 3 of 154

Page 4: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

4064 03300 Academy Houses Cast-in-Place Concrete (Parking) Concrete surface out of tolerance, near drinking fountain, column line N.3 1/4" by 2" depression 4 feet long.

AB4-1.01

4040 03300 Academy Houses Cast-in-Place Concrete (Parking) Concrete surface out of tolerance, near door 121, voids in concrete slab at construction joint.

AB4-1.01 P0001931.jpg

4032 03300 Academy Houses Cast-in-Place Concrete (Parking) Concrete surface out of tolerance, concrete slab outside of door 114-116-117, concrete uneven.

AB4-1.01 P0001936.jpg

4043 03300 Academy Houses Cast-in-Place Concrete (Parking) Concrete surface out of tolerance, rough concrete floor finish. AB4-1.01 P0001943.jpg4044 03300 Academy Houses Cast-in-Place Concrete (Parking) Concrete surface out of tolerance, rough concrete floor finish near column line N.3 and

3.1.AB4-1.01

4047 03300 Academy Houses Cast-in-Place Concrete (Parking) Concrete surface out of tolerance, near floor door 112 concrete slab uneven. AB4-1.01 P0001957.jpg4050 03300 Academy Houses Cast-in-Place Concrete (Parking) Concrete surface out of tolerance, near door 119 along column line S surface uneven and

contains voids in concrete.AB4-1.01 P0001931.jpg

4058 03300 Academy Houses Cast-in-Place Concrete (Parking) Concrete surface out of tolerance, East-West joint at slab, column line P.5 surface uneven.

AB4-1.01 P0001940.jpg

4065 03300 Academy Houses Cast-in-Place Concrete (Parking) Concrete surface out of tolerance, rough concrete floor finish near column line N and between 3.2 to 4.0.

AB4-1.01

4041 03300 Academy Houses Cast-in-Place Concrete (Parking) Concrete surface out of tolerance, near door 120 and 118, column line S 1/4" deep by 2" wide depression.

AB4-1.01 P0001929.jpg

631 03300 Academy Houses Cast-in-Place Concrete (Parking) Fill holes in deck slab use for safety post at fire rated West wall. AB4-1.02 P0001316.jpg5017 03300 Academy Houses Concrete (School) Slab on grade concrete has not been placed. AB1-1.01 P0002097.jpg5016 03300 Academy Houses Concrete (School) All rusted and dirty reinforcing to be cleaned before concrete placement. AB1-1.01 P0002097.jpg5015 03300 Academy Houses Concrete (School) All bent and broken reinforcing to be corrected. AB1-1.01 P0002097.jpg5135 03300 Academy Houses Concrete (School) Foot prints in concrete full width of corridor column 11.5 to 12.2. AB1-1.02 P0001938.jpg5136 03300 Academy Houses Concrete (School) Concrete surface out of tolerance. Concrete 2" to high at door 214.1, about 7 foot by 2

foot.AB1-1.02 P0001930.jpg

5128 03300 Academy Houses Concrete (School) Concrete surface out of tolerance at doors; 215-217-218-219-220-221-222 and at drinking fountain column line 12.2, about 65' lineal.

AB1-1.02 P0001929.jpg

5114 03300 Academy Houses Concrete (School) Concrete has not been placed for stairs, rebar exposed at floor. AB1-1.02 P0001985.jpg5129 03300 Academy Houses Concrete (School) No concrete placed at corridor floor edge stairs; 301-201-350-250-351-251, about 1 foot

by 19 feet (6 locations) and steel stair stringer rebar tie-ins about 18" by 6 ' (12 total).AB1-1.02-1.03

P0001975.jpg

5132 03300 Academy Houses Concrete (School) Concrete surface out of tolerance at doors; 314-314.1-315.1-316-317-319. AB1-1.03 P0001929.jpg5130 03300 Academy Houses Concrete (School) No concrete placed at corridor floors, seismic joint, 2' by full width of corridor, column

line 11.AB1-1.03 P0002577.jpg

5088 03300 Academy Houses Concrete (School) Concrete has not been placed at rebar from stair stringers to landing. AB1-1.03 P0001985.jpg5131 03300 Academy Houses Concrete (School) Foot prints between column lines 12.5 to 14 and 16.5 17, full width of corridor. AB1-1.03 P0001938.jpg5086 03300 Academy Houses Concrete (School) Corridor entry to door 314.1 concrete not placed, wire mesh and shear studs exposed. AB1-1.03 P0001986.jpg5133 03300 Academy Houses Concrete (School) Concrete surface out of tolerance on floor slab; full width of corridor from column line

14 to 15.5.AB1-1.03 P0001934.jpg

5134 03300 Academy Houses Concrete (School) Concrete surface out of tolerance full width of corridor, column 18.5 to 19. AB1-1.03 P0001934.jpg1402 03300 Academy Houses Concrete (School) Roof pads not installed. AB1-1.041404 03300 Academy Houses Concrete (School) Roof pads not installed. AB1-1.045011 03300 Academy Houses Concrete (School) At elevation 363.00 foundation has not been placed for masonry veneer. AB1-2.01 P0002469.jpg5006 03300 Academy Houses Concrete (School) Concrete foundation is not placed for block veneer 363 elevation. AB1-2.01 P0002470.jpg5010 03300 Academy Houses Concrete (School) At elevation 363.00 foundation has not been placed for masonry veneer. AB1-2.01 P0002470.jpg2127 03300 Academy Houses Concrete (School) Cement droppings on floor slab column 5.7 to 6 and C to C.3. AB2-1.01 P0001935.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 4 of 154

Page 5: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

2128 03300 Academy Houses Concrete (School) Concrete surface out of tolerance. Floor drain, concrete placed too high, one location, column line 7.8 and 2.3.

AB2-1.01 P0001932.jpg

2129 03300 Academy Houses Concrete (School) Concrete surface out of tolerance. Uneven floor at doors 211 and column line 2.7 from E.7 to F.

AB2-1.01 P0001929.jpg

2235 03300 Academy Houses Concrete (School) Concrete structural slab does not slope to drain about 10 x 14 foot area expected. AB2-1.022116 03300 Academy Houses Concrete (School) Concrete surface out of tolerance. Uneven concrete floor at doors; 216.1-217.1. AB2-1.02 P0001929.jpg2118 03300 Academy Houses Concrete (School) Foot prints in concrete at column B to B.5 full width of corridor. AB2-1.02 P0001938.jpg2126 03300 Academy Houses Concrete (School) Concrete surface out of tolerance. Uneven floor column line 9 to 10 and C to D. AB2-1.02 P0001939.jpg2238 03300 Academy Houses Concrete (School) Concrete surface out of tolerance. Floor slab rough and slopes about 1", 4 x 5 foot area

expected.AB2-1.02

2117 03300 Academy Houses Concrete (School) Concrete surface out of tolerance, floor at doors 317 and 318. AB2-1.02 P0001930.jpg2115 03300 Academy Houses Concrete (School) Concrete surface out of tolerance, floor at door 317. AB2-1.03 P0001930.jpg2114 03300 Academy Houses Concrete (School) Concrete surface out of tolerance. Uneven floor at doors; 316-316.1-316.2, 18' long. AB2-1.03 P0001929.jpg2122 03300 Academy Houses Concrete (School) Concrete surface out of tolerance floor; uneven column 5.7 to 6.1 full width. No concrete

placed at seismic joint, about 1 foot by full width of corridor.AB2-1.03 P0001939.jpg

2123 03300 Academy Houses Concrete (School) Voids in floor column 10 and G, about 6" x 6" each, 2 locations. Concrete droppings between column line 7&8.

AB2-1.03 P0001935.jpg

2124 03300 Academy Houses Concrete (School) Concrete surface out of tolerance. Uneven floor column line 5.5 to 6, full width of corridor.

AB2-1.03 P0001939.jpg

2125 03300 Academy Houses Concrete (School) Concrete surface out of tolerance. Uneven concrete at doors; 212-213-214-215-222-223. AB2-1.03 P0001929.jpg2130 03300 Academy Houses Concrete (School) Concrete surface out of tolerance. Floor drain, concrete placed too high, 2 locations. AB2-1.03 P0001932.jpg2131 03300 Academy Houses Concrete (School) Concrete surface out of tolerance. Uneven floor at door 311 and column line 2.7 from E.7

to F.AB2-1.03 P0001929.jpg

3239 03300 Academy Houses Concrete (School) Concrete surface out of tolerance: Rough concrete (#1) at doors 212-213, rough concrete with voids (#2) column 5.3 to 6.5. Full width of corridor.

AB3-1.02 P0002004.jpg

3244 03300 Academy Houses Concrete (School) Concrete surface out of tolerance. Concrete floor rough column line M to L and 2.7 to 3.0.

AB3-1.02 P0001943.jpg

3235 03300 Academy Houses Concrete (School) Concrete surface out of tolerance: Uneven floor (#1) full width, column F to G.3; foor prints (#2) full width, column F to G.3.

AB3-1.02 P0002003.jpg

3242 03300 Academy Houses Concrete (School) Concrete surface out of tolerance, floor rough at door 221. AB3-1.02 P0002004.jpg3236 03300 Academy Houses Concrete (School) Concrete surface out of tolerance: Uneven floor (#1) width of corridor, column 3 to 5;

foot prints (#2) width of corridor, column 4 to 5.AB3-1.02 P0002003.jpg

3243 03300 Academy Houses Concrete (School) Concrete surface out of tolerance. Floor drain, concrete placed to high, 1 location. Column L.7 and 2.3.

AB3-1.02 P0001932.jpg

3234 03300 Academy Houses Concrete (School) Concrete surface out of tolerance: Full width and length uneven (#1) and foot prints (#2). AB3-1.03

3238 03300 Academy Houses Concrete (School) Concrete surface out of tolerance: Rough concrete (#1) at doors 312-313. Also rough concrete near stairs, column 5.5 to 6.5, 2 foot wire.

AB3-1.03 P0002004.jpg

3327 03300 Academy Houses Concrete (School) Concrete surface out of tolerance floors, uneven floor (#1) full width of corridor, column 3 to 5.5, foot prints (#2) full length of corridor column 3 to 5.5.

AB3-1.03 P0002003.jpg

3245 03300 Academy Houses Concrete (School) Concrete surface out of tolerance. Floor drain concrete placed too high, column line L.5 to 2.8.

AB3-1.03 P0001932.jpg

2119 03300 Academy Houses Concrete (School) Concrete surface out of tolerance. Uneven finish on floors at doors 318-319-320 and 321.

AB3-1.03 P0001929.jpg

4038 03300 Academy Houses Concrete (School) Concrete surface out of tolerance at two locations 1) Col. 7.8 to 7 and R.7 to S about 8 by 30' 2) Col.2.7 to 3.2 and R.7 to S about 8 by 20 feet.

AB4-1.02 P0001934.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 5 of 154

Page 6: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

4049 03300 Academy Houses Concrete (School) East-West joint in concrete floor slab at column line P, surface uneven and contains voids.

AB4-1.02 P0001931.jpg

4048 03300 Academy Houses Concrete (School) Foot prints in concrete, column line M.2 and 3, about 4 by 8 foot area. AB4-1.02 P0001937.jpg4042 03300 Academy Houses Concrete (School) Floor slab placed too high and floor drain will not receive water at column line R.7 and 3-

3.5-4.5-5.8-6.8.AB4-1.02 P0001943.jpg

4039 03300 Academy Houses Concrete (School) Cold joint and voids at column line S near doors 218-219-220.1. Total of about 20' lineal. AB4-1.02 P0001931.jpg

4057 03300 Academy Houses Concrete (School) Concrete surface out of tolerance at deck drains, 5 total. Column line 3, 3.5, 4.5, 5.8 and 6.8 at line R.7.

AB4-1.02 P0001955.jpg

4055 03300 Academy Houses Concrete (School) Concrete surface out of tolerance in triangle shaped area, outside rooms 214 & 216. AB4-1.02 P0001936.jpg4052 03300 Academy Houses Concrete (School) Concrete slab outside of doors 316-317, triangle shaped area, two total, concrete uneven.

About 24 square feet total.AB4-1.03 P0001936.jpg

4054 03300 Academy Houses Concrete (School) East-West joint in concrete floor at column line P, surface uneven and contains voids. AB4-1.03 P0001931.jpg4053 03300 Academy Houses Concrete (School) Concrete surface out of tolerance imperresions in concrete slab, column line 3 to 2.7 and

N to N.5 about 10 by 12 foot area.AB4-1.03 P0001937.jpg

4051 03300 Academy Houses Concrete (School) Concrete surface out of tolerance, 2 locations, column line P.3 and Q.3 at 3. AB4-1.03 P0001932.jpg4037 03300 Academy Houses Concrete (School) Concrete surface out of tolerance, near column line 4.2 and N.3, about 20 square feet. AB4-1.03 P0001934.jpg4036 03300 Academy Houses Concrete (School) Foot prints in concrete near column line N, from 6 to 6.6. About 2 by 8 feet. AB4-1.03 P0001937.jpg4034 03300 Academy Houses Concrete (School) Concrete surface out of tolerance. AB4-1.03 P0001934.jpg4060 03300 Academy Houses Concrete (School) Concrete surface out of tolerance at floor drains, 5 total. Column line 3, 3.5, 4.5, 5.8 and

6.8 at line R.7.AB4-1.03 P0001955.jpg

4035 03300 Academy Houses Concrete (School) Concrete surface out of tolerance near stairs, N to N.3 from 6 to 6.8 also uneven (1 1/2") area expected about 120 square feet.

AB4-1.03 P0001934.jpg

4059 03300 Academy Houses Concrete (School) Concrete joint irregular and voids column line N near doors 312-313. AB4-1.03 P0001931.jpg4056 03300 Academy Houses Concrete (School) Joint in floor slab with voids, column line S near door 218-219. AB4-1.03 P0001931.jpg4062 03300 Academy Houses Concrete (School) Concrete surface out of tolerance two locations; 1) Column 7.8 to 7 and R.7 to S, about 8

by 30', 2) Column 2.7 to 3.2 and R.7 to S.AB4-1.03 P0001934.jpg

4063 03300 Academy Houses Concrete (School) Concrete surface out of tolerance. Steep sloped elevation change in concrete column line S at doors 320.1- 321.1 about 1 1/2" high.

AB4-1.03 P0001940.jpg

3014 03300 Academy Houses Electrical (School) 2 Floor penetrations for temporary power require repair of holes and temporary fire stopping at L.7-2.6.

AB3-1.02 P0001656.jpg

2237 03300 Academy Houses General Contracting Temporary steel safety rail posts project 1/2" +/- above finish floor, total of 42 locations. AB2-1.02 P0001182.jpg

2067 03300 Academy Houses General Contracting Hole thru floor slab to floor below, one 2", 2' North of door 218 at corridor to room 218. AB2-1.02

2379 03300 Academy Houses General Contracting Steel safety rail post locations, holes and irregular surfaces at concrete floor slabs. Total of 27 locations.

AB2-1.03 P0001182.jpg

2378 03300 Academy Houses General Contracting Steel safety rail posts are not cut off at finish floor. Up about 1/2" at shafts and exterior walls. Total of 27 locations with one post not cut at room 322.

AB2-1.03 P0001182.jpg

3202 03300 Academy Houses General Contracting Hole in slab used for safety rail post to be filled (10) and 6 angles not burnt flush to slab to be ground flush with slab.

AB3-1.02 P0001182.jpg

949 03300 Academy Houses General Contracting Concrete finish irregular room 210, chips in concrete floor 20 locations, holes in slab where safety rail posts removed 23 locations, safety rail posts project above finish floor 9 locations.

AB4-1.02 P0001181.jpg

628 03300 Academy Houses General Contracting Holes in elevated slab need patching. AB4-1.02 P0001182.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 6 of 154

Page 7: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

1006 03300 Academy Houses General Contracting Steel safety posts 1/2"+1- above concrete floor slab with open holes at square tubes, total of 30 locations.

AB4-1.03 P0001181.jpg

4061 03300 Academy Houses Roofing and Waterproofing Floor flashing at wall at deck drain too high, not sealed, one location. Column 5.8 and R.7.

AB4-1.03 P0001956.jpg

9029 03300 Administration Concrete (School) Slab on grade concrete has not been placed. AE-1.01 P0002243.jpg9027 03300 Administration Concrete (School) Reinforcing steel that is bent or broken to be replaced. All rusty bar to be cleaned. All

reinforcing bars that are bent, broken and rusty shall be corrected before concrete placement.

AE-1.01 P0002128.jpg

9086 03300 Administration Concrete (School) Concrete surface out of tolerance. Rough floor finish, 2 locations about 20' square each. AE-1.02 P0002298.jpg9038 03300 Administration Concrete (School) Concrete surface out of tolerance. Floor out of level up to 3/4" from column line B.5 to D

and 2 to 3.AE-1.02

9085 03300 Administration Concrete (School) No floor concrete placed at top of stair, about 6 by 3 feet. AE-1.02 P0002297.jpg9001 03300 Administration Concrete (School) Foundation and footing for masonry walls and columns have not been placed. SE-1.1 P0002484.jpg

582 03300 Parking Garage Cast-in-Place Concrete (Parking) Finish floor ramp from Parking Level 2 to Parking Level 1. Interior finish slab out of tolerance 1/2".

P0002564.jpg

350 03300 Parking Garage Cast-in-Place Concrete (Parking) Concrete stair trend do not have warning spripes. AA 1.03 P0000759.jpg246 03300 Parking Garage Cast-in-Place Concrete (Parking) Two block outs at floor slab elev. For door frame remove wood - patch Concrete slab as

required.AA 1.04 P0000324.jpg

400 03300 Parking Garage Cast-in-Place Concrete (Parking) Correction of cold joint where concrete column angle butts with concrete beam North wall side at N-2 horizontal joint.

AA 1.05 P0000664.jpg

90 03300 Parking Garage Cast-in-Place Concrete (Parking) Finish floor to be level 1/8 inch to 10 feet section not acceptable to specification for interior finish slabs (out of tolerance by 1/2")

AA 1.07 P0002551.jpg

91 03300 Parking Garage Cast-in-Place Concrete (Parking) Finish floor ramp from PL-3 to PL-2. Interior finish slab out of tolerance by 1/2". AA 1.08 P0002557.jpg

46 03300 Parking Garage Cast-in-Place Concrete (Parking) Holes in slab on grade concrete. AA-1.01 P0000731.jpg664 03300 Parking Garage Cast-in-Place Concrete (Parking) Concrete stairs to lower Parking Level. Do not have stair tread warning strips per ADA

requirements.AA-1.02 P0000761.jpg

332 03300 Parking Garage Cast-in-Place Concrete (Parking) Concrete stairs to lower Parking Level. Do not have stair tread warning strips per ADA requirements.

AA-1.02 P0002550.jpg

217 03300 Parking Garage Cast-in-Place Concrete (Parking) At concrete column on north-west corner and south-east corner repair damage at 24" max from deck.

AA-1.07 P0000399.jpg

343 03300 Parking Garage Cast-in-Place Concrete (Parking) Snap ties and are exposed in ceiling of stair shaft. P 306 P0000683.jpg414 03300 Parking Garage Electrical (School) Concrete wall on 7.5 line and level # 2 wall and over head in corridor have not been

finished. Example: Snap tie holes, form edges uneven and concrete drips.AA 1.01-4.04-1.07

P0000755.jpg

5 03300 Parking Garage Electrical (School) Correction of hole on slab on grade for mislocated conduit into gypsum wall. AA 1.03 P0000164.jpg2502 03300 Site-Wide Concrete/Masonry/Reinforcing Steel (Site

Retaining Walls)From 2+40 to end of wall 1+00 footing not placed. C-1.12 P0002434.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 7 of 154

Page 8: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

2509 03300 Site-Wide Concrete/Masonry/Reinforcing Steel (Site Retaining Walls)

From station 4+36.00 to end of wall at station 2+00.00 foundation is not placed. C-1.12 P0002441.jpg

2503 03300 Site-Wide Concrete/Masonry/Reinforcing Steel (Site Retaining Walls)

From 2+40 to end of wall 1+00 footing not placed. C-1.12 P0002434.jpg

2496 03300 Site-Wide Concrete/Masonry/Reinforcing Steel (Site Retaining Walls)

From station 5+72 to station 4+96 footing for masonry wall not placed. C-1.13 P0002448.jpg

1450 03521 Triple Gym Metal Deck and Insulating Concrete Cement stains on block from concrete placed at roof deck typical 3 rooms. Total 5 rooms. P0002146.jpg

1458 03521 Triple Gym Metal Deck and Insulating Concrete Concrete stains on block walls, typical, from concrete placed at roof deck. Typical this room.

AC1.01 P0002146.jpg

690 04200 Academy Houses Reinforced Masonry and Veneer Systems CMU walls are not complete at stair tower walls. P0001205.jpg700 04200 Academy Houses Reinforced Masonry and Veneer Systems Sprinkler branch lines is embodied in CMU wall 1" clearance is not provided over access

door at N.3-5.6 and N.7-5.7AB4-1.01 P0001175.jpg

688 04200 Academy Houses Reinforced Masonry and Veneer Systems Top of parapet CMU wall not complete. AB4-1.01 P0001200.jpg691 04200 Academy Houses Reinforced Masonry and Veneer Systems Top of spandrel rail at CMU wall not complete. AB4-1.01 P0001202.jpg834 04200 Academy Houses Reinforced Masonry and Veneer Systems CMU veneer at elevator and door 102 is not installed. AB4-1.01-

1.02-1.03P0001188.jpg

689 04200 Academy Houses Reinforced Masonry and Veneer Systems CMU at top of wall has not been installed. AB4-1.02 P0001202.jpg9079 04200 Administration Reinforced Masonry and Veneer Systems Masonry wall not built to correct height about 2' short of bottom of roof deck, about 45'

long. Column line 2.7 to 3 and D to D.4.AE-1.03 P0002207.jpg

301 04200 Parking Garage Drywall/EIFS/SOFP CMU wall not caulked at end and top as required. S-0.4 P0000520.jpg

10 04200 Parking Garage Drywall/EIFS/SOFP Compressable material and caulk missing at top and sides of walls. SA-1.3 P0000520.jpg

364 04200 Parking Garage Reinforced Masonry and Veneer Systems CMU walls in area exhibit efforcesence required to be corrected. AA 1.09 P0000672.jpg218 04200 Parking Garage Reinforced Masonry and Veneer Systems CMU wall at louver opening top course not complete. AA-1.07 P0000401.jpg

2167 04220 Academy Houses Reinforced Masonry and Veneer Systems At elevation 363.00 masonry wall has not been built, rebar bent and rusted. AA-2.05 P0002487.jpg3241 04220 Academy Houses Reinforced Masonry and Veneer Systems Concrete floor: Motar droppings (#3) full width of corridor and full length. AB3-1.02 P0002003.jpg3237 04220 Academy Houses Reinforced Masonry and Veneer Systems Concrete floors: Motar dropings (#3) full width of corridor, column 4 to 5. AB3-1.02 P0002003.jpg3240 04220 Academy Houses Reinforced Masonry and Veneer Systems Concrete floor: Motar droppings (#3) full width of corridor, column 3 to 5.5. AB3-1.03 P0002003.jpg

902 04220 Academy Houses Reinforced Masonry and Veneer Systems Mitered corners have poor tooling and mortar missing in corridors S, 3 and N. AB4-1.01 P0000988.jpg903 04220 Academy Houses Reinforced Masonry and Veneer Systems Mitered corners are poorly tooled and missing mortar in corridors S, 3 and N. AB4-1.02 P0000988.jpg904 04220 Academy Houses Reinforced Masonry and Veneer Systems Mitered corners are poorly tooled and missing mortar in corridors S, 3 and N. AB4-1.03 P0000988.jpg

9081 04220 Administration Drywall/EIFS/SOFP No caulked joints at masonry expansion joints, 7 locations. AE-1.03 P0002217.jpg9071 04220 Administration Reinforced Masonry and Veneer Systems Void between thru steel beams and masonry at beam pocket. Typical 12 locations. AE-1.02 P0002299.jpg9114 04220 Administration Reinforced Masonry and Veneer Systems Cold joint cracking at corner where two different walls meet. AE-1.02 P0002238.jpg9024 04220 Administration Reinforced Masonry and Veneer Systems Beams thru masonry walls have not been grouted in place. AE-1.1 P0002159.jpg

166 04220 Parking Garage Drywall/EIFS/SOFP Masonry wall not fire safed at top of wall. AA 1.07 P0000392.jpg279 04220 Parking Garage Drywall/EIFS/SOFP Wood shims left in top of wall and penetrating fire safeing AA-1.06 P0000538.jpg182 04220 Parking Garage Drywall/EIFS/SOFP Masonry walls at top and sides not fire safed. AA-1.07 P0000392.jpg181 04220 Parking Garage Drywall/EIFS/SOFP Compressable material and caulk not done at top and sides of wall. AA-1.07 P0000392.jpg207 04220 Parking Garage Drywall/EIFS/SOFP Edge of deck at masonry not fire safed. AA-1.07 P0002509.jpg215 04220 Parking Garage Drywall/EIFS/SOFP Top of masonry wall has not been fire safed. AA-1.07 P0000392.jpg165 04220 Parking Garage Miscellaneous Iron and Steel Stairs Vehicle corner guards not installed. AA 1.07 P0000516.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 8 of 154

Page 9: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

64 04220 Parking Garage Reinforced Masonry and Veneer Systems Door sill not complete, missing grout. P0000310.jpg73 04220 Parking Garage Reinforced Masonry and Veneer Systems Top of wall not properly fire caulked at CMU wall. AA 109 P0000510.jpg68 04220 Parking Garage Reinforced Masonry and Veneer Systems Masonry sill solider course not done. AA-1.01 P0000156.jpg56 04220 Parking Garage Reinforced Masonry and Veneer Systems Cap block missing at top of 4' wall. AA-1.01 P0000688.jpg34 04220 Parking Garage Reinforced Masonry and Veneer Systems Dowels and block at store front window sill not done to above print detail. AA-1.0123 04220 Parking Garage Reinforced Masonry and Veneer Systems At entrance to elevator CMU toothed - not per spec. AA-1.03 P0000545.jpg62 04220 Parking Garage Reinforced Masonry and Veneer Systems Veneer work from 6' 6" to 10' above footing chipped off and not replaced. AA-1.03 P0000307.jpg

292 04220 Parking Garage Reinforced Masonry and Veneer Systems Block missing under duct work. AA-1.06 P0000580.jpg213 04220 Parking Garage Reinforced Masonry and Veneer Systems Masonry wall I course below window not layed. AA-1.07 P0000514.jpg205 04220 Parking Garage Reinforced Masonry and Veneer Systems Wall over door at generator room incomplete. AA-1.07 P0000384.jpg228 04220 Parking Garage Reinforced Masonry and Veneer Systems Block missing at top of wall where conduit penetrates wall. AA-1.07 P0000370.jpg141 04220 Parking Garage Reinforced Masonry and Veneer Systems CMU top row last course at openings along wall not complete at louvers 14 total. AA1.07-1.08-

1.09P0000401.jpg

373 04220 Parking Garage Reinforced Masonry and Veneer Systems Large opening in CMU South and North elevator shaft walls not complete. Note: Structure steel beam penetrates thru both walls of elevator shaft.

AB4-1.02 P0000549.jpg

61 04220 Parking Garage Reinforced Masonry and Veneer Systems Masonry work incomplete. Not to detail above. SA- P0000156.jpg60 04220 Parking Garage Reinforced Masonry and Veneer Systems Masonry work incomplete. Dowles for horizontal bars missing. Work not to detail.

Bars bent.SA-1.01 P0000306.jpg

2504 04220 Site-Wide Concrete/Masonry/Reinforcing Steel (Site Retaining Walls)

From elevation 399.17 to station 2+00.00 masonry wall incomplete, not grouted an rebar rusted.

C-1.12 P0002437.jpg

2505 04220 Site-Wide Concrete/Masonry/Reinforcing Steel (Site Retaining Walls)

From station 2+10.67 to station 2+00.00 rebar have been cut flush with concrete starter wall.

C-1.12 P0002438.jpg

2508 04220 Site-Wide Concrete/Masonry/Reinforcing Steel (Site Retaining Walls)

From station 7+64.00 to station 4+36.00 1st course of masonry laid. Vertical reinforcing badly rusted and needs to be cleaned.

C-1.12 P0002440.jpg

2497 04220 Site-Wide Concrete/Masonry/Reinforcing Steel (Site Retaining Walls)

From station 5+72 to station 4+96 masonry wall not erected. C-1.13 P0002447.jpg

536 04220 Triple Gym Drywall/EIFS/SOFP Control joint at CMU to CMU North-South walls caulking not completed location at W-3.5 and V.5-3.5

AC-1.02 P0000415.jpg

442 04220 Triple Gym Reinforced Masonry and Veneer Systems Beam not grouted at CMU wall 4 locations. P0000859.jpg1451 04220 Triple Gym Reinforced Masonry and Veneer Systems Cement stains on block. Typical these rooms. P0002147.jpg

441 04220 Triple Gym Reinforced Masonry and Veneer Systems Grout around beam penetration at CMU wall above entrance door and West wall. P0000859.jpg473 04220 Triple Gym Reinforced Masonry and Veneer Systems Beam penetration thru CMU wall has not been grouted. AC 1.00 P0000827.jpg439 04220 Triple Gym Reinforced Masonry and Veneer Systems Wood embedded in CMU wall for openning at North wall. AC 1.00519 04220 Triple Gym Reinforced Masonry and Veneer Systems Grouting and/or dry packing of area under structural steel member where penetration of

CMU walls occurred has not been completed at East-West-South walls.AC-1.02 P0000827.jpg

537 04220 Triple Gym Reinforced Masonry and Veneer Systems Grouting or dry pack of beam past thru CMU wall is not completed at East-South. AC-1.02 P0000827.jpg505 04220 Triple Gym Reinforced Masonry and Veneer Systems Grouting and/or dry packing of area under structural steel beam where penetration of

CMU wall occures have not been completed total of 4 areas effected in Team room and entrance area.

AC-1.02 P0000827.jpg

524 04220 Triple Gym Reinforced Masonry and Veneer Systems Block out at CMU wall at line 3.8 correction required. Left space void. AC-1.02 P0000860.jpg523 04220 Triple Gym Reinforced Masonry and Veneer Systems Grouting and/or dry packing of area under structure steel members where penetration of

CMU wall occures have not been completed. 5 Different areas effected in room.AC-1.02 P0000827.jpg

1365 04220 Triple Gym Reinforced Masonry and Veneer Systems Grout stain from top of elec. box down typical condition on wall. AC-1.02 P0002195.jpg516 04220 Triple Gym Reinforced Masonry and Veneer Systems CMU block cut out. Penetration at 3.8 line correction required (Left space void). AC-1.02 P0000860.jpg

1449 04220 Triple Gym Reinforced Masonry and Veneer Systems Wood forms in block wall for 12 by 12 openings, 3 total. AC1.01 P0002145.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 9 of 154

Page 10: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

1370 04220 Triple Gym Reinforced Masonry and Veneer Systems Hair line cracking of CMU parapet wall and CMU wall on at line DD at five different spots, on line CC at three different spots.

AC1.01 P0002172.jpg

1371 04220 Triple Gym Reinforced Masonry and Veneer Systems Masonry beam between lines 4.2 to 5.5 at DD line is sagging about 3/4" at roof parapet elevation.

AC1.01 P0002168.jpg

1372 04220 Triple Gym Reinforced Masonry and Veneer Systems Hair line cracking at CMU joints and bottom side of CMU joints have not been grouted or tooled in area noted.

AC1.01 P0002166.jpg

1430 04220 Triple Gym Reinforced Masonry and Veneer Systems Open beam pocket no masonry or concrete for roof beam, one location East wall. AC1.01 P0002159.jpg1431 04220 Triple Gym Reinforced Masonry and Veneer Systems Beam pocket for thru steel roof beam not filled in with masonry/concrete. Typical 2

locations.AC1.01 P0002159.jpg

1463 04220 Triple Gym Reinforced Masonry and Veneer Systems Rebar floor dowels also horizontal bars at door openings coated with cement, typical. AC1.01 P0002141.jpg1434 04220 Triple Gym Reinforced Masonry and Veneer Systems Concrete trash not removed. One location, about 3" by 3". AC1.01 P0002157.jpg1455 04220 Triple Gym Reinforced Masonry and Veneer Systems Cement stains on concrete block. Typical all walls. AC1.01 P0002147.jpg1476 04220 Triple Gym Reinforced Masonry and Veneer Systems Typical condition: Efflorescent on CMU walls North, South, West sides of exterior walls. AC1.01 P0002129.jpg

1468 04220 Triple Gym Reinforced Masonry and Veneer Systems Concrete stains on block walls, typical this room. AC1.01 P0002147.jpg1438 04220 Triple Gym Reinforced Masonry and Veneer Systems Open beam pockets for through the wall steel roof beams. No masonry two openings

(One each East and West walls).AC1.01 P0002159.jpg

1465 04220 Triple Gym Reinforced Masonry and Veneer Systems Cement on block walls, typical. AC1.01 P0002147.jpg1464 04220 Triple Gym Reinforced Masonry and Veneer Systems Temp. wood frames not removed from masonry openings, 2 total 8 1/2" by 8 1/2". AC1.01 P0002145.jpg1460 04220 Triple Gym Reinforced Masonry and Veneer Systems Concrete stains on block, typical. AC1.01 P0002147.jpg1453 04220 Triple Gym Reinforced Masonry and Veneer Systems Cement stains on block, typical. AC1.01 P0002147.jpg1433 04220 Triple Gym Reinforced Masonry and Veneer Systems Temp. wood forms not removed from two, 12" by 12" openings in attic. AC1.01 P0002145.jpg1474 04220 Triple Gym Reinforced Masonry and Veneer Systems 3/16 Gap-crack found on CMU parapet wall-crack stair steps down from top of parapet

wall landing down under beam ledger angle located at North wall, approx. 1' from West side.

SC1.03 P0002109.jpg

1475 04220 Triple Gym Reinforced Masonry and Veneer Systems 1/16 Gap crack found on CMU parapet wall. Crack steps down from top of parapet wall, leading down under beam ledger angle. Located at West wall approx. 1' to 2' from North side.

SC1.03 P0002108.jpg

3259 04245 Academy Houses Drywall/EIFS/SOFP Door frames not caulked where block veneer abutts, door jambs and door head, typical. Level 1 at 16 doors total.

AB3-1.01 P0000960.jpg

3258 04245 Academy Houses Drywall/EIFS/SOFP Backer rod and caulking at top of masonry veneer and EIFS ceiling not started at level 1 and 2. Note: Level 3 veneer not installed. This is a typical condition.

AB3-1.01-1.02-1.03

P0000978.jpg

3357 04245 Academy Houses Reinforced Masonry and Veneer Systems From elevation 376.33 to top of roof parapet masonry veneer has not been installed. P0002463.jpg3340 04245 Academy Houses Reinforced Masonry and Veneer Systems From 363.33 to 376.33 masonry veneer is showing efflorescence. P0002461.jpg2177 04245 Academy Houses Reinforced Masonry and Veneer Systems From elevation 363.00 to top of parapet, craft paper and veneer track has not been

installed.AA-2.01 P0002466.jpg

2169 04245 Academy Houses Reinforced Masonry and Veneer Systems From elevation 363.00 to top of parapet no craft or veneer track has been installed. AA-2.02 P0002485.jpg2166 04245 Academy Houses Reinforced Masonry and Veneer Systems From elevation 376.33 to top of parapet craft paper and veneer track has not been

installed.AA-2.02 P0002466.jpg

5001 04245 Academy Houses Reinforced Masonry and Veneer Systems Masonry veneer is incomplete. AA-2.05-2.06 P0002480.jpg

5000 04245 Academy Houses Reinforced Masonry and Veneer Systems From elevation 359.00 to 363.00 masonry veneer incomplete from 363.00 to top of parapet craft paper and veneer track not installed.

AA-2.06 P0002479.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 10 of 154

Page 11: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

1396 04245 Academy Houses Reinforced Masonry and Veneer Systems Work at control joints and where veneer abuts other work, not done to above spec. Where CMU abutts other materials, flashing shall be installed to seal both materials from leaking. See spec section above.

AA4-1.4 P0002407.jpg

5009 04245 Academy Houses Reinforced Masonry and Veneer Systems From elevation 363.00 to roof parapet craft paper and veneer track has not been installed. AB1-2.01 P0002477.jpg

5008 04245 Academy Houses Reinforced Masonry and Veneer Systems On shear wall below level 1 to elevation 363.00 veneer track and veneer not installed. AB1-2.01 P0002478.jpg2184 04245 Academy Houses Reinforced Masonry and Veneer Systems Craft paper and veneer track has not been installed on Dens-glass. AB2-2.01 P0002472.jpg2187 04245 Academy Houses Reinforced Masonry and Veneer Systems Craft paper and veneer track has not been installed at elevation 363.00 to 376.33. AB2-2.01 P0002472.jpg2190 04245 Academy Houses Reinforced Masonry and Veneer Systems Craft paper and veneer track has not been installed on Dens-glass from 363.00 elevation

to top of roof parapet..AB2-2.01 P0002466.jpg

2193 04245 Academy Houses Reinforced Masonry and Veneer Systems Craft paper and veneer track has not been installed on Dens-glass. AB2-2.01 P0002466.jpg2194 04245 Academy Houses Reinforced Masonry and Veneer Systems Craft paper and veneer track has not been installed from elevation 363.00 to 376.33. AB2-2.01 P0002473.jpg2183 04245 Academy Houses Reinforced Masonry and Veneer Systems From elevation 363.00 to 376.33 Dens-glass installed. Craft paper or veneer track has not

been installed.AB2-2.01 P0002475.jpg

2199 04245 Academy Houses Reinforced Masonry and Veneer Systems Craft paper and veneer track is not installed from elevation 376.33 to top of parapet. AB2-2.01 P0002467.jpg2196 04245 Academy Houses Reinforced Masonry and Veneer Systems Craft paper and veneer has not been installed at elevation 363.00 to 376.33. AB2-2.01 P0002468.jpg2176 04245 Academy Houses Reinforced Masonry and Veneer Systems From elevation 363.00 to top of parapet, craft paper and veneer track has not been

installed.AB2-2.01 P0002466.jpg

2180 04245 Academy Houses Reinforced Masonry and Veneer Systems From elevation 363.00 to top of roof parapet masonry veneer has not been installed. AB2-2.01 P0002467.jpg3070 04245 Academy Houses Reinforced Masonry and Veneer Systems Typical block veneer, poor tooling at mitered corners, vertical joint at 16 locations, level

1. 16 locations, level 2AB3-1.01-1.02

P0001186.jpg

3153 04245 Academy Houses Reinforced Masonry and Veneer Systems At elevator door block veneer incomplete including kraft paper, veneer anchor find block veneer.

AB3-1.01-1.02-1.03

P0001381.jpg

3010 04245 Academy Houses Reinforced Masonry and Veneer Systems Veneer walls in corridor and stair shaft not installed. Note: Steel stud metal support system in place only.

AB3-1.01-1.02-1.03

P0001626.jpg

3251 04245 Academy Houses Reinforced Masonry and Veneer Systems Door frames not caulked where block veneer abutts door jambs and door head, typical. Level 2, 18 doors total.

AB3-1.02 P0000988.jpg

3253 04245 Academy Houses Reinforced Masonry and Veneer Systems 1) Masonry cap at stair stringer not caulked. 2) Horizontal expansion joint not caulked at level 2.

AB3-1.02 P0001218.jpg

3150 04245 Academy Houses Reinforced Masonry and Veneer Systems Block veneer incomplete at James & Sill at openning. AB3-1.02 P0001384.jpg3347 04245 Academy Houses Reinforced Masonry and Veneer Systems From elevation 389.00 to top of roof parapet masonry veneer is not installed. AB3-1.02 P0002464.jpg3152 04245 Academy Houses Reinforced Masonry and Veneer Systems At stair walls interior and building exterior block veneer not installed. AB3-1.03 P0001428.jpg3151 04245 Academy Houses Reinforced Masonry and Veneer Systems Typical, masonry veneer not installed. AB3-1.03 P0001358.jpg3356 04245 Academy Houses Reinforced Masonry and Veneer Systems From 376.33 to top of roof parapet wall masonry veneer has not been installed. AB3-2.01 P0002463.jpg3351 04245 Academy Houses Reinforced Masonry and Veneer Systems From elevation 389.00 to top of roor parapet wall veneer has not been installed. AB3-2.01 P0002464.jpg3352 04245 Academy Houses Reinforced Masonry and Veneer Systems From elevation 389.00 to top of roof parapet wall masonry veneer has not been installed. AB3-2.01 P0002464.jpg

3353 04245 Academy Houses Reinforced Masonry and Veneer Systems From elevation 389.00 to top of roof parapet wall masonry veneer has not been installed. AB3-2.01 P0002464.jpg

973 04245 Academy Houses Reinforced Masonry and Veneer Systems Fire sprinkler line penetrating veneer 1" clearance around sprinkler pipe not provided. Pipe over access door.

AB4-1.01 P0001554.jpg

968 04245 Academy Houses Reinforced Masonry and Veneer Systems Fire sprinkler pipe T section embedded in veneer. 1" clearance around sprinkler pipe not provided.

AB4-1.01 P0001556.jpg

972 04245 Academy Houses Reinforced Masonry and Veneer Systems Fire sprinkler line penetrating veneer 1" clearance around sprinkler pipe not provided. Pipe over access door.

AB4-1.01 P0001544.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 11 of 154

Page 12: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

997 04245 Academy Houses Reinforced Masonry and Veneer Systems Typical at exterior side of exterior doors, concrete block not caulked to door frame, 18 locations total. Doors 302-310-308-309-312-312.1-313-313.1-314-315-316-317-318-319-320-320.1-321-321.1

AB4-1.03 P0000960.jpg

3321 04250 Academy Houses Reinforced Masonry and Veneer Systems Motar dropings typical (about 10 by 150 foot area). AB3-1.01 P0001957.jpg3326 04250 Academy Houses Reinforced Masonry and Veneer Systems Motar droppings typical this area, about 10 by 120'. AB3-1.01 P0001957.jpg4045 04250 Academy Houses Reinforced Masonry and Veneer Systems Mortar droppings stuck floor slab near column line N.3, between 3.5 to 4.5, about 2 by

20 feet.AB4-1.01 P0001957.jpg

4046 04250 Academy Houses Reinforced Masonry and Veneer Systems Mortar droppings stuck to floor slab near column line N and N.3 between 3.5 to 5. AB4-1.03 P0001957.jpg692 04250-07920 Academy Houses Reinforced Masonry and Veneer Systems Gray CMU wall veneer cap block missing and top of wall not caulked for full length. AB4-1.01 P0001211.jpg371 04260 Parking Garage Drywall/EIFS/SOFP Rated wall framed gypsum board not installed incompleted at this time line 7.5 from S

to T. Podium level.AB4.01 P0000547.jpg

608 05129 Academy Houses General Contracting Safety cable has not been removed. AB4-1.02 P0001271.jpg657 05129 Academy Houses General Contracting Remove safety cable from beam over door 216. AB4-1.02

2029 05129 Academy Houses Miscellaneous Iron and Steel Stairs Metal deck removed for roof davit and not replaced. AB2-1.03 P0001818.jpg2040 05129 Academy Houses Miscellaneous Iron and Steel Stairs Metal deck removed for roof davit has not been replaced. AB2-1.03 P0001818.jpg

693 05129 Academy Houses Miscellaneous Iron and Steel Stairs Exterior handrail at second to third floor does not have safety guard screen installed. AB4-1.01 P0001220.jpg694 05129 Academy Houses Miscellaneous Iron and Steel Stairs Wall rail at interior and exterior walls has not been installed. AB4-1.01-

1.03P0001221.jpg

3171 05129 Academy Houses Structural Steel Remove safety posts (2) and safety cable hanging from beam. AB3-1.02 P0001442.jpg5012 05129 Academy Houses Structural Steel Elevator guide rail support columns have not been installed on floors noted. SB1-1.1-1.2-

1.3P0001347.jpg

2492 05129 Academy Houses Structural Steel Elevator guide rail support columns have not been installed on floors noted. SB2-1.1-1.2-1.3

P0001347.jpg

3358 05129 Academy Houses Structural Steel Elevator guide rail support columns have not been installed on floors noted. SB3-1.1-1.2-1.3

P0001347.jpg

1063 05129 Academy Houses Structural Steel Elevator guiderail support columns have not been installed. Sb4-1.1, 1.2, 1.3

P0001347.jpg

844 05129 Academy Houses Structural Steel Elevator guiderail support columns have not been installed. Sb4-1.1, 1.2, 1.3

P0001347.jpg

1062 05129 Academy Houses Structural Steel Elevator guiderail support columns have not been installed. Sb4-1.1, 1.2, 1.3

P0001347.jpg

9108 05129 Administration Miscellaneous Iron and Steel Stairs Ledger angleat CMU wall for decking support is not welded continuously, not per detail at all walls.

AE-1.02 P0002240.jpg

9016 05129 Administration Miscellaneous Iron and Steel Stairs Anchor bolts at ledger angle support lock nuts have not been installed in AE-1.03 P0002227.jpg9107 05129 Administration Miscellaneous Iron and Steel Stairs Ledger angle at CMU walls for decking support is not welded continuously, not per

detail at walls.AE-1.03 P0002225.jpg

9022 05129 Administration Structural Steel Structural steel beams and columns have not been installed for canopy area at North-West sides of building in area noted.

AE-1.01-1.02-1.03

P0002206.jpg

9014 05129 Administration Structural Steel Elevator guide rail support columns have not been installed on floors noted. SE-1.1-1.2-1.3 P0002247.jpg

9015 05129 Administration Structural Steel Elevator guide rail support columns have not been installed on floors noted. SE-1.1-1.2-1.3 P0002247.jpg

65 05129 Parking Garage Miscellaneous Iron and Steel Stairs Horizontal leg on ledger angle at bottom of solider course missing; ledge angle is not long enough to hold block.

P0000312.jpg

286 05129 Parking Garage Miscellaneous Iron and Steel Stairs Acid waste line needs guard protection. Q/5 line. AA-1.06 P0002516.jpg1467 05129 Triple Gym Metal Deck and Insulating Concrete Steel framing at roof hatch incomplete and deck opening not cut. AC1.01 P0002153.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 12 of 154

Page 13: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

1439 05129 Triple Gym Metal Deck and Insulating Concrete No steel supports for roof drains and overflows at underside of metal roof deck. 5 Locations.

AC1.01 P0002152.jpg

1363 05129 Triple Gym Miscellaneous Iron and Steel Stairs Ledger angles 6 by 4 by 5/16 is not provided as plan details require. 1) Angles not completed at corners. 2) Connection plates are not provided at splices 3)Welding of splices is not done.

SC1.03 P0002100.jpg

9021 05300 Administration Metal Deck and Insulating Concrete Decking partial installation in area of canopy at the Northwest side of building. AE-1.03 P0002206.jpg

1471 05300 Triple Gym Metal Deck and Insulating Concrete Roof decking seam and plug welds require removal of slag on plug welds and galvacon painting of seam and plug welds for protection from weather on exposed roof deck welds.

