identify your kit

12
1 Thank you for choosing Hydro-Core. This valve kit was designed to facilitate installation and regular maintenance of your boiler. It was not designed for installations exposed to subfreezing conditions. Drain valves should remain closed during normal operation. Do not rely on the drain cap to stop the water from draining. When draining, always remove drain caps slowly to ensure that no pressure exists. IMPORTANT: Follow all federal/national, state and local codes when installing or performing work on systems. All parts are covered by a lifetime warranty against manufacturing defects provided they are installed by a licensed plumber and operated under normal working conditions. Disassembling parts other than the unions, strainer and handle will void this warranty. If you have any questions or comments, please contact us at (800) 225-9529 or visit us on the web - www.webstonevalves.com. INSTALLATION Hydro-Core Flex Introduction ................... 2 Complete Kits, Boilers with Internal Circulator Pumps ........................ 3 Complete Kits, Boilers with External Circulator Pumps .................. 4–5 Near Boiler Component Kits ................ 6–7 Manifold-Only Kits .................................. 8 Parts and Accessories ............................ 8 SERVICING Secondary System Purging ...................... 9 Filling/Power Purging ............................ 10 Strainer Servicing ................................ 11 Boiler Heat Exchanger Descaling/Cleaning ............................. 12 Kits with two rigid copper supply lines Kits with one rigid copper & one Hydro-Core Flex line Kits with two Hydro-Core Flex lines NEAR BOILER COMPONENT KITS Kits not including pre-fabricated supply lines Kits with Manifold and Union Connection only Identify Your Kit BOILERS WITH EXTERNAL CIRCULATOR PUMPS . . . . . . . . . . . . . . . . . . . . . . PAGES 4–5 BOILERS WITH EXTERNAL CIRCULATOR PUMPS . . . . . . . . . . . . . . . . . . . . . . PAGES 6–7 ALL BOILER STYLES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PAGE 8 BOILERS WITH INTERNAL CIRCULATOR PUMPS . . . . . . . . . . . . . . . . . . . . . . . . . . PAGE 3 4CC4-080 4CC4-105 4CC4-150 4CC4-210 4CC4-WHN 4CC4L-080 4CC4L-105 4CC4L-150 4CC4L-210 IPS SYSTEM PIPING 8CC4-080 8CC4-105 8CC4-150 8CC4-210 8CC4-WHN 8CC4L-080 8CC4L-105 8CC4L-150 8CC4L-210 PRESS SYSTEM PIPING 4CF4-FS184 4CF4-WH154 4CF4-WH1R44 4CF4-WH1R54 4CF4L-FT144 4CF4L-WH144 4CF4L-WHNHB 4CF4R-FT144 4CF4R-WH144 4CF5-FS185 4CF5-FT245 4CF5-FT2R45 4CF5-WH255 4CF5L-WH245 4CF5R-WH245 IPS SYSTEM PIPING 8CF4-FS184 8CF4-WH154 8CF4-WH1R44 8CF4-WH1R54 8CF4L-FT144 8CF4L-WH144 8CF4L-WHNHB 8CF4R-FT144 8CF4R-WH144 8CF5-FS185 8CF5-FT245 8CF5-FT2R45 8CF5-WH255 8CF5L-WH245 8CF5R-WH245 PRESS SYSTEM PIPING 4FK3-WIF 4FK3-WIF-18 4FK3-WIF-18-2 4FK3-WIS 4FK3-WIS-18 4FK4-WIF 4FK4-WIF-18 4FK4-WIS-18 4FK5-CH IPS SYSTEM PIPING 8FK3-WIF 8FK3-WIF-18 8FK3-WIF-18-2 8FK3-WIS 8FK3-WIS-18 8FK4-WIF 8FK4-WIF-18 8FK4-WIS-18 8FK5-CH PRESS SYSTEM PIPING 48754-FS144 48754-FS184 48754-FT144 48754-FT344 48754-WH144 48754-WH154 48754-WH1R44 48754-WH1R54 48765-FS145 48765-FS185 48765-FS245 48765-FS345 48765-FT245 48765-FT2R45 48765-WH245 48765-WH255 48765-WH345 48854-FS144 48854-FS184 48854-FT144 48854-WH144 48854-WHNHB 48865-WH245 IPS SYSTEM PIPING 88754-FS144 88754-FS184 88754-FT144 88754-FT344 88754-WH144 88754-WH154 88754-WH1R44 88754-WH1R54 88765-FS145 88765-FS185 88765-FS245 88765-FS345 88765-FT245 88765-FT2R45 88765-WH245 88765-WH255 88765-WH345 88854-FS144 88854-FS184 88854-FT144 88854-WH144 88854-WHNHB 88865-WH245 PRESS SYSTEM PIPING 48354-43 48354-44 48754-43 48754-44 48755-45 48764-44 48765-45 48766-56 48854-43 48854-44 48855-45 48864-44 48865-45 IPS SYSTEM PIPING 88354-43 88354-44 88354-53 88354-54 88754-43 88754-44 88754-53 88754-54 88755-45 88755-55 88764-44 88764-54 88765-45 88765-55 88766-56 88854-43 88854-44 88854-53 88854-54 88855-45 88855-55 88864-44 88864-54 88865-45 88865-55 PRESS SYSTEM PIPING 5CC4-080 5CC4-105 5CC4-150 5CC4-210 5CC4-WHN 5CC4L-080 5CC4L-105 5CC4L-150 5CC4L-210 SWT SYSTEM PIPING 5CF4-FS184 5CF4-WH154 5CF4-WH1R44 5CF4-WH1R54 5CF4L-FT144 5CF4L-WH144 5CF4L-WHNHB 5CF4R-FT144 5CF4R-WH144 5CF5-FS185 5CF5-FT245 5CF5-FT2R45 5CF5-WH255 5CF5L-WH245 5CF5R-WH245 SWT SYSTEM PIPING 5FK3-WIF 5FK3-WIF-18 5FK3-WIF-18-2 5FK3-WIS 5FK3-WIS-18 5FK4-WIF 5FK4-WIF-18 5FK4-WIS-18 5FK5-CH SWT SYSTEM PIPING 58754-FS144 58754-FS184 58754-FT144 58754-FT344 58754-WH144 58754-WH154 58754-WH1R44 58754-WH1R54 58765-FS145 58765-FS185 58765-FS245 58765-FS345 58765-FT245 58765-FT2R45 58765-WH245 58765-WH255 58765-WH345 58775-FS185 58854-FS144 58854-FS184 58854-FT144 58854-WH144 58854-WHNHB 58865-WH245 SWT SYSTEM PIPING 58354-43 58354-53 58354-54 58744-53 58744-54 58754-53 58754-54 58755-55 58764-54 58765-55 58766-56 58774-44 58775-45 58776-56 58854-43 58854-54 58855-55 58864-54 58865-55 SWT SYSTEM PIPING COMPLETE NEAR BOILER PIPING KITS MANIFOLD ONLY

