IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

Upload: rosalyn-powell

Post on 14-Jan-2016

217 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

IEA Annex 37:Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology

Jenny Love8th March 2013

Page 2: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

What is Annex 37?

“Demonstration of field measurements of heat pump systems in buildings -Good examples with modern technology”

UK field trials:EST phase 2

Swedish field trials Swiss field trials

Outputs: report, website, recommendations

Page 3: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

Introduction to the heat pumps

Site A B C D

Heat pump type 5 kW GSHP 7.5 kW ASHP & 3.4 kW Exhaust-ASHP

8 kW GHSP 6 kW ASHP

Purpose Space heating and DHW

Heat source Ground - Slinky

Air and exhaust air

Ground - Borehole

Air

Heat sink Underfloor heating & DHW

Underfloor heating & DHW

Radiators & DHW

Radiators & DHW

Refrigerant R407C(except the Exhaust ASHP: R290)

Page 4: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

Measured variables:

Site A B C D

TEMPERATURE: External air temperature

Ground temperature

Living room temperature

Bedroom temperature

Central heating flow temperature

Central heating return temperature

Ground loop flow temperature

Ground loop return temperature

What data do we have: temperature

Page 5: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

Measured variables:

Site A B C D

HEATHeat to space heating

Heat to DHW No, but we can work it out from other variables

Total heat out of heat pump

ELECTRICITYElectricity supply to heat pump

Electricity to immersion heater in the domestic hot water cylinder

Electricity for auxiliary space heating

Auxiliary heating was disabled

No auxiliary heating separate to any provided by the heat pump itself

No auxiliary heating separate to any provided by the heat pump itself

Electricity to compressor

Electricity to pump on ground loop side

No, so we take the difference between electricity to heat pump and electricity to compressor and assume a 90% : 10% attribution between the ground loop and central heating pumps respectively.

Electricity to pump on house side

What data do we have: heat and electricity

Page 6: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

Site 416 Site 418 Site 421 Site 4220

0.5

1

1.5

2

2.5x 10

4

Hea

t o

utp

ut,

kW

hHeat to central heating and DHW for each site over the monitoring period

Space heating

DHW

What heat was being used for

A B C D

Page 7: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

Performance metrics

- Seasonal Performance Factors (SPFs)

- Energy, CO2 and running cost savings compared to other heating technologies

Page 8: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

SPF3

Page 9: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

Site A B C DSPF3 3.91 3.67 3.44 3.30

Performance metric 1: Seasonal performance factor (e.g. SPF3)

SEPEMO definition:

heat to central heating + heat to DHW + auxiliary elec

compressor elec + groundloop elec or fan elec + auxiliary elec

SPF3 =

Page 10: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

0

1

2

3

4

5

6

Mo

nth

ly a

vera

ge S

PF

3

Monthly SPF3, site 416

0

1

2

3

4

5

6

Mo

nth

ly a

vera

ge

SP

F3

Monthly SPF3, site 421

0

1

2

3

4

5

6M

on

thly

av

era

ge

SP

F3

Monthly SPF3, site 422

SPF3: Monthly timeseries

0

1

2

3

4

5

6

Mo

nth

ly a

vera

ge

SP

F3

Monthly SPF3, site 418

GSHPs

ASHPs

Site A Site C

Site B Site D

Page 11: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

-5 0 5 10 15 200

5

10

15

20

25

30

35

40

45

50

External Temperature, degrees C

Centr

al h

eating flo

w a

nd retu

rn tem

pera

ture

s, d

egre

es C

Daily central heating flow and return temperature against external temperature, filtered, site 416