SC1.03 P0002098.jpg

1470 05300 Triple Gym Metal Deck and Insulating Concrete Decking not installed at area noted North-East corner of building. SC1.03 P0002104.jpg92 05400 Parking Garage Plumbing Storm drain lines require hangers from deck and to be braced column for vertical piping. AA 1.09 P0000502.jpg

2155 05410 Academy Houses Drywall/EIFS/SOFP Fire rating of wall is not complete at fire extinguisher cabinet, missing Dens-glass. AB2-1.01 P0001609.jpg2374 05410 Academy Houses Drywall/EIFS/SOFP Fire/smoke seal from deck edge to exterior wall at the floor is damaged. AB2-1.03 P0002031.jpg2210 05500 Academy Houses Miscellaneous Iron and Steel Stairs Backer plates have not been welded to studs for restroom. AB2-1.02-

1.03P0001762.jpg

398 05500 Parking Garage Miscellaneous Iron and Steel Stairs 1) Stair landing channel at East wall intermitted level angle clip connection missing. 2) 2nd angle clip connections for stair landing at bottom of 2nd deck not installed on North wall.

AA 1.02 P0000631.jpg

248 05500 Parking Garage Miscellaneous Iron and Steel Stairs A) 3-step stair at A.9 between 7.5 to 7.3 Handrail gap at end of Rail top not acceptable. B) Same rail at bottom step to drop to concrete floor. C) 2-step stair at C.9 Between 7.5 to 7.3 gap at handrail to gypsum wall.

AA 1.04 P0002528.jpg

157 05500 Parking Garage Miscellaneous Iron and Steel Stairs Sprinkler line requires a vehicle guard for protection of line against damage. AA 1.05 P0000577.jpg167 05500 Parking Garage Miscellaneous Iron and Steel Stairs Pipe guards not installed. Pipe must be protected from damage. AA 1.08 P0000473.jpg550 05500 Triple Gym Miscellaneous Iron and Steel Stairs Ledger angle has not been welded together to form a continuous angle as required by

plans.AC-1.02 P0000772.jpg

549 05500 Triple Gym Miscellaneous Iron and Steel Stairs Non-Bearing concrete block walls (Shown on sheet SC 1.4) 6 by 4 angles not installed per detail for CMU walls.

AC-1.02 P0000817.jpg

542 05500 Triple Gym Miscellaneous Iron and Steel Stairs Ledger angle has not been welded together to form a continuous angle as required by plans.

AC-1.02 P0000772.jpg

534 05500 Triple Gym Miscellaneous Iron and Steel Stairs Ledger angle has not been welded together to form a continuous angle as required by plans.

AC-1.02 P0000772.jpg

895 05510 Academy Houses Acoustical Ceilings In rooms noted separation of all ceiling hanging and bracing wires are not at least 6" from all unbraced ducts, pipes, conduits etc,. grid system rejected. T-bar ceiling rejected.

AB4-1.01 P0001043.jpg

5080 05510 Academy Houses Miscellaneous Iron and Steel Stairs Stairs stringer, risers, T.S. columns and intermittent landing erected temporary track welded in place, not complete.

AB1-1.01-1.02-1.03

P0002050.jpg

3157 05510 Academy Houses Miscellaneous Iron and Steel Stairs Metal hand rails incomplete at levels 1-2-3. Missing grab bars and exterior hand rails. AB3-1.01-1.02-1.03

P0001221.jpg

971 05510 Academy Houses Miscellaneous Iron and Steel Stairs Wall rail at stair veneer wall not installed. AB4-1.01-1.02-1.03

P0001221.jpg

969 05510 Academy Houses Miscellaneous Iron and Steel Stairs Guard screen for exterior hand rail wall not installed. AB4-1.01-1.02-1.03

P0001220.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 13 of 154

Page 14: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

360 05510 Parking Garage Miscellaneous Iron and Steel Stairs Remove all drilled anchor erection aids at bottom of slabs in stair wells. A 103, 106, 109

362 05510 Parking Garage Miscellaneous Iron and Steel Stairs Remove temporary angles on sides of stringers. A 109 P0000669.jpg380 05510 Parking Garage Miscellaneous Iron and Steel Stairs Handrail not installed at CMU walls all levels. AA 1.02 P0000766.jpg381 05510 Parking Garage Miscellaneous Iron and Steel Stairs 12" angle for stair support at South end at smooth face CMU has a slotted hole for the

stringer (shop fab)AA 1.02 P0000754.jpg

392 05510 Parking Garage Miscellaneous Iron and Steel Stairs Structural angle for stairs not installed at bottom on L-2 landing. AA 1.02 P0000620.jpg394 05510 Parking Garage Miscellaneous Iron and Steel Stairs Some of the drilled anchors are missing at 1st landing of stairs and other areas on the

stairs.AA 1.02 P0000616.jpg

395 05510 Parking Garage Miscellaneous Iron and Steel Stairs Nuts and washer missing on stair stringer at first landing for soft bolts and drilled anchors.

AA 1.02 P0000618.jpg

396 05510 Parking Garage Miscellaneous Iron and Steel Stairs At 1.9 line from M.9 to N. 2nd floor level stair pan, 2nd angle support not installed. AA 1.02 P0000642.jpg399 05510 Parking Garage Miscellaneous Iron and Steel Stairs Stair landing channel at 2nd floor intermitted level to wall concrete column at North East

corner not anchored to column.AA 1.02 P0000636.jpg

405 05510 Parking Garage Miscellaneous Iron and Steel Stairs 2-3/4" anchors at level 1 slab for stair stringer have not been tightened per code requirement.

AA 1.02

397 05510 Parking Garage Miscellaneous Iron and Steel Stairs 1) General clean up of handrail and stair treads, stair pan not complete. 2) Wall rails not installed.

AA 1.02-1.05 P0000643.jpg

385 05510 Parking Garage Miscellaneous Iron and Steel Stairs Remove all erection aids for stairs at underside slabs. AA 1.02-1.05 P0000665.jpg

382 05510 Parking Garage Miscellaneous Iron and Steel Stairs Grid and clean all hand rail welds. AA 1.02-1.05 P0000658.jpg

393 05510 Parking Garage Miscellaneous Iron and Steel Stairs Welds have not been primed and cleaned. AA 1.02-1.05-1.08

P0000620.jpg

391 05510 Parking Garage Miscellaneous Iron and Steel Stairs Washers have not been installed on all soft bolts for stairs. AA 1.02-1.05-1.08

P0000634.jpg

359 05510 Parking Garage Miscellaneous Iron and Steel Stairs Hand rail not installed at concrete stair at entrance door P 106. AA 1.03 P0000761.jpg386 05510 Parking Garage Miscellaneous Iron and Steel Stairs Large gap at stair landing on L-2 at main support angle and landing support angle. Bolts

appear to be drilled out of level and too close to edge of CMU wall.AA 1.04 P0000639.jpg

404 05510 Parking Garage Miscellaneous Iron and Steel Stairs From PL-1 side angle support at North & South side of 2nd level intermitted landing pan not welded to pan.

AA 1.05 P0000649.jpg

355 05510 Parking Garage Miscellaneous Iron and Steel Stairs Gap at end of wall handrail to concrete and CMU walls at all elevator levels not acceptable from 3rd level thru 1st level.

AA 1.06, 1.09 AA 1.03

P0000699.jpg

379 05510 Parking Garage Miscellaneous Iron and Steel Stairs Top plate treshold at top of stair stringer at 3rd floor elevator not installed. AA 1.08 P0000660.jpg401 05510 Parking Garage Miscellaneous Iron and Steel Stairs Ledger angle at CMU support to slab on line 1.5 between N to M.6 has not been

installed. (Removal of non fire rated wood used as support required).AA 1.08 P0000666.jpg

365 05510 Parking Garage Miscellaneous Iron and Steel Stairs No handrail installed at intermitted East side. 1 1/2" gap at end of hand rail to CMU wall not acceptable to code.

AA 1.09 P0000676.jpg

363 05510 Parking Garage Miscellaneous Iron and Steel Stairs Top of stair at line 7.5 is not structually connected (Note; support wall concrete not placed.)

AA 1.09 P0000669.jpg

357 05510 Parking Garage Miscellaneous Iron and Steel Stairs Kick plate not complete at top of L-3 landings. This occurs at shear wall and at stringer. AA 109 P0000695.jpg416 05510 Parking Garage Miscellaneous Iron and Steel Stairs Room partition hand rail at end of stair on line D.4 from 7.4 to 7.5 is not installed per

plan detail 1/AA 4.01.AA1.01 P0000749A.jpg

418 05510 Parking Garage Miscellaneous Iron and Steel Stairs All wall hand rails in corridor not as per ADA requirements. AA1.04 P0000753A.jpg1377 05810 Triple Gym Flashing and Sheet Metal Seismic joint flashing and membrane not installed, two locations. (W & 2.0, T & 2.0). P0002182.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 14 of 154

Page 15: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

1447 05921 Triple Gym Structural Steel Steel support of metal roof decking not installed at roof 18" by 18" openings. AC1.01 P0002153.jpg155 06010 Parking Garage Electrical (School) Exposed box not installed per spec. Specs require cast boxes in exposed areas. AA 1.07 P0000474.jpg

9109 06100 Administration General Contracting Remove wood ladder. AE-1.02 P0002233.jpg3335 06100-03300 Academy Houses Concrete (School) Shaped 2X4 sleeper and concrete curb not installed for pan flashing. AA-1.11 P0002451.jpg3331 06100-03300 Academy Houses Concrete (School) Shaped 2X4 sleeper and concrete curb not installed. AA-1.12 P0002451.jpg4024 06100-03300 Academy Houses Concrete (School) Shaped 2X4 sleepers and concrete curb not installed. AA-1.134003 06100-03300 Academy Houses Concrete (School) Shaped 2X4 sleepers and concrete curb not installed. AA1.122436 06110 Academy Houses Electrical (School) Conductors missing in boxes. AB2-1.01 P0001604.jpg5085 07110 Academy Houses Roofing and Waterproofing Elevator shaft masonry walls at column line C.9 to D.1 and 11.5 to 11.7 have not been

water proofed on soil side.AB1-1.01 P0002036.jpg

2182 07110 Academy Houses Roofing and Waterproofing Water proofing membrane has not been installed over sheet metal at elevation 363.00. AB2-2.01 P0002474.jpg2192 07110 Academy Houses Roofing and Waterproofing Water proofing membrane is not installed over metal flashing at elevation 363.00. AB2-2.01 P0002473.jpg2195 07110 Academy Houses Roofing and Waterproofing Water proofing membrane has not been installed over metal flashing at elevation 363.00. AB2-2.01 P0002473.jpg

9003 07110 Administration Roofing and Waterproofing From elevation 363.00 to 377.67 water proofing has not been installed on below grade masonry.

AE-2.01 P0002483.jpg

9004 07110 Administration Roofing and Waterproofing From elevation 363.00 to 377.67 water proofing membrane on below grade masonry has not been installed.

AE-2.02 P0002483.jpg

2494 07110 Site-Wide Drywall/EIFS/SOFP From station 4+96 to station 4+76 extruded polystyrene board has deteriorated and fallen off of masonry retaining wall.

C-1.13 P0002449.jpg

2499 07110 Site-Wide Roofing and Waterproofing At corner or walls # 5 and 15 at station 3+96.92 cracks on wall allowing water to drain thru.

C-1.12 P0002430.jpg

2501 07110 Site-Wide Roofing and Waterproofing At station 3+55 water draining thru crack in wall. C-1.12 P0002430.jpg2498 07110 Site-Wide Roofing and Waterproofing From station 5+40.00 to intersection of wall # 5 at station 3+96.92 cracks in wall

allowing water to drain thru.C-1.13 P0002431.jpg

1368 07110 Triple Gym Roofing and Waterproofing Membrane and top penetration board damaged. AC-1.02 P0002193.jpg3338 07110-07511 Academy Houses Roofing and Waterproofing Sheet membrane water proofing and built up roofing not installed. AA-1.11 P0002453.jpg2179 07110-07511 Academy Houses Roofing and Waterproofing Water proofing membrane and built up roofing is not installed. AA-1.11 P0002453.jpg2175 07110-07511 Academy Houses Roofing and Waterproofing Water proofing membrane and built up roofing not installed. AA-1.11 P0002453.jpg2173 07110-07511 Academy Houses Roofing and Waterproofing Water proofing membrane and built up roofing are not installed. AA-1.11 P0002453.jpg3333 07110-07511 Academy Houses Roofing and Waterproofing Water proof membrane and built roofing not installed. AA-1.12 P0002453.jpg3329 07110-07511 Academy Houses Roofing and Waterproofing Water proof membrane and built up roofing installed. AA-1.12 P0002453.jpg4030 07110-07511 Academy Houses Roofing and Waterproofing Water proof membrane and built up roofing not installed. AA-1.134001 07110-07511 Academy Houses Roofing and Waterproofing Water proof membrane and built up roofing not installed. AA1.121477 07110-07511 Triple Gym Roofing and Waterproofing Water proof membrane and built up roofing not installed. AA1.13 P0002548.jpg2321 07210 Academy Houses Drywall/EIFS/SOFP Fire proofing has been sprayed on sprinkler head completely enclosing head. Replace

head.AB1-1.01 P0001705.jpg

5127 07210 Academy Houses Drywall/EIFS/SOFP Insulation not installed in exterior walls. AB1-1.02 P0001676.jpg5112 07210 Academy Houses Drywall/EIFS/SOFP Insulation is not installed in corridor walls 2nd and 3rd floors. AB1-

1.02,1.03P0001984.jpg

2328 07210 Academy Houses Drywall/EIFS/SOFP Wall insulation is not complete at rated walls in all rooms noted. AB2-1.01-1.02-1.03

P0001710.jpg

3000 07210 Academy Houses Drywall/EIFS/SOFP EIFS exterior finish bubbling or blistering at surface. South exterior elevation. AB3-1.02-1.0-3

P0002351.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 15 of 154

Page 16: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

3001 07210 Academy Houses Drywall/EIFS/SOFP EIFS exterior finish bubbling or blistering at surface. North exterior elevations. AB3-1.02-1.0-3

P0002353.jpg

952 07210 Academy Houses Drywall/EIFS/SOFP Insulation incomplete at wall between column line 1.6 to exterior wall in attic, two rooms-one location each.

AB4-1.02 P0001216.jpg

707 07210 Academy Houses Drywall/EIFS/SOFP Exterior wall building insulation (batting) is not provided at bottom beam flange elevation.

AB4-1.02 P0002502.jpg

563 07210 Triple Gym Drywall/EIFS/SOFP Provide expansion joint at corridor entry door 126 and door 125 between buildings. AC-1.02 P0000945.jpg2145 07220 Academy Houses Plumbing Plumbing line penetration at rated wall is not fire stopped at F-2.2. AB2-1.02 P0002007.jpg3339 07240 Academy Houses Drywall/EIFS/SOFP From 376.33 elevation to top of parapet EIFS blistering in various locations. P0002465.jpg4006 07240 Academy Houses Drywall/EIFS/SOFP Between elevations 376.33 to 384 EIFS wall stained. AA2.014008 07240 Academy Houses Drywall/EIFS/SOFP From elevation 363.00 and 389.00 EIFS has marks and stains. AA2.014007 07240 Academy Houses Drywall/EIFS/SOFP From elevation 376.370 402.33 EIFS panels have marks and stains. AA2.015079 07240 Academy Houses Drywall/EIFS/SOFP Plaster over spray stuck to floor, typical B.7 to C from 11 to 21.4. AB1-1.02 P0002033.jpg2361 07240 Academy Houses Drywall/EIFS/SOFP Insulation of exterior wall is incomplete. AB2-1.01 P0001676.jpg2146 07240 Academy Houses Drywall/EIFS/SOFP Insulation at exterior walls on 1st floor to 2nd floor has not been provided at line 2-E.8 to

F.AB2-1.02 P0002008.jpg

2107 07240 Academy Houses Drywall/EIFS/SOFP 1) Hole in Dens glass board at exterior wall E.9-2. 2) Insulation has not been provided. AB2-1.03 P0001988.jpg2197 07240 Academy Houses Drywall/EIFS/SOFP EIFS work incomplete from 376.33 elevation to roof parapet. AB2-2.01 P0002468.jpg2181 07240 Academy Houses Drywall/EIFS/SOFP Finish coat on EIFS spandrels has not been installed. AB2-2.01 P0002472.jpg2198 07240 Academy Houses Drywall/EIFS/SOFP EIFS is not installed from elevation 376.33 to top of parapet. AB2-2.01 P0002466.jpg2188 07240 Academy Houses Drywall/EIFS/SOFP EIFS work incomplete at elevation 376.33. AB2-2.01 P0002472.jpg3028 07240 Academy Houses Drywall/EIFS/SOFP 1st and 2nd layers of Dens glass board have not been installed at doors noted. AB3-1.01-

1.02-1.03P0001596.jpg

3345 07240 Academy Houses Drywall/EIFS/SOFP At elevation 376.00 EIFS blistering and peeling. AB3-2.01 P0002465.jpg3027 07240 Academy Houses Drywall/EIFS/SOFP 1st and 2nd layers of Dens glass board have not been completed for EIFS corridor door

entrances.AB3-3.01 P0001596.jpg

4013 07240 Academy Houses Drywall/EIFS/SOFP EIFS surfaces discolored, contain swirl marks and stains. AB4-2.022419 07250 Academy Houses Electrical (School) Conduit is not properly fire stopped. AB2-1.01 P0001649.jpg2341 07255 Academy Houses Drywall/EIFS/SOFP Top of all walls have not been fire proofed. AB1-1.01 P0001723.jpg5123 07255 Academy Houses Drywall/EIFS/SOFP 9 Beams for roof davits supports have not been fire proofed. AB1-1.03 P0001818.jpg2449 07255 Academy Houses Drywall/EIFS/SOFP Both sides of work room walls are not fire proofed at top of walls. AB2-.1012352 07255 Academy Houses Drywall/EIFS/SOFP Framing angle clips attached to beam is not fire proofed. AB2-1.01 P0001694.jpg2416 07255 Academy Houses Drywall/EIFS/SOFP Top of wall to deck is not fire proofed. AB2-1.01 P0001720.jpg2476 07255 Academy Houses Drywall/EIFS/SOFP Top of West wall has not been fire proofed. AB2-1.01 P0001078.jpg2203 07255 Academy Houses Drywall/EIFS/SOFP Fire proof patching required where angle clips for stud walls attach to beams in the

following locations; 1) B.5-3.4 2) B.5-3.8 3) B.5-3.9 in all rooms and floors noted.AB2-1.01-1.02-1.03

P0001684.jpg

2257 07255 Academy Houses Drywall/EIFS/SOFP Tops of rated walls to deck are not fire proofed. AB2-1.02 P0001078.jpg2473 07255 Academy Houses Drywall/EIFS/SOFP At fire rated corridor wall, top of wall to deck is not fire proofed about 12 foot lineal. AB2-1.02 P0001078.jpg2472 07255 Academy Houses Drywall/EIFS/SOFP At fire rated corridor wall, top of wall to deck is not fire proofed about 12 foot lineal. AB2-1.02 P0001078.jpg2255 07255 Academy Houses Drywall/EIFS/SOFP Tops of rated walls to deck are not fire stopped. AB2-1.02 P0001078.jpg2261 07255 Academy Houses Drywall/EIFS/SOFP Tops of rated walls are not fire stopped. AB2-1.02 P0001078.jpg2244 07255 Academy Houses Drywall/EIFS/SOFP Top of wall to metal deck is not fire proofed at rated wall. AB2-1.02 P0001078.jpg2266 07255 Academy Houses Drywall/EIFS/SOFP Top of wall to metal deck at rated duct shaft is not fire proofed. AB2-1.02 P0001078.jpg2313 07255 Academy Houses Drywall/EIFS/SOFP Top of wall at duct shaft is not fire proofed. AB2-1.02 P0001078.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 16 of 154

Page 17: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

2276 07255 Academy Houses Drywall/EIFS/SOFP Top of wall to deck is not fire proofed. AB2-1.02 P0001078.jpg2287 07255 Academy Houses Drywall/EIFS/SOFP Top of wall to metal deck is not fire proofed. AB2-1.02 P0001400.jpg2037 07255 Academy Houses Drywall/EIFS/SOFP Fireproofing missing on beam in ceiling at roof davit. AB2-1.03 P0001818.jpg2375 07255 Academy Houses Drywall/EIFS/SOFP Top of wall is not fire proofed at deck. 3 Locations total. AB2-1.03 P0001720.jpg2030 07255 Academy Houses Drywall/EIFS/SOFP Fireproofing missing on structural beam. AB2-1.03 P0001818.jpg2369 07255 Academy Houses Drywall/EIFS/SOFP Fire proof patch clamp and beam for trapeze hanger. AB2-1.03 P0001136.jpg2027 07255 Academy Houses Drywall/EIFS/SOFP Top of wall to beam is not fire proofed at rated walls. AB2-1.03 P0001490.jpg2002 07255 Academy Houses Drywall/EIFS/SOFP Fire proofing at roof davit beams in 3 places has not been done. AB2-1.03 P0001818.jpg2010 07255 Academy Houses Drywall/EIFS/SOFP Fireproofing at top of wall to beam is missing. AB2-1.03 P0001858.jpg3267 07255 Academy Houses Drywall/EIFS/SOFP Top of wall at line G.3 for corridor is not fire proofed and line 5.2 also not fire proofed at

top of north wall.AB3-1.01 P0001373.jpg

3254 07255 Academy Houses Drywall/EIFS/SOFP Where top of wall meets bottom of steel floor beam not sealed to maintain fire rating, in void space under stair landing.

AB3-1.01 P0001421.jpg

3221 07255 Academy Houses Drywall/EIFS/SOFP Top of wall corridor and exterior in rooms above have not been fire proofed at beam. Rated walls in rooms and corridor have not been fire proofed, at rooms listed above.

AB3-1.01 P0001432.jpg

3057 07255 Academy Houses Drywall/EIFS/SOFP At top of fire rated walls to deck and beams fire proofing is not done. East-West-South sides of room.

AB3-1.01 P0001557.jpg

3228 07255 Academy Houses Drywall/EIFS/SOFP Fire proofing patch required at unistrut. At bottom of beam for electrical sway brace connection.

AB3-1.01 P0001423.jpg

3317 07255 Academy Houses Drywall/EIFS/SOFP East-West walls have not been fire proofed at top of wall. AB3-1.01 P0001388.jpg3009 07255 Academy Houses Drywall/EIFS/SOFP EIFS exterior insulation and finish system at ceiling not installed at all levels for stair

shaft. Note: Steel stud frame in place only.AB3-1.01-1.02-1.03

P0001626.jpg

3186 07255 Academy Houses Drywall/EIFS/SOFP Top of wall is not fire proofed at East and South side of room. AB3-1.02 P0001427.jpg3109 07255 Academy Houses Drywall/EIFS/SOFP Fire stop at top of wall to beam at rated walls incomplete. AB3-1.02 P0001490.jpg3170 07255 Academy Houses Drywall/EIFS/SOFP Top of wall at deck not fire proofed at South wall to elevator & South East corner of

room on East wall.AB3-1.02 P0001078.jpg

3187 07255 Academy Houses Drywall/EIFS/SOFP Top of wall to beam is not fire proofed on West and South walls .Note: South corridor wall is not fire proofed on both sides of wall.

AB3-1.02 P0001426.jpg

3160 07255 Academy Houses Drywall/EIFS/SOFP Fire proof patch areas where fire proofing required electrical clamp attached to 5.S beam. Total of 4 places in room.

AB3-1.02 P0001136.jpg

3126 07255 Academy Houses Drywall/EIFS/SOFP At top of walls to deck and beams not fire proofed at corridor wall line G.3, Janitor 303 Room and Electrical Room 304 line 4.6, Vestibule 302 line 5.2.

AB3-1.03 P0001078.jpg

3019 07255 Academy Houses Drywall/EIFS/SOFP At top of fire rate wall to deck fire proofing is not done. AB3-1.03 P0001078.jpg3037 07255 Academy Houses Drywall/EIFS/SOFP Top of wall to deck not fire rated at South and West walls. AB3-1.03 P0001078.jpg3046 07255 Academy Houses Drywall/EIFS/SOFP 2 Unistrut connections to flange of beam fire proof patch missing. AB3-1.03 P0001560.jpg3021 07255 Academy Houses Drywall/EIFS/SOFP Fire proof patching of beam where hanger beam clamps used for fire sprinkler support

two locations L.7-2.5.AB3-1.03 P0001619.jpg

3041 07255 Academy Houses Drywall/EIFS/SOFP Fire proofing at top of rated wall to beam incomplete. AB3-1.03 P0001490.jpg824 07255 Academy Houses Drywall/EIFS/SOFP Patch fire proofed beam where beam flange was used for support of conduit. AB4-1.01 P0001134.jpg835 07255 Academy Houses Drywall/EIFS/SOFP Fire proof top of CMU wall and along side of riser pipe for fire sprinkler system South

wall line N3 from 6.0 to 5.5, and riser located at N.3-5.5.AB4-1.01 P0001173.jpg

634 07255 Academy Houses Drywall/EIFS/SOFP Fire proof patching required at following locations 1) N.9-5, 2)N.7-5, 3)N.6-5.2, 4)N.6-5.3

AB4-1.02 P0001308.jpg

594 07255 Academy Houses Drywall/EIFS/SOFP The East wall has not been fire proofed at top of wall. Drywall not repaired at conduit penetrations.

AB4-1.02 P0001280.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 17 of 154

Page 18: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

956 07255 Academy Houses Drywall/EIFS/SOFP Attic area, West wall, top of wall to deck not fire proofed. AB4-1.02 P0001078.jpg704 07255 Academy Houses Drywall/EIFS/SOFP Top of wall at deck not fire proofed on corridor fire rated wall on line N.23 from 5.2 to

4.7.AB4-1.02 P0001078.jpg

793 07255 Academy Houses Drywall/EIFS/SOFP At top of elevator shaft rated walls have not been fire proofed to deck. AB4-1.03 P0001346.jpg808 07255 Academy Houses Drywall/EIFS/SOFP Top of fire rated corridor wall is not fire proofed and East wall of Janitor room 303 is not

fire proofed.AB4-1.03 P0001078.jpg

953 07255 Academy Houses Electrical (School) Attic area, patch steel beam fire proofing where cut away for sway brace to cable tray and to attach telcom box, two locations total.

P0001177.jpg

2072 07255 Academy Houses Electrical (School) Fire proof patch all conduit and equipment hanger on beams. AB2-1.03 P0001832.jpg937 07255 Academy Houses Electrical (School) Attic space; top fire rated walls not sealed, South and West walls typical. AB4-1.02-

1.03P0001467.jpg

2493 07255 Academy Houses Plumbing Fire proofing required where hangers for plumbing supports to beam attached to beams in following locations; 1) B.5-3.4 2) B.5-3.8 3) B.5-3.9 in all rooms and floors noted.

AB 2-1.01-1.02-1.03

P0001684.jpg

9025 07255 Administration Drywall/EIFS/SOFP Columns and floor beams have not been fire proofed. AE-1.01 P0002241.jpg9094 07255 Administration Drywall/EIFS/SOFP Fire proofing incomplete at columns, grid line 1.2 to 1.5 and C to D.3, 5 total. AE-1.02 P0002307.jpg9097 07255 Administration Drywall/EIFS/SOFP Fire proofing incomplete at beams, grid line 1.2 to 1.5 and B.8 to D.3, also, grid line 2 to

3 and D.3 to D.5.AE-1.02 P0002307.jpg

9101 07255 Administration Drywall/EIFS/SOFP Fire proofing of steel beams incomplete at masonry wall column line B.5 between 2-3. AE-1.02 P0002310.jpg9034 07255 Administration Drywall/EIFS/SOFP Fire proofing missing at "Z" clips at top of wall, typical. AE-1.02 P0002314.jpg

372 07255 Parking Garage Drywall/EIFS/SOFP Stiffener plates welded to structure steel beam have not been fire proof patched on 2nd floor elevator S.5 frame.

AB 4-1.02 P0000547.jpg

480 07255 Triple Gym Drywall/EIFS/SOFP Beam not fire proofed at the end of beam at plaster. AC 1.02471 07255 Triple Gym Drywall/EIFS/SOFP Bottom of structural beam has not been fire proofed in Vestiblule and corridor 118. AC 1.02 P0000806.jpg511 07255 Triple Gym Drywall/EIFS/SOFP Fire proofing of structure thru CMU walls have not been completed. Total of 4 areas

effected in Team Room 141 and Entrance area.AC-1.02 P0000859.jpg

508 07255 Triple Gym Drywall/EIFS/SOFP Fire proof patch beam at V.3-6.1 and V.3-6.6. AC-1.02 P0000885.jpg503 07255 Triple Gym Drywall/EIFS/SOFP Fire proof patch areas where Garvin F.P. hangar and sway bracing removed from beams.

Total of 8 in this area.AC-1.02 P0000886.jpg

560 07255 Triple Gym Drywall/EIFS/SOFP Angle bracing between ledger off CMU wall to beam are not fire proofed . AC-1.02 P0000809.jpg498 07255 Triple Gym Drywall/EIFS/SOFP Fire proofing removed at bottom beam flange where sprinkler pipe crosses at locations V-

6.6, V-5.4.AC-1.02 P0000921.jpg

522 07255 Triple Gym Drywall/EIFS/SOFP Fire proofing of structure steel members penetrating thru CMU walls are not complete. Areas shall be fire proof patched 5 diffent beams areas effect in room.

AC-1.02 P0000859.jpg

492 07255 Triple Gym Drywall/EIFS/SOFP Framing clips at beam need to be resprayed with Monocote. AC-1.02 P0000823.jpg518 07255 Triple Gym Drywall/EIFS/SOFP Conduit runs in room not complete. AC-1.02 P0000859.jpg502 07255 Triple Gym Drywall/EIFS/SOFP Patch fire proofing of beams where they penetrate thru CMU wall. Total of 9 beam

penetration on line 7 between V.5 to T.AC-1.02 P0000827.jpg

1452 07255 Triple Gym Drywall/EIFS/SOFP Steel beams not fire proofed, typical. AC1.01 P0002145.jpg1444 07255 Triple Gym Drywall/EIFS/SOFP Temporary plastic protection falling off fire proofed beams and columns. Fire proofing

damaged due to rains.AC1.01 P0002148.jpg

455 07255 Triple Gym Electrical (School) Patch fire proofing at hanger clamps. AC 1.00 P0000823.jpg489 07255 Triple Gym Electrical (School) Monokote removed to install conduit hanger supports and shall be replaced. AC-1.02 P0000823.jpg493 07255 Triple Gym Electrical (School) Monocote removed around unistalled clip hanger. AC-1.02 P0000823.jpg452 07255 Triple Gym Fire Protection Fire sprinkler line has rubbed off the Monokote above door 123.1 AC 1.00 P0000836.jpg474 07255 Triple Gym Fire Protection Hanger for pipe on beams need to be patched with fire proofing. AC 1.00 P0000823.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 18 of 154

Page 19: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

486 07255 Triple Gym Fire Protection 4 Clip hanger to be patched with fire proofing. AC-1.02 P0000823.jpg490 07255 Triple Gym Fire Protection Monokote removed to install pipe hangers and must be replaced. AC-1.02 P0000823.jpg487 07255 Triple Gym HVAC and Temperature Control Systems Monokote removed to install duct hanger supports and shall be replaced. AC-1.02 P0000823.jpg

456 07255 Triple Gym Plumbing Patch fire proofing at hanger clamps. AC 1.00 P0000776.jpg478 07255 Triple Gym Plumbing Fire proofing at beams for hanger clips removed need patching. AC 1.02 P0000823.jpg433 07255 Triple Gym Plumbing Patch fire proofing at support hangers to structure 6 locations. AC 1.02 P0000823.jpg488 07255 Triple Gym Plumbing Monokote removed to install pipe support hangers and shall be replaced. AC-1.02 P0000823.jpg499 07255 Triple Gym Plumbing Fire proof patch hanger rod clip to beam where pipe hung at line 5.4 between V.4 to U. AC-1.02 P0000924.jpg573 07255 Triple Gym Plumbing Repair fireproofing at all beams where pipe support hangers are placed and fire proofing

has been removed.AC-1.02 P0000823.jpg

5073 07270 Academy Houses Drywall/EIFS/SOFP Foil backed mineral wool and smoke/fire caulk not installed between deck and exterior framing East wall room 221 and North wall 212 to 204 and corridor C.9-19.8 to 17.4.

AB1-1.02 P0002063.jpg

5111 07270 Academy Houses Drywall/EIFS/SOFP Foil backed mineral and smoke fire seal caulk not installed in East wall. AB1-1.02 P0001885.jpg5121 07270 Academy Houses Drywall/EIFS/SOFP Foil backed mineral wool and smoke/fire seal not installed at edge of deck to exterior

wall framing.AB1-1.03 P0001885.jpg

5116 07270 Academy Houses Drywall/EIFS/SOFP Foil backed mineral wool and smoke/fire seal not installed at edge of deck to exterior wall framing.

AB1-1.03 P0001885.jpg

5115 07270 Academy Houses Drywall/EIFS/SOFP Foil backed mineral wool and smoke seal not installed at deck edge to exterior wall framing.

AB1-1.03 P0001885.jpg

2231 07270 Academy Houses Drywall/EIFS/SOFP 2 Holes in drywall North side of damper, repair of fire stop required. AB2-1.0 P0001741.jpg2490 07270 Academy Houses Drywall/EIFS/SOFP Repair oversize holes in shaft wall by the 4" conduit 2-3/4" and 1-1 1/2". AB2-1.01 P0001638.jpg2213 07270 Academy Houses Drywall/EIFS/SOFP 4 Holes in West fire rated wall, repair required. AB2-1.02 P0001769.jpg2012 07270 Academy Houses Drywall/EIFS/SOFP Smoke/fire seal at edge of deck to exterior wall, seal broken and foil backed mineral

wool pushed down in various locations.AB2-1.03 P0001885.jpg

2000 07270 Academy Houses Drywall/EIFS/SOFP Lightening holes in studs do not have smoke/fire seal West wall floor line. AB2-1.03 P0001903.jpg2001 07270 Academy Houses Drywall/EIFS/SOFP Smoke/ fire seal and foil back mineral wool at edge of deck to exterior wall has not been

done.AB2-1.03 P0001885.jpg

2006 07270 Academy Houses Drywall/EIFS/SOFP Smoke/fire sealed foil back mineral at edge of deck to exterior wall framing has not been completed.

AB2-1.03 P0001885.jpg

2013 07270 Academy Houses Drywall/EIFS/SOFP Smoke/fire seal at edge of deck to exterior wall framing has not been done. AB2-1.03 P0001885.jpg3029 07270 Academy Houses Drywall/EIFS/SOFP Fire rated expansion joint is not installed on podium deck slab. Note: Joint seal

temporary.AB3-1.01 P0001575.jpg

3268 07270 Academy Houses Drywall/EIFS/SOFP At top of wall at corridor where conduit sits on top of track is not fire stopped on both side of fire rated wall on line G.3.

AB3-1.01 P0001372.jpg

3121 07270 Academy Houses Drywall/EIFS/SOFP Smoke fire seal at edge of deck and exterior wall caulk seal broken and foil backed mineral wool pushed down.

AB3-1.02 P0001447.jpg

3200 07270 Academy Houses Drywall/EIFS/SOFP Smoke/fire seal between edge of deck and exterior wall framing caulk seal broken and foil backed mineral wool push down at East wall.

AB3-1.02 P0001447.jpg

3204 07270 Academy Houses Drywall/EIFS/SOFP Smoke fire seal missing at edge of deck seal broken and mineral wool (foil backed) missing.

AB3-1.02 P0001447.jpg

3203 07270 Academy Houses Drywall/EIFS/SOFP Smoke/fire seal at edge of deck to exterior framing caulk seal broken and foil backed mineral wool push down along East wall.

AB3-1.02 P0001447.jpg

3030 07270 Academy Houses Drywall/EIFS/SOFP Fire rated expansion joint is not installed at 2nd and 3rd floor slab. AB3-1.02-1.03

P0001572.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 19 of 154

Page 20: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

3007 07270 Academy Houses Drywall/EIFS/SOFP Smoke/fire seal is not completed at edge of slab and exterior stud wall framing on 2nd floor line 3-4 cells void, 3rd floor line 3-7 cells void, and 2nd & 3rd floors on line 2.6 and 2, all cells are void, no smoke / fire seal provided at all.

AB3-1.02-1.03

P0001623.jpg

3056 07270 Academy Houses Drywall/EIFS/SOFP Fire proofing at roof elevator shaft wall not done. AB3-1.02-1.03-1.04

P0001346.jpg

3040 07270 Academy Houses Drywall/EIFS/SOFP Smoke/fire seal at edge of deck to exterior wall framing caulk seal has been broken and foil back mineral wool pushed down in various locations on South wall.

AB3-1.03 P0001447.jpg

3052 07270 Academy Houses Drywall/EIFS/SOFP Smoke/fire seal at edge of deck to exterior framed wall, caulk seal broken and foil backed mineral wool pushed down.

AB3-1.03 P0001447.jpg

630 07270 Academy Houses Drywall/EIFS/SOFP 2-Wall penetration at floor level on West wall are not fire stopped at line 5.5 at N.8 and N.9.

AB4-1.02 P0001315.jpg

2448 07270 Academy Houses Electrical (School) 15 Conduits thru rated walls are not fire stopped. AB2-.101 P0001121.jpg2220 07270 Academy Houses Electrical (School) Fire stop the floor penetration under the main panels. AB2-1.0 P0001784.jpg2483 07270 Academy Houses Electrical (School) Conduit that penetrates the rated wall at the South East corner of the room has not been

fire stopped. 2-3/4" and 1-1" conduit.AB2-1.0 P0001633.jpg

2400 07270 Academy Houses Electrical (School) Conduit penetrations thru rated wall from room 113 thru workroom 124, to room 112, not fire stopped.

AB2-1.01 P0001078.jpg

2404 07270 Academy Houses Electrical (School) 4 Conduit penetration from room 115 thru workroom 125 to room 114 are not fire stopped.

AB2-1.01 P0001121.jpg

2417 07270 Academy Houses Electrical (School) 4 Flex and 5 conduit penetrations thru rated wall is not fire stopped. AB2-1.01 P0001121.jpg

2333 07270 Academy Houses Electrical (School) Fire stop all conduit penetrations on East and West walls 13-1", 4-4", 1-3", 2-2" and 4-3/4".

AB2-1.01 P0001722.jpg

2339 07270 Academy Houses Electrical (School) Conduit is half embedded in rated wall. AB2-1.01 P0001729.jpg2491 07270 Academy Houses Electrical (School) Fire proof trapeze hanger clamps above bus way. AB2-1.01 P0001639.jpg2411 07270 Academy Houses Electrical (School) 15 Conduit thru rated wall are not stopped. AB2-1.01 P0001652.jpg2329 07270 Academy Houses Electrical (School) 4S boxes on East wall require fire resistant pads in all rooms noted. AB2-1.01-

1.02-1.03P0001710.jpg

2330 07270 Academy Houses Electrical (School) 3-4S boxes require fire stopping at South rated wall in all rooms noted. AB2-1.01-1.02-1.03

P0001724.jpg

2202 07270 Academy Houses Electrical (School) 9 Conduits thru rated walls are not fire stopped. AB2-1.02 P0001652.jpg2273 07270 Academy Houses Electrical (School) 8 Conduits of various sizes thru rated wall are not fire stopped. AB2-1.02 P0001652.jpg2268 07270 Academy Houses Electrical (School) Seven 1" and two 4" conduit thru rated walls are not fire stopped. AB2-1.02 P0001652.jpg2212 07270 Academy Houses Electrical (School) Conduit penetrations not fire stopped at fire rated walls. 2 on South wall, 2 West wall. AB2-1.02 P0001769.jpg2302 07270 Academy Houses Electrical (School) Eight 1" Conduits thru rated wall are not fire stopped. AB2-1.02 P0001652.jpg2260 07270 Academy Houses Electrical (School) 2" conduits thru rated wall are not fire stopped. AB2-1.02 P0001121.jpg2298 07270 Academy Houses Electrical (School) 12 1" conduits thru rated walls are not fire stopped. AB2-1.02 P0001121.jpg2243 07270 Academy Houses Electrical (School) Six 1" and two 4" conduits thru rated wall are not fire stopped. AB2-1.02 P0001652.jpg2224 07270 Academy Houses Electrical (School) Fire stop all conduit floor penetrations: 4-2 1/2 ", 1-3", 3-1 1/2", 2-3/4" and 2-1". AB2-1.03 P0001779.jpg2108 07270 Academy Houses Electrical (School) Conduit penetration over door 311 South side of corridor rated wall line E. Total of 6

penetrations are not fire stopped.AB2-1.03 P0001980.jpg

2229 07270 Academy Houses Electrical (School) Conduit penetrations require fire stopping at East wall and North wall. AB2-1.03 P0001781.jpg2228 07270 Academy Houses Electrical (School) Conduit penetrations require fire stopping at West wall, total of 20 conduits. AB2-1.03 P0001780.jpg2016 07270 Academy Houses Electrical (School) 16 1" and 2 4" conduits thru rated wall are not fire stopped. AB2-1.03 P0001652.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 20 of 154

Page 21: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

3273 07270 Academy Houses Electrical (School) Conduit wall penetrations at rated walls are not fire stopped. 5 Penetrations at South wall and 3 penetrations at East wall.

AB3-1.01 P0001380.jpg

3309 07270 Academy Houses Electrical (School) Conduit penetrating riser shaft have not been fire stopped, 7 locations. AB3-1.01 P0001397.jpg3264 07270 Academy Houses Electrical (School) 4-Conduit penetrating thru top of wall at 2nd layer of gypsum board are not fire stopped. AB3-1.01 P0001373.jpg

3310 07270 Academy Houses Electrical (School) Conduit have not been fire stopped at floor 1-4", 1-3 1/2, 2-5", 5-1 1/2" and 2-4" floor penetration.

AB3-1.01 P0001405.jpg

3306 07270 Academy Houses Electrical (School) Conduit penetrations in West wall need to be fire stopped, 4 location. AB3-1.01 P0001397.jpg3059 07270 Academy Houses Electrical (School) 4 Conduit penetration at fire rated East wall not fire stopped. AB3-1.01 P0001557.jpg3012 07270 Academy Houses Electrical (School) Conduit penetration at fire rated wall not fire stopped. AB3-1.01 P0001121.jpg3168 07270 Academy Houses Electrical (School) Sleeved and non-sleeved floor deck penetrations are not fire stopped at following

locations; East wall; 4-4" dia sleeved holes & 1-1 1/2" dia non-sleeved hole. West wall; 1-4" dia sleeved hole & 2-3" sleeved holes & 1-1 1/2" non-sleeved hole. South wall;

AB3-1.02 P0001357.jpg

3163 07270 Academy Houses Electrical (School) Conduit wall penetraions at fire rated wall are not fire stopped at East wall. Total of 3 penetrations and at West wall a total 1 penetration East corner.

AB3-1.02 P0001453.jpg

3192 07270 Academy Houses Electrical (School) 3-Conduit penetrations at top of wall are not fire stopped at South corridor rated wall. AB3-1.02 P0001426.jpg3114 07270 Academy Houses Electrical (School) Conduit thru rated wall not fire stopped. AB3-1.02 P0001121.jpg3173 07270 Academy Houses Electrical (School) Buss duct deck penetration is not fire stopped, penetration is partially in non-rated wall. AB3-1.02 P0001443.jpg3082 07270 Academy Houses Electrical (School) Conduit at North wall and 4S box at North wall have not been fire stopped. 2 Locations,

4S box not identified.AB3-1.03 P0001532.jpg

3102 07270 Academy Houses Electrical (School) 14 Conduit penetrations thru rated walls have not been fire stopped. AB3-1.03 P0001121.jpg3091 07270 Academy Houses Electrical (School) Fire stopping has not been done at shaft wall in 4 locations, all 3/4" conduit. AB3-1.03 P0001484.jpg3134 07270 Academy Houses Electrical (School) Conduit wall penetrations at fire rated wall are not fire stopped. Total of 28 penetration

over door 302.AB3-1.03 P0001479.jpg

3020 07270 Academy Houses Electrical (School) 3 Flex conduit penetrating thru fire rated wall are not fire stopped in wall behind furred out steel stud frame.

AB3-1.03 P0001624.jpg

3124 07270 Academy Houses Electrical (School) Conduit penetrations at fire rated corridor wall not fire stopped. AB3-1.03 P0001492.jpg820 07270 Academy Houses Electrical (School) Seven ceiling penetrations have not been fire stopped at riser shaft. AB4-1.01 P0001146.jpg654 07270 Academy Houses Electrical (School) Conduit penetrations at fire rated wall not fire stopped a total of 16 conduits over door

202.AB4-1.02 P0001251.jpg

647 07270 Academy Houses Electrical (School) Conduit wall penetration not fire stopped on East rated wall. AB4-1.02 P0001257.jpg627 07270 Academy Houses Electrical (School) Cable tray and 14 penetration thru East and West walls not fire rated. AB4-1.02 P0002496.jpg632 07270 Academy Houses Electrical (School) Conduit wall penetration is not fire stopped at East fire rated wall at South East corner. AB4-1.02 P0001313.jpg619 07270 Academy Houses Electrical (School) Cable tray and 5 conduit penetration thru rated wall not fire stopped. AB4-1.02 P0001258.jpg617 07270 Academy Houses Electrical (School) Fire stop conduit in rated wall. AB4-1.02 P0001262.jpg713 07270 Academy Houses Electrical (School) 4 1" Conduit penetrations thru rated wall not fire stopped. AB4-1.02 P0001277.jpg715 07270 Academy Houses Electrical (School) 8 1 1/2 conduit and cable tray thru rated wall not fire stopped. AB4-1.02 P0001258.jpg789 07270 Academy Houses Electrical (School) 1) Sleeved and non sleeved deck penetrations have not been fire stopped at East wall a

total of 5 penetration. 2) At North West corner of room 2 penetrations.AB4-1.03 P0001357.jpg

809 07270 Academy Houses Electrical (School) Conduit penetrations and unistrut penetration at fire rated wall have not been fire stopped, a total of 25 conduit penetrations and 1 unistrut penetration.