Upload: others

Post on 12-May-2022

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Identify Your Kit

1

Thank you for choosing Hydro-Core. This valve kit was designed to facilitate installation and regular maintenance of your boiler. It was not designed for installations exposed to subfreezing conditions. Drain valves should remain closed during normal operation. Do not rely on the drain cap to stop the water from draining. When draining, always remove drain caps slowly to ensure that no pressure exists.

IMPORTANT: Follow all federal/national, state and local codes when installing or performing work on systems. All parts are covered by a lifetime warranty against manufacturing defects provided they are installed by a licensed plumber and operated under normal working conditions. Disassembling parts other than the unions, strainer and handle will void this warranty. If you have any questions or comments, please contact us at (800) 225-9529 or visit us on the web - www.webstonevalves.com.

INSTALLATIONHydro-Core Flex Introduction ................... 2

Complete Kits, Boilers with Internal Circulator Pumps ........................ 3

Complete Kits, Boilers with External Circulator Pumps .................. 4–5

Near Boiler Component Kits ................ 6–7

Manifold-Only Kits .................................. 8

Parts and Accessories ............................ 8

SERVICINGSecondary System Purging ...................... 9

Filling/Power Purging ............................ 10

Strainer Servicing ................................ 11

Boiler Heat Exchanger Descaling/Cleaning ............................. 12

Kits with two rigid copper supply lines

Kits with one rigid copper & one Hydro-Core Flex line

Kits with two Hydro-Core Flex lines

NEAR BOILER COMPONENT

KITS

Kits not including pre-fabricated supply lines

Kits with Manifold and Union Connection only

Identify Your KitBOILERS WITH EXTERNAL CIRCULATOR PUMPS . . . . . . . . . . . . . . . . . . . . . .PAGES 4–5

BOILERS WITH EXTERNAL CIRCULATOR PUMPS . . . . . . . . . . . . . . . . . . . . . . PAGES 6–7

ALL BOILER STYLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PAGE 8

BOILERS WITH INTERNAL CIRCULATOR PUMPS . . . . . . . . . . . . . . . . . . . . . . . . . . PAGE 3

4CC4-0804CC4-1054CC4-1504CC4-2104CC4-WHN

4CC4L-0804CC4L-1054CC4L-1504CC4L-210

IPS SYSTEM PIPING

8CC4-0808CC4-1058CC4-1508CC4-2108CC4-WHN

8CC4L-0808CC4L-1058CC4L-1508CC4L-210

PRESS SYSTEM PIPING

4CF4-FS1844CF4-WH1544CF4-WH1R444CF4-WH1R544CF4L-FT1444CF4L-WH1444CF4L-WHNHB4CF4R-FT144

4CF4R-WH1444CF5-FS1854CF5-FT2454CF5-FT2R454CF5-WH2554CF5L-WH2454CF5R-WH245

IPS SYSTEM PIPING

8CF4-FS1848CF4-WH1548CF4-WH1R448CF4-WH1R548CF4L-FT1448CF4L-WH144 8CF4L-WHNHB8CF4R-FT144

8CF4R-WH1448CF5-FS1858CF5-FT2458CF5-FT2R458CF5-WH2558CF5L-WH2458CF5R-WH245

PRESS SYSTEM PIPING

4FK3-WIF4FK3-WIF-184FK3-WIF-18-24FK3-WIS4FK3-WIS-18

4FK4-WIF4FK4-WIF-18 4FK4-WIS-184FK5-CH

IPS SYSTEM PIPING

8FK3-WIF8FK3-WIF-188FK3-WIF-18-28FK3-WIS8FK3-WIS-18

8FK4-WIF8FK4-WIF-18 8FK4-WIS-188FK5-CH

PRESS SYSTEM PIPING

48754-FS14448754-FS18448754-FT14448754-FT34448754-WH14448754-WH15448754-WH1R4448754-WH1R5448765-FS14548765-FS18548765-FS24548765-FS345

48765-FT24548765-FT2R4548765-WH24548765-WH25548765-WH34548854-FS14448854-FS18448854-FT14448854-WH14448854-WHNHB48865-WH245

IPS SYSTEM PIPING

88754-FS14488754-FS18488754-FT14488754-FT34488754-WH14488754-WH15488754-WH1R4488754-WH1R5488765-FS14588765-FS18588765-FS24588765-FS345

88765-FT24588765-FT2R4588765-WH24588765-WH25588765-WH34588854-FS14488854-FS18488854-FT14488854-WH14488854-WHNHB88865-WH245

PRESS SYSTEM PIPING

48354-4348354-4448754-4348754-4448755-4548764-4448765-4548766-5648854-4348854-44

48855-4548864-4448865-45

IPS SYSTEM PIPING

88354-4388354-4488354-5388354-5488754-4388754-4488754-5388754-5488755-4588755-55

88764-4488764-5488765-4588765-5588766-5688854-4388854-4488854-5388854-5488855-45

88855-5588864-4488864-5488865-4588865-55

PRESS SYSTEM PIPING

5CC4-0805CC4-1055CC4-1505CC4-2105CC4-WHN

5CC4L-0805CC4L-1055CC4L-1505CC4L-210

SWT SYSTEM PIPING

5CF4-FS1845CF4-WH1545CF4-WH1R445CF4-WH1R545CF4L-FT1445CF4L-WH1445CF4L-WHNHB5CF4R-FT144

5CF4R-WH1445CF5-FS1855CF5-FT2455CF5-FT2R455CF5-WH2555CF5L-WH2455CF5R-WH245

SWT SYSTEM PIPING

5FK3-WIF5FK3-WIF-185FK3-WIF-18-25FK3-WIS5FK3-WIS-18

5FK4-WIF5FK4-WIF-185FK4-WIS-185FK5-CH

SWT SYSTEM PIPING

58754-FS14458754-FS18458754-FT14458754-FT34458754-WH14458754-WH15458754-WH1R4458754-WH1R5458765-FS14558765-FS18558765-FS24558765-FS345

