ida indoor climate and energy on the effects of decoupling air flow and heat balance in building...
TRANSCRIPT
![Page 1: IDA Indoor Climate and Energy On the effects of decoupling air flow and heat balance in building simulation models Per Sahlin EQUA Simulation AB Stockholm,](https://reader036.vdocument.in/reader036/viewer/2022062500/5697bfdc1a28abf838cb1059/html5/thumbnails/1.jpg)
IDA Indoor Climate and Energy
On the effects of decoupling air flow and heat balance in building simulation models
Per SahlinEQUA Simulation ABStockholm, Swedenwww.equa.se
IDA Simulation Environment
IDA Indoor Climate and Energy
IDA Room
IDA Road Tunnel Ventilation
![Page 2: IDA Indoor Climate and Energy On the effects of decoupling air flow and heat balance in building simulation models Per Sahlin EQUA Simulation AB Stockholm,](https://reader036.vdocument.in/reader036/viewer/2022062500/5697bfdc1a28abf838cb1059/html5/thumbnails/2.jpg)
Problem and Outline
• Why air-flow coupled thermal simulation by symbolic equations and general-purpose, variable-timestep DAE solvers?
• A decent GUI will be used
• Coupled models may be mathematically sticky:non-linearities + stiffness = short steps
• Will “ping-pong” decoupling help?simpler structure – stability problems > 0 ?
• Brief demo
• Test cases and results
• Alternative measures
• Summary and conclusions
![Page 3: IDA Indoor Climate and Energy On the effects of decoupling air flow and heat balance in building simulation models Per Sahlin EQUA Simulation AB Stockholm,](https://reader036.vdocument.in/reader036/viewer/2022062500/5697bfdc1a28abf838cb1059/html5/thumbnails/3.jpg)
Why DAE based building simulation?
Traditional approach:
– Flexibility
– Reuse
+ Speed?
![Page 4: IDA Indoor Climate and Energy On the effects of decoupling air flow and heat balance in building simulation models Per Sahlin EQUA Simulation AB Stockholm,](https://reader036.vdocument.in/reader036/viewer/2022062500/5697bfdc1a28abf838cb1059/html5/thumbnails/4.jpg)
Why DAE based building simulation?
GUI
Equation Based Framework
SymbolicProcessor
LanguageParser
NumericalSolver 1
NumericalSolver 2
Envelope & Zone Heat Balance
Models
Climate & Radiation
Models
Shading
Models
HVAC
Models
Industry independent Industry specific
Symbolic equation based approach:
+ Flexibility
+ Reuse
+ Secure model investment
– Speed?
![Page 5: IDA Indoor Climate and Energy On the effects of decoupling air flow and heat balance in building simulation models Per Sahlin EQUA Simulation AB Stockholm,](https://reader036.vdocument.in/reader036/viewer/2022062500/5697bfdc1a28abf838cb1059/html5/thumbnails/5.jpg)
The experiment
Full coupling:
m1-2Enthal(T1, H1), m1-2 > 0
q1-2 =
m1-2Enthal(T2, H2), m1-2 < 0
“Ping-pong” decoupling:
m1-2,oldEnthal(T1, H1), m1-2,old > 0
q1-2 =
m1-2,oldEnthal(T2, H2), m1-2,old < 0
![Page 6: IDA Indoor Climate and Energy On the effects of decoupling air flow and heat balance in building simulation models Per Sahlin EQUA Simulation AB Stockholm,](https://reader036.vdocument.in/reader036/viewer/2022062500/5697bfdc1a28abf838cb1059/html5/thumbnails/6.jpg)
Demo
Link to demo
![Page 7: IDA Indoor Climate and Energy On the effects of decoupling air flow and heat balance in building simulation models Per Sahlin EQUA Simulation AB Stockholm,](https://reader036.vdocument.in/reader036/viewer/2022062500/5697bfdc1a28abf838cb1059/html5/thumbnails/7.jpg)
Test cases and results
case decoupled execution time
family apartment two-zone constant air volume (CAV) office with open door -
13%temperature controlled variable air volume (VAV) ditto +
74%single-zone office with natural ventilation + 59%single family, naturally ventilated house
Bedroom 1Living room
Entrance
Bedroom 1Kitchen
Bathroom
0,90m
![Page 8: IDA Indoor Climate and Energy On the effects of decoupling air flow and heat balance in building simulation models Per Sahlin EQUA Simulation AB Stockholm,](https://reader036.vdocument.in/reader036/viewer/2022062500/5697bfdc1a28abf838cb1059/html5/thumbnails/8.jpg)
Alternative measures
Apartment case:
fanout=5 simpl.
zone
kmax=2,
n_jac=4, tol=0.2
no internal LVOs
execution time
√
- 46%
√ √
- 59%
√ √ √
- 67%
√ √ √ √ - 79%
![Page 9: IDA Indoor Climate and Energy On the effects of decoupling air flow and heat balance in building simulation models Per Sahlin EQUA Simulation AB Stockholm,](https://reader036.vdocument.in/reader036/viewer/2022062500/5697bfdc1a28abf838cb1059/html5/thumbnails/9.jpg)
Summary and conclusions
•“Ping-pong” decoupling provided minor improvements for some cases.
•It also gave rise to fatal instabilities, making the approach unattractive
•A combination of other means proved effective in dealing with the problematic Apartment case
•Packaging and automating the application of such means seems to be a viable alternative
![Page 10: IDA Indoor Climate and Energy On the effects of decoupling air flow and heat balance in building simulation models Per Sahlin EQUA Simulation AB Stockholm,](https://reader036.vdocument.in/reader036/viewer/2022062500/5697bfdc1a28abf838cb1059/html5/thumbnails/10.jpg)
Questions and discussion
On the effects of decoupling air flow and heat balance in building simulation models
Per SahlinEQUA Simulation ABStockholm, Swedenwww.equa.se