AB4-1.03 P0001121.jpg

798 07270 Academy Houses Electrical (School) Conduit penetration at rated wall not fire stopped wall exit. AB4-1.03 P0001336.jpg791 07270 Academy Houses Electrical (School) 4 Conduit penetration on line 5.5 fire rated wall have not been fire stopped. AB4-1.03 P0001351.jpg727 07270 Academy Houses Electrical (School) 4s box and conduit penetration thru wall not fire stopped. AB4-1.03 P0001264.jpg

2451 07270 Academy Houses Fire Protection 6 Sprinkler penetrations thru rated wall don't have sleeves and are not fire stopped. AB2-.101 P0000529.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 21 of 154

Page 22: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

2290 07270 Academy Houses Fire Protection 2 Sprinkler lines are not fire stopped. AB2-1.01 P0001123.jpg2294 07270 Academy Houses Fire Protection 3 Sprinkler lines thru rated wall with sleeves and 1 without, not fire stopped. AB2-1.01 P0001123.jpg2413 07270 Academy Houses Fire Protection Sprinkler pipe thru rated wall has not been sleeved and not fire stopped. AB2-1.01 P0001650.jpg2264 07270 Academy Houses Fire Protection 3 Sprinkler lines with sleeves thru rated wall are not fire stopped. AB2-1.02 P0001123.jpg2267 07270 Academy Houses Fire Protection 2 Sprinkler lines with sleeves thru rated wall is not fire stopped. AB2-1.02 P0001123.jpg2274 07270 Academy Houses Fire Protection 2 Sprinkler lines in sleeves are not fire stopped at rated wall. AB2-1.02 P0001123.jpg2278 07270 Academy Houses Fire Protection 3 Sprinklers in sleeves thru rated wall are not fire stopped. AB2-1.02 P0001123.jpg2256 07270 Academy Houses Fire Protection 3 Sprinklers with sleeved penetrations are not fire stopped at rated wall. AB2-1.02 P0001123.jpg2247 07270 Academy Houses Fire Protection One sprinkler line sleeved thru rated wall is not fire stopped. AB2-1.02 P0001123.jpg2300 07270 Academy Houses Fire Protection 6 Sprinkler penetration thru rated wall, 2 with sleeves, 4 without, are not fire stopped. AB2-1.02 P0000542.jpg2318 07270 Academy Houses Fire Protection 2 Sprinkler lines thru rated wall is not fire stopped. AB2-1.02 P0001380.jpg2211 07270 Academy Houses Fire Protection Sprinkler line non-sleeved penetration at West side fire rated wall is not fire stopped. AB2-1.02 P0001761.jpg2306 07270 Academy Houses Fire Protection Three sprinkler lines without sleeves thru rated walls are not fire stopped. AB2-1.02 P0000529.jpg2024 07270 Academy Houses Fire Protection Sleeved sprinkler line thru rated walls are not fire stopped. AB2-1.03 P0001380.jpg2099 07270 Academy Houses Fire Protection Two fire sprinkler line sleeved and one fire sprinkler non-sleeved penetrations are not

fire stopped on line B, fire rated wall.AB2-1.03 P0001862.jpg

2092 07270 Academy Houses Fire Protection Fire sprinkler line penetrations not fire stopped, East wall two non-sleeved penetrations, South wall-1 sleeved penetration.

AB2-1.03 P0001806.jpg

3299 07270 Academy Houses Fire Protection A) 3 Sprinkler penetration thru rated wall no sleeve and not fire stopped B) 19 Penetration thru rated wall with sleeves have not been fire stopped.

AB3-1.01 P0000529.jpg

3058 07270 Academy Houses Fire Protection Sprinkler line penetration at fire rated wall, 1" clearance is not provided and is not fire stopped.

AB3-1.01 P0001557.jpg

3311 07270 Academy Houses Fire Protection Sprinkler pipe branch line has not been sleeved as required at rated West wall of room. AB3-1.01 P0001413.jpg3278 07270 Academy Houses Fire Protection Sleeved sprinkler penetrations at East fire rated wall is not fire stopped. AB3-1.01 P0001380.jpg3005 07270 Academy Houses Fire Protection 2 Sprinkler lines at top of wall change of elevator partially in in rated walls. Not

acceptable for code requirements.AB3-1.02 P0001644.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 22 of 154

Page 23: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

3208 07270 Academy Houses Fire Protection 11 Penetrations thru rated wall not fire stopped. AB3-1.02 P0001123.jpg3185 07270 Academy Houses Fire Protection Sprinkler line penetration is not sleeved and fire stopped at East rated wall. AB3-1.02 P0001426.jpg3008 07270 Academy Houses Fire Protection A) Fire sprinkler line penetration wall at M-3 not sleeved and penetration at M-2.6 sleeve

not fire stopped. B) Sprinkler pipe support over door 311 thru rated corridor require fire stopping at end of pipe. Note: Two different deficiencies.

AB3-1.03 P0001622.jpg

3042 07270 Academy Houses Fire Protection Two pipe penetrations thru rated wall for sprinkler pipe support not fire stopped. AB3-1.03 P0001544.jpg3129 07270 Academy Houses Fire Protection Fire sprinkler penetrations not sleeved and fire stopped at rated wall. AB3-1.03 P0001495.jpg3051 07270 Academy Houses Fire Protection 2 Pipe supports for sprinkler line penetrations thru wall not fire stopped. AB3-1.03 P0001544.jpg3101 07270 Academy Houses Fire Protection 26 Sleeved sprinkler penetrations thru rated walls not fire stopped. AB3-1.03 P0001123.jpg3085 07270 Academy Houses Fire Protection A sleeve has not been provided for pipe at shaft wall and head is close to wall. AB3-1.03 P0001481.jpg

831 07270 Academy Houses Fire Protection Sleeved fire sprinkler line at fire rated wall not fire stopped. AB4-1.01 P0001123.jpg646 07270 Academy Houses Fire Protection Fire sprinkler line penetrations at rated walls not sleeved or fire stopped. AB4-1.02 P0001257.jpg625 07270 Academy Houses Fire Protection Sprinkler line thru rated wall no sleeve and not fire stopped. AB4-1.02 P0000529.jpg796 07270 Academy Houses Fire Protection 2" Fire sprinkler line penetration is not sleeved or fire stopped at wall. AB4-1.03 P0001336.jpg

2236 07270 Academy Houses General Contracting 1/2" Cap thru concrete floor slab, floor fire rating is not maintained this area. AB2-1.012444 07270 Academy Houses HVAC and Temperature Control Systems 6 Duct penetrations thru rated walls are not fire stopped, 6 retaining angels are not

installed and 2 installed but not attached to ducts.AB2-.101 P0001467.jpg

2402 07270 Academy Houses HVAC and Temperature Control Systems 2 Refrigerant line penetration into duct shaft is not fire stopped at sleeve. AB2-1.01 P0001670.jpg

2410 07270 Academy Houses HVAC and Temperature Control Systems Rectangle duct is not fire stopped. AB2-1.01 P0001651.jpg

2409 07270 Academy Houses HVAC and Temperature Control Systems Round duct is not fire stopped at rated wall. AB2-1.01 P0001653.jpg

2367 07270 Academy Houses HVAC and Temperature Control Systems Refrigerant condensate line thru rated wall is not fire stopped and insulation damaged. AB2-1.01 P0001681.jpg

2011 07270 Academy Houses HVAC and Temperature Control Systems HVAC duct is not fire stopped at rated wall. AB2-1.03 P0001901.jpg

3139 07270 Academy Houses HVAC and Temperature Control Systems Exhaust air duct penetration not fire stopped at fire rated wall East side of room. AB3-1.03 P0001494.jpg

3038 07270 Academy Houses HVAC and Temperature Control Systems Round duct thru rated wall insulation not continuous thru wall and not fire stopped. AB3-1.03 P0001035.jpg

3044 07270 Academy Houses HVAC and Temperature Control Systems Unistrut penetration thru rated wall into corridor not fire rated. AB3-1.03 P0001563.jpg

644 07270 Academy Houses HVAC and Temperature Control Systems Exhaust duct penetration at East rated wall not fire stopped. AB4-1.02 P0001257.jpg

799 07270 Academy Houses HVAC and Temperature Control Systems Duct penetration at fire rated wall not fire stopped at wall exit. AB4-1.03 P0001336.jpg

2323 07270 Academy Houses Plumbing Floor penetrations at South wall have not been fire stopped, 2 penetrations. AB1-1.01 P0001715.jpg5049 07270 Academy Houses Plumbing 2 Vent penetrations thru deck not fire stopped. AB1-1.02 P0000867.jpg2395 07270 Academy Houses Plumbing 2 Plumbing line wall penetrations have not been fire stopped at East corridor wall and at

domestic water valve, identification is not provided.AB2-1.01 P0001057.jpg

2288 07270 Academy Houses Plumbing Plumbing line thru rated wall is not fire stopped. AB2-1.01 P0001057.jpg2305 07270 Academy Houses Plumbing 9 Plumbing penetrations of various sizes thru rated wall are not fire stopped. AB2-1.02 P0001057.jpg2207 07270 Academy Houses Plumbing Plumbing line penetration at rated south wall is not fire stopped at penetration. AB2-1.02 P0001766.jpg2297 07270 Academy Houses Plumbing 7 Plumbing penetrations thru rated walls are not fire stopped. AB2-1.02 P0001057.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 23 of 154

Page 24: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

2201 07270 Academy Houses Plumbing 5 Plumbing pipe thru rated wall is not fire stopped. AB2-1.02 P0001057.jpg2142 07270 Academy Houses Plumbing 2 Plumbing lines penetrate into corner of fire rated walls. 1Penetration at South wall is

not fire stopped and 1 penetration into corner connection hub half in wall not accepted to code.

AB2-1.02 P0002010.jpg

2100 07270 Academy Houses Plumbing Numerous penetrations for plumbing, gas, condensate, and unistrut penetrations at fire rated wall are not fire stopped on line B. Total of 5 penetrations.

AB2-1.03 P0001861.jpg

2109 07270 Academy Houses Plumbing 1) Water line penetrations over door 311 South side of corridor is not fire stopped. 2) Plumbing vent line partially in wall at D.9-2.7 location, and is not properly supported.

AB2-1.03 P0001979.jpg

2019 07270 Academy Houses Plumbing 4 Pipes thru rated wall are not fire stopped. AB2-1.03 P0001057.jpg2093 07270 Academy Houses Plumbing Two pipe penetrations at shaft wall not fire stopped. AB2-1.03 P0001807.jpg3271 07270 Academy Houses Plumbing Plumbing penetrations at fire rated walls not fire stopped at East wall 5 penetration at

South wall 6 penetration.AB3-1.01 P0001380.jpg

3184 07270 Academy Houses Plumbing Plumbing penetrations at fire rated walls are not fire stopped. South corridor wall 6 penetrations, East wall 5 penetrations.

AB3-1.02 P0001427.jpg

3013 07270 Academy Houses Plumbing Plumbing line floor penetration is not fire stopped at L.9-2.5. AB3-1.02 P0001657.jpg3115 07270 Academy Houses Plumbing Plumbing line penetration thru East rated wall not fire stopped. AB3-1.02-

1.03P0001475.jpg

3131 07270 Academy Houses Plumbing Plumbing lines and unistrut support for plumbing penetrating fire rated wall are not fire stopped. South corridor wall 6 penetrations, East wall 6 penetration.

AB3-1.03 P0001496.jpg

3017 07270 Academy Houses Plumbing Plumbing line 2nd and 3rd floor penetrations not fire stopped at L.2-3. AB3-1.03 P0001623.jpg3039 07270 Academy Houses Plumbing A) One plumbing pipe thru rated wall not fire stopped. B) Two unistruts thru rated wall

not fire stopped.AB3-1.03 P0001057.jpg

606 07270 Academy Houses Plumbing 4" and 2" floor penetrations have not been fire stopped. AB4-1.02 P0001263.jpg624 07270 Academy Houses Plumbing 6 Plumbing penetrations thru rated walls not fire stopped. AB4-1.02 P0001057.jpg616 07270 Academy Houses Plumbing 4 Plumbing penetration thru rated wall not fire stopped. AB4-1.02 P0001057.jpg649 07270 Academy Houses Plumbing Plumbing line penetration thru rated walls are not fire stopped, South wall a total of 6

penetrations, exit wall a total of 3 penetrations.AB4-1.02 P0001256.jpg

611 07270 Academy Houses Plumbing 3 Penetrations thru rated wall not fire stopped. AB4-1.02 P0001057.jpg614 07270 Academy Houses Plumbing 2" Acid waste line not fire stopped at floor penetration. AB4-1.02 P0001263.jpg641 07270 Academy Houses Plumbing Sleeved deck penetration is not fire stopped. AB4-1.02 P0001265.jpg801 07270 Academy Houses Plumbing Plumbing lines and unistrut wall penetration thru fire rated wall have not been fire

stopped, total of 8 on South corridor wall and 4 on exit wall.AB4-1.03 P0001336.jpg

788 07270 Academy Houses Plumbing 2 Plumbing line penetrations thru rated wall not fire stopped. AB4-1.03 P0001057.jpg9105 07270 Administration Electrical (School) Electrical conduits have not been fire stopped at floors or walls, typical. AE-1.02 P0002322.jpg9104 07270 Administration Fire Protection Fire sprinklers have not been fire stopped at floors or walls, typical. AE-1.02 P0002321.jpg9103 07270 Administration HVAC and Temperature Control Systems Ducts, no fire stopping at fire rated walls, typical. AE-1.02 P0002318.jpg

261 07270 Parking Garage Doors, Frames and Finish Hardware A) Wood shims used at door/frame to CMU wall not fire rated. B) Seal caulk and backer rod required at door framing to CMU.

AA 1.05 P0000562.jpg

257 07270 Parking Garage Doors, Frames and Finish Hardware A) Wood shims at door frame between CMU and frame not fire rated. B) Fire stop smoke seal door/frame to CMU required.

AA 1.05 P0000435.jpg

40 07270 Parking Garage Doors, Frames and Finish Hardware Doors at trash room not rated and shims left in place are combustable. Work not done to above spec and print detail.

AA-1.01 P0000383.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 24 of 154

Page 25: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

230 07270 Parking Garage Doors, Frames and Finish Hardware Typical conditions at all doors. 1. Woods shims cannot be used 2. Fire rated door frames have not been caulked and smoke seals have not been installed at following doors: P104.1, P104, P110, P109, P102, P108, P108.3 P107, P111.2, P117, P115, P119, P1

AA-1.04, 1.02, 1.03

P0000435.jpg

266 07270 Parking Garage Doors, Frames and Finish Hardware Typical conditions at all doors. 1) Wood shims cannot be used. 2) Fire rated door frames have not been caulked. 3) smoke seals have not been installed at following doors: r P204.1, P204, P207, P207.1, P202, P211, P213, P210, P208, P205.1, P214, P215, P2

AA-1.04/.05/.06

P0000435.jpg

255 07270 Parking Garage Drywall/EIFS/SOFP Compressable material not caulked at edge of slab and columns on Both sides of south wall.

AA 1.05 P0000504.jpg

258 07270 Parking Garage Drywall/EIFS/SOFP Seal caulk compress material at edge of slab and concrete walls and Column. AA 1.05 P0000386.jpg

237 07270 Parking Garage HVAC and Temperature Control Systems Damper angles have not been installed as required by code. AA 104

447 07270 Triple Gym Electrical (School) Conduit sleeves not fire stopped, 5 locations on South wall. AC 1.00 P0000839.jpg454 07270 Triple Gym Electrical (School) Fire proofing damaged at all beam clamps attachments for hangers. AC 1.02 P0000823.jpg

2245 07270-15250 Academy Houses HVAC and Temperature Control Systems Round duct thru rated wall from Room 222, Work Room 223. Insulation doesn't run thru wall and duct not fire stopped.

P0001035.jpg

687 07270-16470 Academy Houses Electrical (School) Conduit floor penetration have not been fire stopped at N-E corner of room. AB4-1.01 P0001249.jpg4005 07290 Academy Houses Drywall/EIFS/SOFP From elevation 363.00 to top of parapet, caulk has not been installed where masonry

veneer abutts EIFS. From elevation 402.33 to roof parapet 4 control joints have not been caulked.

AA2.01

6030 07511 Academy Houses Roofing and Waterproofing Three-coarse and protective silver paint damage throughout roof. AB1-1.04 P0002385.jpg6035 07511 Academy Houses Roofing and Waterproofing Mechanical pad corners damaged need three-coarse and protective silver paint. AB2-1.04 P0002385.jpg6034 07511 Academy Houses Roofing and Waterproofing Misc. penetrations need repair. AB2-1.04 P0002393.jpg6033 07511 Academy Houses Roofing and Waterproofing Exposed roofing nails on vertical capsheet below parapet wall sheet metal coping. AB2-1.04 P0002395.jpg6032 07511 Academy Houses Roofing and Waterproofing Vertical cap sheet not properly adhered. AB2-1.04 P0002394.jpg6036 07511 Academy Houses Roofing and Waterproofing Roof nails exposed at top of vertical capsheet. AB3-1.04 P0002395.jpg6003 07511 Academy Houses Roofing and Waterproofing Vertical capsheet damaged. AB4-1.04 P0002410.jpg1401 07511 Academy Houses Roofing and Waterproofing Roof vent mastic damaged. AB4-1.04 P0000263.jpg6042 07511 Academy Houses Roofing and Waterproofing Capsheet damaged. AB4-1.04 P0002405.jpg6040 07511 Academy Houses Roofing and Waterproofing Mechanical box corners and pipe penetrations either damaged or not sealed with

protective silver paint.AB4-1.04 P0002387.jpg

6039 07511 Academy Houses Roofing and Waterproofing Nail through capsheet. AB4-1.04 P0002413.jpg6043 07511 Academy Houses Roofing and Waterproofing Ponding problem. AB4-1.04 P0002409.jpg6021 07511 Administration Roofing and Waterproofing Repair damage caused by temporary ladder. AE-1.03 P0002349.jpg6020 07511 Administration Roofing and Waterproofing Corner roofing material not properly adhered. AE-1.03 P0002329.jpg9077 07511 Administration Roofing and Waterproofing Roofing lead flashing not installed, 2 locations. Column line 3.5 and C.5. AE-1.03 P0002210.jpg9073 07511 Administration Roofing and Waterproofing No roof insulating concrete this area, canopy D to D.5 and 2.5 to 4.5. AE-1.03 P0002206.jpg

6022 07511 Administration Roofing and Waterproofing Temporary base flashing not sealed correctly. AE-1.03 P0002345.jpg6023 07511 Administration Roofing and Waterproofing Lead pipe flashing not installed. AE-1.03 P0002343.jpg6024 07511 Administration Roofing and Waterproofing Tear in roof capsheet. AE-1.03 P0002344.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 25 of 154

Page 26: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

6026 07511 Administration Roofing and Waterproofing Dynaflex base flashing damaged. AE-1.03 P0002336.jpg6027 07511 Administration Roofing and Waterproofing Re-torque bolts on drains, overflows and condensation drains. AE-1.03 P0002337.jpg1379 07511 Triple Gym Roofing and Waterproofing Roofing materials stored on roof: Roof felt, cap sheet, walking pads and fasteners. P0002186.jpg6014 07511 Triple Gym Roofing and Waterproofing 1" by 1" Opening between bottom of wall and metal counter flashing. AC-1.03 P0002361.jpg6017 07511 Triple Gym Roofing and Waterproofing Capsheet not properly adhered. AC-1.03 P0002356.jpg6013 07511 Triple Gym Roofing and Waterproofing Remove nails from roof deck. AC-1.03 P0002368.jpg6012 07511 Triple Gym Roofing and Waterproofing Mechanical box corners need to be three-coarsed and paint with protective silver paint

due to damage.AC-1.03 P0002377.jpg

6011 07511 Triple Gym Roofing and Waterproofing Roofing material improperly stored. AC-1.03 P0002411.jpg6015 07511 Triple Gym Roofing and Waterproofing Capsheet base flashing not properly adhered. AC-1.03 P0002362.jpg

309 07511-11 3.7 Academy Houses Flashing and Sheet Metal Clean up asphalt markings pipes walls. AB4-1.04 P0000260.jpg320 07511-8 3.2A Administration Flashing and Sheet Metal Reseal caulking as necessary at counter flashings at walls units; Line 8 O.C. AE1.03 P0000275.jpg317 07511-8 3.4A Academy Houses Flashing and Sheet Metal Fasten top of all base flashings and wall sheets 8 inches O.C. AB 1-1.04 P0000257.jpg316 07511-8 3.4A Academy Houses Flashing and Sheet Metal Re-Coat all mastic work. AB 2-1.04 P0000209.jpg315 07511-8 3.4A Academy Houses Flashing and Sheet Metal Fasten top of all base flashings and wall sheets 8 inches O.C. AB3-1.04 P0000257.jpg312 07511-8 3.4A Academy Houses Flashing and Sheet Metal Fasten top of all base flashings and wall sheets 8 O.C. AB3-1.04 P0000257.jpg314 07511-8 3.4A Academy Houses Flashing and Sheet Metal Recoat all mastic work. AB3-1.04 P0000209.jpg313 07511-8 3.4A Academy Houses Flashing and Sheet Metal Repair fishmouths at base flashing - various locations. AB3-1.04 P0000264.jpg311 07511-8 3.4A Academy Houses Flashing and Sheet Metal Build up mastic to proper cant at roof penetrations. AB3-1.04 P0000263.jpg302 07511-8 3.4A Academy Houses Flashing and Sheet Metal Repair nail hole near unit B42A #5; Grid 5.5 - R.6 AB4-1.04 P0000253.jpg319 07511-8 3.4A Administration Flashing and Sheet Metal Repair holes in roof caused by caps by other trades. AE1.03 P0000253.jpg321 07511-8 3.4A Administration Flashing and Sheet Metal Remove wooden ladder and re-roof to match existing roofing. AE1.03 P0000278.jpg318 07511-8 3.4A Administration Flashing and Sheet Metal Fasten top of all base flashings and wall sheets 8 O.C. AE1.03 P0000257.jpg310 07511-9 3.4 B4 Academy Houses Flashing and Sheet Metal Repair missing granules on cap sheet. AB3-1.04 P0000258.jpg303 07511-9 3.4 B4 Academy Houses Flashing and Sheet Metal Repair missing granules on cap sheet - various locations. AB4-1.04 P0000258.jpg308 07511-9 3.4A Academy Houses Flashing and Sheet Metal Recoat all mastic work. AB4-1.04 P0000209.jpg307 07511-9 3.4A Academy Houses Flashing and Sheet Metal Apply 3 course at corners at all curbs platforms walls etc. AB4-1.04 P0000257.jpg306 07511-9 3.4A Academy Houses Flashing and Sheet Metal Repair fishmouths at base flashings at various locations. AB4-1.04 P0000264.jpg305 07511-9 3.4A Academy Houses Flashing and Sheet Metal Fasten all base flashings walls 8 O.C. AB4-1.04 P0000257.jpg304 07511-9 3.4A Academy Houses Flashing and Sheet Metal Build up mastic to proper cant at roof penetrations conduits etc. AB4-1.04 P0000263.jpg

3337 07600 Academy Houses Flashing and Sheet Metal Sheet metal flashing not installed. AA-1.11 P0002453.jpg3336 07600 Academy Houses Flashing and Sheet Metal Pan sheet metal flashing not installed. AA-1.11 P0002451.jpg2172 07600 Academy Houses Flashing and Sheet Metal Sheet metal pan flashing not installed at slab to EIFS wall. AA-1.11 P0002451.jpg2178 07600 Academy Houses Flashing and Sheet Metal Flashing is not installed. AA-1.11 P0002453.jpg2174 07600 Academy Houses Flashing and Sheet Metal Flashing is not installed. AA-1.11 P0002453.jpg3330 07600 Academy Houses Flashing and Sheet Metal Sheet metal flashing not installed. AA-1.12 P0002453.jpg3334 07600 Academy Houses Flashing and Sheet Metal Sheet metal flashing not installed. AA-1.12 P0002453.jpg3332 07600 Academy Houses Flashing and Sheet Metal Sheet metal pan flashing not installed. AA-1.12 P0002451.jpg4025 07600 Academy Houses Flashing and Sheet Metal Sheet metal flashing not installed. AA-1.134031 07600 Academy Houses Flashing and Sheet Metal Sheet metal flashing not installed. AA-1.132168 07600 Academy Houses Flashing and Sheet Metal At elevation 363.00 sheet metal flashing not installed. AA-2.02 P0002474.jpg4002 07600 Academy Houses Flashing and Sheet Metal Sheet metal flashing not installed. AA1.124004 07600 Academy Houses Flashing and Sheet Metal Sheet metal flashing not installed. AA1.12

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 26 of 154

Page 27: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

1423 07600 Academy Houses Flashing and Sheet Metal Typical condition: Modified reglet and counter flashing at AC unit base not installed per plan detail.

AB-1.04 P0000341.jpg

1403 07600 Academy Houses Flashing and Sheet Metal Flashing around all roof equipment pads incomplete and work not done to above print and detail.

AB1-1.04 P0000257.jpg

1427 07600 Academy Houses Flashing and Sheet Metal Typical conditions. Modified reglet corner joints not soldiered per spec. requirement. AB1.04 P0000341.jpg1426 07600 Academy Houses Flashing and Sheet Metal Typical condition: Fastening is not 24' O.C. or washered under fastener on modified

reglet and counter flash for AC units per plan detail.AB1.04 P0000342.jpg

2462 07600 Academy Houses Flashing and Sheet Metal Typical at corridor sheet metal flashing mastic is not installed. AB2-1.02 P0001594.jpg1421 07600 Academy Houses Flashing and Sheet Metal Typical condition: 1) Corners and angles shall be tapped and soldered per spec. 2) No

standing seam approx. 8 inches O.C. at parapet cap as required per spec.AB2-1.04

1422 07600 Academy Houses Flashing and Sheet Metal Typical condition: Parapet cap flashing and double cleat is not provided per plan detail. AB2-1.04 P0000338.jpg

2186 07600 Academy Houses Flashing and Sheet Metal Flashing is not installed at 363.00 elevation. AB2-2.01 P0002474.jpg2189 07600 Academy Houses Flashing and Sheet Metal Flashing is not installed at elevation 363.00. AB2-2.01 P0002474.jpg2191 07600 Academy Houses Flashing and Sheet Metal Flashing is not installed at the 363.00 elevation. AB2-2.01 P0002474.jpg2185 07600 Academy Houses Flashing and Sheet Metal Flashing is not installed at 363.00 elevation. AB2-2.01 P0002474.jpg1418 07600 Academy Houses Flashing and Sheet Metal Typical conditions: 1) Corners and angles shall be lapped and soldered per specs. 2) No

standing seams approx. 8' O.C at parapet cap as required per spec.AB3-1.04

1420 07600 Academy Houses Flashing and Sheet Metal Typical condition: Modified reglet and counter flash at O.C. unit base not installed per plan details.

AB3-1.04 P0000341.jpg

1424 07600 Academy Houses Flashing and Sheet Metal Typical conditions: Fastening is not 24" O.C. on modified reglet and counter flash for AC units per plan detail. (Fastener not washered).

AB3-1.04 P0000342.jpg

1419 07600 Academy Houses Flashing and Sheet Metal Typical condition: Parapet cap coping double cleat is not provided per plan detail. AB3-1.041425 07600 Academy Houses Flashing and Sheet Metal Typical condition: Modified reglet corner miter joints not soldered per spec. AB3-1.04 P0000341.jpg6038 07600 Academy Houses Flashing and Sheet Metal Vertical capsheet at the parapet wall extension not counter flashed. AB3-1.04 P0002400.jpg1415 07600 Academy Houses Flashing and Sheet Metal Typical conditions: 1) Corners and angles shall be lapped and soldered per spec. 2) No

standing seams approx. 8' O.C at parapet cap per spec.AB4-1.04 P0000344.jpg

1417 07600 Academy Houses Flashing and Sheet Metal Typical conditions: Modified reglet and counter flash at AC unit base not installed per plan detail.

AB4-1.04 P0000341.jpg

1416 07600 Academy Houses Flashing and Sheet Metal Typical conditions: Parapet cap coping double cleat is not provided per plan detail. AB4-1.04 P0000224.jpg

1414 07600 Academy Houses Flashing and Sheet Metal Typical condition: Modified reglet corner miter joints not soldered per spec. AB4-1.04 P0000341.jpg

1413 07600 Academy Houses Flashing and Sheet Metal Typical condition: Fastening is not 24" O.C on modified reglet and counter flash for AC units per plan detail. (Picture: 343 = Fasteners also require washer).

AB4-1.04 P0000342.jpg

6041 07600 Academy Houses Flashing and Sheet Metal Parapet wall where vertical capsheet meets stucco not sealed. Parapet wall where vertical capsheet meets veneer not counter flashed. Parapet wall where vertical capsheet meets sheet metal coping, coping not wide enough.

AB4-1.04 P0002406.jpg

6019 07600 Administration Flashing and Sheet Metal Sheet metal counter flashing does not properly seal vertical roof surface. AE-1.03 P0002328.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 27 of 154

Page 28: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

1410 07600 Administration Flashing and Sheet Metal Typical condition: Modified reglet and counter flash at AC unit base not installed per plan details.

AE1.03 P0000347.jpg

1409 07600 Administration Flashing and Sheet Metal Typical condition: Parapet cap coping double cleat is not provided per plan detail. AE1.03 P0000338.jpg

1408 07600 Administration Flashing and Sheet Metal Typical condition: 1) Corners and angles shall be lapped and soldered per spec. 2) No standing seams approx. 8 O.C at parapet cap as required per spec.

AE1.03 P0000339.jpg

1412 07600 Administration Flashing and Sheet Metal Typical condition: Modified reglet corner miter joints not soldered per spec. AE1.03 P0000341.jpg1411 07600 Administration Flashing and Sheet Metal Typical condition: Fastening is not 24" O.C on modified reglet and counter flash for AC

units per plan detail. (No washer under faster).AE1.03 P0000342.jpg

174 07600 Parking Garage Flashing and Sheet Metal Cap flashing not installed per detail at exterior CMU parapet AA-1.07 P0000405.jpg1378 07600 Triple Gym Flashing and Sheet Metal Construction material stored on roof, sheet metal caps and flashing. P0002187.jpg1478 07600 Triple Gym Flashing and Sheet Metal Sheet metal flashing not installed. AA1.13 P0002547.jpg6016 07600 Triple Gym Flashing and Sheet Metal Sheet metal counter flashing not properly sealed. AC-1.03 P0002362.jpg1381 07600 Triple Gym Flashing and Sheet Metal Sheet metal wall flashing not installed from 2.0 to 3.5 at column line W about 55' total. AC1.02 P0002191.jpg

3182 07700 Academy Houses Electrical (School) 2 Conduit penetrations at East fire rated wall are not fire stopped. AB3-1.02 P0001426.jpg7000 07700 Triple Gym Drywall/EIFS/SOFP No access door installed at roof level. AC-1.03 P0002372.jpg3344 07920 Academy Houses Drywall/EIFS/SOFP From elevation 363.00 to 376.33 caulking has not been done where masonry veneer

abutts EIFS and one control joint has not been caulked.P0002455.jpg

3342 07920 Academy Houses Drywall/EIFS/SOFP From elevation 363.00 to 376.33 vertical joints and where EIFS abutts masonry veneer missing caulking.

P0002454.jpg

3348 07920 Academy Houses Drywall/EIFS/SOFP From elevation 376.33 to 389.00 where EIFS spandrel panels abutts masonry veneer missing caulk.

P0002457.jpg

4021 07920 Academy Houses Drywall/EIFS/SOFP At elevation 376.33 to 389.00 masonry abutting EIFS not caulked and no caulking at ledger angles.

4029 07920 Academy Houses Drywall/EIFS/SOFP From elevation 389.00 to top of roof parapet 2 ledger angles 2 control joints and where EIFS spandrel panel abutts masonry veneer not caulked.

3349 07920 Academy Houses Drywall/EIFS/SOFP From elevation 376.35 to 389.00 where EIFS abutts masonry veneer caulking has not been installed.

P0002454.jpg

3341 07920 Academy Houses Drywall/EIFS/SOFP At the 376.33 elevation no caulk installed between masonry veneer and EIFS. AB2-2.01 P0002454.jpg3343 07920 Academy Houses Drywall/EIFS/SOFP At elevation 376.33 no caulking where masonry veneer abutts EIFS spandrel panel. AB3-2.01 P0002457.jpg3350 07920 Academy Houses Drywall/EIFS/SOFP At elevation 376.33 where masonry veneer abutts EIFS caulking has not been installed. AB3-2.02 P0002454.jpg3355 07920 Academy Houses Drywall/EIFS/SOFP From elevation 363.00 to 376.33 three control joints have not been caulked at 376.33

elevation where masonry veneer abutts EIFS.AB3-2.02 P0002454.jpg

3354 07920 Academy Houses Drywall/EIFS/SOFP From elevation 376.35 to 389.00 where EIFS spandrel panels abutts masonry veneer caulking has not been installed.

AB3-2.02 P0002464.jpg

970 07920 Academy Houses Drywall/EIFS/SOFP Veneer diagonal riser at interior stair wall from 1st level to intermitted level not seal caulked.

AB4-1.01 P0001218.jpg

4026 07920 Academy Houses Drywall/EIFS/SOFP From elevation 363.00 to 376.35 2 vertical control joints and where EIFS abutts masonry veneer not caulked.

AB4-2.01

4011 07920 Academy Houses Drywall/EIFS/SOFP Just above the 376.33 elevation EIFS has surface damage. AB4-2.014028 07920 Academy Houses Drywall/EIFS/SOFP From elevation 376.33 to parapet no caulking where masonry veneer abuts EIFS, at

ledger angle and at 4 control joints.AB4-2.02

4019 07920 Academy Houses Drywall/EIFS/SOFP From elevation 402.33 to top of parapet 2 control joints not caulked and ledger angle not caulked.

AB4-2.02

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 28 of 154

Page 29: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

4018 07920 Academy Houses Drywall/EIFS/SOFP From elevation 389.66 to top of parapet no caulk at ledger; elevation 402.33 and 7 control joints have not been caulked.

AB4-2.02

4017 07920 Academy Houses Drywall/EIFS/SOFP From elevation 363.00 to 389.00 masonry abutting EIFS not caulked, ledger not caulked and 6 control joints not caulked.

AB4-2.02

4016 07920 Academy Houses Drywall/EIFS/SOFP At elevation 402.33 ledger angle not caulked and from 402.33 to top of parapet 2 control joints not caulked.

AB4-2.02

4020 07920 Academy Houses Drywall/EIFS/SOFP At elevations 389.00, 402.33 no caulk at ledger angles and from elevation 402.33 to parapet control joints not caulked.

AB4-2.02

4014 07920 Academy Houses Drywall/EIFS/SOFP At elevation 402.33 to top of roof parapet ledger angle not caulked. 6 Control joints not caulked where masonry veneer abutts EIFS spandrels no caulking.

AB4-2.02

4022 07920 Academy Houses Drywall/EIFS/SOFP 2 Control joints not caulked and no caulking between masonry veneer and EIFS from 363.00 to 376.33.

AB4-2.02

4023 07920 Academy Houses Drywall/EIFS/SOFP Masonry abutting EIFS at 3 and 5.5 lines. No caulk 376.33 to top of parapet. AB4-2.024015 07920 Academy Houses Drywall/EIFS/SOFP For 402.33 to top of parapet 2 control joints, ledger angle and EIFS spandrel abutting

masonry veneer have not been caulked.AB4-2.02

6031 07920 Academy Houses Plumbing / Electrical (School) / HVAC and Temperature Control Systems

Pipe penetrations not sealed at top of flashing. AB2-1.04 P0002380.jpg

6029 07920 Administration Drywall/EIFS/SOFP CMU expansion joint not properly sealed. AE-1.03 P0002335.jpg9000 07920 Administration Drywall/EIFS/SOFP From elevation 363.00 to top of roof parapet control joints have not been caulked. AE-2.01 P0002481.jpg9002 07920 Administration Drywall/EIFS/SOFP Control joints from elevation 363.00 to top of roof parapet have not been caulked. AE-2.01 P0002481.jpg9005 07920 Administration Drywall/EIFS/SOFP From elevation 363.00 to top of roof parapet control joints have not been caulked. AE-2.02 P0002482.jpg6028 07920 Administration Flashing and Sheet Metal Caulking seal on top of reglet incomplete. AE-1.03 P0002334.jpg6025 07920 Administration Plumbing / Electrical (School) / HVAC

and Temperature Control SystemsAll pipe penetration not sealed at top of pipe flashing. AE-1.03 P0002340.jpg

415 07920 Parking Garage Doors, Frames and Finish Hardware Exit doors for stair shaft have not been fire stopped and wood shims shall be removed. This applies to the corridor on level 2 as well.

AA 1.01-4.04-1.07

P0000562.jpg

403 07920 Parking Garage Drywall/EIFS/SOFP Top of CMU walls to edge of slab, batting material (compressible material) not installed or seal caulked fire stopped in stair area walls.

P0000520.jpg

83 07920 Parking Garage Drywall/EIFS/SOFP Typical Condition at joint between CMU Walls abutting to columns and concrete walls 1. compressible material is not in place 2. caulking of joints not complete

AA 1.07/1.08/1.09

P0000465.jpg

351 07920 Parking Garage Drywall/EIFS/SOFP All CMU walls need to be fire stopped at top of walls and columns. AA 1.09 P0000504.jpg175 07920 Parking Garage Drywall/EIFS/SOFP At edge of slab and CMU parapet wall - compressable material and seal caulk required. AA-1.07 P0000406.jpg417 07920 Parking Garage Drywall/EIFS/SOFP Typical condition at all floor levels where CMU abutts to slab edge require compressible

material & fire stop caulk.AA1.01-1.04-1.07

P0000520.jpg

344 07920 Parking Garage Electrical (School) On East wall of stairwell 5' from landing cored hole in rated wall. AA 109 P0000696.jpg347 07920 Parking Garage Fire Protection Two - 2" sprinkler line penetrations at top of gypsum South corridor wall not sleeved or

fire stopped.AA 1.03 P0000529.jpg

423 07920 Parking Garage Fire Protection Typical condition fire sprinkler line penetrations thru CMU walls not fire stopped at all floors and all wall for stair # 1.

AA1.01-1.04-1.07

P0000398.jpg

116 07920 Parking Garage Plumbing Hot and cold water line penetration into podium level fire stop seal and Caulk not completed.

AA 1.08 P0000472.jpg

422 07920 Parking Garage Plumbing Typical condition plumbing lines penetration thru CMU wall not fire stopped at all floors and all wall for stair # 1.

AA1.01-1.04-1.07

P0000746.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 29 of 154

Page 30: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

117 07920 Parking Garage Plumbing 6" SD penetrating thru CMU stair #2 was not fire stopped at interior and exterior side of walls.

PA/AA 1.08 P0000463.jpg

1376 07920 Triple Gym Drywall/EIFS/SOFP No caulking at masonry vertical expansion joints, 4 location parapets. P0002196.jpg564 07920 Triple Gym Drywall/EIFS/SOFP Top and sides of gypsum walls not sealed / caulked. AC-1.02 P0000571.jpg

521 07920 Triple Gym Drywall/EIFS/SOFP CMU to CMU expansion joint no caulk seal provided at North wall at V.5-3.5. AC-1.02 P0000415.jpg558 07920 Triple Gym Drywall/EIFS/SOFP CMU control joints at W.5-1.7 East wall at W-3.7 South wall at X.6-3.7, caulking and

sealing of joint is not done.AC-1.02

1429 07920 Triple Gym Drywall/EIFS/SOFP Expansion joint not caulked, one location. AC1.01 P0002129.jpg1441 07920 Triple Gym Drywall/EIFS/SOFP Expansion joints not caulked at four locations. AC1.01 P0002129.jpg1459 07920 Triple Gym Drywall/EIFS/SOFP Exterior wall vertical expansion joint not caulked, 1 location. AC1.01 P0002129.jpg

514 07920 Triple Gym Electrical (School) 12 Penetrations sleeves and cored are not fire rated, fire stopped. AC-1.02 P0000828.jpg566 07920 Triple Gym Electrical (School) Conduit penetrations at East-West sides of corridor are not fire stopped. AC-1.02 P0000544.jpg512 07920 Triple Gym Fire Protection Sprinkler line penetration at South CMU wall not fire stopped. AC-1.02 P0000392.jpg510 07920 Triple Gym Fire Protection Sprinkler line South CMU wall penetration not fire stopped. Total of 3. AC-1.02 P0000880.jpg533 07920 Triple Gym Fire Protection Sprinkler line CMU wall penetrations not fire stopped, 1 at East wall, 1 at South wall. AC-1.02 P0000834.jpg515 07920 Triple Gym Plumbing 2 Core hole wall penetration not fire stopped for water line at East-West walls and 1

sleeve 4" hole in West wall also not fire stopped.AC-1.02 P0000868.jpg

556 07920 Triple Gym Plumbing 2) 2-4" O.F. and R.D. lines at South wall and 1-3"1) domestic water line on South CMU wall, 1) 1-3" domestic water line on North wall all penetrations for these line are not fire stopped.

AC-1.02 P0000778.jpg

352 07920 15300 Parking Garage Fire Protection Sprinkler pipe penetrations through CMU walls in stair shaft have not been fire stopped. AA 109 P0000392.jpg

244 08100 Parking Garage Doors, Frames and Finish Hardware 1) Wood shim material used between door frame and concrete wall not rated. 2) Caulk seal door frame to concrete wall.

AA 1.04 P0000435.jpg

98 08100 Parking Garage Doors, Frames and Finish Hardware Compressible and combustible shims used; door and jam not fire stopped. AA 1.09 P0000435.jpg122 08100 Parking Garage Doors, Frames and Finish Hardware Compressable and combustible shims used. Window frame not fire stopped. AA1.09 P0000383.jpg121 08100 Parking Garage Doors, Frames and Finish Hardware Compressable and combustible shims used. Door and jam not fire stopped. AA1.09 P0000383.jpg120 08100 Parking Garage Doors, Frames and Finish Hardware Compressable and combustible shims used. Window frame Not fire stopped. AA1.09 P0000383.jpg552 08100 Triple Gym Doors, Frames and Finish Hardware Doors and frames 115-115.1-114 are not installed. AC-1.02 P0000795.jpg

2152 08110 Academy Houses Doors, Frames and Finish Hardware Door lock as installed does not function, key will not unlock door. P0001593.jpg5071 08110 Academy Houses Doors, Frames and Finish Hardware Doors have not been installed in corridor entry way to rooms and also in work rooms. AB1-1.02 P0001958.jpg5103 08110 Academy Houses Doors, Frames and Finish Hardware Doors not installed. AB1-1.03 P0001958.jpg5100 08110 Academy Houses Doors, Frames and Finish Hardware Door not installed in work rooms. AB1-1.03 P0001959.jpg2153 08110 Academy Houses Doors, Frames and Finish Hardware One hinge is missing at door 102. AB2-1.012154 08110 Academy Houses Doors, Frames and Finish Hardware Door does not close properly at doors; 105-116-116.1-118-118.1-119-119.1-111-124-

124.1-128.1. Total of 11doors.AB2-1.01 P0001593.jpg

3154 08110 Academy Houses Doors, Frames and Finish Hardware 32" W by 40" H. access door not installed at wall, to secure void space under stair. AB3-1.01 P0000963.jpg3155 08110 Academy Houses Doors, Frames and Finish Hardware Ceiling access door not installed. AB3-1.013011 08110 Academy Houses Doors, Frames and Finish Hardware Access door not installed to area under stair. AB3-1.01 P0001658.jpg3262 08110 Academy Houses Doors, Frames and Finish Hardware Doors are not painted and doors 103-104, door hardware not installed. AB3-1.01 P0001185.jpg3004 08110 Academy Houses Doors, Frames and Finish Hardware Double doors in corridor have not been installed. AB3-1.01-

1.02-1.03P0001574.jpg

3127 08110 Academy Houses Doors, Frames and Finish Hardware Hardware installed before doors painted. AB3-1.03 P0001185.jpg701 08110 Academy Houses Doors, Frames and Finish Hardware Doors noted not painted. AB4-1.01 P0001185.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 30 of 154

Page 31: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

702 08110 Academy Houses Doors, Frames and Finish Hardware Double door is not installed at East end of corridor 111. AB4-1.01 P0001186.jpg618 08110 Academy Houses Doors, Frames and Finish Hardware Non-rated door installed in rated wall leading into wk room 224. AB4-1.02 P0001261.jpg950 08110 Academy Houses Doors, Frames and Finish Hardware Door 206 and 207 not installed. Door 210 smoke seal closer and threshold not installed. AB4-1.02 P0001185.jpg

653 08110 Academy Houses Doors, Frames and Finish Hardware 1) Door hardware not installed for doors 203-204. 2) Locking door hardware at door 202 not installed properly.

AB4-1.02 P0001253.jpg

656 08110 Academy Houses Doors, Frames and Finish Hardware Double doors not installed. AB4-1.02-1.03

P0001186.jpg

699 08110 Academy Houses Drywall/EIFS/SOFP Access door at stair 101 is not installed. AB4-1.01 P0001189.jpg620 08110 Academy Houses Drywall/EIFS/SOFP Non fire rated jamb installed in rated wall into Wk room 224. AB4-1.02 P0001261.jpg337 08110 Parking Garage Doors, Frames and Finish Hardware Door frames requires fire stopping an wood shims to be removed. AA 1.03 P0000435.jpg

153 08110 Parking Garage Doors, Frames and Finish Hardware Compressable and combustable shims used. Window frame not fire stopped. AA 1.07 P0000435.jpg146 08110 Parking Garage Doors, Frames and Finish Hardware Compressable material and combustible shims were used. Door and jam not fire stopped. AA 1.08 P0000435.jpg

367 08110 Parking Garage Doors, Frames and Finish Hardware Automatic door closures in 3rd floor slab not installed at entrance. AA 1.09 P0000675.jpg63 08110 Parking Garage Doors, Frames and Finish Hardware Door jam and door not installed. AA-1.03 P0000310.jpg

299 08110 Parking Garage Doors, Frames and Finish Hardware Wood shims have been used at doors p207.1 and p207.2 and have not been fire stopped at CMU wall. Frames require smoke gasket.