58765-FT24558765-FT2R4558765-WH24558765-WH25558765-WH34558775-FS18558854-FS14458854-FS18458854-FT14458854-WH14458854-WHNHB58865-WH245

SWT SYSTEM PIPING

58354-4358354-5358354-5458744-5358744-5458754-5358754-5458755-5558764-5458765-55

58766-5658774-4458775-4558776-5658854-4358854-5458855-5558864-5458865-55

SWT SYSTEM PIPING

COMPLETE NEAR BOILER PIPING KITS

MANIFOLDONLY

Page 2: Identify Your Kit

2

REMOVE 1"INSULATION

CUT MUST BE CENTERED

IN CONVOLUTION

NUT ISOLATION RING

SILICONE RING

FITTING

4-5 CORRUGATIONS

1. Remove the nut and check that the fi tting internal components are in place (silicone ring and isolation ring).

2. Replace the loosened nut and internal components as shown in the illustration to the right. Turn the nut clockwise two revolutions on the threads. Before tightening the nut, insert the tubing completely in the fi tting to the tubing stop until it meets the internal wall. If done correctly, the tubing should be approximately one inch, or four to fi ve corrugations inside the fi tting.

3. Hold the fi tting on the pipe and tighten the nut onto the fi tting using the appropriate torque as shown in the table below.

Tube Size (Inch) 3/4" 1" 1 1/4"

Torque Value (Ft./lb) ≈44–48 ≈72–76 ≈120–140

Specifi cations & Preparing for Installation (not applicable to all kits)

To Cut Tubing (If Desired)

IMPORTANT!Tighten End Connections

The amount of Hydro-Core Flex Piping provided is suitable for wide range of boilers. However, tubing may be cut to suit the needs of your specifi c installation if so desired. Retaining excess length will not effect the performance of the system.

1. Remove end connections.

2. Measure the desired pipe length and mark this point on the insulation.

3. Remove the insulation beyond this mark – DO NOT CUT THE TUBING.

4. Measure one inch of exposed pipe above the insulation. This is the cut point.

5. Using a metal tube cutter, cut the tube at the cut point. Cut MUST be centered in a valley between corrugations.

6. Insert tube into the fi tting, then tighten end connections.

Warning:

• To avoid crimping the pipe, DO NOT use excess force.

• Cut must be a clean cut. A rough cut with irregular edges can perforate the silicone ring and cause leakage.

• Caution should be used when handling the fl ex piping with the end fi ttings removed due to potential for injury on a sharp edge.

• Included in select Complete Near Boiler Piping Kits

• Flexible Supply/Return lines designed to accommodate a wide variety of boiler installations

• Tubing may be cut for installations in close quarters

PATENTS PENDING

Flex Pipe Conforms to NSF/ANSI 61,

ASTM A 312/312M, IAMPO, IGC-233

3/4" 1" 1 1/4"

Inner Diameter 0.83" 1.03" 1.26Max Operating Temperature 212° 212° 212°Max Cold Working Pressure 176 PSI 147 PSI 110 PSI

Page 3: Identify Your Kit

3

HYDROCORE MANIFOLDA

Union Ball ValveConnection

Union Ball ValveConnection

SYSTEM SUPPLYPIPED ASSEMBLY

SYSTEM RETURNPIPED ASSEMBLY

System Return Port /Boiler Inlet

System Supply Port /Boiler Outlet

CB

Union Nut Union Nut

BOILER

HYDROCORE MANIFOLDA

Union Ball ValveConnection

Union Ball ValveConnection

SYSTEM SUPPLYPIPED ASSEMBLY

SYSTEM RETURNPIPED ASSEMBLY

System Return Port /Boiler Inlet

System Supply Port /Boiler Outlet

CB

Union Nut Union Nut

BOILER

Union Ball ValveConnection

Union Ball ValveConnection

Pressure Relief Valve

(150 PSI)

Pressure Relief Valve (30 PSI)

SYSTEM SUPPLYPIPED ASSEMBLY

SYSTEM RETURNPIPED ASSEMBLY

System Return Port /Boiler Inlet

System Supply Port / Boiler Outlet

Domestic Water /

Hot Outlet

Domestic Water /

Cold Inlet

C

B

Union NutUnion Nut

Pressure Gauge

HYDROCORE MANIFOLDA

BOILER

Complete Near Boiler Piping Kit InstallationsBOILERS WITH INTERNAL CIRCULATOR PUMPS

WARNING! • Both end connections of the fl ex piping are loosely assembled at the factory & MUST be properly tightened as part of product installation.

Caution should be used when handling the fl ex piping with the end fi ttings removed due to potential for injury on a sharp edge.

Before Installation • Review boiler manufacturers’ installation literature for any required/recommended clearances for manifold installation.

Installation PRESS CONNECTIONS: See Pro-Connect Press Installation Instructions for specifi c requirements. 1. Establish the “as installed” location of the Hydro-Core Manifold .

2. Bend the System Supply Piped Assembly and System Return Piped Assembly to the desired path using the maximum radius possible to minimize the frictional losses.

3. Adjust the System Supply Piped Assembly and System Return Piped Assembly length as desired per the instructions provided on page 2 making sure to include the length of piping installed into the fi ttings on both ends.

4. Tighten the end connection on both ends of each fl ex pipe & per the instructions provided on page 2.

5. Loosely assemble the System Supply Piped Assembly and System Return Piped Assembly to the respective boiler ports.

6. Connect the union nut of the System Supply Piped Assembly and System Return Piped Assembly to the respective Hydro-Core Manifold ports and fully tighten.