Central heating flow (blue) and return (green) temperatures, site A

Page 12: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

0

2

4

6

8

10

12

14

16

18

20

Month

Ext

ernal

Tem

per

ature

, deg

rees

C

Monthly external temperatures with standard deviations, site 416

Monthly external temperature

Page 13: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

SPF3: Daily against external temperature

-5 0 5 10 15 200

1

2

3

4

5

6

Daily average external T, degrees C

Dai

ly a

vera

ge

SP

F3

Daily average SPF3 against external temperature , site 416

-5 0 5 10 15 200

1

2

3

4

5

6

Daily average external T, degrees C

Dai

ly a

ver

age

SP

F3

Daily average SPF3 against external temperature , site 422

-5 0 5 10 15 200

1

2

3

4

5

6

Daily average external T, degrees C

Dai

ly a

vera

ge

SP

F3

Daily average SPF3 against external temperature , site 421

-5 0 5 10 15 200

1

2

3

4

5

6

Daily average external T, degrees C

Dai

ly a

vera

ge

SP

F3

Daily average SPF3 against external temperature , site 418

Site A

Site B

Site C

Site D

SPF3 – daily averages against external temperature

GSHPs

ASHPs

Page 14: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

-5 0 5 10 15 200

1

2

3

4

5

6

7

Daily average external T, degrees C

Dai

ly a

ve

rag

e S

PF

3

Daily average SPF3 for space heating separated from DHW, site 421

-5 0 5 10 15 200

1

2

3

4

5

6

Daily average external T, degrees C

Dai

ly a

vera

ge

SP

F3

Daily average SPF3 for space heating separated from DHW, site 422

SPF3 - Daily against external T – split into space heating and DHW

-5 0 5 10 15 200

1

2

3

4

5

6

7

Daily average external T, degrees C

Dai

ly a

vera

ge

SP

F3

Daily average SPF3 for space heating separated from DHW, site 416

-5 0 5 10 15 200

1

2

3

4

5

6

Daily average external T, degrees C

Dai

ly a

vera

ge

SP

F3

Daily average SPF3 against external temperature , site 418

Site A

Site B

Site C

Site D

GSHPs

ASHPs

Page 15: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

2 observations

1. DHW production has a lower SPF3 than space heating2. The ASHPs’ performance drops off at T(ext) > 10°C

DO THESE THINGS MATTER?

So far…

Page 16: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

Site 416 Site 418 Site 421 Site 4220

0.5

1

1.5

2

2.5x 10

4

Hea

t o

utp

ut,

kW

hHeat to central heating and DHW for each site over the monitoring period

Space heating

DHW

1. SPF3 of DHW lower than that of space heating

A B C D

Page 17: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

-5 0 5 10 15 200

1

2

3

4

5

6

Daily average external T, degrees C

Dai

ly a

vera

ge

SP

F3

Daily average SPF3 against external temperature , site 418

-5 0 5 10 15 200

1

2

3

4

5

6

Daily average external T, degrees CD

aily

av

erag

e S

PF

3

Daily average SPF3 for space heating separated from DHW, site 422

15% 25%

2. SPF3 of space heating dropping after 10 degrees outside

Site B Site D

Page 18: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

Savings:- Energy- CO2- Running costs

Page 19: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

Performance metric 2: Savings – energy use

Heat pump Gas condensing boiler Gas combi boiler Oil condensing boiler Electric storage heater0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

2x 10

4

CO

2 em

issi

on

s, k

gC

O2

Energy use, site A

Space heating

DHW

Heat pump Gas condensing boiler Gas combi boiler Oil condensing boiler Electric storage heater0

2000

4000

6000

8000

10000

12000

14000

16000

18000

CO

2 em

issi

on

s, k

gC

O2

Energy use, site D

Space heating

DHW

Heat pump Gas condensing boiler Gas combi boiler Oil condensing boiler Electric storage heater0

0.5

1

1.5

2

2.5

3x 10

4

CO

2 em

issi

on

s, k

gC

O2

Energy use, site B

Space heating

DHW

Heat pump Gas condensing boiler Gas combi boiler Oil condensing boiler Electric storage heater0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

2x 10

4

CO

2 em

issi

on

s, k

gC

O2

Energy use, site C

Space heating

DHW

Ene

rgy

cons

umpt

ion,

Kw

h E

nerg

y co

nsum

ptio

n, K

wh

Ene

rgy

cons

umpt

ion,

Kw

h E

nerg

y co

nsum

ptio

n, K

wh

Page 20: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

Performance metric 2: Savings – CO2 emissions

Heat pump Gas condensing boiler Gas combi boiler Oil condensing boiler Electric storage heater0

1000

2000

3000

4000

5000

6000

7000

8000

9000

10000

CO

2 em

issi

on

s, k

gC

O2

CO2 emissions, site A

Space heating

DHW

Heat pump Gas condensing boiler Gas combi boiler Oil condensing boiler Electric storage heater0