AA-1.04 P0000562.jpg

283 08110 Parking Garage Doors, Frames and Finish Hardware Store front and Jamb not fire safed. Compressable wood shims used. AA-1.06 P0000562.jpg282 08110 Parking Garage Doors, Frames and Finish Hardware Door jambs not properly installed for fire safeing. Compressable and combustable shims

used.AA-1.06 P0000562.jpg

194 08110 Parking Garage Doors, Frames and Finish Hardware Compressable and combustable shims used . Door and jam not fire stopped. AA-1.07 P0000435.jpg212 08110 Parking Garage Doors, Frames and Finish Hardware Compressable and combustable shims used. Door and jambnot fire stopped. AA-1.07 P0000435.jpg210 08110 Parking Garage Doors, Frames and Finish Hardware Combustable and compressable shims used. Door and jam not fire stopped. Louver at

bottom of door not installed.AA-1.07 P0000435.jpg

199 08110 Parking Garage Doors, Frames and Finish Hardware Compressable and combustable shims at door jamb used. Door and jam not fire stopped. AA-1.07 P0000383.jpg

192 08110 Parking Garage Doors, Frames and Finish Hardware Compressable and combustable shims at door used. Doors and jam not fire stopped. AA-1.07 P0000383.jpg187 08110 Parking Garage Doors, Frames and Finish Hardware Compressable and combustable shims at door used. Door and jam not fire stopped. AA-1.07 P0000383.jpg214 08110 Parking Garage Doors, Frames and Finish Hardware Compressable and combustable shims used. Door and jamb not fire stopped. AA-1.07 P0000435.jpg129 08110 Parking Garage Doors, Frames and Finish Hardware Compressable and combustable shims used. Door and jam not fire stopped. AA-1.09 P0000383.jpg59 08110 Parking Garage Doors, Frames and Finish Hardware Door and jamb not fire rated at stair #2 entry non compressable and non combustable

shims not used.SA-1.02 P0000562.jpg

535 08110 Triple Gym Doors, Frames and Finish Hardware Doors and frames not installed # 130-130.1 AC-1.02 P0000795.jpg1457 08110 Triple Gym Doors, Frames and Finish Hardware Doors and frames not set at doors; 108-108.1-108.2-108.3-108.4. AC1.01 P0002148.jpg1456 08110 Triple Gym Doors, Frames and Finish Hardware No doors or frames set in masonry walls, total 25 doors. AC1.01 P0002148.jpg5084 08400 Academy Houses Glass, Glazing and Storefront Systems Windows not installed, frames on ground and damaged, 5 total. AB1-1.01 P0002034.jpg5054 08400 Academy Houses Glass, Glazing and Storefront Systems 2 Windows 213, 3-213, 2,-222, 2-223, one each in rooms 208-209-110, windows and

glazing not installed.AB1-1.02 P0001759.jpg

5089 08400 Academy Houses Glass, Glazing and Storefront Systems Glazing, backer rod, and caulking of window exterior framing is not installed. AB1-1.03 P0001973.jpg5090 08400 Academy Houses Glass, Glazing and Storefront Systems Windows not installed. Rooms 313-1, 312-3, 322-1, Work Room 329-1, 323-2, 309-1,

308-1, 310-1.AB1-1.03 P0001759.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 31 of 154

Page 32: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

2418 08400 Academy Houses Glass, Glazing and Storefront Systems 4 Windows on A line are not installed. AB2-1.012360 08400 Academy Houses Glass, Glazing and Storefront Systems 3 Windows in work area 132 each in offices 136-135 and in Dean's office 134 glazing is

not installed.AB2-1.01 P0001678.jpg

2359 08400 Academy Houses Glass, Glazing and Storefront Systems 3 Panels of glazing in large frame is not installed. AB2-1.01 P0001677.jpg2438 08400 Academy Houses Glass, Glazing and Storefront Systems Window frames and glazing are not installed. AB2-1.01 P0001055.jpg2277 08400 Academy Houses Glass, Glazing and Storefront Systems Windows boarded up, no frame of glazing set in 3 openings. AB2-1.02 P0001759.jpg2282 08400 Academy Houses Glass, Glazing and Storefront Systems 2 Window frames and glazing are not installed. AB2-1.02 P0001759.jpg2105 08400 Academy Houses Glass, Glazing and Storefront Systems Exterior windows on East and South walls do not have backer rod or caulking on exterior

faces.AB2-1.03 P0001945.jpg

2031 08400 Academy Houses Glass, Glazing and Storefront Systems 2 Windows in room 319 and three in room 316 do not have frames and glazing installed. AB2-1.03 P0001759.jpg

3220 08400 Academy Houses Glass, Glazing and Storefront Systems Frames and glazing not installed in above rooms. (Total of 11). AB3-1.01 P0001055.jpg3298 08400 Academy Houses Glass, Glazing and Storefront Systems Frame and glazing not installed at small framed openings. AB3-1.01 P0001055.jpg

963 08400 Academy Houses Glass, Glazing and Storefront Systems All classrooms typical, windows installed (13 total) but interior not finished at head, jambs and sill.

AB4-1.02 P0001180.jpg

960 08400 Academy Houses Glass, Glazing and Storefront Systems Windows installed, interior not finished at head, jambs and sill. AB4-1.02 P0001130.jpg1002 08400 Academy Houses Glass, Glazing and Storefront Systems At interior side gap between window head, jambs and sill aluminum frame and gypsum

wall. Typical all locations, 14 total.AB4-1.03 P0001180.jpg

9018 08400 Administration Drywall/EIFS/SOFP Welding of light gage steel frame to tube steel support frame for curtain wall screen has not been done.

AE-1.03 P0002213.jpg

9031 08400 Administration Glass, Glazing and Storefront Systems Exterior doors frames and side lites not installed. Doors 201-221-236. AE-1.02 P0002271.jpg548 08400 Triple Gym Doors, Frames and Finish Hardware Doors # 116-117-118 and frames and window with frame #116 are not installed. AC-1.02 P0000817.jpg555 08400 Triple Gym Glass, Glazing and Storefront Systems Windows not installed at East wall-3 window and West wall- 3 windows. AC-1.02 P0000825.jpg

1454 08400 Triple Gym Glass, Glazing and Storefront Systems No window or frame installed. AC1.01 P0002138.jpg547 08450 Triple Gym Doors, Frames and Finish Hardware Doors 116-117-118 frames and window frames, # 116 are not installed. AC-1.02 P0000822.jpg

3261 08700 Academy Houses Doors, Frames and Finish Hardware Doors do not close properly at door 103 and 128.1 AB3-1.01 P0000960.jpg2453 08710 Academy Houses Doors, Frames and Finish Hardware Doors 216-216.1-202-217-218.1-219.1-229.1 do not close properly. Total of 7 doors. AB2-.101 P0001588.jpg3063 08710 Academy Houses Doors, Frames and Finish Hardware No prep. for door lock at door edge, door 116 and 116.1. AB3-1.01 P0001185.jpg3064 08710 Academy Houses Doors, Frames and Finish Hardware Door not installed at door 111. AB3-1.01 P0001186.jpg3065 08710 Academy Houses Doors, Frames and Finish Hardware No finish hardware at door 103-104. AB3-1.01 P0001185.jpg3066 08710 Academy Houses Doors, Frames and Finish Hardware Door does not close properly at door numbers 103-105-111.1-112-113-109. Total of 6

doors.AB3-1.01 P0000960.jpg

3068 08710 Academy Houses Doors, Frames and Finish Hardware No door locks installed, door number 116-116.1-111.1 AB3-1.01 P0001185.jpg3260 08710 Academy Houses Doors, Frames and Finish Hardware No finish hardware to include 1) Locks 2) Closers 3) Glass with metal glass frame at

doors 124-124.1-125-125.1-126-127-127.1-128-128.1. Total of 9 doors.AB3-1.01 P0000991.jpg

3067 08710 Academy Houses Doors, Frames and Finish Hardware Exterior doors typical: No smoke seal, no closer, no threshold. Door numbers; 102-105-106-107-108-109-111-112-113-114-115-116-116.1-117-118-119-120-121. Total of 18 doors.

AB3-1.01 P0000988.jpg

3146 08710 Academy Houses Doors, Frames and Finish Hardware Doors do not close properly at doors 224-226.1-227.1. 3 Locations total. AB3-1.02 P0000960.jpg3062 08710 Academy Houses Doors, Frames and Finish Hardware No doors locks installed at door 216-216.1-217-217.1-211-211.1. Total of 6 doors. AB3-1.02 P0001185.jpg3074 08710 Academy Houses Doors, Frames and Finish Hardware Door do not close properly, door numbers; 202-219-224-224.1-226.1-206-227.1. Total of

7 doors.AB3-1.02 P0000960.jpg

3073 08710 Academy Houses Doors, Frames and Finish Hardware Doors not installed, door numbers 211-211.1. AB3-1.02 P0001186.jpg3145 08710 Academy Houses Doors, Frames and Finish Hardware No finish hardware to include: 1) Locks 2) Closers 3) Glass with metal frame at door

numbers 224-224.1-225-225.1-226-226.1-227-227.1-228-228.1. Total of 10 doors.AB3-1.02 P0000991.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 32 of 154

Page 33: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

3075 08710 Academy Houses Doors, Frames and Finish Hardware Door edge not prepared for locks at door numbers; 216-216.1-217-217.1. Total of 4 doors.

AB3-1.02 P0001185.jpg

3076 08710 Academy Houses Doors, Frames and Finish Hardware Typical at exterior doors. No smoke seals, no closers, no thresholds at door numbers; 302-308-309-310-311-311.1-312-313-314-315-316-316.1-317-317.1-318-319-320-321. Total of 18 doors.

AB3-1.02 P0000960.jpg

3061 08710 Academy Houses Doors, Frames and Finish Hardware Typical at exterior doors: No smoke seals, no closers, no thresholds door numbers; 202-208-209-210-212-213-214-215-216-216.1-217-217.1-218-219-220-221-211-211.1. Total of 18 doors.

AB3-1.02 P0000988.jpg

3143 08710 Academy Houses Doors, Frames and Finish Hardware No finish hardware to include: 1) Locks 2) Closers 3) Glass with metal frame, door numbers 324, 324.1, 325, 325.1, 326, 326.1, 327, 327.1, 328, 328.1. Total of 10 doors.

AB3-1.03 P0000991.jpg

3144 08710 Academy Houses Doors, Frames and Finish Hardware Doors do not close properly at doors 303-326-326.1. AB3-1.03 P0000960.jpg3077 08710 Academy Houses Doors, Frames and Finish Hardware No finish hardware installed at doors; 304-305-306-307-324-324.1-325-325.1-326-326.1-

327-327.1-328-328.1.AB3-1.03 P0000991.jpg

3078 08710 Academy Houses Doors, Frames and Finish Hardware No glass or metal frame installed at doors; 324-324.1-325-325.1-326-326.1-327-327.1-328-328.1.

AB3-1.03 P0001011.jpg

2370 08710 G Academy Houses Doors, Frames and Finish Hardware Door does not close properly door 319. AB-1.03 P0001593.jpg2372 08710 G Academy Houses Doors, Frames and Finish Hardware Door out of square with door frame, doors 303-312-313-314, total of 4 doors. AB2-1.03 P0001591.jpg

964 08710 G Academy Houses Doors, Frames and Finish Hardware No keyed cylinders installed; 224-224.1-225-225.1-226-226.1-227-227.1-228-228.1. No door locks; 224 and 224.1. Wrong height floor door stop (top short); 224 and 227.1.

AB4-1.02 P0001212.jpg

995 08710 G Academy Houses Doors, Frames and Finish Hardware Interior doors 1) Typical no glass, no frame or cylinders to work room doors, 10 total. Door 324-324.1-325-325.1-326-326.1-327-327.1-328-328.1. 2) No doors at 328-328.1-324-324.1-4 total.

AB4-1.03 P0000991.jpg

1000 08710 G Academy Houses Doors, Frames and Finish Hardware Exterior doors either out of square with frame or door binds to frame when closed. Door 112.1-113-114-119-120-121-121.1. Total of 7.

AB4-1.03 P0001319.jpg

999 08710 G Academy Houses Doors, Frames and Finish Hardware Exterior doors 1) All 18 doors, no smoke seals, no closers, no thresholds. 2) Doors 317-321 have no fire label. 3) Doors 312-312.1-313-313.1-320-320.1-321-321.1. No finish hardware- 8 total.

AB4-1.03

965 08710 G Academy Houses Doors, Frames and Finish Hardware No keyed cylinders installed; 324-324.1-325-325.1-326-326.1-327-327.1-328-328.1. No door or door hardware; 324-324.1-328-328.1. No door closer, lock or stop; 325. Wrong height door floor stop (too short); 325.1-326-326.1-327.

AB4-1.03 P0001212.jpg

996 08710 G Academy Houses Doors, Frames and Finish Hardware Interior doors 1) Door 303-304-306-307, no finish hardware installed. AB4-1.03 P0001212.jpg

5025 09100 Academy Houses Drywall/EIFS/SOFP No framing around plumbing trees. AB1-1.02 P0002088.jpg5019 09100 Academy Houses Drywall/EIFS/SOFP Strong backs missing on all furred walls and exterior for one sided gypsum. AB1-1.02 P0002083.jpg5028 09100 Academy Houses Drywall/EIFS/SOFP Window frame king studs not welded to trimmer stud. AB1-1.02 P0002089.jpg5027 09100 Academy Houses Drywall/EIFS/SOFP West wall at stair has not been framed. AB1-1.02 P0001975.jpg5072 09100 Academy Houses Drywall/EIFS/SOFP King studs not welded to trimmers at corridor doors. AB1-1.02 P0001958.jpg5074 09100 Academy Houses Drywall/EIFS/SOFP Backing has not been installed for case work or waterless chalk boards. AB1-1.02 P0001904.jpg5032 09100 Academy Houses Drywall/EIFS/SOFP South side of elevator shaft not framed. AB1-1.02 P0001950.jpg5039 09100 Academy Houses Drywall/EIFS/SOFP No interior or walls framed. AB1-1.02 P0002095.jpg5035 09100 Academy Houses Drywall/EIFS/SOFP Anchor bolts for corridor veneer walls not installed. AB1-1.02 P0002092.jpg5033 09100 Academy Houses Drywall/EIFS/SOFP Metal stud framing above work room door incomplete. AB1-1.02 P0001958.jpg5042 09100 Academy Houses Drywall/EIFS/SOFP East wall at stairs has not been framed. AB1-1.02 P0001975.jpg5101 09100 Academy Houses Drywall/EIFS/SOFP King studs and trimmers not welded. AB1-1.03 P0001958.jpg5122 09100 Academy Houses Drywall/EIFS/SOFP Backing for case work and waterless chalk boards are not installed. AB1-1.03 P0001904.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 33 of 154

Page 34: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

5120 09100 Academy Houses Drywall/EIFS/SOFP East elevator shaft wall not framed. AB1-1.03 P0001907.jpg5118 09100 Academy Houses Drywall/EIFS/SOFP Framing over door header incomplete. AB1-1.03 P0001911.jpg5117 09100 Academy Houses Drywall/EIFS/SOFP Interior walls not framed. AB1-1.03 P0001910.jpg5110 09100 Academy Houses Drywall/EIFS/SOFP Duct shaft not built. AB1-1.03 P0001950.jpg5126 09100 Academy Houses Drywall/EIFS/SOFP Corridor wall framing incomplete. AB1-1.03 P0001908.jpg5107 09100 Academy Houses Drywall/EIFS/SOFP Openings are not framed in walls for ducts that pass through walls. AB1-1.03 P0001948.jpg5099 09100 Academy Houses Drywall/EIFS/SOFP Framing for door incomplete. AB1-1.03 P0001966.jpg5097 09100 Academy Houses Drywall/EIFS/SOFP Walls are not framed in bathrooms. AB1-1.03 P0001967.jpg5091 09100 Academy Houses Drywall/EIFS/SOFP Drilled in anchors for veneer wall not installed. AB1-1.03 P0001968.jpg5087 09100 Academy Houses Drywall/EIFS/SOFP Wall framing incomplete at stairs. AB1-1.03 P0001975.jpg2365 09100 Academy Houses Drywall/EIFS/SOFP Black channel iron for single sided gypsum framed wall is not secured to studs. AB2-1.01 P0001672.jpg2366 09100 Academy Houses Drywall/EIFS/SOFP Bottom track is not continuous, and has not been spliced. AB2-1.01 P0001674.jpg2412 09100 Academy Houses Drywall/EIFS/SOFP Rated wall framing between rooms 115-116 incomplete. AB2-1.01 P0001650.jpg2358 09100 Academy Houses Drywall/EIFS/SOFP Cold rolled steel not welded to jambs and kings studs per plan. AB2-1.01 P0001680.jpg2151 09100 Academy Houses Drywall/EIFS/SOFP Acid waste sink partially installed in furred wall. AB2-1.01 P0001570.jpg2303 09100 Academy Houses Drywall/EIFS/SOFP Acid waste floor sink installed partially in furred walls. AB2-1.02 P0001748.jpg2096 09100 Academy Houses Drywall/EIFS/SOFP King studs at doors have not been welded from deck to floor on both sides of double stud

frames.AB2-1.03 P0001848.jpg

2017 09100 Academy Houses Drywall/EIFS/SOFP King stud to trimmer is not welded from floor to ceiling as required by plans. AB2-1.03 P0001865.jpg2050 09100 Academy Houses Drywall/EIFS/SOFP Framed opening not provided for access panel for plumbing valves in furred wall. AB2-1.03 P0001813.jpg2052 09100 Academy Houses Drywall/EIFS/SOFP Floor sink drain built half in and half out of furred wall. AB2-1.03 P0001784.jpg3293 09100 Academy Houses Drywall/EIFS/SOFP No framed opening for access to smoke fire damper motor and no access door installed. AB3-1.01 P0001409.jpg3116 09100 Academy Houses Drywall/EIFS/SOFP Opening for access to smoke fire damper not framed. Note: Picture 1478 shows panel lay

out on floor.AB3-1.02 P0001476.jpg

3106 09100 Academy Houses Drywall/EIFS/SOFP No framed access openning for smoke/fire damper. AB3-1.03 P0001409.jpg3025 09100 Academy Houses Drywall/EIFS/SOFP Strong back steel stud for ceiling frame set up tight against fire sprinkler line 1" clearance

is not provided, line 2.5.AB3-1.03 P0001619.jpg

6037 09100 Academy Houses Drywall/EIFS/SOFP Parapet wall not completed per plan and exposed nails at base flashing. AB3-1.04 P0002401.jpg864 09100 Academy Houses Drywall/EIFS/SOFP At top of furred wall channel track sloted for plumbing line which is not centered on

track. Correction required.AB4-1.01 P0001085.jpg

660 09100 Academy Houses Drywall/EIFS/SOFP Access opening not large enough for access to smoke/fire damper motor control and access door not installed.

AB4-1.02 P0001258.jpg

667 09100 Academy Houses Drywall/EIFS/SOFP Opening for access to smoke fire dampers are not large enough to access motor. AB4-1.03 P0001258.jpg9026 09100 Administration Drywall/EIFS/SOFP The bottom of the HVAC shaft has not been framed. AE-1.01 P0002242.jpg9046 09100 Administration Drywall/EIFS/SOFP Metal stud framing incomplete at East and South wall. AE-1.02 P0002276.jpg9115 09100 Administration Drywall/EIFS/SOFP No metal stud framing except double stud at door at door 242. AE-1.02 P0002289.jpg9041 09100 Administration Drywall/EIFS/SOFP Corridor metal stud framing not installed at West wall, stair, elevator shaft, door 220 not

set and West wall.AE-1.02 P0002319.jpg

9042 09100 Administration Drywall/EIFS/SOFP No stud framing at East wall and incomplete at West and South walls. No backing, no straps at chase wall, no wall, no framing for recessed toilet accessories.

AE-1.02 P0002320.jpg

9045 09100 Administration Drywall/EIFS/SOFP Metal stud framing incomplete at door 236.1. AE-1.02 P0002275.jpg9064 09100 Administration Drywall/EIFS/SOFP No metal stud framing at North-West and South walls. AE-1.02 P0002290.jpg9057 09100 Administration Drywall/EIFS/SOFP No metal stud framing at East-West walls between rooms. North walls incomplete

framing at doors and HVAC framed opening.AE-1.02 P0002284.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 34 of 154

Page 35: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

9056 09100 Administration Drywall/EIFS/SOFP No stud framing North and West walls. AE-1.02 P0002283.jpg9047 09100 Administration Drywall/EIFS/SOFP Metal stud exterior wall furring, none installed, typical. AE-1.02 P0002277.jpg9062 09100 Administration Drywall/EIFS/SOFP No metal stud framing all walls; no doors frames set, door 214-215. AE-1.02 P0002290.jpg9063 09100 Administration Drywall/EIFS/SOFP No metal stud framing west wall and North wall, except at North wall door jambs. AE-1.02 P0002290.jpg9059 09100 Administration Drywall/EIFS/SOFP Metal stud framing 50% complete North wall, East-West wall 0%. AE-1.02 P0002286.jpg9061 09100 Administration Drywall/EIFS/SOFP Metal studs not installed at North-South walls; East and West walls 75% incomplete. AE-1.02 P0002288.jpg9060 09100 Administration Drywall/EIFS/SOFP Metal stud walls not framed at East-West-South walls. Door 223 frame not set. AE-1.02 P0002286.jpg9058 09100 Administration Drywall/EIFS/SOFP No metal stud framing East-West walls. South wall incomplete, framing only at door

jamb and wall corners.AE-1.02 P0002285.jpg

9095 09100 Administration Drywall/EIFS/SOFP Metal stud framing incomplete, no backing, studs installed, not screwed to tracks, straps for chase wall not in and no framing for recessed items.

AE-1.02 P0002305.jpg

9093 09100 Administration Drywall/EIFS/SOFP No metal stud framing at North-East-West-South walls except at rooms; 204-205-206-208 and part of 213.

AE-1.02 P0002306.jpg

9096 09100 Administration Drywall/EIFS/SOFP No metal stud wall framing or door frames set. AE-1.02 P0002306.jpg9052 09100 Administration Drywall/EIFS/SOFP No metal studs installed at East-West and South walls except for double stud at door

frame.AE-1.02 P0002288.jpg

9065 09100 Administration Drywall/EIFS/SOFP No metal stud framing at North wall, West wall about 50% complete. AE-1.02 P0002291.jpg9066 09100 Administration Drywall/EIFS/SOFP Metal stud framing incomplete; no backing, studs not screwed to track, straps for chase

walls not in, framing not installed for recessed items.AE-1.02 P0002292.jpg

9051 09100 Administration Drywall/EIFS/SOFP No stud framing at East and West wall, North wall has only 5 studs standing. Also no straps at chase wall, no backing, no framing for recessed toilet accessories.

AE-1.02 P0002287.jpg

9050 09100 Administration Drywall/EIFS/SOFP West wall studs to not secured to tracks. North wall metal stud framing incomplete (missing studs).

AE-1.02 P0002279.jpg

9067 09100 Administration Drywall/EIFS/SOFP No metal stud framing North and East walls. No door frame set, door 217. AE-1.02 P0002292.jpg9049 09100 Administration Drywall/EIFS/SOFP No metal stud framing except door frames, top and bottom tracks. AE-1.02 P0002280.jpg9048 09100 Administration Drywall/EIFS/SOFP Metal stud framing incomplete; 33%, interior wall studs installed. AE-1.02 P0002278.jpg9055 09100 Administration Drywall/EIFS/SOFP No studs installed at East wall, incomplete at North and West walls, including screws,

framing over door frames.AE-1.02 P0002277.jpg

239 09100 Parking Garage Drywall/EIFS/SOFP Duct smoke/ fire damper penetration at rated gypsum wall framed in around smoke/fire damper incorrectly.

AA 1.04

252 09100 Parking Garage Drywall/EIFS/SOFP Top and bottom framing stud tracks pin shot not per plans (spacing) AA 1.05 P0000298.jpg251 09100 Parking Garage Drywall/EIFS/SOFP North wall ductwork penetration at rated wall not framed in per plan. AA 1.05 P0000317.jpg

7 09100 Parking Garage Drywall/EIFS/SOFP Incorrect stud gage used for length and bridging not in place. AA-1.03288 09100 Parking Garage Drywall/EIFS/SOFP Framed opening for fire/smoke damper is too large for damper. AA-1.06 P0000317.jpg424 09100 Triple Gym Drywall/EIFS/SOFP 1) Duct penetration thru West wall is not framed properly-No support provided for duct

thru wall. 2) Electrical box South side duct not framed properly at 5.5-3 location. Also item noted not fire caulked. 3) Ceiling access door for fire damper is not prov

AC 1.02 P0001026.jpg

453 09100 Triple Gym Drywall/EIFS/SOFP Shot pins for studs to CMU wall are shot at 24" OC should be 16". AC 1.02 P0000838.jpg543 09100 Triple Gym Drywall/EIFS/SOFP 1) Ceiling wall track for over stud ceiling on North-South-East wall sides shot pin of wall

track is not 16" O.C. 2) Over head hard ceiling is not installed.AC-1.02 P0000648.jpg

484 09100 Triple Gym Drywall/EIFS/SOFP Furred walls at EBF frame shot pin spacing not to print. AC-1.02 P0000587.jpg2251 09160 Academy Houses Drywall/EIFS/SOFP Black channel iron strong back for one sided gypsum walls is not attached to studs. AB2-1.02 P0001764.jpg4010 09245 Academy Houses Reinforced Masonry and Veneer Systems Masonry veneer starting to show efflorescence. AB4-2.013263 09250 Academy Houses Drywall/EIFS/SOFP At East side wall of vestibule gypsum board cut out around conduit running North to

South direction not acceptable to plan requirments.AB3-1.01 P0001379.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 35 of 154

Page 36: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

3132 09250 Academy Houses Drywall/EIFS/SOFP Top of non-rated wall between Vestibule 302 and Janitor 303 is not complete per plan and North wall over door 304. Openings around conduit require patching.

AB3-1.03 P0001483.jpg

959 09250 Academy Houses Drywall/EIFS/SOFP Incomplete drywall at attic West wall. AB4-1.02 P0001322.jpg939 09250 Academy Houses Drywall/EIFS/SOFP Attic area, fire rated gypsum board not installed in exterior wall metal stud cavity at

column line T, 5.4&5.6.AB4-1.03 P0001344.jpg

940 09250 Academy Houses Drywall/EIFS/SOFP Attic area; gypsum board incomplete at West wall and not tapped at South and West walls, typical.

AB4-1.03 P0001467.jpg

2468 09260 Academy Houses Drywall/EIFS/SOFP Dens-glass board at electrical J boxes is not cut tight in corridor, fire caulk or replacement may be required. 7 Seven boxes total, at walls.

P0001607.jpg

4009 09260 Academy Houses Drywall/EIFS/SOFP Dens glass has not been completely installed from 363.00 elevation to top of parapet. AA2.011145 09260 Academy Houses Drywall/EIFS/SOFP Bubbles and/or blistering on EFIS Exterior coat. Wall line H between three to four 2nd

thru roof area, line J second floor, wall line L 3 to 4 2nd floor, and line 4 from L-K at second floor. New photos taken of 2/14/00. 1773 thru 1778.

AB-3 1.02-1.03

P0001535.jpg

2326 09260 Academy Houses Drywall/EIFS/SOFP Gypsum board is not installed in room. (Mop sink is too close to wall studs to maintain rating of room) in all rooms noted.

AB1-1.01-1.02-1.03

P0001716.jpg

5018 09260 Academy Houses Drywall/EIFS/SOFP Gypsum board not installed. AB1-1.02 P0001904.jpg5113 09260 Academy Houses Drywall/EIFS/SOFP No Dens glass installed on corridor wall 2nd and 3rd floors. AB1-1.02 P0001985.jpg5125 09260 Academy Houses Drywall/EIFS/SOFP Gypsum board not installed at duct shaft framing. AB1-1.03 P0001905.jpg2455 09260 Academy Houses Drywall/EIFS/SOFP Dens-glass board at electrical J boxes in corridor is not cut tight at boxes, 6 locations

total at walls.AB2-.101 P0001607.jpg

2457 09260 Academy Houses Drywall/EIFS/SOFP Dens-glass is not cut tight to fire proofed steel columns to maintain fire rating. Total of 6 locations, corridor walls.

AB2-.101 P0001613.jpg

2458 09260 Academy Houses Drywall/EIFS/SOFP Dens-glass fire rated board is not installed at drinking fountain bracing. 1 Location corridor fire rating is not maintained.

AB2-.101 P0001394.jpg

2450 09260 Academy Houses Drywall/EIFS/SOFP Hole in rated wall is not patched. AB2-.101 P0001605.jpg2362 09260 Academy Houses Drywall/EIFS/SOFP Gypsum insulation on exterior wall is incomplete. AB2-1.01 P0001676.jpg2354 09260 Academy Houses Drywall/EIFS/SOFP Gypsum board framing incomplete in all areas. AB2-1.01 P0001675.jpg2484 09260 Academy Houses Drywall/EIFS/SOFP Fire proof top of East rated wall and finish drywall at the South near the East rated wall. AB2-1.01 P0001633.jpg

2084 09260 Academy Houses Drywall/EIFS/SOFP A framed box for the valve is required. AB2-1.01 P0001881.jpg2289 09260 Academy Houses Drywall/EIFS/SOFP Sprinkler fitting built into rated wall. AB2-1.01 P0001747.jpg2408 09260 Academy Houses Drywall/EIFS/SOFP Angular space around round duct too big and drywall is damaged around conduit

penetration at rated wall.AB2-1.01 P0001653.jpg

2364 09260 Academy Houses Drywall/EIFS/SOFP Gypsum board is not installed on furred wall. AB2-1.01 P0001675.jpg2157 09260 Academy Houses Drywall/EIFS/SOFP Holes are too large for conduit above door 104. AB2-1.01 P0001580.jpg2421 09260 Academy Houses Drywall/EIFS/SOFP Rated wall is not complete interior portion of corridor 3 wall at room 116. AB2-1.01 P0001646.jpg2150 09260 Academy Houses Drywall/EIFS/SOFP Gypsum board installation on rated wall incomplete. AB2-1.01 P0001567.jpg2324 09260 Academy Houses Drywall/EIFS/SOFP Room has not been taped. AB2-1.01 P0001723.jpg2406 09260 Academy Houses Drywall/EIFS/SOFP 3 Conduits partially installed in wall. AB2-1.01 P0001654.jpg2396 09260 Academy Houses Drywall/EIFS/SOFP 1) Green board 2) Gypsum board is not installed in walls and ceiling of rooms noted on

each floor.AB2-1.01-1.02-1.03

P0001690.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 36 of 154

Page 37: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

2327 09260 Academy Houses Drywall/EIFS/SOFP Wall for the exhaust duct has not been properly framed to support duct in wall. AB2-1.01-1.02-1.03

P0001727.jpg

2285 09260 Academy Houses Drywall/EIFS/SOFP Dens-glass is not installed on inside of rated wall behind furred wall. AB2-1.02 P0001468.jpg2249 09260 Academy Houses Drywall/EIFS/SOFP Interior gypsum framing at furred walls incomplete. AB2-1.02 P0001675.jpg2144 09260 Academy Houses Drywall/EIFS/SOFP 2 4S boxes in Dens-glass wall board exceed 1/8" gap max requirement of code. AB2-1.02 P0001999.jpg2258 09260 Academy Houses Drywall/EIFS/SOFP Gypsum insulation on furred wall is not done. AB2-1.02 P0001675.jpg2248 09260 Academy Houses Drywall/EIFS/SOFP Insulation and gypsum framing on exterior rated wall is not done. AB2-1.02 P0001676.jpg2209 09260 Academy Houses Drywall/EIFS/SOFP Hole below plumbing penetration in dry wall at fire rated wall. AB2-1.02 P0001766.jpg2147 09260 Academy Houses Drywall/EIFS/SOFP 5-4S boxes opening in Dens-glass wall board, opening exceed 1/8" gap maximum

required by code.AB2-1.02 P0001999.jpg

2466 09260 Academy Houses Drywall/EIFS/SOFP Den-glass board incomplete at corridor walls. AB2-1.02 P0001596.jpg2469 09260 Academy Houses Drywall/EIFS/SOFP Dens-glass fire rated board is not installed at drinking fountain backing, one location.

Corridor fire rating is not maintained.AB2-1.02 P0001394.jpg

2296 09260 Academy Houses Drywall/EIFS/SOFP Plumbing pipe framed partially in rated wall and not fire stopped. AB2-1.022299 09260 Academy Houses Drywall/EIFS/SOFP 2 Sleeves on sprinkler are not framed into the rated wall. AB2-1.02 P0001745.jpg2470 09260 Academy Houses Drywall/EIFS/SOFP Dens-glass is not cut tight to fire proofed steel columns to maintain fire rating. Total of 7

locations, corridor walls.AB2-1.02 P0001613.jpg

2471 09260 Academy Houses Drywall/EIFS/SOFP Dens-glass fire rated board is not installed at drinking fountain backing, one location, corridor fire rating is not maintained.

AB2-1.02 P0000957.jpg

2467 09260 Academy Houses Drywall/EIFS/SOFP Dens-glass board is not installed at corridor ceiling. AB2-1.02 P0001614.jpg2392 09260 Academy Houses Drywall/EIFS/SOFP Ceiling framing is not framed out for access door, 2 total. AB2-1.03 P0001698.jpg2111 09260 Academy Houses Drywall/EIFS/SOFP At Dens-glass wall weld tab plates for safety lines penetrate wall. Remove penetrations

and repair holes.AB2-1.03 P0002061.jpg

2078 09260 Academy Houses Drywall/EIFS/SOFP Drywall has not been installed in room walls. East and West walls are full height walls and are rated, South wall is not.

AB2-1.03 P0001871.jpg

2028 09260 Academy Houses Drywall/EIFS/SOFP The rated walls in the work room do not have gypsum board installed. AB2-1.03 P0001838.jpg2018 09260 Academy Houses Drywall/EIFS/SOFP Interior portion of exterior rated wall is not complete, see plan. AB2-1.03 P0001468.jpg2098 09260 Academy Houses Drywall/EIFS/SOFP Gypsum board has not been screwed to stud framing at edges as required per plan and

code.AB2-1.03 P0001854.jpg

2097 09260 Academy Houses Drywall/EIFS/SOFP Fire rated wall has not been framed and gypsum board has not been installed to corner of room.

AB2-1.03 P0001852.jpg

3198 09260 Academy Houses Drywall/EIFS/SOFP Opening for exhaust air duct has not been framed at South wall. AB3-1.0 P0001460.jpg3319 09260 Academy Houses Drywall/EIFS/SOFP West rated wall has not been drywalled at top wall (2 Hr wall). AB3-1.01 P0001388.jpg3289 09260 Academy Houses Drywall/EIFS/SOFP 4" by 4" Opening in gypsum board 3 1/2" foot from floor-repair patch opening. AB3-1.01 P0001412.jpg3316 09260 Academy Houses Drywall/EIFS/SOFP The stud framing has not been completed for the exhaust air duct at the South wall. AB3-1.01 P0001402.jpg3320 09260 Academy Houses Drywall/EIFS/SOFP At East wall between the riser shaft and the South wall. The slip track has not been

covered with dry wall.AB3-1.01 P0001389.jpg

3266 09260 Academy Houses Drywall/EIFS/SOFP Gypsum board has been stopped at top of janitor sink. This causes the loss of the rating of the wall. This occurs at the east and south walls.

AB3-1.01-1.02-1.03

P0001337.jpg

3169 09260 Academy Houses Drywall/EIFS/SOFP Buss duct unistrut support at floor penetration unistruts penetrate into non-rated wall and large 12" by 9" hole behind buss duct. Bus way has not been anchored to floor.

AB3-1.02 P0001444.jpg

3193 09260 Academy Houses Drywall/EIFS/SOFP Gypsum board wall openning over door for electrical box exceeds 1/8 gap max. AB3-1.02 P0001426.jpg3113 09260 Academy Houses Drywall/EIFS/SOFP Gypsum installation on rated wall incomplete. AB3-1.02 P0001468.jpg3181 09260 Academy Houses Drywall/EIFS/SOFP Holes at gypsum board fire rated and non-rated walls require patching. AB3-1.02 P0001425.jpg3161 09260 Academy Houses Drywall/EIFS/SOFP Patch and repair all holes at non-rated wall, South side and North side. AB3-1.02 P0001458.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 37 of 154

Page 38: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

3142 09260 Academy Houses Drywall/EIFS/SOFP Bubbles or blistring of EIFS exterior coat. Wall line H between 3 to 4, 2nd thru roof area. Line J, 2nd floor. Wall line L, 3 to 4 2nd floor and line 4 from L-K at 2nd floor. New photos taken on 2/14/00 1773 thru 1779.

AB3-1.02-1.03

P0001535.jpg

3049 09260 Academy Houses Drywall/EIFS/SOFP 2 Electrical boxes framed partially in wall. Conduit running down wall gypsum has been notched.

AB3-1.03 P0001545.jpg

3135 09260 Academy Houses Drywall/EIFS/SOFP Drywall opennings around electrical boxes exceed 1/8" gap max. Two electrical box over door 302.

AB3-1.03 P0001479.jpg

3036 09260 Academy Houses Drywall/EIFS/SOFP Gypsum board on rated wall incomplete. AB3-1.03 P0001468.jpg3050 09260 Academy Houses Drywall/EIFS/SOFP Gypsum board has been damaged above entry door in rated wall. AB3-1.03 P0001543.jpg3080 09260 Academy Houses Drywall/EIFS/SOFP Poor fit for gypsum board by 4S box at North wall. AB3-1.03 P0001533.jpg3094 09260 Academy Houses Drywall/EIFS/SOFP Rated wall at shaft does not extend to outside wall shown on plans. AB3-1.03 P0001501.jpg3133 09260 Academy Houses Drywall/EIFS/SOFP At fire rated wall and non-rated wall between rooms 304-303 and 310 is not fire rated as

required per plan.AB3-1.03 P0001486.jpg

3125 09260 Academy Houses Drywall/EIFS/SOFP Patch holes in gypsum board fire rated walls and fire taping of wall joints not completed. AB3-1.03 P0001529.jpg

640 09260 Academy Houses Drywall/EIFS/SOFP At North wall exhaust duct wall penetration-gypsum board opening for duct exceeds 1/8 gap around duct work.

AB4-1.0 P0001274.jpg

645 09260 Academy Houses Drywall/EIFS/SOFP Rated wall is not completed at deck, North East corner behind water line. AB4-1.0 P0002498.jpg823 09260 Academy Houses Drywall/EIFS/SOFP Access doors at ceiling shaft for exhaust air is not installed. AB4-1.01 P0001144.jpg855 09260 Academy Houses Drywall/EIFS/SOFP Drywall openings around outlet box is too large at East wall. Code requires 1/8" existing

opening 1/4" to 1/2" around box.AB4-1.01 P0001131.jpg

651 09260 Academy Houses Drywall/EIFS/SOFP Drywall opening for 2-S electrical box 1/8 gap around box exceeded. AB4-1.02 P0001254.jpg655 09260 Academy Houses Drywall/EIFS/SOFP Wall penetration over door 204 on both sides of door not accepted workmanship, not to

industry standard.AB4-1.02 P0002500.jpg

705 09260 Academy Houses Drywall/EIFS/SOFP Top of fire rated wall is not installed per spec. AB4-1.02 P0001251.jpg579 09260 Academy Houses Drywall/EIFS/SOFP Dry wall is not complete at fire rated wall at the fire damper on the East wall. AB4-1.02 P0001278.jpg648 09260 Academy Houses Drywall/EIFS/SOFP Fire rated gyp board wall behind Janitor sink is not continuous to floor deck at South and

East wall of room.AB4-1.02 P0001255.jpg

800 09260 Academy Houses Drywall/EIFS/SOFP Green board not carried to deck behind Janitor sink at rated walls East and South walls. AB4-1.03 P0001337.jpg802 09260 Academy Houses Drywall/EIFS/SOFP Tape and mudding of wall is not finished in rooms. AB4-1.03 P0001328.jpg790 09260 Academy Houses Drywall/EIFS/SOFP The top track for shaft walls shall not be exposed in the shaft. This occurs at the second

and third levels.AB4-1.03 P0001347.jpg

807 09260 Academy Houses Drywall/EIFS/SOFP Openings for 2-4S electrical boxes and 25 conduit penetration on gypsum board are not accepted to code exceed 1/8" gap max. required.

AB4-1.03 P0001334.jpg

777 09260 Academy Houses Drywall/EIFS/SOFP Top and side of rated wall has not been fire stopped. AB4-1.03 P0001139.jpg776 09260 Academy Houses Drywall/EIFS/SOFP Taped joints are not finish sanded. Not all of the joints have been taped. AB4-1.03 P0001340.jpg810 09260 Academy Houses Drywall/EIFS/SOFP Gap in fire rated drywall at wall extension above fire damper. AB4-1.03 P0001341.jpg

4012 09260 Academy Houses Drywall/EIFS/SOFP EIFS panel damaged. AB4-2.02590 09260 Academy Houses Electrical (School) The framed opening for the exhaust air is too small for duct. AB4-1.02 P0001302.jpg

2233 09260 Academy Houses Electrical (School) / Drywall/EIFS/SOFP Sleeved deck penetration partially in top of West rated wall, total of 3. AB2-1.02 P0001737.jpg9053 09260 Administration Drywall/EIFS/SOFP Gypsum board not installed. AE-1.02 P0002280.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 38 of 154

Page 39: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

390 09260 Parking Garage Drywall/EIFS/SOFP Rated shaft required for storm drain lines in stairwell. AA 1.02 P0000631.jpg6 09260 Parking Garage Drywall/EIFS/SOFP Gypsum dry wall not accepted - mold growing at base of wall. AA 1.03 P0000750.jpg

249 09260 Parking Garage Drywall/EIFS/SOFP A) 3-step stair - opening at rated wall under stair. And second layer Of wall not complete

AA 1.04 P0000605.jpg

256 09260 Parking Garage Drywall/EIFS/SOFP Fire rated wall not installed. AA 1.05 P0000298.jpg376 09260 Parking Garage Drywall/EIFS/SOFP At Parking level 2 b/n North East concrete column and North CMU wall 2" gap exists,

problem weather proofing?AA 1.05 P0000623.jpg

154 09260 Parking Garage Drywall/EIFS/SOFP Wall not caulked at top, bottom, or sides. AA 1.07 P0000571.jpg

25 09260 Parking Garage Drywall/EIFS/SOFP Stud wall not anchored to CMU wall per above detail and not shot into above slab per above detail. 1HR framing incomplete.

AA-1.01 P0000587.jpg

29 09260 Parking Garage Drywall/EIFS/SOFP Shot pins at top of wall not spaced per detail above. AA-1.02 P0000648.jpg12 09260 Parking Garage Drywall/EIFS/SOFP Caulking at top, bottom and sides of wall not done to detail above. AA-1.03 P0000571.jpg

13 09260 Parking Garage Drywall/EIFS/SOFP Drilled in anchors missing and not torqued to code section above. AA-1.03 P0000003.jpg297 09260 Parking Garage Drywall/EIFS/SOFP Top of 1 Hr. slip track wall not installed per plans and detail and not completely screwed

off.AA-1.05 P0000591.jpg

296 09260 Parking Garage Drywall/EIFS/SOFP Top of 1 Hr. slip track gypsum framing not installed per plans and detail. AA-1.05 P0000591.jpg281 09260 Parking Garage Drywall/EIFS/SOFP Shot pins in ceiling and at wall edges spaced too far apart. AA-1.06 P0000587.jpg67 09260 Parking Garage Drywall/EIFS/SOFP Wall not caulked at top bottom and sides. AA-1.06 P0000572.jpg

280 09260 Parking Garage Drywall/EIFS/SOFP Opening between masonry wall and column not framed in. AA-1.06 P0002518.jpg179 09260 Parking Garage Drywall/EIFS/SOFP Round duct penetration thru deck not fire safed. Shaft not built. AA-1.07 P0000441.jpg458 09260 Triple Gym Drywall/EIFS/SOFP King studs on West side of wall openning has been cut short at HVAC duct for door

123.1. Door header not installed.AC 1.00 P0000848.jpg

482 09260 Triple Gym Drywall/EIFS/SOFP No strong back on one sided gyp walls. AC 1.02 P0000856.jpg525 09260 Triple Gym Drywall/EIFS/SOFP 1) Shot pinning of ceiling wall track not at 16" O.C. per plan detail at ceiling gypsum

board not installed.AC-1.02 P0000538.jpg

506 09260 Triple Gym Drywall/EIFS/SOFP Shot pinning of ceiling wall track is not installed at 16"O.C. spacing at North, South, East, West walls of Team room and Entrance area. 2) Ceiling gypsum board is not installed. 3) Furred ceiling stud framing is not correct gage per plan. ( Cells for 10

AC-1.02 P0000648.jpg

520 09260 Triple Gym Drywall/EIFS/SOFP Ceiling wall track shot pinning of track to CMU wall not at 16 O.C. North-South walls. No ceiling hung or installed.

AC-1.02 P0000648.jpg

570 09260 Triple Gym Drywall/EIFS/SOFP Fire proof patch where ceiling hat channel cross under bottom of beam at V-3 North side of column.

AC-1.02 P0000935.jpg

3189 09260-7270 Academy Houses Drywall/EIFS/SOFP At top of wall over door 202 wall is not complete per plan detail, also is not fire stopped. AB3-1.02 P0001425.jpg

3055 09270 Academy Houses Drywall/EIFS/SOFP On 2nd, 3rd floor elevators at top of shaft wall ledge left exposed, shaft wall incomplete on these areas.

AB3-1.02-1.03-1.04

P0001347.jpg

9054 09270 Administration Drywall/EIFS/SOFP Shaft walls not installed except at column line C.5 and 3.5. Shaft wall at C.5 and 3.5 incomplete.

AE-1.02 P0002281.jpg

245 09270 Parking Garage Drywall/EIFS/SOFP 10" round duct penetration of floor not fire stopped. Duct exits thru floor at corner of room. Shaft enclosure required per code.

AA 1.04 P0000518.jpg

370 09270 Parking Garage Drywall/EIFS/SOFP Rated wall framing & gypsum board not installed per plan. Detail at line 7.1 from T to S.6

AA 1.09 P0000673.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 39 of 154

Page 40: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

32 09270 Parking Garage Drywall/EIFS/SOFP The top of 4x8 dry wall sheet is installed to low as detailed in plan, Gap at top of wall is too large. Plan requires 1/4" gap.

AA-1.02 P0000591.jpg

3215 09300 Academy Houses Ceramic Tile Tile around window incomplete. AB3-1.01 P0001103.jpg3233 09300 Academy Houses Ceramic Tile Fire alarm strobe box has been tiled over. AB3-1.01 P0001441.jpg3217 09300 Academy Houses Ceramic Tile Walls and floor not grouted. AB3-1.01 P0001439.jpg

761 09300 Academy Houses Ceramic Tile Tile around window incomplete. AB4-1.03 P0001103.jpg762 09300 Academy Houses Ceramic Tile Tile around window incomplete. AB4-1.03 P0001103.jpg758 09300 Academy Houses Ceramic Tile Tile around floor drain incomplete AB4-1.03 P0001102.jpg879 09510 Academy Houses Acoustical Ceilings Ceiling support wire attached to smoke/fire damper angle. P0001025.jpg

5082 09510 Academy Houses Acoustical Ceilings No ceiling wires or seismic wires for T-bar or hard lid ceilings, testing of wires required level 1, typical.