7. Support the near boiler piping assembly with hangers and clamps.

8. Connect the Hydro-Core Manifold to the remaining hydronic system.

9. Fully tighten the System Supply Piped Assembly and System Return Piped Assembly fi ttings at the boiler.

10. Combi Boiler Kits (4FK5-CH/ 5FK5-CH): Remove side pipe plug from System Supply Piped Assembly and screw the 30 PSI pressure relief valve into the threaded port. The discharge line from the PRV should pitch downward and terminate 6" above drains where discharge will be clearly visible. The discharge end of the line shall be plain (unthreaded) and a minimum of 3/4" in diameter. The discharge line material must be suitable for water at least 180° Fahrenheit. The discharge line shall be as short and straight as possible such that the arrangement does not reduce the relieving capacity of the pressure relief valve. No valve of any type may be installed in the discharge line of the pressure relief valve. See included Isolator EXP/E2/E3 directions for Domestic Water installation and servicing directions.

11. Pressure test the system to ensure that all connections are pressure tight. Caution should be used during all pressure testing to avoid potential personal injury.

FOR WALL HUNG BOILERS WITH

INTERNAL CIRCULATOR PUMPS

PRESS SYSTEM PIPING

IPS SYSTEM PIPING

SWT SYSTEM PIPING

8FK3-WIF 8FK3-WIF-18-2

8FK3-WIS8FK4-WIF

4FK3-WIF 4FK3-WIF-18-2

4FK3-WIS4FK4-WIF

5FK3-WIF 5FK3-WIF-18-2

5FK3-WIS5FK4-WIF

FOR WALL HUNG BOILERS WITH

INTERNAL CIRCULATOR PUMPS

PRESS SYSTEM PIPING

IPS SYSTEM PIPING

SWT SYSTEM PIPING

8FK3-WIF-188FK3-WIS-188FK4-WIF-188FK4-WIS-18

4FK3-WIF-184FK3-WIS-184FK4-WIF-184FK4-WIS-18

5FK3-WIF-185FK3-WIS-185FK4-WIF-185FK4-WIS-18

FOR SELECT COMBI BOILERS

PRESS SYSTEM PIPING

IPS SYSTEM PIPING

SWT SYSTEM PIPING

8FK5-CH 4FK5-CH 5FK5-CH

Boilers shown for illustration purposes only.

COMPLETE NEAR BOILER PIPING KITS

Page 4: Identify Your Kit

4 Boilers shown for illustration purposes only. Boiler fi ttings may vary from illustration.

WARNING! • Both end connections of the fl ex piping are loosely

assembled at the factory & MUST be properly tightened as part of product installation. Caution should be used when handling the fl ex piping with the end fi ttings removed due to potential for injury on a sharp edge.

Before Installation • The Circulator Pump is sold separately (see

the boiler manufacturer for recommendation on suitable models). The Hydro-Core kits are designed to accommodate a 6 1/2" long circulator pump.

• Review boiler manufacturers’ installation literature for any required/recommended clearances for manifold installation.

InstallationPRESS CONNECTIONS: See Pro-Connect Press Installation Instructions for specifi c requirements.

1. Disassembled the System Supply and Return Supply Union Connections from their respective piped assemblies.

2. Assemble the System Supply and Return Supply Union Connections to their respective boiler ports.

3. Loosely connect the Circulator Pump to the Hydro-Core fl anged ball valve connection making sure the fl ange gaskets are properly located. IMPORTANT: Verify the installation direction of the circulator pump, it should pump into the boiler.

4. Loosely connect the Circulator Pump fl ange to the fl ange on the System Return Piped Assembly .

5. Follow the instructions for your installation type.

COPPER/COPPER - Loosely connect the union nut on the System Supply Piped Assembly to the Hydro-Core union ball valve connection. Loosely connect the System Supply Piped Assembly and System Return Piped Assembly Union to their respective union connections already connected to the boiler.

COPPER/FLEX - Loosely connect the System Return Piped Assembly to the Return Supply Union Connection already connected to the boiler.

6. Align the Circulator Pump to the desired position ensuring that both gaskets are properly aligned.

7. Fully tighten the bolts to the two-fl anged connections on the Circulator Pump (Hydro-Core and pipe sides).

8. Follow the instructions for your installation type.

COPPER/COPPER - Fully tighten the System Supply union nut to the Hydro-Core union ball valve connection. Fully tighten the union nuts of the System Supply andReturn Supply Union.

COPPER/FLEX - Fully tighten the union nut of the Return Piped Assembly and System Return Union Connection.

9. Support the near boiler piping assembly with hangers and clamps.

10. COPPER/FLEX INSTALLATION ONLY (COPPER/COPPER skip to step 11)

A Bend the fl ex line of the System Supply Piped Assembly to the desired path using the maximum radius possible to minimize the frictional losses.

B Adjust the fl ex pipe length as desired/required per the instructions provided on page 2 making sure to include the length of piping installed into the fi ttings on both ends.

C Tighten the fl ex pipe end connection on both ends per the instructions provided on page 2.

D Connect & fully tighten the System Supply Piped Assembly to the system supply Union Connection at the boiler.

E Connect and fully tighten the union nut on the System Supply Piped Assembly to the Hydro-Core union ball valve connection.

11. Connect the Hydro-Core Manifold to the remaining hydronic system.

12. Pressure test the system to ensure that all connections are pressure tight. Caution should be used during all pressure testing to avoid potential personal injury.