1000

2000

3000

4000

5000

6000

7000

8000

9000

CO

2 em

issi

on

s, k

gC

O2

CO2 emissions, site D

Space heating

DHW

Heat pump Gas condensing boiler Gas combi boiler Oil condensing boiler Electric storage heater0

2000

4000

6000

8000

10000

12000

14000

CO

2 em

issi

on

s, k

gC

O2

CO2 emissions, site B

Space heating

DHW

Heat pump Gas condensing boiler Gas combi boiler Oil condensing boiler Electric storage heater0

1000

2000

3000

4000

5000

6000

7000

8000

9000

10000

CO

2 em

issi

on

s, k

gC

O2

CO2 emissions, site C

Space heating

DHW

Page 21: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

Performance metric 2: Savings - running cost

Heat pump Gas condensing boiler Gas combi boiler Oil condensing boiler Electric storage heater0

200

400

600

800

1000

1200

Co

st,

£/m

on

ito

rin

g p

erio

d

Overall (hot water and space heating) running costs over the monitoringperiod by different heating technologies, site 416

Space heating

DHW

Heat pump Gas condensing boiler Gas combi boiler Oil condensing boiler Electric storage heater0

200

400

600

800

1000

1200

Co

st,

£/m

on

ito

rin

g p

erio

d

Overall (space heating and hot water) running costs over the monitoringperiod by different heating technologies, site 422

Space heating

DHW

Site A

Heat pump Gas condensing boiler Gas combi boiler Oil condensing boiler Electric storage heater0

200

400

600

800

1000

1200

1400

1600

1800

Co

st,

£/m

on

ito

rin

g p

erio

d

Overall running costs over the monitoring period by different heating technologies, site 418

Space heating

Heat pump Gas condensing boiler Gas combi boiler Oil condensing boiler Electric storage heater0

200

400

600

800

1000

1200

Co

st,

£/m

on

ito

rin

g p

erio

d

Overall (space heating and hot water) running costs over the monitoringperiod by different heating technologies, site 421

Space heating

DHW

Site B

Site C

Site D

Page 22: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

Conclusions from UK contribution to IEA Annex 37

About performance: SPF3

About space heating

About water heating

About performance: Savings

About unknowns…

Page 23: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

What was found in the other countries in Annex 37?

SPF3 against external temperature

Nicolas Piezel, Fabrice Rognon, Stephanie Perret

We

ekl

y S

PF

3

We

ekl

y S

PF

3

Mean external temperature, °C Mean external temperature, °C

SPF3 against external temperature

Page 24: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

• Brine/water HP• Year of installation: 2003• Heating and hot water• Heat source: 2 boreholes• Floor heating system• Floor heating temperature settings:

30/25°C (for outside temperature of -8°C)

• Hot water temperature settings: 57/52°C• Refrigerant: R407c• Heating system 100% HP

How was a SPF3 of 4.7 achieved?

Page 25: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

- Very good performance (SPF3 > 4.5) not impossible in Britain…

From a vertical borehole, off-the-shelf heat pump, but supply temperature = 30 degrees only. Therefore you need a very well-insulated building.

How was a SPF3 of 4.7 achieved?

Page 26: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

Thank you

Any questions?

[email protected]

Page 27: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

Other information

Site A B C D

Monitoring period 15/06/2011 – 31/03/2012

01/03/2011 – 31/03/2012

09/02/2011 – 31/03/2012

22/02/2011 – 31/03/2012

Page 28: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

Site A Site B Site C Site D

Estimate of heat demand (from degree day calculation), kWh

10,378 13,191 19,983 8,816

Heat delivered to space heating, kWh

10,444 20,788 12,784 9,146

Space heating SPF3

4.54 3.67 3.55 3.55

Heat delivered to DHW, kWh

3,877 - 1,864 3,902

DHW SPF3 2.76 - 2.53 2.20

Total heat delivered, kWh

14,253 20,788 14,648 13,318

SPF3 3.91 3.67 3.44 3.30

Page 29: IEA Annex 37: Demonstration of field measurements of heat pump systems in buildings – Good examples with modern technology Jenny Love 8 th March 2013

-5 0 5 10 15 200

500

1000

1500

2000

2500

External Temperature, degrees C

Dai

ly e

lect

ric

imm

ersi

on

use

, Wh

Backup heating, site D