AB1-1.01 P0002039.jpg

2003 09510 Academy Houses Acoustical Ceilings Support wires for suspended ceiling have not been installed. AB2-1.03 P0001891.jpg3224 09510 Academy Houses Acoustical Ceilings Ceiling support wires for suspended ceiling have not been installed or attached to grid. AB3-1.01 P0001424.jpg3290 09510 Academy Houses Acoustical Ceilings Uplift struts not installed for ceiling grid. AB3-1.01 P0001386.jpg3296 09510 Academy Houses Acoustical Ceilings V-struts not installed in ceiling grid. AB3-1.01 P0001039.jpg3301 09510 Academy Houses Acoustical Ceilings All unused ceiling grid wires to be removed. AB3-1.01 P0000953.jpg3227 09510 Academy Houses Acoustical Ceilings Shot pins in 8 uplift struts for suspended deck need pull test and 43 support wires shot

into deck need pull test. Power driven anchors for uplift strut and support wires for ceiling grid system will need to have 50% pull tested. Drilled anchors shall

AB3-1.01 P0000976.jpg

916 09510 Academy Houses Acoustical Ceilings Remove all unused hanger wires. AB4-1.01 P0000953.jpg915 09510 Academy Houses Acoustical Ceilings Shot pins for hanger wires for acoustical ceilings shall be pull tested. 35 pins per room, 8

pins per work room total.AB4-1.01 P0000976.jpg

911 09510 Academy Houses Acoustical Ceilings Remove all unused ceiling wires. AB4-1.01 P0000953.jpg897 09510 Academy Houses Acoustical Ceilings V- strut missing on ceiling grid. See detail above. AB4-1.01 P0001039.jpg892 09510 Academy Houses Acoustical Ceilings Splay wires improperly installed for the grid at the South West corner of the room. AB4-1.01 P0001017.jpg883 09510 Academy Houses Acoustical Ceilings Uplift strut for the suspended ceiling has been removed from the grid system. AB4-1.01 P0001037.jpg845 09510 Academy Houses Acoustical Ceilings T-Bar attachment to duct plenum is not per plans. AB4-1.01 P0001038.jpg898 09510 Academy Houses Acoustical Ceilings At the bottom of duct riser shaft the ceiling grid has been attached without approval for

this type of attachment.AB4-1.01 P0001038.jpg

1321 09510 Academy Houses Acoustical Ceilings V Struts not installed as per plans. AB4-1.02 P0001039.jpg859 09510 Academy Houses Acoustical Ceilings Uplift struts not to plan. Missing 2 in room 219. AB4-1.02 P0001119.jpg860 09510 Academy Houses Acoustical Ceilings No uplift struts installed in ceiling grid. AB4-1.02 P0001125.jpg983 09510 Academy Houses Acoustical Ceilings Ceiling wires installed not pull tested. AB4-1.03 P0000976.jpg

5119 09510 Academy Houses Drywall/EIFS/SOFP Support wires are not installed for suspended ceiling. AB1-1.03 P0001891.jpg3291 09510 Academy Houses Electrical (School) Slack wires for lights in ceiling grid not installed. AB3-1.01 P0001378.jpg

861 09510 Academy Houses Electrical (School) No support wires attached to light fixtures in ceiling grid. AB4-1.02 P0001120.jpg9023 09510 Administration Acoustical Ceilings Support wires for suspended ceiling not installed. AA-1.01 P0002248.jpg9032 09510 Administration Acoustical Ceilings Ceiling support wires have not been installed. Typical for the entire level #2 AE-1.02 P0002272.jpg3248 09900 Academy Houses Paint and Acoustical Wall Panels Doors not painted and door frames, typical all floors, all rooms. Interior and exterior. AB3-1.01-

1.02-1.03P0000988.jpg

3156 09900 Academy Houses Paint and Acoustical Wall Panels 1) Stairs at levels 1-2-3 not painted, including access door. 2) Handicap stripe not painted on first and last tread at each stair run, 8 total.

AB3-1.01-1.02-1.03

P0001428.jpg

703 09900 Academy Houses Paint and Acoustical Wall Panels At window wall and ceiling painting not done. AB4-1.02 P0001208.jpg1367 1) 09720 2) 04220 Triple Gym Drywall/EIFS/SOFP 1) Construction CMU joints are not caulked and grout stain from elec. box down over

door 132.AC-1.02 P0002196.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 40 of 154

Page 41: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

1366 1) 09720 2) 04220 Triple Gym Drywall/EIFS/SOFP 1) Construction CMU joint at 5.6-X.7 is not caulked. 2) Grout staining of CMU wall condition typical.

AC-1.02 P0002196.jpg

3246 10999 Academy Houses Drywall/EIFS/SOFP Fire extinguisher cabinets not set, typical 3 floors for a total of 9. AB3-1.01-1.02-1.03

P0000959.jpg

9076 10999 Administration Roofing and Waterproofing Sheet metal incomplete at roof hatch, exposed roof nail heads. AE-1.03 P0002211.jpg839 11457 Academy Houses Electrical (School) Coax cable pulled into 4S boxes in ceiling not landed. AB4-1.02 P0001030.jpg

3276 14000 Academy Houses Electrical (School) Anchorage and shot pin for electrical support to conduits from deck have not been tested. AB3-1.01-1.02-1.03

P0001033.jpg

3178 14000 Academy Houses Electrical (School) Anchorage for hanger rods to electrical conduit and conduit rack unustrut support rods not tested.

AB3-1.02 P0001033.jpg

3280 14000 Academy Houses Fire Protection Anchorage for splay wires and hanger rods to sprinkler lines have not been tested. AB3-1.01-1.02-1.03

P0001399.jpg

3176 14000 Academy Houses Fire Protection Anchorage of splay wire and hanger rods attached to deck for sprinkler support have not been tested.

AB3-1.02 P0001399.jpg

3277 14000 Academy Houses Plumbing Anchorage for plumbing lines support from deck have not been tested. AB3-1.01-1.02-1.03

P0001400.jpg

3179 14000 Academy Houses Plumbing Anchorage for plumbing line hanger rods to deck not tested. AB3-1.02 P0001400.jpg20 14000 Parking Garage Drywall/EIFS/SOFP 1) Shot pin at top track to concrete slab should be sapced at 16 O.C. 2) Anchorage to

top of CMU and bottom track not complete.AA-1.02 P0000587.jpg

75 14000 Parking Garage HVAC and Temperature Control Systems Drilled anchors have not been tested. AA 109 P0002539.jpg

368 14240 Parking Garage Hydraulic Elevators Elevator not installed. AA 1.09 P0000678.jpg686 14655-07270 Academy Houses Electrical (School) Riser duct not fire stopped at floor penetration and riser duct not anchored to floor. AB4-1.01 P0001245.jpg

3270 15010 Academy Houses HVAC and Temperature Control Systems Exhaust air grills are not installed in 1) Vestibul 102 East wall and 2) Janitor room 103. AB3-1.01 P0001379.jpg

3205 15010 Academy Houses HVAC and Temperature Control Systems Flange of duct in contact with ladder cable tray does not have 1/8" gap as required. Resilient pad between construction elements not installed.

AB3-1.02 P0001449.jpg

3180 15010 Academy Houses HVAC and Temperature Control Systems Two 12 by 6 grills for air ventilation over doors 203-204 are not installed. AB3-1.02 P0001434.jpg

659 15010 Academy Houses HVAC and Temperature Control Systems Access doors to smoke fire damper not installed, 4 typical. AB4-1.02 P0001233.jpg

710 15010 Academy Houses HVAC and Temperature Control Systems Access doors not provided for fire damper motors over doors 228-228.1. AB4-1.02 P0001234.jpg

2077 15010 Academy Houses Plumbing Acid waste lines do have felt pads installed in the clevis clamps as required. AB2-1.03 P0001873.jpg2073 15010 Academy Houses Plumbing Vertical acid waste line in walls shall be protected from puncture (by screws on room

side from hanging pictures, etc).AB2-1.03 P0001845.jpg

2076 15010 Academy Houses Plumbing Acid waste shall be protected from rubbing on metal surfaces at both walls. AB2-1.03 P0001841.jpg9113 15010 Administration Plumbing Gas riser (1 1/4") not installed from finish floor to attic lines. AE-1.02 P0002324.jpg

33 15010 Parking Garage HVAC and Temperature Control Systems Hanger straps to duct loose. Required to be taught without slack. AA-1.01 P0000691.jpg

272 15010 Parking Garage HVAC and Temperature Control Systems Retaining angle not installed. AA-1.04

271 15010 Parking Garage HVAC and Temperature Control Systems Duct penetration not fire safed. AA-1.04

180 15010 Parking Garage HVAC and Temperature Control Systems Duct thru masonry wall not fire safed at exaust fan and bolts not torqued. AA-1.07 P0002503.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 41 of 154

Page 42: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

114 15010 Parking Garage Plumbing Cold water line in contact with hangar rod for drain line. Not to spec. AA 1.08 P0000471.jpg84 15010 Parking Garage Plumbing Felt wrap at seismic hanger clamps not acceptable for protection of dissimilar metals. U

clamp to large for felt used.PA 1.08 P0000491.jpg

540 15010 Triple Gym HVAC and Temperature Control Systems Mechanical ventilation system in room not installed. AC-1.02 P0000824.jpg

947 15050 Academy Houses Electrical (School) Retaining angles not installed at West wall fire dampers, 3 total. AB4-1.02674 15050 Academy Houses Fire Protection All piping shall have ID per spec. above. AB4-1.01-

1.02-1.03723 15050 Academy Houses Fire Protection Hanger missing and hanger on South side of sprinkler run not within 4' 8" of drop. AB4-1.03 P0001362.jpg

5024 15050 Academy Houses HVAC and Temperature Control Systems Refrigerant condensation line hanger missing. AB1-1.02 P0002087.jpg

5021 15050 Academy Houses HVAC and Temperature Control Systems Fan coil unit installed in ceiling has not been connected to power source. The unit has not been braced or plumbed.

AB1-1.02 P0002086.jpg

2357 15050 Academy Houses HVAC and Temperature Control Systems Insulation cut on condensation line at trapeze. Sleeve missing around pipe at trapeze hanger.

AB2-1.01 P0001655.jpg

2214 15050 Academy Houses HVAC and Temperature Control Systems No access door provided to smoke/fire dampers. AB2-1.02 P0001233.jpg

3232 15050 Academy Houses HVAC and Temperature Control Systems Access panel and door not installed in ceiling for smoke fire damper. AB3-1.01-1.02-1.03

P0001106.jpg

858 15050 Academy Houses HVAC and Temperature Control Systems Remove unused duct straps above ceiling. AB4-1.01 P0001115.jpg

882 15050 Academy Houses HVAC and Temperature Control Systems Round duct penetration thru rated wall not fire rated and insulation not extended thru opening.

AB4-1.01 P0001035.jpg

826 15050 Academy Houses HVAC and Temperature Control Systems Bird screen has not been installed on return air registers in rooms 104-118-120-116-114-113-204-210-211-212-214-216-228-302-316-320-313-319-321.

AB4-1.01-1.02-1.03

P0001147.jpg

951 15050 Academy Houses HVAC and Temperature Control Systems Fan coil unit installation incomplete. Primary and secondary drip pans not per specifications 15850-11, page 2.08-D.

AB4-1.02 P0001466.jpg

1003 15050 Academy Houses HVAC and Temperature Control Systems Ceiling mounted access doors missing room 308-309, 4 total. AB4-1.03 P0001514.jpg

990 15050 Academy Houses HVAC and Temperature Control Systems Attic area insulated ducts, no fire caulking on duct insulation at fire walls. Room 312-4 locations, 313-2 locations, 315-3 locations.

AB4-1.03 P0001036.jpg

987 15050 Academy Houses HVAC and Temperature Control Systems Attic area insulated ducts, no fire caulking on duct insulation at fire walls. Room 316-4 locations, 320-3 locations, 321-3 locations.

AB4-1.03

770 15050 Academy Houses HVAC and Temperature Control Systems Access panel door not installed in ceiling to smoke fire damper. AB4-1.03 P0001106.jpg

1001 15050 Academy Houses HVAC and Temperature Control Systems Attic areas metal ducts, fire caulking not installed where metal duct penetrates fire rated gypsum wall. Room 312-1 location, 313-2 locations, 303-1 location, 310-1 location. Total of 5 location.

AB4-1.03 P0001036.jpg

1004 15050 Academy Houses HVAC and Temperature Control Systems Fire rated access doors at attic area fire walls not installed, typical all areas. Include room 312-3 total, 313-3 total, 315-1 total, 316-1 total, 320-3 total, 321-3 total. Total of 14 doors.

AB4-1.03 P0001514.jpg

989 15050 Academy Houses HVAC and Temperature Control Systems Attic areas insulated ducts, insulation not installed thru wall cavity. Room 312-4 locations, 313-2 locations, 315-3 locations, 316-4 locations, room 320-321-3 locations each.

AB4-1.03 P0001036.jpg

753 15050 Academy Houses HVAC and Temperature Control Systems Access panel door not installed in ceiling smoke/fire dampers. AB4-1.03 P0001106.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 42 of 154

Page 43: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

672 15050 Academy Houses Plumbing No metal shield under foam insulation at hangers for condensation line. P0000863.jpg4027 15050 Academy Houses Plumbing 2 Roof drains set in masonry veneer have no sleeves.5022 15050 Academy Houses Plumbing Copper water line missing 3 hangers at change of direction. AB1-1.02 P0001817.jpg5026 15050 Academy Houses Plumbing No support hangers at valve loop and valves have not been identified. AB1-1.02 P0001817.jpg5078 15050 Academy Houses Plumbing Plumbing ventilation lines not supported in walls. Pipe has no ID. AB1-1.02 P0001954.jpg5077 15050 Academy Houses Plumbing Storm drain lines are not supported in chase walls, no identification on pipe. AB1-1.02 P0001952.jpg5105 15050 Academy Houses Plumbing Plumbing pipe in corridor walls for rooms 308-310 and in work room 325 are not braced. AB1-1.03 P0001954.jpg

5104 15050 Academy Houses Plumbing In rooms 312-1415-17-322-23 two vertical plumbing lines are not supported and in room 321 3 pipes not supported in furred walls.

AB1-1.03 P0001952.jpg

5108 15050 Academy Houses Plumbing Shields are not installed at hangers to support foam on condensation lines. AB1-1.03 P0000863.jpg5109 15050 Academy Houses Plumbing Roof drain not connected. AB1-1.03 P0001949.jpg5013 15050 Academy Houses Plumbing 30 Lateral and 15 longitudinal seismic braces missing. AB1-1.03 P0001960.jpg5096 15050 Academy Houses Plumbing Hanger misssing for valves. AB1-1.03 P0001965.jpg2083 15050 Academy Houses Plumbing None of the piping systems have been supported in the walls of the work room. AB2-1.01 P0001874.jpg2149 15050 Academy Houses Plumbing Acid waste line is not supported at 4' O.C. no felt at clamps and not installed in workman

like fashion. Also not felt on hangers in furred wall.AB2-1.01 P0001194.jpg

2422 15050 Academy Houses Plumbing Plumbers tape used to support storm drain line inside of chase wall. AB2-1.01 P0001640.jpg

2315 15050 Academy Houses Plumbing Tie wire used to support roof drain in wall. AB2-1.02 P0001733.jpg2304 15050 Academy Houses Plumbing Access panels to water hammer arrester are not installed. AB2-1.02 P0001272.jpg2345 15050 Academy Houses Plumbing Plumbers tape used to support acid waste line behind furred wall. AB2-1.02 P0001717.jpg2283 15050 Academy Houses Plumbing No felt at hangers and seismic brace on acid waste line. AB2-1.02 P0000994.jpg2307 15050 Academy Houses Plumbing 2 Access panel doors for plumbing shut off valves are not installed. Pipe and valves have

not been identified.AB2-1.02 P0001196.jpg

2343 15050 Academy Houses Plumbing Acid waste line is not supported at 4' O.C. and no felt at clamps. AB2-1.02 P0001194.jpg2039 15050 Academy Houses Plumbing Floor support for acid waste line not attached to floor behind furred wall. Felt missing

for clamps.AB2-1.03 P0001811.jpg

2015 15050 Academy Houses Plumbing Roof drain lines are not supported inside furred walls. AB2-1.03 P0001877.jpg2035 15050 Academy Houses Plumbing Hanger required for valve loop and valve. Identification is not provided for pipes or

valves.AB2-1.03 P0001817.jpg

2051 15050 Academy Houses Plumbing Support at change of direction is missing at two water lines, one gas line, one acid waste line.

AB2-1.03 P0001815.jpg

2036 15050 Academy Houses Plumbing Hanger missing at change of direction. AB2-1.03 P0001824.jpg2038 15050 Academy Houses Plumbing Hangers missing on either side of valve, ID is not provided on pipe or valve. AB2-1.03 P0001816.jpg2026 15050 Academy Houses Plumbing Plumbing line is not braced properly and floor clamp sticking out into the room. AB2-1.03 P0001840.jpg2055 15050 Academy Houses Plumbing Plumbers taped used to support acid waste to wall not felt at plumbers tape behind furred

walls.AB2-1.03 P0001717.jpg

2081 15050 Academy Houses Plumbing Hangers have not been provided at change of direction of pipe and at valves. AB2-1.03 P0001875.jpg2004 15050 Academy Houses Plumbing Hanger missing at change of direction on gas line. AB2-1.03 P0001894.jpg2023 15050 Academy Houses Plumbing Plumbing lines are not supported inside of wall. AB2-1.03 P0001851.jpg2054 15050 Academy Houses Plumbing Acid waste vents behind furred wall not supported vertically and missing clamps at floor. AB2-1.03 P0001795.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 43 of 154

Page 44: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

2053 15050 Academy Houses Plumbing Access panel doors not installed for plumbing shut-off valves. ID is not provided for valves and pipe.

AB2-1.03 P0001196.jpg

2007 15050 Academy Houses Plumbing Rod support for fire sprinkler line in contact with copper line, felt pad required at the contact points.

AB2-1.03 P0001074.jpg

2022 15050 Academy Houses Plumbing Plumbing lines are missing hangers at change of direction. AB2-1.03 P0001850.jpg3003 15050 Academy Houses Plumbing No shields installed at hanger clevis for support of insulated condensate drain line in

corridor, total of 5 hangers.AB3-1.03 P0000863.jpg

3053 15050 Academy Houses Plumbing No shield installed at hangers for foam support on condensate lines. AB3-1.03 P0000863.jpg3346 15050 Academy Houses Plumbing 2 Roof drains penetrating masonry veneer have not been sleeved of caulked. AB3-2.01 P0002456.jpg

673 15050 Academy Houses Plumbing All plumbing pipe shall be identified. AB4-1.01-1.02-1.03

604 15050 Academy Houses Plumbing Acid waste line not supported properly and felt not used at clamps. AB4-1.02 P0001269.jpg849 15050 Academy Houses Plumbing Acid waste line not braced at 4' O.C. and clamps do not have felt around acid waste line. AB4-1.02 P0001194.jpg

842 15050 Academy Houses Plumbing Clevis hanger rusted not di-chromate on 2" acid waste line. 2" acid waste line not fire rated under deck.

AB4-1.02 P0001137.jpg

841 15050 Academy Houses Plumbing No hangers at change of direction on 4" acid waste lines. AB4-1.02 P0001138.jpg843 15050 Academy Houses Plumbing Hangers for acid waste line do not have felt at hangers. AB4-1.02 P0000455.jpg720 15050 Academy Houses Plumbing Access door for water hammer arrestor not installed. AB4-1.03 P0001272.jpg730 15050 Academy Houses Plumbing No hanger at change of direction on 3" gas line. AB4-1.03 P0001350.jpg666 15050 Academy Houses Plumbing No metal shield under insulation foam at hangers for condensate line. AB4-1.03 P0000863.jpg728 15050 Academy Houses Plumbing A) Hanger missing on drop and change of direction, B) Hangers missing at change of

direction and at values.AB4-1.03 P0001352.jpg

724 15050 Academy Houses Plumbing Access door for valves not installed, valves unaccessible and no valve ID. AB4-1.03 P0001196.jpg743 15050 Academy Houses Plumbing Access panel door in ceiling for shut-off valve not installed. AB4-1.03 P0001105.jpg764 15050 Academy Houses Plumbing Access panel in ceilling for shut-off valve not installed. AB4-1.03 P0001105.jpg719 15050 Academy Houses Plumbing Hanger missing from valve loop. AB4-1.03 P0001270.jpg

1005 15050 Academy Houses Plumbing At fire rated walls, fire caulk not installed at penetrationss thru walls .1) 76 4" and less 2) 3 - 6" copper lines 3) 7 unistrut hangers thru fire wall. Total of 86 locations.

AB4-1.03 P0001057.jpg

726 15050 Academy Houses Plumbing No metal shield under foam insulation at hanger at condenser line. AB4-1.03 P0001354.jpg677 15050 Academy Houses Plumbing No sleeves around domestic water line at trapeeze. Insulation has been removed at

trapezee.AB4-1.03 P0001375.jpg

721 15050 Academy Houses Plumbing No metal shield under foam insulation at hanger on condenser line. AB4-1.03 P0001354.jpg763 15050 Academy Houses Plumbing Plumbing fixtures have not been installed and piping to fixtures incomplete. AB4-1.03 P0001102.jpg733 15050 Academy Houses Plumbing Hangers missing at change of direction and at valve loop on copper line. AB4-1.03 P0001264.jpg669 15050 Academy Houses Plumbing Acid waste line not supported at 4' O.C. and felt has not been used at clamps. AB4-1.03 P0001194.jpg681 15050 Academy Houses Plumbing Hanger missing at change of direction on domestic water line. AB4-1.03 P0001264.jpg680 15050 Academy Houses Plumbing No metal shield under foam insulation at hanger for condensate line and domestic water

line.AB4-1.03 P0000863.jpg

725 15050 Academy Houses Plumbing Hangers missing on insulated pipe runs and at change of direction. Insulation torn and pipe is sagging from lack of support.

AB4-1.03 P0001356.jpg

749 15050 Academy Houses Plumbing Access panel door for shut-off valve not installed. AB4-1.03 P0001105.jpg684 15050 Academy Houses Plumbing No felt around acid waste line at hanger supports. AB4-1.03 P0001194.jpg675 15050 Academy Houses Plumbing Hanger missing on copper line at change of direction. AB4-1.03 P0001864.jpg22 15050 Parking Garage Fire Protection Fire protection line at column drop head on grid line requires 1" clearance all around. AA-1.02 P0000594.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 44 of 154

Page 45: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

24 15050 Parking Garage Fire Protection Fire sprinkler lines 1" clearance around pipe not provided at concrete beam drop. AA-1.0221 15050 Parking Garage Fire Protection Fire protection line bearing on hard ceiling light gage studs - Sprinkler line requires 1"

clearance all around.AA-1.03

169 15050 Parking Garage HVAC and Temperature Control Systems Fire damper installation inverted. AA 1.08 P0000335.jpg

109 15050 Parking Garage HVAC and Temperature Control Systems Lateral brace gauge is not to code above. Longitudinal bracing missing AA 1.09 P0000553.jpg

27 15050 Parking Garage HVAC and Temperature Control Systems 6" duct penetration in framed wall not fire safed. AA-1.02

290 15050 Parking Garage HVAC and Temperature Control Systems Smoke/fire damper installed inverted in the return air duct. AA-1.06 P0000335.jpg

204 15050 Parking Garage HVAC and Temperature Control Systems Duct not properly installed and not seismically braced. AA-1.07 P0000394.jpg

112 15050 Parking Garage Plumbing Hangars for 5" drain line is not dye chromate. AA 1.07 P0000484.jpg103 15050 Parking Garage Plumbing Hanger missing at change of direction. Pipe guard required. AA 1.09 P0000473.jpg108 15050 Parking Garage Plumbing Rod length for hanger support exceeds SMACNA requirements. Vertical angel brace

needed per code above.AA 1.09 P0000487.jpg

107 15050 Parking Garage Plumbing Rod length for storm drain exceeds code requirements. Vertical angel brace needed per code above.

AA 1.09 P0000487.jpg

105 15050 Parking Garage Plumbing Longitudinal bracing missing on 6" to 4" SSD lines. AA 1.09 P0000554.jpg104 15050 Parking Garage Plumbing Clamps for vertical support not within 12" per spec above. Bracing missing at change of

direction above floor.AA 1.09 P0000473.jpg

93 15050 Parking Garage Plumbing Storm drain lines require supports at columns, as required by specs. AA 1.09 P0000506.jpg37 15050 Parking Garage Plumbing Hangers not di-chromate per spec above. AA-1.01 P0001134.jpg36 15050 Parking Garage Plumbing Hanger missing and not within 1' 0" of branch line per spec above. AA-1.01

127 15050 Parking Garage Plumbing Acid waste line not properly supported. Hangars not to spec. section above. Penetration not fire safed and no felt on hangers.

AA-1.08-.09 P0000454.jpg

118 15050 Parking Garage Plumbing Acid waste line hangers not to spec. above. No felt on hangers. AA1.07 P0000454.jpg102 15050 Parking Garage Plumbing Support not within 12" of clamp in vertical run; bracing missing at change of direction

and projecting out of deckAA1.09 P0002543.jpg

3 15050 Parking Garage Plumbing Copper line at second floor elevation: no hanger support at vertical change of direction for riser.

PA 1.06 P0001981.jpg

1 15050 Parking Garage Plumbing No longitudinal bracing on vent line at location on line R.2 from 2 to 7.5 PA 1.06 P0000477.jpg143 15050 Parking Garage Plumbing Storm drain at change of direction requires support within 18" of change of direction and

pipe guard required.PA 1.08 P0000445.jpg

88 15050 Parking Garage Plumbing Hangers for 4" vent lines are not dye chromate as requires per spec. All hangers shall be clevis type.

PA 1.08 P0000490.jpg

76 15050 Parking Garage Plumbing 8" and 6" storm drain risers have not been properly supported as required by spec section above.

PA 109 P0000496.jpg

49 15050 Parking Garage Plumbing 4" no hub pipe clamp is skewed 13'4" from floor near CMU wall. Pipe clamp not close enough to no hub fitting.

PA-1.01 P0000689.jpg

663 15050 Parking Garage Plumbing Rectangular storm drain line does not penetrate shear wall. PA-1.0148 15050 Parking Garage Plumbing Clamps shall have factory installed di-chromate finish. PA-1.01 P0001134.jpg47 15050 Parking Garage Plumbing Storm drain risers have not been supported as required by specs. Supports shall be

installed within 18" of no hub clamps.PA-1.01 P0000372.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 45 of 154

Page 46: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

41 15050 Parking Garage Plumbing All clevis hangers for piping shall be di-chromate. PA-1.08 P0001134.jpg131 15050 Parking Garage Plumbing The incorrect type of clamp has been used to support the waste line. PA108 P0000449.jpg572 15050 Triple Gym HVAC and Temperature Control Systems Wood block under strap on round duct. AC-1.02 P0000938.jpg

440 15050 Triple Gym Plumbing Copper pipe has not been supported at change of direction as required at the vertical and horizontal runs.

AC 1.00 P0000875.jpg

445 15050 Triple Gym Plumbing Valve on South wall has not been properly supported for vertical piping. AC 1.00 P0000875.jpg457 15050 Triple Gym Plumbing Copper 1" pipe not verticaly supported at CMU wall at 6' spacing 6 pipe 1" in size also

pipe not supported with one foot at change of direction as required.AC 1.00 P0000831.jpg

446 15050 Triple Gym Plumbing Hangers missing on insulated copper tube. AC 1.02 P0000884.jpg450 15050 Triple Gym Plumbing Pipe supports for storm drain lines at bottom of pipe is 32" from clamp and support

clamp at top of pipe at unistrut is missing.AC 1.02 P0000819.jpg

3269 15050-9100-07270 Academy Houses Drywall/EIFS/SOFP Exhaust air duct at-into North East corner of room at fire rated corridor wall line 4.6, not framed properly, not fire stopped.

AB3-1.01 P0001374.jpg

293 15050/15010 Parking Garage HVAC and Temperature Control Systems Round duct hung tight to fire sprinkler line fitting. Not to NFPA 13. AA-1.06 P0000594.jpg

856 15050/15400 Academy Houses Plumbing 1" Clearance is not provided at fire protection sprinkler line per code requirement. Duct strap is up tight against sprinkler line and plumbing line within 3/8" of sprinkler line at M.8-6.7. Also at M.8-5 plumbing line within 1/4 of sprinkler line.

AB4-1.01 P0001110.jpg

905 15110 Academy Houses Plumbing Clevis hanger clamp is loose on cast iron pipe at North wall. AB4-1.01 P0001003.jpg906 15110 Academy Houses Plumbing A light gage sprinkler type clamp has been used on a 2.5" vent line running

North&South.AB4-1.01 P0001004.jpg

825 15170 Academy Houses Electrical (School) 3 Smoke fire dampers motor not connected to power sources for return air, supply air and exhaust air units in room.

AB4-1.01 P0001024.jpg

1380 15170 Triple Gym HVAC and Temperature Control Systems Fan motors stored on roof, misc. boxes. P0002186.jpg

827 15190 Academy Houses HVAC and Temperature Control Systems Mechanical systems in electrical rooms not identified. AB4-1.01-1.02-1.03

2082 15190 Academy Houses Plumbing Identify all piping and valves in room. AB2-1.03 P0001875.jpg917 15190 Academy Houses Plumbing Identify all piping in rooms and work rooms. AB4-1.01 P0000968.jpg

9036 15190 Administration Plumbing No piping or valve identification where systems have been installed, typical. AE-1.0281 15190 Parking Garage HVAC and Temperature Control Systems Mechanical system piping and valves require identification Room #P311, P313, P318,

P314, P315, P302, P303, P312, P301, P307, P309, P319, P308, P310, P306, P305, P304.AA 1.07/1.08/1.09

232 15190 Parking Garage HVAC and Temperature Control Systems Mechanical system piping and valves require identification Room # P110, P109, P102, P108, P107, P103, P117, P119, P115, P118, P101, P120, P106, P122, P123, P127, P105, P104

AA-1.01, 1.02, 1.03

268 15190 Parking Garage HVAC and Temperature Control Systems Mechanical systems, piping, values require identification. Rooms P201, P203, P207, P211, P213, P208, P214, P213, P216, P206, P205, P204, P210, P209

AA-1.04/.05/.06

294 15240/15800 Parking Garage HVAC and Temperature Control Systems Round duct not seismically restrained per spec above 8" and 10". AA-1.06 P0000578.jpg

2252 15250 Academy Houses HVAC and Temperature Control Systems Insulation is not installed around ducts and supporting straps are not attached to ducts. AB2-1.02 P0001765.jpg

881 15250 Academy Houses HVAC and Temperature Control Systems Insulation around round duct doesn't continue thru rated wall per spec above. AB4-1.01 P0001035.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 46 of 154

Page 47: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

886 15250 Academy Houses HVAC and Temperature Control Systems 1/8" gap between duct work and ladder cable tray not provided at S.5-5.4 AB4-1.01 P0001045.jpg

851 15250 Academy Houses HVAC and Temperature Control Systems Insulation around round duct doesn't continue thru wall per spec. AB4-1.02 P0001035.jpg

838 15250 Academy Houses HVAC and Temperature Control Systems Insulation on round duct doesn't continue thru wall per spec. AB4-1.02 P0001035.jpg

961 15250 Academy Houses HVAC and Temperature Control Systems Round duct at one location duct insulation not through wall cavity and not fire caulked. AB4-1.02 P0001035.jpg

840 15250 Academy Houses HVAC and Temperature Control Systems Insulation around round duct doesn't continue thru wall per spec and not fire rated in Wk Rm 225.

AB4-1.02 P0001035.jpg

1405 15250 Academy Houses HVAC and Temperature Control Systems Exhaust fan not installed properly. MB1-1.04 P0000210.jpg

1407 15250 Academy Houses HVAC and Temperature Control Systems Exhaust fan not installed properly. MB2-1.04 P0000210.jpg

1406 15250 Academy Houses HVAC and Temperature Control Systems Exhaust fan not installed properly. MB2-1.04 P0000210.jpg

2373 15250 Academy Houses Plumbing Typical at insulated condensate hangers, shields are required. AB2-1.03 P0000863.jpg874 15250 Academy Houses Plumbing 1 1/2" Copper main not insulated and branch line insulation incomplete. AB4-1.01 P0001049.jpg273 15250 Parking Garage HVAC and Temperature Control Systems 8" Duct work in room not seismically braced. AA-1.04 P0002524.jpg

434 15250 Triple Gym HVAC and Temperature Control Systems All insulated ducts that exit locker room to other rooms have not been insulated thru the walls.

AC 1.00 P0000931.jpg

444 15250 Triple Gym HVAC and Temperature Control Systems Supply air duct not insulated. AC 1.00 P0000870.jpg

575 15250 Triple Gym HVAC and Temperature Control Systems All exposed edges of duct insulation shall be sealed and tears repaired. AC-1.00

426 15250 Triple Gym Plumbing Shields area required at hangers for foam insulated pipe. AC 1.00 P0000869.jpg476 15250 Triple Gym Plumbing 2 2" copper lines have not been insulated. AC 1.02 P0000870.jpg485 15250 Triple Gym Plumbing Shield needed at hanger protection condensated line and hanger missing at change of

direction.AC-1.02

2087 15300 Academy Houses Drywall/EIFS/SOFP Wall framing stud tight against sprinkler line, 1" clearance is not provided around fire sprinkler line at B.6-3.3.

AB2-1.03 P0001819.jpg

2090 15300 Academy Houses Electrical (School) 2 Conduits up against sprinkler line, 1" clearance is not provided around fire sprinkler line at B.6-3.7.

AB2-1.03 P0001820.jpg

3195 15300 Academy Houses Electrical (School) 2-Conduit runs resting on sprinkler pipe, 1" clearance is not provided. AB3-1.02 P0001434.jpg711 15300 Academy Houses Electrical (School) 1" Clearance not provided at electrical conduit runs where sprinkler line cross over at

following locations; S.2-5.2, 5.2-4.5, S.2-4.2.AB4-1.02 P0001226.jpg

992 15300 Academy Houses Fire Protection Fire sprinkler fire caulking not per NFPA 13, room 312-5, 324-1, 313-3, 314-2, 315-1, 317-2, 318-2, 319-1.

2461 15300 Academy Houses Fire Protection Fire sprinkler lines thru corridor fire walls are not fire caulked at 3 locations.2325 15300 Academy Houses Fire Protection 1) Head is too close to beam for proper spray cover in room. 2) Hanger missing at change

of direction. Note: 1) Applies to 2nd floor Janitor room.AB1-1.01-1.02

P0001705.jpg

5066 15300 Academy Houses Fire Protection Provide 1" clearance between sprinkler drop and conduit. AB1-1.02 P0001734.jpg5053 15300 Academy Houses Fire Protection Provide 1" clearance between conduit and sprinkler line drop. AB1-1.02 P0001734.jpg5034 15300 Academy Houses Fire Protection Provide 1" clearance between sprinkler drop and conduit. AB1-1.02 P0001734.jpg5059 15300 Academy Houses Fire Protection Provide 1" clearance between sprinkler pipe and conduit. AB1-1.02 P0001734.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 47 of 154

Page 48: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

5058 15300 Academy Houses Fire Protection Provide 1" clearance between sprinkler drop and conduit. AB1-1.02 P0001734.jpg5098 15300 Academy Houses Fire Protection Hangers missing at change of directions on branch lines. AB1-1.03 P0001960.jpg5014 15300 Academy Houses Fire Protection 1) Two fire sprinkler heads in room are not installed. 2) Fire sprinkler line tight against

ceiling strong back studs: No 1" clearance provided around fire sprinkler line.AB1-1.03 P0002078.jpg

2452 15300 Academy Houses Fire Protection 1" clearance between sprinkler line and cable tray at 2 locations is required. AB2-.101 P0001602.jpg2442 15300 Academy Houses Fire Protection Sprinkler pipe limits access to return air duct. AB2-.101 P0001599.jpg2454 15300 Academy Houses Fire Protection Fire sprinkler pipe is not isolated from electrical, conduit support is required. AB2-.101 P0001616.jpg2158 15300 Academy Houses Fire Protection Hanger for sprinkler line is out of plumb with line and pipe to stair is not fire stopped. AB2-1.0 P0001579.jpg2440 15300 Academy Houses Fire Protection Sprinkler pipe doesn't have 1" clearance at cable tray. AB2-1.01 P0001602.jpg2355 15300 Academy Houses Fire Protection Sprinkler pipe in contact with cable tray, 1" clearance per above code is not provided. AB2-1.01 P0001602.jpg2425 15300 Academy Houses Fire Protection All piping and valves shall be provided with identification for all floors and rooms. AB2-1.012353 15300 Academy Houses Fire Protection Sprinkler line drop penetrating thru cable tray. AB2-1.01 P0001695.jpg2397 15300 Academy Houses Fire Protection 4" sprinkler pipe section and fitting placed inside HVAC shaft area at east wall south

corner of room. Shaft is not installed at present time.AB2-1.01-1.02-1.03

P0001682.jpg

2143 15300 Academy Houses Fire Protection Fire protection sprinkler line at East fire rated wall, 90 degree elbow, and pipe clampare half in wall and is not acceptable to code.

AB2-1.02 P0002010.jpg

2314 15300 Academy Houses Fire Protection Provide 1" clearance between sprinkler line and cable tray. AB2-1.02 P0001734.jpg2208 15300 Academy Houses Fire Protection 1" Clearance is not provided crossing over plumbing line and top track of stud wall. AB2-1.02 P0001763.jpg2464 15300 Academy Houses Fire Protection Corridor ceiling fire sprinkler head missing, one total. AB2-1.02 P0001595.jpg2312 15300 Academy Houses Fire Protection Provide 1" clearance at sprinkler drop next to conduit. AB2-1.02 P0001734.jpg2463 15300 Academy Houses Fire Protection Corridor ceiling fire sprinkler head missing, one total. AB2-1.02 P0001595.jpg2308 15300 Academy Houses Fire Protection Sprinkler line in front of return air duct will not allow access to duct. AB2-1.02 P0001746.jpg2232 15300 Academy Houses Fire Protection 1" Clearance is not provided on fire sprinkler line at electrical conduit where it crosses

under the conduit above the door.AB2-1.02 P0001743.jpg

2033 15300 Academy Houses Fire Protection Provide 1" clearance where sprinkler pipe passes over cable tray. AB2-1.03 P0001602.jpg2095 15300 Academy Houses Fire Protection Sprinkler line under duct work, 1" clearance around sprinkler line is not provided. AB2-1.03 P0001892.jpg2020 15300 Academy Houses Fire Protection Provide 1" clearance between sprinkler pipe and duct work. AB2-1.03 P0001856.jpg2110 15300 Academy Houses Fire Protection Sprinkler above EIFS ceiling penetrates fire rated wall, 90 degree elevation change half

in stud wall cavity, no sleeve and not fire stopped, elevation change is not accepted to plan, located at E-2.7.

AB2-1.03 P0001977.jpg

2074 15300 Academy Houses Fire Protection Sprinkler line clamp will be inside of wall. AB2-1.03 P0001846.jpg2393 15300 Academy Houses Fire Protection Fire sprinkler piping too close to top of corridor lights near door 317 and 318, 2 locations

total.AB2-1.03

2371 15300 Academy Houses Fire Protection Fire sprinkler lines, drops are not centered in corridor. AB2-1.03 P0001699.jpg2377 15300 Academy Houses Fire Protection Fire sprinkler horizontal pipe and drop below finish ceiling at door 319.1. AB2-1.03 P0001698.jpg2394 15300 Academy Houses Fire Protection Fire sprinkler pipes (drops) are not completed where heads are required, 3 in corridor

between B.3-D at column line 3 and 1 near door 316, total of 4.AB2-1.03 P0001699.jpg

3255 15300 Academy Houses Fire Protection At void space under stair landing fire sprinkler lines: 1) Fire caulk of wall penetration not done . 2) Sprinkler pipe encased in block wall. 3) Pipe drops not cut to length with no heads installed.

AB3-1.01 P0001421.jpg

3231 15300 Academy Houses Fire Protection Sprinkler drops and heads not installed in ceiling grid. AB3-1.01 P0001191.jpg3016 15300 Academy Houses Fire Protection Fire sprinkler resting on ceiling stud track 1" clearance is not provided. AB3-1.01 P0001645.jpg3257 15300 Academy Houses Fire Protection Typical all corridors; fire sprinkler pipe not cut to length and heads not installed at

ceilings. Level 1-21 locations, level 3-19 locations.AB3-1.01-1.02-1.03

P0000948.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 48 of 154

Page 49: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

3031 15300 Academy Houses Fire Protection Sprinkler heads not installed in framed ceiling of stair and corridor area. Level 1-3 sprinkler, level 2-3 sprinkler and level 3-4 sprinkler, total of 10.

AB3-1.01-1.02-1.03

P0001568.jpg

3026 15300 Academy Houses Fire Protection Access doors at flow and tamper cabinet not installed. AB3-1.01-1.02-1.03

P0001620.jpg

3247 15300 Academy Houses Fire Protection Fire hose cabinets 1) Level one, glass not installed in door. 2) Level two glass not installed in door. 3) Level three door and glass not installed.

AB3-1.01-1.02-1.03

P0000957.jpg

3006 15300 Academy Houses Fire Protection Fire sprinkler line resting on ceiling stud track at line M and line 2.8. 1" clearance is not provided.

AB3-1.02 P0001645.jpg

3117 15300 Academy Houses Fire Protection HVAC strap used to support sprinkler pipe. AB3-1.02 P0001472.jpg3023 15300 Academy Houses Fire Protection Vertical 4" fire sprinkler line at 11' from deck not braced at change of direction. AB3-1.03 P0001621.jpg3138 15300 Academy Houses Fire Protection Fire sprinkler head uptight against unistruts not accepted to code. AB3-1.03 P0001493.jpg3137 15300 Academy Houses Fire Protection Fire sprinkler line rod hanger up tight against conduit. Isolation not provided. AB3-1.03 P0001483.jpg3252 15300 Academy Houses Fire Protection At finished ceiling: 1) Pipe drops not cut to length, 2 total. 2) Holes in finished ceiling

too small to remove pipe drops, 2 total. 3) Sprinkler heads not installed.AB3-1.03 P0000948.jpg

3022 15300 Academy Houses Fire Protection Sway bracing for fire sprinkler lines, wires to deck too slack and at 1 location wire cut over door 311.

AB3-1.03 P0001622.jpg

3136 15300 Academy Houses Fire Protection Fire sprinkler line up tight against support hanger rod. 1" clearance is not provided. AB3-1.03 P0001483.jpg920 15300 Academy Houses Fire Protection Fire Hose Cabinet at following locations; 1) R.6-6.9 door and hose not installed. 2) R.6-

3.7 cabinet door window (glazing light) and hose not installed and N-5.9 cabinet door window light and hose not installed. (FVC: Fire valve cabinet).

AB4-1.01 P0001957.jpg

889 15300 Academy Houses Fire Protection Fire sprinkler line at head not plumb. AB4-1.01885 15300 Academy Houses Fire Protection 1" Clearance of fire sprinkler not provide hanger rod for plumbing line and 2 conduit

lines apply in this situation at S-5.2.AB4-1.01 P0001048.jpg

857 15300 Academy Houses Fire Protection Fire protection sprinkler line 90 elbow pipe connection is embedded in wall. AB4-1.01 P0001114.jpg652 15300 Academy Houses Fire Protection 1" Clearance not provided between unistrut support for conduit run and fire sprinkler

line.AB4-1.02 P0001252.jpg

658 15300 Academy Houses Fire Protection Hanger rod for sprinkler line up tight against conduit. AB4-1.02 P0001232.jpg717 15300 Academy Houses Fire Protection Sprinkler thru rated wall no sleeve and not fire rated. AB4-1.02 P0000529.jpg709 15300 Academy Houses Fire Protection 1) 1" Clearance is not provided on sprinkler line at unistrut and unistrut rod support at P.3

2.3, 2) Sprinkler head not installed at P.7-2.3.AB4-1.02 P0001190.jpg

982 15300 Academy Houses Fire Protection Fire sprinkler pipe clearance to electrical conduits not maintained: Room 214-1 location, 215-1 pipe rack, 216-1 pipe rack. 3 locations.

AB4-1.02 P0001226.jpg

909 15300 Academy Houses Fire Protection Fire hose cabinet at following locations; cabinet door, window (glazing light) and hose are not installed at following locations; R.6-3.7, N-5.9, R.6-6.9. (FVC: Fire Valve Cabinet)

AB4-1.02 P0000958.jpg

706 15300 Academy Houses Fire Protection Electrical conduits crossing under sprinkler line, 1" clearance not provided. AB4-1.02 P0001227.jpg980 15300 Academy Houses Fire Protection Fire sprinkler pipe clearance to electrical conduits not maintained: Room 210-1 location,

212-2 locations, 213-1 location. 4 total.AB4-1.02 P0001226.jpg

708 15300 Academy Houses Fire Protection Electrical conduits cross under sprinkler line, 1" clearance not provided. AB4-1.02 P0001229.jpg712 15300 Academy Houses Fire Protection 1" Clearance not provided conduit tight against sprinkler line. AB4-1.02 P0001206.jpg621 15300 Academy Houses Fire Protection Sprinkler pipe thru rated wall no sleeve and not fire rated. AB4-1.02 P0000529.jpg976 15300 Academy Houses Fire Protection Fire sprinkler pipe clearance to electrical conduit not maintained: Room 221-pipe racks 3

locations, 225-one conduit, 226-one conduit, 227-one conduit. 6 locations total.AB4-1.02 P0001226.jpg

955 15300 Academy Houses Fire Protection One fire sprinkler drop not cut in at each classroom, total of two. AB4-1.02 P0001191.jpg981 15300 Academy Houses Fire Protection Fire sprinkler pipe clearance to electrical conduits not maintained: Room 217-1 location,

218-1 pipe rack, 220-3 pipe racks.AB4-1.02 P0001226.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 49 of 154

Page 50: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

910 15300 Academy Houses Fire Protection Fire hose cabinet at following locations cabinet door window glazing light and hose are not installed. R.6-3.7, N-5.9, R.6-6.9.

AB4-1.03 P0000958.jpg

804 15300 Academy Houses Fire Protection Fire sprinkler line at conduit rack does not have one inch required clearance as required. AB4-1.03 P0001327.jpg993 15300 Academy Houses Fire Protection Where tee bar ceilings are installed, pipes are not cut to length and heads are not

installed.AB4-1.03 P0001911.jpg

988 15300 Academy Houses Fire Protection Fire sprinkler lines thru fire walls fire caulking not installed. Room 303-1, 310-1, 312-1, 313-1, 309-1, 320-1, 321-2, 328-2.

AB4-1.03 P0001127.jpg

979 15300 Academy Houses Fire Protection Fire sprinkler pipe clearance to electrical conduits not maintained: Room 318-2 locations, 320-3 locations. 5 total.

AB4-1.03 P0001226.jpg

978 15300 Academy Houses Fire Protection Fire sprinkler pipe clearance to electrical conduits not maintained: Room 314-1 location, 315-2 locations, 316-2 location, 317-2 locations. 7 total.

AB4-1.03 P0001226.jpg

977 15300 Academy Houses Fire Protection Fire sprinkler pipe clearance to electrical conduit not maintained: Room 312-2 location, room 324, one location, room 313, one location. 4 total.

AB4-1.03 P0001226.jpg

994 15300 Academy Houses Fire Protection These two rooms do not have fire sprinklers. AB4-1.039012 15300 Administration Drywall/EIFS/SOFP 1" Clearance is not provided around sprinkler pipe, wall studs tight against sprinkler pipe

at Room 210 South wall and Room 232. 3 Sprinkler lines up against East wall framing studs and Room 236 sprinkler line up against East wall framing stud.