Complete Near Boiler Piping Kit InstallationsBOILERS WITH EXTERNAL CIRCULATOR PUMPSCOMPLETE NEAR

BOILER PIPING KITS

UNION CONNECTION

UNIONCONNECTION

Union Nut Union Nut

Union Nut

Union Ball ValveConnection

Rotating FlangeBall ValveConnection

CIRCULATORPUMP

HYDROCORE MANIFOLD

SYSTEM SUPPLYPIPED ASSEMBLY

SYSTEM RETURNPIPED ASSEMBLY

System Return Port /Boiler Inlet

System Supply Port /Boiler Outlet

D

A

C

B

E F

Rotating Flange

BOILER

FOR WALL HUNG BOILERS

PRESS SYSTEM PIPING

IPS SYSTEM PIPING

SWT SYSTEM PIPING

8CC4-WHN 4CC4-WHN 5CC4-WHN

FOR WALL HUNG BOILERS

PRESS SYSTEM PIPING

IPS SYSTEM PIPING

SWT SYSTEM PIPING

8CF4L-WH1448CF5L-WH245

4CF4L-WH1444CF5L-WH245

5CF4L-WH1445CF5L-WH245

UNIONCONNECTION

UNIONCONNECTION

Union Nut

Union Nut

Union Ball Valve

Connection

Rotating Flange

Ball Valve Connection

CIRCULATORPUMP

HYDROCORE MANIFOLD

SYSTEM SUPPLY PIPED ASSEMBLY

SYSTEM RETURNPIPED ASSEMBLY

System Return Port /Boiler Inlet

System Supply Port /Boiler Outlet

D

A

C

B

E

F

Rotating Flange

Union NutBOILER

Page 5: Identify Your Kit

5Boilers shown for illustration purposes only. Boiler fi ttings may vary from illustration.

UNION CONNECTION

UNIONCONNECTION

Union NutUnion Nut

Union Ball ValveConnection

Rotating FlangeBall Valve Connection

CIRCULATORPUMP

HYDROCORE MANIFOLD

SYSTEM SUPPLY PIPED ASSEMBLY

SYSTEM RETURNPIPED ASSEMBLY

System Return Port /Boiler Inlet

System Supply Port /Boiler Outlet

D

A

C

B

E F

Rotating Flange“Y” Strainer

Union Nut

BOILER

Union Nut Union Nut

Union Ball ValveConnection

Rotating FlangeBall Valve Connection

System Return Port /Boiler Inlet

System Supply Port /Boiler Outlet

CIRCULATORPUMP

D

HYDROCORE MANIFOLDA

SYSTEM RETURNPIPED ASSEMBLY

C

SYSTEM SUPPLY PIPED ASSEMBLY

B

UNIONCONNECTION E

UNION CONNECTIONF

Rotating Flange

Union Nut

BOILER

FOR FLOOR STANDING,

TOP MOUNT BOILERS

PRESS SYSTEM PIPING

IPS SYSTEM PIPING

SWT SYSTEM PIPING

8CF4L-FT144 4CF4L-FT144 5CF4L-FT144

Union Nut

HYDROCORE MANIFOLDA

UNION CONNECTION

UNIONCONNECTION

Union Nut Union Nut

Union Ball ValveConnection

Rotating FlangeBall ValveConnection

CIRCULATORPUMP

SYSTEM SUPPLYPIPED ASSEMBLY

SYSTEM RETURNPIPED ASSEMBLY

System Return Port /Boiler Inlet

System Supply Port /Boiler Outlet

D

C

B

E F

Rotating Flange

BOILER

FOR WALL HUNG BOILERS

PRESS SYSTEM PIPING

IPS SYSTEM PIPING

SWT SYSTEM PIPING

8CF4-WH1548CF4-WH1R448CF4-WH1R548CF4R-WH1448CF5R-WH245

4CF4-WH1544CF4-WH1R444CF4-WH1R544CF4R-WH1444CF5R-WH245

5CF4-WH1545CF4-WH1R445CF4-WH1R545CF4R-WH1445CF5R-WH245

FOR WALL HUNG BOILERS

PRESS SYSTEM PIPING

IPS SYSTEM PIPING

SWT SYSTEM PIPING

8CF4L-WHNHB8CF5-WH255

4CF4L-WHNHB4CF5-WH255

5CF4L-WHNHB5CF5-WH255

FOR FLOOR STANDING,

TOP MOUNT BOILERS

PRESS SYSTEM PIPING

IPS SYSTEM PIPING

SWT SYSTEM PIPING

8CF4R-FT1448CF5-FT245

8CF5-FT2R45

4CF4R-FT1444CF5-FT245

4CF5-FT2R45

5CF4R-FT1445CF5-FT245

5CF5-FT2R45

UNION CONNECTION

UNION CONNECTION

Union NutUnion Nut

Union Nut

Union Ball Valve Connection

Rotating FlangeBall Valve

Connection

BO

ILE

R

CIRCULATORPUMP

HYDROCORE MANIFOLD

SYSTEM SUPPLY PIPED ASSEMBLY

SYSTEM RETURNPIPED ASSEMBLY

System Return Port /Boiler Inlet

System Supply Port /Boiler Outlet

D

A

C

B

E

F

Rotating Flange“Y” Strainer

FOR FLOOR STANDING,

SIDE MOUNT BOILERS

PRESS SYSTEM PIPING

IPS SYSTEM PIPING

SWT SYSTEM PIPING

8CC4-0808CC4-1058CC4-1508CC4-2108CC4L-0808CC4L-1058CC4L-1508CC4L-210

4CC4-0804CC4-1054CC4-1504CC4-2104CC4L-0804CC4L-1054CC4L-1504CC4L-210

5CC4-0805CC4-1055CC4-1505CC4-2105CC4L-0805CC4L-1055CC4L-1505CC4L-210

FOR FLOOR STANDING,

SIDE MOUNT BOILERS

PRESS SYSTEM PIPING

IPS SYSTEM PIPING

SWT SYSTEM PIPING

8CF4-FS1848CF5-FS185

4CF4-FS1844CF5-FS185

5CF4-FS1845CF5-FS185

HYDROCORE MANIFOLD

System Return Port /Boiler Inlet

System Supply Port /Boiler Outlet

A

UNIONCONNECTION

UNIONCONNECTION

Union Nut Union Nut

Union Ball ValveConnection

Rotating FlangeBall Valve Connection

CIRCULATORPUMP SYSTEM SUPPLY

PIPED ASSEMBLY

SYSTEM RETURNPIPED ASSEMBLY

D

C

B

EF

Rotating Flange“Y” Strainer

Union Nut

BOILERUNION

CONNECTION

UNION CONNECTION

Union NutUnion Nut

Union Nut

Union Ball Valve Connection

Rotating FlangeBall Valve

Connection

BO

ILE

R

CIRCULATORPUMP

HYDROCORE MANIFOLD

SYSTEM SUPPLY PIPED ASSEMBLY

SYSTEM RETURNPIPED ASSEMBLY

System Return Port /Boiler Inlet

System Supply Port /Boiler Outlet

D

A

C

B

E

F

Rotating Flange“Y” Strainer

Page 6: Identify Your Kit

6

Before Installation • Circulator Pump sold separately (see boiler manufacturer for suitable models).