AE-1.02 P0002254.jpg

9112 15300 Administration Electrical (School) Fire sprinkler line over conduit, 1" clearance is not provided. P0002256.jpg9007 15300 Administration Electrical (School) 1" Clearance is not provided around sprinkler line. Race way under sprinkler line at A.8-

on 1.6 and 1.8.AE-1.02 P0002264.jpg

9111 15300 Administration Electrical (School) 1" Clearance is not provided around sprinkler pipe, rod hangers for electrical panel box up against sprikler line.

AE-1.02 P0002255.jpg

9008 15300 Administration Electrical (School) 1" Clearance is not provided around sprinkler pipe. Conduit tight against sprinkler pipe at B.7-2.8 and at B.7-2.5 locations.

AE-1.02 P0002256.jpg

9006 15300 Administration Electrical (School) 1" Clearance is not provided around fire protection line. Race way over sprinkler line is uptight against it at A.8-1.4 locations.

AE-1.02 P0002264.jpg

9013 15300 Administration Electrical (School) 1" Clearance around fire sprinkler line is not provided at location A.8-2.3. Conduit tight against sprinkler line.

AE-1.02 P0002268.jpg

9010 15300 Administration Electrical (School) 1" Clearance is not provided around sprinkler pipe. Rod hanger for unistrut at 4.4-A.8 location corridor 220 and Room 236 at rod hanger for unistrut support at C.1-4.2 location.

AE-1.02 P0002258.jpg

9088 15300 Administration Fire Protection Fire sprinkler riser not installed from overhead line down to first floor. AE-1.02 P0002301.jpg9043 15300 Administration Fire Protection Fire proofing of steel beams at fire sprinkler beam clamps not patched, typical about 100

locations.AE-1.02 P0002273.jpg

9092 15300 Administration Fire Protection Fire sprinkler hangers incomplete at stair 220. AE-1.02 P0002304.jpg9091 15300 Administration Fire Protection Fire sprinkler overhead piping not seismically braced. AE-1.02 P0002303.jpg9090 15300 Administration Fire Protection Fire sprinkler lines not installed at North exterior roof canopy line D to D.5 and 2.7 to

4.7.AE-1.02 P0002302.jpg

9089 15300 Administration Fire Protection Fire sprinkler pipe drops not cut to length and heads not installed. AE-1.02 P0002301.jpg9011 15300 Administration Fire Protection Fire sprinkler line under duct air supply sytem at C.4-3.3 location does not have 1"

clearance.AE-1.02 P0002259.jpg

9009 15300 Administration HVAC and Temperature Control Systems 1" Clearance is not provided around sprinkler pipe. Duct strap tight against fire sprinkler at B.7-1.8 location.

AE-1.02 P0002257.jpg

9084 15300 Administration Plumbing No roof drain: Pipes installed North of column line A.2. AE-1.02 P0002296.jpg9083 15300 Administration Plumbing No cast iron waste of vent except for vertical pipe at room 234-223-216-217 (one riser

each).AE-1.02 P0002295.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 50 of 154

Page 51: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

9072 15300 Administration Plumbing No hot or cold water lines, typical. AE-1.029082 15300 Administration Plumbing No plumbing pipe installed thru roof jacks, 8 locations. AE-1.03 P0002215.jpg

345 15300 Parking Garage Fire Protection 2" sprinkler at horizontal required support. A 103 P0000715.jpg353 15300 Parking Garage Fire Protection Sprinkler line for spray head should extend to middle of stairwell. This line is capped off

at reducer. The spray head is about 4' East of entrance door.A 109 P0000680.jpg

334 15300 Parking Garage Fire Protection Wall interferes with sprinkler head spray pattern, correction required. AA 1.01 P0000726.jpg413 15300 Parking Garage Fire Protection Short nipple should be added to inspector test drain at plumbing line. AA 1.01 P0000743.jpg412 15300 Parking Garage Fire Protection Sprinkler pipe is hitting light fixture and head is turned 90 degrees. Replace removed

hanger for sprinkler pipe on 2" line.AA 1.01 P0000740.jpg

384 15300 Parking Garage Fire Protection Wall interferes with sprinkler head spray pattern correction required. AA 1.01 P0000726.jpg333 15300 Parking Garage Fire Protection Sprinkler line drops under HVAC duct not properly supported. AA 1.01 AA

1.02P0000739.jpg

387 15300 Parking Garage Fire Protection Drilled anchors are too small for the size of holes provided at base of sprinkler supports. AA 1.02 P0000646.jpg406 15300 Parking Garage Fire Protection Fire sprinkler line and fire sprinkler heads interfere with lighting fixtures in corridor and

stair area. Note: 1" Clearance is required on fire protection lines with any other obstruction minimum.

AA 1.04 P0000754A.jpg

240 15300 Parking Garage Fire Protection Fire sprinkler line at deck ceiling beam drops. Does not maintain 1" clearance per code requirements.

AA 1.04 P0002525.jpg

241 15300 Parking Garage Fire Protection Fire sprinkler line west side of column required 4-way sway brace. AA 1.04 P0000328.jpg242 15300 Parking Garage Fire Protection Sprinkler piping installed below ductwork shall be supported from structure. AA 1.04 P0002533.jpg243 15300 Parking Garage Fire Protection Sprinkler line interferes with light. AA 1.04 P0000290.jpg247 15300 Parking Garage Fire Protection Fire sprinkler line in corridor interferes with light fixtures in corridor. AA 1.04 P0002532.jpg145 15300 Parking Garage Fire Protection Hanger missing on sprinkler line. AA 1.07 P0000447.jpg158 15300 Parking Garage Fire Protection Sprinkler line couplings in contact with other consruction. Line does not have 1"

clearance per code.AA 1.07 P0002511.jpg

162 15300 Parking Garage Fire Protection Longitudinal seismic bracing missing on 4" sprinkler line. AA 1.07 P0002510.jpg163 15300 Parking Garage Fire Protection Hangers missing at change of direction of 2" sprinkler line under concrete beam. AA 1.07 P0000424.jpg147 15300 Parking Garage Fire Protection 4" Line not seismically braced and vertical pipe not properly supported. AA 1.08 P0000576.jpg115 15300 Parking Garage Fire Protection Hangar required at 6' foot pipe segment. AA 1.08 P0000480.jpg148 15300 Parking Garage Fire Protection 2" pipe in contact with 4" rigid conduit, not to specs. Requires 1" separation. AA 1.08 P0000569.jpg111 15300 Parking Garage Fire Protection Sprinkler head obstructed by 4" drain lines. AA 1.08 P0000481.jpg149 15300 Parking Garage Fire Protection Sprinkler line missing support hangers at change of direction under beam. Sprinkler line

fitting is above bus way.AA 1.08 P0000436.jpg

324 15300 Parking Garage Fire Protection At column capitals fire sprinkler line does not maintain 1" clearance per code requirements.

AA 1.08 P0000466.jpg

95 15300 Parking Garage Fire Protection Sprinkler head too close to 2" conduit. Does not maintain 1" clearance per code requirements.

AA 1.09 P0000569.jpg

369 15300 Parking Garage Fire Protection Fire sprikler lines in rooms noted have not been installed. AA 1.09 P0000674.jpg234 15300 Parking Garage Fire Protection Branch lines 30' and longer have not been braced as required by NFPA #13 for sway and

uplift.AA 102 P0000596.jpg

72 15300 Parking Garage Fire Protection Hanger missing on sprinkler piping. AA 107 P0000533.jpg69 15300 Parking Garage Fire Protection Sprinkler heads missing. AA 107 P0000526.jpg70 15300 Parking Garage Fire Protection Sprinkler will spray on bus duct. It should not. AA 107 P0000527.jpg74 15300 Parking Garage Fire Protection Sprinkler drop on north side of exhaust duct hanger missing. AA 109 P0002538.jpg28 15300 Parking Garage Fire Protection Sprinkler penetration thru framed wall has not been sleeved and not fire safed. AA-1.02 P0000168.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 51 of 154

Page 52: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

15 15300 Parking Garage Fire Protection Sprinkler pipe penetration thru rated wall has no sleeve and fire safeing. Not fire rated. AA-1.03 P0000168.jpg16 15300 Parking Garage Fire Protection Hanger missing under side of beam for sprinkler pipe. AA-1.03 P0000371.jpg

278 15300 Parking Garage Fire Protection Sprinkler pipe too close to light fixture, work not to code above. AA-1.04263 15300 Parking Garage Fire Protection In parking area at elevator pit #208 CMU shaft on east and west exterior sides of CMU

shaft at north end. Sprinkler fire protection coverage is not adequate to cover area.AA-1.05 P0002519.jpg

128 15300 Parking Garage Fire Protection Sprinkler pipe gives no clearance for light frame basket. Can't service lamps. AA-1.05 P0000290.jpg287 15300 Parking Garage Fire Protection Sprinkler line requires guard at column. AA-1.06 P0000577.jpg201 15300 Parking Garage Fire Protection 1 1/2" sprinkler lines missing hanger under beam. And heads missing. AA-1.07 P0000373.jpg198 15300 Parking Garage Fire Protection Pipe penetration thru wall not fire safed. AA-1.07 P0000392.jpg221 15300 Parking Garage Fire Protection 1 1/2" sprinkler pipe hanger missing on north side of beam. AA-1.07 P0000373.jpg191 15300 Parking Garage Fire Protection Sprinkler line penetrations not fire safed. AA-1.07 P0000392.jpg209 15300 Parking Garage Fire Protection Sprinkler lines incomplete. Heads and hangers missing. AA-1.07 P0000376.jpg172 15300 Parking Garage Fire Protection Bent hanger rod at 6" fire sprinkler line requires correction. AA-1.07 P0000411.jpg222 15300 Parking Garage Fire Protection Sprinkler pipe lines not connected. AA-1.07 P0002506.jpg208 15300 Parking Garage Fire Protection Sprinkler pipe not fire safed. AA-1.07 P0000392.jpg173 15300 Parking Garage Fire Protection Support and protection requied for sprinkler line. AA-1.07 P0000402.jpg137 15300 Parking Garage Fire Protection Hangar for sprinkler to far from end of drop. 24" max. AA101 P0000422.jpg236 15300 Parking Garage Fire Protection Sprinkler pipes are resting on light fixture guards. Guards cannot be Removed to change

light tubes.EA 205 P0000290.jpg

89 15300 Parking Garage Plumbing Rod hangers for 8" and 6" storm drain lines; tight up against sprinkler line code 1" clearance around fire sprinkler line.

PA 1.09 P0000494.jpg

134 15300 Parking Garage Plumbing Pipe hangar is resting on light fixture at ramp. Cannot remove light guard to service lamps.

PA107 P0000420.jpg

569 15300 Triple Gym Drywall/EIFS/SOFP Fire proof patch where sprinkler lines cross under flange of beam at West-South sides of column 1) V-3 2) T.8-3.

AC-1.02 P0000935.jpg

1446 15300 Triple Gym Fire Protection No fire sprinkler risers installed from building exterior "P.I.V." (Post indicator valve) to exterior overhead piping except 6' elbow thru exterior wall.

P0002152.jpg

435 15300 Triple Gym Fire Protection Sprinkler pipe will not allow removal of smoke detector access cover at duct riser. AC 1.02 P0000918.jpg462 15300 Triple Gym Fire Protection Fire proofings sprinkler line East wall to vestibule. See note G-1. AC 1.02 P0000777.jpg463 15300 Triple Gym Fire Protection Fire proof patch all pipe hanger to structure 3 places. AC 1.02 P0000774.jpg464 15300 Triple Gym Fire Protection Cored hole for sprinkler pipe above main entrance 1-# 4 vertical, 2-#4 horizontal and 1-

#5 horizontal rebar have been cored thru.AC 1.02 P0000787.jpg

465 15300 Triple Gym Fire Protection Fire stop all pipe penetrations in CMU walls. 3 Penetrations all 1" see note on G-1. AC 1.02 P0000398.jpg461 15300 Triple Gym Fire Protection Patch fire proofings at all pipe hangers and braces. AC 1.02 P0000774.jpg470 15300 Triple Gym Fire Protection The cored hole for the 4"sprinkler line above the door to the Janitor Room 117 has cut

thru 2-# 5 horizontal rebar.AC 1.02 P0000804.jpg

571 15300 Triple Gym Fire Protection 1) 2 Sprinkler heads not installed. 2) 4" D.A. sprinkler line wall at S.9-3. 3) Conduit crossing over sprinkler line No 1" clearance provided at S.1-2.8. Photo # 940.

AC-1.02 P0000821.jpg

561 15300 Triple Gym Fire Protection Sprinkler heads have not been installed. AC-1.02 P0000821.jpg578 15300 Triple Gym Fire Protection 4" Sprinkler line not fire rated. AC-1.02 P0000701.jpg504 15300 Triple Gym Fire Protection 3" Cored hole under sprinkler line has cut through a reinforcing bar. AC-1.02 P0000879.jpg530 15300 Triple Gym Fire Protection 2-Cored 8" diameter holes North and South walls reinforcing steel cut 3 - #5 cord steel

rebar and 1 - #4 vertical rebar cut off by coring process. Typical to both holes.AC-1.02 P0000834.jpg

501 15300 Triple Gym Fire Protection Fire sprinkler handles not installed. Total of 6. AC-1.02 P0000883.jpg546 15300 Triple Gym Fire Protection Sprinkler heads have not been installed. AC-1.02 P0000821.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 52 of 154

Page 53: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

507 15300 Triple Gym Fire Protection Two cored holes 3" size under fire sprinkler wall penetration left void at locations 1) V.3-6.1 and 2) V.3-6.6. Correction of blank holes required.

AC-1.02 P0000880.jpg

509 15300 Triple Gym Fire Protection Fire sprinkler heads in room are not installed. Total of 3. AC-1.02 P0000821.jpg513 15300 Triple Gym Fire Protection 3" Cored hole for sprinkler line in south CMU wall cut one # 5 horz. rebar. AC-1.02532 15300 Triple Gym Fire Protection 1) 2 Fire sprinkler heads in room not installed. 2) Fire sprinkler line 1" clearence all

around not provided. Two areas effected on some sprinkler head. A) 3/8 rod hanger for 2" copper line and B) sprinkler line drop tight against 2" copper line at V.4-3

AC-1.02 P0000821.jpg

1445 15300 Triple Gym Fire Protection No over head fire sprinkler or risers rooms 101-102-103-104-105-106-107-108-109-110-111-112-113 & 121. Total 14 rooms.

AC1.01

402 15300 05510 Parking Garage Fire Protection / Miscellaneous Iron and Steel Stairs

1" Clearance around 4" fire sprinkler line not in compiance with code requirement (stair stringer channel in contact with F.S. line.)

AA 1.05 P0000662.jpg

867 15300-15400 Academy Houses Fire Protection / Plumbing 1" Clearance not provided at sprinkler line crossing plumbing lines at following locations M.8-4.3, M.8-4, M.8-3.6, M.1-3.

AB4-1.01 P0001075.jpg

5102 15400 Academy Houses Fire Protection Provide 1" clearance between sprinkler pipe and drops at cable tray and trapeze for cable tray.

AB1-1.03 P0001602.jpg

967 15400 Academy Houses Plumbing Vertical pipe clamp at floor projecting outside of wall. P0001230.jpg696 15400 Academy Houses Plumbing Floor clamp for acid waste line is protruding from wall at the West side of the window. P0001230.jpg698 15400 Academy Houses Plumbing At North West corner of the room the acid waste line is resting on a sprinkler line and a

2" conduit.P0001235.jpg

2170 15400 Academy Houses Plumbing Storm drains incomplete until built up roofing is installed. AA-1.11 P0002453.jpg2171 15400 Academy Houses Plumbing Storm drains incomplete until built up roofing's is installed. AA-1.11 P0002453.jpg3328 15400 Academy Houses Plumbing Storm drains incomplete until built up roofing is installed. AA-1.12-1.13 P0002453.jpg

4000 15400 Academy Houses Plumbing Storm drains incomplete untill built up roofing is installed. AA1.13-1.122322 15400 Academy Houses Plumbing Mop sink is to close to studs to maintain fire rating of wall. AB1-1.01-

1.02-1.03P0001716.jpg

5037 15400 Academy Houses Plumbing Roof drain not connected. AB1-1.02 P0002093.jpg2405 15400 Academy Houses Plumbing Condensate line incomplete. AB2-1.01 P0001669.jpg2426 15400 Academy Houses Plumbing Bathroom roughed in, has not been finished. AB2-1.01 P0001636.jpg2423 15400 Academy Houses Plumbing All piping and valves shall be provided with identification for all floors and rooms. AB2-1.012279 15400 Academy Houses Plumbing Plumbing line skewed at hubbless coupling. AB2-1.02 P0001760.jpg2309 15400 Academy Houses Plumbing Trap primer line rusted at connection. AB2-1.02 P0001758.jpg2085 15400 Academy Houses Plumbing Piping has not been provided for two sinks on the East wall for the work room and

classroom 317 and the classroom 316 on the West wall.AB2-1.03 P0001886.jpg

2025 15400 Academy Houses Plumbing No plumbing stubs taped out at floor sink. Domestic hot and cold water and sink drain has not been installed.

AB2-1.03 P0001849.jpg

2205 15400 Academy Houses Plumbing Plumbing lines tight against flex conduit isolation required. AB2-1.03 P0001792.jpg2103 15400 Academy Houses Plumbing Hanger rod and clevis half in fire rated wall at B.5. AB2-1.03 P0001861.jpg2376 15400 Academy Houses Plumbing Plumbing penetrations at corridor walls fire stopping is not done. 10 locations total in

area noted.AB2-1.03 P0001076.jpg

2086 15400 Academy Houses Plumbing Floor clamp extends past finish wall surface and floor clamp does not have felt. AB2-1.03 P0001889.jpg2032 15400 Academy Houses Plumbing Floor sink and splash for acid waste not installed. AB2-1.03 P0001273.jpg3250 15400 Academy Houses Plumbing At level 1 enclosed area under stair 4" roof drain exposed (North wall). Water tight

surface omitted this area.AB3-1.01 P0001420.jpg

3275 15400 Academy Houses Plumbing Plumbing hanger clamps are not dichoramate. Total of 4 in room. AB3-1.01 P0001004.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 53 of 154

Page 54: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

3216 15400 Academy Houses Plumbing Plumbing fixtures not installed and piping to fixtures incomplete. AB3-1.01 P0001102.jpg3149 15400 Academy Houses Plumbing Fire caulk at hose bib valve box not done. AB3-1.01 P0000987.jpg3272 15400 Academy Houses Plumbing Water line is not supported at deck. AB3-1.01 P0001380.jpg3212 15400 Academy Houses Plumbing Access panels and doors not installed for plumbing shut-off valves in walls (total of 12

locations).AB3-1.01 P0001105.jpg

3223 15400 Academy Houses Plumbing Abondon sleeve in deck not fire stopped. AB3-1.01 P0001431.jpg3183 15400 Academy Houses Plumbing Hanger clamps are not dichoramate for plumbing lines. AB3-1.02 P0001427.jpg3054 15400 Academy Houses Plumbing Flammable material stuffed into roof sleeve at vent penetration. AB3-1.03 P0001564.jpg3034 15400 Academy Houses Plumbing Expansion swing joints are not provided for 1" by 4" dia plumbing water lines, medium

pressure natural gas pipe and condensate drain line.AB3-1.03 P0001576.jpg

642 15400 Academy Houses Plumbing Hot and cold water lines faucets not installed. AB4-1.0 P0001266.jpg873 15400 Academy Houses Plumbing 5 Plumbing penetrations thru rated deck not fire rated. AB4-1.01 P0001058.jpg869 15400 Academy Houses Plumbing Isolation is not provided for following items; 1) at M.2 - 3.3 & M.8 - 3.6 rod hanger for

clevis is tight against water line. 2) At M.9 - 3.6 duct support strap is tight against water line.

AB4-1.01 P0001074.jpg

866 15400 Academy Houses Plumbing At M.2 - 5.8 location rod hanger is tight against water line. Isolation required. AB4-1.01 P0001088.jpg870 15400 Academy Houses Plumbing Isolation is not provided at M.9 - 4.3 location water line is tight against stud wall

framing.AB4-1.01 P0001087.jpg

918 15400 Academy Houses Plumbing Seismic bracing required for cast iron at North and West walls. AB4-1.01 P0000964.jpg868 15400 Academy Houses Plumbing Remove all unused plumbing line rod clevis hangers above ceiling. AB4-1.01 P0001070.jpg872 15400 Academy Houses Plumbing Clevic hanger for plumbing lines are not dichromate. Room 113 total of 16, Room 124

total of 2, Room 112 total of 9.AB4-1.01 P0001052.jpg

875 15400 Academy Houses Plumbing 3" Gas line has not been seismically braced and hanger not installed hangers not dichromate and loose.

AB4-1.01 P0001050.jpg

863 15400 Academy Houses Plumbing Waste line fitting set in gypsum has not been fire stopped and rubber cap has been used on the clean out.

AB4-1.01 P0001080.jpg

876 15400 Academy Houses Plumbing Vent live has no longitudinal bracing hangers not dichromate. AB4-1.01 P0001052.jpg877 15400 Academy Houses Plumbing 25 Plumbing penetrations in rated wall have not been fire rated. AB4-1.01 P0001057.jpg891 15400 Academy Houses Plumbing Sprinkler clamps have been used to support cast iron plumbing lines at the South East

corner of the. For the 2" line that runs Norht+South.AB4-1.01 P0001018.jpg

880 15400 Academy Houses Plumbing Acid waste does not have felt on hangers and is not seismically braced and no ID. AB4-1.01 P0000964.jpg865 15400 Academy Houses Plumbing 1) At M.2 - 5.8 rod hanger for water line is disconnected from clevis hanger. 2) At M.9 -

5.9 rod hanger for insulated water line is disconnected at deck support.AB4-1.01 P0001088.jpg

900 15400 Academy Houses Plumbing Open 6" by 24" hole in deck needs to be fire stopped or filled with concrete next to this hole a 4" cast iron pipe penetrates the floor and 12" above finish floor. Pipe shall be rated at the floor and a floor clamp installed.

AB4-1.01 P0001007.jpg

615 15400 Academy Houses Plumbing Hanger missing on gas line at change of direction. AB4-1.02 P0001264.jpg605 15400 Academy Houses Plumbing Water hammer arestor not isolated from wall no felt around pipe and access door not

installed.AB4-1.02 P0001272.jpg

623 15400 Academy Houses Plumbing Sink assembly and splash for acid waste line has not been installed in floor. AB4-1.02 P0001273.jpg603 15400 Academy Houses Plumbing Sink assembly and splash for acid waste line has not been installed in floor. AB4-1.02 P0001273.jpg613 15400 Academy Houses Plumbing Hanger support for plumbing valve loop not installed . AB4-1.02 P0001270.jpg602 15400 Academy Houses Plumbing Water hammer arestor not isolated from wall and no access panel door installed. AB4-1.02 P0001272.jpg601 15400 Academy Houses Plumbing Abandoned hole for acid waste drain not filled in. AB4-1.02 P0001288.jpg610 15400 Academy Houses Plumbing Control valves are unaccessible panel door not installed and valves have no ID. AB4-1.02 P0001196.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 54 of 154

Page 55: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

718 15400 Academy Houses Plumbing Hanger missing from valve loop. AB4-1.02 P0001264.jpg714 15400 Academy Houses Plumbing Acid waste line not properly supported and felt not used at clamps. AB4-1.02 P0001194.jpg737 15400 Academy Houses Plumbing Acid waste line not properly supported and no felt at clamps. AB4-1.03 P0001194.jpg731 15400 Academy Houses Plumbing No shield at hanger on condensate line. AB4-1.03 P0000863.jpg786 15400 Academy Houses Plumbing Storm drain lines are above main electrical panel this is construction problem and a

design problem.AB4-1.03 P0001325.jpg

736 15400 Academy Houses Plumbing Sink and splash for acid waste not installed. AB4-1.03 P0001263.jpg670 15400 Academy Houses Plumbing Access panel not installed lower shut-off valves unaccessible and all piping not ID. AB4-1.03 P0001196.jpg668 15400 Academy Houses Plumbing Sink for acid waste and splash are not installed. AB4-1.03 P0001273.jpg735 15400 Academy Houses Plumbing Access panel not installed in wall. Lower shut off valve inaccessable and pipe no ID. AB4-1.03 P0001196.jpg871 15400 Academy Houses Plumbing At the gas line the clevis hangers are not dichromate type. In room 112 total of 23, in

room 124 total of 4, in room 113 total of 14.AB4-1.04 P0001134.jpg

901 15400 Academy Houses Plumbing Roof drain lines inside of electrical room. AB4-1.04 P0000980.jpg1061 15400 Academy Houses Plumbing All roof drains need to be hooked up and screens attached to above detail and print. PA1-2-3/1.04

& PA4-1.059028 15400 Administration Plumbing All below grade piping to be retested. AE-1.01 P0002244.jpg9106 15400 Administration Plumbing Overflow drain, roof drain and catch basket have not been installed, total of 2. AE-1.02 P0002233.jpg9078 15400 Administration Plumbing No plumbing at roof flashing, 8 locations. AE-1.03 P0002215.jpg9074 15400 Administration Plumbing No overflow drain installed, one location. Column line 2.5-D.1. AE-1.03 P0002207.jpg

250 15400 Parking Garage Drywall/EIFS/SOFP A) Drain line drop at rated wall - from third level penetration of rated Wall assembly not acceptable. B) Pipe coupler assembly in wall not acceptable. C) Penetration of Pipe in wall not fire stopped.

AA 1.04 P0000315.jpg

79 15400 Parking Garage Fire Protection 3" sprinkler line bent; has bent the light fixture guard and is installed against a 4" conduit.

AA 109 P0000499.jpg

26 15400 Parking Garage HVAC and Temperature Control Systems Hydronic water line valve hangers missing. PA-1.01 P0000722.jpg

66 15400 Parking Garage Plumbing 3" vent penetrations not fire safed; cannot fire rate diagonal penetration. P0000173.jpg389 15400 Parking Garage Plumbing Storm drain lines do not leave enough head room clearance at stair treads at South wall. AA 1.02 P0000631.jpg388 15400 Parking Garage Plumbing 8" and 6" storm drain lines not installed thru wall. AA 1.02 P0000629.jpg378 15400 Parking Garage Plumbing Hubbless clamps are inside of CMU for 8" and storm drain lines at South wall of stair. AA 1.05 P0000667.jpg260 15400 Parking Garage Plumbing Waste line is not supported at its base. Hanger missing at top of line. AA 1.05 P0002536.jpg259 15400 Parking Garage Plumbing Drain piping anchorage at column and deck not tested for sheer and tension. AA 1.05 P0002535.jpg160 15400 Parking Garage Plumbing Storm drain line not centered in sleeve per code. AA 1.07 P0000438.jpg164 15400 Parking Garage Plumbing Storm drain line is not centered in sleeve and pipe does not have watertight seal at

penetration per code and specs.AA 1.07 P0000438.jpg

159 15400 Parking Garage Plumbing 4" storm drain line not centered in sleeve. Requires 1" clearance per code. AA 1.07 P0000438.jpg150 15400 Parking Garage Plumbing 4" storm drain line hanger rod bent. Doesn't allow for 1" clearance from 1 1/2" sprinkler

pipe.AA 1.07 P0000569.jpg

113 15400 Parking Garage Plumbing Rod stiffiner requirements max length exceeded for rod hanger at Seismic brace. See code listed.

AA 1.07 P0000483.jpg

80 15400 Parking Garage Plumbing Plumbing piping systems for pipe sizes and valves require identification Room #P311, P313, P318, P314, P315, P302, P303, P312, P301, P307, P308, P317, P310, P309, P306, P305, P304.

AA 1.07/1.08/1.09

152 15400 Parking Garage Plumbing End caps at clean outs are incorrect type. AA 1.08 P0000172.jpg161 15400 Parking Garage Plumbing Storm drain line not seismically braced per code. AA 1.08 P0000554.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 55 of 154

Page 56: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

151 15400 Parking Garage Plumbing 4" storm drain line not seismically braced. AA 1.08 P0000477.jpg168 15400 Parking Garage Plumbing Lateral seismic bracing missing on storm drain line. AA 1.08 P0002514.jpg156 15400 Parking Garage Plumbing 6" copper line not seismically braced. AA 1.08 P0000469.jpg101 15400 Parking Garage Plumbing Longitudinal bracing is missing on storm drain line and line has not been fire stopped. AA 1.09 P0000511.jpg110 15400 Parking Garage Plumbing Rod length for hanger supports on storm drain lines exceed SMACNA requirements.

Vertical angle bracing needed per code above.AA 1.09 P0000489.jpg

106 15400 Parking Garage Plumbing Rubber gem cap at end of 2" waste line not to code above. AA 1.09 P0000439.jpg96 15400 Parking Garage Plumbing Hanger missing at change of direction and no support at riser. AA 1.09 P0000369.jpg

97 15400 Parking Garage Plumbing Waste and vent lines not supported at floor or change of direction. AA 1.09 P0000512.jpg99 15400 Parking Garage Plumbing Seismic brace on plumbing line has been removed. AA 1.09 P0002541.jpg

100 15400 Parking Garage Plumbing 8" SSD line missing longitudinal brace. Numerous hangers loose on line. AA 1.09 P0000513.jpg358 15400 Parking Garage Plumbing 4" drain line for inspectors test line is not properly supported at vertical riser and P trap

2" cast line is not supported at hubbless clamps as required by spec.AA 103

53 15400 Parking Garage Plumbing Bottom of 4" riser not supported per above code. AA-1.01 P0000372.jpg51 15400 Parking Garage Plumbing 4" riser not supported per code above. AA-1.01 P0000372.jpg38 15400 Parking Garage Plumbing Two 3" drain lines at column pipe skewed at coupling. AA-1.01 P0000689.jpg35 15400 Parking Garage Plumbing 4" SSD line not seismically braced per detail and print above. AA-1.01 P0000477.jpg

231 15400 Parking Garage Plumbing Plumbing piping systems for all pipe sizes and valves require identification; Room # P110, P109, P102, P108, P107, P103, P117, P119, P115, P118, P101, P120, P106, P122, P123, P127, P105, P104

AA-1.01, 1.02, 1.03

328 15400 Parking Garage Plumbing Drain elevation higher then low point of dock ramp. AA-1.03 P0000189.jpg327 15400 Parking Garage Plumbing Drain screen too small for drain opening. AA-1.03 P0000188.jpg

8 15400 Parking Garage Plumbing 8" SSD and copper lines have not been fire safed to above print, spec or code. AA-1.03 P0000175.jpg329 15400 Parking Garage Plumbing Hose bib missing. AA-1.03 P0000179.jpg325 15400 Parking Garage Plumbing Plumbing lines not braced at wall as required AA-1.03 P0000178.jpg270 15400 Parking Garage Plumbing 4" SSD lines not spaced through masonry wall per code above. AA-1.04275 15400 Parking Garage Plumbing End cap on 6" SSD not to code. AA-1.04 P0000172.jpg267 15400 Parking Garage Plumbing Plumbing piping system for all pipe sizes and values require identification. Rooms P201,

P203, P207, P211, P213, P208, P214, P213, P216, P206, P205, P204, P210, P209AA-1.04/.05/.06

265 15400 Parking Garage Plumbing 3" vent line drop hanger required at change of direction. AA-1.05 P0000575.jpg264 15400 Parking Garage Plumbing 3" S.D. line floor deck penetration open. No line installed. AA-1.05291 15400 Parking Garage Plumbing 4" acid waste line not centered in sleeve as required by code. AA-1.06 P0002515.jpg185 15400 Parking Garage Plumbing 2 2" vent pipe and 1 3/4" copper line penetrate deck, not fire safed. AA-1.07 P0000408.jpg226 15400 Parking Garage Plumbing 4" SSD line not braced to column at hub couplings. Vehicle guard required. AA-1.07 P0000375.jpg203 15400 Parking Garage Plumbing 10" SSD line not properly seismically braced. AA-1.07 P0000382.jpg202 15400 Parking Garage Plumbing 4" acid waste line not secured to column on floor. Felt not used in clamps AA-1.07 P0000395.jpg197 15400 Parking Garage Plumbing 3" vent passing over bus duct needs sleeve to prevent dripping onto bus duct. AA-1.07 P0000382.jpg216 15400 Parking Garage Plumbing Storm drain line is not properly seismically braced. AA-1.07 P0000382.jpg196 15400 Parking Garage Plumbing 4" acid waste line must be moved. Line can't pass over bus duct. Bus duct must be

protected from acid leaks.AA-1.07 P0000381.jpg

193 15400 Parking Garage Plumbing 3" vent not seismically braced. AA-1.07 P0000382.jpg225 15400 Parking Garage Plumbing 4" acid waste line hangers not properly spaced. Also, felt missing on hanger. AA-1.07 P0000374.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 56 of 154

Page 57: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

219 15400 Parking Garage Plumbing 4" SSD line not seismically braced. AA-1.07 P0000371.jpg227 15400 Parking Garage Plumbing Bracing missing at change of direction on 4" SSD coming out of second level dock. AA-1.07 P0000369.jpg183 15400 Parking Garage Plumbing Two 2" vent pipes not secured inside of wall. AA-1.07 P0000407.jpg223 15400 Parking Garage Plumbing 2 4" SSD lines not properly seismically braced. AA-1.07 P0002507.jpg195 15400 Parking Garage Plumbing 4" SSD line not seismically braced. AA-1.07 P0000380.jpg176 15400 Parking Garage Plumbing Over flow and roof drains are not installed at D & E - 0.8 grid. AA-1.07 P0000405.jpg184 15400 Parking Garage Plumbing 1 1 1/2" and 1 1" copper lines not secured inside of walls. AA-1.07 P0000407.jpg220 15400 Parking Garage Plumbing 6" SSD line not braced at column. AA-1.07 P0000372.jpg178 15400 Parking Garage Plumbing 3" vent missing hanger at change of direction. AA-1.07 P0002505.jpg177 15400 Parking Garage Plumbing 1/2" copper line and 3" vent line penetration not centered in sleeve and not fire safed at

CMU wall.AA-1.07 P0000521.jpg

171 15400 Parking Garage Plumbing 6" copper line not centered in sleeve thru beam. AA-1.08 P0002513.jpg170 15400 Parking Garage Plumbing 3" copper line not seismically braced per code. AA-1.08/.09 P0000458.jpg419 15400 Parking Garage Plumbing Bottom of "P" trap is not supported as required. AA1.01 P0000744.jpg421 15400 Parking Garage Plumbing 1/2" Copper line is not supported at column. AA1.01 P0000745.jpg142 15400 Parking Garage Plumbing Acid waste lines 4" and 2" at riser to podium level not welded together. End caps for

testing still in place. Also, clamps are missing felt pads.AA1.07 P0000417.jpg

140 15400 Parking Garage Plumbing Relocate hangar at 4" acid waste line from trap joint to horizontal pipe. Also, hanger doesn't have a felt pad as required.

AA1.07 P0000418.jpg

119 15400 Parking Garage Plumbing 2" vent line in contact with sprinkler line. Doesn't have 1" clearance. AA1.08 P0000460.jpg123 15400 Parking Garage Plumbing 10" to 8" SSD line not seismically restrained. AA1.09 P0000477.jpg124 15400 Parking Garage Plumbing 10" to 8" SSD line not properly seismically restrained. AA1.09 P0000382.jpg

125 15400 Parking Garage Plumbing 3" vent line not suported at 30 degree transition. AA1.09 P0002545.jpg126 15400 Parking Garage Plumbing 4" SSD line has no longitudinal seismic bracing. Rod stiffner required where rod length

has been exceeded per code section above.AA1.09 P0000477.jpg

2 15400 Parking Garage Plumbing Existing vent line drop combination type fitting: requires 90 degree fitting at location T-5.9 not per plan.

PA 1.06 P0000172.jpg

87 15400 Parking Garage Plumbing Rod stiffener angle required per SMACNA detail on 6" storm drain line. PA 1.08 P0000486.jpg144 15400 Parking Garage Plumbing Storm drain line at change of direction requires hanger within 18" of change of direction. PA 1.08 P0000446.jpg

86 15400 Parking Garage Plumbing Storm Drain and overflow drain lines, rod stiffener angles not installed at hanger rod seismic connection per code.

PA 1.08 P0000485.jpg

235 15400 Parking Garage Plumbing Riser pipe at column requires protection from damage in parking areas. This has not been provided.

PA 102

238 15400 Parking Garage Plumbing Seismic bracing has not been installed on 4" waste line in room 207 and outside of room. PA 104 P0000477.jpg

78 15400 Parking Garage Plumbing No hub 4" waste line running east and west does not have longitudinal brace. PA 109 P0000507.jpg42 15400 Parking Garage Plumbing Floor drain pipe and floor opening for pipe is inside rated corridor wall and has effected

rating of wall.PA-1.01 P0000733.jpg

43 15400 Parking Garage Plumbing Storm drain line that passes thru the shear wall has the no hub clamp inside the wall. PA-1.01 P0000728.jpg44 15400 Parking Garage Plumbing Storm drain line that passes thru the concrete shear wall shall have a pipe hanger at the

90 degree fitting.PA-1.01 P0000727.jpg

45 15400 Parking Garage Plumbing All clevis clamp hangers shall be di-chromate finished. PA-1.01 P0001134.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 57 of 154

Page 58: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

52 15400 Parking Garage Plumbing No hub clamps and fitting are embedded in CMU wall at floor line; work not in compliance with above code

PA-1.01 P0000163.jpg

135 15400 Parking Garage Plumbing Lateral brace missing for waste line at ramp. PA107 P0000420.jpg132 15400 Parking Garage Plumbing Clevis hangars are loose on waste lines. PA108 P0000450.jpg133 15400 Parking Garage Plumbing Trap primer copper lines are not wraped in felt at floor penetration. PA108 P0000451.jpg568 15400 Triple Gym Drywall/EIFS/SOFP Fire proof patch where plumbing lines and water lines under bottom flange of beam at

U.5-3AC-1.02 P0000937.jpg

431 15400 Triple Gym Fire Protection Patch fire proofing for sprinkler pipe hangers at structure 10 locations. AC 1.02 P0000823.jpg483 15400 Triple Gym Plumbing 3" plumbing pipe not supported in wall. P0000855.jpg

1375 15400 Triple Gym Plumbing Roof overflow drains exceeds max height 2" from top of roof at roof drain. One location column T & 2.

P0002188.jpg

1479 15400 Triple Gym Plumbing Storm drains incomplete until built up roofing is installed. AA1.13 P0002546.jpg443 15400 Triple Gym Plumbing Pipe insulation started but not finished above ceiling for hot water lines. AC 1.00 P0000869.jpg475 15400 Triple Gym Plumbing Hanger missing at change of direction. AC 1.02 P0000850.jpg459 15400 Triple Gym Plumbing Repair cored hole above copper line 4" below roof. AC 1.02 P0000784.jpg479 15400 Triple Gym Plumbing 1 Copper condensate and 3 copper domestic water line have not been insulated and

penetration thru CMU walls not fire rated.AC 1.02 P0000168.jpg

481 15400 Triple Gym Plumbing 2 1" Copper lines not supported at CMU wall and missing hangers at change of direction. AC 1.02 P0000850.jpg

466 15400 Triple Gym Plumbing A 3/4" and 2 1/2" copper line penetrations CMU walls shall be fire stopped. 3 Penetration 1-3/4" 2-2 1/2". See note on G-1.

AC 1.02 P0000786.jpg

438 15400 Triple Gym Plumbing Strom drain line at East wall does not have vertical or horizontal supports installed. AC 1.02 P0000883.jpg449 15400 Triple Gym Plumbing Two # 4 rebar have cut thru for cored hole. AC 1.02 P0000813.jpg437 15400 Triple Gym Plumbing Copper pipes that transit from horizontal to vertical requires a hanger at the drop to

vertical at the East and West walls 4 pipes.AC 1.02 P0000883.jpg

428 15400 Triple Gym Plumbing The CMU wall at the insulated copper pipes has cracked from the beam pocket thru the cored hole down approx. 27". There is a crack at each cored hole top and bottom of cored hole. The core drill has cut the two horizontal bars.

AC 1.02 P0000899.jpg

469 15400 Triple Gym Plumbing The cored hole for the 2 1/2" copper line on the South wall has cut thru a # 1 vertical bar. AC 1.02 P0000786.jpg

472 15400 Triple Gym Plumbing Patch fire proofing for pipe hangers. AC 1.02 P0000776.jpg432 15400 Triple Gym Plumbing Fiberglass insulated copper line requires hanger at change of direction. AC 1.02 P0000891.jpg574 15400 Triple Gym Plumbing Protection shields required for foam insulation on condensate drain line. AC-1.00 P0000869.jpg495 15400 Triple Gym Plumbing Roof vent at V1-5.1 location left open seal weather proofing required. AC-1.02 P0000926.jpg496 15400 Triple Gym Plumbing 3/4" Domestic water line is not isolated at ceiling furring hat channel at V1-5.1 AC-1.02 P0000926.jpg497 15400 Triple Gym Plumbing 1) 3/4" Domestic water line penetration and R.D.& O.F. penetration at CMU wall not fire

stopped. 2) 3/4" domestic water line drop not attached to wall. 3) Vent penetration at deck no fire stopped or sealed at location 5.1-V1.

AC-1.02 P0000926.jpg

494 15400 Triple Gym Plumbing 1) 3/4" Domestic water line above ceiling not fire stopped at CMU wall. 2) Vertical drop of 3/4" Domestic water line is not attached to wall.

AC-1.02 P0000932.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 58 of 154

Page 59: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

567 15400 Triple Gym Plumbing Plumbing line floor penetrations is not fire stopped at V.1-4.3 plumb line vertical drop at CMU wall is not attached at wall.

AC-1.02 P0000933.jpg

577 15400 Triple Gym Plumbing 8 Insulated penetration an 6 copper line penetrations not fire stopped. AC-1.02 P0000796.jpg

541 15400 Triple Gym Plumbing 1" Water line tight against ceiling studs. Isolation of copper line required. AC-1.02 P0000826.jpg528 15400 Triple Gym Plumbing 2 Cored 5" diameter holes one on North and the other on South walls. - #5 vertical rebar

cut by hole coring process.AC-1.02 P0000835.jpg

531 15400 Triple Gym Plumbing 6 Plumbing line CMU wall penetrations not fire stopped, - 3 at North wall and 3 at South wall. Note O.D. R.D. and water line.

AC-1.02 P0000835.jpg

559 15400 Triple Gym Plumbing domestic water line hanger rod in contact with sprinkler line at X.2-3.6. No 1" clearence around fire sprinkler line provided.

AC-1.02 P0000785.jpg

557 15400 Triple Gym Plumbing 1) Roof drain is not properly supported East end of bldg. 2) Roof drain is not properly supported West side of bldg. Hangers are not installed for those conditions.

AC-1.02 P0000782.jpg

491 15400 Triple Gym Plumbing 2 Insulated plumbing lines not centered, fire safeing. AC-1.02 P0000789.jpg1362 15400 Triple Gym Plumbing Roof and overflow drain missing basket. AC-1.02 P0002190.jpg1448 15400 Triple Gym Plumbing Retest all underground plumbing, typical. AC1.01 P0002150.jpg1436 15400 Triple Gym Plumbing Vertical piping not installed from floor to roof for roof and overflow drain. (2 total). AC1.01 P0002152.jpg1466 15400 Triple Gym Plumbing Underground roof drain piping not installed. Vertical overflow and drain pipe not

installed from rough grade to roof.AC1.01 P0002152.jpg

2075 15400-15010 Academy Houses Plumbing Copper lines in walls have not been insulated from other crafts with felt. AB2-1.03 P0001843.jpg85 15400/15300 Parking Garage Fire Protection Vent line obstructing sprinkler head for fire protection. AA 1.08 P0000492.jpg

2088 15480 Academy Houses HVAC and Temperature Control Systems Hydronic water lines seismic longitudinal sway bracing not installed at East wall. AB2-1.03 P0001823.jpg

822 15500 Academy Houses HVAC and Temperature Control Systems Access damper doors at exhaust air, supply air, return air are not installed. AB4-1.01 P0001145.jpg

862 15500 Academy Houses Plumbing Remove erection aid which is welded to pipe. AB4-1.01 P0001124.jpg285 15500 Parking Garage HVAC and Temperature Control Systems Drip pan under condenser not installed, no drain lines, no floor sink. AA-1.06 P0002517.jpg

224 15500 Parking Garage HVAC and Temperature Control Systems 6" hydronic water lines not braced at wall and beam. AA-1.07 P0000379.jpg

31 15500 Parking Garage HVAC and Temperature Control Systems No expansion joint installed on hydronic water line. PA-1.02 P0000687.jpg

3112 15500-07270 Academy Houses HVAC and Temperature Control Systems Insulation on refrigerant condensation line incomplete and lines not fire stopped at rated wall penetration.

AB3-1.02 P0001482.jpg

974 15509-01500 Academy Houses Electrical (School) / General Contracting Temp. lighting: 1) Temp. light fixtures in attics. 2) Temp light J box, J box support, non plenum rated wire (romex). 3) Non plenum rated wire thru rated walls. 27 rooms total.

AB4-1.01-1.02-1.03

P0001429.jpg

2356 15650 Academy Houses HVAC and Temperature Control Systems Insulation incomplete on refrigerant condensation lines. AB2-1.01 P0001655.jpg

9017 15650 Administration HVAC and Temperature Control Systems AC units seismic strap Tek screws are not used per detail. Total of 19 AC units. AE-1.03 P0002214.jpg

944 15725 Academy Houses Electrical (School) Attic area TV open J boxes with wires not landed, one 5 by 5 box at each room for total of three.

AB4-1.02 P0001401.jpg

276 15800 Parking Garage HVAC and Temperature Control Systems Seismic bracing on 10" duct passing under hydronic water line must be seismically braced per spec above.

AA-1.04 P0000579.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 59 of 154

Page 60: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

295 15800 Parking Garage HVAC and Temperature Control Systems 10" round duct not seismically braced per spec above. AA-1.05 P0000579.jpg

467 15800 Triple Gym HVAC and Temperature Control Systems Fire caulk HVAC duct penetrations at CMU walls on East and South walls. Note: See sheet G-1 plan legend and notes.

AC 1.02 P0000788.jpg

460 15800 Triple Gym HVAC and Temperature Control Systems Opening around HVAC ducts have not been weather proofed at penetration thru CMU wall.

AC 1.02 P0000784.jpg

6000 15850 Academy Houses HVAC and Temperature Control Systems AC unit anchorage at bottom foot print frame to metal stud curb not completed per submittal # 15850.13 sheets 22593.2A & 25A. (1/4 dia Tek screws 3 at each side.)

AB1-1.04 P0002214.jpg

1400 15850 Academy Houses HVAC and Temperature Control Systems AC units seismic tie down straps Tek screws not proper size per submittal 15850.13 sheets 22593-2A & 25A.