Installation PRESS CONNECTIONS: See Pro-Connect Press Installation Instructions for specifi c requirements.

1. Fabricate the System Return Piped Assembly: Solder the Flanged Pump Connection and Union Body Component to opposite ends of a length of copper tubing sized appropriately for your boiler’s return line.

2. Remove the o-ring from the Hydro-Core End and save for reinstallation.

3. Fabricate the System Supply Piped Assembly:Solder the Hydro-Core End and Union Body Component to either ends of a length of copper tubing sized appropriately for your boiler’s supply line.

4. Assemble the System Supply Union Connection to the system supply port.

5. Assemble the System Return Union Connection to the system return port.

6. Loosely connect the Circulator to the Hydro-Core fl anged ball valve connection. IMPORTANT: The Circulator should pump into the boiler.

7. Loosely connect the Circulator fl ange to the fl ange on the System Return Piped Assembly.

8. Loosely connect the union nut, o-ring and fi tting on the System Supply Piped Assembly to the Hydro-Core union ball valve connection.

9. Connect the System Supply and System Return Union Connections to their respective piped assemblies.

10. Align the Circulator into the desired position. Ensure both pump gaskets are properly aligned.

11. Fully tighten the bolts to the two fl anged connections.

12. Fully tighten the union nut to the Hydro-Core union ball valve connection.

13. Fully tighten the union nuts to the union fi ttings at the boiler.

14. Support the near boiler piping assembly with hangers and clamps.

15. Connect the Hydro-Core Manifold to the remaining hydronic system.

16. Pressure test the system to ensure that all connections are pressure tight. Caution should be used during all pressure testing to avoid potential personal injury.

NEAR BOILER COMPONENT KITS

Near Boiler Component Kit Installations

UNIONBODY

UNIONBODY

FLANGED PUMPCONNECTION

HYDRO-CORE END

Union NutUnion Nut

Union Nut

BO

ILE

R

System Return Port / Boiler Inlet

System Supply Port / Boiler Outlet

Cop

per Tu

bin

g

Cop

per Tu

bin

g

Union Ball Valve Connection

Rotating FlangeBall Valve

Connection

UNION CONNECTION

UNION CONNECTION

CIRCULATORPUMP

HYDROCORE MANIFOLD

D

A

H

G

E

F

I

J

UNIONBODY

UNIONBODY

FLANGED PUMPCONNECTION

HYDRO-CORE END

Union NutUnion Nut

Union Nut

BO

ILE

R

Cop

per Tu

bin

g

Cop

per Tu

bin

g

Union Ball Valve Connection

Rotating FlangeBall Valve

Connection

UNION CONNECTION

UNION CONNECTION

CIRCULATORPUMP

HYDROCORE MANIFOLD

D

A

H

G

E

F

I

J

System Return Port / Boiler Inlet

System Supply Port / Boiler Outlet

UNIONBODY

UNIONBODY

FLANGED PUMPCONNECTION

HYDRO-COREEND

Union NutUnion Nut

Union Nut

BO

ILE

R

System Return Port /Boiler Inlet

System Supply Port /Boiler Outlet

Cop

per Tu

bin

g

Cop

per Tu

bin

g

Union Ball Valve Connection

Rotating FlangeBall ValveConnection

UNION CONNECTION

UNION CONNECTION

CIRCULATORPUMP

HYDROCORE MANIFOLD

D

A

H

G

E

F

I

J

FOR FLOOR STANDING, SIDE MOUNT BOILERS

PRESS SYSTEM PIPING

IPS SYSTEM PIPING

SWT SYSTEM PIPING

88754-FS14488754-FS18488765-FS14588765-FS18588854-FS14488854-FS184

48754-FS14448754-FS18448765-FS14548765-FS18548854-FS14448854-FS184

58754-FS14458754-FS18458765-FS14558765-FS18558775-FS18558854-FS14458854-FS184

FOR FLOOR STANDING, SIDE MOUNT BOILERS

PRESS SYSTEM PIPING

IPS SYSTEM PIPING

SWT SYSTEM PIPING

88765-FS245 48765-FS245 58765-FS245

FOR FLOOR STANDING, SIDE MOUNT BOILERS

PRESS SYSTEM PIPING

IPS SYSTEM PIPING

SWT SYSTEM PIPING

88765-FS345 48765-FS345 58765-FS345

Boilers shown for illustration purposes only.