AB1-2-3-4/1.04

P0002171.jpg

5002 15850 Academy Houses HVAC and Temperature Control Systems AC unit anchorage at bottom foot print frame to metal stud curb not completed per submittal # 15850.13 sheets 22593.2A & 11A. (1/4 dia Tek screws 3 at each side.)

AB1-2-3-4/1.04

P0002359.jpg

1399 15850 Academy Houses HVAC and Temperature Control Systems AC unit frame bottom anchorage to metal stud curb not completed per submittal # 15850.13 sheets 22593.2A & 11A. (1/4 dia Tek screws 3 at each side required.)

AB1-2-3-4/1.04

5004 15850 Academy Houses HVAC and Temperature Control Systems AC unit anchorage at bottom foot print frame to metal stud curb not completed per submittal # 15850.13 sheets 22593.2A & 11A. (1/4 dia Tek screws 3 at each side.)

AB2-1.04 P0002359.jpg

6001 15850 Academy Houses HVAC and Temperature Control Systems AC unit anchorage at bottom foot print frame to metal stud curb not completed per submittal # 15850.13 sheets 22593.2A & 25A. (1/4 dia Tek screws 3 at each side.)

AB2-1.04 P0002214.jpg

5003 15850 Academy Houses HVAC and Temperature Control Systems AC unit anchorage at bottom foot print frame to metal stud curb not completed per submittal # 15850.13 sheets 22593.2A & 11A. (1/4 dia Tek screws 3 at each side.)

AB3-1.04 P0002359.jpg

6002 15850 Academy Houses HVAC and Temperature Control Systems AC unit anchorage at bottom foot print frame to metal stud curb not completed per submittal # 15850.13 sheets 22593.2A & 25A. (1/4 dia Tek screws 3 at each side.)

AB3-1.04 P0002214.jpg

853 15850 Academy Houses HVAC and Temperature Control Systems Round ducts are not supported properly at smoke fire dampers. AB4-1.01 P0001130.jpg

792 15850 Academy Houses HVAC and Temperature Control Systems Spun aluminum relief ventilator not installed. AB4-1.03 P0001348.jpg

5005 15850 Academy Houses HVAC and Temperature Control Systems AC unit anchorage at bottom foot print frame to metal stud curb not completed per submittal # 15850.13 sheets 22593.2A & 11A. (1/4 dia Tek screws 3 at each side.)

AB4-1.04 P0002359.jpg

1398 15850 Administration HVAC and Temperature Control Systems The screws that are used to attach the air handler support curb to the building curb are the incorrect size and not completed per submittal 15850.13 sheets 22593-2A & 11A. (1/4 dia Tek screws 3 on each side required). Change 5002, 5003, 5004, and 5005.

AE1.03 P0002359.jpg

1397 15850 Administration HVAC and Temperature Control Systems AC units seismic tie down straps Tek screws are not proper size per submittal 15850.13 sheets 2 2593-2A-25A.

AE1.03 P0002214.jpg

1469 15850 Triple Gym HVAC and Temperature Control Systems The Tek screws used to hold the air handler to its base are the incorrect size, and have not been installed as required by the submitalls.

AC1.01 P0002121.jpg

1369 15850 Triple Gym HVAC and Temperature Control Systems Tek screws for AC units to base framing and seismic strap of AC to base not correct size. AC1.01 P0002171.jpg

1472 15850 Triple Gym HVAC and Temperature Control Systems At AC units total of 3 Tek screw use for anchorage are not correct size per curb flashing detail noted.

SC1.03 P0002099.jpg

1473 15850 Triple Gym HVAC and Temperature Control Systems One AC unit Tek screw used for anchorage are not correct size. SC1.03 P0002099.jpg

39 15850/15050 Parking Garage HVAC and Temperature Control Systems Hanger missing at shut off valve. Work not done to spec section 15050 and pipe not identified.

AA-1.01 P0000722.jpg

894 15870 Academy Houses HVAC and Temperature Control Systems Relief air grille duct is not laterally and seismically braced in both rooms. AB4-1.01 P0001068.jpg

3092 15880 Academy Houses Drywall/EIFS/SOFP Openning for exhaust air duct has not been framed at South wall. AB3-1.03 P0001484.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 60 of 154

Page 61: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

2058 15880 Academy Houses Electrical (School) 13 Smoke detectors on return air ducts not hooked to power and covers not installed. AB2-1.03 P0001787.jpg3103 15880 Academy Houses Electrical (School) 11 Smoke detectors not wired to power source. AB3-1.03 P0001516.jpg3104 15880 Academy Houses Electrical (School) 4 Covers not installed over smoke detectors. AB3-1.03 P0001517.jpg

912 15880 Academy Houses HVAC and Temperature Control Systems Remove all unused HVAC hanger straps. P0000979.jpg

5030 15880 Academy Houses HVAC and Temperature Control Systems Flex duct not installed strap not attached to the rigid duct. AB1-1.02 P0002090.jpg

5076 15880 Academy Houses HVAC and Temperature Control Systems Access doors not installed at smoke/fire dampers. AB1-1.02 P0001233.jpg

5106 15880 Academy Houses HVAC and Temperature Control Systems Duct work in shaft incomplete. AB1-1.03 P0001950.jpg

2459 15880 Academy Houses HVAC and Temperature Control Systems Round duct is not fire caulked at corridor fire wall, 4 locations. AB2-.101 P0001123.jpg

2443 15880 Academy Houses HVAC and Temperature Control Systems 11 Smoke/fire damper access doors are not installed. AB2-.101 P0001233.jpg

2445 15880 Academy Houses HVAC and Temperature Control Systems 6 Bird screens at return air ducts are not installed. AB2-.101 P0001404.jpg

2334 15880 Academy Houses HVAC and Temperature Control Systems Damper restraining angles have not been installed also bird screens have not been installed.

AB2-1.01 P0001723.jpg

2163 15880 Academy Houses HVAC and Temperature Control Systems Bird screens are not installed at air ducts, exhaust duct is not secured in wall. AB2-1.01-1.02-1.03

P0001586.jpg

2336 15880 Academy Houses HVAC and Temperature Control Systems Duct is not anchored to wall framing and does not protrude into room to receive the bird screen.

AB2-1.02 P0001719.jpg

2344 15880 Academy Houses HVAC and Temperature Control Systems No access door to smoke/fire damper. AB2-1.02 P0001233.jpg

2347 15880 Academy Houses HVAC and Temperature Control Systems Bird screen is not installed on return air duct. AB2-1.02 P0001404.jpg

2021 15880 Academy Houses HVAC and Temperature Control Systems Access panel and door for smoke fire damper are not installed. AB2-1.03 P0001233.jpg

2089 15880 Academy Houses HVAC and Temperature Control Systems Access door to smoke/fire damper not installed. AB2-1.03 P0001821.jpg

2226 15880 Academy Houses HVAC and Temperature Control Systems Damper restraining angles have not been installed. AB2-1.03 P0001781.jpg

2239 15880 Academy Houses HVAC and Temperature Control Systems Duct retaining angles are not installed at four locations. AB2-1.03 P0001749.jpg

2068 15880 Academy Houses HVAC and Temperature Control Systems Damper has not been properly supported. AB2-1.03 P0001827.jpg

2057 15880 Academy Houses HVAC and Temperature Control Systems 19 Access doors in above rooms access smoke/fire dampers not installed. AB2-1.03 P0001233.jpg

2059 15880 Academy Houses HVAC and Temperature Control Systems Bird sceens on return air ducts not installed. AB2-1.03 P0001404.jpg

3199 15880 Academy Houses HVAC and Temperature Control Systems Exhaust aur duct has not been properly set through wall. Bird screen can not be installed. AB3-1.0 P0001460.jpg

3090 15880 Academy Houses HVAC and Temperature Control Systems Bird screen missing on supply air duct. AB3-1.0 P0001512.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 61 of 154

Page 62: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

3297 15880 Academy Houses HVAC and Temperature Control Systems Defusers not installed in ceiling grid and flex duct to defusers incomplete. AB3-1.01 P0001032.jpg

3308 15880 Academy Houses HVAC and Temperature Control Systems Smoke fire dampers do not have retaining angles installed at the riser shaft, 3 dampers. AB3-1.01 P0001396.jpg

3295 15880 Academy Houses HVAC and Temperature Control Systems Remove all unused HVAC hanger straps. AB3-1.01 P0000979.jpg

3315 15880 Academy Houses HVAC and Temperature Control Systems Exhaust air duct does not extend past wall. The flanges at the end of duct are set inside of wall.

AB3-1.01 P0001402.jpg

3292 15880 Academy Houses HVAC and Temperature Control Systems Bird screens have not been attached to return air ducts at a total of five. AB3-1.01 P0001404.jpg

3211 15880 Academy Houses HVAC and Temperature Control Systems Supply and return air defusers not installed (total of 18). AB3-1.01 P0001105.jpg

3294 15880 Academy Houses HVAC and Temperature Control Systems 10 Access door to smoke fire dampers have not been installed. AB3-1.01 P0001233.jpg

3305 15880 Academy Houses HVAC and Temperature Control Systems The South smoke fire damper on the West wall has been installed in the inverted position. The retaining angles for both dampers are not tight to wall. Boxes in room 105 have pushed dampers into room.

AB3-1.01 P0001371.jpg

3206 15880 Academy Houses HVAC and Temperature Control Systems A) No access doors installed at smoke fire dampers. B) In rooms; 219-215-213 bird screen on return air ducts not installed.

AB3-1.02 P0001233.jpg

3111 15880 Academy Houses HVAC and Temperature Control Systems Retaining angel not screwed to dampers. AB3-1.02 P0001480.jpg

3188 15880 Academy Houses HVAC and Temperature Control Systems Exhaust air register is not installed and exhaust air duct penetration thru fire rated wall is not fire stopped at East wall.

AB3-1.02 P0001427.jpg

3110 15880 Academy Houses HVAC and Temperature Control Systems Strap around round duct to be relocated to allow gypsum installation at rated wall. AB3-1.02 P0001482.jpg

3122 15880 Academy Houses HVAC and Temperature Control Systems 1) Grills over doors 304-303 2) Exhaust air grills in Janitor Room not installed. AB3-1.03 P0001483.jpg

3108 15880 Academy Houses HVAC and Temperature Control Systems One access door to smoke/fire damper missing in Room 319 and in Work Room 326. AB3-1.03 P0001233.jpg

3105 15880 Academy Houses HVAC and Temperature Control Systems 5 Bird screens not installed to return air ducts in above rooms. AB3-1.03 P0001404.jpg

3093 15880 Academy Houses HVAC and Temperature Control Systems Exhaust air duct does not protrude into room. Bird screen cannot be installed. AB3-1.03 P0001484.jpg

908 15880 Academy Houses HVAC and Temperature Control Systems Remove all unused HVAC hanger straps. AB4-1.01 P0000953.jpg

591 15880 Academy Houses HVAC and Temperature Control Systems Bird sceens have not been installed at supply and exhaust air ducts. Exhaust air duct does not extend into room enough.

AB4-1.02 P0001276.jpg

595 15880 Academy Houses HVAC and Temperature Control Systems Damper angles are not installed at smoke / fire damper on East wall. AB4-1.02 P0001276.jpg

596 15880 Academy Houses HVAC and Temperature Control Systems Fire damper has been installed in the inverted position. AB4-1.02 P0000335.jpg

626 15880 Academy Houses HVAC and Temperature Control Systems No access doors to smoke fire dampers. AB4-1.02 P0001233.jpg

782 15880 Academy Houses HVAC and Temperature Control Systems Exhaust air duct in room is too close to East rated wall and is effecting the rating. AB4-1.03 P0001339.jpg

676 15880 Academy Houses HVAC and Temperature Control Systems Smoke/fire dampers not installed in rated fire wall for flex duct. AB4-1.03 P0001376.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 62 of 154

Page 63: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

811 15880 Academy Houses HVAC and Temperature Control Systems Damper angles have not been installed for smoke damper. AB4-1.03 P0001342.jpg

803 15880 Academy Houses HVAC and Temperature Control Systems 12 by 6 grill is not installed above door 303. AB4-1.03 P0001328.jpg

748 15880 Academy Houses HVAC and Temperature Control Systems Supply air defuser not installed. AB4-1.03 P0001105.jpg

750 15880 Academy Houses HVAC and Temperature Control Systems Supply air defuser not installed. AB4-1.03 P0001105.jpg

985 15880 Academy Houses HVAC and Temperature Control Systems Attic fire rated walls fire damper retaining angles not installed; room 304-3 locations, 310-2 locations, 320-2 locations, 328-4 locations. 11 total.

AB4-1.03 P0001233.jpg

986 15880 Academy Houses HVAC and Temperature Control Systems Fire dampers not installed in fire rated walls, 4 locations, room 328. AB4-1.03

752 15880 Academy Houses HVAC and Temperature Control Systems Supply and return air defusers not installed. AB4-1.03 P0001105.jpg

769 15880 Academy Houses HVAC and Temperature Control Systems Supply and return air defusers not installed. AB4-1.03 P0001105.jpg

9040 15880 Administration HVAC and Temperature Control Systems AC heating ducts incomplete: Horizontal rectangular ducts at shaft to AC 3-4-5. AE-1.02 P0002319.jpg

9039 15880 Administration HVAC and Temperature Control Systems Exhaust ducts incomplete at Bathrooms for 16" round from column line B.5-2 to B.5-3.5. AE-1.02 P0002325.jpg

9037 15880 Administration HVAC and Temperature Control Systems Horizontal duct runs installed but no drops to ceilings. Typical and no ducts to roof at corridor # 220. 2 Locations.

AE-1.02 P0002315.jpg

9087 15880 Administration HVAC and Temperature Control Systems Ducts not installed thru wall at B.5 including dampers, 2 locations. Also opening thru masonry at wrong height.

AE-1.02 P0002300.jpg

9035 15880 Administration HVAC and Temperature Control Systems HVAC ducts incomplete, typical: Drops from horizontal ducts to ceilings not installed. AE-1.02 P0002315.jpg

17 15880 Parking Garage HVAC and Temperature Control Systems Drilled in anchors need tension or torque testing. AA-1.03 P0000003.jpg

477 15880 Triple Gym Electrical (School) 3 Supply air ducts have not been insulated and insulation does not pass thru masonry walls.

AC 1.02 P0000870.jpg

451 15880 Triple Gym HVAC and Temperature Control Systems Fire dampers have not been installed at rated wall for supply and return air ducts at South wall.

AC 1.00 P0000842.jpg

429 15880 Triple Gym HVAC and Temperature Control Systems Patch fire proofing at duct hanger and bend clamp retainer strap around beam flange. AC 1.02 P0000913.jpg

436 15880 Triple Gym HVAC and Temperature Control Systems Insulation has not been installed thru the CMU wall. AC 1.02 P0000870.jpg

539 15880 Triple Gym HVAC and Temperature Control Systems 1) Access not provide for emerg. fire dampers at line V.5 North wall 2) Air supply to room not complete.

AC-1.02 P0000851.jpg

527 15880 Triple Gym HVAC and Temperature Control Systems 2 Round duct penetrations on South CMU wall and 1 Round duct penetration on North CMU wall are not fire safed.

AC-1.02 P0000858.jpg

1428 15880 Triple Gym HVAC and Temperature Control Systems Water heater combustion air duct thru roof incomplete and missing bird screen. AC1.02 P0002192.jpg

3230 15970 Academy Houses HVAC and Temperature Control Systems Thermostat controls and temperature control system not installed, all rooms, all floors. AB3-1.01-1.02-1.03

P0001011.jpg

926 15970 Academy Houses HVAC and Temperature Control Systems Attic area AC controls. Room 317, 1-4s box open with no wires. Room 319, 1-5s box wires not landed, no cover and 1-4s box open with wires not landed.

AB4-1.03 P0001455.jpg

850 16000 Academy Houses Electrical (School) Exposed rebar used to hold conduit apart. P0001169.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 63 of 154

Page 64: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

887 16000 Academy Houses Electrical (School) 4" Conduit run tight up against duct (gap not provided) at entrance to room at S.2-5.6. P0001031.jpg893 16000 Academy Houses Electrical (School) Remove 1 1/2" black iron channel that is not being used at the South corner of the room. AB4-1.01

815 16000 Academy Houses Electrical (School) Per electrical detail, fire rated plywood is required to be installed on the East wall of all electrical rooms for tele/data purposes. This has not been done.

AB4-1.01

913 16000 Academy Houses Electrical (School) Hole in telecom box, near West wall. AB4-1.01 P0000974.jpg896 16000 Academy Houses Electrical (School) 3" deck penetration has been left open. Fire stopping required. AB4-1.01 P0001040.jpg888 16000 Academy Houses Electrical (School) Light fixture support wires do not have tight turns, shall be as close to vertical as possible

and shall not have excessive slack.AB4-1.01 P0001041.jpg

854 16000 Academy Houses Electrical (School) Light fixture has not been seismically braced. AB4-1.01 P0001129.jpg408 16000 Parking Garage Electrical (Parking) 4s Box embedded in column is too close to the exit door and the sprinkler risers will

interfere with the store light.AA 1.01 P0000748.jpg

410 16000 Parking Garage Electrical (School) Electrical box on ceiling conduit hole must be closed off in box. AA 1.01 P0000741.jpg409 16000 Parking Garage Electrical (School) All surface mounted outlet boxes shall be cast not pressed in all exposed areas this

includes the corridors on all levels.AA 1.01-1.04-1.07

377 16000 Parking Garage Electrical (School) Conduit not completed at deck edge. AA 1.02 P0000753.jpg349 16000 Parking Garage Electrical (School) Conductor hanging from box between concrete column and CMU batt melt. AA 1.03 P0000534.jpg383 16000 Parking Garage Electrical (School) 2S box is out of plumb and deep set in CMU wall for exit light. AA 1.05 P0000661.jpg407 16000 Parking Garage Electrical (School) Illumination from ceiling fixtures restricted by sprinkler pipe. AA 1.07 P0000757.jpg361 16000 Parking Garage Electrical (School) Outlet boxes 3 each have not been ID. AA 103 P0000765.jpg341 16000 Parking Garage Electrical (School) Conduit is rusting at floor behind door P 106. AA 103340 16000 Parking Garage Electrical (School) All exposed outlet boxes are required to be cast. Photo 706 is for power to flow + tamper

on shear wall. 708 mounted on East wall near door. P106 709 under stair on CMU wall.AA 103 P0000706.jpg

71 16000 Parking Garage Electrical (School) Square penetrations thru communication room wall have not been fire stopped. AA 107 P0000528.jpg354 16000 Parking Garage Electrical (School) Tamper proof screws should be used on conduit in stairwell and the center unistrut has

not been anchored.AA 109 P0000681.jpg

298 16000 Parking Garage Electrical (School) Light fixtures not inspected for proper installation. AA-1.04420 16000 Parking Garage Electrical (School) Outlet box for fire alarm is too close to drain for sprinkler system and should be a cast

box or waterproof box.AA1.01 P0000743.jpg

338 16000 Parking Garage Electrical (School) CMU wall is partly covering round outlet box for home run. P 106 P0000712.jpg448 16000 Triple Gym Electrical (School) Conduit not completed in room 7 places. AC 1.00 P0000839.jpg427 16000 Triple Gym Electrical (School) Two inch conduit that runs East & West just South of U line near rooms 134-135 clamps

have been removed at unistrut and conduit requires longitudinal brace.EC 1.02 P0000927.jpg

2234 16010 Academy Houses Electrical (School) Conduit penetrations thru sleeved holes in deck are not supported to wall for electrical power panels.

AB2-1.02-1.03

P0001744.jpg

2060 16010 Academy Houses Electrical (School) Flex with conductors for future case work, conductors not landed, no green conductor, 2 locations total.

AB2-1.03 P0001435.jpg

2240 16010 Academy Houses Electrical (School) Corridor fire rated walls incomplete at wall mounted electrical outlets, 2 locations total. Membrane penetrations exceed code maximum.

AB2-1.03

2066 16010 Academy Houses Electrical (School) Flex with conductors for future case work, conductors not landed, no green conductor, 1 location.

AB2-1.03 P0001435.jpg

2065 16010 Academy Houses Electrical (School) Where conductors pulled to wall mounted boxes some have no grounding conductor (green) at about 45 locations.

AB2-1.03 P0001802.jpg

2061 16010 Academy Houses Electrical (School) Typical all areas; attic electrical conduit supports screwed to bottom of roof deck flute and not to side.

AB2-1.03 P0001836.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 64 of 154

Page 65: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

3229 16010 Academy Houses Electrical (School) Coax cable pulled into 4S box have not been landed, cover missing, and box not identified.

AB3-1.01 P0001030.jpg

3265 16010 Academy Houses Electrical (School) Trapeze hanger rod and end of unistrut support for conduit rack terminated inside of framed gypsum board wall not per plan.

AB3-1.01 P0001379.jpg

3210 16010 Academy Houses Electrical (School) Recepticals not installed in tiled walls. AB3-1.01 P0001107.jpg3279 16010 Academy Houses Electrical (School) Conduit screw connector is disconnected at the Southeast corner of the room. AB3-1.01 P0001380.jpg3218 16010 Academy Houses Electrical (School) Hole chipped into slab to move conduit into wall not repaired and damaged day wall not

repaired.AB3-1.01 P0001433.jpg

3118 16010 Academy Houses Electrical (School) Conduit and boxes attached to metal deck above ceiling wires pulled, no ID on boxes. AB3-1.02 P0001470.jpg3201 16010 Academy Houses Electrical (School) 5 Gray tel-com boxes, no wire or cable pulled, cover plates not installed and boxes are

not identified.AB3-1.02 P0000972.jpg

3120 16010 Academy Houses Electrical (School) 5 Gray tel-com boxes, no cable or wire pulled, no covers and no ID on boxes. AB3-1.02 P0000972.jpg3119 16010 Academy Houses Electrical (School) A) Gray tel-com box cable pulled no lid, no ID on box. B) Tel-com no cable, no cover,

no ID on box.AB3-1.02 P0001171.jpg

3099 16010 Academy Houses Electrical (School) 3 - 2" Conduit runs above ceiling incomplete. AB3-1.03 P0000967.jpg3100 16010 Academy Houses Electrical (School) Conduit and boxes attached to metal deck wires pulled, no cover and no ID on boxes

(40).AB3-1.03 P0001470.jpg

3035 16010 Academy Houses Electrical (School) 2-Electrical conduit over door 311.1, no expansion joint provided. AB3-1.03 P0001576.jpg639 16010 Academy Houses Electrical (School) 5-S Electrical box conductors pulled and no cover plate provided, flex conduit

conductors pulled, not connected.AB4-1.0 P0001267.jpg

830 16010 Academy Houses Electrical (School) All tel-com panels not identified. AB4-1.01 P0001155.jpg962 16010 Academy Houses Electrical (School) 4 by 4 Electrical J box open with wires not landed. AB4-1.02 P0001215.jpg650 16010 Academy Houses Electrical (School) 4-S, 2-S box over door 202, cable pulled not landed at 4-S box and conductors not pulled

at 2S box.AB4-1.02 P0001254.jpg

622 16010 Academy Houses Electrical (School) Motor controls for smoke fire dampers not installed and covers have not been installed. AB4-1.02 P0001259.jpg966 16010 Academy Houses Electrical (School) One open 5 by 5 J box attic area; wires not landed cover not installed. AB4-1.02 P0001215.jpg759 16010 Academy Houses Electrical (School) Hand dryers not installed. AB4-1.03 P0001104.jpg741 16010 Academy Houses Electrical (School) Recepticals not installed in boxes in tiled walls. AB4-1.03 P0001107.jpg682 16010 Academy Houses Electrical (School) Wires not pulled thru conduit into boxes on metal ceiling. AB4-1.03 P0000857.jpg742 16010 Academy Houses Electrical (School) Speaker not installed in box in hard ceiling. AB4-1.03 P0001105.jpg938 16010 Academy Houses Electrical (School) Smoke dampers typical all rooms, hook up to power source incomplete, 32 locations

total.AB4-1.03 P0001024.jpg

738 16010 Academy Houses Electrical (School) Flex conduit with conductors pulled for future case work. AB4-1.03 P0001195.jpg740 16010 Academy Houses Electrical (School) Light fixture in hard ceiling not installed. AB4-1.03 P0001105.jpg683 16010 Academy Houses Electrical (School) Conduit runs above ceiling incomplete. AB4-1.03 P0000967.jpg755 16010 Academy Houses Electrical (School) Recepticles not installed in tiled walls. AB4-1.03 P0001107.jpg768 16010 Academy Houses Electrical (School) Recepticals not installed in tiled wall. AB4-1.03 P0001107.jpg729 16010 Academy Houses Electrical (School) Conduit runs above ceiling incomplete. AB4-1.03 P0000967.jpg722 16010 Academy Houses Electrical (School) A) Tel-com box cable pulled ID on box. B) Tel-com boxes no wire pulled and box not

ID.AB4-1.03 P0000971.jpg

754 16010 Academy Houses Electrical (School) Motion detector not installed. AB4-1.03 P0001104.jpg671 16010 Academy Houses Electrical (School) Gutter tray under computer counter has no coax cable or conductor runs for unintrupted

power system.AB4-1.03 P0000995.jpg

744 16010 Academy Houses Electrical (School) Light fixtures in hard ceiling not installed. AB4-1.03 P0001105.jpg745 16010 Academy Houses Electrical (School) Speaker not installed in box in hard ceiling. AB4-1.03 P0001105.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 65 of 154

Page 66: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

766 16010 Academy Houses Electrical (School) Speaker not installed in box in ceiling. AB4-1.03 P0001105.jpg760 16010 Academy Houses Electrical (School) Light fixtures in hard ceilings not installed. AB4-1.03 P0001105.jpg756 16010 Academy Houses Electrical (School) Speaker in box in hard ceiling not installed. AB4-1.03 P0001105.jpg991 16010 Academy Houses Electrical (School) Fire rated wall thru penetrations not fire caulked, about 310 locations for conduits for

power TV, etc.AB4-1.03 P0001121.jpg

747 16010 Academy Houses Electrical (School) Recepticals not installed in boxes in tiled walls . AB4-1.03 P0001107.jpg3324 16010 Academy Houses Toilet Partitions and Accessories Hand dryers not installed. 12 Total. AB3-1.01 P0001104.jpg9099 16010 Administration Electrical (School) No conductors, no pull strings, typical. AE-1.029100 16010 Administration Electrical (School) No conductors or J boxes installed at walls, typical. AE-1.02 P0002309.jpg9102 16010 Administration Electrical (School) Where conduits and J boxes have been installed, black iron hanger screwed to bottom of

deck and not to side of flute, typical. Column line A.8 to D and 2 to 4.2.AE-1.02 P0002211.jpg

9044 16010 Administration Electrical (School) Overhead electrical piping and racks, fire proofing not patched, about 50 locations. AE-1.02 P0002274.jpg336 16010 Parking Garage Electrical (School) PVC conduit broken off at column @ W-1.5 AA 1.03 P0000719.jpg254 16010 Parking Garage Electrical (School) Wiring for fight fixtures not inspected or accepted prior to placement Of 12 light fixtures

in room.AA 1.05 P0002534.jpg

253 16010 Parking Garage Electrical (School) Wiring for light fixtures not inspected or accepted prior to placement of 4 light fixtures in corridor.

AA 1.05 P0002537.jpg

54 16010 Parking Garage Electrical (School) Conduit through wall not fire safed per code above. AA-1.01 P0000544.jpg58 16010 Parking Garage Electrical (School) Conductors not pulled into boxes in walls and ceiling. AA-1.01 P0000523.jpg

331 16010 Parking Garage Electrical (School) Box rusted in concrete from flooding in loading dock area. AA-1.03 P0000171.jpg19 16010 Parking Garage Electrical (School) 1) all drilled anchors for light fixtures shall be tension or torque tested per above code. 2)

conductor guard over light fixture missing.AA-1.03 P0000738.jpg

284 16010 Parking Garage Electrical (School) 1" conduit and unistrut not secured to wall. AA-1.06 P0000582.jpg186 16010 Parking Garage Electrical (School) Conduit thru wall not fire safed thru CMU wall. AA-1.07 P0000386.jpg188 16010 Parking Garage Electrical (School) Conduit not sleeved or fire safed between fan room and generator room. AA-1.07 P0000386.jpg189 16010 Parking Garage Electrical (School) Conduit penetration not fire safed between fan room and generator room. AA-1.07 P0000386.jpg211 16010 Parking Garage Electrical (School) Drilled anchors for distribution transformer not torqued. AA-1.07 P0002508.jpg200 16010 Parking Garage Electrical (School) Conductor not pulled into all boxes. AA-1.07 P0000389.jpg206 16010 Parking Garage Electrical (School) Panels not covered. AA-1.07 P0000440.jpg229 16010 Parking Garage Electrical (School) 2 1/2" conduit not sleeved and not spaced at 3 diameters on center at top of wall. AA-1.07 P0000370.jpg544 16010 Triple Gym Electrical (School) 8 by 8 elec. panel at V.6-3 1) No panel cover installed 2) Penetration of CMU sleeve for

conduit from panel is not fire stopped.AC-1.02 P0000802.jpg

517 16010 Triple Gym Electrical (School) Conduit runs in room not complete. AC-1.02 P0000868.jpg1443 16010 Triple Gym Electrical (School) Switch boxes in masonry walls, typical; no conductors, no pull strings 4" by 6" & 4" by

8" : 2 total.AC1.01 P0002138.jpg

1442 16010 Triple Gym Electrical (School) 4S boxes in masonry walls, no conductors, no pull strings. Typical, about 37 locations counted.

AC1.01 P0002138.jpg

1440 16010 Triple Gym Electrical (School) 12" by 12" Pull box mounted in masonry wall, not labeled, no conductors or pull strings. 1 Location.

AC1.01 P0002149.jpg

1437 16010 Triple Gym Electrical (School) J boxes installed in masonry walls without conductors or pull strings. 7-4S boxes total. AC1.01 P0002138.jpg4 16010/3300/9260 Parking Garage Electrical (School) Mislocated conduit in slab on grade; relocate to 2 Hr rated wall. AA-1.03 P0000164.jpg

2433 16011 Academy Houses Electrical (School) Conductors missing in boxes. AB2-1.01 P0001604.jpg545 16013 Triple Gym Electrical (School) Black channel attached to roof deck connected incorrectly on blk channel used to support

panel at V.6-3 location. Note attahment of channel at top hat of deck screwed in to roofAC-1.02 P0000802.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 66 of 154

Page 67: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

5081 16020 Academy Houses Electrical (School) Wall plugs column line C.7, no grounding wire (green) pulled with power conductors, typical 5 locations.

AB1-1.02 P0001804.jpg

2148 16050 Academy Houses Electrical (School) Opening in Dens-glass wall for an outlet box. Does not have box installed. AB2-1.02 P0002001.jpg2465 16050 Academy Houses Electrical (School) About 10 conduits pass thru fire rated wall at two locations are not caulked. AB2-1.02 P0001615.jpg1060 16050 Academy Houses Electrical (School) Cover plate over box not installed. AB2-1.043285 16050 Academy Houses Electrical (School) Electrical box and switches have not been installed. AB3-1.01 P0001412.jpg3281 16050 Academy Houses Electrical (School) 2-5S boxes conductors pulled not landed, 1-4S box no conductor pulled in over head, no

covers provided.AB3-1.01 P0001079.jpg

3213 16050 Academy Houses Electrical (School) Lights not installed in hard ceilings in all restrooms (30 lights total). AB3-1.01 P0001105.jpg3219 16050 Academy Houses Electrical (School) Gray tel-com box does not have conductors pulled into box. AB3-1.01 P0000971.jpg3286 16050 Academy Houses Electrical (School) Conductor hanging out of 4S wall box, not landed. No receptical installed or cover plate

provided.AB3-1.01 P0001412.jpg

3148 16050 Academy Houses Electrical (School) Magnetic door hold open for a pair of doors (111) wires not installed, finish not set. AB3-1.01 P0001549.jpg3069 16050 Academy Houses Electrical (School) Typical all corridors, exit signs conductors not landed, exit sign not installed, 4 for each

floor for a total of twelve.AB3-1.01-1.02-1.03

P0000947.jpg

3194 16050 Academy Houses Electrical (School) 2-Electrical boxes 4-S type 1-conductors not pulled, 1-conductor pulled and hanging out of box, no covers provided over door 202.

AB3-1.02 P0001426.jpg

3191 16050 Academy Houses Electrical (School) Conduit from north wall between rooms, conductor hanging from incomplete runs into areas noted. Conduit is not complete on either side of wall.

AB3-1.02 P0001427.jpg

3209 16050 Academy Houses Electrical (School) 53 Conduits run above ceiling no wire pulled, no caps on ends and no ID. AB3-1.02 P0000967.jpg3177 16050 Academy Houses Electrical (School) 5-Electric boxes in wall conductor pulled not landed, switch and recepticals not installed

and cover plates not provided.AB3-1.02 P0001268.jpg

3015 16050 Academy Houses Electrical (School) 1-4S boxes in ceiling and 3-4S boxes in walls, conductors pulled not landed and no conductor pulled. No cover plates and no ID provided.

AB3-1.02 P0001624.jpg

3140 16050 Academy Houses Electrical (School) 5S box at West wall and North wall conductors pulled, not landed, no covers provided. AB3-1.02 P0001464.jpg3018 16050 Academy Houses Electrical (School) 2-4S boxes, conductors not pulled, 2-4S boxes conductors pulled, not landed. No cover

plates on all 4 boxes and no ID provided.AB3-1.03 P0001624.jpg

3123 16050 Academy Houses Electrical (School) 5 Electrical boxes in wall 4S and 5S conductor pulled not landed. Switch and recepticals or cover plates not provided.

AB3-1.03 P0001268.jpg

832 16050 Academy Houses Electrical (School) Box and conduit at mechanical shaft wall not complete located at N8-4.7. AB4-1.01 P0001166.jpg816 16050 Academy Houses Electrical (School) All unistrut above tele/data panels improperly secured with drywall screws. AB4-1.01 P0001158.jpg818 16050 Academy Houses Electrical (School) 4S box is mounted directly to drywall and not to studs this occurs at North wall 8' off

finish floor.AB4-1.01 P0001159.jpg

819 16050 Academy Houses Electrical (School) Two 5S boxes for tele/data are mounted directly to dry wall and not to studs. AB4-1.01 P0001160.jpg817 16050 Academy Houses Electrical (School) Outlet 4S and 5S boxes for tele/data mounted on drywall at North wall have conductors

pulled in boxes but not landed. Conduit missing between boxes.AB4-1.01 P0001165.jpg

829 16050 Academy Houses Electrical (School) All surface mounted 4S and 5S boxes shall be cast metal. AB4-1.01 P0001161.jpg828 16050 Academy Houses Electrical (School) Conduit stub out from deck incomplete, located at West wall total of 3, South wall total

of 2, East wall a total of 5.AB4-1.01 P0001126.jpg

716 16050 Academy Houses Electrical (School) Gray tel-com box cable pulled not landed. AB4-1.02 P0000971.jpg794 16050 Academy Houses Electrical (School) At 2-4S and 1-2S box conductor pulled not landed, no switch or recepticals or cover

plates provided.AB4-1.03 P0001378.jpg

348 16050 Parking Garage Electrical (School) 2-Electrical boxes on North concrete wall- conductors not pulled no fixtures installed. AA 1.03 P0000524.jpg82 16050 Parking Garage Electrical (School) Electrical system junction boxes pull boxes and receptacles require identification Room

#P311, P313, P318, P314, P315, P302, P303, P312, P301, P307, P308, P319, P317, P310, P306, P305, P304.

AA 1.07/1.08/1.09

P0002540.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 67 of 154

Page 68: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

50 16050 Parking Garage Electrical (School) Light fixture outlet box placed partially in rated wall. AA- P0000732.jpg269 16050 Parking Garage Electrical (School) Elec systems - junction boxes, pull boxes, recepticals require identification. Rooms

P201, P203, P207, P211, P213, P208, P214, P213, P216, P206, P205, P204, P210, P209AA-1.04/.05/.06

130 16050 Parking Garage Electrical (School) Junction box is not weather proof type and has not been protected from vehicle damage. AA101 P0000429.jpg77 16050 Parking Garage Electrical (School) Ceiling mounted 12" x 16" junction box is damaged. EA 109 P0000498.jpg

554 16050 Triple Gym Electrical (School) Conductor not pulled into boxes on North and East walls. 7-2 S-Boxes and 3-4-Boxes. AC-1.02538 16050 Triple Gym Electrical (School) Sleeved cored holes in West CMU wall penetration total of 6. East wall total of 7. North

wall total of 9. South wall total of 6 have not been fire stopped.AC-1.02 P0000845.jpg

529 16050 Triple Gym Electrical (School) 1-Cored 3" diameter hole at North CMU wall. 1 -#5 vertical rebar cut by coring process. AC-1.02 P0000835.jpg553 16050 Triple Gym Electrical (School) Cured hole in CMU wall at W-4.2 blank hole left void. Note: 4-S box is install at outside

of wall.AC-1.02 P0000796.jpg

7100 16050 Triple Gym Electrical (School) Receptacles not set in boxes on CMU wall. AC-1.02 P0000589.jpg526 16050/16710 Triple Gym Electrical (School) 1) Fire damper motors are not connected to power source. 2) Conductor not pulled to box

and no cover on box at North wall. 3) Conductors not pulled into box on South CMU wall and audible visual alarm not installed.

AC-1.02 P0000853.jpg

3162 16100 Academy Houses Electrical (School) All trapeze supports and light supports longer than 24" shall be sway braced. AB3-1.02 P0001451.jpg138 16100 Parking Garage Electrical (School) Weather tight box required in exposed areas. EA101 P0000428.jpg425 16100 Triple Gym Electrical (School) Two inch and three inch lines require longitudinal bracing. AC 1.00 P0000939.jpg

3175 16110 Academy Houses Drywall/EIFS/SOFP 3-2" conduit runs, 1-1 1/2" conduit run, 3-1 1/4" conduit runs require support from ceiling to conduit.

AB3-1.02 P0001452.jpg

2331 16110 Academy Houses Electrical (School) Conduit is too close to sprinkler pipe, one inch clearance required in all rooms noted. A2-1.01-1.02-1.03

P0001728.jpg

5043 16110 Academy Houses Electrical (School) Conductors missing in boxes. Boxes without cover plates and identification missing. AB1-1.02 P0001704.jpg5029 16110 Academy Houses Electrical (School) Conductors missing in boxes. Boxes set in framed walls, no ID on boxes. AB1-1.02 P0001704.jpg5050 16110 Academy Houses Electrical (School) Conductors missing in boxes. No ID on boxes. AB1-1.02 P0001704.jpg5045 16110 Academy Houses Electrical (School) Conductors missing in boxes. Boxes missing cover plates and identification. AB1-1.02 P0001697.jpg5047 16110 Academy Houses Electrical (School) 1 Box suspended from metal deck, cover plates missing and conductors have not been

pulled.AB1-1.02 P0001697.jpg

5051 16110 Academy Houses Electrical (School) Conductors missing in boxes. Boxes without cover plates or identification. AB1-1.02 P0001697.jpg5048 16110 Academy Houses Electrical (School) Gray pull box, conductors, cover plates and identification missing. AB1-1.02 P0000971.jpg5038 16110 Academy Houses Electrical (School) Conductors missing in boxes. No ID on boxes. AB1-1.02 P0001704.jpg5056 16110 Academy Houses Electrical (School) Conductors missing in boxes. Boxes missing identification. AB1-1.02 P0001704.jpg5031 16110 Academy Houses Electrical (School) 4 Conduit stubs out of deck not complete. Conductors have not been pulled and boxes

have not been identified.AB1-1.02 P0000981.jpg

5065 16110 Academy Houses Electrical (School) Conductors missing in boxes. Boxes missing cover plates and identification. AB1-1.02 P0001697.jpg5069 16110 Academy Houses Electrical (School) Boxes and conduit installed on metal deck, 4 per room, conductors pulled, cover plates

and identification missing.AB1-1.02 P0001470.jpg

5064 16110 Academy Houses Electrical (School) Conductors missing in boxes. Boxes missing identification. AB1-1.02 P0001704.jpg5055 16110 Academy Houses Electrical (School) Conductors missing in boxes. Boxes missing identification. AB1-1.02 P0001704.jpg5067 16110 Academy Houses Electrical (School) Conductors missing in boxes. Boxes missing cover plates and identification. AB1-1.02 P0001697.jpg5040 16110 Academy Houses Electrical (School) Conductors missing in boxes. Boxes over door 222-223, not identified. AB1-1.02 P0001704.jpg5041 16110 Academy Houses Electrical (School) Suspended boxes in each room, all without conductors or identification. AB1-1.02 P0001697.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 68 of 154

Page 69: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

5068 16110 Academy Houses Electrical (School) Conductors missing in boxes. Boxes missing identification. AB1-1.02 P0001704.jpg5075 16110 Academy Houses Electrical (School) Smoke/fire dampers not connected to power source, missing cover plates, 1 each rooms

221 to 216-213-212-208-202, and each Work room 225-229, 3 in room 210, 3 total.AB1-1.02 P0001024.jpg

5046 16110 Academy Houses Electrical (School) Conductors missing in boxes. Boxes missing identification. AB1-1.02 P0001704.jpg5057 16110 Academy Houses Electrical (School) Conductors missing in boxes. Boxes missing cover plates and identification. AB1-1.02 P0001697.jpg5020 16110 Academy Houses Electrical (School) 24 1" to 2" conduit in slab, 2 with wire pulled, 3 with string pulled thru, 8 4" conduit stub

thru slab all without ID.AB1-1.02 P0002085.jpg

5070 16110 Academy Houses Electrical (School) Conductors missing in boxes. Boxes missing identification. AB1-1.02 P0001704.jpg5061 16110 Academy Houses Electrical (School) Conductors missing in boxes. Boxes missing cover plates and identification. AB1-1.02 P0001697.jpg5023 16110 Academy Houses Electrical (School) Conductors missing in boxes. Cover plates and ID not provided. AB1-1.02 P0001697.jpg5062 16110 Academy Houses Electrical (School) Conductors missing in boxes. Boxes missing identification. AB1-1.02 P0001704.jpg5036 16110 Academy Houses Electrical (School) Gray pull box, conductors have not been pulled and boxes have not been identified. AB1-1.02 P0000971.jpg5052 16110 Academy Houses Electrical (School) Conductors missing in boxes. Boxes missing cover plates and identification. AB1-1.02 P0001697.jpg5060 16110 Academy Houses Electrical (School) Conductors missing in boxes. Boxes missing cover plates and identification. AB1-1.02 P0001704.jpg5063 16110 Academy Houses Electrical (School) Conductors missing in boxes. Boxes missing cover plates and identification. AB1-1.02 P0001697.jpg5044 16110 Academy Houses Electrical (School) Conductors missing in boxes. Boxes missing identification. AB1-1.02 P0001704.jpg5093 16110 Academy Houses Electrical (School) 2 Gray pull boxes, no conductors, cover plates or identification provided. AB1-1.03 P0000971.jpg5095 16110 Academy Houses Electrical (School) Gray pull box, no conductors, cover plates or identification provided. AB1-1.03 P0000971.jpg5094 16110 Academy Houses Electrical (School) Gray pull box, no conductors, cover plates or identification provided. AB1-1.03 P0000971.jpg5092 16110 Academy Houses Electrical (School) Gray pull box, no conductors, no cover plates provided and no identification. AB1-1.03 P0000971.jpg2162 16110 Academy Houses Electrical (School) Drywall screws have been used to attach unistrut to wall struts. This condition applies at

floors.AB2-1.0 P0001511.jpg

2481 16110 Academy Houses Electrical (School) 3-4S and 1-5S box on West wall have conductors pulled in them but not landed. AB2-1.01 P0001661.jpg2291 16110 Academy Houses Electrical (School) 10 Boxes with conductors pulled and 8 without in framed walls. AB2-1.01 P0001704.jpg2348 16110 Academy Houses Electrical (School) Cover plates and identification missing on boxes. AB2-1.01 P0001697.jpg2293 16110 Academy Houses Electrical (School) 5 Suspended boxes for ceiling, 2 with conductors pulled, and not landed, 3 with

conductors not pulled. Cover plates and identification missing.AB2-1.01 P0001697.jpg

2320 16110 Academy Houses Electrical (School) Conduit that is run East-West in the room is disconnected at the fitting. Conduit when connected will rub on the plumbing line and hanger rod and is not supported from the over head.

AB2-1.01 P0001711.jpg

2292 16110 Academy Houses Electrical (School) Gray pull box, no conductors pulled, covers and identification missing. AB2-1.01 P0000972.jpg2156 16110 Academy Houses Electrical (School) 4-3/4" Conduit that exit the South wall and run to the teledata cabinets on the West wall

require ceiling supports.AB2-1.01 P0001577.jpg

2480 16110 Academy Houses Electrical (School) The 3 1/2" conduit at the PA panel and 2 1/2" conduit at the TV panel are not supported at the wall.

AB2-1.01 P0001661.jpg

2337 16110 Academy Houses Electrical (School) Threaded rods for conduit trapezes are too long and require sway bracing. AB2-1.01 P0001722.jpg2474 16110 Academy Houses Electrical (School) Close hole in side of 5S box at West wall above door 104. AB2-1.01 P0000741.jpg2415 16110 Academy Houses Electrical (School) Conductors missing in boxes. AB2-1.01 P0001604.jpg2477 16110 Academy Houses Electrical (School) Close 2 1/2" hole in TV panel box on West wall. AB2-1.01 P0001668.jpg2164 16110 Academy Houses Electrical (School) 2 1/2" Conduit is not secured to shaft wall. AB2-1.01 P0001586.jpg2430 16110 Academy Houses Electrical (School) Conductors missing in boxes. AB2-1.01 P0001604.jpg2414 16110 Academy Houses Electrical (School) Conductors missing in boxes. AB2-1.01 P0001604.jpg2160 16110 Academy Houses Electrical (School) 1 1/2" Conduit above door 104 is not anchored to trapeze and ceiling, coming out of box

panel AC2L18.AB2-1.01 P0001577.jpg

2429 16110 Academy Houses Electrical (School) Conductors missing in boxes. AB2-1.01 P0001604.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 69 of 154

Page 70: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

2431 16110 Academy Houses Electrical (School) Conductors missing in boxes. AB2-1.01 P0001604.jpg2487 16110 Academy Houses Electrical (School) 1 1/2" Concuit does not have any support or hangers at panel PK3H1. AB2-1.01 P0001664.jpg2478 16110 Academy Houses Electrical (School) 3/4" Conduit from panel PK3H1 to shaft has not been secured to unistrut trapeze. AB2-1.01 P0001782.jpg2488 16110 Academy Houses Electrical (School) 4" Conduit from transfer switch is not supported at shaft. AB2-1.01 P0001630.jpg2432 16110 Academy Houses Electrical (School) Conductors missing in boxes. AB2-1.01 P0001604.jpg2428 16110 Academy Houses Electrical (School) Conductors missing in boxes. None of the boxes have lids or IDs. AB2-1.01 P0001634.jpg2403 16110 Academy Houses Electrical (School) Gray pull box does not have conductors pulled and identification is not provided. AB2-1.01 P0000972.jpg2079 16110 Academy Houses Electrical (School) Fire stop outlet boxes in walls. AB2-1.01 P0001872.jpg2349 16110 Academy Houses Electrical (School) Conductors missing in boxes. AB2-1.01 P0001704.jpg2350 16110 Academy Houses Electrical (School) Conductors missing in boxes. AB2-1.01 P0001704.jpg2351 16110 Academy Houses Electrical (School) Conductors missing in boxes. AB2-1.01 P0001704.jpg2434 16110 Academy Houses Electrical (School) Conductors missing in boxes. AB2-1.01 P0001604.jpg2489 16110 Academy Houses Electrical (School) 3" Conduit from floor above to HVAC shaft is not supported and is not fire stopped. AB2-1.01 P0001630.jpg2435 16110 Academy Houses Electrical (School) Conductors missing in boxes. AB2-1.01 P0001604.jpg2441 16110 Academy Houses Electrical (School) 8 Flex conduit runs with conductors pulled for future case work. AB2-1.01 P0001194.jpg2439 16110 Academy Houses Electrical (School) Conductors missing in boxes. AB2-1.01 P0001604.jpg2363 16110 Academy Houses Electrical (School) Repair hole chipped into slab to move conduit into wall framing. AB2-1.01 P0001673.jpg2420 16110 Academy Houses Electrical (School) Gray pull box, conductor is not pulled and identification is not provided. AB2-1.01 P0000972.jpg2368 16110 Academy Houses Electrical (School) 6 Boxes and conduit installed on metal deck in ceiling, conductors pulled, covers are

missing and there is not identification provided.AB2-1.01 P0001470.jpg

2165 16110 Academy Houses Electrical (School) Trapeze for conduit and bus way are not sway braced. AB2-1.01-1.02-1.03

P0001584.jpg

2159 16110 Academy Houses Electrical (School) EMT has been used below 6' in room at East wall. AB2-1.01-1.02-1.03

P0001581.jpg

2310 16110 Academy Houses Electrical (School) 6 Boxes with conductor pulled and 5 without conductors. There is no identification of boxes in walls.

AB2-1.02 P0001704.jpg

2259 16110 Academy Houses Electrical (School) 7 Boxes in framed walls, conductors pulled and 6 without conductors. Identification is not provided in all of the boxes.

AB2-1.02 P0001704.jpg

2241 16110 Academy Houses Electrical (School) 6 Boxes in gypsum framed wall have conductors pulled and 8 have no conductors pulled. All boxes have not been identified.

AB2-1.02 P0001704.jpg

2221 16110 Academy Houses Electrical (School) 1" Conduit from panel AC2H2 requires another hanger before the trapeze. Also the 1 1/2" conduit and 1"above door 204 require hanger.

AB2-1.02 P0001753.jpg

2216 16110 Academy Houses Electrical (School) 4" Teledata conduit is not secured to trapeze, 2 trapezes. AB2-1.02 P0001740.jpg2222 16110 Academy Houses Electrical (School) Conduit in front of damper will not allow access to damper. AB2-1.02 P0001741.jpg2265 16110 Academy Houses Electrical (School) 6 Boxes in framed wall, no conductors pulled and 6 boxes with conductors pulled. Boxes

don't have ID.AB2-1.02 P0001704.jpg

2281 16110 Academy Houses Electrical (School) 3 Boxes in framed wall conductors pulled and 2 boxes conductors are not pulled. AB2-1.02 P0001704.jpg2275 16110 Academy Houses Electrical (School) 5 Boxes suspended from ceiling, 3 with conductor or cable pulled, not landed, 2 without.

There are no covers or IDs on boxes.AB2-1.02 P0001697.jpg

2272 16110 Academy Houses Electrical (School) Flex thru wall and wire pulled for future case work in work rooms. AB2-1.02 P0001435.jpg2284 16110 Academy Houses Electrical (School) One suspended box from ceiling conductors pulled. There is no lid or ID on box. AB2-1.02 P0001697.jpg2271 16110 Academy Houses Electrical (School) 5 Boxes suspended from ceiling, 3 with conductor and cable pulled, 2 without. None

have lids or IDs on boxes.AB2-1.02 P0001697.jpg

2286 16110 Academy Houses Electrical (School) 5 Boxes suspended from ceiling, 3 with conductors or cables pulled, and 2 without conductors pulled. All boxes have missing covers and have not been identified.

AB2-1.02 P0001697.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 70 of 154

Page 71: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

2295 16110 Academy Houses Electrical (School) 11 Boxes with conductors pulled, there is no identification on boxes. AB2-1.02 P0001704.jpg2269 16110 Academy Houses Electrical (School) Seven boxes in framed wall conductors pulled and five boxes with no conductors pulled,

there is no identification on boxes.AB2-1.02 P0001704.jpg

2242 16110 Academy Houses Electrical (School) 4 Boxes suspended from ceiling, two have conductors pulled not landed, two have no conductors pulled, all have no lids and ID numbers are not provided on boxes.

AB2-1.02 P0001697.jpg

2263 16110 Academy Houses Electrical (School) 4 Boxes suspended from ceiling 2 with conductor pulled, 2 without conductor pulled. There are no lids or ID on boxes.

AB2-1.02 P0001697.jpg

2262 16110 Academy Houses Electrical (School) 5 Boxes suspended from ceiling 3 with conductor pulled and 2 without. There are no lids on boxes and ID is not provided.

AB2-1.02 P0001697.jpg

2280 16110 Academy Houses Electrical (School) 14 Boxes in framed wall are not conductor pulled and 15 boxes in framed walls conductor pulled. There is no identification on any boxes.

AB2-1.02 P0001704.jpg

2254 16110 Academy Houses Electrical (School) Seven boxes in framed wall have conductor pulled and seven have no conductors pulled. No identification is provided on all boxes.

AB2-1.02 P0001704.jpg

2253 16110 Academy Houses Electrical (School) Six boxes suspended from ceiling , three with conductor or cable pulled and three without. None have lids and identification on boxes is not provided.

AB2-1.02 P0001697.jpg

2250 16110 Academy Houses Electrical (School) Six boxes in gypsum framed wall conductor pulled and six boxes have no conductors pulled. No identification is provided in all boxes.

AB2-1.02 P0001704.jpg

2246 16110 Academy Houses Electrical (School) 4 Boxes suspended from ceiling 3 have conductor pulled, one has no conductor pulled. All have no lids and no ID provided on boxes.

AB2-1.02 P0001697.jpg

2270 16110 Academy Houses Electrical (School) 2 With conductors pulled into boxes and 4 without conductors pulled, typical in work room frame walls.

AB2-1.02 P0001704.jpg

2335 16110 Academy Houses Electrical (School) EMT has been used below 6'0" in room. AB2-1.02 P0001732.jpg2311 16110 Academy Houses Electrical (School) 3 Boxes suspended from ceiling, 2 with conductors pulled, 1 without. Cover plates and

identification have not been provided.AB2-1.02 P0001697.jpg

2316 16110 Academy Houses Electrical (School) Gray pull box does not have cover plate or identification, and conductors are not pulled. AB2-1.02 P0000972.jpg2317 16110 Academy Houses Electrical (School) Identification on six boxes is not provided in walls. AB2-1.02 P0001704.jpg2319 16110 Academy Houses Electrical (School) 2 Sets per room of conduit and boxes attached to metal deck conductors pulled.

Identification is not provided and the cover plates are missing.AB2-1.02 P0001470.jpg

2009 16110 Academy Houses Electrical (School) Conduit attached to duct above door 317.1. AB2-1.03 P0001896.jpg2005 16110 Academy Houses Electrical (School) Conduit hangers missing on runs out for AC 243 box West wall. AB2-1.03 P0001893.jpg2080 16110 Academy Houses Electrical (School) Hanger rods over 24" long shall be sway braced. AB2-1.03 P0001870.jpg2225 16110 Academy Houses Electrical (School) A 2-S and a 4S box have conductors pulled but not landed. AB2-1.03 P0001268.jpg2227 16110 Academy Houses Electrical (School) Conduit with condulet from South to East walls does not have any hangers for support. AB2-1.03 P0001790.jpg2034 16110 Academy Houses Electrical (School) Gray pull box is supported from light gauge deck; it needs to be supported from a

structural beam. Conductors have not been pulled into the box and the box has not been identified.

AB2-1.03 P0001825.jpg

2101 16110 Academy Houses Electrical (School) Unistrut trapeze for raceway improperly supported. AB2-1.03 P0001878.jpg2014 16110 Academy Houses Electrical (School) Gray pull box suspended for light gauge deck, no conductor pulled into box and

identification has not been provided.AB2-1.03 P0001825.jpg

2102 16110 Academy Houses Electrical (School) Unistrut trapeze at radius turn for raceway is not provided. AB2-1.03 P0001882.jpg2200 16110 Academy Houses Electrical (School) Box surface mounted on duct shaft no conductors pulled, identification is not provided. AB2-1.03 P0001550.jpg2104 16110 Academy Houses Electrical (School) Conduit support wire tied to other craft support hanger at three hanger rods. AB2-1.03 P0001898.jpg2069 16110 Academy Houses Electrical (School) 4" Teledata conduit connector is partly in the fire rated wall. AB2-1.03 P0001829.jpg2219 16110 Academy Houses Electrical (School) Conduit below the cabinets require support at the East wall. AB2-1.03 P0001779.jpg2230 16110 Academy Houses Electrical (School) Conduits in overhead are not properly supported. AB2-1.03 P0001782.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 71 of 154

Page 72: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

2070 16110 Academy Houses Electrical (School) 3/4" Conduit from fire alarm cabinet to the roof has not been supported at the beam and shall run true to building lines.

AB2-1.03 P0001826.jpg

3088 16110 Academy Houses Electrical (School) Light fixture threaded rod is rubbing on conduit. AB3-1.0 P0001512.jpg3097 16110 Academy Houses Electrical (School) 2 1/2" conduit above main panels at North wall in ceiling are not supported properly. AB3-1.0 P0001522.jpg3096 16110 Academy Houses Electrical (School) Hanger missing on double back unistrut at South end of trapeze and trapeze support rod

requires uplift brace.AB3-1.0 P0001518.jpg

3222 16110 Academy Houses Electrical (School) 6 Conduit runs thru deck no conductors pulled runs incomplete and not identified. AB3-1.01 P0000981.jpg3060 16110 Academy Houses Electrical (School) Unistrut for conduit rack support is uptight against sprinkler pipe 1" clearance for

sprinkler pipe is not provided.AB3-1.01 P0001557.jpg

3226 16110 Academy Houses Electrical (School) Conduit run above ceiling incomplete, all rooms, all floors. AB3-1.01-1.02-1.03

P0000967.jpg

3083 16110 Academy Houses Electrical (School) Conduit not supported under panels for sleeved holes at North wall. AB3-1.03 P0001521.jpg3045 16110 Academy Houses Electrical (School) Conduit run incomplete wires pull, no ID on conduit and not secured to wall. AB3-1.03 P0001561.jpg3048 16110 Academy Houses Electrical (School) 10 Conduit box installed on gypsum walls no conductor pulled, no lids, no ID on boxes. AB3-1.03 P0001550.jpg

3043 16110 Academy Houses Electrical (School) One gray pull box, no lid , no ID and One pull box wires pulled, no lid, no ID. AB3-1.03 P0001562.jpg3047 16110 Academy Houses Electrical (School) A) One tel-com box wire pulled in box, no ID on box. B) Tel-com box, no wire pulled,

no ID on box.AB3-1.03 P0001471.jpg

3081 16110 Academy Houses Electrical (School) Trapezes for conduit are spaced too far apart to support conduit. AB3-1.03 P0001525.jpg3079 16110 Academy Houses Electrical (School) Conduit EMT has been installed below 6' above finish floor. AB3-10 P0001534.jpg

919 16110 Academy Houses Electrical (School) Hangers missing on conduit that runs diagonal from West wall to North wall. Also conduit is rubbing on sprinkler main.

AB4-1.01 P0000966.jpg

914 16110 Academy Houses Electrical (School) 4S box above 2' by 2' light at S-W corner of room has had the hanger removed for the box. Cover is missing on box.

AB4-1.01 P0000962.jpg

846 16110 Academy Houses Electrical (School) Cable tray in ceiling incompleete. AB4-1.02 P0002501.jpg848 16110 Academy Houses Electrical (School) Conduit runs in ceiling incomplete. AB4-1.02 P0000967.jpg607 16110 Academy Houses Electrical (School) Conductor pulled thru flex for future case work. AB4-1.02 P0001269.jpg598 16110 Academy Houses Electrical (School) EMT has been used below 6' from finish floor in the electrical rooms. AB4-1.04-

2.04-3.04P0001303.jpg

9030 16110 Administration Electrical (School) Conduit for electrical room stubbed up. Conductors have not been pulled and conduit has not been identified.

AE-1.01 P0002243.jpg

9069 16110 Administration Electrical (School) Attic area conduit runs incomplete (Only to roof HVAC and attic area. Motorized dampers). No conductors or pull strings.

AE-1.02 P0002293.jpg

346 16110 Parking Garage Electrical (School) Conduit run requires anchorage within 18" of coupler splice connector. A 1.03 P0000716.jpg500 16110 Triple Gym Electrical (School) Suspended conduit run in room requires seismic bracing per spec. noted. AC-1.02 P0000916.jpg565 16110 Triple Gym Electrical (School) Sway bracing of conduit runs and hangers thru Room 125 & Corridor 127 missing. AC-1.02 P0000941.jpg

9098 16114 Administration Electrical (School) Bonding of cable tray not done. AE-1.02 P0002308.jpg9033 16114 Administration Electrical (School) Seismic bracing of cable tray and conduit rack not done from column line 1 to 2.5 and

incomplete from 2.5 to 5.0.AE-1.02 P0002312.jpg

695 16114-01400 Academy Houses Electrical (School) Cable tray and conduit rack drilled anchors have not been tested. AB4-1.02 P0001228.jpg3164 16429 Academy Houses Electrical (School) Connection lugs inside panels have not been torque tested. AB3-1.01-

1.02-1.03P0001296.jpg

9080 16429 Administration Electrical (School) Roof mounted electrical panels missing at three locations. AE-1.03 P0002210.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 72 of 154

Page 73: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

697 16455 Academy Houses Electrical (School) Distribution panel AC4MDL is anchored to wall with 8 # 8 Tek screws to drywall studs at a non structural furred wall.

P0001250.jpg

3196 16455 Academy Houses Electrical (School) At various locations room drywall screws have been used to support panel boards and wall unistrut to support conduit.

AB3-1.0 P0001507.jpg

3089 16455 Academy Houses Electrical (School) Panels and unistrut for conduit support have been anchored to drywall with drywall screws.

AB3-1.0 P0001507.jpg

3283 16455 Academy Houses Electrical (School) Main power panel North side of room, conductors have not been pulled into boxes. AB3-1.01 P0001419.jpg3282 16455 Academy Houses Electrical (School) Main power panels covers missing, total of 3. AB3-1.01 P0001418.jpg3314 16455 Academy Houses Electrical (School) Close 1 3/4" hole in 8" by 8" gray pull box under panel AC3H1. AB3-1.01 P0001405.jpg3312 16455 Academy Houses Electrical (School) Bus duct is not anchored to concrete deck and fire stopping has sunk below floor line. AB3-1.01 P0001410.jpg3313 16455 Academy Houses Electrical (School) Drywall screws used to attach unistrut to drywall for conduit support. Also drywall

screws have been used to hang the panels AC3LAB and AC3L1A.AB3-1.01 P0001411.jpg

3304 16455 Academy Houses Electrical (School) 6 Conduits not properly supported in ceiling of room. AB3-1.01 P0001417.jpg3318 16455 Academy Houses Electrical (School) Dampers have not been connected to power supply. AB3-1.01 P0001371.jpg3284 16455 Academy Houses Electrical (School) Electrical room power panels, no covers provided debris at bottom of panels in all rooms. AB3-1.01-

1.02-1.03P0001419.jpg

3172 16455 Academy Houses Electrical (School) Busway not anchored at the floor. Unistrut support is in non-rated wall. AB3-1.02 P0001443.jpg3141 16455 Academy Houses Electrical (School) 1200 amp distribution panel covers not installed. AB3-1.02 P0001469.jpg

678 16455 Academy Houses Electrical (School) Main power panel covers not provided in rooms noted. AB4-1.01-1.02-1.03

P0001418.jpg

679 16455 Academy Houses Electrical (School) Electrical power panels no covers provided. Debris at bottom of panels in all rooms noted.

AB4-1.01-1.02-1.03

P0001418.jpg

589 16455 Academy Houses Electrical (School) Dry wall screws and small Tek screws have been used to mount all cabinets and panels in room.

AB4-1.02 P0001287.jpg

600 16455 Academy Houses Electrical (School) 4s Junction box above security panel has not been identified. AB4-1.02 P0001292.jpg599 16455 Academy Houses Electrical (School) 2" Conduit for fire alarm cabinet has not been supported from ceiling. AB4-1.02 P0001291.jpg662 16455 Academy Houses Electrical (School) Conductor's have not been torqued at their termination points in the panels. AB4-1.02 P0001293.jpg597 16455 Academy Houses Electrical (School) Fire alarm cabinet at East wall has three 5s boxes next to it that are mounted to drywall

not studs.AB4-1.02 P0001284.jpg

638 16455 Academy Houses Electrical (School) Anchorage for combination pull and 1200 amp main, and 1200 amp distribution panels and 225 KVA transformer has not been tested.

AB4-1.02 P0001293.jpg

592 16455 Academy Houses Electrical (School) Unistrut for conduit has not been rated at shaft wall. AB4-1.02 P0001285.jpg583 16455 Academy Houses Electrical (School) Conduits that are in sleeved holes at the floor shall be supported at the floor. AB4-1.02 P0001298.jpg588 16455 Academy Houses Electrical (School) Terminal cabinets have non-rated plywood inside of all cabinets. AB4-1.02 P0001284.jpg586 16455 Academy Houses Electrical (School) Power cables are not supported inside of panel, cables are resting on the bottom of the

panelAB4-1.02 P0001296.jpg

585 16455 Academy Houses Electrical (School) Grounding cables and grounding systems has not been connected to panels and building. AB4-1.02 P0001303.jpg

580 16455 Academy Houses Electrical (School) 2" Conduit is too close to fire damper and damper angle cannot be installed. AB4-1.02 P0001275.jpg581 16455 Academy Houses Electrical (School) Conduits at the fire damper have not been fire stopped as required (3 Conduit) on the

East wall.AB4-1.02 P0001278.jpg

584 16455 Academy Houses Electrical (School) Hanger rods over 24" long must have vertical stiffeners. AB4-1.02 P0001282.jpg593 16455 Academy Houses Electrical (School) Conduit has not been fire stopped at East wall of room 7 penetration. AB4-1.02 P0001280.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 73 of 154

Page 74: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

635 16455 Academy Houses Electrical (School) Floor penetrations in room are not fire stopped at following locations: North wall at N.9-5.1 - Two - 1" penetrations at N.9-5.5 -1- 3" penetration, West wall at C line 5.5 from N.8 to N.7 -4- 3" penetrations and South wall at line N.6 from 5.3 to 5.4 -2-

AB4-1.02 P0001297.jpg

633 16455 Academy Houses Electrical (School) Dry type transformer conductors pulled not landed and no panel cover provided. AB4-1.02 P0001312.jpg636 16455 Academy Houses Electrical (School) Conduit pull box cover plate not installed. AB4-1.02 P0001297.jpg775 16455 Academy Houses Electrical (School) Fire alarm does not have cable pulled and has not been identified at the box and conduit.

(red stripes)AB4-1.03 P0001345.jpg

773 16455 Academy Houses Electrical (School) 2 3/4" conduit from rated wall are resting on sprinkler lines. Hangers are required. AB4-1.03 P0001364.jpg778 16455 Academy Houses Electrical (School) Supports and hanger have not been provided for 2" conduit at the North East of the room. AB4-1.03 P0001358.jpg

787 16455 Academy Houses Electrical (School) Drilled anchors have not been torque tested. AB4-1.03 P0001293.jpg785 16455 Academy Houses Electrical (School) Conduit has not been fire stopped at floor penetration for main panel feed. AB4-1.03 P0001331.jpg784 16455 Academy Houses Electrical (School) Teledata panels have non rated plywood installed inside of panels. AB4-1.03 P0001332.jpg783 16455 Academy Houses Electrical (School) Conduit is half in wall above exhaust air duct and is not fire stopped. Also two conduits

have not been fire stopped at rated wall near exhaust air duct.AB4-1.03 P0001339.jpg

781 16455 Academy Houses Electrical (School) Conduit cluster has not been fire stopped at East rated wall. AB4-1.03 P0001340.jpg780 16455 Academy Houses Electrical (School) Cables from floor penetration under main panel are bent too severe at tie-in to main

panel.AB4-1.03 P0001330.jpg

772 16455 Academy Houses Electrical (School) Tele/Data panels conduit does not have any wall supports. AB4-1.03 P0001332.jpg774 16455 Academy Houses Electrical (School) 5 3/4" Conduit above furred wall does have hangers installed. AB4-1.03 P0001359.jpg779 16455 Academy Houses Electrical (School) Main electrical panel frame has been deformed due to over torqueing of drilled anchors. AB4-1.03 P0001333.jpg812 16455 Academy Houses Electrical (School) 4S box at South wall has conductors wall receptical not installed. AB4-1.03 P0001349.jpg587 16455-01900 Academy Houses Electrical (School) Bus duct is not secured to unistrut trapeze. Hangers missing at exit and change of

direction.AB4-1.02 P0001294.jpg

661 16455-01900 Academy Houses Electrical (School) All drilled anchors require testing 18 anchors. AB4-1.02 P0001033.jpg3197 16455-16110 Academy Houses Electrical (School) EMT has been used below six feet at finish floor. AB3-1.0 P0001442.jpg2486 16465 Academy Houses Electrical (School) Hanger missing at busway where the busway comes from the floor below verticaly and

turns horizontal.AB2-1.01 P0001659.jpg

2485 16465 Academy Houses Electrical (School) Bus way joint above long junction box is difficult to reach bolts at North wall. Cut off long all thread at trapeze hanger.

AB2-1.01 P0001639.jpg

2161 16465 Academy Houses Electrical (School) Bus way is not anchored to slab. This condition applies to both floors. AB2-1.01-1.02

P0001581.jpg

2215 16465 Academy Houses Electrical (School) Bus way is not fire stopped at floor. AB2-1.02 P0001739.jpg833 16465 Academy Houses Electrical (School) Bus duct system is not anchored at deck located at N6-4.8. AB4-1.01 P0001168.jpg

2479 16470 Academy Houses Electrical (School) Non rated plywood has been used in all terminal cabinets. AB2-1.01-1.02-1.03

P0001667.jpg

813 16470 Academy Houses Electrical (School) Four telecom panels have cables pulled into them but not landed. Also plywood inside panels is not fire rated and panels are dirty.

AB4-1.01 P0001154.jpg

814 16470 Academy Houses Electrical (School) Conductor have been pulled into electrical panel but not landed and panel is dirty. AB4-1.01 P0001156.jpg821 16470 Academy Houses Electrical (School) Electrical panels are dirty and do not have covers installed. AB4-1.01 P0001148.jpg

2446 16479 Academy Houses Electrical (School) Smoke fire damper is not connected to power and cover is not installed. AB2-.101 P0001024.jpg2056 16479 Academy Houses Electrical (School) 30 Smoke/fire dampers not hooked to power and covers not installed. AB2-1.03 P0001024.jpg3207 16479 Academy Houses Electrical (School) Smoke/fire damper motor not connected to power. AB3-1.02 P0001024.jpg3107 16479 Academy Houses Electrical (School) Motor control to smoke/fire dampers not hooked to power source and covers not on

boxes, 18 total.AB3-1.03 P0001259.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 74 of 154

Page 75: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

771 16479 Academy Houses Electrical (School) Motor controls wire pulled but not landed. AB4-1.03 P0001106.jpg751 16479 Academy Houses Electrical (School) Motor control wires pulled but not landed. AB4-1.03 P0001106.jpg

2346 16497 Academy Houses Electrical (School) 14 Smoke/fire damper not connected to power and covers not installed. AB2-1.02 P0001024.jpg643 16504 Academy Houses Electrical (School) Light fixtures not installed in each room. AB4-1.02 P0001790.jpg

3159 16505 Academy Houses Electrical (School) Hanger rods for light fixture up tight against conduit, 1/8" gap, isolation required. AB3-1.02 P0001461.jpg2206 16509 Academy Houses Electrical (School) Light fixture is not installed in room. AB2-1.02 P0001426.jpg3288 16509 Academy Houses Electrical (School) Light fixtures in rooms noted not installed. AB3-1.01 P0001426.jpg3032 16509 Academy Houses Electrical (School) Ceiling light fixture installed in incomplete steel stud frame ceiling of stair and corridor.

Level 1-3 lights, level 2-3 lights, level 3-4 lights. Total of 10.AB3-1.01-1.02-1.03

P0001569.jpg

3071 16509 Academy Houses Electrical (School) Typical all corridors; ceiling lights, finish not set including reflectors, bulbs, lense and bulbs. Level 1, 21 locations. Level 2, 19 locations. Level 3, 19 locations.

AB3-1.01-1.02-1.03

P0000947.jpg

3190 16509 Academy Houses Electrical (School) Light fixtures not installed in rooms noted. AB3-1.02 P0001426.jpg3249 16509 Academy Houses Electrical (School) Wall mounted stair well lights; wires not landed, finish not set. Typical 2 locations. AB3-1.023130 16509 Academy Houses Electrical (School) Light fixtures are not sway braced in rooms noted. AB3-1.03 P0001495.jpg

943 16509 Academy Houses Electrical (School) Attic area lighting J boxes and pull box open with wires not landed. 1) Room 217, one 8 by 8 pull box and one 4 by 4 J box. 2) Room 218, one 5 by 5 J box. 3) Room 219, one 5 by 5 J box.

AB4-1.02 P0001401.jpg

958 16509 Academy Houses Electrical (School) Attic area, electrical J boxes open and wires not landed, 2- 4 by 4 and 3- 5 by 5. Attic area wall mounted electrical conduits not fastened at East, South and West wall, two conduits total.

AB4-1.02 P0001401.jpg

852 16509 Academy Houses Electrical (School) Light fixtures not installed in suspended ceiling. AB4-1.02 P0001192.jpg837 16509 Academy Houses Electrical (School) Light fixtures not installed in suspended ceiling. AB4-1.02 P0001192.jpg942 16509 Academy Houses Electrical (School) Attic area flex and conductors not landed to tee bar light fixtures typical room 217-218-

219.AB4-1.02 P0001378.jpg

922 16509 Academy Houses Electrical (School) Attic area lighting system. Room 325-326-327, Typical each room; 1-4s box, open with wires not landed and fixture whip with conductors not landed.

AB4-1.03 P0001498.jpg

941 16509 Academy Houses Electrical (School) Attic area lighting system. Room 320-321, typical each room, 5-5s boxes open with wires not landed, no fixture whips or light fixtures installed.

AB4-1.03 P0001498.jpg

924 16509 Academy Houses Electrical (School) Attic area lighting system. Room 313; 5-4s boxes, wires not landed, no cover, no light fixture whips.

AB4-1.03 P0001498.jpg

805 16509 Academy Houses Electrical (School) Light fixture not installed in room, conduit stub out from wall and conductor hanging from conduit for light fixture.

AB4-1.03 P0001328.jpg

923 16509 Academy Houses Electrical (School) Attic area lighting system. Room 312; 5-4s boxes, wires not landed, no cover, no light fixtures, no fixture conduits, boxes, in wall switches, fixture whips or lights.

AB4-1.03 P0001498.jpg

921 16509 Academy Houses Electrical (School) Attic area lighting system. Room 314-315-316-319. Typical each room-1.5's box no cover, wires not landed, fixture whips not connected to lights (no lights installed).

AB4-1.03 P0001498.jpg

797 16509 Academy Houses Electrical (School) Light fixture not installed in room and conduit stab out from West wall over door conductors hanging from incomplete conduit run.

AB4-1.03 P0001336.jpg

984 16509 Academy Houses Electrical (School) Typical at the bar ceilings. 1) Slack wires not pull tested. 2) Flex whips not installed to light fixtures, wires not landed. 3) Lights not secured to grid.

AB4-1.03

94 16509 Parking Garage Electrical (School) Light fixture and guard installed tight to 4' overflow drain and roof drain. AA 1.09 P0000505.jpg2407 16550-16050 Academy Houses HVAC and Temperature Control Systems Insulation incomplete on refrigrant condensation line. Insulation cut at trapeze and no

sleeve where pipe lands on trapeze.AB2-1.01 P0001655.jpg

954 16710 Academy Houses Electrical (School) Fire alarm conduits and boxes in attics not identified. Typical all rooms. P0001223.jpg2460 16710 Academy Houses Electrical (School) Conduits and boxes are not labelled for fire alarm system. AB2-.101 P0001223.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 75 of 154

Page 76: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

2447 16710 Academy Houses Electrical (School) 32 Smoke detectors have not been installed. AB2-.101 P0000951.jpg2340 16710 Academy Houses Electrical (School) Fire alarm conduit and boxes have not been identified. AB2-1.01 P0001723.jpg2338 16710 Academy Houses Electrical (School) Fire alarm conduit has not been identified. AB2-1.01 P0001723.jpg2204 16710 Academy Houses Electrical (School) Smoke/fire damper not connected to power in rooms noted in each floor. AB2-1.01-

1.02-1.03P0001024.jpg

2391 16710 Academy Houses Electrical (School) Fire alarm duct detectors are not per plans and specs, 2 locations. AB2-1.03 P0001698.jpg2071 16710 Academy Houses Electrical (School) None of the fire alarm conduits have been identified as required. AB2-1.03 P0001828.jpg3086 16710 Academy Houses Electrical (School) Low voltage cable for smoke detector should be run in a raceway. AB3-1.0 P0001519.jpg3095 16710 Academy Houses Electrical (School) Smoke detectors are set too low in ceiling to meet code requirement and should have two

detectors (Because of 18" beam depth two detectors are required).AB3-1.0 P0001518.jpg

3302 16710 Academy Houses Electrical (School) Smoke detectors fire alarms and strobes have not been installed in all rooms and work room all floors.

AB3-1.01-1.02-1.03

P0000951.jpg

3024 16710 Academy Houses Electrical (School) Flow and tamper switch 55 boxes conductors pulled not landed and sensor not connected to power source.

AB3-1.01-1.02-1.03

P0001620.jpg

3256 16710 Academy Houses Electrical (School) Fire alarm strobes incomplete at ceilings, wires not landed strobes not installed. AB3-1.01-1.02-1.03

P0000947.jpg

3165 16710 Academy Houses Electrical (School) Smoke detector in room required to be set at deck. Level and 2 smoke detectors required in room.

AB3-1.02 P0001446.jpg

957 16710 Academy Houses Electrical (School) Fire alarm conduits and boxes in attics not identified B classrooms and 4 workrooms. AB4-1.01 P0001223.jpg948 16710 Academy Houses Electrical (School) Attic area fire alarm open J boxes, wires not landed. 1)Room 217; 1-5 by 5 and 1- 4 by 4

box. 2) Room 218, 1 - 5 by 5 box.AB4-1.02 P0000973.jpg

739 16710 Academy Houses Electrical (School) Fire alarm strobe not installed. AB4-1.03 P0001104.jpg767 16710 Academy Houses Electrical (School) Fire alarm strobe not installed. AB4-1.03 P0001104.jpg757 16710 Academy Houses Electrical (School) Fire alarm strobe not installed. AB4-1.03 P0001104.jpg931 16710 Academy Houses Electrical (School) Attic area fire alarm 1-open 5s box open without cover or wires landed and 1-5.8 box

with no cover or wires pulled.AB4-1.03 P0000973.jpg

933 16710 Academy Houses Electrical (School) Attic area fire alarm open boxes, open boxes with wires not landed. 312-1-4s box without cover, no cover, 1-4s box without cover wires not landed. 324- 1-4s box, no cover, wires not landed. 313-2-4s boxes, no cover, wires not landed.

AB4-1.03 P0000973.jpg

934 16710 Academy Houses Electrical (School) Attic area fire alarm open boxes open boxes with wires not landed. Room 314-1-5s box without cover wires not landed. 315-316-317-318-319-320-321, typical 7 locations total 1-5s box without cover and wires not landed.

AB4-1.03 P0000973.jpg

935 16710 Academy Houses Electrical (School) Duct detectors, typical all locations 32 total. 1) Wires not landed. 2) Detector head not installed. Note: Two duct detector circuit boards and detector heads sprayed with wall texture. Room 312-213 (One each).

AB4-1.03 P0001024.jpg

936 16710 Academy Houses Electrical (School) Attic areas fire alarm conduit and boxes not stripped red in color. AB4-1.03 P0001223.jpg746 16710 Academy Houses Electrical (School) Fire alarm strobe not installed. AB4-1.03 P0001104.jpg

9068 16710 Administration Electrical (School) No fire alarm conduits or boxes in walls. AE-1.02 P0002279.jpg9070 16710 Administration Electrical (School) Fire alarm attic area, no conduits or boxes except to motorized fire dampers about 14

boxes, 4S.AE-1.02 P0002294.jpg

356 16710 Parking Garage Electrical (School) Exit signs have not been installed at entrance to stairs. AA 1.09 P0000702.jpg3147 16721 Academy Houses Electrical (School) Security system for exterior door typical; wires not landed, finish not set, level one

corridors. Level 1; doors 102-116-116.1. Level 2; doors 202-216-216.1-217-217.1. Level 3; doors 302-316-316.1-317-317.1. Total of 13 doors.

AB3-1.01-1.03

P0001548.jpg

945 16722 Academy Houses Electrical (School) Attic area security open pull box, 8 by 8 with no wire or pull string one at room 217 and one at room 218.

AB4-1.02 P0000972.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 76 of 154

Page 77: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Los Angeles Unified School DistrictBelmont Learning Complex

Request for ProposalIOR Deficiency Report by Specification Number

ID Spec. Section <1> Location Trade Description Drawing # Image # <2>

DISCLAIMER: THE DISTRICT PROVIDES INFORMATION ABOUT THE DOCUMENTS AVAILABLE FOR REVIEW. THIS INFORMATION IS INFORMATIONAL ONLY AND THE DISTRICT DOES NOT WARRANT THAT THE INFCOMPLETE OR CURRENT. ALTHOUGH EVERY REASONABLE EFFORT HAS BEEN MADE TO MAKE THE INFORMATION AS COMPLETE AS POSSIBLE, ANYONE OR ANY ENTITY UTILIZING OR ACCESSING THIS INFORMAT

PERFORM ITS OWN DUE DILIGENCE AND MAY NOT RELY ON THE SUPPLIED INFORMATION ALONE.

927 16722 Academy Houses Electrical (School) Attic area security system. Room 312, 1-12 by 12 pull box open with no wires pulled. 313, 1-6 by 6 pull box open with no wires pulled. 314, 1-8 by 8 pull box open with no wires pulled. 318, 1-5s box no cover, no wires pulled. Also 319&329 (3 Locations tot

AB4-1.03 P0000972.jpg

3303 16723 Academy Houses Electrical (School) Motion detectors in all rooms all floors not installed. AB3-1.01-1.02-1.03

P0000970.jpg

928 16725 Academy Houses Electrical (School) Attic area TV system. Room 312-313-315-316-317-318-319-320-321 typical 5s box open, no cover and wires not landed, typical 9 locations one per room.

AB4-1.03 P0000974.jpg

932 16730 Academy Houses Electrical (School) Attic area clock system. Room 312, open 5s box without cover and wires not landed. AB4-1.03 P0001401.jpg946 16740 Academy Houses Electrical (School) Attic area PA open J boxes with wires not landed; 1) Room 217, 2-5 by 5 2) Room 218, 1

5 by 5.AB4-1.02 P0001401.jpg

3214 16770 Academy Houses Electrical (School) Speakers not installed in boxes in hard ceilings (total of 12). AB3-1.01 P0001105.jpg3300 16770 Academy Houses Electrical (School) Black channel support for speakers in suspended ceiling is not tied to the ceiling grid. AB3-1.01 P0001021.jpg3072 16770 Academy Houses Electrical (School) Typical all corridors; Ceiling speaker cans, wire not landed, speakers not installed, finish

not set. Level 1, 5 speakers. Level 2, 4 speakers. Level 3, 4 speakers.AB3-1.01-1.02-1.03

P0000947.jpg

3033 16770 Academy Houses Electrical (School) Speaker box installed in incomplete steel stud frame ceiling in corridor area 1 on each level. Total of 3.

AB3-1.01-1.02-1.03

P0001569.jpg

930 16770 Academy Houses Electrical (School) Attic area PA system. Room 316, 1-5s box, no cover, wires not landed. Same for room 317-318-319-320-321 total of 5 locations.

AB4-1.03 P0000974.jpg

929 16770 Academy Houses Electrical (School) Attic area PA system. Room 312, 1-12 by 12 pull box open with wires not landed; 313, 1-6 by 6 pull box open with wires not landed; 314, 1-8 by 8 pull box open with wires not landed; 315, 1-5s box no cover with wires not landed.

AB4-1.03 P0000974.jpg

322 17511-8 3.4A Triple Gym Flashing and Sheet Metal Fasten top of all base flashings and wall sheets 8" O.C. AC-1.03/1.04 P0000280.jpg

925 72155 Academy Houses Drywall/EIFS/SOFP Top of fire rated wall to deck not fire proofed. Room 320 West wall, room 321 East wall, room 328 East and West wall.

AB4-1.03 P0001078.jpg

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 77 of 154

Page 78: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

P0001637P0001054

P0001617

P0000972

P0001000

P0002207; P0002208; P0002228

ORMATION IS TION MUST STILL

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 78 of 154

Page 79: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0002223; P0002224

P0002232

P0002523

P0001034

P0001034

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 79 of 154

Page 80: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0002041

P0001283

P0000742; P0000752

P0001930P0001999

P0001183

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 80 of 154

Page 81: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001944

P0001317

P0001986

P0001985

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 81 of 154

Page 82: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001957

P0001944

P0001936

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 82 of 154

Page 83: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001938P0001944

P0001938

P0001938

P0001183

P0001183

P0001183

P0001183

P0001182; P0001183

P0001183

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 83 of 154

Page 84: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001182; P0001183

P0002565; P0002566; P0002567; P0002568

P0000761

P0002552; P0002553; P0002554; P0002555; P0002556

P0002558; P0002559; P0002560; P0002561; P0002562; P0002563

P0000756

P0000167

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 84 of 154

Page 85: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001176

P0000386; P0000397; P0000504P0000386; P0000397

P0000989P0000989P0000989

P0000397

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 85 of 154

Page 86: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0000694

P0000827

P0000827

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 86 of 154

Page 87: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0002173; P0002174

P0002167

P0002130; P0002131; P0002132

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 87 of 154

Page 88: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001627; P0001628

P0000978

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 88 of 154

Page 89: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0000548

P0001445

P0002245; P0002246

P0002240

P0002207

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 89 of 154

Page 90: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0002101

P0002207; P0002208

P0000503

P0000635

P0002529; P0002531

P0000773

P0000773

P0000773

P0002051; P0002052; P0002053; P0002054; P0002055

P0001428

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 90 of 154

Page 91: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0000670

P0000617

P0000645

P0000660

P0000640; P0000641P0000650

P0000677

P0000698

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 91 of 154

Page 92: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001617

P0002432

P0002352; P0002355

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 92 of 154

Page 93: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0002354

P0001217

P0001685

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 93 of 154

Page 94: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001558; P0001559

P0001393

P0001174

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 94 of 154

Page 95: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001468

P0001685

P0000548

P0000886P0000924

P0000922

P0000854

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 95 of 154

Page 96: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001373

P0001448

P0001448

P0001448

P0001448

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 96 of 154

Page 97: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001448

P0001262

P0001262; P0001267

P0001770

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 97 of 154

Page 98: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001414; P0001415

P0001558

P0001361

P0001262

P0001262

P0002497

P0001361

P0000542

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 98 of 154

Page 99: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001809

P0001123P0000542

P0000542

P0001863

P0000530; P0000531; P0000532; P0000533; P0000534; P0000535; P0000536; P0000537; P0000538; P0000539; P0000540; P0000541; P0000542; P0000543; P0000544; P0000545; P0000546; P0000547; P0000548; P0000549; P0001123

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 99 of 154

Page 100: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0000549

P0001036

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 100 of 154

Page 101: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001867; P0001868P0001980

P0001563

P0002323

P0000563; P0000435; P0000383P0000562; P0000563; P0000383P0000435; P0000562; P0000563

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 101 of 154

Page 102: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0000383

P0000383

P0000397; P0000504; P0000520

P0000776P0001036

P0002387

P0002408

P0002207; P0002208; P0002228

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 102 of 154

Page 103: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0002378

P0002412

P0000276

P0000266

P0000266

P0000264P0000254P0000254

P0000259P0000259P0000266P0000277

P0000280P0000264

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 103 of 154

Page 104: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0000347; P0000348

P0000339; P0000340; P0000224

P0000347; P0000348

P0000347; P0000348; P0000349P0000338; P0000339; P0000340; P0000345

P0000347; P0000348; P0000349P0000343; P0000348; P0000349P0002407

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 104 of 154

Page 105: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0000348; P0000349P0000339; P0000340; P0000224P0000344; P0000352

P0002457

P0002455

P0002455

P0001219

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 105 of 154

Page 106: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0002382

P0000563; P0000435; P0000383P0000386; P0000397P0000504

P0000520

P0000392; P0000386; P0000397

P0000542

P0000522; P0000559

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 106 of 154

Page 107: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0000572; P0000573

P0000779

P0000398; P0000522P0000563

P0000383P0000435P0000435P0000435

P0001959

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 107 of 154

Page 108: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0000562; P0000563; P0000383P0000383P0000383; P0000562

P0000563; P0000435P0000383P0000563; P0000435; P0000383P0000383P0000383P0000383; P0000443P0000435

P0000435P0000435P0000303P0000435P0000563

P0002035

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 108 of 154

Page 109: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0002229

P0001593

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 109 of 154

Page 110: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001213; P0001214

P0001213; P0001214

P0001213; P0001214

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 110 of 154

Page 111: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001866

P0001478

P0002402

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 111 of 154

Page 112: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0002289

P0001027

P0000821

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 112 of 154

Page 113: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001468

P0001536; P0001537; P0001538; P0001539; P0001540; P0001541; P0001542

P0001906

P0001634; P0001635

P0001688

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 113 of 154

Page 114: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0002013

P0002013

P0001855

P0001426P0001459

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 114 of 154

Page 115: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001542

P0001546

P0001505P0001487; P0001488; P0001489; P0001491; P0001492; P0001494

P0001530; P0001531

P0002499

P0001279

P0001323

P0001340

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 115 of 154

Page 116: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0000572; P0000573P0000298; EX000002; EX000003

P0000572; P0000573

P0000593

P0000593

P0000573

P0000866

P0001426

P0002282

P0000441

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 116 of 154

Page 117: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0000593

P0001440

P0002195

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 117 of 154

Page 118: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0002198

P0001034

P0001034

P0000679

P0001380

P0001880

P0001842

P0002504

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 118 of 154

Page 119: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001363

P0001036

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 119 of 154

Page 120: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001195

P0001641; P0001642; P0001643

P0001195

P0001879

P0001796

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 120 of 154

Page 121: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001195

P0001139

P0001353

P0001355

P0001195

P0001195

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 121 of 154

Page 122: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0000488

P0000488

P0000455; P0000374; P0000484P0000455P0002544

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 122 of 154

Page 123: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0000876

P0000850

P0000579

P0001036

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 123 of 154

Page 124: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001036

P0001036

P0001036

P0001036

P0001707; P0001708

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 124 of 154

Page 125: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0002079

P0001422

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 125 of 154

Page 126: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001958

P0000542P0001191

P0000542

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 126 of 154

Page 127: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001075

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 127 of 154

Page 128: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0002526

P0002512

P0000570P0000482

P0000570

P0000602

P0000527

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 128 of 154

Page 129: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0002520

P0000396

P0000398

P0000936

P0000798; P0000799

P0000541

P0000398

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 129 of 154

Page 130: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0000830

P0001236

P0001637

P0001890

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 130 of 154

Page 131: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001081

P0001071P0001138

P0001051

P0000994P0001089

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 131 of 154

Page 132: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001195P0001195

P0001326

P0000500

P0000570

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 132 of 154

Page 133: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0000512; P0000575

P0000394

P0000394

P0000484

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 133 of 154

Page 134: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0000484

P0000394; P0000513

P0000483

P0000728

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 134 of 154

Page 135: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001675; P0000870

P0000900; P0000901; P0000902; P0000903; P0000904; P0000905; P0000906; West side P0000912

P0000928

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 135 of 154

Page 136: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0000168; P0000175

P0000781

P0001844

P0001430

P0002222

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 136 of 154

Page 137: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 137 of 154

Page 138: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 138 of 154

Page 139: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001404

P0001494

P0001302

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 139 of 154

Page 140: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0002327

P0002326

P0000872

P0000844

P0000871; P0000872P0000854

P0001014

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 140 of 154

Page 141: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001042

P0000543

P0000708

P0000682

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 141 of 154

Page 142: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0000971

P0000972

P0001105

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 142 of 154

Page 143: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0000540

P0002139

P0002139

P0002139P0000167P0001617

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 143 of 154

Page 144: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001401

P0001434

P0001625

P0001465P0001625

P0001162

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 144 of 154

Page 145: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0000598

P0001453; P0001455; P0001456; P0001457

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 145 of 154

Page 146: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001583

P0001617

P0001617P0001617

P0001617

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 146 of 154

Page 147: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001617

P0001617

P0001617

P0001617

P0001617

P0001585

P0001755

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 147 of 154

Page 148: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0000972

P0000972

P0001830

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 148 of 154

Page 149: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001971

P0000942

P0002313

P0002220; P0002221

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 149 of 154

Page 150: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001511

P0001511

P0001419

P0001419

P0001276P0001279

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 150 of 154

Page 151: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001298; P0001299; P0001311

P0001359

P0001341

P0001295

P0001034

P0001155

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 151 of 154

Page 152: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

P0001427P0001427

P0001427

P0001079

P0001500

P0001500

P0001500

P0001500

P0001500

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 152 of 154

Page 153: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 153 of 154

Page 154: ID Spec. Section  · AB2-1.01 P000 1799.jpg 2064 01400 Academy Houses General Contracting Trash at inside of wall void spaces and stud wall bottom tracks, typical. AB2-1.02

Other Images

ORMATION IS TION MUST STILL

<1> Specification Section as determined by the Inspector of Record (IOR).<2> Corresponds to the image numbers on the "Index of Deficiency Photographs".

Print Date: 7/3/01 Page 154 of 154