Page 7: Identify Your Kit

7

FOR FLOOR STANDING,

TOP MOUNT BOILERS

PRESS SYSTEM PIPING

IPS SYSTEM PIPING

SWT SYSTEM PIPING

88754-FT14488854-FT144

48754-FT14448854-FT144

58754-FT14458854-FT144

FOR FLOOR STANDING,

TOP MOUNT BOILERS

PRESS SYSTEM PIPING

IPS SYSTEM PIPING

SWT SYSTEM PIPING

88765-FT24588765-FT2R45

48765-FT24548765-FT2R45

58765-FT24558765-FT2R45

FOR FLOOR STANDING,

TOP MOUNT BOILERS

PRESS SYSTEM PIPING

IPS SYSTEM PIPING

SWT SYSTEM PIPING

88754-FT344 48754-FT344 58754-FT344

FOR WALL HUNG BOILERS

PRESS SYSTEM PIPING

IPS SYSTEM PIPING

SWT SYSTEM PIPING

88754-WH14488754-WH154

88754-WH1R4488754-WH1R5488854-WH144

48754-WH14448754-WH154

48754-WH1R4448754-WH1R5448854-WH144

58754-WH14458754-WH154

58754-WH1R4458754-WH1R5458854-WH144

FOR WALL HUNG BOILERS

PRESS SYSTEM PIPING

IPS SYSTEM PIPING

SWT SYSTEM PIPING

88765-WH24588765-WH25588854-WHNHB88865-WH245

48765-WH24548765-WH25548854-WHNHB48865-WH245

58765-WH24558765-WH25558854-WHNHB58865-WH245

FOR WALL HUNG BOILERS

PRESS SYSTEM PIPING

IPS SYSTEM PIPING

SWT SYSTEM PIPING

88765-WH345 48765-WH345 58765-WH345

UNIONBODY

UNIONBODY

FLANGED PUMPCONNECTION

HYDRO-COREEND

Union Nut Union Nut

Union Nut

BOILER

System Return Port /Boiler Inlet

System Supply Port /Boiler Outlet

Cop

per Tu

bin

g

Cop

per Tu

bin

g

Union Ball Valve Connection

Rotating FlangeBall ValveConnection

UNIONCONNECTION

UNIONCONNECTION

CIRCULATORPUMP

HYDROCORE MANIFOLD

D

A

H

G

E F

I J

UNIONBODY

UNIONBODY

FLANGED PUMPCONNECTION

HYDRO-CORE END

Union NutUnion Nut

Union Nut

BOILER

Copper Tu

bin

g

Cop

per Tu

bin

g

Union Ball Valve Connection

Rotating FlangeBall Valve

Connection

UNIONCONNECTION

UNION CONNECTION

CIRCULATORPUMP

HYDROCORE MANIFOLD

D

A

H

G

EF

IJ

System Return Port /Boiler Inlet

System Supply Port /Boiler Outlet

UNIONBODY

UNIONBODY

FLANGED PUMPCONNECTION

HYDRO-COREEND

Union Nut Union Nut

Union Nut

BOILER

Cop

per Tu

bin

g

Cop

per Tu

bin

g

Union Ball Valve Connection

Rotating FlangeBall ValveConnection

UNIONCONNECTION

UNIONCONNECTION

CIRCULATORPUMP

HYDROCORE MANIFOLD

D

A

H

G

E F

I J

System Return Port /Boiler Inlet

System Supply Port /Boiler Outlet

UNIONBODY

UNIONBODY

FLANGED PUMPCONNECTION

HYDRO-CORE END

Union NutUnion Nut

Union Nut

BOILER

System Return Port /Boiler Inlet

System Supply Port /Boiler Outlet

Copper Tu

bin

g

Cop

per Tu

bin

g

Union Ball Valve Connection

Rotating FlangeBall Valve

Connection

UNIONCONNECTION

UNION CONNECTION

CIRCULATORPUMP

HYDROCORE MANIFOLD

D

A

H

G

EF

IJ

UNIONBODY

UNIONBODY

FLANGED PUMPCONNECTION

HYDRO-COREEND

Union NutUnion Nut

Union Nut

BO

ILE

R

System Return Port / Boiler Inlet

System Supply Port / Boiler Outlet

Cop

per Tu

bin

g

Cop

per Tu

bin

g

Union Ball Valve Connection

Rotating FlangeBall ValveConnection

UNIONCONNECTION

UNIONCONNECTION

CIRCULATORPUMP

HYDROCORE MANIFOLD

D

A

H

G

F

EI

J

UNIONBODY

UNIONBODY

FLANGED PUMPCONNECTION

HYDRO-COREEND

Union Nut Union Nut

Union Nut

BOILER

System Return Port /Boiler Inlet

System Supply Port /Boiler Outlet

Cop

per Tu

bin

g

Copper Tu

bin

g

Union Ball ValveConnection

Rotating FlangeBall ValveConnection

UNIONCONNECTION

UNIONCONNECTION

CIRCULATORPUMP

HYDROCORE MANIFOLD

D

A

H

G

E F

I J

Boilers shown for illustration purposes only.

Page 8: Identify Your Kit

8

• Note: Not all installation steps applicable to all Manifold styles.

InstallationPRESS CONNECTIONS: See Pro-Connect Press Installation Instructions for specifi c requirements.

1. Remove the o-ring from the Hydro-Core End(s) and save for reinstallation.

2. Connect the Hydro-Core End (s) to branch tubing.

3. Loosely connect the Circulator to the Hydro-Core fl anged ball valve connection. IMPORTANT: The Circulator should pump into the boiler, if applicable.

4. Loosely connect the Hydro-Core End(s) union nut, o-ring and fi tting to the Hydro-Core union ball valve connection.

5. Align the Circulator into the desired position. Ensure both pump gaskets are properly aligned.

6. Fully tighten the bolts to the fl anged connection.

7. Fully tighten the union nut to the Hydro-Core union ball valve connection.

8. Support the piping assembly with hangers and clamps.

9. Connect the Hydro-Core Manifold to the remaining hydronic system.

10. Pressure test the system to ensure that all connections are pressure tight. Caution should be used during all pressure testing to avoid potential personal injury.

MANIFOLD

Manifold Only Installations

Parts and Accessories

HYDRO-CORE END

Union Nut

Bra

nch Tu

bin

g

Union Ball Valve Connection

Rotating FlangeBall Valve

Connection

CIRCULATORPUMP

HYDROCORE MANIFOLD

D

A

G

Interested in upgrading your Manifold Kit to a Complete or Component kit? Or do you have an unusual set of system requirements or a particularly unique area to work within? Craft your own kit - all Hydro-Core components are available for individual purchase. A solution is available for any given need.

MANIFOLDS UNION CONNECTIONS

PUMP CONNECTIONS BOILER CONNECTIONS

See www.webstonevalves.com/hydro-core/boilercompatiblity for a complete list of parts and accessories.

W W W . W E B S T O N E V A L V E S. C O

M

15

100

150

200kPapsi

50

0

10

5

0

20

25

30

DUAL SCALE PRESSURE GAUGE

Page 9: Identify Your Kit

9

Secondary System PurgingTypically boiler manufacturers want to make sure that any foreign matter (dirt, shavings, PTFE thread tape, etc.) is fl ushed out of the Hydronic Piping System before fl uid begins to fl ow between the boiler and the piping system.

To purge the secondary system the following is needed:

• A hose w/ 3⁄4" hose thread connection

• A water source

• Power to the circulator pump in the secondary loop

1. Turn the lever handles on both Hydro-Core ball valves so that they are parallel to the fl ange and the main valves are in the closed position. This will prevent any debris from entering the near boiler loop during fl ushing. If multiple circuits are present, repeat for each circuit.

8. Close the purging valve on the drain in the secondary loop.

9. Remove the hose and replace the cap.

10. Open the main valve on the drain valve in the secondary loop.

6. Turn on the circulator pump in the secondary system to purge the entire loop with fresh water.

7. Once the debris has been purged out and the drainage from the hose runs clear, turn off the circulator.

2. Close the main valve and remove the cap from the drain valve in the secondary loop.

3. Connect the hose to the purging port on the drain valve in the secondary loop.

4. Direct the other end of the hose into a bucket or drain.

5. With the main water supply on and fl owing into the system, open the purging valve on the drain in the secondary loop.

11. Return the lever handled ball valves on the Hydro-Core manifold to their normal operating position (handles perpendicular to the fl ange). Repeat for each circuit.

Page 10: Identify Your Kit

10

CONNECT TO

WATE

R S

OU

RC

E

RUN FO

R D

RA

INA

GE

SUPPLYRETURN

FLOW

FLOW

SUPPLYRETURN

1. Turn the Lever Handles on both Hydro-Core ball valves so that they are parallel to the fl ange. The T-Flow handle logo indicates the fl ow pattern inside the valve. The logo should indicate that fl ow can go through the purging valve and both the supply and return piped assemblies.

2. Remove both purging valve caps

3. Using a hose, connect a water source to the system return purging valve (located above the fl ange connection).

4. Connect a hose to the system supply purging valve for drainage.

5. Turn the drain handles on both the system return & system supply purging valves into the open position (drain handles parallel with the fl ange).

6. Turn on the water source and allow water to fl ow into the circulator from the hose.

7. Allow water to run until all excess air has been purged from the boiler and the water coming from the drainage hose appears clear. If needed, turn on the circulator pump to force water through the system.

8. Once the air has been purged out and the drainage runs clear, turn off the circulator, close the two purging valves, remove the hoses, and replace the drain caps.

9. The boiler and NBP loop will now be fi lled with clean fresh water. If a glycol solution is preferred, see steps 2–14 on the next page and follow the instructions for “Descaling the Boiler Heat Exchanger” utilizing glycol rather than a descaling solution.

10. Return the lever handled ball valves to their normal operating position (handles perpendicular to the fl ange).

Filling/Power PurgingThe Hydro-Core and associated NBP offers several benefi cial features for a system’s startup and future maintenance. At startup the boiler can be isolated from the remaining hydronic system and the trapped air in the boiler and associated piping can be power purged out.

To Power Purge and/or fi ll the boiler the following is needed:

• Two hoses w/ 3⁄4" hose thread connection

• A water source

• Power to the circulator pump in the NBP Loop

• 5 gallon bucket (for glycol fi lling only)

Page 11: Identify Your Kit

11

Strainer Servicing

SUPPLYRETURN

1. Turn the lever handles on both Hydro-Core ball valves so that they are parallel to the fl ange. The T-Flow handle logo indicates the fl ow pattern inside the valve. The logo should indicate that fl ow can go through the purging valve and both the supply and return piped assemblies.

2. Release internal pressure by removing the system return purging valve cap and turning the drain handle on the system return purging valve into the open position (parallel with the fl ange). Pressure release should emit a small amount of fl uid.

5. Reinstall the plug, ensuring that it is seated properly in the strainer cap.

3. Remove the strainer plug by turning it counterclockwise.

4. Clean out the strainer.

6. Close the purging valve (drain handle perpendicular to the fl ange).

7. Return the lever handled ball valves to their normal operating position (handles perpendicular to the fl ange) and replace the cap.

8. Pressure test the system to ensure that all connections are pressure tight.

Page 12: Identify Your Kit

12

Boiler Heat Exchanger Descaling/CleaningTo Descale/Clean the boiler the following is needed:

• Boiler Manufacturer Maintenance InstructionsShould there be a discrepancy or confl ict with these instructions, follow the Boiler Manufacturer’s instructions.

• Descaling/cleaning solution

• 2 hoses

• Bucket

• Ability to activate the NBP System Circulator

TO B

UC

KET

TO B

UC

KET

SUPPLYRETURN

FLOW

FLOW

SUPPLYRETURN

SUPPLYRETURN

CONNECT TO

WATE

R S

OU

RC

E

TO B

UC

KET

1. Turn the lever handles on both Hydro-Core ball valves so that they are parallel to the fl ange. The T-Flow handle logo indicates the fl ow pattern inside the valve. The logo should indicate that fl ow can go through the purging valve and both the supply and return piped assemblies.

2. Remove both purging valve caps.

3. Connect one of the hoses to the system return purging valve (located above the fl ange connection).

4. Connect the other hose to the system supply purging valve.

5. Fill a 5 gallon bucket with the boiler manufacturer’s recommended cleaning/descaling solution.

6. Place the ends of both hoses into bucket of solution.

7. Turn the drain handles on both the system return & system supply purging valves into the open position (drain handles parallel with the fl ange).

8. Turn on the circulator pump in the NBP Loop and allow the solution to fl ow into and out of the NBP System.

9. See boiler manufacturer maintenance instructions to determine when system is suffi ciently cleaned.

10. When boiler is suffi ciently cleaned, remove the hose connected to the system return’s purging valve from the bucket (system return is the side with the fl ange connection).

11. Connect system return purging valve hose to a water source.

12. Turn on the water source and allow water to fl ow into the circulator to purge the entire loop with fresh water. If needed, turn on the circulator pump to force water through the system.

13. Once the solution has been purged out in the bucket and the drainage from the hose on the system supply purging valve runs clear, turn off the circulator.

14. Close the two purging valves, remove the hoses, and replace the caps.

15. The boiler and NBP loop will now be fi lled with clean fresh water. If a glycol solution is preferred, repeat steps 2–14 above with glycol rather than a descaling solution.

16. Return the lever handled ball valves to their normal operating position (handles perpendicular to the fl ange).

The Isolator® and Pro-Pal® are registered trademarks of Webstone Company, Inc.© 2015 Webstone Company

HCM-0515